mibs/MIBS/ict/ICT-MODULAR-POWER-SYSTEM-MIB

314 lines
7.8 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
-- ICT MIB file for ICT Modular Power System.
--
-- Date Version
-- =============================
-- 1/5/18 v1.01
--
ICT-MODULAR-POWER-SYSTEM-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
powerSystem OBJECT IDENTIFIER ::= { ictPower 13 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Model Number"
::= { powerSystem 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device Name"
::= { powerSystem 2 }
deviceHardware OBJECT-TYPE
SYNTAX INTEGER (0..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Hardware Version"
::= { powerSystem 3 }
deviceFirmware OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Firmware Version"
::= { powerSystem 4 }
deviceMacAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "MAC Address"
::= { powerSystem 5 }
inputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Input Voltage (VAC)"
::= { powerSystem 6 }
outputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Voltage (VDC)"
::= { powerSystem 7 }
outputCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Total System Current (Amps)"
::= { powerSystem 8 }
outputEnable OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Output Enable Status (a value of '1' indicates Output is Enabled, and a value of '2' indicates Output is Disabled. Output cannot be disabled during an AC Failure)"
::= { powerSystem 9 }
moduleTable OBJECT-TYPE
SYNTAX SEQUENCE OF ModuleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Module Table"
::= { powerSystem 10 }
moduleEntry OBJECT-TYPE
SYNTAX ModuleEntry
ACCESS not-accessible
STATUS mandatory
INDEX { moduleNumber }
::= { moduleTable 1 }
ModuleEntry ::=
SEQUENCE {
moduleNumber INTEGER,
moduleStatus INTEGER,
moduleType INTEGER,
moduleVoltage DisplayString,
moduleCurrentA DisplayString,
moduleCurrentB DisplayString,
moduleCurrentC DisplayString,
moduleCurrentD DisplayString,
moduleControlA INTEGER,
moduleControlB INTEGER,
moduleControlC INTEGER,
moduleControlD INTEGER
}
moduleNumber OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Number"
::= { moduleEntry 1 }
moduleStatus OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), ok(2), alarm(3) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Status"
::= { moduleEntry 2 }
moduleType OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), power(2), battery(3), distribution(4) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Type ('1' indicates Module is NOT INSTALLED,'2' indicates POWER Module,'3' indicates BATTERY Module, and '4' indicates DISTRIBUTION Module)"
::= { moduleEntry 3 }
moduleVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Voltage (VDC)"
::= { moduleEntry 4 }
moduleCurrentA OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 1 Current (Amps)"
::= { moduleEntry 5 }
moduleCurrentB OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 2 Current (Amps)"
::= { moduleEntry 6 }
moduleCurrentC OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 3 Current (Amps)"
::= { moduleEntry 7 }
moduleCurrentD OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 4 Current (Amps)"
::= { moduleEntry 8 }
moduleControlA OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 1 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 9 }
moduleControlB OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 2 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 10 }
moduleControlC OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 3 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 11 }
moduleControlD OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 4 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 12 }
alarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Alarm Input Table"
::= { powerSystem 11 }
alarmEntry OBJECT-TYPE
SYNTAX AlarmEntry
ACCESS not-accessible
STATUS mandatory
INDEX { alarmNumber }
::= { alarmTable 1 }
AlarmEntry ::=
SEQUENCE {
alarmNumber INTEGER,
alarmName DisplayString,
alarmStatus INTEGER
}
alarmNumber OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Number"
::= { alarmEntry 1 }
alarmName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Name"
::= { alarmEntry 2 }
alarmStatus OBJECT-TYPE
SYNTAX INTEGER { inactive(1), ready(2), alarm(3) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)"
::= { alarmEntry 3 }
--
-- Trap definitions:
--
moduleAlarmTrap TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { moduleNumber }
DESCRIPTION "Trap generated when a Module Alarm is triggered"
::= 101
alarmInputTrap TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is activated"
::= 102
acFailAlarmTrap TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the AC Failure Alarm is triggered"
::= 103
sysCurrentLimitTrap TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the System Current Limit Alarm is triggered"
::= 104
moduleAlarmClear TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { moduleNumber }
DESCRIPTION "Trap generated when a Module Alarm is cleared"
::= 111
alarmInputClear TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is cleared"
::= 112
acFailAlarmClear TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the AC Failure Alarm is cleared"
::= 113
sysCurrentLimitClear TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the System Current Limit Alarm is cleared"
::= 114
batteryTestStart TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test is started"
::= 121
batteryTestComplete TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test completes successfully"
::= 122
batteryTestFail TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test fails"
::= 123
batteryEqualiseStart TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Equalise Charge is started"
::= 124
batteryEqualiseComplete TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Equalise Charge completes"
::= 125
END