Argus-Power-System-MIB DEFINITIONS ::= BEGIN
--==========================================================================
-- NOTE: Refer to RFC1628 for the formal definition of the SNMPv2-SMI MIB.
--==========================================================================
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises
FROM SNMPv2-SMI;
argus MODULE-IDENTITY
LAST-UPDATED "201612090000Z"
ORGANIZATION "Alpha Technologies Ltd."
CONTACT-INFO
"Alpha Technologies Ltd.
7700 Riverfront Gate
Burnaby, BC V5J 5M4
Canada
Tel: 1-604-436-5900
Fax: 1-604-436-1233"
DESCRIPTION
"This MIB defines the information block(s) available in CXC RMU
as defined by the following list:
- upsDevice: the CXC-series of controllers"
REVISION "201612090000Z" -- December 9, 2016
DESCRIPTION
"
Updated upsSecondsOnBattery to upsMinutesOnBattery to match unit value of the data.
"
::= { enterprises 7309 }
PositiveInteger ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"This data type is a non-zero and non-negative value."
SYNTAX INTEGER (1..2147483647)
NonNegativeInteger ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"This data type is a non-negative value."
SYNTAX INTEGER (0..2147483647)
DisplayString ::=
OCTET STRING
-- This data type is used to model textual information taken
-- from the NVT ASCII character set. By convention, objects
-- with this syntax are declared as having
--
-- SIZE (0..255)
PhysAddress ::=
OCTET STRING
-- This data type is used to model media addresses. For many
-- types of media, this will be in a binary representation.
-- For example, an ethernet address would be represented as
-- a string of 6 octets.
upsPower OBJECT IDENTIFIER ::= { argus 6}
upsDevice OBJECT IDENTIFIER ::= { upsPower 1}
upsIdent OBJECT IDENTIFIER ::= { upsDevice 1}
upsBattery OBJECT IDENTIFIER ::= { upsDevice 2}
upsInput OBJECT IDENTIFIER ::= { upsDevice 3}
upsOutput OBJECT IDENTIFIER ::= { upsDevice 4}
upsAlarm OBJECT IDENTIFIER ::= { upsDevice 5}
upsConfig OBJECT IDENTIFIER ::= { upsDevice 6}
upsTraps OBJECT IDENTIFIER ::= { upsDevice 7}
upsExtra OBJECT IDENTIFIER ::= { upsDevice 8}
--==========================================================================
-- Start of Extra Information
-- Power upstem specified variables and alarm status are maintained in the extra
-- table. CXC RMU will populate realtime live data to these variables and
-- status entries in the table. Table entries' string value are configured by
-- CXC RMU web interface and support unicode string
--==========================================================================
upsExtraCount OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of extra variables"
::= { upsExtra 1 }
upsExtraTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsExtraEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table of CXC upstem controller extra variables"
::= { upsExtra 2 }
upsExtraEntry OBJECT-TYPE
SYNTAX UpsExtraEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An entry into the CXC upstem controller extra variable table"
INDEX { upsExtraIndex }
::= { upsExtraTable 1 }
UpsExtraEntry
::= SEQUENCE {
upsExtraIndex INTEGER,
upsExtraName DisplayString ,
upsExtraIntegerValue INTEGER,
upsExtraStringValue DisplayString
}
upsExtraIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The index of the extra variable in the CXC upstem controller table"
::= { upsExtraEntry 1 }
upsExtraName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..30))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The description of the extra variable as reported by the CXC upstem controller"
::= { upsExtraEntry 2 }
upsExtraIntegerValue OBJECT-TYPE
SYNTAX INTEGER (-1000000000..1000000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The integer value of the extra variable as reported by the CXC upstem controller"
::= { upsExtraEntry 3 }
upsExtraStringValue OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The string value of the extra variable as reported by the CXC upstem controller"
::= { upsExtraEntry 4 }
--==========================================================================
-- The OBJECT IDENTIFIERs for the traps must be defined in this manner to
-- satisfy the NetSight MIB compiler; in particular, nodes cannot be defined
-- concatenated in a single line, but must be defined explicitly node by node
-- (hence, the upsDevice.upsTraps.upsTrap definition)
-- In addition, forward references to extra upstem variables are needed for
-- upsTrap by CastleRock SNMPc for event filter and match features.
--==========================================================================
upsTrap OBJECT IDENTIFIER ::= { upsTraps 0 }
--==========================================================================
-- Start of Traps
--==========================================================================
upsAlarmTrap NOTIFICATION-TYPE
OBJECTS {
upsExtraIntegerValue,
upsExtraStringValue,
upsExtraIndex,
upsExtraName
}
STATUS current
DESCRIPTION "A trap issued from a change in state in one of the Alarms on the Novus controller"
::= { upsTrap 1 }
upsAgentStartupTrap NOTIFICATION-TYPE
OBJECTS {
upsIdentSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that the agent software has started up."
::= { upsTrap 2 }
upsAgentShutdownTrap NOTIFICATION-TYPE
OBJECTS {
upsIdentSiteName
}
STATUS current
DESCRIPTION "A trap to indicate that the agent software has shutdown."
::= { upsTrap 3 }
upsAgentFaultTrap NOTIFICATION-TYPE
OBJECTS {
upsExtraIntegerValue,
upsExtraStringValue,
upsExtraIndex,
upsExtraName
}
STATUS current
DESCRIPTION "A trap issued from a change in state in one of the Faults on the Novus controller"
::= { upsTrap 4 }
upsAgentEventTrap NOTIFICATION-TYPE
OBJECTS {
upsExtraIntegerValue,
upsExtraStringValue,
upsExtraIndex,
upsExtraName
}
STATUS current
DESCRIPTION "A trap issued from a change in state in one of the Events on the Novus controller"
::= { upsTrap 5 }
--
-- The Device Identification group.
-- All objects in this group are set at device initialization
-- and remain static.
--
upsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the UPS manufacturer."
::= { upsIdent 1 }
upsIdentProductCode OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS Model designation."
::= { upsIdent 2 }
upsIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS Product code designation."
::= { upsIdent 3 }
upsIdentUPSSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS firmware/software version(s). This variable
may or may not have the same value as
upsIdentAgentSoftwareVersion in some implementations."
::= { upsIdent 4 }
upsIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS agent software version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations."
::= { upsIdent 5 }
upsIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A string identifying the UPS. This object should be
set by the administrator."
::= { upsIdent 6 }
upsIdentAttachedDevices OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator."
::= { upsIdent 7 }
upsIdentSiteName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Site Name"
::= { upsIdent 8 }
upsIdentSiteCity OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Site City"
::= { upsIdent 9 }
upsIdentSiteRegion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Site Region"
::= { upsIdent 10 }
upsIdentSiteCountry OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Site Country"
::= { upsIdent 11 }
upsIdentContactName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Contact Name"
::= { upsIdent 12 }
upsIdentPhoneNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Phone Number"
::= { upsIdent 13 }
upsIdentDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Date of the RMU-Novus"
::= { upsIdent 14 }
upsIdentTime OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Time of the RMU-Novus"
::= { upsIdent 15 }
--
-- Battery Group
--
upsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output)."
::= { upsBattery 1 }
upsMinutesOnBattery OBJECT-TYPE
SYNTAX INTEGER
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
The accumulated elapsed time that the UPS system have been on battery.
"
::= { upsBattery 2 }
upsBatteryVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volt DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present battery voltage."
::= { upsBattery 3 }
upsBatteryChargingCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present battery charging current."
::= { upsBattery 4 }
upsBatteryCapacity OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present battery capacity."
::= { upsBattery 5 }
upsBatteryTemperature OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees Centigrade"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the UPS Battery
casing."
::= { upsBattery 6 }
upsBatteryLowWarning OBJECT-TYPE
SYNTAX INTEGER
UNITS "percentage"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The set battery capacity percentage at which the unit will raise an alarm."
::= { upsBattery 7 }
--
-- Input Group
--
upsInputNumLines OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input lines utilized in this device.
This variable indicates the number of rows in the
input table."
::= { upsInput 1 }
upsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of input table entries. The number of entries
is given by the value of upsInputNumLines."
::= { upsInput 2 }
upsInputEntry OBJECT-TYPE
SYNTAX UpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular input line."
INDEX { upsInputLineIndex }
::= { upsInputTable 1 }
UpsInputEntry ::= SEQUENCE {
upsInputLineIndex INTEGER ,
upsInputFrequency INTEGER ,
upsInputVoltage INTEGER
}
upsInputLineIndex OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input line identifier."
::= { upsInputEntry 1 }
upsInputFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency."
::= { upsInputEntry 2 }
upsInputVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage."
::= { upsInputEntry 3 }
--
-- The Output group.
--
upsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
standby(1),
line(2),
boost2(3),
boost1(4),
buck1(5),
buck2(6),
inverter(7),
retransfer(8),
transfer(9),
shutdown(10),
bypass(11)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration
line(2) indicates that the Novus is in line mode."
::= { upsOutput 1 }
upsOutputFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency."
::= { upsOutput 2 }
upsOutputNumLines OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table."
::= { upsOutput 3 }
upsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of output table entries. The number of
entries is given by the value of upsOutputNumLines."
::= { upsOutput 4 }
upsOutputEntry OBJECT-TYPE
SYNTAX UpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular output line."
INDEX { upsOutputLineIndex }
::= { upsOutputTable 1 }
UpsOutputEntry ::= SEQUENCE {
upsOutputLineIndex INTEGER ,
upsOutputVoltage INTEGER ,
upsOutputCurrent INTEGER ,
upsOutputPowerVA INTEGER ,
upsOutputPowerWatt INTEGER ,
upsPowerFactor INTEGER ,
upsOutputPercentLoad INTEGER
}
upsOutputLineIndex OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output line identifier."
::= { upsOutputEntry 1 }
upsOutputVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output voltage."
::= { upsOutputEntry 2 }
upsOutputCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 RMS Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output current."
::= { upsOutputEntry 3 }
upsOutputPowerVA OBJECT-TYPE
SYNTAX INTEGER
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output VA."
::= { upsOutputEntry 4 }
upsOutputPowerWatt OBJECT-TYPE
SYNTAX INTEGER
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output true power."
::= { upsOutputEntry 5 }
upsPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present power factor."
::= { upsOutputEntry 6 }
upsOutputPercentLoad OBJECT-TYPE
SYNTAX INTEGER (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA."
::= { upsOutputEntry 7 }
--
-- The Alarms group.
--
upsAlarmsPresent OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of active alarm conditions."
::= { upsAlarm 1 }
upsAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of alarm table entries. "
::= { upsAlarm 2 }
upsAlarmEntry OBJECT-TYPE
SYNTAX UpsAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular alarm."
INDEX { upsAlarmId }
::= { upsAlarmTable 1 }
UpsAlarmEntry ::= SEQUENCE {
upsAlarmId INTEGER ,
upsAlarmDescr DisplayString,
upsAlarmStatus INTEGER
}
upsAlarmId OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique identifier for an alarm condition. This
value must remain constant."
::= { upsAlarmEntry 1 }
upsAlarmDescr OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique description of the alarm. "
::= { upsAlarmEntry 2 }
upsAlarmStatus OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"1 - ON or 0 - OFF. "
::= { upsAlarmEntry 3 }
--
-- The Config group.
--
upsConfigLineQualifyTime OBJECT-TYPE
SYNTAX INTEGER
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This objects displays the line qualify time."
::= { upsConfig 1 }
upsConfigLineOutputVoltageHighLimit OBJECT-TYPE
SYNTAX INTEGER
UNITS "volttenth"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object represents the Line output High Voltage Limit."
::= { upsConfig 2 }
upsConfigLineOutputVoltageLowLimit OBJECT-TYPE
SYNTAX INTEGER
UNITS "volttenth"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object represents the Line output Low Voltage Limit."
::= { upsConfig 3 }
upsConfigFanOnTemperature OBJECT-TYPE
SYNTAX INTEGER
UNITS "degreeC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object represents the Fan on temperature."
::= { upsConfig 4 }
upsShutdownStatus OBJECT-TYPE
SYNTAX INTEGER
UNITS ""
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object tells us if output is disabled or enabled."
::= { upsConfig 5 }
upsInverterOffDelayTime OBJECT-TYPE
SYNTAX INTEGER
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object represents the inverter off delay time."
::= { upsConfig 6 }
upsConfigIPAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This objects displays the IP address of the RMU."
::= { upsConfig 7 }
upsConfigNetMask OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object displays the Net Mask of the RMU."
::= { upsConfig 8 }
upsConfigGateway OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object displays the Gateway of the RMU."
::= { upsConfig 9 }
upsConfigSnmpCommunity OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object displays the SNMP community"
::= { upsConfig 10 }
upsConfigSnmpTrapIPDestination OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..255))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object displays the SNMP Trap IP destination."
::= { upsConfig 11 }
END