mibs/MIBS/emerson/EES-POWER-MIB

1116 lines
30 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
------------------------------------------------------------
-- Emerson Energy Systems (EES)
-- Power MIB
------------------------------------------------------------
EES-POWER-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
Integer32, Counter32, enterprises
FROM SNMPv2-SMI
TEXTUAL-CONVENTION, DisplayString, DateAndTime
FROM SNMPv2-TC;
powerMIB MODULE-IDENTITY
LAST-UPDATED "201504100857Z"
ORGANIZATION "
Emerson Energy Systems (EES)"
CONTACT-INFO "
Emerson Energy Systems
141 82 Stockholm
Sweden"
DESCRIPTION "
Emerson Energy Systems (EES) Power MIB, revision D."
::= { enterprises 6302 2 1 }
------------------------------------------------------------
-- Node definitions
------------------------------------------------------------
ees OBJECT IDENTIFIER ::= { enterprises 6302 }
global OBJECT IDENTIFIER ::= { ees 2 }
------------------------------------------------------------
-- Textual conventions
------------------------------------------------------------
Status ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "
This integer value represents the operational or administrative
status of the system. Also used as alarm severity.
Depending on situation there may be limits on allowed values.
Operational values:
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
Administrative values:
(7) unmanaged
(8) restricted
(9) testing
(10) disabled"
SYNTAX INTEGER {
unknown(1),
normal(2),
warning(3),
minor(4),
major(5),
critical(6),
unmanaged(7),
restricted(8),
testing(9),
disabled(10) }
StatusChange ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "
Indicates 'activated' (1) or 'deactivated' (2) alarm events."
SYNTAX INTEGER {
activated(1),
deactivated(2) }
------------------------------------------------------------
-- 1.1 Identification of the plant { powerMIB 1 }
------------------------------------------------------------
ident OBJECT IDENTIFIER ::= { powerMIB 1 }
identManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The name of the equipment manufacturer."
::= { ident 1 }
identModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The manufacturers model designation of the power system."
::= { ident 2 }
identControllerFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The firmware (software) version of the controller."
::= { ident 3 }
identName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
The name of the power plant. This object should be set by
the administrator."
::= { ident 4 }
identSNMPCfgVer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The snmp cfg version"
::= { ident 5 }
identControllerSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The serial number of this controller"
::= { ident 6 }
------------------------------------------------------------
-- 1.2 System values { powerMIB 2 }
------------------------------------------------------------
system OBJECT IDENTIFIER ::= { powerMIB 2 }
systemStatus OBJECT-TYPE
SYNTAX Status
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Status of the complete plant (highest alarm). One of
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled"
::= { system 1 }
systemVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
System voltage, stored as mV, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { system 2 }
systemCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
System current, stored as mA, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { system 3 }
systemUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { system 4 }
-- ------------------------------------------------------------------------
-- 1.2.5. Battery group
-- ------------------------------------------------------------------------
psBattery OBJECT IDENTIFIER ::= { system 5 }
psBatteryVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery voltage, stored as mV, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { psBattery 1 }
psTotalBatteryCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery current, stored as mA, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { psBattery 2 }
psBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Calculated capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psBattery 3 }
psBatteryNominalCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
nominal installed capacity, stored as mAh.
The integer 2147483647 represents invalid value."
::= { psBattery 4 }
psBatteryTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery Table."
::= { psBattery 5 }
psBatteryEntry OBJECT-TYPE
SYNTAX PSBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery Measurement Table Entry."
INDEX { psBatteryIndex }
::= { psBatteryTable 1 }
PSBatteryEntry ::= SEQUENCE {
psBatteryIndex Integer32,
psBatteryCurrent Integer32,
psBatteryName DisplayString
}
psBatteryIndex OBJECT-TYPE
SYNTAX Integer32(1..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psBatteryEntry 1 }
psBatteryCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery current in Amps."
::= { psBatteryEntry 2 }
psBatteryName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery shunt name."
::= { psBatteryEntry 3 }
-- ------------------------------------------------------------------------
-- 1.2.6. the psInput group
-- ------------------------------------------------------------------------
psInput OBJECT IDENTIFIER ::= { system 6 }
psInputLineAVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line A voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 1 }
psInputLineBVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line B voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 2 }
psInputLineCVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line C voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 3 }
-- ------------------------------------------------------------------------
-- 1.2.7. the temperatures
-- ------------------------------------------------------------------------
psTemperature OBJECT IDENTIFIER ::= { system 7 }
psTemperature1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The first route temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value."
::= { psTemperature 1 }
psTemperature2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The second route temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value.."
::= { psTemperature 2 }
psTemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Measurement Table."
::= { psTemperature 3 }
psTemperatureEntry OBJECT-TYPE
SYNTAX PSTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Measurement Table Entry."
INDEX { psTemperatureIndex }
::= { psTemperatureTable 1 }
PSTemperatureEntry ::= SEQUENCE {
psTemperatureIndex Integer32,
psTemperatureMeasurement Integer32,
psTemperatureName DisplayString,
psTemperatureType INTEGER,
psTemperatureAlarmStatus INTEGER
}
psTemperatureIndex OBJECT-TYPE
SYNTAX Integer32(1..71)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Number "
::= { psTemperatureEntry 1 }
psTemperatureMeasurement OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Value In Centigrade."
::= { psTemperatureEntry 2 }
psTemperatureName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Configured Temperature Probe Name."
::= { psTemperatureEntry 3 }
psTemperatureType OBJECT-TYPE
SYNTAX INTEGER {
none(0),
ambient(1),
battery(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Type "
::= { psTemperatureEntry 4 }
psTemperatureAlarmStatus OBJECT-TYPE
SYNTAX INTEGER {
high(0),
low(1),
fail(2),
none(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Alarm Status "
::= { psTemperatureEntry 5 }
psStatusCommunication OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
normal(2),
interrupt(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of communication with the Power System. interrupt(3) indicates
some errors occurred between Power System and agent."
::= { system 8 }
psStatusBatteryMode OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
floatCharging(2),
shortTest(3),
bcForTest(4),
manualTesting(5),
planTesting(6),
acFailTesting(7),
acFail(8),
manualBC(9),
autoBC(10),
cyclicBC(11),
masterBC(12),
masterBT(13)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of battery modes,
FloatCharging(2),
ShortTest(3),
BoostChargingForTest(4),
ManualTesting(5),
PlanTesting(6),
ACFailTesting(7),
ACFail(8),
ManualBoostCharging(9),
AutoBoostCharging(10),
CyclicBoostCharging(11),
MasterBoostCharging(12),
MasterBateryTesting(13)."
::= { system 9 }
-- ------------------------------------------------------------------------
-- 1.2.10. the SM series group(only get number of SM series)
-- ------------------------------------------------------------------------
psSMNumber OBJECT IDENTIFIER ::= { system 10 }
psSMACNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM AC module."
::= { psSMNumber 1 }
psSMBATNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM BAT module."
::= { psSMNumber 2 }
psSMIONumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM IO module."
::= { psSMNumber 3 }
-- ------------------------------------------------------------------------
-- 1.2.11. Rectifier group
-- ------------------------------------------------------------------------
psRectifier OBJECT IDENTIFIER ::= { system 11 }
numberOfInstalledRectifiers OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of rectifiers, stored as integer.
The integer 2147483647 represents invalid value."
::= { psRectifier 1 }
numberOfRectifiersCommunicating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of rectifiers communicating, stored as integer.
The integer 2147483647 represents invalid value."
::= { psRectifier 2 }
rectifiersUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psRectifier 3 }
psRectifierTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about indivual rectifiers."
::= { psRectifier 4 }
psRectifierEntry OBJECT-TYPE
SYNTAX PSRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the rectifierInfoTable."
INDEX { psRectifierIndex }
::= { psRectifierTable 1 }
PSRectifierEntry ::= SEQUENCE {
psRectifierIndex Integer32,
psRectifierProductNumber DisplayString,
psRectifierHWVersion DisplayString,
psRectifierSWVersion DisplayString,
psRectifierSerialNumber DisplayString,
psRectifierCurrent Integer32,
psRectifierIdent DisplayString,
psRectifierFail StatusChange
}
psRectifierIndex OBJECT-TYPE
SYNTAX Integer32(1..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psRectifierEntry 1 }
psRectifierProductNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Product Number."
::= { psRectifierEntry 2}
psRectifierHWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Hardware Revision."
::= { psRectifierEntry 3}
psRectifierSWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Software Revision."
::= { psRectifierEntry 4}
psRectifierSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Serial Number."
::= { psRectifierEntry 5}
psRectifierCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Current."
::= { psRectifierEntry 6}
psRectifierIdent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier physical location identifier."
::= { psRectifierEntry 7}
psRectifierFail OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { psRectifierEntry 8}
-- ------------------------------------------------------------------------
-- 1.2.12. the Distribution
-- ------------------------------------------------------------------------
psDistribution OBJECT IDENTIFIER ::= { system 12 }
psTotalLoadCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Total Load current, stored as integer.
The integer 2147483647 represents invalid value."
::= { psDistribution 1 }
psDistributionLoadTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSDistributionLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Table."
::= { psDistribution 2 }
psDistributionLoadEntry OBJECT-TYPE
SYNTAX PSDistributionLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Measurement Table Entry."
INDEX { psDistributionLoadIndex }
::= { psDistributionLoadTable 1 }
PSDistributionLoadEntry ::= SEQUENCE {
psDistributionLoadIndex Integer32,
psDistributionLoadCurrent Integer32,
psDistributionLoadName DisplayString
}
psDistributionLoadIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psDistributionLoadEntry 1 }
psDistributionLoadCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution current in Amps."
::= { psDistributionLoadEntry 2 }
psDistributionLoadName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution name."
::= { psDistributionLoadEntry 3 }
psDistributionGeneralTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSDistributionGeneralEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Table."
::= { psDistribution 3 }
psDistributionGeneralEntry OBJECT-TYPE
SYNTAX PSDistributionGeneralEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Measurement Table Entry."
INDEX { psDistributionGeneralIndex }
::= { psDistributionGeneralTable 1 }
PSDistributionGeneralEntry ::= SEQUENCE {
psDistributionGeneralIndex Integer32,
psDistributionGeneralCurrent Integer32,
psDistributionGeneralName DisplayString
}
psDistributionGeneralIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psDistributionGeneralEntry 1 }
psDistributionGeneralCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution current in Amps."
::= { psDistributionGeneralEntry 2 }
psDistributionGeneralName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution name."
::= { psDistributionGeneralEntry 3 }
-- ------------------------------------------------------------------------
-- 1.2.13. Converter group
-- ------------------------------------------------------------------------
psConverter OBJECT IDENTIFIER ::= { system 13 }
numberOfInstalledConverters OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of converters, stored as integer.
The integer 2147483647 represents invalid value."
::= { psConverter 1 }
numberOfConvertersCommunicating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of converters communicating, stored as integer.
The integer 2147483647 represents invalid value."
::= { psConverter 2 }
convertersUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psConverter 3 }
psConverterVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Converter voltage in mV.
The integer 2147483647 represents invalid value."
::= { psConverter 4 }
psTotalConverterCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Total Converter current in Amps.
The integer 2147483647 represents invalid value."
::= { psConverter 5 }
psConverterTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSConverterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about indivual converters."
::= { psConverter 6 }
psConverterEntry OBJECT-TYPE
SYNTAX PSConverterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the ConverterInfoTable."
INDEX { psConverterIndex }
::= { psConverterTable 1 }
PSConverterEntry ::= SEQUENCE {
psConverterIndex Integer32,
psConverterProductNumber DisplayString,
psConverterHWVersion DisplayString,
psConverterSWVersion DisplayString,
psConverterSerialNumber DisplayString,
psConverterCurrent Integer32,
psConverterIdent DisplayString,
psConverterFail StatusChange }
psConverterIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psConverterEntry 1 }
psConverterProductNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Product Number."
::= { psConverterEntry 2}
psConverterHWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Hardware Revision."
::= { psConverterEntry 3}
psConverterSWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Software Revision."
::= { psConverterEntry 4}
psConverterSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Serial Number."
::= { psConverterEntry 5}
psConverterCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Current."
::= { psConverterEntry 6}
psConverterIdent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter physical location identifier."
::= { psConverterEntry 7}
psConverterFail OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { psConverterEntry 8}
-- ------------------------------------------------------------------------
-- 1.2.14. Control group
-- ------------------------------------------------------------------------
psControl OBJECT IDENTIFIER ::= { system 14 }
controlBatteryTest OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control battery test, start(1), stop (0)."
::= { psControl 1 }
controlRelay8 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay8, close(1), open(0)."
::= { psControl 2 }
controlRelay7 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay7, close(1), open(0)."
::= { psControl 3 }
controlRelay6 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay6, close(1), open(0)."
::= { psControl 4 }
controlRelayTest OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control Relay test, start(1), stop (0)."
::= { psControl 5 }
-- ------------------------------------------------------------------------
-- 1.2.15. EquipmentSignalTable
-- ------------------------------------------------------------------------
psEquipmentSignalTable OBJECT-TYPE
SYNTAX SEQUENCE OF EquipmentSignalTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table of indexed equipment signal values."
::= { system 15 }
equipmentSignalTableEntry OBJECT-TYPE
SYNTAX EquipmentSignalTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the psEquipment Signal Table."
INDEX { psEquipmentSignalTableEntryIndex }
::= { psEquipmentSignalTable 1 }
EquipmentSignalTableEntry ::= SEQUENCE {
psEquipmentSignalTableEntryIndex Integer32,
psEquipmentSignalValue Integer32 }
psEquipmentSignalTableEntryIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The unique sequence number of this equipment signal."
::= { equipmentSignalTableEntry 1 }
psEquipmentSignalValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Indexed equipment signal value."
::= { equipmentSignalTableEntry 2 }
------------------------------------------------------------
-- Alarm trap counter { powerMIB 3 }
------------------------------------------------------------
alarmLastTrapNo OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The sequence number of last submitted alarm trap,
also last row in alarmTrapTable."
::= { powerMIB 3 }
------------------------------------------------------------
-- Active Alarm table { powerMIB 4 }
------------------------------------------------------------
alarmActiveAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF ActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about the currently active alarms."
::= { powerMIB 4 }
activeAlarmEntry OBJECT-TYPE
SYNTAX ActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the alarmTrapTable."
INDEX { alarmIndex }
::= { alarmActiveAlarmTable 1 }
ActiveAlarmEntry ::= SEQUENCE {
alarmIndex Counter32,
alarmTime DateAndTime,
alarmStatusChange StatusChange,
alarmSeverity Status,
alarmDescription DisplayString,
alarmType Integer32 }
alarmIndex OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The unique sequence number of this alarm trap."
::= { activeAlarmEntry 1 }
alarmTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Date and time when event occured (local time), including
timezone if supported by controller."
::= { activeAlarmEntry 2 }
alarmStatusChange OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { activeAlarmEntry 3 }
alarmSeverity OBJECT-TYPE
SYNTAX Status
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The severity of the alarm. One of
(3) warning - OA, lowest level of alarm severity
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of alarm severity"
::= { activeAlarmEntry 4 }
alarmDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Free-text description of alarm."
::= { activeAlarmEntry 5 }
alarmType OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Alarm type, i.e. an integer specifying the type of alarm."
::= { activeAlarmEntry 6 }
------------------------------------------------------------
-- Events/traps { powerMIB 5 }
------------------------------------------------------------
powerEvents OBJECT IDENTIFIER ::= { powerMIB 5 }
alarmTrap NOTIFICATION-TYPE
OBJECTS {
alarmIndex,
alarmTime,
alarmStatusChange,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm occurs (activated) or
returns to normal state (deactivated). Alarm traps are logged
in alarmTrapTable. Variables in this trap:
* alarmIndex - The unique sequence number of this alarm trap.
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmStatusChange - (1) activated or (2) deactivated.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 1 }
alarmActiveTrap NOTIFICATION-TYPE
OBJECTS {
alarmTime,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm occurs (activated)
Variables in this trap
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 2 }
alarmCeaseTrap NOTIFICATION-TYPE
OBJECTS {
alarmTime,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm returns to normal state (clear, deactivated).
Variables in this trap:
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 3 }
------------------------------------------------------------
-- End of MIB definitions
------------------------------------------------------------
END