-- Chatsworth Products Inc.
|
||
|
-- Copyright (c) Chatsworth Products Inc., 1998-2019.
|
||
|
-- Version : 2.1.0.1 (netsnmp compliant)
|
||
|
-- ************************************************************************
|
||
|
|
||
|
CPI-UNITY-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
MODULE-IDENTITY,
|
||
|
OBJECT-TYPE,
|
||
|
NOTIFICATION-TYPE,
|
||
|
IpAddress,
|
||
|
Integer32,
|
||
|
Counter64,
|
||
|
enterprises
|
||
|
FROM SNMPv2-SMI
|
||
|
DisplayString
|
||
|
FROM SNMPv2-TC
|
||
|
MacAddress
|
||
|
FROM SNMPv2-TC
|
||
|
TruthValue
|
||
|
FROM SNMPv2-TC
|
||
|
Unsigned32
|
||
|
FROM SNMPv2-SMI
|
||
|
MODULE-COMPLIANCE,
|
||
|
OBJECT-GROUP,
|
||
|
NOTIFICATION-GROUP
|
||
|
FROM SNMPv2-CONF;
|
||
|
|
||
|
products MODULE-IDENTITY
|
||
|
LAST-UPDATED "201903011508Z"
|
||
|
ORGANIZATION "Chatsworth Products Inc."
|
||
|
CONTACT-INFO
|
||
|
"Chatsworth Products, Inc.
|
||
|
3004 South Austin Avenue
|
||
|
Georgetown, TX 78626
|
||
|
Tel: (800) 834-4969
|
||
|
Email: techsupport@chatsworth.com"
|
||
|
DESCRIPTION
|
||
|
"The MIB module is used to register Chatsworth eConnect related
|
||
|
SNMP OIDs for all models.
|
||
|
|
||
|
Copyright 2014-2019 Chatsworth Products, Inc. All rights reserved.
|
||
|
Reproduction of this document is authorized on the condition
|
||
|
that the forgoing copyright notice is included.
|
||
|
|
||
|
This Specification is supplied 'AS IS' and Chatsworth Products, Inc
|
||
|
makes no warranty, either express or implied, as to the use,
|
||
|
operation, condition, or performance of the Specification."
|
||
|
REVISION "201903010000Z"
|
||
|
DESCRIPTION
|
||
|
"Consolidating Legacy MIBs into the Unity MIB base."
|
||
|
REVISION "201408011508Z"
|
||
|
DESCRIPTION
|
||
|
"Initial version of the Unity SNMP OIDs"
|
||
|
::= { cpi 1 }
|
||
|
|
||
|
cpi OBJECT IDENTIFIER ::= { enterprises 30932 }
|
||
|
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
--
|
||
|
-- Legacy MIBS Below
|
||
|
--
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
|
||
|
cpiPDU OBJECT IDENTIFIER ::= { products 1 }
|
||
|
|
||
|
systemInfo OBJECT IDENTIFIER ::= { cpiPDU 1 }
|
||
|
|
||
|
version OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..14))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Software Version."
|
||
|
::= { systemInfo 1 }
|
||
|
|
||
|
modelCode OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..14))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Model code for the PDU."
|
||
|
::= { systemInfo 2 }
|
||
|
|
||
|
hwAddress OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (17))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU hardware MAC address."
|
||
|
::= { systemInfo 3 }
|
||
|
|
||
|
configuration OBJECT IDENTIFIER ::= { cpiPDU 2 }
|
||
|
|
||
|
logInterval OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The time interval in seconds for logging metrics (disabled if < 10)."
|
||
|
::= { configuration 1 }
|
||
|
|
||
|
alarmInterval OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The time interval in seconds for alarm cycle (disabled if < 10)."
|
||
|
::= { configuration 2 }
|
||
|
|
||
|
logDifference OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current difference in 1/100 Amps that triggers logging metrics."
|
||
|
::= { configuration 3 }
|
||
|
|
||
|
pduIP OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU IP address."
|
||
|
::= { configuration 4 }
|
||
|
|
||
|
netOptions OBJECT IDENTIFIER ::= { configuration 5 }
|
||
|
|
||
|
autoIP OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Select dynamic (Auto) or static IP, 0=static and 1=dynamic."
|
||
|
::= { netOptions 1 }
|
||
|
|
||
|
autoDNS OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Select dynamic (Auto) or static DNS, 0=static and 1=dynamic."
|
||
|
::= { netOptions 2 }
|
||
|
|
||
|
ipV4Enable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable IPV4 Network, 0=disable and 1=enable."
|
||
|
::= { netOptions 3 }
|
||
|
|
||
|
snmpEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable SNMP network service, 0=disable and 1=enable."
|
||
|
::= { netOptions 4 }
|
||
|
|
||
|
telnetEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable Telnet service, 0=disable and 1=enable."
|
||
|
::= { netOptions 5 }
|
||
|
|
||
|
sshEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable SSH Service, 0=disable and 1=enable."
|
||
|
::= { netOptions 6 }
|
||
|
|
||
|
httpEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable HTTP Service, 0=disable and 1=enable."
|
||
|
::= { netOptions 7 }
|
||
|
|
||
|
httpsEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable HTTPS Service, 0=disable and 1=enable."
|
||
|
::= { netOptions 8 }
|
||
|
|
||
|
subnetMask OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Subnet Mask."
|
||
|
::= { configuration 6 }
|
||
|
|
||
|
gateway OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Gateway Address."
|
||
|
::= { configuration 7 }
|
||
|
|
||
|
dnsHosts OBJECT IDENTIFIER ::= { configuration 8 }
|
||
|
|
||
|
dns1 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 1 IP."
|
||
|
::= { dnsHosts 1 }
|
||
|
|
||
|
dns2 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 2 IP."
|
||
|
::= { dnsHosts 2 }
|
||
|
|
||
|
dns3 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 3 IP."
|
||
|
::= { dnsHosts 3 }
|
||
|
|
||
|
snmpHosts OBJECT IDENTIFIER ::= { configuration 9 }
|
||
|
|
||
|
snmpHost1 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 1 IP address."
|
||
|
::= { snmpHosts 1 }
|
||
|
|
||
|
snmpHost2 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 2 IP address."
|
||
|
::= { snmpHosts 2 }
|
||
|
|
||
|
snmpHost3 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 3 IP address."
|
||
|
::= { snmpHosts 3 }
|
||
|
|
||
|
pduIPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU IPV6 address."
|
||
|
::= { configuration 10 }
|
||
|
|
||
|
netOptionsIPv6 OBJECT IDENTIFIER ::= { configuration 11 }
|
||
|
|
||
|
autoIPv6 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Select IPV6 dynamic (Auto) or static IP, 0=static and 1=dynamic."
|
||
|
::= { netOptionsIPv6 1 }
|
||
|
|
||
|
autoDNSIPv6 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Select IPV6 dynamic (Auto) or static DNS, 0=static and 1=dynamic."
|
||
|
::= { netOptionsIPv6 2 }
|
||
|
|
||
|
ipv6Enable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable IPV6 Network, 0=disable and 1=enable."
|
||
|
::= { netOptionsIPv6 3 }
|
||
|
|
||
|
linkLocalEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable IPV6 Link-Local, 0=disable and 1=enable."
|
||
|
::= { netOptionsIPv6 4 }
|
||
|
|
||
|
globalAddrEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable IPV6 Global Address, 0=disable and 1=enable."
|
||
|
::= { netOptionsIPv6 5 }
|
||
|
|
||
|
subnetMaskIPv6 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..127)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU IPV6 Subnet Mask."
|
||
|
::= { configuration 12 }
|
||
|
|
||
|
gatewayIPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU IPV6 Gateway Address."
|
||
|
::= { configuration 13 }
|
||
|
|
||
|
dnsHostIPv6 OBJECT IDENTIFIER ::= { configuration 14 }
|
||
|
|
||
|
dns1IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 2 for IPV6."
|
||
|
::= { dnsHostIPv6 1 }
|
||
|
|
||
|
dns2IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 3 for IPV6."
|
||
|
::= { dnsHostIPv6 2 }
|
||
|
|
||
|
dns3IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU DNS 4 for IPV6."
|
||
|
::= { dnsHostIPv6 3 }
|
||
|
|
||
|
snmpHostsIPv6 OBJECT IDENTIFIER ::= { configuration 15 }
|
||
|
|
||
|
snmpHost1IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 1 IPV6."
|
||
|
::= { snmpHostsIPv6 1 }
|
||
|
|
||
|
snmpHost2IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 2 IPV6."
|
||
|
::= { snmpHostsIPv6 2 }
|
||
|
|
||
|
snmpHost3IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Host 3 IPV6."
|
||
|
::= { snmpHostsIPv6 3 }
|
||
|
|
||
|
receptacleControl OBJECT IDENTIFIER ::= { configuration 16 }
|
||
|
|
||
|
outlet1Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 1 }
|
||
|
|
||
|
outlet2Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 2 }
|
||
|
|
||
|
outlet3Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 3 }
|
||
|
|
||
|
outlet4Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 4 }
|
||
|
|
||
|
outlet5Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 5 }
|
||
|
|
||
|
outlet6Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 6 }
|
||
|
|
||
|
outlet7Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 7 }
|
||
|
|
||
|
outlet8Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 8 }
|
||
|
|
||
|
outlet9Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 9 }
|
||
|
|
||
|
outlet10Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 10 }
|
||
|
|
||
|
outlet11Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 11 }
|
||
|
|
||
|
outlet12Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 12 }
|
||
|
|
||
|
outlet13Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 13 }
|
||
|
|
||
|
outlet14Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 14 }
|
||
|
|
||
|
outlet15Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 15 }
|
||
|
|
||
|
outlet16Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 16 }
|
||
|
|
||
|
outlet17Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 17 }
|
||
|
|
||
|
outlet18Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 18 }
|
||
|
|
||
|
outlet19Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 19 }
|
||
|
|
||
|
outlet20Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 20 }
|
||
|
|
||
|
outlet21Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 21 }
|
||
|
|
||
|
outlet22Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 22 }
|
||
|
|
||
|
outlet23Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 23 }
|
||
|
|
||
|
outlet24Ctrl OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleControl 24 }
|
||
|
|
||
|
receptacleONdelay OBJECT IDENTIFIER ::= { configuration 17 }
|
||
|
|
||
|
outlet1ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 1 }
|
||
|
|
||
|
outlet2ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 2 }
|
||
|
|
||
|
outlet3ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 3 }
|
||
|
|
||
|
outlet4ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 4 }
|
||
|
|
||
|
outlet5ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 5 }
|
||
|
|
||
|
outlet6ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 6 }
|
||
|
|
||
|
outlet7ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 7 }
|
||
|
|
||
|
outlet8ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 8 }
|
||
|
|
||
|
outlet9ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 9 }
|
||
|
|
||
|
outlet10ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 10 }
|
||
|
|
||
|
outlet11ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 11 }
|
||
|
|
||
|
outlet12ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 12 }
|
||
|
|
||
|
outlet13ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 13 }
|
||
|
|
||
|
outlet14ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 14 }
|
||
|
|
||
|
outlet15ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 15 }
|
||
|
|
||
|
outlet16ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 16 }
|
||
|
|
||
|
outlet17ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 17 }
|
||
|
|
||
|
outlet18ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 18 }
|
||
|
|
||
|
outlet19ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 19 }
|
||
|
|
||
|
outlet20ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 20 }
|
||
|
|
||
|
outlet21ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 21 }
|
||
|
|
||
|
outlet22ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 22 }
|
||
|
|
||
|
outlet23ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 23 }
|
||
|
|
||
|
outlet24ONdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 power-on delay in seconds."
|
||
|
::= { receptacleONdelay 24 }
|
||
|
|
||
|
receptacleResetDelay OBJECT IDENTIFIER ::= { configuration 18 }
|
||
|
|
||
|
outlet1RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 1 }
|
||
|
|
||
|
outlet2RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 2 }
|
||
|
|
||
|
outlet3RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 3 }
|
||
|
|
||
|
outlet4RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 4 }
|
||
|
|
||
|
outlet5RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 5 }
|
||
|
|
||
|
outlet6RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 6 }
|
||
|
|
||
|
outlet7RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 7 }
|
||
|
|
||
|
outlet8RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 8 }
|
||
|
|
||
|
outlet9RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 9 }
|
||
|
|
||
|
outlet10RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 10 }
|
||
|
|
||
|
outlet11RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 11 }
|
||
|
|
||
|
outlet12RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 12 }
|
||
|
|
||
|
outlet13RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 13 }
|
||
|
|
||
|
outlet14RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 14 }
|
||
|
|
||
|
outlet15RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 15 }
|
||
|
|
||
|
outlet16RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 16 }
|
||
|
|
||
|
outlet17RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 17 }
|
||
|
|
||
|
outlet18RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 18 }
|
||
|
|
||
|
outlet19RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 19 }
|
||
|
|
||
|
outlet20RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 20 }
|
||
|
|
||
|
outlet21RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 21 }
|
||
|
|
||
|
outlet22RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 22 }
|
||
|
|
||
|
outlet23RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 23 }
|
||
|
|
||
|
outlet24RESdly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 reset delay in seconds."
|
||
|
::= { receptacleResetDelay 24 }
|
||
|
|
||
|
maxCurrentLimits OBJECT IDENTIFIER ::= { configuration 19 }
|
||
|
|
||
|
xy1MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that XY1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 1 }
|
||
|
|
||
|
yz1MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that YZ1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 2 }
|
||
|
|
||
|
zx1MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that ZX1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 3 }
|
||
|
|
||
|
xy2MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that XY2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 4 }
|
||
|
|
||
|
yz2MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that YZ2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 5 }
|
||
|
|
||
|
zx2MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum current that ZX2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { maxCurrentLimits 6 }
|
||
|
|
||
|
minCurrentLimits OBJECT IDENTIFIER ::= { configuration 20 }
|
||
|
|
||
|
xy1MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that XY1 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 1 }
|
||
|
|
||
|
yz1MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that YZ1 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 2 }
|
||
|
|
||
|
zx1MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that ZX1 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 3 }
|
||
|
|
||
|
xy2MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that XY2 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 4 }
|
||
|
|
||
|
yz2MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that YZ2 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 5 }
|
||
|
|
||
|
zx2MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum current that ZX2 should draw in 1/100 Amps, 0=ignore."
|
||
|
::= { minCurrentLimits 6 }
|
||
|
|
||
|
warnHiCurrentLimits OBJECT IDENTIFIER ::= { configuration 21 }
|
||
|
|
||
|
xy1WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that XY1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 1 }
|
||
|
|
||
|
yz1WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that YZ1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 2 }
|
||
|
|
||
|
zx1WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that ZX1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 3 }
|
||
|
|
||
|
xy2WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that XY2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 4 }
|
||
|
|
||
|
yz2WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that YZ2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 5 }
|
||
|
|
||
|
zx2WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning upper current limit that ZX2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnHiCurrentLimits 6 }
|
||
|
|
||
|
warnLoCurrentLimits OBJECT IDENTIFIER ::= { configuration 22 }
|
||
|
|
||
|
xy1WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that XY1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 1 }
|
||
|
|
||
|
yz1WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that YZ1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 2 }
|
||
|
|
||
|
zx1WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that ZX1 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 3 }
|
||
|
|
||
|
xy2WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that XY2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 4 }
|
||
|
|
||
|
yz2WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that YZ2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 5 }
|
||
|
|
||
|
zx2WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning lower current limit that ZX2 can draw in 1/100 Amps, 0=ignore."
|
||
|
::= { warnLoCurrentLimits 6 }
|
||
|
|
||
|
maxVoltageLimits OBJECT IDENTIFIER ::= { configuration 24 }
|
||
|
|
||
|
xy1MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that XY1 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 1 }
|
||
|
|
||
|
yz1MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that YZ1 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 2 }
|
||
|
|
||
|
zx1MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that ZX1 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 3 }
|
||
|
|
||
|
xy2MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that XY2 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 4 }
|
||
|
|
||
|
yz2MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that YZ2 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 5 }
|
||
|
|
||
|
zx2MaxVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum voltage that ZX2 can reach up to in volts, 0=ignore."
|
||
|
::= { maxVoltageLimits 6 }
|
||
|
|
||
|
minVoltageLimits OBJECT IDENTIFIER ::= { configuration 25 }
|
||
|
|
||
|
xy1MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that XY1 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 1 }
|
||
|
|
||
|
yz1MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that YZ1 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 2 }
|
||
|
|
||
|
zx1MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that ZX1 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 3 }
|
||
|
|
||
|
xy2MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that XY2 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 4 }
|
||
|
|
||
|
yz2MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that YZ2 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 5 }
|
||
|
|
||
|
zx2MinVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum voltage that ZX2 can sag in volts, 0=ignore."
|
||
|
::= { minVoltageLimits 6 }
|
||
|
|
||
|
warnHiVoltageLimits OBJECT IDENTIFIER ::= { configuration 26 }
|
||
|
|
||
|
xy1WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that XY1 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 1 }
|
||
|
|
||
|
yz1WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that YZ1 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 2 }
|
||
|
|
||
|
zx1WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that ZX1 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 3 }
|
||
|
|
||
|
xy2WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that XY2 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 4 }
|
||
|
|
||
|
yz2WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that YZ2 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 5 }
|
||
|
|
||
|
zx2WarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High voltage in volts that ZX2 can reach before triggering warning notifications, 0=ignore."
|
||
|
::= { warnHiVoltageLimits 6 }
|
||
|
|
||
|
warnLoVoltageLimits OBJECT IDENTIFIER ::= { configuration 27 }
|
||
|
|
||
|
xy1WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that XY1 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 1 }
|
||
|
|
||
|
yz1WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that YZ1 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 2 }
|
||
|
|
||
|
zx1WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that ZX1 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 3 }
|
||
|
|
||
|
xy2WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that XY2 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 4 }
|
||
|
|
||
|
yz2WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that YZ2 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 5 }
|
||
|
|
||
|
zx2WarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low voltage in volts that ZX2 can sag before triggering notifications, 0=ignore."
|
||
|
::= { warnLoVoltageLimits 6 }
|
||
|
|
||
|
receptacleMaxCurrent OBJECT IDENTIFIER ::= { configuration 28 }
|
||
|
|
||
|
outlet1MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 1 }
|
||
|
|
||
|
outlet2MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 2 }
|
||
|
|
||
|
outlet3MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 3 }
|
||
|
|
||
|
outlet4MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 4 }
|
||
|
|
||
|
outlet5MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 5 }
|
||
|
|
||
|
outlet6MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 6 }
|
||
|
|
||
|
outlet7MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 7 }
|
||
|
|
||
|
outlet8MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 8 }
|
||
|
|
||
|
outlet9MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 9 }
|
||
|
|
||
|
outlet10MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 10 }
|
||
|
|
||
|
outlet11MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 11 }
|
||
|
|
||
|
outlet12MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 12 }
|
||
|
|
||
|
outlet13MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 13 }
|
||
|
|
||
|
outlet14MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 14 }
|
||
|
|
||
|
outlet15MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 15 }
|
||
|
|
||
|
outlet16MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 16 }
|
||
|
|
||
|
outlet17MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 17 }
|
||
|
|
||
|
outlet18MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 18 }
|
||
|
|
||
|
outlet19MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 19 }
|
||
|
|
||
|
outlet20MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 20 }
|
||
|
|
||
|
outlet21MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 21 }
|
||
|
|
||
|
outlet22MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 22 }
|
||
|
|
||
|
outlet23MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 23 }
|
||
|
|
||
|
outlet24MaxCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 maximum current in 1/100 Amps."
|
||
|
::= { receptacleMaxCurrent 24 }
|
||
|
|
||
|
receptacleMinCurrent OBJECT IDENTIFIER ::= { configuration 29 }
|
||
|
|
||
|
outlet1MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 1 }
|
||
|
|
||
|
outlet2MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 2 }
|
||
|
|
||
|
outlet3MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 3 }
|
||
|
|
||
|
outlet4MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 4 }
|
||
|
|
||
|
outlet5MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 5 }
|
||
|
|
||
|
outlet6MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 6 }
|
||
|
|
||
|
outlet7MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 7 }
|
||
|
|
||
|
outlet8MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 8 }
|
||
|
|
||
|
outlet9MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 9 }
|
||
|
|
||
|
outlet10MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 10 }
|
||
|
|
||
|
outlet11MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 11 }
|
||
|
|
||
|
outlet12MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 12 }
|
||
|
|
||
|
outlet13MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 13 }
|
||
|
|
||
|
outlet14MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 14 }
|
||
|
|
||
|
outlet15MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 15 }
|
||
|
|
||
|
outlet16MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 16 }
|
||
|
|
||
|
outlet17MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 17 }
|
||
|
|
||
|
outlet18MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 18 }
|
||
|
|
||
|
outlet19MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 19 }
|
||
|
|
||
|
outlet20MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 20 }
|
||
|
|
||
|
outlet21MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 21 }
|
||
|
|
||
|
outlet22MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 22 }
|
||
|
|
||
|
outlet23MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 23 }
|
||
|
|
||
|
outlet24MinCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 minimum current in 1/100 Amps."
|
||
|
::= { receptacleMinCurrent 24 }
|
||
|
|
||
|
receptacleWarnHiCurrent OBJECT IDENTIFIER ::= { configuration 30 }
|
||
|
|
||
|
outlet1WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 1 }
|
||
|
|
||
|
outlet2WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 2 }
|
||
|
|
||
|
outlet3WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 3 }
|
||
|
|
||
|
outlet4WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 4 }
|
||
|
|
||
|
outlet5WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 5 }
|
||
|
|
||
|
outlet6WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 6 }
|
||
|
|
||
|
outlet7WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 7 }
|
||
|
|
||
|
outlet8WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 8 }
|
||
|
|
||
|
outlet9WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 9 }
|
||
|
|
||
|
outlet10WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 10 }
|
||
|
|
||
|
outlet11WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 11 }
|
||
|
|
||
|
outlet12WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 12 }
|
||
|
|
||
|
outlet13WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 13 }
|
||
|
|
||
|
outlet14WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 14 }
|
||
|
|
||
|
outlet15WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 15 }
|
||
|
|
||
|
outlet16WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 16 }
|
||
|
|
||
|
outlet17WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 17 }
|
||
|
|
||
|
outlet18WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 18 }
|
||
|
|
||
|
outlet19WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 19 }
|
||
|
|
||
|
outlet20WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 20 }
|
||
|
|
||
|
outlet21WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 21 }
|
||
|
|
||
|
outlet22WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 22 }
|
||
|
|
||
|
outlet23WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 23 }
|
||
|
|
||
|
outlet24WarnHiCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 warning high current in 1/100 Amps."
|
||
|
::= { receptacleWarnHiCurrent 24 }
|
||
|
|
||
|
receptacleWarnLoCurrent OBJECT IDENTIFIER ::= { configuration 31 }
|
||
|
|
||
|
outlet1WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 1 }
|
||
|
|
||
|
outlet2WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 2 }
|
||
|
|
||
|
outlet3WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 3 }
|
||
|
|
||
|
outlet4WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 4 }
|
||
|
|
||
|
outlet5WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 5 }
|
||
|
|
||
|
outlet6WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 6 }
|
||
|
|
||
|
outlet7WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 7 }
|
||
|
|
||
|
outlet8WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 8 }
|
||
|
|
||
|
outlet9WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 9 }
|
||
|
|
||
|
outlet10WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 10 }
|
||
|
|
||
|
outlet11WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 11 }
|
||
|
|
||
|
outlet12WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 12 }
|
||
|
|
||
|
outlet13WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 13 }
|
||
|
|
||
|
outlet14WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 14 }
|
||
|
|
||
|
outlet15WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 15 }
|
||
|
|
||
|
outlet16WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 16 }
|
||
|
|
||
|
outlet17WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 17 }
|
||
|
|
||
|
outlet18WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 18 }
|
||
|
|
||
|
outlet19WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 19 }
|
||
|
|
||
|
outlet20WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 20 }
|
||
|
|
||
|
outlet21WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 21 }
|
||
|
|
||
|
outlet22WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 22 }
|
||
|
|
||
|
outlet23WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 23 }
|
||
|
|
||
|
outlet24WarnLoCurr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 warning low current in 1/100 Amps."
|
||
|
::= { receptacleWarnLoCurrent 24 }
|
||
|
|
||
|
maxTempLimits OBJECT IDENTIFIER ::= { configuration 32 }
|
||
|
|
||
|
maxTempProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { maxTempLimits 1 }
|
||
|
|
||
|
maxTempProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { maxTempLimits 2 }
|
||
|
|
||
|
minTempLimits OBJECT IDENTIFIER ::= { configuration 33 }
|
||
|
|
||
|
minTempProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { minTempLimits 1 }
|
||
|
|
||
|
minTempProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { minTempLimits 2 }
|
||
|
|
||
|
warnHiTempLimits OBJECT IDENTIFIER ::= { configuration 34 }
|
||
|
|
||
|
warnHiTempProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { warnHiTempLimits 1 }
|
||
|
|
||
|
warnHiTempProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { warnHiTempLimits 2 }
|
||
|
|
||
|
warnLoTempLimits OBJECT IDENTIFIER ::= { configuration 35 }
|
||
|
|
||
|
warnLoTempProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { warnLoTempLimits 1 }
|
||
|
|
||
|
warnLoTempProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore."
|
||
|
::= { warnLoTempLimits 2 }
|
||
|
|
||
|
maxHumidityLimits OBJECT IDENTIFIER ::= { configuration 36 }
|
||
|
|
||
|
maxHumidProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum humidity for Probe 1 in 1/100 of %, 0=ignore."
|
||
|
::= { maxHumidityLimits 1 }
|
||
|
|
||
|
maxHumidProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum humidity for Probe 2 in 1/100 of %, 0=ignore."
|
||
|
::= { maxHumidityLimits 2 }
|
||
|
|
||
|
minHumidityLimits OBJECT IDENTIFIER ::= { configuration 37 }
|
||
|
|
||
|
minHumidProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum humidity for Probe 1 in 1/100 of %, 0=ignore."
|
||
|
::= { minHumidityLimits 1 }
|
||
|
|
||
|
minHumidProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Minimum humidity for Probe 2 in 1/100 of %, 0=ignore."
|
||
|
::= { minHumidityLimits 2 }
|
||
|
|
||
|
warnHiHumidityLimits OBJECT IDENTIFIER ::= { configuration 38 }
|
||
|
|
||
|
warnHiHumidProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High humidity for Probe 1 in 1/100 of %, 0=ignore."
|
||
|
::= { warnHiHumidityLimits 1 }
|
||
|
|
||
|
warnHiHumidProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning High humidity for Probe 2 in 1/100 of %, 0=ignore."
|
||
|
::= { warnHiHumidityLimits 2 }
|
||
|
|
||
|
warnLoHumidityLimits OBJECT IDENTIFIER ::= { configuration 39 }
|
||
|
|
||
|
warnLoHumidProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low humidity for Probe 1 in 1/100 of %, 0=ignore."
|
||
|
::= { warnLoHumidityLimits 1 }
|
||
|
|
||
|
warnLoHumidProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Warning Low humidity for Probe 2 in 1/100 of %, 0=ignore."
|
||
|
::= { warnLoHumidityLimits 2 }
|
||
|
|
||
|
pduName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Name."
|
||
|
::= { configuration 40 }
|
||
|
|
||
|
pduDescrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Description."
|
||
|
::= { configuration 41 }
|
||
|
|
||
|
receptacleNames OBJECT IDENTIFIER ::= { configuration 42 }
|
||
|
|
||
|
outlet1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 Name."
|
||
|
::= { receptacleNames 1 }
|
||
|
|
||
|
outlet2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 Name."
|
||
|
::= { receptacleNames 2 }
|
||
|
|
||
|
outlet3Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 Name."
|
||
|
::= { receptacleNames 3 }
|
||
|
|
||
|
outlet4Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 Name."
|
||
|
::= { receptacleNames 4 }
|
||
|
|
||
|
outlet5Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 Name."
|
||
|
::= { receptacleNames 5 }
|
||
|
|
||
|
outlet6Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 Name."
|
||
|
::= { receptacleNames 6 }
|
||
|
|
||
|
outlet7Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 Name."
|
||
|
::= { receptacleNames 7 }
|
||
|
|
||
|
outlet8Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 Name."
|
||
|
::= { receptacleNames 8 }
|
||
|
|
||
|
outlet9Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 Name."
|
||
|
::= { receptacleNames 9 }
|
||
|
|
||
|
outlet10Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 Name."
|
||
|
::= { receptacleNames 10 }
|
||
|
|
||
|
outlet11Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 Name."
|
||
|
::= { receptacleNames 11 }
|
||
|
|
||
|
outlet12Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 Name."
|
||
|
::= { receptacleNames 12 }
|
||
|
|
||
|
outlet13Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 Name."
|
||
|
::= { receptacleNames 13 }
|
||
|
|
||
|
outlet14Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 Name."
|
||
|
::= { receptacleNames 14 }
|
||
|
|
||
|
outlet15Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 Name."
|
||
|
::= { receptacleNames 15 }
|
||
|
|
||
|
outlet16Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 Name."
|
||
|
::= { receptacleNames 16 }
|
||
|
|
||
|
outlet17Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 Name."
|
||
|
::= { receptacleNames 17 }
|
||
|
|
||
|
outlet18Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 Name."
|
||
|
::= { receptacleNames 18 }
|
||
|
|
||
|
outlet19Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 Name."
|
||
|
::= { receptacleNames 19 }
|
||
|
|
||
|
outlet20Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 Name."
|
||
|
::= { receptacleNames 20 }
|
||
|
|
||
|
outlet21Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 Name."
|
||
|
::= { receptacleNames 21 }
|
||
|
|
||
|
outlet22Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 Name."
|
||
|
::= { receptacleNames 22 }
|
||
|
|
||
|
outlet23Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 Name."
|
||
|
::= { receptacleNames 23 }
|
||
|
|
||
|
outlet24Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 Name."
|
||
|
::= { receptacleNames 24 }
|
||
|
|
||
|
receptacleDescrips OBJECT IDENTIFIER ::= { configuration 43 }
|
||
|
|
||
|
outlet1Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 Description."
|
||
|
::= { receptacleDescrips 1 }
|
||
|
|
||
|
outlet2Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 Description."
|
||
|
::= { receptacleDescrips 2 }
|
||
|
|
||
|
outlet3Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 Description."
|
||
|
::= { receptacleDescrips 3 }
|
||
|
|
||
|
outlet4Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 Description."
|
||
|
::= { receptacleDescrips 4 }
|
||
|
|
||
|
outlet5Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 Description."
|
||
|
::= { receptacleDescrips 5 }
|
||
|
|
||
|
outlet6Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 Description."
|
||
|
::= { receptacleDescrips 6 }
|
||
|
|
||
|
outlet7Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 Description."
|
||
|
::= { receptacleDescrips 7 }
|
||
|
|
||
|
outlet8Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 Description."
|
||
|
::= { receptacleDescrips 8 }
|
||
|
|
||
|
outlet9Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 Description."
|
||
|
::= { receptacleDescrips 9 }
|
||
|
|
||
|
outlet10Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 Description."
|
||
|
::= { receptacleDescrips 10 }
|
||
|
|
||
|
outlet11Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 Description."
|
||
|
::= { receptacleDescrips 11 }
|
||
|
|
||
|
outlet12Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 Description."
|
||
|
::= { receptacleDescrips 12 }
|
||
|
|
||
|
outlet13Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 Description."
|
||
|
::= { receptacleDescrips 13 }
|
||
|
|
||
|
outlet14Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 Description."
|
||
|
::= { receptacleDescrips 14 }
|
||
|
|
||
|
outlet15Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 Description."
|
||
|
::= { receptacleDescrips 15 }
|
||
|
|
||
|
outlet16Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 Description."
|
||
|
::= { receptacleDescrips 16 }
|
||
|
|
||
|
outlet17Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 Description."
|
||
|
::= { receptacleDescrips 17 }
|
||
|
|
||
|
outlet18Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 Description."
|
||
|
::= { receptacleDescrips 18 }
|
||
|
|
||
|
outlet19Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 Description."
|
||
|
::= { receptacleDescrips 19 }
|
||
|
|
||
|
outlet20Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 Description."
|
||
|
::= { receptacleDescrips 20 }
|
||
|
|
||
|
outlet21Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 Description."
|
||
|
::= { receptacleDescrips 21 }
|
||
|
|
||
|
outlet22Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 Description."
|
||
|
::= { receptacleDescrips 22 }
|
||
|
|
||
|
outlet23Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 Description."
|
||
|
::= { receptacleDescrips 23 }
|
||
|
|
||
|
outlet24Descrip OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 Description."
|
||
|
::= { receptacleDescrips 24 }
|
||
|
|
||
|
groupNames OBJECT IDENTIFIER ::= { configuration 50 }
|
||
|
|
||
|
group1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 1 of receptacles."
|
||
|
::= { groupNames 1 }
|
||
|
|
||
|
group2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 2 of receptacles."
|
||
|
::= { groupNames 2 }
|
||
|
|
||
|
group3Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 3 of receptacles."
|
||
|
::= { groupNames 3 }
|
||
|
|
||
|
group4Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 4 of receptacles."
|
||
|
::= { groupNames 4 }
|
||
|
|
||
|
group5Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 5 of receptacles."
|
||
|
::= { groupNames 5 }
|
||
|
|
||
|
group6Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 6 of receptacles."
|
||
|
::= { groupNames 6 }
|
||
|
|
||
|
group7Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 7 of receptacles."
|
||
|
::= { groupNames 7 }
|
||
|
|
||
|
group8Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 8 of receptacles."
|
||
|
::= { groupNames 8 }
|
||
|
|
||
|
group9Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 9 of receptacles."
|
||
|
::= { groupNames 9 }
|
||
|
|
||
|
group10Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 10 of receptacles."
|
||
|
::= { groupNames 10 }
|
||
|
|
||
|
group11Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 11 of receptacles."
|
||
|
::= { groupNames 11 }
|
||
|
|
||
|
group12Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 12 of receptacles."
|
||
|
::= { groupNames 12 }
|
||
|
|
||
|
group13Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 13 of receptacles."
|
||
|
::= { groupNames 13 }
|
||
|
|
||
|
group14Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 14 of receptacles."
|
||
|
::= { groupNames 14 }
|
||
|
|
||
|
group15Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 15 of receptacles."
|
||
|
::= { groupNames 15 }
|
||
|
|
||
|
group16Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 16 of receptacles."
|
||
|
::= { groupNames 16 }
|
||
|
|
||
|
groupMaps OBJECT IDENTIFIER ::= { configuration 51 }
|
||
|
|
||
|
group1Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 1 of receptacels."
|
||
|
::= { groupMaps 1 }
|
||
|
|
||
|
group2Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 2 of receptacels."
|
||
|
::= { groupMaps 2 }
|
||
|
|
||
|
group3Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 3 of receptacels."
|
||
|
::= { groupMaps 3 }
|
||
|
|
||
|
group4Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 4 of receptacels."
|
||
|
::= { groupMaps 4 }
|
||
|
|
||
|
group5Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 5 of receptacels."
|
||
|
::= { groupMaps 5 }
|
||
|
|
||
|
group6Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 6 of receptacels."
|
||
|
::= { groupMaps 6 }
|
||
|
|
||
|
group7Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 7 of receptacels."
|
||
|
::= { groupMaps 7 }
|
||
|
|
||
|
group8Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 8 of receptacels."
|
||
|
::= { groupMaps 8 }
|
||
|
|
||
|
group9Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 9 of receptacels."
|
||
|
::= { groupMaps 9 }
|
||
|
|
||
|
group10Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 10 of receptacels."
|
||
|
::= { groupMaps 10 }
|
||
|
|
||
|
group11Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 11 of receptacels."
|
||
|
::= { groupMaps 11 }
|
||
|
|
||
|
group12Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 12 of receptacels."
|
||
|
::= { groupMaps 12 }
|
||
|
|
||
|
group13Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 13 of receptacels."
|
||
|
::= { groupMaps 13 }
|
||
|
|
||
|
group14Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 14 of receptacels."
|
||
|
::= { groupMaps 14 }
|
||
|
|
||
|
group15Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 15 of receptacels."
|
||
|
::= { groupMaps 15 }
|
||
|
|
||
|
group16Map OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..256))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map for Group 16 of receptacels."
|
||
|
::= { groupMaps 16 }
|
||
|
|
||
|
dispTimeout OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..90)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Inactivity timeout in minutes to blank the local display (minimum is 1 minute)."
|
||
|
::= { configuration 55 }
|
||
|
|
||
|
loginTimeout OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..60)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Inactivity timeout in minutes to terminate a logged in session (minimum is 1 minute)."
|
||
|
::= { configuration 56 }
|
||
|
|
||
|
dispBrightness OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..9)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The relative brightness of the local display (0 in min, 9 is max)."
|
||
|
::= { configuration 57 }
|
||
|
|
||
|
pduOptions OBJECT IDENTIFIER ::= { configuration 58 }
|
||
|
|
||
|
inputTop OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord entry orientation, 1 = top, 0 = bottom."
|
||
|
::= { pduOptions 1 }
|
||
|
|
||
|
pduRole OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Role, 1 = primary, 0 = secondary."
|
||
|
::= { pduOptions 2 }
|
||
|
|
||
|
celsiusTemp OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature units, 1=Celsius, 0=Fahrenheit."
|
||
|
::= { pduOptions 3 }
|
||
|
|
||
|
enableWeb OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable Web Access, 1 = enable, 0 = disable."
|
||
|
::= { pduOptions 4 }
|
||
|
|
||
|
snmpHostOnly OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Restrict access to SNMP via listed Hosts only, 1 = listed SNMP hosts only, 0 = any host."
|
||
|
::= { pduOptions 5 }
|
||
|
|
||
|
disLocalAuth OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Disable local authentication, 1 = disable, 0 = enable."
|
||
|
::= { pduOptions 6 }
|
||
|
|
||
|
enaRadiusAuth OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable Radius authentication, 1 = disable, 0 = enable."
|
||
|
::= { pduOptions 7 }
|
||
|
|
||
|
enaADAuth OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable Active Directory authentication, 1 = disable, 0 = enable."
|
||
|
::= { pduOptions 8 }
|
||
|
|
||
|
enaSMTP OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable Mail Notification, 1 = disable, 0 = enable."
|
||
|
::= { pduOptions 9 }
|
||
|
|
||
|
pduAltRole OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Alternate Role, 1 = alternate, 0 = secondary."
|
||
|
::= { pduOptions 10 }
|
||
|
|
||
|
shareRole OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Allow sharing of PDU Primary and Alternate Roles, 1 = shared, 0 = backup only."
|
||
|
::= { pduOptions 11 }
|
||
|
|
||
|
outOfService OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Remove a PDU from normal operation, 1 = out of service, 0 = normal operation."
|
||
|
::= { pduOptions 12 }
|
||
|
|
||
|
missingPDUNotify OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notify when a PDU is missing from the link, 1 = enable, 0 = disable."
|
||
|
::= { pduOptions 13 }
|
||
|
|
||
|
roleChangeNotify OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notify when a PDU changes role in the link, 1 = enable, 0 = disable."
|
||
|
::= { pduOptions 14 }
|
||
|
|
||
|
sumAmp OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Display the sum of the current across branches, 1 = enable, 0 = disable."
|
||
|
::= { pduOptions 15 }
|
||
|
|
||
|
httpPorts OBJECT IDENTIFIER ::= { configuration 59 }
|
||
|
|
||
|
httpPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for unsecure HTTP access."
|
||
|
::= { httpPorts 1 }
|
||
|
|
||
|
httpsPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for secure HTTPS access."
|
||
|
::= { httpPorts 2 }
|
||
|
|
||
|
sshPorts OBJECT IDENTIFIER ::= { configuration 60 }
|
||
|
|
||
|
sshPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for secure SSH access."
|
||
|
::= { sshPorts 1 }
|
||
|
|
||
|
telnetPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for non secure Telnet access."
|
||
|
::= { sshPorts 2 }
|
||
|
|
||
|
snmpPorts OBJECT IDENTIFIER ::= { configuration 61 }
|
||
|
|
||
|
snmpQueryPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for SNMP query access."
|
||
|
::= { snmpPorts 1 }
|
||
|
|
||
|
snmpTrapPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for SNMP trap."
|
||
|
::= { snmpPorts 2 }
|
||
|
|
||
|
smtpPorts OBJECT IDENTIFIER ::= { configuration 62 }
|
||
|
|
||
|
smtpSendPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for SMTP send."
|
||
|
::= { smtpPorts 1 }
|
||
|
|
||
|
smtpReceivePort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for SMTP Receive."
|
||
|
::= { smtpPorts 2 }
|
||
|
|
||
|
rfcTimeServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"RFC Time Server Address."
|
||
|
::= { configuration 63 }
|
||
|
|
||
|
ntpTimeServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"NTP Time Server Address."
|
||
|
::= { configuration 64 }
|
||
|
|
||
|
smtpServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Email Server Address."
|
||
|
::= { configuration 65 }
|
||
|
|
||
|
snmpReadComm OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Read Community."
|
||
|
::= { configuration 66 }
|
||
|
|
||
|
snmpWriteComm OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Write Community."
|
||
|
::= { configuration 67 }
|
||
|
|
||
|
snmpUSMuserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP USM User Name."
|
||
|
::= { configuration 68 }
|
||
|
|
||
|
snmpSecurityLevelAlgorithm OBJECT IDENTIFIER ::= { configuration 69 }
|
||
|
|
||
|
snmpSecurityLevel OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..4)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Security Level for SNMP: 0 = v1, 1 = v2c, 2 = v3 no authentication,
|
||
|
3 = v3 with authentication only, 4 = v3 with authentication and privacy"
|
||
|
::= { snmpSecurityLevelAlgorithm 1 }
|
||
|
|
||
|
snmpAuthAlgo OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Authentication Algorithm for SNMP: 0 = SHA, 1 = MD5."
|
||
|
::= { snmpSecurityLevelAlgorithm 2 }
|
||
|
|
||
|
snmpPrivAlgo OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Privacy Algorithm for SNMP: 0 = DES, 1 = AES."
|
||
|
::= { snmpSecurityLevelAlgorithm 3 }
|
||
|
|
||
|
snmpAuthPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Authentication Password."
|
||
|
::= { configuration 70 }
|
||
|
|
||
|
snmpPrivPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Privacy Password."
|
||
|
::= { configuration 71 }
|
||
|
|
||
|
snmpContextName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Context Name."
|
||
|
::= { configuration 72 }
|
||
|
|
||
|
snmpEngineID OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Engine ID."
|
||
|
::= { configuration 73 }
|
||
|
|
||
|
snmpLocAuthKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Local Authentication Key."
|
||
|
::= { configuration 74 }
|
||
|
|
||
|
snmpLocPrivKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Local Privacy Key."
|
||
|
::= { configuration 75 }
|
||
|
|
||
|
smtpUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Email User Login Name."
|
||
|
::= { configuration 76 }
|
||
|
|
||
|
smtpUserPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Email User Login Password."
|
||
|
::= { configuration 77 }
|
||
|
|
||
|
smtpEmailAddr OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Email address."
|
||
|
::= { configuration 78 }
|
||
|
|
||
|
smtpEmailDestinations OBJECT IDENTIFIER ::= { configuration 79 }
|
||
|
|
||
|
smtpEmailDestination1 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Email destination for recipient 0."
|
||
|
::= { smtpEmailDestinations 1 }
|
||
|
|
||
|
smtpEmailDestination2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Email destination for recipient 1."
|
||
|
::= { smtpEmailDestinations 2 }
|
||
|
|
||
|
smtpEmailDestination3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Email destination for recipient 2."
|
||
|
::= { smtpEmailDestinations 3 }
|
||
|
|
||
|
smtpServOptions OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SMTP Server Options."
|
||
|
::= { configuration 80 }
|
||
|
|
||
|
radiusServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Radius Authentication Server."
|
||
|
::= { configuration 81 }
|
||
|
|
||
|
radiusSHSecret OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Radius Shared Secret."
|
||
|
::= { configuration 82 }
|
||
|
|
||
|
radiusNASServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Radius Network Access Service."
|
||
|
::= { configuration 83 }
|
||
|
|
||
|
radiusNASPorts OBJECT IDENTIFIER ::= { configuration 84 }
|
||
|
|
||
|
radiusPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for radius authentication."
|
||
|
::= { radiusNASPorts 1 }
|
||
|
|
||
|
nasPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for Radius Network Access Service."
|
||
|
::= { radiusNASPorts 2 }
|
||
|
|
||
|
adServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Active Directory Server."
|
||
|
::= { configuration 85 }
|
||
|
|
||
|
adDomain OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Active Directory Domain."
|
||
|
::= { configuration 86 }
|
||
|
|
||
|
adAllPorts OBJECT IDENTIFIER ::= { configuration 87 }
|
||
|
|
||
|
adPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Port for Active Directory authentication."
|
||
|
::= { adAllPorts 1 }
|
||
|
|
||
|
adResvPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Alternate or reserved port for Active Directory Authentication."
|
||
|
::= { adAllPorts 2 }
|
||
|
|
||
|
envProbeNames OBJECT IDENTIFIER ::= { configuration 88 }
|
||
|
|
||
|
probe1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for Environmental Probe 1."
|
||
|
::= { envProbeNames 1 }
|
||
|
|
||
|
probe2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for Environmental Probe 2."
|
||
|
::= { envProbeNames 2 }
|
||
|
|
||
|
dLogOptions OBJECT IDENTIFIER ::= { configuration 89 }
|
||
|
|
||
|
dLogEnable OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable data logging feature, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 1 }
|
||
|
|
||
|
netservdLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable data logging to log server over network, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 11 }
|
||
|
|
||
|
autonetLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable automatic transfer to log server every 6 hours, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 12 }
|
||
|
|
||
|
stdmeterdLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of branch, receptacle and environmental metrics, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 2 }
|
||
|
|
||
|
groupmeterdLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of grouped receptacle metrics, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 3 }
|
||
|
|
||
|
alarmdLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of alarm events, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 4 }
|
||
|
|
||
|
userlogindLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of user login events, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 5 }
|
||
|
|
||
|
usersetupdLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of user setup change events, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 6 }
|
||
|
|
||
|
fwupdatedLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable data logging feature, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 7 }
|
||
|
|
||
|
setupchangedLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of setup change events, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 8 }
|
||
|
|
||
|
recepchangedLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of receptacle state changes, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 9 }
|
||
|
|
||
|
pduopchangedLog OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable logging of PDU operation and state changes, 0=disable and 1=enable."
|
||
|
::= { dLogOptions 10 }
|
||
|
|
||
|
dLogCycle OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The time interval in minutes for internal data logging to occur."
|
||
|
::= { configuration 90 }
|
||
|
|
||
|
dLogFullWarnLevel OBJECT-TYPE
|
||
|
SYNTAX Integer32 (50..100)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The warning threshold for percentage of storage full (min=50, max=100)."
|
||
|
::= { configuration 91 }
|
||
|
|
||
|
netdLogServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The network address for the data log server."
|
||
|
::= { configuration 92 }
|
||
|
|
||
|
netdLogPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The port used by the data log server."
|
||
|
::= { configuration 93 }
|
||
|
|
||
|
netdLogUser OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user name to access the data log server."
|
||
|
::= { configuration 94 }
|
||
|
|
||
|
netdLogPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user password to access the data log server."
|
||
|
::= { configuration 95 }
|
||
|
|
||
|
netdLogDestdir OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The destination directory in the data log server."
|
||
|
::= { configuration 96 }
|
||
|
|
||
|
netdLogOptions OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The options string when accessing the data log server."
|
||
|
::= { configuration 97 }
|
||
|
|
||
|
snmpTrapHosts OBJECT IDENTIFIER ::= { configuration 98 }
|
||
|
|
||
|
snmpTrapHost1 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 1 IP address."
|
||
|
::= { snmpTrapHosts 1 }
|
||
|
|
||
|
snmpTrapHost2 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 2 IP address."
|
||
|
::= { snmpTrapHosts 2 }
|
||
|
|
||
|
snmpTrapHost3 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 3 IP address."
|
||
|
::= { snmpTrapHosts 3 }
|
||
|
|
||
|
snmpTrapHostsIPv6 OBJECT IDENTIFIER ::= { configuration 99 }
|
||
|
|
||
|
snmpTrapHost1IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 1 IPV6."
|
||
|
::= { snmpTrapHostsIPv6 1 }
|
||
|
|
||
|
snmpTrapHost2IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 2 IPV6."
|
||
|
::= { snmpTrapHostsIPv6 2 }
|
||
|
|
||
|
snmpTrapHost3IPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SNMP Trap Host 3 IPV6."
|
||
|
::= { snmpTrapHostsIPv6 3 }
|
||
|
|
||
|
lnkAttachCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..19)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Count of secondary PDUs that are attached to the link."
|
||
|
::= { configuration 100 }
|
||
|
|
||
|
metrics OBJECT IDENTIFIER ::= { cpiPDU 3 }
|
||
|
|
||
|
mcurrent OBJECT IDENTIFIER ::= { metrics 1 }
|
||
|
|
||
|
currentxy1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY1 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 1 }
|
||
|
|
||
|
currentyz1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ1 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 2 }
|
||
|
|
||
|
currentzx1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX1 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 3 }
|
||
|
|
||
|
currentxy2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY2 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 4 }
|
||
|
|
||
|
currentyz2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ2 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 5 }
|
||
|
|
||
|
currentzx2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX2 current draw in 1/100 Amps."
|
||
|
::= { mcurrent 6 }
|
||
|
|
||
|
mvoltage OBJECT IDENTIFIER ::= { metrics 2 }
|
||
|
|
||
|
voltagexy1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY1 voltage in 1/10 volts."
|
||
|
::= { mvoltage 1 }
|
||
|
|
||
|
voltageyz1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ1 voltage in 1/10 volts."
|
||
|
::= { mvoltage 2 }
|
||
|
|
||
|
voltagezx1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX1 voltage in 1/10 volts."
|
||
|
::= { mvoltage 3 }
|
||
|
|
||
|
voltagexy2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY2 voltage in 1/10 volts."
|
||
|
::= { mvoltage 4 }
|
||
|
|
||
|
voltageyz2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ2 voltage in 1/10 volts."
|
||
|
::= { mvoltage 5 }
|
||
|
|
||
|
voltagezx2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3120)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX2 voltage in 1/10 volts."
|
||
|
::= { mvoltage 6 }
|
||
|
|
||
|
mpower OBJECT IDENTIFIER ::= { metrics 3 }
|
||
|
|
||
|
powerxy1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY1 power consumption in Watts."
|
||
|
::= { mpower 1 }
|
||
|
|
||
|
poweryz1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ1 power consumption in Watts."
|
||
|
::= { mpower 2 }
|
||
|
|
||
|
powerzx1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX1 power consumption in Watts."
|
||
|
::= { mpower 3 }
|
||
|
|
||
|
powerxy2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY2 power consumption in Watts."
|
||
|
::= { mpower 4 }
|
||
|
|
||
|
poweryz2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ2 power consumption in Watts."
|
||
|
::= { mpower 5 }
|
||
|
|
||
|
powerzx2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6240)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX2 power consumption in Watts."
|
||
|
::= { mpower 6 }
|
||
|
|
||
|
mpowerFactor OBJECT IDENTIFIER ::= { metrics 4 }
|
||
|
|
||
|
powerFactxy1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY1 power factor x 100."
|
||
|
::= { mpowerFactor 1 }
|
||
|
|
||
|
powerFactyz1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ1 power factor x 100."
|
||
|
::= { mpowerFactor 2 }
|
||
|
|
||
|
powerFactzx1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX1 power factor x 100."
|
||
|
::= { mpowerFactor 3 }
|
||
|
|
||
|
powerFactxy2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY2 power factor x 100."
|
||
|
::= { mpowerFactor 4 }
|
||
|
|
||
|
powerFactyz2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ2 power factor x 100."
|
||
|
::= { mpowerFactor 5 }
|
||
|
|
||
|
powerFactzx2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (-100..100)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX2 power factor x 100."
|
||
|
::= { mpowerFactor 6 }
|
||
|
|
||
|
receptacleCurrent OBJECT IDENTIFIER ::= { metrics 5 }
|
||
|
|
||
|
outlet1Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 1 }
|
||
|
|
||
|
outlet2Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 2 }
|
||
|
|
||
|
outlet3Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 3 }
|
||
|
|
||
|
outlet4Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 4 }
|
||
|
|
||
|
outlet5Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 5 }
|
||
|
|
||
|
outlet6Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 6 }
|
||
|
|
||
|
outlet7Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 7 }
|
||
|
|
||
|
outlet8Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 8 }
|
||
|
|
||
|
outlet9Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 9 }
|
||
|
|
||
|
outlet10Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 10 }
|
||
|
|
||
|
outlet11Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 11 }
|
||
|
|
||
|
outlet12Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 12 }
|
||
|
|
||
|
outlet13Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 13 }
|
||
|
|
||
|
outlet14Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 14 }
|
||
|
|
||
|
outlet15Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 15 }
|
||
|
|
||
|
outlet16Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 16 }
|
||
|
|
||
|
outlet17Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 17 }
|
||
|
|
||
|
outlet18Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 18 }
|
||
|
|
||
|
outlet19Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 19 }
|
||
|
|
||
|
outlet20Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 20 }
|
||
|
|
||
|
outlet21Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 21 }
|
||
|
|
||
|
outlet22Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 22 }
|
||
|
|
||
|
outlet23Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 23 }
|
||
|
|
||
|
outlet24Current OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 current draw in 1/100 Amps."
|
||
|
::= { receptacleCurrent 24 }
|
||
|
|
||
|
receptacleCurrentMap OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..120))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map of receptacle currents in ascending order and delimited by space."
|
||
|
::= { metrics 6 }
|
||
|
|
||
|
receptacleStatus OBJECT IDENTIFIER ::= { metrics 7 }
|
||
|
|
||
|
outlet1State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 1 }
|
||
|
|
||
|
outlet2State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 2 }
|
||
|
|
||
|
outlet3State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 3 }
|
||
|
|
||
|
outlet4State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 4 }
|
||
|
|
||
|
outlet5State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 5 }
|
||
|
|
||
|
outlet6State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 6 }
|
||
|
|
||
|
outlet7State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 7 }
|
||
|
|
||
|
outlet8State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 8 }
|
||
|
|
||
|
outlet9State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 9 }
|
||
|
|
||
|
outlet10State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 10 }
|
||
|
|
||
|
outlet11State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 11 }
|
||
|
|
||
|
outlet12State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 12 }
|
||
|
|
||
|
outlet13State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 13 }
|
||
|
|
||
|
outlet14State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 14 }
|
||
|
|
||
|
outlet15State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 15 }
|
||
|
|
||
|
outlet16State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 16 }
|
||
|
|
||
|
outlet17State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 17 }
|
||
|
|
||
|
outlet18State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 18 }
|
||
|
|
||
|
outlet19State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 19 }
|
||
|
|
||
|
outlet20State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 20 }
|
||
|
|
||
|
outlet21State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 21 }
|
||
|
|
||
|
outlet22State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 22 }
|
||
|
|
||
|
outlet23State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 23 }
|
||
|
|
||
|
outlet24State OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 power state, 0=OFF, 1=ON."
|
||
|
::= { receptacleStatus 24 }
|
||
|
|
||
|
temperature OBJECT IDENTIFIER ::= { metrics 8 }
|
||
|
|
||
|
temperatureProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Probe 1 temperature in 1/100 degree Fahrenheit."
|
||
|
::= { temperature 1 }
|
||
|
|
||
|
temperatureProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..20000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Probe 2 temperature in 1/100 degree Fahrenheit."
|
||
|
::= { temperature 2 }
|
||
|
|
||
|
humidity OBJECT IDENTIFIER ::= { metrics 9 }
|
||
|
|
||
|
humidityProbe1 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Probe 1 humidity in 1/100 %."
|
||
|
::= { humidity 1 }
|
||
|
|
||
|
humidityProbe2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..10000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Probe 2 humidity in 1/100 %."
|
||
|
::= { humidity 2 }
|
||
|
|
||
|
alarms OBJECT IDENTIFIER ::= { metrics 10 }
|
||
|
|
||
|
alarmsMaxMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Max threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ...
|
||
|
bit6=voltA, bit7=voltB, bit8=voltC ...
|
||
|
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2"
|
||
|
::= { alarms 1 }
|
||
|
|
||
|
alarmsMinMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Min threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ...
|
||
|
bit6=voltA, bit7=voltB, bit8=voltC ...
|
||
|
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2"
|
||
|
::= { alarms 2 }
|
||
|
|
||
|
alarmsWarnHiMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"High threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ...
|
||
|
bit6=voltA, bit7=voltB, bit8=voltC ...
|
||
|
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2"
|
||
|
::= { alarms 3 }
|
||
|
|
||
|
alarmsWarnLoMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Low threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ...
|
||
|
bit6=voltA, bit7=voltB, bit8=voltC ...
|
||
|
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2"
|
||
|
::= { alarms 4 }
|
||
|
|
||
|
recep1To32AlarmsMaxMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Max threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32"
|
||
|
::= { alarms 5 }
|
||
|
|
||
|
recep1To32AlarmsMinMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Min threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32"
|
||
|
::= { alarms 7 }
|
||
|
|
||
|
recep1To32WarnHiMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"High threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32"
|
||
|
::= { alarms 9 }
|
||
|
|
||
|
recep1To32WarnLoMap OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Low threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32"
|
||
|
::= { alarms 11 }
|
||
|
|
||
|
menergy OBJECT IDENTIFIER ::= { metrics 11 }
|
||
|
|
||
|
energyxy1s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 1 }
|
||
|
|
||
|
energyyz1s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 2 }
|
||
|
|
||
|
energyzx1s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 3 }
|
||
|
|
||
|
energyxy2s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"XY2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 4 }
|
||
|
|
||
|
energyyz2s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"YZ2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 5 }
|
||
|
|
||
|
energyzx2s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"ZX2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { menergy 6 }
|
||
|
|
||
|
receptacleEnergy OBJECT IDENTIFIER ::= { metrics 12 }
|
||
|
|
||
|
receptacleEnergyoutlet1s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet1 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 1 }
|
||
|
|
||
|
receptacleEnergyoutlet2s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet2 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 2 }
|
||
|
|
||
|
receptacleEnergyoutlet3s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet3 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 3 }
|
||
|
|
||
|
receptacleEnergyoutlet4s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet4 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 4 }
|
||
|
|
||
|
receptacleEnergyoutlet5s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet5 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 5 }
|
||
|
|
||
|
receptacleEnergyoutlet6s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet6 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 6 }
|
||
|
|
||
|
receptacleEnergyoutlet7s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet7 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 7 }
|
||
|
|
||
|
receptacleEnergyoutlet8s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet8 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 8 }
|
||
|
|
||
|
receptacleEnergyoutlet9s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet9 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 9 }
|
||
|
|
||
|
receptacleEnergyoutlet10s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet10 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 10 }
|
||
|
|
||
|
receptacleEnergyoutlet11s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet11 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 11 }
|
||
|
|
||
|
receptacleEnergyoutlet12s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet12 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 12 }
|
||
|
|
||
|
receptacleEnergyoutlet13s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet13 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 13 }
|
||
|
|
||
|
receptacleEnergyoutlet14s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet14 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 14 }
|
||
|
|
||
|
receptacleEnergyoutlet15s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet15 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 15 }
|
||
|
|
||
|
receptacleEnergyoutlet16s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet16 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 16 }
|
||
|
|
||
|
receptacleEnergyoutlet17s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet17 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 17 }
|
||
|
|
||
|
receptacleEnergyoutlet18s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet18 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 18 }
|
||
|
|
||
|
receptacleEnergyoutlet19s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet19 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 19 }
|
||
|
|
||
|
receptacleEnergyoutlet20s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet20 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 20 }
|
||
|
|
||
|
receptacleEnergyoutlet21s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet21 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 21 }
|
||
|
|
||
|
receptacleEnergyoutlet22s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet22 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 22 }
|
||
|
|
||
|
receptacleEnergyoutlet23s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet23 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 23 }
|
||
|
|
||
|
receptacleEnergyoutlet24s OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet24 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { receptacleEnergy 24 }
|
||
|
|
||
|
mline OBJECT IDENTIFIER ::= { metrics 13 }
|
||
|
|
||
|
line1curr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line 1 current draw in 1/100 Amps."
|
||
|
::= { mline 1 }
|
||
|
|
||
|
line2curr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line 2 current draw in 1/100 Amps."
|
||
|
::= { mline 2 }
|
||
|
|
||
|
line3curr OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..3000)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line 3 current draw in 1/100 Amps."
|
||
|
::= { mline 3 }
|
||
|
|
||
|
control OBJECT IDENTIFIER ::= { cpiPDU 4 }
|
||
|
|
||
|
creceptacleControl OBJECT IDENTIFIER ::= { control 1 }
|
||
|
|
||
|
outlet1ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet1, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 1 }
|
||
|
|
||
|
outlet2ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet2, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 2 }
|
||
|
|
||
|
outlet3ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet3, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 3 }
|
||
|
|
||
|
outlet4ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet4, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 4 }
|
||
|
|
||
|
outlet5ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet5, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 5 }
|
||
|
|
||
|
outlet6ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet6, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 6 }
|
||
|
|
||
|
outlet7ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet7, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 7 }
|
||
|
|
||
|
outlet8ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet8, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 8 }
|
||
|
|
||
|
outlet9ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet9, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 9 }
|
||
|
|
||
|
outlet10ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet10, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 10 }
|
||
|
|
||
|
outlet11ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet11, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 11 }
|
||
|
|
||
|
outlet12ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet12, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 12 }
|
||
|
|
||
|
outlet13ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet13, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 13 }
|
||
|
|
||
|
outlet14ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet14, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 14 }
|
||
|
|
||
|
outlet15ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet15, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 15 }
|
||
|
|
||
|
outlet16ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet16, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 16 }
|
||
|
|
||
|
outlet17ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet17, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 17 }
|
||
|
|
||
|
outlet18ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet18, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 18 }
|
||
|
|
||
|
outlet19ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet19, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 19 }
|
||
|
|
||
|
outlet20ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet20, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 20 }
|
||
|
|
||
|
outlet21ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet21, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 21 }
|
||
|
|
||
|
outlet22ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet22, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 22 }
|
||
|
|
||
|
outlet23ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet23, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 23 }
|
||
|
|
||
|
outlet24ONOFF OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Turn ON or OFF power to Outlet24, 1=ON, 0=OFF."
|
||
|
::= { creceptacleControl 24 }
|
||
|
|
||
|
receptacleReset OBJECT IDENTIFIER ::= { control 2 }
|
||
|
|
||
|
outlet1Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet1, 1=reset."
|
||
|
::= { receptacleReset 1 }
|
||
|
|
||
|
outlet2Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet2, 1=reset."
|
||
|
::= { receptacleReset 2 }
|
||
|
|
||
|
outlet3Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet3, 1=reset."
|
||
|
::= { receptacleReset 3 }
|
||
|
|
||
|
outlet4Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet4, 1=reset."
|
||
|
::= { receptacleReset 4 }
|
||
|
|
||
|
outlet5Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet5, 1=reset."
|
||
|
::= { receptacleReset 5 }
|
||
|
|
||
|
outlet6Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet6, 1=reset."
|
||
|
::= { receptacleReset 6 }
|
||
|
|
||
|
outlet7Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet7, 1=reset."
|
||
|
::= { receptacleReset 7 }
|
||
|
|
||
|
outlet8Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet8, 1=reset."
|
||
|
::= { receptacleReset 8 }
|
||
|
|
||
|
outlet9Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet9, 1=reset."
|
||
|
::= { receptacleReset 9 }
|
||
|
|
||
|
outlet10Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet10, 1=reset."
|
||
|
::= { receptacleReset 10 }
|
||
|
|
||
|
outlet11Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet11, 1=reset."
|
||
|
::= { receptacleReset 11 }
|
||
|
|
||
|
outlet12Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet12, 1=reset."
|
||
|
::= { receptacleReset 12 }
|
||
|
|
||
|
outlet13Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet13, 1=reset."
|
||
|
::= { receptacleReset 13 }
|
||
|
|
||
|
outlet14Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet14, 1=reset."
|
||
|
::= { receptacleReset 14 }
|
||
|
|
||
|
outlet15Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet15, 1=reset."
|
||
|
::= { receptacleReset 15 }
|
||
|
|
||
|
outlet16Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet16, 1=reset."
|
||
|
::= { receptacleReset 16 }
|
||
|
|
||
|
outlet17Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet17, 1=reset."
|
||
|
::= { receptacleReset 17 }
|
||
|
|
||
|
outlet18Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet18, 1=reset."
|
||
|
::= { receptacleReset 18 }
|
||
|
|
||
|
outlet19Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet19, 1=reset."
|
||
|
::= { receptacleReset 19 }
|
||
|
|
||
|
outlet20Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet20, 1=reset."
|
||
|
::= { receptacleReset 20 }
|
||
|
|
||
|
outlet21Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet21, 1=reset."
|
||
|
::= { receptacleReset 21 }
|
||
|
|
||
|
outlet22Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet22, 1=reset."
|
||
|
::= { receptacleReset 22 }
|
||
|
|
||
|
outlet23Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet23, 1=reset."
|
||
|
::= { receptacleReset 23 }
|
||
|
|
||
|
outlet24Reset OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Reset power to Outlet24, 1=reset."
|
||
|
::= { receptacleReset 24 }
|
||
|
|
||
|
receptacleCtrlMap OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..24))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Map of receptacle status in ascending order, 1=ON, 0=OFF."
|
||
|
::= { control 3 }
|
||
|
|
||
|
chained OBJECT IDENTIFIER ::= { cpiPDU 5 }
|
||
|
|
||
|
pduCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..32)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Count of number of PDUs in the chain."
|
||
|
::= { chained 1 }
|
||
|
|
||
|
pduMap OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..300))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Table map of PDU IDs in the chain, each ID consists of 4 bytes."
|
||
|
::= { chained 2 }
|
||
|
|
||
|
pduSelect OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..16777215)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Selects the PDUs in the chain for access."
|
||
|
::= { chained 3 }
|
||
|
|
||
|
pduNamelist OBJECT-TYPE
|
||
|
SYNTAX OCTET STRING (SIZE (0..2048))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"List of PDU Names in the chain link, delimited by '|' and in matching order with pduMap."
|
||
|
::= { chained 4 }
|
||
|
|
||
|
cpiTraps OBJECT IDENTIFIER ::= { cpiPDU 6 }
|
||
|
|
||
|
cpiSpecific OBJECT IDENTIFIER ::= { cpiTraps 0 }
|
||
|
|
||
|
maxCurrentxy1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentxy1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in XY1 exceeds set limit."
|
||
|
::= { cpiSpecific 1 }
|
||
|
|
||
|
maxCurrentyz1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentyz1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in YZ1 exceeds set limit."
|
||
|
::= { cpiSpecific 2 }
|
||
|
|
||
|
maxCurrentzx1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentzx1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in ZX1 exceeds set limit."
|
||
|
::= { cpiSpecific 3 }
|
||
|
|
||
|
maxCurrentxy2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentxy2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in XY2 exceeds set limit."
|
||
|
::= { cpiSpecific 4 }
|
||
|
|
||
|
maxCurrentyz2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentyz2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in YZ2 exceeds set limit."
|
||
|
::= { cpiSpecific 5 }
|
||
|
|
||
|
maxCurrentzx2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentzx2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in ZX2 exceeds set limit."
|
||
|
::= { cpiSpecific 6 }
|
||
|
|
||
|
minCurrentxy1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentxy1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in XY1 drops below set limit."
|
||
|
::= { cpiSpecific 7 }
|
||
|
|
||
|
minCurrentyz1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentyz1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in YZ1 drops below set limit."
|
||
|
::= { cpiSpecific 8 }
|
||
|
|
||
|
minCurrentzx1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentzx1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in ZX1 drops below set limit."
|
||
|
::= { cpiSpecific 9 }
|
||
|
|
||
|
minCurrentxy2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentxy2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in XY2 drops below set limit."
|
||
|
::= { cpiSpecific 10 }
|
||
|
|
||
|
minCurrentyz2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentyz2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in YZ2 drops below set limit."
|
||
|
::= { cpiSpecific 11 }
|
||
|
|
||
|
minCurrentzx2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, currentzx2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when current in ZX2 drops below set limit."
|
||
|
::= { cpiSpecific 12 }
|
||
|
|
||
|
maxVoltxy1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagexy1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in XY1 exceeds high limit."
|
||
|
::= { cpiSpecific 13 }
|
||
|
|
||
|
maxVoltyz1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltageyz1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in YZ1 exceeds high limit."
|
||
|
::= { cpiSpecific 14 }
|
||
|
|
||
|
maxVoltzx1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagezx1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in ZX1 exceeds high limit."
|
||
|
::= { cpiSpecific 15 }
|
||
|
|
||
|
maxVoltxy2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagexy2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in XY2 exceeds high limit."
|
||
|
::= { cpiSpecific 16 }
|
||
|
|
||
|
maxVoltyz2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltageyz2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in YZ2 exceeds high limit."
|
||
|
::= { cpiSpecific 17 }
|
||
|
|
||
|
maxVoltzx2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagezx2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in ZX2 exceeds high limit."
|
||
|
::= { cpiSpecific 18 }
|
||
|
|
||
|
minVoltxy1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagexy1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in XY1 drops below low limit."
|
||
|
::= { cpiSpecific 19 }
|
||
|
|
||
|
minVoltyz1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltageyz1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in YZ1 drops below low limit."
|
||
|
::= { cpiSpecific 20 }
|
||
|
|
||
|
minVoltzx1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagezx1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in ZX1 drops below low limit."
|
||
|
::= { cpiSpecific 21 }
|
||
|
|
||
|
minVoltxy2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagexy2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in XY2 drops below low limit."
|
||
|
::= { cpiSpecific 22 }
|
||
|
|
||
|
minVoltyz2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltageyz2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in YZ2 drops below low limit."
|
||
|
::= { cpiSpecific 23 }
|
||
|
|
||
|
minVoltzx2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, voltagezx2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when voltage in ZX2 drops below low limit."
|
||
|
::= { cpiSpecific 24 }
|
||
|
|
||
|
maxTemperature1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, temperatureProbe1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when temperature exceeds high limit."
|
||
|
::= { cpiSpecific 25 }
|
||
|
|
||
|
maxTemperature2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, temperatureProbe2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when temperature exceeds high limit."
|
||
|
::= { cpiSpecific 26 }
|
||
|
|
||
|
minTemperature1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, temperatureProbe1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when temperature drops below low limit."
|
||
|
::= { cpiSpecific 27 }
|
||
|
|
||
|
minTemperature2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, temperatureProbe2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when temperature drops below low limit."
|
||
|
::= { cpiSpecific 28 }
|
||
|
|
||
|
maxHumidity1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, humidityProbe1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when humidity exceeds high limit."
|
||
|
::= { cpiSpecific 29 }
|
||
|
|
||
|
maxHumidity2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, humidityProbe2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when humidity exceeds high limit."
|
||
|
::= { cpiSpecific 30 }
|
||
|
|
||
|
minHumidity1 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, humidityProbe1 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when humidity drops below low limit."
|
||
|
::= { cpiSpecific 31 }
|
||
|
|
||
|
minHumidity2 NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect, humidityProbe2 }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when humidity drops below low limit."
|
||
|
::= { cpiSpecific 32 }
|
||
|
|
||
|
changeLog NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect,
|
||
|
voltagexy1,
|
||
|
voltageyz1,
|
||
|
voltagezx1,
|
||
|
voltagexy2,
|
||
|
voltageyz2,
|
||
|
voltagezx2,
|
||
|
currentxy1,
|
||
|
currentyz1,
|
||
|
currentzx1,
|
||
|
currentxy2,
|
||
|
currentyz2,
|
||
|
currentzx2,
|
||
|
receptacleCurrentMap,
|
||
|
receptacleCtrlMap,
|
||
|
temperatureProbe1,
|
||
|
humidityProbe1,
|
||
|
temperatureProbe2,
|
||
|
humidityProbe2,
|
||
|
alarmsMaxMap,
|
||
|
alarmsMinMap,
|
||
|
alarmsWarnHiMap,
|
||
|
alarmsWarnLoMap,
|
||
|
recep1To32AlarmsMaxMap,
|
||
|
recep1To32AlarmsMinMap,
|
||
|
recep1To32WarnHiMap,
|
||
|
recep1To32WarnLoMap
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when changes in current exceed the amount set in LOGDIFFERENCE."
|
||
|
::= { cpiSpecific 33 }
|
||
|
|
||
|
dataLog NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect,
|
||
|
voltagexy1,
|
||
|
voltageyz1,
|
||
|
voltagezx1,
|
||
|
voltagexy2,
|
||
|
voltageyz2,
|
||
|
voltagezx2,
|
||
|
currentxy1,
|
||
|
currentyz1,
|
||
|
currentzx1,
|
||
|
currentxy2,
|
||
|
currentyz2,
|
||
|
currentzx2,
|
||
|
receptacleCurrentMap,
|
||
|
receptacleCtrlMap,
|
||
|
temperatureProbe1,
|
||
|
humidityProbe1,
|
||
|
temperatureProbe2,
|
||
|
humidityProbe2,
|
||
|
alarmsMaxMap,
|
||
|
alarmsMinMap,
|
||
|
alarmsWarnHiMap,
|
||
|
alarmsWarnLoMap,
|
||
|
recep1To32AlarmsMaxMap,
|
||
|
recep1To32AlarmsMinMap,
|
||
|
recep1To32WarnHiMap,
|
||
|
recep1To32WarnLoMap
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when the data logging interval time is reached"
|
||
|
::= { cpiSpecific 34 }
|
||
|
|
||
|
alarmChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduSelect,
|
||
|
alarmsMaxMap,
|
||
|
alarmsMinMap,
|
||
|
alarmsWarnHiMap,
|
||
|
alarmsWarnLoMap,
|
||
|
recep1To32AlarmsMaxMap,
|
||
|
recep1To32AlarmsMinMap,
|
||
|
recep1To32WarnHiMap,
|
||
|
recep1To32WarnLoMap
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Trap is sent when all alarms have been resolved/cleared"
|
||
|
::= { cpiSpecific 35 }
|
||
|
|
||
|
-- conformance information
|
||
|
|
||
|
cpiMIBConformance OBJECT IDENTIFIER ::= { products 2 }
|
||
|
|
||
|
cpiMIBCompliances OBJECT IDENTIFIER ::= { cpiMIBConformance 1 }
|
||
|
|
||
|
cpiMIBGroups OBJECT IDENTIFIER ::= { cpiMIBConformance 2 }
|
||
|
|
||
|
cpiMIBComplianceRev1 MODULE-COMPLIANCE
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The compliance statement for this MIB."
|
||
|
MODULE -- this module
|
||
|
MANDATORY-GROUPS {
|
||
|
cpiMIBGroupsObjects,
|
||
|
cpiMIBGroupNotifications
|
||
|
}
|
||
|
::= { cpiMIBCompliances 1 }
|
||
|
|
||
|
-- units of conformance
|
||
|
|
||
|
cpiMIBGroupsObjects OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
version,
|
||
|
modelCode,
|
||
|
hwAddress,
|
||
|
logInterval,
|
||
|
alarmInterval,
|
||
|
logDifference,
|
||
|
pduIP,
|
||
|
autoIP,
|
||
|
autoDNS,
|
||
|
ipV4Enable,
|
||
|
snmpEnable,
|
||
|
telnetEnable,
|
||
|
sshEnable,
|
||
|
httpEnable,
|
||
|
httpsEnable,
|
||
|
subnetMask,
|
||
|
gateway,
|
||
|
dns1,
|
||
|
dns2,
|
||
|
dns3,
|
||
|
snmpHost1,
|
||
|
snmpHost2,
|
||
|
snmpHost3,
|
||
|
pduIPv6,
|
||
|
autoIPv6,
|
||
|
autoDNSIPv6,
|
||
|
ipv6Enable,
|
||
|
linkLocalEnable,
|
||
|
globalAddrEnable,
|
||
|
subnetMaskIPv6,
|
||
|
gatewayIPv6,
|
||
|
dns1IPv6,
|
||
|
dns2IPv6,
|
||
|
dns3IPv6,
|
||
|
snmpHost1IPv6,
|
||
|
snmpHost2IPv6,
|
||
|
snmpHost3IPv6,
|
||
|
outlet1Ctrl,
|
||
|
outlet2Ctrl,
|
||
|
outlet3Ctrl,
|
||
|
outlet4Ctrl,
|
||
|
outlet5Ctrl,
|
||
|
outlet6Ctrl,
|
||
|
outlet7Ctrl,
|
||
|
outlet8Ctrl,
|
||
|
outlet9Ctrl,
|
||
|
outlet10Ctrl,
|
||
|
outlet11Ctrl,
|
||
|
outlet12Ctrl,
|
||
|
outlet13Ctrl,
|
||
|
outlet14Ctrl,
|
||
|
outlet15Ctrl,
|
||
|
outlet16Ctrl,
|
||
|
outlet17Ctrl,
|
||
|
outlet18Ctrl,
|
||
|
outlet19Ctrl,
|
||
|
outlet20Ctrl,
|
||
|
outlet21Ctrl,
|
||
|
outlet22Ctrl,
|
||
|
outlet23Ctrl,
|
||
|
outlet24Ctrl,
|
||
|
outlet1ONdly,
|
||
|
outlet2ONdly,
|
||
|
outlet3ONdly,
|
||
|
outlet4ONdly,
|
||
|
outlet5ONdly,
|
||
|
outlet6ONdly,
|
||
|
outlet7ONdly,
|
||
|
outlet8ONdly,
|
||
|
outlet9ONdly,
|
||
|
outlet10ONdly,
|
||
|
outlet11ONdly,
|
||
|
outlet12ONdly,
|
||
|
outlet13ONdly,
|
||
|
outlet14ONdly,
|
||
|
outlet15ONdly,
|
||
|
outlet16ONdly,
|
||
|
outlet17ONdly,
|
||
|
outlet18ONdly,
|
||
|
outlet19ONdly,
|
||
|
outlet20ONdly,
|
||
|
outlet21ONdly,
|
||
|
outlet22ONdly,
|
||
|
outlet23ONdly,
|
||
|
outlet24ONdly,
|
||
|
outlet1RESdly,
|
||
|
outlet2RESdly,
|
||
|
outlet3RESdly,
|
||
|
outlet4RESdly,
|
||
|
outlet5RESdly,
|
||
|
outlet6RESdly,
|
||
|
outlet7RESdly,
|
||
|
outlet8RESdly,
|
||
|
outlet9RESdly,
|
||
|
outlet10RESdly,
|
||
|
outlet11RESdly,
|
||
|
outlet12RESdly,
|
||
|
outlet13RESdly,
|
||
|
outlet14RESdly,
|
||
|
outlet15RESdly,
|
||
|
outlet16RESdly,
|
||
|
outlet17RESdly,
|
||
|
outlet18RESdly,
|
||
|
outlet19RESdly,
|
||
|
outlet20RESdly,
|
||
|
outlet21RESdly,
|
||
|
outlet22RESdly,
|
||
|
outlet23RESdly,
|
||
|
outlet24RESdly,
|
||
|
xy1MaxCurr,
|
||
|
yz1MaxCurr,
|
||
|
zx1MaxCurr,
|
||
|
xy2MaxCurr,
|
||
|
yz2MaxCurr,
|
||
|
zx2MaxCurr,
|
||
|
xy1MinCurr,
|
||
|
yz1MinCurr,
|
||
|
zx1MinCurr,
|
||
|
xy2MinCurr,
|
||
|
yz2MinCurr,
|
||
|
zx2MinCurr,
|
||
|
xy1WarnHiCurr,
|
||
|
yz1WarnHiCurr,
|
||
|
zx1WarnHiCurr,
|
||
|
xy2WarnHiCurr,
|
||
|
yz2WarnHiCurr,
|
||
|
zx2WarnHiCurr,
|
||
|
xy1WarnLoCurr,
|
||
|
yz1WarnLoCurr,
|
||
|
zx1WarnLoCurr,
|
||
|
xy2WarnLoCurr,
|
||
|
yz2WarnLoCurr,
|
||
|
zx2WarnLoCurr,
|
||
|
xy1MaxVolt,
|
||
|
yz1MaxVolt,
|
||
|
zx1MaxVolt,
|
||
|
xy2MaxVolt,
|
||
|
yz2MaxVolt,
|
||
|
zx2MaxVolt,
|
||
|
xy1MinVolt,
|
||
|
yz1MinVolt,
|
||
|
zx1MinVolt,
|
||
|
xy2MinVolt,
|
||
|
yz2MinVolt,
|
||
|
zx2MinVolt,
|
||
|
xy1WarnHiVolt,
|
||
|
yz1WarnHiVolt,
|
||
|
zx1WarnHiVolt,
|
||
|
xy2WarnHiVolt,
|
||
|
yz2WarnHiVolt,
|
||
|
zx2WarnHiVolt,
|
||
|
xy1WarnLoVolt,
|
||
|
yz1WarnLoVolt,
|
||
|
zx1WarnLoVolt,
|
||
|
xy2WarnLoVolt,
|
||
|
yz2WarnLoVolt,
|
||
|
zx2WarnLoVolt,
|
||
|
outlet1MaxCurr,
|
||
|
outlet2MaxCurr,
|
||
|
outlet3MaxCurr,
|
||
|
outlet4MaxCurr,
|
||
|
outlet5MaxCurr,
|
||
|
outlet6MaxCurr,
|
||
|
outlet7MaxCurr,
|
||
|
outlet8MaxCurr,
|
||
|
outlet9MaxCurr,
|
||
|
outlet10MaxCurr,
|
||
|
outlet11MaxCurr,
|
||
|
outlet12MaxCurr,
|
||
|
outlet13MaxCurr,
|
||
|
outlet14MaxCurr,
|
||
|
outlet15MaxCurr,
|
||
|
outlet16MaxCurr,
|
||
|
outlet17MaxCurr,
|
||
|
outlet18MaxCurr,
|
||
|
outlet19MaxCurr,
|
||
|
outlet20MaxCurr,
|
||
|
outlet21MaxCurr,
|
||
|
outlet22MaxCurr,
|
||
|
outlet23MaxCurr,
|
||
|
outlet24MaxCurr,
|
||
|
outlet1MinCurr,
|
||
|
outlet2MinCurr,
|
||
|
outlet3MinCurr,
|
||
|
outlet4MinCurr,
|
||
|
outlet5MinCurr,
|
||
|
outlet6MinCurr,
|
||
|
outlet7MinCurr,
|
||
|
outlet8MinCurr,
|
||
|
outlet9MinCurr,
|
||
|
outlet10MinCurr,
|
||
|
outlet11MinCurr,
|
||
|
outlet12MinCurr,
|
||
|
outlet13MinCurr,
|
||
|
outlet14MinCurr,
|
||
|
outlet15MinCurr,
|
||
|
outlet16MinCurr,
|
||
|
outlet17MinCurr,
|
||
|
outlet18MinCurr,
|
||
|
outlet19MinCurr,
|
||
|
outlet20MinCurr,
|
||
|
outlet21MinCurr,
|
||
|
outlet22MinCurr,
|
||
|
outlet23MinCurr,
|
||
|
outlet24MinCurr,
|
||
|
outlet1WarnHiCurr,
|
||
|
outlet2WarnHiCurr,
|
||
|
outlet3WarnHiCurr,
|
||
|
outlet4WarnHiCurr,
|
||
|
outlet5WarnHiCurr,
|
||
|
outlet6WarnHiCurr,
|
||
|
outlet7WarnHiCurr,
|
||
|
outlet8WarnHiCurr,
|
||
|
outlet9WarnHiCurr,
|
||
|
outlet10WarnHiCurr,
|
||
|
outlet11WarnHiCurr,
|
||
|
outlet12WarnHiCurr,
|
||
|
outlet13WarnHiCurr,
|
||
|
outlet14WarnHiCurr,
|
||
|
outlet15WarnHiCurr,
|
||
|
outlet16WarnHiCurr,
|
||
|
outlet17WarnHiCurr,
|
||
|
outlet18WarnHiCurr,
|
||
|
outlet19WarnHiCurr,
|
||
|
outlet20WarnHiCurr,
|
||
|
outlet21WarnHiCurr,
|
||
|
outlet22WarnHiCurr,
|
||
|
outlet23WarnHiCurr,
|
||
|
outlet24WarnHiCurr,
|
||
|
outlet1WarnLoCurr,
|
||
|
outlet2WarnLoCurr,
|
||
|
outlet3WarnLoCurr,
|
||
|
outlet4WarnLoCurr,
|
||
|
outlet5WarnLoCurr,
|
||
|
outlet6WarnLoCurr,
|
||
|
outlet7WarnLoCurr,
|
||
|
outlet8WarnLoCurr,
|
||
|
outlet9WarnLoCurr,
|
||
|
outlet10WarnLoCurr,
|
||
|
outlet11WarnLoCurr,
|
||
|
outlet12WarnLoCurr,
|
||
|
outlet13WarnLoCurr,
|
||
|
outlet14WarnLoCurr,
|
||
|
outlet15WarnLoCurr,
|
||
|
outlet16WarnLoCurr,
|
||
|
outlet17WarnLoCurr,
|
||
|
outlet18WarnLoCurr,
|
||
|
outlet19WarnLoCurr,
|
||
|
outlet20WarnLoCurr,
|
||
|
outlet21WarnLoCurr,
|
||
|
outlet22WarnLoCurr,
|
||
|
outlet23WarnLoCurr,
|
||
|
outlet24WarnLoCurr,
|
||
|
maxTempProbe1,
|
||
|
maxTempProbe2,
|
||
|
minTempProbe1,
|
||
|
minTempProbe2,
|
||
|
warnHiTempProbe1,
|
||
|
warnHiTempProbe2,
|
||
|
warnLoTempProbe1,
|
||
|
warnLoTempProbe2,
|
||
|
maxHumidProbe1,
|
||
|
maxHumidProbe2,
|
||
|
minHumidProbe1,
|
||
|
minHumidProbe2,
|
||
|
warnHiHumidProbe1,
|
||
|
warnHiHumidProbe2,
|
||
|
warnLoHumidProbe1,
|
||
|
warnLoHumidProbe2,
|
||
|
pduName,
|
||
|
pduDescrip,
|
||
|
outlet1Name,
|
||
|
outlet2Name,
|
||
|
outlet3Name,
|
||
|
outlet4Name,
|
||
|
outlet5Name,
|
||
|
outlet6Name,
|
||
|
outlet7Name,
|
||
|
outlet8Name,
|
||
|
outlet9Name,
|
||
|
outlet10Name,
|
||
|
outlet11Name,
|
||
|
outlet12Name,
|
||
|
outlet13Name,
|
||
|
outlet14Name,
|
||
|
outlet15Name,
|
||
|
outlet16Name,
|
||
|
outlet17Name,
|
||
|
outlet18Name,
|
||
|
outlet19Name,
|
||
|
outlet20Name,
|
||
|
outlet21Name,
|
||
|
outlet22Name,
|
||
|
outlet23Name,
|
||
|
outlet24Name,
|
||
|
outlet1Descrip,
|
||
|
outlet2Descrip,
|
||
|
outlet3Descrip,
|
||
|
outlet4Descrip,
|
||
|
outlet5Descrip,
|
||
|
outlet6Descrip,
|
||
|
outlet7Descrip,
|
||
|
outlet8Descrip,
|
||
|
outlet9Descrip,
|
||
|
outlet10Descrip,
|
||
|
outlet11Descrip,
|
||
|
outlet12Descrip,
|
||
|
outlet13Descrip,
|
||
|
outlet14Descrip,
|
||
|
outlet15Descrip,
|
||
|
outlet16Descrip,
|
||
|
outlet17Descrip,
|
||
|
outlet18Descrip,
|
||
|
outlet19Descrip,
|
||
|
outlet20Descrip,
|
||
|
outlet21Descrip,
|
||
|
outlet22Descrip,
|
||
|
outlet23Descrip,
|
||
|
outlet24Descrip,
|
||
|
group1Name,
|
||
|
group2Name,
|
||
|
group3Name,
|
||
|
group4Name,
|
||
|
group5Name,
|
||
|
group6Name,
|
||
|
group7Name,
|
||
|
group8Name,
|
||
|
group9Name,
|
||
|
group10Name,
|
||
|
group11Name,
|
||
|
group12Name,
|
||
|
group13Name,
|
||
|
group14Name,
|
||
|
group15Name,
|
||
|
group16Name,
|
||
|
group1Map,
|
||
|
group2Map,
|
||
|
group3Map,
|
||
|
group4Map,
|
||
|
group5Map,
|
||
|
group6Map,
|
||
|
group7Map,
|
||
|
group8Map,
|
||
|
group9Map,
|
||
|
group10Map,
|
||
|
group11Map,
|
||
|
group12Map,
|
||
|
group13Map,
|
||
|
group14Map,
|
||
|
group15Map,
|
||
|
group16Map,
|
||
|
dispTimeout,
|
||
|
loginTimeout,
|
||
|
dispBrightness,
|
||
|
inputTop,
|
||
|
pduRole,
|
||
|
celsiusTemp,
|
||
|
enableWeb,
|
||
|
snmpHostOnly,
|
||
|
disLocalAuth,
|
||
|
enaRadiusAuth,
|
||
|
enaADAuth,
|
||
|
enaSMTP,
|
||
|
pduAltRole,
|
||
|
shareRole,
|
||
|
outOfService,
|
||
|
missingPDUNotify,
|
||
|
roleChangeNotify,
|
||
|
httpPort,
|
||
|
httpsPort,
|
||
|
sshPort,
|
||
|
telnetPort,
|
||
|
snmpQueryPort,
|
||
|
snmpTrapPort,
|
||
|
smtpSendPort,
|
||
|
smtpReceivePort,
|
||
|
rfcTimeServer,
|
||
|
ntpTimeServer,
|
||
|
smtpServer,
|
||
|
snmpReadComm,
|
||
|
snmpWriteComm,
|
||
|
snmpUSMuserName,
|
||
|
snmpSecurityLevel,
|
||
|
snmpAuthAlgo,
|
||
|
snmpPrivAlgo,
|
||
|
snmpAuthPasswd,
|
||
|
snmpPrivPasswd,
|
||
|
snmpContextName,
|
||
|
snmpEngineID,
|
||
|
snmpLocAuthKey,
|
||
|
snmpLocPrivKey,
|
||
|
smtpUserName,
|
||
|
smtpUserPasswd,
|
||
|
smtpEmailAddr,
|
||
|
smtpEmailDestination1,
|
||
|
smtpEmailDestination2,
|
||
|
smtpEmailDestination3,
|
||
|
smtpServOptions,
|
||
|
radiusServer,
|
||
|
radiusSHSecret,
|
||
|
radiusNASServer,
|
||
|
radiusPort,
|
||
|
nasPort,
|
||
|
adServer,
|
||
|
adDomain,
|
||
|
adPort,
|
||
|
adResvPort,
|
||
|
probe1Name,
|
||
|
probe2Name,
|
||
|
dLogEnable,
|
||
|
netservdLog,
|
||
|
autonetLog,
|
||
|
stdmeterdLog,
|
||
|
groupmeterdLog,
|
||
|
alarmdLog,
|
||
|
userlogindLog,
|
||
|
usersetupdLog,
|
||
|
fwupdatedLog,
|
||
|
setupchangedLog,
|
||
|
recepchangedLog,
|
||
|
pduopchangedLog,
|
||
|
dLogCycle,
|
||
|
dLogFullWarnLevel,
|
||
|
netdLogServer,
|
||
|
netdLogPort,
|
||
|
netdLogUser,
|
||
|
netdLogPasswd,
|
||
|
netdLogDestdir,
|
||
|
netdLogOptions,
|
||
|
snmpTrapHost1,
|
||
|
snmpTrapHost2,
|
||
|
snmpTrapHost3,
|
||
|
snmpTrapHost1IPv6,
|
||
|
snmpTrapHost2IPv6,
|
||
|
snmpTrapHost3IPv6,
|
||
|
lnkAttachCount,
|
||
|
currentxy1,
|
||
|
currentyz1,
|
||
|
currentzx1,
|
||
|
currentxy2,
|
||
|
currentyz2,
|
||
|
currentzx2,
|
||
|
voltagexy1,
|
||
|
voltageyz1,
|
||
|
voltagezx1,
|
||
|
voltagexy2,
|
||
|
voltageyz2,
|
||
|
voltagezx2,
|
||
|
powerxy1,
|
||
|
poweryz1,
|
||
|
powerzx1,
|
||
|
powerxy2,
|
||
|
poweryz2,
|
||
|
powerzx2,
|
||
|
powerFactxy1,
|
||
|
powerFactyz1,
|
||
|
powerFactzx1,
|
||
|
powerFactxy2,
|
||
|
powerFactyz2,
|
||
|
powerFactzx2,
|
||
|
outlet1Current,
|
||
|
outlet2Current,
|
||
|
outlet3Current,
|
||
|
outlet4Current,
|
||
|
outlet5Current,
|
||
|
outlet6Current,
|
||
|
outlet7Current,
|
||
|
outlet8Current,
|
||
|
outlet9Current,
|
||
|
outlet10Current,
|
||
|
outlet11Current,
|
||
|
outlet12Current,
|
||
|
outlet13Current,
|
||
|
outlet14Current,
|
||
|
outlet15Current,
|
||
|
outlet16Current,
|
||
|
outlet17Current,
|
||
|
outlet18Current,
|
||
|
outlet19Current,
|
||
|
outlet20Current,
|
||
|
outlet21Current,
|
||
|
outlet22Current,
|
||
|
outlet23Current,
|
||
|
outlet24Current,
|
||
|
receptacleCurrentMap,
|
||
|
outlet1State,
|
||
|
outlet2State,
|
||
|
outlet3State,
|
||
|
outlet4State,
|
||
|
outlet5State,
|
||
|
outlet6State,
|
||
|
outlet7State,
|
||
|
outlet8State,
|
||
|
outlet9State,
|
||
|
outlet10State,
|
||
|
outlet11State,
|
||
|
outlet12State,
|
||
|
outlet13State,
|
||
|
outlet14State,
|
||
|
outlet15State,
|
||
|
outlet16State,
|
||
|
outlet17State,
|
||
|
outlet18State,
|
||
|
outlet19State,
|
||
|
outlet20State,
|
||
|
outlet21State,
|
||
|
outlet22State,
|
||
|
outlet23State,
|
||
|
outlet24State,
|
||
|
temperatureProbe1,
|
||
|
temperatureProbe2,
|
||
|
humidityProbe1,
|
||
|
humidityProbe2,
|
||
|
alarmsMaxMap,
|
||
|
alarmsMinMap,
|
||
|
alarmsWarnHiMap,
|
||
|
alarmsWarnLoMap,
|
||
|
recep1To32AlarmsMaxMap,
|
||
|
recep1To32AlarmsMinMap,
|
||
|
recep1To32WarnHiMap,
|
||
|
recep1To32WarnLoMap,
|
||
|
energyxy1s,
|
||
|
energyyz1s,
|
||
|
energyzx1s,
|
||
|
energyxy2s,
|
||
|
energyyz2s,
|
||
|
energyzx2s,
|
||
|
receptacleEnergyoutlet1s,
|
||
|
receptacleEnergyoutlet2s,
|
||
|
receptacleEnergyoutlet3s,
|
||
|
receptacleEnergyoutlet4s,
|
||
|
receptacleEnergyoutlet5s,
|
||
|
receptacleEnergyoutlet6s,
|
||
|
receptacleEnergyoutlet7s,
|
||
|
receptacleEnergyoutlet8s,
|
||
|
receptacleEnergyoutlet9s,
|
||
|
receptacleEnergyoutlet10s,
|
||
|
receptacleEnergyoutlet11s,
|
||
|
receptacleEnergyoutlet12s,
|
||
|
receptacleEnergyoutlet13s,
|
||
|
receptacleEnergyoutlet14s,
|
||
|
receptacleEnergyoutlet15s,
|
||
|
receptacleEnergyoutlet16s,
|
||
|
receptacleEnergyoutlet17s,
|
||
|
receptacleEnergyoutlet18s,
|
||
|
receptacleEnergyoutlet19s,
|
||
|
receptacleEnergyoutlet20s,
|
||
|
receptacleEnergyoutlet21s,
|
||
|
receptacleEnergyoutlet22s,
|
||
|
receptacleEnergyoutlet23s,
|
||
|
receptacleEnergyoutlet24s,
|
||
|
line1curr,
|
||
|
line2curr,
|
||
|
line3curr,
|
||
|
outlet1ONOFF,
|
||
|
outlet2ONOFF,
|
||
|
outlet3ONOFF,
|
||
|
outlet4ONOFF,
|
||
|
outlet5ONOFF,
|
||
|
outlet6ONOFF,
|
||
|
outlet7ONOFF,
|
||
|
outlet8ONOFF,
|
||
|
outlet9ONOFF,
|
||
|
outlet10ONOFF,
|
||
|
outlet11ONOFF,
|
||
|
outlet12ONOFF,
|
||
|
outlet13ONOFF,
|
||
|
outlet14ONOFF,
|
||
|
outlet15ONOFF,
|
||
|
outlet16ONOFF,
|
||
|
outlet17ONOFF,
|
||
|
outlet18ONOFF,
|
||
|
outlet19ONOFF,
|
||
|
outlet20ONOFF,
|
||
|
outlet21ONOFF,
|
||
|
outlet22ONOFF,
|
||
|
outlet23ONOFF,
|
||
|
outlet24ONOFF,
|
||
|
outlet1Reset,
|
||
|
outlet2Reset,
|
||
|
outlet3Reset,
|
||
|
outlet4Reset,
|
||
|
outlet5Reset,
|
||
|
outlet6Reset,
|
||
|
outlet7Reset,
|
||
|
outlet8Reset,
|
||
|
outlet9Reset,
|
||
|
outlet10Reset,
|
||
|
outlet11Reset,
|
||
|
outlet12Reset,
|
||
|
outlet13Reset,
|
||
|
outlet14Reset,
|
||
|
outlet15Reset,
|
||
|
outlet16Reset,
|
||
|
outlet17Reset,
|
||
|
outlet18Reset,
|
||
|
outlet19Reset,
|
||
|
outlet20Reset,
|
||
|
outlet21Reset,
|
||
|
outlet22Reset,
|
||
|
outlet23Reset,
|
||
|
outlet24Reset,
|
||
|
receptacleCtrlMap,
|
||
|
pduCount,
|
||
|
pduMap,
|
||
|
pduSelect,
|
||
|
pduNamelist
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A collection of objects for managing the PDU."
|
||
|
::= { cpiMIBGroups 1 }
|
||
|
|
||
|
cpiMIBGroupNotifications NOTIFICATION-GROUP
|
||
|
NOTIFICATIONS {
|
||
|
maxCurrentxy1,
|
||
|
maxCurrentyz1,
|
||
|
maxCurrentzx1,
|
||
|
maxCurrentxy2,
|
||
|
maxCurrentyz2,
|
||
|
maxCurrentzx2,
|
||
|
minCurrentxy1,
|
||
|
minCurrentyz1,
|
||
|
minCurrentzx1,
|
||
|
minCurrentxy2,
|
||
|
minCurrentyz2,
|
||
|
minCurrentzx2,
|
||
|
maxVoltxy1,
|
||
|
maxVoltyz1,
|
||
|
maxVoltzx1,
|
||
|
maxVoltxy2,
|
||
|
maxVoltyz2,
|
||
|
maxVoltzx2,
|
||
|
minVoltxy1,
|
||
|
minVoltyz1,
|
||
|
minVoltzx1,
|
||
|
minVoltxy2,
|
||
|
minVoltyz2,
|
||
|
minVoltzx2,
|
||
|
maxTemperature1,
|
||
|
maxTemperature2,
|
||
|
minTemperature1,
|
||
|
minTemperature2,
|
||
|
maxHumidity1,
|
||
|
maxHumidity2,
|
||
|
minHumidity1,
|
||
|
minHumidity2,
|
||
|
changeLog,
|
||
|
dataLog
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A collection of notifications supported by PDU."
|
||
|
::= { cpiMIBGroups 2 }
|
||
|
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
--
|
||
|
-- UNITY MIBS Below
|
||
|
--
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
-- ######################################################################
|
||
|
unity OBJECT IDENTIFIER ::= { products 10 }
|
||
|
|
||
|
econnect OBJECT IDENTIFIER ::= { unity 1 }
|
||
|
|
||
|
configuration OBJECT IDENTIFIER ::= { econnect 1 }
|
||
|
|
||
|
network OBJECT IDENTIFIER ::= { configuration 1 }
|
||
|
|
||
|
ipv4 OBJECT IDENTIFIER ::= { network 1 }
|
||
|
|
||
|
ipV4Enable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv4 network interface is enabled."
|
||
|
::= { ipv4 1 }
|
||
|
|
||
|
pduIP OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the PDU."
|
||
|
::= { ipv4 2 }
|
||
|
|
||
|
autoIP OBJECT-TYPE
|
||
|
SYNTAX INTEGER { static(0), dynamic(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv4 address is retrieved from a
|
||
|
DHCP server or is set statically."
|
||
|
::= { ipv4 3 }
|
||
|
|
||
|
autoDNS OBJECT-TYPE
|
||
|
SYNTAX INTEGER { static(0), dynamic(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the DNS addresses are retrieved from
|
||
|
a DHCP server or are set statically."
|
||
|
::= { ipv4 4 }
|
||
|
|
||
|
subnetMask OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The subnet mask associated with the IPv4 address of this
|
||
|
entry. The value of the mask is an IPv4 address with all the
|
||
|
network bits set to 1 and all the hosts bits set to 0."
|
||
|
::= { ipv4 5 }
|
||
|
|
||
|
gateway OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the gateway router for the PDU."
|
||
|
::= { ipv4 6 }
|
||
|
|
||
|
dns1 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the first DNS entry for the PDU."
|
||
|
::= { ipv4 7 }
|
||
|
|
||
|
dns2 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the second DNS entry for the PDU."
|
||
|
::= { ipv4 8 }
|
||
|
|
||
|
dns3 OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the third DNS entry for the PDU."
|
||
|
::= { ipv4 9 }
|
||
|
|
||
|
ipv6 OBJECT IDENTIFIER ::= { network 2 }
|
||
|
|
||
|
ipV6Enable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv6 network interface is enabled."
|
||
|
::= { ipv6 1 }
|
||
|
|
||
|
linkLocalEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv6 link-local address is enabled."
|
||
|
::= { ipv6 2 }
|
||
|
|
||
|
globalAddrEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv6 global address is enabled."
|
||
|
::= { ipv6 3 }
|
||
|
|
||
|
pduIPv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the PDU."
|
||
|
::= { ipv6 4 }
|
||
|
|
||
|
autoIPv6 OBJECT-TYPE
|
||
|
SYNTAX INTEGER { static(0), dynamic(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the IPv6 address is retrieved from a
|
||
|
DHCP server or is set statically."
|
||
|
::= { ipv6 5 }
|
||
|
|
||
|
autoDNSv6 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..1)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the DNS IPv6 address is retrieved from a
|
||
|
DHCP server or is set statically."
|
||
|
::= { ipv6 6 }
|
||
|
|
||
|
subnetMaskv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The subnet mask associated with the IPv6 address of this
|
||
|
entry. The value of the mask is an IPv6 address with all the
|
||
|
network bits set to 1 and all the hosts bits set to 0."
|
||
|
::= { ipv6 7 }
|
||
|
|
||
|
gatewayv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the gateway router for the PDU."
|
||
|
::= { ipv6 8 }
|
||
|
|
||
|
dns1v6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the first DNS entry for the PDU."
|
||
|
::= { ipv6 9 }
|
||
|
|
||
|
dns2v6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the second DNS entry for the PDU."
|
||
|
::= { ipv6 10 }
|
||
|
|
||
|
dns3v6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the third DNS entry for the PDU."
|
||
|
::= { ipv6 11 }
|
||
|
|
||
|
time OBJECT IDENTIFIER ::= { network 3 }
|
||
|
|
||
|
rfcTimeServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the RFC Time Server."
|
||
|
::= { time 1 }
|
||
|
|
||
|
ntpTimeServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the NTP Time Server."
|
||
|
::= { time 2 }
|
||
|
|
||
|
interfaces OBJECT IDENTIFIER ::= { configuration 2 }
|
||
|
|
||
|
snmp OBJECT IDENTIFIER ::= { interfaces 1 }
|
||
|
|
||
|
snmpEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the SNMP network service is enabled."
|
||
|
::= { snmp 1 }
|
||
|
|
||
|
snmpHosts OBJECT IDENTIFIER ::= { snmp 2 }
|
||
|
|
||
|
snmpHostOnly OBJECT-TYPE
|
||
|
SYNTAX INTEGER { any(0), listed(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether access to the SNMP service responsed to
|
||
|
the listed hosts (snmpHost1, snmpHost2, snmpHost3) or
|
||
|
to any host requesting data."
|
||
|
::= { snmpHosts 1 }
|
||
|
|
||
|
snmpHost1 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the first host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 2 }
|
||
|
|
||
|
snmpHost2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the second host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 3 }
|
||
|
|
||
|
snmpHost3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the third host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 4 }
|
||
|
|
||
|
snmpHostIPv61 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the first host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 5 }
|
||
|
|
||
|
snmpHostIPv62 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the first host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 6 }
|
||
|
|
||
|
snmpHostIPV63 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the first host the SNMP service
|
||
|
will reply to."
|
||
|
::= { snmpHosts 7 }
|
||
|
|
||
|
snmpQueryPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for SNMP query access."
|
||
|
::= { snmp 3 }
|
||
|
|
||
|
snmpTrapPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for SNMP traps."
|
||
|
::= { snmp 4 }
|
||
|
|
||
|
snmpReadComm OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Read Community."
|
||
|
::= { snmp 5 }
|
||
|
|
||
|
snmpWriteComm OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Write Community."
|
||
|
::= { snmp 6 }
|
||
|
|
||
|
snmpUSMuserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP USM User Name."
|
||
|
::= { snmp 7 }
|
||
|
|
||
|
snmpSecurityLevel OBJECT-TYPE
|
||
|
SYNTAX INTEGER { v1(0), v2c(1), v3(2), v3Auth(3), v3AuthPriv(4) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the security Level for SNMP: 0 = v1, 1 = v2c, 2 = v3 no authentication,
|
||
|
3 = v3 with authentication only, 4 = v3 with authentication and privacy"
|
||
|
::= { snmp 8 }
|
||
|
|
||
|
snmpAuthAlgo OBJECT-TYPE
|
||
|
SYNTAX INTEGER { sha(0), md5(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the Authentication Algorithm for SNMP."
|
||
|
::= { snmp 9 }
|
||
|
|
||
|
snmpPrivAlgo OBJECT-TYPE
|
||
|
SYNTAX INTEGER { des(0), aes(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or get the Privacy Algorithm for SNMP."
|
||
|
::= { snmp 10 }
|
||
|
|
||
|
snmpAuthPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or Get the SNMP Authentication Password."
|
||
|
::= { snmp 11 }
|
||
|
|
||
|
snmpPrivPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Privacy Password."
|
||
|
::= { snmp 12 }
|
||
|
|
||
|
snmpContextName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Context Name."
|
||
|
::= { snmp 13 }
|
||
|
|
||
|
snmpEngineID OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Engine ID."
|
||
|
::= { snmp 14 }
|
||
|
|
||
|
snmpLocAuthKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Local Authentication Key."
|
||
|
::= { snmp 15 }
|
||
|
|
||
|
snmpLocPrivKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SNMP Local Privacy Key."
|
||
|
::= { snmp 16 }
|
||
|
|
||
|
snmpTrapHosts OBJECT IDENTIFIER ::= { snmp 17 }
|
||
|
|
||
|
snmpTrapHost1 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the first SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 1 }
|
||
|
|
||
|
snmpTrapHost2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the second SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 2 }
|
||
|
|
||
|
snmpTrapHost3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv4 address of the third SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 3 }
|
||
|
|
||
|
snmpTrapHostIPv61 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the first SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 4 }
|
||
|
|
||
|
snmpTrapHostIPv62 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the second SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 5 }
|
||
|
|
||
|
snmpTrapHostIPv63 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IPv6 address of the third SNMP Trap Host."
|
||
|
::= { snmpTrapHosts 6 }
|
||
|
|
||
|
snmpControl OBJECT IDENTIFIER ::= { snmp 18 }
|
||
|
|
||
|
enableEASSNMPControl OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Allows the use of SNMP to open/close the door locks. It is recommended that this only be enabled with SNMP v3 configurations."
|
||
|
::= { snmpControl 5 }
|
||
|
|
||
|
http OBJECT IDENTIFIER ::= { interfaces 2 }
|
||
|
|
||
|
enableWeb OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the web interface is enabled."
|
||
|
::= { http 1 }
|
||
|
|
||
|
httpEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the HTTP service is enabled."
|
||
|
::= { http 2 }
|
||
|
|
||
|
httpsEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the HTTPS service is enabled."
|
||
|
::= { http 3 }
|
||
|
|
||
|
httpPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for unsecure HTTP access."
|
||
|
::= { http 4 }
|
||
|
|
||
|
httpsPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for secure HTTPS access."
|
||
|
::= { http 5 }
|
||
|
|
||
|
smtp OBJECT IDENTIFIER ::= { interfaces 3 }
|
||
|
|
||
|
enableSMTP OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the mail notification service is enabled.."
|
||
|
::= { smtp 1 }
|
||
|
|
||
|
smtpSendPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for SMTP send."
|
||
|
::= { smtp 2 }
|
||
|
|
||
|
smtpReceivePort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for SMTP Receive."
|
||
|
::= { smtp 3 }
|
||
|
|
||
|
smtpServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the e-mail server."
|
||
|
::= { smtp 4 }
|
||
|
|
||
|
smtpUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the PDU e-mail user login name."
|
||
|
::= { smtp 5 }
|
||
|
|
||
|
smtpUserPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the PDU e-mail user login password."
|
||
|
::= { smtp 6 }
|
||
|
|
||
|
smtpEmailAddr OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the PDU e-mail address."
|
||
|
::= { smtp 7 }
|
||
|
|
||
|
smtpEmailDestination1 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the e-mail address of the first recipient."
|
||
|
::= { smtp 8 }
|
||
|
|
||
|
smtpEmailDestination2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the e-mail address of the second recipient."
|
||
|
::= { smtp 9 }
|
||
|
|
||
|
smtpEmailDestination3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the e-mail address of the third recipient."
|
||
|
::= { smtp 10 }
|
||
|
|
||
|
smtpServOptions OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the SMTP server options."
|
||
|
::= { smtp 11 }
|
||
|
|
||
|
logging OBJECT IDENTIFIER ::= { configuration 3 }
|
||
|
|
||
|
logEnable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the data logging feature is enabled."
|
||
|
::= { logging 1 }
|
||
|
|
||
|
logInterval OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the time interval in seconds for logging metrics (disabled if < 10)."
|
||
|
::= { logging 2 }
|
||
|
|
||
|
logDifference OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..2000)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current difference in 1/100 Amps that triggers logging metrics."
|
||
|
::= { logging 3 }
|
||
|
|
||
|
netservdLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls sending the data logs to log server over network."
|
||
|
::= { logging 4 }
|
||
|
|
||
|
autonetLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether automatic transfer to log server every 6 hours is enabled."
|
||
|
::= { logging 5 }
|
||
|
|
||
|
stdmeterdLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether logging of branch, receptacle and environmental metrics is enabled."
|
||
|
::= { logging 6 }
|
||
|
|
||
|
groupmeterdLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether logging of grouped receptacle metrics is enabled."
|
||
|
::= { logging 7 }
|
||
|
|
||
|
alarmdLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether logging of alarm events is enabled."
|
||
|
::= { logging 8 }
|
||
|
|
||
|
userlogindLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether logging of user login events is enabled."
|
||
|
::= { logging 9 }
|
||
|
|
||
|
usersetupdLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether logging of user setup change events is enabled."
|
||
|
::= { logging 10 }
|
||
|
|
||
|
fwupdatedLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether the logging of firmware updates is enabled."
|
||
|
::= { logging 11 }
|
||
|
|
||
|
setupchangedLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether the logging of setup change events is enabled."
|
||
|
::= { logging 12 }
|
||
|
|
||
|
recepchangedLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether logging of receptacle state changes is enabled."
|
||
|
::= { logging 13 }
|
||
|
|
||
|
pduopchangedLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether logging of PDU operation and state changes is enabled."
|
||
|
::= { logging 14 }
|
||
|
|
||
|
dLogCycle OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the time interval in minutes for internal data logging to occur."
|
||
|
::= { logging 15 }
|
||
|
|
||
|
dLogFullWarnLevel OBJECT-TYPE
|
||
|
SYNTAX Integer32 (50..100)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the warning threshold for percentage of storage full (min=50, max=100)."
|
||
|
::= { logging 16 }
|
||
|
|
||
|
netdLogServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the network address for the data server."
|
||
|
::= { logging 17 }
|
||
|
|
||
|
netdLogPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port used by the data server."
|
||
|
::= { logging 18 }
|
||
|
|
||
|
netdLogUser OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user name to access the data server."
|
||
|
::= { logging 19 }
|
||
|
|
||
|
netdLogPasswd OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user password to access the data server."
|
||
|
::= { logging 20 }
|
||
|
|
||
|
netdLogDestdir OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or get the destination directory in the data server."
|
||
|
::= { logging 21 }
|
||
|
|
||
|
netdLogOptions OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or set the options string when accessing the data server."
|
||
|
::= { logging 22 }
|
||
|
|
||
|
sysLogIdentity OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or set the identity to use with the syslog. The identity is an arbitrary identification string which syslog will prefix to each message. This is intended to identify the source of the message."
|
||
|
::= { logging 23 }
|
||
|
|
||
|
sysLogFacility OBJECT-TYPE
|
||
|
SYNTAX INTEGER { loglocal0(0), loglocal1(1), loglocal2(2), loglocal3(3), loglocal4(4), loglocal5(5), loglocal(6), loglocal7(7) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or set the facility to use with the syslog. The facility argument is used to specify what type of program is logging the message."
|
||
|
::= { logging 24 }
|
||
|
|
||
|
sysLogCentralServerAddr OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..64))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or set the IP address for the central syslog server."
|
||
|
::= { logging 25 }
|
||
|
|
||
|
sysLogCentralServerPort OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get or set the port for the central syslog server."
|
||
|
::= { logging 26 }
|
||
|
|
||
|
accesscontrol OBJECT IDENTIFIER ::= { configuration 4 }
|
||
|
|
||
|
ldap OBJECT IDENTIFIER ::= { accesscontrol 1 }
|
||
|
|
||
|
enableADAuth OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether the Active Directory authentication is enabled."
|
||
|
::= { ldap 1 }
|
||
|
|
||
|
adServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Active Directory Server."
|
||
|
::= { ldap 2 }
|
||
|
|
||
|
adDomain OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the Active Directory Domain."
|
||
|
::= { ldap 3 }
|
||
|
|
||
|
adPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Active Directory authentication."
|
||
|
::= { ldap 4 }
|
||
|
|
||
|
adResvPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the alternate or reserved port for Active Directory Authentication."
|
||
|
::= { ldap 5 }
|
||
|
|
||
|
radius OBJECT IDENTIFIER ::= { accesscontrol 2 }
|
||
|
|
||
|
enableRadiusAuth OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether radius authentication is enabled."
|
||
|
::= { radius 1 }
|
||
|
|
||
|
radiusServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Radius Authentication Server."
|
||
|
::= { radius 2 }
|
||
|
|
||
|
radiusSHSecret OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the Radius Shared Secret."
|
||
|
::= { radius 3 }
|
||
|
|
||
|
radiusNASServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the Radius Network Access Service."
|
||
|
::= { radius 4 }
|
||
|
|
||
|
radiusPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for radius authentication."
|
||
|
::= { radius 5 }
|
||
|
|
||
|
nasPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Radius Network Access Service."
|
||
|
::= { radius 6 }
|
||
|
|
||
|
radiusip6 OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable IPv6 for radius authentication."
|
||
|
::= { radius 7 }
|
||
|
|
||
|
radiuscardenable OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable Radius for card authentication."
|
||
|
::= { radius 8 }
|
||
|
|
||
|
cardradiusserver OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Primary Radius Card Authentication Server."
|
||
|
::= { radius 9 }
|
||
|
|
||
|
cardradiusshsecret OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the Radius Card Shared Secret."
|
||
|
::= { radius 10 }
|
||
|
|
||
|
cardradiusPort OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Radius Card Authentication."
|
||
|
::= { radius 11 }
|
||
|
|
||
|
cardradiusip6 OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable IPv6 for Radius Card Authentication."
|
||
|
::= { radius 12 }
|
||
|
|
||
|
radiusServer2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Secondary Radius Authentication Server."
|
||
|
::= { radius 13 }
|
||
|
|
||
|
radiusPort2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Secondary Radius Authentication."
|
||
|
::= { radius 14 }
|
||
|
|
||
|
radiusServer3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Tertiary Radius Authentication Server."
|
||
|
::= { radius 15 }
|
||
|
|
||
|
radiusPort3 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Tertiary Radius Authentication."
|
||
|
::= { radius 16 }
|
||
|
|
||
|
cardradiusServer2 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Secondary Radius Card Authentication Server."
|
||
|
::= { radius 17 }
|
||
|
|
||
|
cardradiusPort2 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Secondary Radius Card Authentication."
|
||
|
::= { radius 18 }
|
||
|
|
||
|
cardradiusServer3 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the IP address of the Tertiary Radius Card Authentication Server."
|
||
|
::= { radius 19 }
|
||
|
|
||
|
cardradiusPort3 OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the port for Tertiary Radius Card Authentication."
|
||
|
::= { radius 20 }
|
||
|
|
||
|
pdu OBJECT IDENTIFIER ::= { configuration 6 }
|
||
|
|
||
|
inputTop OBJECT-TYPE
|
||
|
SYNTAX INTEGER { bottom(0), top(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the input cord entry orientation."
|
||
|
::= { pdu 1 }
|
||
|
|
||
|
celsiusTemp OBJECT-TYPE
|
||
|
SYNTAX INTEGER { fahrenheit(0), celsius(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the temperature units."
|
||
|
::= { pdu 2 }
|
||
|
|
||
|
shareRole OBJECT-TYPE
|
||
|
SYNTAX INTEGER { backup(0), shared(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether to allow sharing of PDU Primary and Alternate Roles."
|
||
|
::= { pdu 3 }
|
||
|
|
||
|
missingPDUNotify OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Controls whether to notify when a PDU is missing from the link."
|
||
|
::= { pdu 4 }
|
||
|
|
||
|
roleChangeNotify OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether to notify when a PDU changes role in the link."
|
||
|
::= { pdu 5 }
|
||
|
|
||
|
dispTimeout OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..90)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the inactivity timeout in minutes to blank the local display (minimum is 1 minute)."
|
||
|
::= { pdu 6 }
|
||
|
|
||
|
loginTimeout OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..60)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the inactivity timeout in minutes to terminate a logged in session (minimum is 1 minute)."
|
||
|
::= { pdu 7 }
|
||
|
|
||
|
dispBrightness OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..9)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the relative brightness of the local display (0 in min, 9 is max)."
|
||
|
::= { pdu 8 }
|
||
|
|
||
|
sumAmps OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Control whether the PDU displays the amperage sum of all branchs."
|
||
|
::= { pdu 9 }
|
||
|
|
||
|
alerts OBJECT IDENTIFIER ::= { configuration 7 }
|
||
|
|
||
|
alarmInterval OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..65535)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the time interval in seconds for alarm cycle (disabled if < 10)."
|
||
|
::= { alerts 1 }
|
||
|
|
||
|
routing OBJECT IDENTIFIER ::= { configuration 8 }
|
||
|
|
||
|
eventLogRouting OBJECT IDENTIFIER ::= { routing 1 }
|
||
|
|
||
|
logBranchCritLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical Low Voltage on the Branch to the event log."
|
||
|
::= { eventLogRouting 1 }
|
||
|
|
||
|
logBranchWarnLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning Low Voltage on the Branch to the event log."
|
||
|
::= { eventLogRouting 2 }
|
||
|
|
||
|
logBranchWarnHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning High Voltage on the Branch to the event log."
|
||
|
::= { eventLogRouting 3 }
|
||
|
|
||
|
logBranchCritHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical High Voltage on the Branch to the event log."
|
||
|
::= { eventLogRouting 4 }
|
||
|
|
||
|
logBranchCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical Low Current on the Branch to the event log."
|
||
|
::= { eventLogRouting 5 }
|
||
|
|
||
|
logBranchWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning Low Current on the Branch to the event log."
|
||
|
::= { eventLogRouting 6 }
|
||
|
|
||
|
logBranchWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning High Current on the Branch to the event log."
|
||
|
::= { eventLogRouting 7 }
|
||
|
|
||
|
logBranchCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical High Current on the Branch to the event log."
|
||
|
::= { eventLogRouting 8 }
|
||
|
|
||
|
logOutletCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical Low Current on the Outlet to the event log."
|
||
|
::= { eventLogRouting 9 }
|
||
|
|
||
|
logOutletWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning Low Current on the Outlet to the event log."
|
||
|
::= { eventLogRouting 10 }
|
||
|
|
||
|
logOutletWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning High Current on the Outlet to the event log."
|
||
|
::= { eventLogRouting 11 }
|
||
|
|
||
|
logOutletCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical High Current to the event log."
|
||
|
::= { eventLogRouting 12 }
|
||
|
|
||
|
logTempCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical Low Temperature to the event log."
|
||
|
::= { eventLogRouting 13 }
|
||
|
|
||
|
logTempWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning Low Temperature to the event log."
|
||
|
::= { eventLogRouting 14 }
|
||
|
|
||
|
logTempWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning High Temperature to the event log."
|
||
|
::= { eventLogRouting 15 }
|
||
|
|
||
|
logTempCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical High Temperature to the event log."
|
||
|
::= { eventLogRouting 16 }
|
||
|
|
||
|
logHumidCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical Low Humidity to the event log."
|
||
|
::= { eventLogRouting 17 }
|
||
|
|
||
|
logHumidWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning Low Humidity to the event log."
|
||
|
::= { eventLogRouting 18 }
|
||
|
|
||
|
logHumidWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Warning High Humidity to the event log."
|
||
|
::= { eventLogRouting 19 }
|
||
|
|
||
|
logHumidCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Critical High Humidity to the event log."
|
||
|
::= { eventLogRouting 20 }
|
||
|
|
||
|
logScanPass OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of successful card scan events to the event log."
|
||
|
::= { eventLogRouting 21 }
|
||
|
|
||
|
logScanFail OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of failed card scan events to the event log."
|
||
|
::= { eventLogRouting 22 }
|
||
|
|
||
|
logDoorState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Door Open/Close events to the event log."
|
||
|
::= { eventLogRouting 23 }
|
||
|
|
||
|
logLockState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Lock Open/Close events to the event log."
|
||
|
::= { eventLogRouting 24 }
|
||
|
|
||
|
logExtendedOpen OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of extended door open events to the event log."
|
||
|
::= { eventLogRouting 25 }
|
||
|
|
||
|
logFirmareUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of Firmare Update events to the event log."
|
||
|
::= { eventLogRouting 26 }
|
||
|
|
||
|
logConfigUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of configuration change events to the event log."
|
||
|
::= { eventLogRouting 27 }
|
||
|
|
||
|
logRecepChange OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of receptacle change events to the event log."
|
||
|
::= { eventLogRouting 28 }
|
||
|
|
||
|
logSystem OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of system events to the event log."
|
||
|
::= { eventLogRouting 29 }
|
||
|
|
||
|
logPduAccess OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of access to PDU events to the event log."
|
||
|
::= { eventLogRouting 30 }
|
||
|
|
||
|
logSecureArray OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable logging of SecureArray events to the event log."
|
||
|
::= { eventLogRouting 31 }
|
||
|
|
||
|
emailRouting OBJECT IDENTIFIER ::= { routing 2 }
|
||
|
|
||
|
emailBranchCritLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Voltage on the Branch in an email."
|
||
|
::= { emailRouting 1 }
|
||
|
|
||
|
emailBranchWarnLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Voltage on the Branch in an email."
|
||
|
::= { emailRouting 2 }
|
||
|
|
||
|
emailBranchWarnHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Voltage on the Branch in an email."
|
||
|
::= { emailRouting 3 }
|
||
|
|
||
|
emailBranchCritHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Voltage on the Branch in an email."
|
||
|
::= { emailRouting 4 }
|
||
|
|
||
|
emailBranchCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Current on the Branch in an email."
|
||
|
::= { emailRouting 5 }
|
||
|
|
||
|
emailBranchWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Current on the Branch in an email."
|
||
|
::= { emailRouting 6 }
|
||
|
|
||
|
emailBranchWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Current on the Branch in an email."
|
||
|
::= { emailRouting 7 }
|
||
|
|
||
|
emailBranchCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Current on the Branch in an email."
|
||
|
::= { emailRouting 8 }
|
||
|
|
||
|
emailOutletCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Current on the Outlet in an email."
|
||
|
::= { emailRouting 9 }
|
||
|
|
||
|
emailOutletWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Current on the Outlet in an email."
|
||
|
::= { emailRouting 10 }
|
||
|
|
||
|
emailOutletWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Current on the Outlet in an email."
|
||
|
::= { emailRouting 11 }
|
||
|
|
||
|
emailOutletCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Current in an email."
|
||
|
::= { emailRouting 12 }
|
||
|
|
||
|
emailTempCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Temperature in an email."
|
||
|
::= { emailRouting 13 }
|
||
|
|
||
|
emailTempWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Temperature in an email."
|
||
|
::= { emailRouting 14 }
|
||
|
|
||
|
emailTempWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Temperature in an email."
|
||
|
::= { emailRouting 15 }
|
||
|
|
||
|
emailTempCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Temperature in an email."
|
||
|
::= { emailRouting 16 }
|
||
|
|
||
|
emailHumidCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Humidity in an email."
|
||
|
::= { emailRouting 17 }
|
||
|
|
||
|
emailHumidWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Humidity in an email."
|
||
|
::= { emailRouting 18 }
|
||
|
|
||
|
emailHumidWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Humidity in an email."
|
||
|
::= { emailRouting 19 }
|
||
|
|
||
|
emailHumidCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Humidity in an email."
|
||
|
::= { emailRouting 20 }
|
||
|
|
||
|
emailScanPass OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of successful card scan events in an email."
|
||
|
::= { emailRouting 21 }
|
||
|
|
||
|
emailScanFail OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of failed card scan events in an email."
|
||
|
::= { emailRouting 22 }
|
||
|
|
||
|
emailDoorState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Door Open/Close events in an email."
|
||
|
::= { emailRouting 23 }
|
||
|
|
||
|
emailLockState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Lock Open/Close events in an email."
|
||
|
::= { emailRouting 24 }
|
||
|
|
||
|
emailExtendedOpen OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of extended door open events in an email."
|
||
|
::= { emailRouting 25 }
|
||
|
|
||
|
emailFirmareUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Firmare Update events in an email."
|
||
|
::= { emailRouting 26 }
|
||
|
|
||
|
emailConfigUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of configuration change events in an email."
|
||
|
::= { emailRouting 27 }
|
||
|
|
||
|
emailRecepChange OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of receptacle change events in an email."
|
||
|
::= { emailRouting 28 }
|
||
|
|
||
|
emailSystem OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of system events in an email."
|
||
|
::= { emailRouting 29 }
|
||
|
|
||
|
emailPduAccess OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of access to PDU events in an email."
|
||
|
::= { emailRouting 30 }
|
||
|
|
||
|
emailSecureArray OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of SecureArray events in an email."
|
||
|
::= { emailRouting 31 }
|
||
|
|
||
|
trapRouting OBJECT IDENTIFIER ::= { routing 3 }
|
||
|
|
||
|
trapBranchCritLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Voltage on the Branch in a trap."
|
||
|
::= { trapRouting 1 }
|
||
|
|
||
|
trapBranchWarnLowVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Voltage on the Branch in a trap."
|
||
|
::= { trapRouting 2 }
|
||
|
|
||
|
trapBranchWarnHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Voltage on the Branch in a trap."
|
||
|
::= { trapRouting 3 }
|
||
|
|
||
|
trapBranchCritHighVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Voltage on the Branch in a trap."
|
||
|
::= { trapRouting 4 }
|
||
|
|
||
|
trapBranchCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Current on the Branch in a trap."
|
||
|
::= { trapRouting 5 }
|
||
|
|
||
|
trapBranchWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Current on the Branch in a trap."
|
||
|
::= { trapRouting 6 }
|
||
|
|
||
|
trapBranchWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Current on the Branch in a trap."
|
||
|
::= { trapRouting 7 }
|
||
|
|
||
|
trapBranchCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Current on the Branch in a trap."
|
||
|
::= { trapRouting 8 }
|
||
|
|
||
|
trapOutletCritLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Current on the Outlet in a trap."
|
||
|
::= { trapRouting 9 }
|
||
|
|
||
|
trapOutletWarnLowCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Current on the Outlet in a trap."
|
||
|
::= { trapRouting 10 }
|
||
|
|
||
|
trapOutletWarnHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Current on the Outlet in a trap."
|
||
|
::= { trapRouting 11 }
|
||
|
|
||
|
trapOutletCritHighCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Current in a trap."
|
||
|
::= { trapRouting 12 }
|
||
|
|
||
|
trapTempCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Temperature in a trap."
|
||
|
::= { trapRouting 13 }
|
||
|
|
||
|
trapTempWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Temperature in a trap."
|
||
|
::= { trapRouting 14 }
|
||
|
|
||
|
trapTempWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Temperature in a trap."
|
||
|
::= { trapRouting 15 }
|
||
|
|
||
|
trapTempCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Temperature in a trap."
|
||
|
::= { trapRouting 16 }
|
||
|
|
||
|
trapHumidCritLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical Low Humidity in a trap."
|
||
|
::= { trapRouting 17 }
|
||
|
|
||
|
trapHumidWarnLow OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning Low Humidity in a trap."
|
||
|
::= { trapRouting 18 }
|
||
|
|
||
|
trapHumidWarnHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Warning High Humidity in a trap."
|
||
|
::= { trapRouting 19 }
|
||
|
|
||
|
trapHumidCritHigh OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Critical High Humidity in a trap."
|
||
|
::= { trapRouting 20 }
|
||
|
|
||
|
trapScanPass OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of successful card ID scans in a trap."
|
||
|
::= { trapRouting 21 }
|
||
|
|
||
|
trapScanFail OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of failed card ID scans in a trap."
|
||
|
::= { trapRouting 22 }
|
||
|
|
||
|
trapDoorState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Door Open/Closed events in a trap."
|
||
|
::= { trapRouting 23 }
|
||
|
|
||
|
trapLockState OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Lock Open/Closed events in a trap."
|
||
|
::= { trapRouting 24 }
|
||
|
|
||
|
trapExtendedOpen OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of extended door open events in an trap."
|
||
|
::= { trapRouting 25 }
|
||
|
|
||
|
trapFirmareUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of Firmare Update events in a trap."
|
||
|
::= { trapRouting 26 }
|
||
|
|
||
|
trapConfigUpdate OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of configuration change events in a trap."
|
||
|
::= { trapRouting 27 }
|
||
|
|
||
|
trapRecepChange OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of receptacle change events in a trap."
|
||
|
::= { trapRouting 28 }
|
||
|
|
||
|
trapSystem OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of system events in a trap."
|
||
|
::= { trapRouting 29 }
|
||
|
|
||
|
trapPduAccess OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of access to PDU events in a trap."
|
||
|
::= { trapRouting 30 }
|
||
|
|
||
|
trapSecureArray OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enable/Disable notification of SecureArray events in a trap."
|
||
|
::= { trapRouting 31 }
|
||
|
|
||
|
systeminfo OBJECT IDENTIFIER ::= { econnect 2 }
|
||
|
|
||
|
cpiPduTableCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of PDUs being monitored by this PDU. This is the
|
||
|
number of entries in the cpiPduTable."
|
||
|
::= { systeminfo 1 }
|
||
|
|
||
|
cpiPduTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU entries that are being monitored
|
||
|
by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the
|
||
|
number of PDUs being monitored. Each row in the table represents a PDU
|
||
|
in the daisy chain.
|
||
|
|
||
|
This table always contains at least one entry and a maximum of 32 entries.
|
||
|
The MAC address is used as an index on the table to allow data collectors
|
||
|
to ensure that information can be retrieved for a specific PDU."
|
||
|
::= { systeminfo 10 }
|
||
|
|
||
|
cpiPduEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduTable'. Each column represents an attribute of a PDU.
|
||
|
This table is indexed by the PDU MAC that is globally unique."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduMac
|
||
|
}
|
||
|
::= { cpiPduTable 1 }
|
||
|
|
||
|
CpiPduEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduMac MacAddress,
|
||
|
cpiPduModel DisplayString,
|
||
|
cpiPduName DisplayString,
|
||
|
cpiPduDescription DisplayString,
|
||
|
cpiPduHasBranchMonitor Integer32,
|
||
|
cpiPduHasOutletMonitor Integer32,
|
||
|
cpiPduHasOutletControl Integer32,
|
||
|
cpiPduNumberBranches Integer32,
|
||
|
cpiPduNumberOutlets Integer32,
|
||
|
cpiPduVersion DisplayString,
|
||
|
cpiPduUpgrade Integer32,
|
||
|
cpiPduChainRole Integer32,
|
||
|
cpiPduOutOfService Integer32,
|
||
|
cpiPduIp IpAddress,
|
||
|
cpiPduIpv6 DisplayString,
|
||
|
cpiPduTotalPower Integer32,
|
||
|
cpiPduCabinetId DisplayString,
|
||
|
cpiPduSerialNum DisplayString
|
||
|
}
|
||
|
|
||
|
cpiPduMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduEntry 1 }
|
||
|
|
||
|
cpiPduModel OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the model number of the PDU."
|
||
|
::= { cpiPduEntry 2 }
|
||
|
|
||
|
cpiPduName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user assigned name of the PDU."
|
||
|
::= { cpiPduEntry 3 }
|
||
|
|
||
|
cpiPduDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user assigned description of the PDU."
|
||
|
::= { cpiPduEntry 4 }
|
||
|
|
||
|
cpiPduHasBranchMonitor OBJECT-TYPE
|
||
|
SYNTAX INTEGER { notsupported(0), supported(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An indicator if the PDU supports monitoring voltage, and current on branches in the PDU."
|
||
|
::= { cpiPduEntry 5 }
|
||
|
|
||
|
cpiPduHasOutletMonitor OBJECT-TYPE
|
||
|
SYNTAX INTEGER { notsupported(0), supported(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An indicator if the PDU supports monitoring current on the individual outlets in the PDU."
|
||
|
::= { cpiPduEntry 6 }
|
||
|
|
||
|
cpiPduHasOutletControl OBJECT-TYPE
|
||
|
SYNTAX INTEGER { notsupported(0), supported(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An indicator if the PDU supports control (turn on/off) individual outlets in the PDU."
|
||
|
::= { cpiPduEntry 7 }
|
||
|
|
||
|
cpiPduNumberBranches OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..6)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of branches (breakers) in the PDU."
|
||
|
::= { cpiPduEntry 8 }
|
||
|
|
||
|
cpiPduNumberOutlets OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..48)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of outlets in the PDU."
|
||
|
::= { cpiPduEntry 9 }
|
||
|
|
||
|
cpiPduOutOfService OBJECT-TYPE
|
||
|
SYNTAX INTEGER { inservice(0), outofservice(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get whether the PDU is in-service."
|
||
|
::= { cpiPduEntry 10 }
|
||
|
|
||
|
cpiPduVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the firmware version number of the PDU."
|
||
|
::= { cpiPduEntry 11 }
|
||
|
|
||
|
cpiPduUpgrade OBJECT-TYPE
|
||
|
SYNTAX INTEGER { no(0), yes(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An indicator if the PDU firmware is being upgraded."
|
||
|
::= { cpiPduEntry 12 }
|
||
|
|
||
|
cpiPduChainRole OBJECT-TYPE
|
||
|
SYNTAX INTEGER { secondary(0), primary(1), alternate(2) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the role of the PDU in a daisy chain."
|
||
|
::= { cpiPduEntry 13 }
|
||
|
|
||
|
cpiPduIp OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get IP address of the PDU."
|
||
|
::= { cpiPduEntry 14 }
|
||
|
|
||
|
cpiPduIpv6 OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the IPv6 address of the PDU."
|
||
|
::= { cpiPduEntry 15 }
|
||
|
|
||
|
cpiPduTotalPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the power in volt-amps for the entire PDU."
|
||
|
::= { cpiPduEntry 16 }
|
||
|
|
||
|
cpiPduCabinetId OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get/set the name of the cabinet the PDU is in."
|
||
|
::= { cpiPduEntry 17 }
|
||
|
|
||
|
cpiPduSerialNum OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the serial number of the PDU."
|
||
|
::= { cpiPduEntry 18 }
|
||
|
|
||
|
branch OBJECT IDENTIFIER ::= { econnect 3 }
|
||
|
|
||
|
cpiLineTableCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of PDU input lines being monitored by this PDU.
|
||
|
This is the number of entries in the cpiLineTable and accounts
|
||
|
for all input lines in a daisy chain."
|
||
|
::= { branch 1 }
|
||
|
|
||
|
cpiPduLineTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduLineEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU line entries that are being
|
||
|
monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of input lines. Each row
|
||
|
in the table represents a PDU line in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Line Input ID and
|
||
|
the source PDU MAC."
|
||
|
::= { branch 10 }
|
||
|
|
||
|
cpiPduLineEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduLineEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduLineTable'. Each column represents an attribute of a PDU.
|
||
|
This table is indexed by the PDU Line identifier that is unique
|
||
|
within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduLineId,
|
||
|
cpiPduLineMac
|
||
|
}
|
||
|
::= { cpiPduLineTable 1 }
|
||
|
|
||
|
CpiPduLineEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduLineMac DisplayString,
|
||
|
cpiPduLineId DisplayString,
|
||
|
cpiPduLineCurrent Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduLineMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU that owns the input line."
|
||
|
::= { cpiPduLineEntry 1 }
|
||
|
|
||
|
cpiPduLineId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the ID of the input line on the PDU."
|
||
|
::= { cpiPduLineEntry 2 }
|
||
|
|
||
|
cpiPduLineCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100."
|
||
|
::= { cpiPduLineEntry 3 }
|
||
|
|
||
|
cpiBranchTableCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of PDU branches being monitored by this PDU. This is the
|
||
|
number of entries in the cpiPduBranchTable."
|
||
|
::= { branch 100 }
|
||
|
|
||
|
cpiPduBranchTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduBranchEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU branch entries that are being
|
||
|
monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of branches per PDU. Each row
|
||
|
in the table represents a PDU branch in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Branch ID and
|
||
|
the source PDU MAC."
|
||
|
::= { branch 110 }
|
||
|
|
||
|
cpiPduBranchEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduBranchEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
|
||
|
This table is indexed by the PDU Line identifier that is unique
|
||
|
within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduBranchId,
|
||
|
cpiPduBranchMac
|
||
|
}
|
||
|
::= { cpiPduBranchTable 1 }
|
||
|
|
||
|
CpiPduBranchEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduBranchMac MacAddress,
|
||
|
cpiPduBranchId DisplayString,
|
||
|
cpiPduBranchCurrent Integer32,
|
||
|
cpiPduBranchMaxCurrent Integer32,
|
||
|
cpiPduBranchVoltage Integer32,
|
||
|
cpiPduBranchPower Integer32,
|
||
|
cpiPduBranchPowerFactor Integer32,
|
||
|
cpiPduBranchStatus Integer32,
|
||
|
cpiPduBranchEnergy Counter64
|
||
|
}
|
||
|
|
||
|
cpiPduBranchMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU that owns the branch."
|
||
|
::= { cpiPduBranchEntry 1 }
|
||
|
|
||
|
cpiPduBranchId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the ID of the branch on the owning PDU."
|
||
|
::= { cpiPduBranchEntry 2 }
|
||
|
|
||
|
cpiPduBranchCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100."
|
||
|
::= { cpiPduBranchEntry 3 }
|
||
|
|
||
|
cpiPduBranchMaxCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100."
|
||
|
::= { cpiPduBranchEntry 4 }
|
||
|
|
||
|
cpiPduBranchVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10."
|
||
|
::= { cpiPduBranchEntry 5 }
|
||
|
|
||
|
cpiPduBranchPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the power in volt-amps for the branch."
|
||
|
::= { cpiPduBranchEntry 6 }
|
||
|
|
||
|
cpiPduBranchPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the power factor for the branch."
|
||
|
::= { cpiPduBranchEntry 7 }
|
||
|
|
||
|
cpiPduBranchStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { noalarm(0), warning(1), alarm(2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the alarm status of the branch."
|
||
|
::= { cpiPduBranchEntry 8 }
|
||
|
|
||
|
cpiPduBranchEnergy OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr."
|
||
|
::= { cpiPduBranchEntry 9 }
|
||
|
|
||
|
cpiPduBranchAlertTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduBranchAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU branch alert entries that are
|
||
|
being monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of branches per PDU. Each row
|
||
|
in the table represents a PDU branch in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Branch ID and the
|
||
|
source PDU MAC."
|
||
|
::= { branch 210 }
|
||
|
|
||
|
cpiPduBranchAlertEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduBranchAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
|
||
|
This table is indexed by the PDU Line identifier that is unique
|
||
|
within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduBranchAlertIndex
|
||
|
}
|
||
|
::= { cpiPduBranchAlertTable 1 }
|
||
|
|
||
|
CpiPduBranchAlertEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduBranchAlertIndex Unsigned32,
|
||
|
cpiPduBranchAlertMac MacAddress,
|
||
|
cpiPduBranchAlertBranchId Integer32,
|
||
|
cpiPduBranchAlertWarnLoCurrent Integer32,
|
||
|
cpiPduBranchAlertWarnHiCurrent Integer32,
|
||
|
cpiPduBranchAlertLoCurrent Integer32,
|
||
|
cpiPduBranchAlertHiCurrent Integer32,
|
||
|
cpiPduBranchAlertCriticalCurrent Integer32,
|
||
|
cpiPduBranchAlertWarnLoVolt Integer32,
|
||
|
cpiPduBranchAlertWarnHiVolt Integer32,
|
||
|
cpiPduBranchAlertLoVolt Integer32,
|
||
|
cpiPduBranchAlertHiVolt Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduBranchAlertMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduBranchAlertEntry 1 }
|
||
|
|
||
|
cpiPduBranchAlertBranchId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the branch ID on the PDU."
|
||
|
::= { cpiPduBranchAlertEntry 2 }
|
||
|
|
||
|
cpiPduBranchAlertWarnLoCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers a warning condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduBranchAlertEntry 3 }
|
||
|
|
||
|
cpiPduBranchAlertWarnHiCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers a warning condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduBranchAlertEntry 4 }
|
||
|
|
||
|
cpiPduBranchAlertLoCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers an alarm condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduBranchAlertEntry 5 }
|
||
|
|
||
|
cpiPduBranchAlertHiCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU, that triggers an alarm condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduBranchAlertEntry 6 }
|
||
|
|
||
|
cpiPduBranchAlertCriticalCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the critical current draw in 1/100 amp of the
|
||
|
branch on the PDU. Convert the value by dividing by 100."
|
||
|
::= { cpiPduBranchAlertEntry 7 }
|
||
|
|
||
|
cpiPduBranchAlertWarnLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the minimum voltage that the branch can reach
|
||
|
up to in 1/10th volts, 0=ignore. Convert the value by
|
||
|
dividing by 10."
|
||
|
::= { cpiPduBranchAlertEntry 8 }
|
||
|
|
||
|
cpiPduBranchAlertWarnHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the maximum voltage that the branch can reach
|
||
|
up to in 1/10th volts, 0=ignore. Convert the value by
|
||
|
dividing by 10."
|
||
|
::= { cpiPduBranchAlertEntry 9 }
|
||
|
|
||
|
cpiPduBranchAlertLoVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the minimum voltage that the branch can reach
|
||
|
up to in 1/10th volts, 0=ignore. Convert the value by
|
||
|
dividing by 10."
|
||
|
::= { cpiPduBranchAlertEntry 10 }
|
||
|
|
||
|
cpiPduBranchAlertHiVolt OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the maximum voltage that the branch can reach
|
||
|
up to in 1/10th volts, 0=ignore. Convert the value by
|
||
|
dividing by 10."
|
||
|
::= { cpiPduBranchAlertEntry 11 }
|
||
|
|
||
|
cpiPduBranchAlertIndex OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for branch aler"
|
||
|
::= { cpiPduBranchAlertEntry 12 }
|
||
|
|
||
|
cpiPduBranchAlertIndex OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for branch alert."
|
||
|
::= { cpiPduBranchAlertEntry 13 }
|
||
|
|
||
|
outlet OBJECT IDENTIFIER ::= { econnect 4 }
|
||
|
|
||
|
cpiOutletTableCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of PDU outlets being monitored by this PDU. This
|
||
|
is the number of entries in the cpiPduOutletTable."
|
||
|
::= { outlet 1 }
|
||
|
|
||
|
cpiPduOutletTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduOutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU outlet entries that are being
|
||
|
monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of outlets on each PDU.
|
||
|
Each row in the table represents a PDU outlet in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Outlet ID and
|
||
|
the source PDU MAC."
|
||
|
::= { outlet 10 }
|
||
|
|
||
|
cpiPduOutletEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduOutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
|
||
|
This table is indexed by the PDU Outlet identifier that is unique
|
||
|
within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduOutletId,
|
||
|
cpiPduOutletMac
|
||
|
}
|
||
|
::= { cpiPduOutletTable 1 }
|
||
|
|
||
|
CpiPduOutletEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduOutletMac MacAddress,
|
||
|
cpiPduOutletId Integer32,
|
||
|
cpiPduOutletBranchId Integer32,
|
||
|
cpiPduOutletName DisplayString,
|
||
|
cpiPduOutletDescription DisplayString,
|
||
|
cpiPduOutletCurrent Integer32,
|
||
|
cpiPduOutletVoltage Integer32,
|
||
|
cpiPduOutletPower Integer32,
|
||
|
cpiPduOutletStatus Integer32,
|
||
|
cpiPduOutletEnergy Counter64,
|
||
|
cpiPduOutletControl Integer32,
|
||
|
cpiPduOutletReset Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduOutletMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the source PDU."
|
||
|
::= { cpiPduOutletEntry 1 }
|
||
|
|
||
|
cpiPduOutletId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the ID of the outlet on the PDU."
|
||
|
::= { cpiPduOutletEntry 2 }
|
||
|
|
||
|
cpiPduOutletBranchId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the ID of the branch the outlet is associated with on the PDU."
|
||
|
::= { cpiPduOutletEntry 3 }
|
||
|
|
||
|
cpiPduOutletName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user supplied name of the outlet on the PDU."
|
||
|
::= { cpiPduOutletEntry 4 }
|
||
|
|
||
|
cpiPduOutletDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user supplied description of the outlet on the PDU."
|
||
|
::= { cpiPduOutletEntry 5 }
|
||
|
|
||
|
cpiPduOutletCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the current draw in 1/100 amp of the outlet on the PDU. Convert
|
||
|
the value by dividing by 100."
|
||
|
::= { cpiPduOutletEntry 6 }
|
||
|
|
||
|
cpiPduOutletVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
|
||
|
value by dividing by 10."
|
||
|
::= { cpiPduOutletEntry 7 }
|
||
|
|
||
|
cpiPduOutletPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power in Volt-Amps of the outlet on the PDU."
|
||
|
::= { cpiPduOutletEntry 8 }
|
||
|
|
||
|
cpiPduOutletStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { noalarm(0), warning(1), alarm(2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the alarm status of the outlet."
|
||
|
::= { cpiPduOutletEntry 9 }
|
||
|
|
||
|
cpiPduOutletEnergy OBJECT-TYPE
|
||
|
SYNTAX Counter64
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr."
|
||
|
::= { cpiPduOutletEntry 10 }
|
||
|
|
||
|
cpiPduOutletControl OBJECT-TYPE
|
||
|
SYNTAX INTEGER { off(0), on(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get power control to the outlet."
|
||
|
::= { cpiPduOutletEntry 11 }
|
||
|
|
||
|
cpiPduOutletReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER { nominal(0), reset(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get reset power to the outlet."
|
||
|
::= { cpiPduOutletEntry 12 }
|
||
|
|
||
|
cpiPduOutletConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduOutletConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU outlet configuration entries
|
||
|
that are being monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of outlets per PDU. Each row
|
||
|
in the table represents a PDU outlet in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Outlet ID and
|
||
|
the source PDU MAC."
|
||
|
::= { outlet 210 }
|
||
|
|
||
|
cpiPduOutletConfigEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduOutletConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduOutletConfigTable'. Each column represents an
|
||
|
configurable attribute of an outlet in the PDU. This
|
||
|
table is indexed by the PDU Line identifier that is
|
||
|
unique within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduOutletConfigOutletId,
|
||
|
cpiPduOutletConfigMac
|
||
|
}
|
||
|
::= { cpiPduOutletConfigTable 1 }
|
||
|
|
||
|
CpiPduOutletConfigEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduOutletConfigMac MacAddress,
|
||
|
cpiPduOutletConfigOutletId Integer32,
|
||
|
cpiPduOutletConfigOnDelay Integer32,
|
||
|
cpiPduOutletConfigResetDelay Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduOutletConfigMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduOutletConfigEntry 1 }
|
||
|
|
||
|
cpiPduOutletConfigOutletId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the ID of the outlet on the PDU."
|
||
|
::= { cpiPduOutletConfigEntry 2 }
|
||
|
|
||
|
cpiPduOutletConfigOnDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the outlet power-on delay in seconds."
|
||
|
::= { cpiPduOutletConfigEntry 3 }
|
||
|
|
||
|
cpiPduOutletConfigResetDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the outlet reset delay in seconds."
|
||
|
::= { cpiPduOutletConfigEntry 4 }
|
||
|
|
||
|
cpiPduOutletAlertTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduOutletAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU outlet alert entries that are
|
||
|
being monitored by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of outlets per PDU. Each row
|
||
|
in the table represents a PDU outlet in the daisy chain.
|
||
|
|
||
|
The table is indexed based on the corresponding Outlet ID and the
|
||
|
source PDU MAC."
|
||
|
::= { outlet 310 }
|
||
|
|
||
|
cpiPduOutletAlertEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduOutletAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
|
||
|
This table is indexed by the PDU Line identifier that is unique
|
||
|
within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduOutletAlertOutletId,
|
||
|
cpiPduOutletAlertMac
|
||
|
}
|
||
|
::= { cpiPduOutletAlertTable 1 }
|
||
|
|
||
|
CpiPduOutletAlertEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduOutletAlertMac MacAddress,
|
||
|
cpiPduOutletAlertOutletId Integer32,
|
||
|
cpiPduOutletAlertWarnLoCurrent Integer32,
|
||
|
cpiPduOutletAlertWarnHiCurrent Integer32,
|
||
|
cpiPduOutletAlertLoCurrent Integer32,
|
||
|
cpiPduOutletAlertHiCurrent Integer32,
|
||
|
cpiPduOutletAlertCriticalCurrent Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduOutletAlertMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduOutletAlertEntry 1 }
|
||
|
|
||
|
cpiPduOutletAlertOutletId OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the outlet ID on the PDU."
|
||
|
::= { cpiPduOutletAlertEntry 2 }
|
||
|
|
||
|
cpiPduOutletAlertWarnLoCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers a warning condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduOutletAlertEntry 3 }
|
||
|
|
||
|
cpiPduOutletAlertWarnHiCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers a warning condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduOutletAlertEntry 4 }
|
||
|
|
||
|
cpiPduOutletAlertLoCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU that triggers an alarm condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduOutletAlertEntry 5 }
|
||
|
|
||
|
cpiPduOutletAlertHiCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the current draw in 1/100 amp of the branch on
|
||
|
the PDU, that triggers an alarm condition. Convert the
|
||
|
value by dividing by 100."
|
||
|
::= { cpiPduOutletAlertEntry 6 }
|
||
|
|
||
|
cpiPduOutletAlertCriticalCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the critical current draw in 1/100 amp of the
|
||
|
outlet on the PDU. Convert the value by dividing by 100."
|
||
|
::= { cpiPduOutletAlertEntry 7 }
|
||
|
|
||
|
sensors OBJECT IDENTIFIER ::= { econnect 5 }
|
||
|
|
||
|
cpiPduSensorCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of PDU sensors being monitored by this PDU. This is the
|
||
|
number of entries in the cpiPduSensorTable."
|
||
|
::= { sensors 1 }
|
||
|
|
||
|
cpiPduProbeTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduProbeEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU probes that are being monitored
|
||
|
by the PDU.
|
||
|
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of probes attached to the PDUs in
|
||
|
the daisy chain. Each row in the table represents a probe in the daisy chain.
|
||
|
|
||
|
The table is index based on the corresponding Probe ID and the source
|
||
|
PDU MAC."
|
||
|
::= { sensors 5 }
|
||
|
|
||
|
cpiPduProbeEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduProbeEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
|
||
|
This table is indexed by the PDU identifier that is unique
|
||
|
within the PDU and the probe ID."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduProbeId,
|
||
|
cpiPduProbeMac
|
||
|
}
|
||
|
::= { cpiPduProbeTable 1 }
|
||
|
|
||
|
CpiPduProbeEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduProbeMac MacAddress,
|
||
|
cpiPduProbeId Integer32,
|
||
|
cpiPduProbeName DisplayString
|
||
|
}
|
||
|
|
||
|
cpiPduProbeMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduProbeEntry 1 }
|
||
|
|
||
|
cpiPduProbeId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the probe ID on the PDU."
|
||
|
::= { cpiPduProbeEntry 2 }
|
||
|
|
||
|
cpiPduProbeName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user defined name of the probe."
|
||
|
::= { cpiPduProbeEntry 3 }
|
||
|
|
||
|
cpiPduSensorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduSensorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU sensor entries that are being monitored
|
||
|
by the PDU.
|
||
|
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of sensors attached to the PDUs in
|
||
|
the daisy chain. Each row in the table represents a sensor in the daisy chain.
|
||
|
|
||
|
The table is index based on the corresponding Sensor ID and the source
|
||
|
PDU MAC."
|
||
|
::= { sensors 10 }
|
||
|
|
||
|
cpiPduSensorEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduSensorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the 'cpiPduSensorTable'.
|
||
|
Each column represents an attribute of a PDU sensor. This table is indexed
|
||
|
by the PDU identifier that is unique within the PDU and the sensor ID."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorMac
|
||
|
}
|
||
|
::= { cpiPduSensorTable 1 }
|
||
|
|
||
|
CpiPduSensorEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduSensorMac MacAddress,
|
||
|
cpiPduSensorId Integer32,
|
||
|
cpiPduSensorName DisplayString,
|
||
|
cpiPduSensorType Integer32,
|
||
|
cpiPduSensorValue Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduSensorMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduSensorEntry 1 }
|
||
|
|
||
|
cpiPduSensorId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the sensor ID on the PDU."
|
||
|
::= { cpiPduSensorEntry 2 }
|
||
|
|
||
|
cpiPduSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the user defined name of the sensor."
|
||
|
::= { cpiPduSensorEntry 3 }
|
||
|
|
||
|
cpiPduSensorType OBJECT-TYPE
|
||
|
SYNTAX INTEGER { temperature(1), humidity(2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the type of sensor for the entry."
|
||
|
::= { cpiPduSensorEntry 4 }
|
||
|
|
||
|
cpiPduSensorValue OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the value of the sensor. For temperature the value is in degrees
|
||
|
Fahrenheit and for humidity the value is percent humidity."
|
||
|
::= { cpiPduSensorEntry 5 }
|
||
|
|
||
|
cpiPduSensorAlertTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiPduSensorAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU sensor alert entries that are
|
||
|
being monitored by the PDU.
|
||
|
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of sensors attached to the PDUs in
|
||
|
the daisy chain. Each row in the table represents a sensor in the daisy chain.
|
||
|
|
||
|
The table is index based on the corresponding Sonsor ID and the source
|
||
|
PDU MAC."
|
||
|
::= { sensors 110 }
|
||
|
|
||
|
cpiPduSensorAlertEntry OBJECT-TYPE
|
||
|
SYNTAX CpiPduSensorAlertEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
|
||
|
Each column represents an attribute of a PDU sensor alert. This table
|
||
|
is indexed by the PDU identifier that is unique within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduSensorAlertSensorId,
|
||
|
cpiPduSensorAlertMac
|
||
|
}
|
||
|
::= { cpiPduSensorAlertTable 1 }
|
||
|
|
||
|
CpiPduSensorAlertEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduSensorAlertMac MacAddress,
|
||
|
cpiPduSensorAlertSensorId Integer32,
|
||
|
cpiPduSensorAlertWarnMin Integer32,
|
||
|
cpiPduSensorAlertWarnMax Integer32,
|
||
|
cpiPduSensorAlertMin Integer32,
|
||
|
cpiPduSensorAlertMax Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduSensorAlertMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiPduSensorAlertEntry 1 }
|
||
|
|
||
|
cpiPduSensorAlertSensorId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the id of the sensor."
|
||
|
::= { cpiPduSensorAlertEntry 2 }
|
||
|
|
||
|
cpiPduSensorAlertWarnMin OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the minimum warning value of the sensor."
|
||
|
::= { cpiPduSensorAlertEntry 3 }
|
||
|
|
||
|
cpiPduSensorAlertWarnMax OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the maximum warning value of the sensor."
|
||
|
::= { cpiPduSensorAlertEntry 4 }
|
||
|
|
||
|
cpiPduSensorAlertMin OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the minimum alarm value of the sensor."
|
||
|
::= { cpiPduSensorAlertEntry 5 }
|
||
|
|
||
|
cpiPduSensorAlertMax OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Set or get the maximum alarm value of the sensor."
|
||
|
::= { cpiPduSensorAlertEntry 6 }
|
||
|
|
||
|
group OBJECT IDENTIFIER ::= { econnect 6 }
|
||
|
|
||
|
cpiPduGroupCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of supported groups by the PDU. Value from 0 to 16."
|
||
|
::= { group 1 }
|
||
|
|
||
|
cpiPduGroupOutletCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of outlets in the Group Outlet Table."
|
||
|
::= { group 2 }
|
||
|
|
||
|
cpiGroupTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiGroupEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU group entries that are being monitored
|
||
|
by the PDU.
|
||
|
|
||
|
The table contains one, or many rows, depending upon the number
|
||
|
of groups that have been configured. Each row in the table represents a
|
||
|
group."
|
||
|
::= { group 10 }
|
||
|
|
||
|
cpiGroupEntry OBJECT-TYPE
|
||
|
SYNTAX CpiGroupEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiGroupTable'. This table is indexed by the group identifier that
|
||
|
is unique within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiGroupEntryIndex
|
||
|
}
|
||
|
::= { cpiGroupTable 1 }
|
||
|
|
||
|
CpiGroupEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiGroupEntryIndex Unsigned32,
|
||
|
cpiGroupName DisplayString
|
||
|
}
|
||
|
|
||
|
cpiGroupEntryIndex OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This is the index that indicates the row of the 'cpiPduTable'."
|
||
|
::= { cpiGroupEntry 1 }
|
||
|
|
||
|
cpiGroupName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 1 of receptacles."
|
||
|
::= { cpiGroupEntry 2 }
|
||
|
|
||
|
|
||
|
cpiGroupOutletTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiGroupOutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of PDU group entries.
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of groups that have been configured. Each row in the table represents a
|
||
|
group."
|
||
|
::= { group 20 }
|
||
|
|
||
|
cpiGroupOutletEntry OBJECT-TYPE
|
||
|
SYNTAX CpiGroupOutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the
|
||
|
'cpiGroupTable'. This table is indexed by the group identifier that
|
||
|
is unique within the PDU."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiGroupOutletEntryIndex
|
||
|
}
|
||
|
::= { cpiGroupOutletTable 1 }
|
||
|
|
||
|
CpiGroupOutletEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiGroupOutletEntryIndex Unsigned32,
|
||
|
cpiGroupOutletGroupID Unsigned32,
|
||
|
cpiGroupOutletPDUMac MacAddress,
|
||
|
cpiGroupOutletOutletId Integer32
|
||
|
}
|
||
|
|
||
|
cpiGroupOutletEntryIndex OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This is the index that indicates the row of the 'cpiGroupOutletTable'."
|
||
|
::= { cpiGroupOutletEntry 1 }
|
||
|
|
||
|
cpiGroupOutletGroupID OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Name for GROUP 1 of receptacles."
|
||
|
::= { cpiGroupOutletEntry 2 }
|
||
|
|
||
|
cpiGroupOutletPDUMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"MAC of PDU the outlet is on."
|
||
|
::= { cpiGroupOutletEntry 3 }
|
||
|
|
||
|
cpiGroupOutletOutletId OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the outlet on the PDU."
|
||
|
::= { cpiGroupOutletEntry 4 }
|
||
|
|
||
|
easData OBJECT IDENTIFIER ::= { econnect 7 }
|
||
|
|
||
|
cpiEasCount OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
UNITS "Count"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the number of locks connected to the PDU. This includes the PDUs on the daisy chain."
|
||
|
::= { easData 1 }
|
||
|
|
||
|
cpiEasConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiEasConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of electronic locks that are connected to the PDU
|
||
|
and allows for the configuration of the various settings associated with the
|
||
|
EAS (electronic access system).
|
||
|
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of locks attached to the PDUs in
|
||
|
the daisy chain. Each row in the table represents a lock in the daisy chain.
|
||
|
|
||
|
The table is index based on the corresponding lock ID and the source
|
||
|
PDU MAC."
|
||
|
::= { easData 90 }
|
||
|
|
||
|
cpiEasConfigEntry OBJECT-TYPE
|
||
|
SYNTAX CpiEasConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the 'cpiEasTable'.
|
||
|
Each column represents an attribute of a PDU lock. This table is indexed
|
||
|
by the PDU identifier that is unique within the PDU and the lock ID."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiEasConfigLockMac
|
||
|
}
|
||
|
::= { cpiEasConfigTable 1 }
|
||
|
|
||
|
CpiEasConfigEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiEasConfigLockMac MacAddress,
|
||
|
cpiEasConfigEnabled Integer32,
|
||
|
cpiEasFrontLockEnabled Integer32,
|
||
|
cpiEasRearLockEnabled Integer32,
|
||
|
cpiEasLockHoldOpenTime Integer32,
|
||
|
cpiEasDoorOpenAlarmTime Integer32
|
||
|
}
|
||
|
|
||
|
cpiEasConfigLockMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiEasConfigEntry 1 }
|
||
|
|
||
|
cpiEasConfigEnabled OBJECT-TYPE
|
||
|
SYNTAX INTEGER { not-available(0), available(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates whether the Electronic Access System (EAS) is available on the PDU."
|
||
|
::= { cpiEasConfigEntry 2 }
|
||
|
|
||
|
cpiEasFrontLockEnabled OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enables the front lock on the EAS."
|
||
|
::= { cpiEasConfigEntry 3 }
|
||
|
|
||
|
cpiEasRearLockEnabled OBJECT-TYPE
|
||
|
SYNTAX INTEGER { disabled(0), enabled(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enables the rear lock on the EAS."
|
||
|
::= { cpiEasConfigEntry 4 }
|
||
|
|
||
|
cpiEasLockHoldOpenTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The length of time in seconds to hold open the lock after a successful card scan."
|
||
|
::= { cpiEasConfigEntry 5 }
|
||
|
|
||
|
cpiEasDoorOpenAlarmTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The length of time in minutes before alerting that the door is open."
|
||
|
::= { cpiEasConfigEntry 6 }
|
||
|
|
||
|
cpiEasTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF CpiEasEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This table contains a list of electronic locks that are connected to the PDU
|
||
|
|
||
|
The table contains zero, one, or many rows, depending upon the number
|
||
|
of PDUs being monitored and the number of locks attached to the PDUs in
|
||
|
the daisy chain. Each row in the table represents a lock in the daisy chain.
|
||
|
|
||
|
The table is index based on the corresponding lock ID and the source
|
||
|
PDU MAC."
|
||
|
::= { easData 100 }
|
||
|
|
||
|
cpiEasEntry OBJECT-TYPE
|
||
|
SYNTAX CpiEasEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This entry defines the columns to be populated in the 'cpiEasTable'.
|
||
|
Each column represents an attribute of a PDU lock. This table is indexed
|
||
|
by the PDU identifier that is unique within the PDU and the lock ID."
|
||
|
|
||
|
INDEX
|
||
|
{
|
||
|
cpiPduLockId,
|
||
|
cpiPduLockMac
|
||
|
}
|
||
|
::= { cpiEasTable 1 }
|
||
|
|
||
|
CpiEasEntry ::= SEQUENCE
|
||
|
{
|
||
|
cpiPduLockMac MacAddress,
|
||
|
cpiPduLockId Integer32,
|
||
|
cpiPduEasStatus Integer32,
|
||
|
cpiPduDoorStatus Integer32,
|
||
|
cpiPduLockStatus Integer32,
|
||
|
cpiPduTamperStatus Integer32,
|
||
|
cpiEasError Integer32,
|
||
|
cpiPduLockCtrl Integer32
|
||
|
}
|
||
|
|
||
|
cpiPduLockMac OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the MAC address of the PDU."
|
||
|
::= { cpiEasEntry 1 }
|
||
|
|
||
|
cpiPduLockId OBJECT-TYPE
|
||
|
SYNTAX INTEGER { front(1), rear(2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the lock ID on the PDU."
|
||
|
::= { cpiEasEntry 2 }
|
||
|
|
||
|
cpiPduEasStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { inactive(0), ready(1), error(2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates if the Electronic Access Control system is ready, inactive, or in an error state.
|
||
|
|
||
|
If the status is Inactive, then the lock is not enabled on the PDU.
|
||
|
If the status is Error, then the cpiEasError field will have an error code to help diagnose the issue.
|
||
|
If the status is Ready, then the lock at the door is enabled and ready."
|
||
|
::= { cpiEasEntry 3 }
|
||
|
|
||
|
cpiPduDoorStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { closed(0), open(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates if the door sensor is closed or open."
|
||
|
::= { cpiEasEntry 4 }
|
||
|
|
||
|
cpiPduLockStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { closed(0), open(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates if the lock is closed or open."
|
||
|
::= { cpiEasEntry 5 }
|
||
|
|
||
|
cpiPduForceStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { normal(0), force(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces."
|
||
|
::= { cpiEasEntry 6 }
|
||
|
|
||
|
cpiPduTamperStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER { normal(0), tamper(1) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates if the cabinet is currently unlocked/opened without an authorization scan."
|
||
|
::= { cpiEasEntry 7 }
|
||
|
|
||
|
cpiEasError OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Gets the error code associated for the electronic lock system. The possible error codes are:
|
||
|
|
||
|
196608 (0x00030000
|
||
|
) - No error, the lock is working and ready.
|
||
|
167968771 (0x0a030003
|
||
|
) - The lock is not enabled. Enable the lock through the cpiEasConfigTable.
|
||
|
167837698 (0x0a010002
|
||
|
) - The lock is not responding. Ensure that the lock is connected to the PDU,
|
||
|
and is recieving power. Try to disable and re-enable the lock in the
|
||
|
cpiEasConfigTable."
|
||
|
::= { cpiEasEntry 8 }
|
||
|
|
||
|
cpiEasLockVer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Gets the version of the electronic lock control."
|
||
|
::= { cpiEasEntry 9 }
|
||
|
|
||
|
cpiEasLockSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Get the serial number of the electronic lock control."
|
||
|
::= { cpiEasEntry 10 }
|
||
|
|
||
|
cpiPduLockCtrl OBJECT-TYPE
|
||
|
SYNTAX INTEGER { close(0), open(1) }
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Tells the system to open the locks on the cabinet."
|
||
|
::= { cpiEasEntry 11 }
|
||
|
|
||
|
traps OBJECT IDENTIFIER ::= { econnect 500 }
|
||
|
|
||
|
trapInformation OBJECT IDENTIFIER ::= { traps 0 }
|
||
|
|
||
|
trapInfoUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user Id associated with the action."
|
||
|
::= { trapInformation 1 }
|
||
|
|
||
|
trapInfoCardId OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The card Id associated with the action."
|
||
|
::= { trapInformation 2 }
|
||
|
|
||
|
trapInfoConfigName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The configuration value that was changed."
|
||
|
::= { trapInformation 3 }
|
||
|
|
||
|
trapInfoInterface OBJECT-TYPE
|
||
|
SYNTAX INTEGER { serial(0), webgui(1), snmp(2), unkown(3), lcd(4), internal(5), bulk(6) }
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An identifier for the affected interface."
|
||
|
::= { trapInformation 4 }
|
||
|
|
||
|
trapInfoVarId OBJECT-TYPE
|
||
|
SYNTAX OBJECT IDENTIFIER
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An identifier for the value that was changed."
|
||
|
::= { trapInformation 5 }
|
||
|
|
||
|
trapInfoBootType OBJECT-TYPE
|
||
|
SYNTAX INTEGER { cold(0), warm(1), restart(2), reboot(3) }
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates that type of boot up occurring. A Cold boot is done from a complete power off. A Warm boot
|
||
|
was not a loss in power, but just a reboot of the control module."
|
||
|
::= { trapInformation 6 }
|
||
|
|
||
|
trapInfoProgress OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..100)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the percent complete of an operation."
|
||
|
::= { trapInformation 7 }
|
||
|
|
||
|
trapInfoResult OBJECT-TYPE
|
||
|
SYNTAX INTEGER { success(0), failure(1) }
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the result of an operation."
|
||
|
::= { trapInformation 8 }
|
||
|
|
||
|
trapInfoErrorCode OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the error code of an operation. See the operation for details.
|
||
|
|
||
|
Firmware Update Operation Error Codes:
|
||
|
151060481 - Error: Insufficient space available on the PDU to complete the operation.
|
||
|
151060482 - Error: Too many packets were lost in the transfer process. Please try the operation again.
|
||
|
151060483 - Error: The firmware file is corrupted and can not be used.
|
||
|
151060484 - Error: There was a failure in writing the firmware data out to internal memory.
|
||
|
151060485 - Error: The firmware file could not be opened and processed correctly.
|
||
|
151060489 - Error: A unknown failure occured while performing a firmware upgrade.
|
||
|
|
||
|
151060490 - Info: A firmware update is in progress. No issue currently.
|
||
|
151191558 - Info: A firmware upgrade has completed and does not need to reboot.
|
||
|
151191559 - Info: A firmware upgrade has compelted and will reboot.
|
||
|
151191560 - Info: A firmware upgrade has compelted and it was not needed. PDU will not reboot."
|
||
|
::= { trapInformation 9 }
|
||
|
|
||
|
trapInfoGroupName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user group Id associated with the action."
|
||
|
::= { trapInformation 10 }
|
||
|
|
||
|
|
||
|
systemNotifications OBJECT IDENTIFIER ::= { traps 1 }
|
||
|
-- config changes notification
|
||
|
|
||
|
systemConfigChangeAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoConfigName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a configuration value was changed on the PDU."
|
||
|
::= { systemNotifications 1 }
|
||
|
|
||
|
-- system booting notification
|
||
|
systemBootAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoBootType
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a PDU is booting up."
|
||
|
::= { systemNotifications 2 }
|
||
|
|
||
|
-- firmware update start notification
|
||
|
systemFWUpdateStartAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a firmware update has been initiated."
|
||
|
::= { systemNotifications 3 }
|
||
|
|
||
|
-- firmware update status notification
|
||
|
systemFWUpdateStatusAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoProgress
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that about the progress of the firmware update."
|
||
|
::= { systemNotifications 4 }
|
||
|
|
||
|
-- firmware update complete notification
|
||
|
systemFWUpdateCompleteAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoResult,
|
||
|
trapInfoErrorCode
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that about the progress of the firmware update."
|
||
|
::= { systemNotifications 5 }
|
||
|
|
||
|
-- SecureArray failover notification
|
||
|
systemSecureArrayFailoverAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that the SecureArray is being managed by the identified PDU."
|
||
|
::= { systemNotifications 6 }
|
||
|
|
||
|
-- SecureArray Pdu disconnected notification
|
||
|
systemSecureArrayDisconnectAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that the specified PDU disconnected from the SecureArray."
|
||
|
::= { systemNotifications 7 }
|
||
|
|
||
|
-- SecureArray Pdu connected notification
|
||
|
systemSecureArrayConnectAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that the specified PDU connected to the SecureArray."
|
||
|
::= { systemNotifications 8 }
|
||
|
|
||
|
systemConfigCertAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that the HTTPS certificate was changed on the PDU."
|
||
|
::= { systemNotifications 9 }
|
||
|
|
||
|
|
||
|
userNotifications OBJECT IDENTIFIER ::= { traps 2 }
|
||
|
-- user login notification
|
||
|
userLoginAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user logged onto the PDU."
|
||
|
::= { userNotifications 1 }
|
||
|
|
||
|
-- login fail notification
|
||
|
userLoginFailAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user failed to log onto the PDU."
|
||
|
::= { userNotifications 2 }
|
||
|
|
||
|
-- user add notification
|
||
|
userAddAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user was added to the PDU."
|
||
|
::= { userNotifications 3 }
|
||
|
|
||
|
-- user deleted notification
|
||
|
userDeleteAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user was deleted from the PDU."
|
||
|
::= { userNotifications 4 }
|
||
|
|
||
|
-- user modified notification
|
||
|
userModifiedAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoUserName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user was modified on the PDU."
|
||
|
::= { userNotifications 5 }
|
||
|
|
||
|
-- group add notification
|
||
|
userGroupAddAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoGroupName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user group was added to the PDU."
|
||
|
::= { userNotifications 6 }
|
||
|
|
||
|
-- group deleted notification
|
||
|
userGroupDeleteAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoGroupName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user group was deleted from the PDU."
|
||
|
::= { userNotifications 7 }
|
||
|
|
||
|
-- group modified notification
|
||
|
userGroupModifyAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
trapInfoGroupName,
|
||
|
trapInfoInterface
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a user group was modified on the PDU."
|
||
|
::= { userNotifications 8 }
|
||
|
|
||
|
inletNotifications OBJECT IDENTIFIER ::= { traps 3 }
|
||
|
-- inlet max current
|
||
|
-- inlet min current
|
||
|
-- inlet critical current
|
||
|
|
||
|
branchNotifications OBJECT IDENTIFIER ::= { traps 4 }
|
||
|
-- branch critical current
|
||
|
-- branch max current
|
||
|
-- branch min current
|
||
|
-- branch max voltage
|
||
|
-- branch min voltage
|
||
|
-- branch max power
|
||
|
-- branch min power
|
||
|
-- branch current delta
|
||
|
-- branch power delta
|
||
|
|
||
|
outletNotifications OBJECT IDENTIFIER ::= { traps 5 }
|
||
|
-- outlet state change
|
||
|
-- outlet max current
|
||
|
-- outlet min current
|
||
|
-- outlet max voltage
|
||
|
-- outlet min voltage
|
||
|
-- outlet max power
|
||
|
-- outlet min power
|
||
|
-- outlet current delta
|
||
|
-- outlet power delta
|
||
|
|
||
|
outletStateChangeAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduOutletId,
|
||
|
cpiPudOutletName,
|
||
|
cpiPduOutletStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The outlet state has changed."
|
||
|
::= { outletNotifications 1 }
|
||
|
|
||
|
environNotification OBJECT IDENTIFIER ::= { traps 6 }
|
||
|
-- environ max temp
|
||
|
environMaxTempAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor reached the Maximum limit."
|
||
|
::= { environNotification 1 }
|
||
|
|
||
|
-- environ min temp
|
||
|
environMinTempAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor reached the minimum limit."
|
||
|
::= { environNotification 2 }
|
||
|
|
||
|
-- environ max humidity
|
||
|
environMaxHumidAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor reached the maximum limit."
|
||
|
::= { environNotification 3 }
|
||
|
|
||
|
-- environ min humidity
|
||
|
environMinHumidAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor reached the maximum limit."
|
||
|
::= { environNotification 4 }
|
||
|
|
||
|
-- environ max temp
|
||
|
environMaxWarnTempAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor reached the Maximum limit."
|
||
|
::= { environNotification 5 }
|
||
|
|
||
|
-- environ min temp
|
||
|
environMinWarnTempAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor reached the minimum limit."
|
||
|
::= { environNotification 6 }
|
||
|
|
||
|
-- environ max humidity
|
||
|
environMaxWarnHumidAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor reached the maximum limit."
|
||
|
::= { environNotification 7 }
|
||
|
|
||
|
-- environ min humidity
|
||
|
environMinWarnHumidAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
cpiPduSensorId,
|
||
|
cpiPduSensorName,
|
||
|
cpiPduSensorType,
|
||
|
cpiPduSensorValue
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor reached the maximum limit."
|
||
|
::= { environNotification 8 }
|
||
|
|
||
|
easNotification OBJECT IDENTIFIER ::= { traps 7 }
|
||
|
-- scan pass notification
|
||
|
|
||
|
easScanPassAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- username
|
||
|
trapInfoUserName,
|
||
|
-- pdu name
|
||
|
cpiPduName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A card was scanned and the associated user was authenticated and authorized to access the cabinet."
|
||
|
::= { easNotification 1 }
|
||
|
|
||
|
-- scan fail notification
|
||
|
easScanFailAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A card was scanned but was not authenticated or authorized to access the cabinet."
|
||
|
::= { easNotification 2 }
|
||
|
|
||
|
-- door open notification
|
||
|
easDoorOpenAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a door was opened."
|
||
|
::= { easNotification 3 }
|
||
|
|
||
|
-- door close notification
|
||
|
easDoorCloseAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a door was closed."
|
||
|
::= { easNotification 4 }
|
||
|
|
||
|
-- handle open notification
|
||
|
easLockOpenAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a lock was opened."
|
||
|
::= { easNotification 5 }
|
||
|
|
||
|
-- handle close notification
|
||
|
easLockCloseAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a lock was closed."
|
||
|
::= { easNotification 6 }
|
||
|
|
||
|
-- extended door open notification
|
||
|
easDoorExtOpenAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting."
|
||
|
::= { easNotification 7 }
|
||
|
|
||
|
-- clear extended door open notification
|
||
|
easDoorExtOpenClearAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- door position
|
||
|
cpiPduLockId,
|
||
|
-- door status
|
||
|
cpiPduDoorStatus,
|
||
|
-- lock status
|
||
|
cpiPduLockStatus,
|
||
|
-- force status
|
||
|
cpiPduForceStatus,
|
||
|
-- tamper indicator
|
||
|
cpiPduTamperStatus
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting."
|
||
|
::= { easNotification 8 }
|
||
|
|
||
|
-- clear extended door open notification
|
||
|
easForceUnlockAlert NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
-- pdu cabinet
|
||
|
cpiPduCabinetId,
|
||
|
-- pdu Mac
|
||
|
cpiPduMac,
|
||
|
-- pdu name
|
||
|
cpiPduName,
|
||
|
-- username
|
||
|
trapInfoUserName,
|
||
|
-- door position
|
||
|
cpiPduLockId
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting."
|
||
|
::= { easNotification 9 }
|
||
|
|
||
|
mibconformance OBJECT IDENTIFIER ::= { econnect 600 }
|
||
|
|
||
|