mibs/MIBS/emerson/NETSURE-MIB-004-A

1822 lines
48 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
------------------------------------------------------------
-- Emerson Energy Systems (EES)
-- Power MIB
------------------------------------------------------------
NETSURE-MIB-004-A DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
Integer32, Counter32, enterprises
FROM SNMPv2-SMI
TEXTUAL-CONVENTION, DisplayString, DateAndTime
FROM SNMPv2-TC;
powerMIB MODULE-IDENTITY
LAST-UPDATED "201401060857Z"
ORGANIZATION "
Emerson Energy Systems (EES)"
CONTACT-INFO "
Emerson Energy Systems
120 07 Stockholm
Sweden"
DESCRIPTION "
Emerson Energy Systems (EES) Power MIB, revision C."
::= { enterprises 6302 2 1 }
------------------------------------------------------------
-- Node definitions
------------------------------------------------------------
ees OBJECT IDENTIFIER ::= { enterprises 6302 }
global OBJECT IDENTIFIER ::= { ees 2 }
------------------------------------------------------------
-- Textual conventions
------------------------------------------------------------
Status ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "
This integer value represents the operational or administrative
status of the system. Also used as alarm severity.
Depending on situation there may be limits on allowed values.
Operational values:
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
Administrative values:
(7) unmanaged
(8) restricted
(9) testing
(10) disabled"
SYNTAX INTEGER {
unknown(1),
normal(2),
warning(3),
minor(4),
major(5),
critical(6),
unmanaged(7),
restricted(8),
testing(9),
disabled(10) }
StatusChange ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "
Indicates 'activated' (1) or 'deactivated' (2) alarm events."
SYNTAX INTEGER {
activated(1),
deactivated(2) }
------------------------------------------------------------
-- 1.1 Identification of the plant { powerMIB 1 }
------------------------------------------------------------
ident OBJECT IDENTIFIER ::= { powerMIB 1 }
identManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The name of the equipment manufacturer."
::= { ident 1 }
identModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The manufacturers model designation of the power system."
::= { ident 2 }
identControllerFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The firmware (software) version of the controller."
::= { ident 3 }
identName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
The name of the power plant. This object should be set by
the administrator."
::= { ident 4 }
identSNMPCfgVer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The name of the power plant. This object should be set by
the administrator."
::= { ident 5 }
------------------------------------------------------------
-- 1.2 System values { powerMIB 2 }
------------------------------------------------------------
system OBJECT IDENTIFIER ::= { powerMIB 2 }
systemStatus OBJECT-TYPE
SYNTAX Status
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Status of the complete plant (highest alarm). One of
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled"
::= { system 1 }
systemVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
System voltage, stored as mV, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { system 2 }
systemCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
System current, stored as mA, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { system 3 }
systemUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { system 4 }
-- ------------------------------------------------------------------------
-- 1.2.5. Battery group
-- ------------------------------------------------------------------------
psBattery OBJECT IDENTIFIER ::= { system 5 }
psBatteryVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery voltage, stored as mV, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { psBattery 1 }
psTotalBatteryCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery current, stored as mA, including positive or negative
sign. The integer 2147483647 represents invalid value."
::= { psBattery 2 }
psBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Calculated capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psBattery 3 }
psBatteryNominalCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
nominal installed capacity, stored as mAh.
The integer 2147483647 represents invalid value."
::= { psBattery 4 }
psBatteryTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery Table."
::= { psBattery 5 }
psBatteryEntry OBJECT-TYPE
SYNTAX PSBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery Measurement Table Entry."
INDEX { psBatteryIndex }
::= { psBatteryTable 1 }
PSBatteryEntry ::= SEQUENCE {
psBatteryIndex Integer32,
psBatteryCurrent Integer32,
psBatteryName DisplayString
}
psBatteryIndex OBJECT-TYPE
SYNTAX Integer32(1..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psBatteryEntry 1 }
psBatteryCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery current in Amps."
::= { psBatteryEntry 2 }
psBatteryName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery shunt name."
::= { psBatteryEntry 3 }
-- ------------------------------------------------------------------------
-- 1.2.6. the psInput group
-- ------------------------------------------------------------------------
psInput OBJECT IDENTIFIER ::= { system 6 }
psInputLineAVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line A voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 1 }
psInputLineBVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line B voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 2 }
psInputLineCVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC line C voltage, stored as mV. The integer 2147483647
represents invalid value."
::= { psInput 3 }
-- ------------------------------------------------------------------------
-- 1.2.7. the temperatures
-- ------------------------------------------------------------------------
psTemperature OBJECT IDENTIFIER ::= { system 7 }
psTemperature1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The first route temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value."
::= { psTemperature 1 }
psTemperature2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The second route temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value.."
::= { psTemperature 2 }
psTemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Measurement Table."
::= { psTemperature 3 }
psTemperatureEntry OBJECT-TYPE
SYNTAX PSTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Measurement Table Entry."
INDEX { psTemperatureIndex }
::= { psTemperatureTable 1 }
PSTemperatureEntry ::= SEQUENCE {
psTemperatureIndex Integer32,
psTemperatureMeasurement Integer32,
psTemperatureName DisplayString,
psTemperatureType INTEGER,
psTemperatureAlarmStatus INTEGER
}
psTemperatureIndex OBJECT-TYPE
SYNTAX Integer32(1..71)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Number "
::= { psTemperatureEntry 1 }
psTemperatureMeasurement OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Value In Centigrade."
::= { psTemperatureEntry 2 }
psTemperatureName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Configured Temperature Probe Name."
::= { psTemperatureEntry 3 }
psTemperatureType OBJECT-TYPE
SYNTAX INTEGER {
none(0),
ambient(1),
battery(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Type "
::= { psTemperatureEntry 4 }
psTemperatureAlarmStatus OBJECT-TYPE
SYNTAX INTEGER {
high(0),
low(1),
fail(2),
none(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Probe Alarm Status "
::= { psTemperatureEntry 5 }
psStatusCommunication OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
normal(2),
interrupt(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of communication with the Power System. interrupt(3) indicates
some errors occurred between Power System and agent."
::= { system 8 }
psStatusBatteryMode OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
floatCharging(2),
shortTest(3),
bcForTest(4),
manualTesting(5),
planTesting(6),
acFailTesting(7),
acFail(8),
manualBC(9),
autoBC(10),
cyclicBC(11),
masterBC(12),
masterBT(13)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of battery modes,
FloatCharging(2),
ShortTest(3),
BoostChargingForTest(4),
ManualTesting(5),
PlanTesting(6),
ACFailTesting(7),
ACFail(8),
ManualBoostCharging(9),
AutoBoostCharging(10),
CyclicBoostCharging(11),
MasterBoostCharging(12),
MasterBateryTesting(13)."
::= { system 9 }
-- ------------------------------------------------------------------------
-- 1.2.10. the SM series group(only get number of SM series)
-- ------------------------------------------------------------------------
psSMNumber OBJECT IDENTIFIER ::= { system 10 }
psSMACNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM AC module."
::= { psSMNumber 1 }
psSMBATNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM BAT module."
::= { psSMNumber 2 }
psSMIONumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SM IO module."
::= { psSMNumber 3 }
-- ------------------------------------------------------------------------
-- 1.2.11. Rectifier group
-- ------------------------------------------------------------------------
psRectifier OBJECT IDENTIFIER ::= { system 11 }
numberOfInstalledRectifiers OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of rectifiers, stored as integer.
The integer 2147483647 represents invalid value."
::= { psRectifier 1 }
numberOfRectifiersCommunicating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of rectifiers communicating, stored as integer.
The integer 2147483647 represents invalid value."
::= { psRectifier 2 }
rectifiersUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psRectifier 3 }
psRectifierTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about indivual rectifiers."
::= { psRectifier 4 }
psRectifierEntry OBJECT-TYPE
SYNTAX PSRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the rectifierInfoTable."
INDEX { psRectifierIndex }
::= { psRectifierTable 1 }
PSRectifierEntry ::= SEQUENCE {
psRectifierIndex Integer32,
psRectifierProductNumber DisplayString,
psRectifierHWVersion DisplayString,
psRectifierSWVersion DisplayString,
psRectifierSerialNumber DisplayString,
psRectifierCurrent Integer32,
psRectifierIdent DisplayString,
psRectifierFail StatusChange
}
psRectifierIndex OBJECT-TYPE
SYNTAX Integer32(1..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psRectifierEntry 1 }
psRectifierProductNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Product Number."
::= { psRectifierEntry 2}
psRectifierHWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Hardware Revision."
::= { psRectifierEntry 3}
psRectifierSWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Software Revision."
::= { psRectifierEntry 4}
psRectifierSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Serial Number."
::= { psRectifierEntry 5}
psRectifierCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Current."
::= { psRectifierEntry 6}
psRectifierIdent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier physical location identifier."
::= { psRectifierEntry 7}
psRectifierFail OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { psRectifierEntry 8}
-- ------------------------------------------------------------------------
-- 1.2.12. the Distribution
-- ------------------------------------------------------------------------
psDistribution OBJECT IDENTIFIER ::= { system 12 }
psTotalLoadCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Total Load current, stored as integer.
The integer 2147483647 represents invalid value."
::= { psDistribution 1 }
psDistributionLoadTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSDistributionLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Table."
::= { psDistribution 2 }
psDistributionLoadEntry OBJECT-TYPE
SYNTAX PSDistributionLoadEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Measurement Table Entry."
INDEX { psDistributionLoadIndex }
::= { psDistributionLoadTable 1 }
PSDistributionLoadEntry ::= SEQUENCE {
psDistributionLoadIndex Integer32,
psDistributionLoadCurrent Integer32,
psDistributionLoadName DisplayString
}
psDistributionLoadIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psDistributionLoadEntry 1 }
psDistributionLoadCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution current in Amps."
::= { psDistributionLoadEntry 2 }
psDistributionLoadName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution name."
::= { psDistributionLoadEntry 3 }
psDistributionGeneralTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSDistributionGeneralEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Table."
::= { psDistribution 3 }
psDistributionGeneralEntry OBJECT-TYPE
SYNTAX PSDistributionGeneralEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Distribution Measurement Table Entry."
INDEX { psDistributionGeneralIndex }
::= { psDistributionGeneralTable 1 }
PSDistributionGeneralEntry ::= SEQUENCE {
psDistributionGeneralIndex Integer32,
psDistributionGeneralCurrent Integer32,
psDistributionGeneralName DisplayString
}
psDistributionGeneralIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Automatically generated index object."
::= { psDistributionGeneralEntry 1 }
psDistributionGeneralCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution current in Amps."
::= { psDistributionGeneralEntry 2 }
psDistributionGeneralName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Distribution name."
::= { psDistributionGeneralEntry 3 }
-- ------------------------------------------------------------------------
-- 1.2.13. Converter group
-- ------------------------------------------------------------------------
psConverter OBJECT IDENTIFIER ::= { system 13 }
numberOfInstalledConverters OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of converters, stored as integer.
The integer 2147483647 represents invalid value."
::= { psConverter 1 }
numberOfConvertersCommunicating OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of converters communicating, stored as integer.
The integer 2147483647 represents invalid value."
::= { psConverter 2 }
convertersUsedCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Used capacity, stored as % of the total capacity.
The integer 2147483647 represents invalid value."
::= { psConverter 3 }
psConverterVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Converter voltage in mV.
The integer 2147483647 represents invalid value."
::= { psConverter 4 }
psTotalConverterCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Total Converter current in Amps.
The integer 2147483647 represents invalid value."
::= { psConverter 5 }
psConverterTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSConverterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about indivual converters."
::= { psConverter 6 }
psConverterEntry OBJECT-TYPE
SYNTAX PSConverterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the ConverterInfoTable."
INDEX { psConverterIndex }
::= { psConverterTable 1 }
PSConverterEntry ::= SEQUENCE {
psConverterIndex Integer32,
psConverterProductNumber DisplayString,
psConverterHWVersion DisplayString,
psConverterSWVersion DisplayString,
psConverterSerialNumber DisplayString,
psConverterCurrent Integer32,
psConverterIdent DisplayString,
psConverterFail StatusChange }
psConverterIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psConverterEntry 1 }
psConverterProductNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Product Number."
::= { psConverterEntry 2}
psConverterHWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Hardware Revision."
::= { psConverterEntry 3}
psConverterSWVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Software Revision."
::= { psConverterEntry 4}
psConverterSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Serial Number."
::= { psConverterEntry 5}
psConverterCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter Current."
::= { psConverterEntry 6}
psConverterIdent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Converter physical location identifier."
::= { psConverterEntry 7}
psConverterFail OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { psConverterEntry 8}
-- ------------------------------------------------------------------------
-- 1.2.14. Control group
-- ------------------------------------------------------------------------
psControl OBJECT IDENTIFIER ::= { system 14 }
controlBatteryTest OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control battery test, start(1), stop (0)."
::= { psControl 1 }
controlRelay8 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay8, close(1), open(0)."
::= { psControl 2 }
controlRelay7 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay7, close(1), open(0)."
::= { psControl 3 }
controlRelay6 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control relay6, close(1), open(0)."
::= { psControl 4 }
controlRelayTest OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "
Control Relay test, start(1), stop (0)."
::= { psControl 5 }
-- ------------------------------------------------------------------------
-- 1.2.15. EquipmentSignalTable
-- ------------------------------------------------------------------------
psEquipmentSignalTable OBJECT-TYPE
SYNTAX SEQUENCE OF EquipmentSignalTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table of indexed equipment signal values."
::= { system 15 }
equipmentSignalTableEntry OBJECT-TYPE
SYNTAX EquipmentSignalTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the psEquipment Signal Table."
INDEX { psEquipmentSignalTableEntryIndex }
::= { psEquipmentSignalTable 1 }
EquipmentSignalTableEntry ::= SEQUENCE {
psEquipmentSignalTableEntryIndex Integer32,
psEquipmentSignalValue Integer32 }
psEquipmentSignalTableEntryIndex OBJECT-TYPE
SYNTAX Integer32(1..268386303)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The unique sequence number of this equipment signal."
::= { equipmentSignalTableEntry 1 }
psEquipmentSignalValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Indexed equipment signal value."
::= { equipmentSignalTableEntry 2 }
-- ------------------------------------------------------------------------
-- 1.2.16. SMDUHCurrentTable
-- ------------------------------------------------------------------------
psSMDUHCurrent OBJECT IDENTIFIER ::= { system 16 }
numberOfInstalledSMDUH OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
number of SMDHU units, stored as integer.
The integer 2147483647 represents invalid value."
::= { psSMDUHCurrent 1 }
psSMDUH1Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH1 Voltage."
::= { psSMDUHCurrent 2 }
psSMDUH2Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH2 Voltage."
::= { psSMDUHCurrent 3 }
psSMDUH3Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH3 Voltage."
::= { psSMDUHCurrent 4 }
psSMDUH4Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH4 Voltage."
::= { psSMDUHCurrent 5 }
psSMDUH5Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH5 Voltage."
::= { psSMDUHCurrent 6 }
psSMDUH6Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH6 Voltage."
::= { psSMDUHCurrent 7 }
psSMDUH7Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDUH7 Voltage."
::= { psSMDUHCurrent 8 }
psSMDUH8Voltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
SMDU8 Voltage."
::= { psSMDUHCurrent 9 }
psSMDUHCurrentTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about SMDUH currents."
::= { psSMDUHCurrent 10 }
psSMDUHCurrentEntry OBJECT-TYPE
SYNTAX PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the SMDUHTable."
INDEX { psSMDUHCurrentIndex }
::= { psSMDUHCurrentTable 1 }
psSMDUHCurrentEntry ::= SEQUENCE {
psSMDUHCurrentIndex Integer32,
psSMDUHCurrent1 Integer32,
psSMDUHCurrent2 Integer32,
psSMDUHCurrent3 Integer32,
psSMDUHCurrent4 Integer32,
psSMDUHCurrent5 Integer32,
psSMDUHCurrent6 Integer32,
psSMDUHCurrent7 Integer32,
psSMDUHCurrent8 Integer32,
psSMDUHCurrent9 Integer32,
psSMDUHCurrent10 Integer32,
psSMDUHCurrent11 Integer32,
psSMDUHCurrent12 Integer32,
psSMDUHCurrent13 Integer32,
psSMDUHCurrent14 Integer32,
psSMDUHCurrent15 Integer32,
psSMDUHCurrent16 Integer32,
psSMDUHCurrent17 Integer32,
psSMDUHCurrent18 Integer32,
psSMDUHCurrent19 Integer32,
psSMDUHCurrent20 Integer32 }
psSMDUHCurrentIndex OBJECT-TYPE
SYNTAX Integer32(1..64)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psSMDUHCurrentEntry 1 }
psSMDUHCurrent1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 1."
::= { psSMDUHCurrentEntry 2}
psSMDUHCurrent2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 2."
::= { psSMDUHCurrentEntry 3}
psSMDUHCurrent3 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 3."
::= { psSMDUHCurrentEntry 4}
psSMDUHCurrent4 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 4."
::= { psSMDUHCurrentEntry 5}
psSMDUHCurrent5 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 5."
::= { psSMDUHCurrentEntry 6}
psSMDUHCurrent6 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 6."
::= { psSMDUHCurrentEntry 7}
psSMDUHCurrent7 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 7."
::= { psSMDUHCurrentEntry 8}
psSMDUHCurrent8 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 8."
::= { psSMDUHCurrentEntry 9}
psSMDUHCurrent9 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 9."
::= { psSMDUHCurrentEntry 10}
psSMDUHCurrent10 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 10."
::= { psSMDUHCurrentEntry 11}
psSMDUHCurrent11 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 11."
::= { psSMDUHCurrentEntry 12}
psSMDUHCurrent12 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 12."
::= { psSMDUHCurrentEntry 13}
psSMDUHCurrent13 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 13."
::= { psSMDUHCurrentEntry 14}
psSMDUHCurrent14 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 14."
::= { psSMDUHCurrentEntry 15}
psSMDUHCurrent15 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 15."
::= { psSMDUHCurrentEntry 16}
psSMDUHCurrent16 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 16."
::= { psSMDUHCurrentEntry 17}
psSMDUHCurrent17 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 17."
::= { psSMDUHCurrentEntry 18}
psSMDUHCurrent18 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 18."
::= { psSMDUHCurrentEntry 19}
psSMDUHCurrent19 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 19."
::= { psSMDUHCurrentEntry 20}
psSMDUHCurrent20 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Current 20."
::= { psSMDUHCurrentEntry 21}
-- ------------------------------------------------------------------------
-- 1.2.17. SMDUHPowerTable
-- ------------------------------------------------------------------------
psSMDUHPower OBJECT IDENTIFIER ::= { system 17 }
psSMDUHPowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about SMDUH power."
::= { psSMDUHPower 1 }
psSMDUHPowerEntry OBJECT-TYPE
SYNTAX PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the SMDUHPowerTable."
INDEX { psSMDUHPowerIndex }
::= { psSMDUHPowerTable 1 }
psSMDUHPowerEntry ::= SEQUENCE {
psSMDUHPowerIndex Integer32,
psSMDUHPower1 Integer32,
psSMDUHPower2 Integer32,
psSMDUHPower3 Integer32,
psSMDUHPower4 Integer32,
psSMDUHPower5 Integer32,
psSMDUHPower6 Integer32,
psSMDUHPower7 Integer32,
psSMDUHPower8 Integer32,
psSMDUHPower9 Integer32,
psSMDUHPower10 Integer32,
psSMDUHPower11 Integer32,
psSMDUHPower12 Integer32,
psSMDUHPower13 Integer32,
psSMDUHPower14 Integer32,
psSMDUHPower15 Integer32,
psSMDUHPower16 Integer32,
psSMDUHPower17 Integer32,
psSMDUHPower18 Integer32,
psSMDUHPower19 Integer32,
psSMDUHPower20 Integer32 }
psSMDUHPowerIndex OBJECT-TYPE
SYNTAX Integer32(1..64)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psSMDUHPowerEntry 1 }
psSMDUHPower1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 1."
::= { psSMDUHPowerEntry 2}
psSMDUHPower2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 2."
::= { psSMDUHPowerEntry 3}
psSMDUHPower3 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 3."
::= { psSMDUHPowerEntry 4}
psSMDUHPower4 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 4."
::= { psSMDUHPowerEntry 5}
psSMDUHPower5 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 5."
::= { psSMDUHPowerEntry 6}
psSMDUHPower6 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 6."
::= { psSMDUHPowerEntry 7}
psSMDUHPower7 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 7."
::= { psSMDUHPowerEntry 8}
psSMDUHPower8 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 8."
::= { psSMDUHPowerEntry 9}
psSMDUHPower9 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 9."
::= { psSMDUHPowerEntry 10}
psSMDUHPower10 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 10."
::= { psSMDUHPowerEntry 11}
psSMDUHPower11 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 11."
::= { psSMDUHPowerEntry 12}
psSMDUHPower12 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 12."
::= { psSMDUHPowerEntry 13}
psSMDUHPower13 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 13."
::= { psSMDUHPowerEntry 14}
psSMDUHPower14 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 14."
::= { psSMDUHPowerEntry 15}
psSMDUHPower15 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 15."
::= { psSMDUHPowerEntry 16}
psSMDUHPower16 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 16."
::= { psSMDUHPowerEntry 17}
psSMDUHPower17 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 17."
::= { psSMDUHPowerEntry 18}
psSMDUHPower18 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 18."
::= { psSMDUHPowerEntry 19}
psSMDUHPower19 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 19."
::= { psSMDUHPowerEntry 20}
psSMDUHPower20 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Power 20."
::= { psSMDUHPowerEntry 21}
-- ------------------------------------------------------------------------
-- 1.2.18. SMDUHEnergyTable
-- ------------------------------------------------------------------------
psSMDUHEnergy OBJECT IDENTIFIER ::= { system 18 }
psSMDUHEnergyTable OBJECT-TYPE
SYNTAX SEQUENCE OF PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about SMDUH energy counters."
::= { psSMDUHEnergy 1 }
psSMDUHEnergyEntry OBJECT-TYPE
SYNTAX PSSMDUHEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the SMDUHEnergyTable."
INDEX { psSMDUHEnergyIndex }
::= { psSMDUHEnergyTable 1 }
psSMDUHEnergyEntry ::= SEQUENCE {
psSMDUHEnergyIndex Integer32,
psSMDUHTotalEnergy1 Integer32,
psSMDUHTotalEnergy2 Integer32,
psSMDUHTotalEnergy3 Integer32,
psSMDUHTotalEnergy4 Integer32,
psSMDUHTotalEnergy5 Integer32,
psSMDUHTotalEnergy6 Integer32,
psSMDUHTotalEnergy7 Integer32,
psSMDUHTotalEnergy8 Integer32,
psSMDUHTotalEnergy9 Integer32,
psSMDUHTotalEnergy10 Integer32,
psSMDUHTotalEnergy11 Integer32,
psSMDUHTotalEnergy12 Integer32,
psSMDUHTotalEnergy13 Integer32,
psSMDUHTotalEnergy14 Integer32,
psSMDUHTotalEnergy15 Integer32,
psSMDUHTotalEnergy16 Integer32,
psSMDUHTotalEnergy17 Integer32,
psSMDUHTotalEnergy18 Integer32,
psSMDUHTotalEnergy19 Integer32,
psSMDUHTotalEnergy20 Integer32 }
psSMDUHEnergyIndex OBJECT-TYPE
SYNTAX Integer32(1..64)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Automatically generated index object."
::= { psSMDUHEnergyEntry 1 }
psSMDUHTotalEnergy1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 1."
::= { psSMDUHEnergyEntry 2}
psSMDUHTotalEnergy2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 2."
::= { psSMDUHEnergyEntry 3}
psSMDUHTotalEnergy3 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 3."
::= { psSMDUHEnergyEntry 4}
psSMDUHTotalEnergy4 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 4."
::= { psSMDUHEnergyEntry 5}
psSMDUHTotalEnergy5 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 5."
::= { psSMDUHEnergyEntry 6}
psSMDUHTotalEnergy6 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 6."
::= { psSMDUHEnergyEntry 7}
psSMDUHTotalEnergy7 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 7."
::= { psSMDUHEnergyEntry 8}
psSMDUHTotalEnergy8 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 8."
::= { psSMDUHEnergyEntry 9}
psSMDUHTotalEnergy9 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 9."
::= { psSMDUHEnergyEntry 10}
psSMDUHTotalEnergy10 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 10."
::= { psSMDUHEnergyEntry 11}
psSMDUHTotalEnergy11 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 11."
::= { psSMDUHEnergyEntry 12}
psSMDUHTotalEnergy12 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 12."
::= { psSMDUHEnergyEntry 13}
psSMDUHTotalEnergy13 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 13."
::= { psSMDUHEnergyEntry 14}
psSMDUHTotalEnergy14 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 14."
::= { psSMDUHEnergyEntry 15}
psSMDUHTotalEnergy15 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 15."
::= { psSMDUHEnergyEntry 16}
psSMDUHTotalEnergy16 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 16."
::= { psSMDUHEnergyEntry 17}
psSMDUHTotalEnergy17 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 17."
::= { psSMDUHEnergyEntry 18}
psSMDUHTotalEnergy18 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 18."
::= { psSMDUHEnergyEntry 19}
psSMDUHTotalEnergy19 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 19."
::= { psSMDUHEnergyEntry 20}
psSMDUHTotalEnergy20 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SMDUH Total Energy 20."
::= { psSMDUHEnergyEntry 21}
------------------------------------------------------------
-- Alarm trap counter { powerMIB 3 }
------------------------------------------------------------
alarmLastTrapNo OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The sequence number of last submitted alarm trap,
also last row in alarmTrapTable."
::= { powerMIB 3 }
------------------------------------------------------------
-- Active Alarm table { powerMIB 4 }
------------------------------------------------------------
alarmActiveAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF ActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
Table holding information about the currently active alarms."
::= { powerMIB 4 }
activeAlarmEntry OBJECT-TYPE
SYNTAX ActiveAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "
An entry (conceptual row) in the alarmTrapTable."
INDEX { alarmIndex }
::= { alarmActiveAlarmTable 1 }
ActiveAlarmEntry ::= SEQUENCE {
alarmIndex Counter32,
alarmTime DateAndTime,
alarmStatusChange StatusChange,
alarmSeverity Status,
alarmDescription DisplayString,
alarmType Integer32 }
alarmIndex OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The unique sequence number of this alarm trap."
::= { activeAlarmEntry 1 }
alarmTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Date and time when event occured (local time), including
timezone if supported by controller."
::= { activeAlarmEntry 2 }
alarmStatusChange OBJECT-TYPE
SYNTAX StatusChange
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The type of alarm change. One of
(1) activated
(2) deactivated"
::= { activeAlarmEntry 3 }
alarmSeverity OBJECT-TYPE
SYNTAX Status
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The severity of the alarm. One of
(3) warning - OA, lowest level of alarm severity
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of alarm severity"
::= { activeAlarmEntry 4 }
alarmDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Free-text description of alarm."
::= { activeAlarmEntry 5 }
alarmType OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
Alarm type, i.e. an integer specifying the type of alarm."
::= { activeAlarmEntry 6 }
------------------------------------------------------------
-- Events/traps { powerMIB 5 }
------------------------------------------------------------
powerEvents OBJECT IDENTIFIER ::= { powerMIB 5 }
alarmTrap NOTIFICATION-TYPE
OBJECTS {
alarmIndex,
alarmTime,
alarmStatusChange,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm occurs (activated) or
returns to normal state (deactivated). Alarm traps are logged
in alarmTrapTable. Variables in this trap:
* alarmIndex - The unique sequence number of this alarm trap.
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmStatusChange - (1) activated or (2) deactivated.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 1 }
alarmActiveTrap NOTIFICATION-TYPE
OBJECTS {
alarmTime,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm occurs (activated)
Variables in this trap
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 2 }
alarmCeaseTrap NOTIFICATION-TYPE
OBJECTS {
alarmTime,
alarmSeverity,
alarmDescription,
alarmType }
STATUS current
DESCRIPTION "
An alarm trap is sent when an alarm returns to normal state (clear, deactivated).
Variables in this trap:
* alarmTime - Date and time when event occured (local time),
including timezone if supported by controller.
* alarmSeverity - Integer describing the severity of the alarm.
* alarmDescription - Free-text description of alarm.
* alarmType - Integer indicating type of alarm."
::= { powerEvents 3 }
------------------------------------------------------------
-- End of MIB definitions
------------------------------------------------------------
END