IMCO-LS110-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE,
Counter32, Integer32, Gauge32,
TimeTicks, IpAddress,
enterprises
FROM SNMPv2-SMI
TRAP-TYPE FROM RFC-1215;
mib-AN-Dcz-SDS MODULE-IDENTITY
LAST-UPDATED "201702090000Z"
ORGANIZATION "ViaNet.sk"
CONTACT-INFO
" Ivan Mochnac
ViaNet
-
-
SK EUROPE
-
vianet@vianet.sk"
DESCRIPTION
"The MIB module to describe PSMSmicro version of SDS."
REVISION "201702090000Z"
DESCRIPTION
"PSMSmicro, by ViaNet.sk."
::= { enterprises 33283 }
--
-- MIB file definition for device: PSMSmicro
--
sdsxpublic OBJECT IDENTIFIER ::= { mib-AN-Dcz-SDS 1 }
sdsBIGandSTSW OBJECT IDENTIFIER ::= { sdsxpublic 30 }
-- ****************************************************************************
sdsOptoInput OBJECT IDENTIFIER ::= { sdsBIGandSTSW 2 }
opto1 OBJECT-TYPE
SYNTAX INTEGER {
activeSignalPresent(0),
noSignal(32768)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current OPTO1 binary input status."
::= { sdsOptoInput 1 }
opto2 OBJECT-TYPE
SYNTAX INTEGER {
activeSignalPresent(0),
noSignal(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current OPTO2 binary input status."
::= { sdsOptoInput 2 }
opto3 OBJECT-TYPE
SYNTAX INTEGER {
activeSignalPresent(0),
noSignal(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current Mains (OPTO3) binary input status."
::= { sdsOptoInput 3 }
-- ****************************************************************************
sdsOutputRelays OBJECT IDENTIFIER ::= { sdsBIGandSTSW 3 }
sdsOutputRelay1 OBJECT IDENTIFIER ::= { sdsOutputRelays 1 }
sdsRE1state OBJECT-TYPE
SYNTAX INTEGER {
off(0),
activated(255)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current RELAY 1 output status."
::= { sdsOutputRelay1 1 }
sdsOutputRelay2 OBJECT IDENTIFIER ::= { sdsOutputRelays 2 }
sdsRE2state OBJECT-TYPE
SYNTAX INTEGER {
off(0),
activated(255)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current RELAY 2 output status."
::= { sdsOutputRelay2 1 }
sdsOutputRelay3 OBJECT IDENTIFIER ::= { sdsOutputRelays 3 }
sdsRE3state OBJECT-TYPE
SYNTAX INTEGER {
off(0),
activated(255)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current RELAY 3 output status."
::= { sdsOutputRelay3 1 }
-- ****************************************************************************
sdsADCinputs OBJECT IDENTIFIER ::= { sdsBIGandSTSW 5 }
sdsADCitem0 OBJECT IDENTIFIER ::= { sdsADCinputs 1 }
sdsTempSensValue OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature Sensor (C) multiplied by 100."
::= { sdsADCitem0 3 }
sdsTempSensName OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User name for the analog temperature sensor."
::= { sdsADCitem0 4 }
-- ****************************************************************************
sdsADCvalues OBJECT IDENTIFIER ::= { sdsBIGandSTSW 7 }
sdsMaximumLoad OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum Load (W) multiplied by 10."
::= { sdsADCvalues 2 }
sdsAlarmText OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SDS Alarm Text."
::= { sdsADCvalues 3 }
sdsOutputVoltage1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output voltage U1 (V) multiplied by 100."
::= { sdsADCvalues 4 }
sdsOutputVoltage2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output voltage U2 (V) multiplied by 100."
::= { sdsADCvalues 5 }
sdsOutputCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output current I (A) multiplied by 10."
::= { sdsADCvalues 6 }
sdsBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Capacity (%) multiplied by 10."
::= { sdsADCvalues 7 }
sdsLoad OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Load (%) multiplied by 10."
::= { sdsADCvalues 8 }
sdsCapTestTime OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time (min) of last Capacity Test."
::= { sdsADCvalues 9 }
-- ****************************************************************************
sdsGeneralInfoEntry OBJECT IDENTIFIER ::= { sdsBIGandSTSW 8 }
sdsManufacturer OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Manufacturer of the device."
::= { sdsGeneralInfoEntry 80 }
sdsModel OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model (type) of the device."
::= { sdsGeneralInfoEntry 81 }
sdsName OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name/Location of the device."
::= { sdsGeneralInfoEntry 82 }
sdsSerialNumber OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the device."
::= { sdsGeneralInfoEntry 83 }
sdsSoftware OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software version of the device."
::= { sdsGeneralInfoEntry 84 }
-- ****************************************************************************
-- ****************************************************************************
-- TRAP-SDS-MICRO-MIB DEFINITIONS
-- ****************************************************************************
opto1-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { opto1 }
DESCRIPTION "TRAP: optical input 1 status."
::= 100
opto2-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { opto2 }
DESCRIPTION "TRAP: optical input 2 status."
::= 101
opto3-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { opto3 }
DESCRIPTION "TRAP: optical input 3 status."
::= 102
-- next
sdsRE1state-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsRE1state }
DESCRIPTION "TRAP: Current RELAY 1 output status."
::= 150
sdsRE2state-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsRE2state }
DESCRIPTION "TRAP: Current RELAY 2 output status."
::= 153
-- next
sdsTempSensValue-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsTempSensValue }
DESCRIPTION "TRAP: Temperature Sensor (C) multiplied by 100."
::= 222
sdsTempSensName-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsTempSensName }
DESCRIPTION "TRAP: User name for analog temperature sensor."
::= 223
-- next
sdsMaximumLoad-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsMaximumLoad }
DESCRIPTION "TRAP: SDS Maximum Load-trap."
::= 401
sdsAlarmText-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsAlarmText }
DESCRIPTION "TRAP: SDS Alarm Text."
::= 402
sdsOutputVoltage1-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsOutputVoltage1 }
DESCRIPTION "TRAP: SDS Output Voltage1-trap."
::= 403
sdsOutputVoltage2-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsOutputVoltage2 }
DESCRIPTION "TRAP: SDS Outpur Voltage2-trap."
::= 404
sdsOutputCurrent-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsOutputCurrent }
DESCRIPTION "TRAP: SDS Output current-trap."
::= 405
sdsBatteryCapacity-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsBatteryCapacity }
DESCRIPTION "TRAP: SDS Battery Capacity-trap."
::= 406
sdsLoad-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsLoad }
DESCRIPTION "TRAP: SDS Load-trap."
::= 407
sdsCapTestTime-trap TRAP-TYPE
-- STATUS current
ENTERPRISE mib-AN-Dcz-SDS
VARIABLES { sdsCapTestTime }
DESCRIPTION "TRAP: SDS CapTestTime-trap."
::= 408
-- end