mibs/MIBS/liebert/LIEBERT-GP-COND-MIB

4817 lines
180 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
LIEBERT-GP-CONDITIONS-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
Gauge32,
TimeTicks,
Unsigned32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
lgpConditions,
liebertConditionsModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsConditionsModule MODULE-IDENTITY
LAST-UPDATED "201302120000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Gregory M. Hoge"
DESCRIPTION
"The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2008,2013 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "201302120000Z"
DESCRIPTION
"Added Surge Protection Device to lgpConditionCondenserTVSSFailure
DESCRIPTION"
REVISION "200811170000Z"
DESCRIPTION
"Added support for NXL unit."
REVISION "200807020000Z"
DESCRIPTION
"o Expanded condtions table with new columns with a set of richer
alarm/condition properties.
o Added additional reference columns to conditions table to allow the
same alarm to be active on multiple instances of an item.
"
REVISION "200801100000Z"
DESCRIPTION
"Modified contact email address and added lgpNetworkName object."
REVISION "200705290000Z"
DESCRIPTION
"Added support for XDF Unit."
REVISION "200608150000Z"
DESCRIPTION
"Added support for HP release and a condition for firmware corrupt."
REVISION "200602220000Z"
DESCRIPTION
"Added support for Liebert DS Unit."
::= { liebertConditionsModuleReg 1 }
-- =============================================================================
-- lgpConditions - Liebert Conditions Registrations
-- =============================================================================
lgpConditionsWellKnown OBJECT IDENTIFIER
-- STATUS current
-- DESCRIPTION
-- "Liebert well known conditions are defined by OIDs that reside
-- in this sub-tree."
::= { lgpConditions 1 }
lgpConditionsPresent OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of conditions (rows) in the lgpConditionsTable."
::= { lgpConditions 2 }
lgpConditionsTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpConditionEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of condition table entries. The table contains zero, one,
or many rows at any moment, depending upon the number of conditions
in effect. The number of rows in the table is given by
(lgpConditionsPresent). The table is initially empty at agent startup.
The agent creates a row in the table each time a condition is detected
and deletes that row subject to the following rules:
Rows are removed from the table based on the following rules:
1. If a condition does not require acknowledgement
(see 'lgpConditionAckReq') the condition is removed as soon as
the issue clears (see 'lgpConditionCurrentState').
2. If a condition requires acknowledgement (see 'lgpConditionAckReq')
the condition is removed as soon as the issue clears
(see 'lgpConditionCurrentState') AND the condition is acknowledged
(see 'lgpConditionAcknowledged').
3. If the columns 'lgpConditionCurrentState' and
'lgpConditionAcknowledged' are not present for the condition
then the condition will be removed as soon as the issue causing
the condition clears.
The agent creates the first row with lgpConditionId equal to 1,
and increments the value of 'lgpConditionId' each time a new row is
created, wrapping to the first free value greater than or equal to 1
when the maximum value of lgpConditionId would otherwise be exceeded.
The number of rows in the table at any given time is reflected by
the value of 'lgpConditionsPresent'.
"
::= { lgpConditions 3 }
lgpConditionEntry OBJECT-TYPE
SYNTAX LgpConditionEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpConditionsTable'. A row in this table cannot be created
or deleted by SNMP operations on columns of the table."
INDEX { lgpConditionId }
::= { lgpConditionsTable 1 }
LgpConditionEntry ::= SEQUENCE {
lgpConditionId Unsigned32,
lgpConditionDescr OBJECT IDENTIFIER,
lgpConditionTime TimeTicks,
lgpConditionTableRef OBJECT IDENTIFIER,
lgpConditionTableRowRef OBJECT IDENTIFIER,
lgpConditionType INTEGER,
lgpConditionCurrentState INTEGER,
lgpConditionSeverity INTEGER,
lgpConditionAcknowledged INTEGER,
lgpConditionAckReq INTEGER
}
lgpConditionId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique identifier for a condition. This value must remain
constant between agent initializations. This OID is used as
an index to identify a row in the table 'lgpConditionsTable'."
::= { lgpConditionEntry 1 }
lgpConditionDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to a condition description object. The object
referenced should not be accessible, but rather be used to provide
a unique description."
::= { lgpConditionEntry 2 }
lgpConditionTime OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime when the condition occurred (became active)."
::= { lgpConditionEntry 3 }
lgpConditionTableRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object will be included as a varbind in some
rows of the table. It is a reference to a table object in
the MIB. The value of this object will be the OID of a table
that the object that the condition applies to is defined.
The table row corresponding to this object will also contain
a varbind 'lgpConditionTableRowRef' that will specify which
instance (row) in the referenced table the object is defined in.
Example:
TABLE ROW:
lgpConditionId 5
lgpConditionDescr lgpConditionRcpBranchBreakerOpen
lgpConditionTime 393884848
lgpConditionTableRef lgpPduRbTable
lgpConditionTableRowRef lgpPduRbEntryId.1.4
lgpConditionType alarm
lgpConditionCurrentState active
lgpConditionSeverity major
lgpConditionAcknowledged acknowledged
lgpConditionAckReq required
In the above example the breaker opened for a Receptacle branch.
The specific receptacle branch is specified by the additional
varbind (lgpEventParmTableRowRef). In this case the notification
is for the 4th receptacle branch on the 1st PDU in the cluster.
"
::= { lgpConditionEntry 5 }
lgpConditionTableRowRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a reference to the (cell) in the table specified by the
companion varbind (lgpConditionTableRef) in this condition.
The row in the table where this cell exists represents the object
that this condition applies to.
Example:
TABLE ROW:
lgpConditionId 5
lgpConditionDescr lgpConditionRcpBranchBreakerOpen
lgpConditionTime 393884848
lgpConditionTableRef lgpPduRbTable
lgpConditionTableRowRef lgpPduRbEntryId.1.4
lgpConditionType
lgpConditionCurrentState active
lgpConditionSeverity major
lgpConditionAcknowledged acknowledged
lgpConditionAckReq required
The table containing the definition of the receptacle branch
(lgpPduRbTable) is given by the varbind (lgpConditionTableRef)
The specific receptacle branch (instance) is specified by the
varbind (lgpConditionTableRowRef). In this case the condition
is for the 4th receptacle branch on the 1st PDU in the PDU cluster.
If one wanted to retrieve the serial number for this
receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.
"
::= { lgpConditionEntry 6 }
lgpConditionType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
message(2),
warning(4),
alarm(6),
fault(8)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of condition in this row in the table."
::= { lgpConditionEntry 10 }
lgpConditionCurrentState OBJECT-TYPE
SYNTAX INTEGER
{
active(1),
inactive(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indication of the current state of the event. If the state
is 'active' then the condition currently exists. If the
state is 'inactive' then the condition no longer exists (i.e.
the situation causing the condition has cleared or been
resolved). The behavior of some devices is to remove
the condition from this table when the condition clears.
The behavior of other devices is to leave the condition
entry in the table until the condition is acknowledged (
see lgpConditionAcknowledged and lgpConditionAckReq)."
::= { lgpConditionEntry 12 }
lgpConditionSeverity OBJECT-TYPE
SYNTAX INTEGER
{
not-applicable(0),
minor(3),
major(6),
critical(9)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This represents the relative severity of the condition."
::= { lgpConditionEntry 14 }
lgpConditionAcknowledged OBJECT-TYPE
SYNTAX INTEGER
{
notAcknowledged(1),
acknowledged(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This indicates if the condition has been acknowledged.
If the value is 'notAcknowledged' then the condition has
not been acknowledged. If the value is 'acknowledged'
then the condition has been acknowledged. Writing a value
of 'acknowledged' to this object acknowledges the condition
and the value will be changed to 'acknowledged'.
If the current state of the condition is 'active'
(see lgpConditionCurrentState) the condition will, for all
devices remain in the table regardless of the state of the
'lgpConditionAcknowledged' object.
If the 'lgpConditionAckReq' is 'notRequired' or this column
does not exist for the row then this object has no affect on
the duration the condition stays in the lgpConditionsTable.
If the 'lgpConditionAckReq' is 'required' then the condition
will remain in the condition table until both the
'lgpConditionCurrentState' is 'inactive' AND
'lgpConditionAcknowledged' is 'acknowledged'.
"
::= { lgpConditionEntry 18 }
lgpConditionAckReq OBJECT-TYPE
SYNTAX INTEGER
{
required(1),
notRequired(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This indicates if the corresponding condition does or does not
require user acknowledgement. Conditions that require
user acknowledgement will have a value of 'required'. Those
conditions that do not require user acknowledgement will have
a value of 'notRequired' or in some devices the column may
not be present at all.
If a condition requires acknowledgement it will remain in the
table until both the 'lgpConditionCurrentState' and
'lgpConditionAcknowledged' are 'inactive' and 'acknowledged'
respectively (see lgpConditionAcknowledged).
If a condition does not require acknowledgement it will
be removed from the table as soon as its
'lgpConditionCurrentState' is 'inactive'.
"
::= { lgpConditionEntry 19 }
-- =============================================================================
-- lgpConditionControl - Condition Control Group
-- =============================================================================
lgpConditionControl OBJECT IDENTIFIER
-- STATUS current
-- DESCRIPTION
-- "Items under this sub-tree allow the user to control actions
-- associated with conditions."
::= { lgpConditions 4 }
lgpConditionControlEventReset OBJECT-TYPE
SYNTAX INTEGER
{
noAction(1),
resetAll(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Event Reset Command. This command will reset all of the
device's events. On some units, when an event is activated, a
'set' field is also marked and maintained even when the event has
become inactive. The 'set' field is only cleared when the user
clears it and the event is no longer active. This item will clear
the 'set' field for all events that are not active."
::= { lgpConditionControl 1 }
lgpConditionControlEventAck OBJECT-TYPE
SYNTAX INTEGER
{
noAction(1),
ackAll(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Event Acknowledge Command. This command will acknowledge all of the
device's events."
::= { lgpConditionControl 2 }
lgpConditionControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpConditionControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of condition control table entries. The table contains zero, one,
or many rows at any moment, depending upon the number of conditions that
are controllable by the unit. This table does not necessarily contain all
conditions supported by the unit. This table only contains conditions that
are end-user modifiable."
::= { lgpConditionControl 20 }
lgpConditionControlEntry OBJECT-TYPE
SYNTAX LgpConditionControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpConditionControlTable'. A row in this table cannot be created
or deleted by user initiated SNMP operations on columns of the table."
INDEX { lgpConditionControlIndex }
::= { lgpConditionControlTable 1 }
LgpConditionControlEntry ::= SEQUENCE {
lgpConditionControlIndex Unsigned32,
lgpConditionControlDescr OBJECT IDENTIFIER,
lgpConditionControlEnableStatus INTEGER,
lgpConditionControlType INTEGER,
lgpConditionControlEnableCapability INTEGER
}
lgpConditionControlIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the nth element of the table."
::= { lgpConditionControlEntry 1 }
lgpConditionControlDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to an Object Identifier (OID) representing a unique
condition. The referenced OID is used solely for identification
purposes.
The object identifier referenced here will be the same object
identifier referenced in the lgpConditionsTable (column:
lgpConditionDescr) when the condition is activated."
::= { lgpConditionControlEntry 2 }
lgpConditionControlEnableStatus OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
enabled(1),
disabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value in this column determines if the device is currently
capable of generating this event. If the value is 'enabled' then
the event will be generated if the condition indicated by
lgpConditionControlDescr becomes active. If the value is
'disabled' the device will never generate the event. This value is
stored on the managed device.
Some devices do not allow write access to some entries in this
column. The 'lgpConditionControlEnableCapability' column indicates
whether this entry can be written."
::= { lgpConditionControlEntry 3 }
lgpConditionControlType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
message(2),
warning(4),
alarm(6),
fault(8)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The 'type' assigned or configured for this condition. The value
assigned to the condition here is displayed in the
lgpConditionsTable (column: lgpConditionType). For some units this
is user configurable. This value is stored on the managed device."
::= { lgpConditionControlEntry 4 }
lgpConditionControlEnableCapability OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
readonly(1),
readwrite(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Some devices do not allow write access to some entries in the
'lgpConditionControlEnableStatus' column. This column indicates
whether the 'lgpConditionControlEnableStatus' entry for this row
can be written."
::= { lgpConditionControlEntry 5 }
lgpConditionDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ASCII text description for the condition."
::= { lgpConditions 5 }
lgpNetworkName OBJECT-TYPE
SYNTAX DisplayString (SIZE (255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The network name in a node.domain.com like format. This object is
intended to be used as a varbind object by other notifications that
have a context of a network address. As an example the
lgpAgentDnsLookupFailure trap which describes a network name that
is failing or has failed to be resolved from a Domain Name Service (DNS)
lookup.
Refer to RFC 952 for further information."
::= { lgpConditions 6 }
-- =============================================================================
-- lgpConditions - Additional Liebert Conditions Registrations
-- =============================================================================
lgpFlexConditions OBJECT IDENTIFIER
-- STATUS current
-- DESCRIPTION
-- "Liebert well known Flexible conditions are defined by OIDs that reside
-- in this sub-tree. These OIDs can be found in the
-- LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB which is located in the file
-- LIEBERT_GP_FLEXIBLE_COND.MIB."
::= { lgpConditions 7 }
-- =============================================================================
-- lgpConditionsWellKnown - Liebert "well-known" conditions
-- =============================================================================
lgpConditionHighTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold."
::= { lgpConditionsWellKnown 1 }
lgpConditionLowTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold."
::= { lgpConditionsWellKnown 2 }
lgpConditionHighHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity has exceeded the high humidity threshold."
::= { lgpConditionsWellKnown 3 }
lgpConditionLowHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity is below the low humidity threshold."
::= { lgpConditionsWellKnown 4 }
lgpConditionLossOfAirflow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of air flow."
::= { lgpConditionsWellKnown 5 }
lgpConditionLossOfAirflow1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of air flow at sensor 1."
::= { lgpConditionLossOfAirflow 1 }
lgpConditionLossOfAirflow2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of air flow at sensor 2."
::= { lgpConditionLossOfAirflow 2 }
lgpConditionLossOfAirflowBlower1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of air flow from blower 1."
::= { lgpConditionLossOfAirflow 3 }
lgpConditionLossOfAirflowAllBlowers OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No air flow through the unit due to failure of all blowers."
::= { lgpConditionLossOfAirflow 4 }
lgpConditionChangeFilter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a condition indicating the air filter
should be changed."
::= { lgpConditionsWellKnown 6 }
lgpConditionCompressorHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an excessive head pressure condition."
::= { lgpConditionsWellKnown 7 }
lgpConditionCompressor1HighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 1."
::= { lgpConditionCompressorHighHeadPressure 1 }
lgpConditionCompressor1AHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 1A."
::= { lgpConditionCompressor1HighHeadPressure 1 }
lgpConditionCompressor1BHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 1B."
::= { lgpConditionCompressor1HighHeadPressure 2 }
lgpConditionCompressor2HighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 2."
::= { lgpConditionCompressorHighHeadPressure 2 }
lgpConditionCompressor2AHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 2A."
::= { lgpConditionCompressor2HighHeadPressure 1 }
lgpConditionCompressor2BHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 2B."
::= { lgpConditionCompressor2HighHeadPressure 2 }
lgpConditionCompressor3HighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 3."
::= { lgpConditionCompressorHighHeadPressure 3 }
lgpConditionCompressor4HighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected excessive head pressure in compressor 4."
::= { lgpConditionCompressorHighHeadPressure 4 }
lgpConditionCompressorOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a compressor overload condition."
::= { lgpConditionsWellKnown 8 }
lgpConditionCompressor1Overload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition on compressor 1."
::= { lgpConditionCompressorOverload 1 }
lgpConditionCompressor2Overload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition on compressor 2."
::= { lgpConditionCompressorOverload 2 }
lgpConditionCompressor3Overload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition on compressor 3."
::= { lgpConditionCompressorOverload 3 }
lgpConditionCompressor4Overload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition on compressor 4."
::= { lgpConditionCompressorOverload 4 }
lgpConditionCompressorShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A compressor has exceeded the maximum number of starts in a
minimum time period."
::= { lgpConditionsWellKnown 9 }
lgpConditionCompressor1ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 1.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressorShortCycle 1 }
lgpConditionCompressor1AShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 1A.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressor1ShortCycle 1 }
lgpConditionCompressor1BShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 1B.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressor1ShortCycle 2 }
lgpConditionCompressor2ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 2.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressorShortCycle 2 }
lgpConditionCompressor2AShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 2A.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressor2ShortCycle 1 }
lgpConditionCompressor2BShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 2B.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressor2ShortCycle 2 }
lgpConditionCompressor3ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 3.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressorShortCycle 3 }
lgpConditionCompressor4ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycle event on compressor 4.
The compressor has exceeded the maximum number of starts for
specified amount of time."
::= { lgpConditionCompressorShortCycle 4 }
lgpConditionCompressorLowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure at a compressor inlet has dropped below the
minimum setting."
::= { lgpConditionsWellKnown 10 }
lgpConditionCompressor1LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure at compressor 1 inlet has dropped below the
minimum setting."
::= { lgpConditionCompressorLowSuctionPressure 1 }
lgpConditionCompressor2LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure at compressor 2 inlet has dropped below the
minimum setting."
::= { lgpConditionCompressorLowSuctionPressure 2 }
lgpConditionCompressor3LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure at compressor 3 inlet has dropped below the
minimum setting."
::= { lgpConditionCompressorLowSuctionPressure 3 }
lgpConditionCompressor4LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure at compressor 4 inlet has dropped below the
minimum setting."
::= { lgpConditionCompressorLowSuctionPressure 4 }
lgpConditionMainFanOverLoad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a main fan overload condition."
::= { lgpConditionsWellKnown 11 }
lgpConditionManualOverride OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a manual override condition."
::= { lgpConditionsWellKnown 12 }
lgpConditionStandbyGlycoolPumpOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The standby Glycol or Glycool pump is activated."
::= { lgpConditionsWellKnown 13 }
lgpConditionWaterUnderFloor OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Moisture has been detected under the floor."
::= { lgpConditionsWellKnown 14 }
lgpConditionHumidifierProblem OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a humidifier problem."
::= { lgpConditionsWellKnown 15 }
lgpConditionLowWaterInHumidifier OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low water condition in the humidifier
reservoir."
::= { lgpConditionsWellKnown 16 }
lgpConditionSmokeDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected smoke."
::= { lgpConditionsWellKnown 17 }
lgpConditionLowWaterFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low water flow rate condition."
::= { lgpConditionsWellKnown 18 }
lgpConditionLostPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has lost power before being switched off using the
controls. This condition is activated when power is restored."
::= { lgpConditionsWellKnown 19 }
lgpGeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A fault condition has been detected that is not identified
in the well known list."
::= { lgpConditionsWellKnown 20 }
lgpConditionLocalAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a local, or customer, alarm condition."
::= { lgpConditionsWellKnown 21 }
lgpConditionLocalAlarm1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 1 is active."
::= { lgpConditionLocalAlarm 1 }
lgpConditionLocalAlarm2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 2 is active."
::= { lgpConditionLocalAlarm 2 }
lgpConditionLocalAlarm3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 3 is active."
::= { lgpConditionLocalAlarm 3 }
lgpConditionLocalAlarm4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 4 is active."
::= { lgpConditionLocalAlarm 4 }
lgpConditionLocalAlarm5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 5 is active."
::= { lgpConditionLocalAlarm 5 }
lgpConditionLocalAlarm6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 6 is active."
::= { lgpConditionLocalAlarm 6 }
lgpConditionLocalAlarm7 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 7 is active."
::= { lgpConditionLocalAlarm 7 }
lgpConditionLocalAlarm8 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that customer alarm condition 8 is active."
::= { lgpConditionLocalAlarm 8 }
lgpConditionStandbyUnitOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the standby unit is operating."
::= { lgpConditionsWellKnown 22 }
lgpConditionCompressorLowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a low head compressor condition."
::= { lgpConditionsWellKnown 23 }
lgpConditionCompressor1LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in compressor 1."
::= { lgpConditionCompressorLowPressure 1 }
lgpConditionTandemCompressorCircuit1LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in tandem compressor circuit 1."
::= { lgpConditionCompressor1LowPressure 1 }
lgpConditionCompressor2LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in compressor 2."
::= { lgpConditionCompressorLowPressure 2 }
lgpConditionTandemCompressorCircuit2LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in tandem compressor circuit 2."
::= { lgpConditionCompressor2LowPressure 1 }
lgpConditionCompressor3LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in compressor 3."
::= { lgpConditionCompressorLowPressure 3 }
lgpConditionCompressor4LowPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected low pressure in compressor 4."
::= { lgpConditionCompressorLowPressure 4 }
lgpConditionHighWaterInPan OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high water condition in the condenser pan."
::= { lgpConditionsWellKnown 24 }
lgpConditionFaultySensor OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a faulty temperature/humidity sensor."
::= { lgpConditionsWellKnown 25 }
lgpConditionServiceCooling OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Cooling system requires scheduled maintenance."
::= { lgpConditionsWellKnown 26 }
lgpConditionServiceHumidifier OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Humidifier requires scheduled maintenance."
::= { lgpConditionsWellKnown 27 }
lgpConditionSystemControlBatteryLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Charge level of the system control's battery is below the
alarm set point."
::= { lgpConditionsWellKnown 28 }
lgpConditionGroundSystemFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a ground system fault."
::= { lgpConditionsWellKnown 29 }
lgpConditionGroundFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a ground failure."
::= { lgpConditionsWellKnown 30 }
lgpConditionSecurityBreach OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a security breach."
::= { lgpConditionsWellKnown 31 }
lgpConditionEmergencyShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an emergency shutdown condition. The System
is shutting down as a result of this emergency."
::= { lgpConditionsWellKnown 32 }
lgpConditionOnBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected the load is being powered by a bypass
source."
::= { lgpConditionsWellKnown 33 }
lgpConditionLoadOnBypass OBJECT-IDENTITY
STATUS obsolete
DESCRIPTION
"The load is being powered by a bypass source."
::= { lgpConditionOnBypass 1 }
lgpConditionLoadOnMaintenceBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load is being powered by a maintenance bypass source."
::= { lgpConditionOnBypass 2 }
lgpConditionParallelSysLoadOnBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has transferred to bypass."
::= { lgpConditionOnBypass 3 }
lgpConditionLoadOnBypassByImpact OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a load impact and has transferred the
load to the bypass source."
::= { lgpConditionOnBypass 4 }
lgpConditionLoadTransferedToBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has transferred to bypass. The load is being powered by
the bypass source."
::= { lgpConditionOnBypass 5 }
lgpConditionEmergencyTransferToBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has performed an emergency transfer to bypass."
::= { lgpConditionOnBypass 6 }
lgpConditionOutputToLoadVoltTHD OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The total harmonic distortion (THD) of the output voltage has exceeded a
pre-determined threshold for a device, or system, defined amount of
time."
::= { lgpConditionsWellKnown 34 }
lgpConditionLogicFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control logic failure."
::= { lgpConditionsWellKnown 35 }
lgpConditionPowerSupplyFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system had detected a power supply fault condition."
::= { lgpConditionsWellKnown 36 }
lgpConditionPowerSupply1Fault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected power supply 1 is in a fault condition."
::= { lgpConditionPowerSupplyFault 1 }
lgpConditionPowerSupply2Fault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected power supply 2 is in a fault condition."
::= { lgpConditionPowerSupplyFault 2 }
lgpConditionPowerSupplyFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a power supply failure condition."
::= { lgpConditionsWellKnown 37 }
lgpConditionPowerSupply1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected power supply 1 has failed."
::= { lgpConditionPowerSupplyFailure 1 }
lgpConditionPowerSupply2Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected power supply 2 has failed."
::= { lgpConditionPowerSupplyFailure 2 }
lgpConditionSource1PowerSupplyInputFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 1 Power supply input has failed."
::= { lgpConditionPowerSupplyFailure 3 }
lgpConditionSource2PowerSupplyInputFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 2 Power supply input has failed."
::= { lgpConditionPowerSupplyFailure 4 }
lgpConditionPowerSupplyLogicFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a power supply logic failure."
::= { lgpConditionPowerSupplyFailure 5 }
lgpConditionCompressorPowerSupplyFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the power supply to the compressors
has failed."
::= { lgpConditionPowerSupplyFailure 6 }
lgpConditionOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an over voltage condition."
::= { lgpConditionsWellKnown 38 }
lgpConditionSource1OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage condition on source 1.
The voltage measurement has risen above a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionOverVoltage 1 }
lgpConditionSource2OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage condition on source 2.
The voltage measurement has risen above a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionOverVoltage 2 }
lgpConditionOutputToLoadOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load is in an over-voltage
condition. The voltage for the load has risen above a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverVoltage 3 }
lgpConditionInputOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an input over voltage condition. The
voltage measurement has risen above a pre-determined threshold for
a specified amount of time."
::= { lgpConditionOverVoltage 4 }
lgpConditionBypassOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage condition on the bypass.
The voltage measurement has risen above a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionOverVoltage 5 }
lgpConditionBypassOverVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage failure condition on the
bypass. The voltage measurement has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverVoltage 6 }
lgpConditionBatteryOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery over voltage condition."
::= { lgpConditionOverVoltage 7 }
lgpConditionDcBusOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a DC Bus over voltage condition."
::= { lgpConditionOverVoltage 8 }
lgpConditionDcBus1OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage condition on DC Bus
1."
::= { lgpConditionDcBusOverVoltage 1 }
lgpConditionDcBus2OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage condition on DC Bus
2."
::= { lgpConditionDcBusOverVoltage 2 }
lgpConditionDcBus1OverVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage failure condition
on DC Bus 1."
::= { lgpConditionDcBusOverVoltage 3 }
lgpConditionDcBus2OverVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over voltage failure condition
on DC Bus 2."
::= { lgpConditionDcBusOverVoltage 4 }
lgpConditionUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an under voltage condition."
::= { lgpConditionsWellKnown 39 }
lgpConditionSource1UnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on source 1.
The voltage measurement has fallen below a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionUnderVoltage 1 }
lgpConditionSource2UnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on source 2.
The voltage measurement has fallen below a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionUnderVoltage 2 }
lgpConditionOutputToLoadUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load is in an under-voltage
condition. The voltage for the load has fallen below a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionUnderVoltage 3 }
lgpConditionSource1UnderVoltageRMS OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on source 1.
The voltage measurement has fallen below a pre-determined threshold
for a specified amount of time."
::= { lgpConditionUnderVoltage 4 }
lgpConditionSource2UnderVoltageRMS OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on source 2.
The voltage measurement has fallen below a pre-determined threshold
for a specified amount of time."
::= { lgpConditionUnderVoltage 5 }
lgpConditionInputUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an input under voltage condition.
The voltage measurement has fallen below a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionUnderVoltage 6 }
lgpConditionBypassUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on the bypass.
The voltage measurement has fallen below a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionUnderVoltage 7 }
lgpConditionBypassUnderVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage failure condition on the
bypass. The voltage measurement has fallen below a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionUnderVoltage 8 }
lgpConditionBatteryUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery under voltage condition."
::= { lgpConditionUnderVoltage 9 }
lgpConditionDcBusUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a DC bus under voltage condition"
::= { lgpConditionUnderVoltage 10 }
lgpConditionDcBus1UnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on DC Bus
1."
::= { lgpConditionDcBusUnderVoltage 1 }
lgpConditionDcBus2UnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage condition on DC Bus
2."
::= { lgpConditionDcBusUnderVoltage 2 }
lgpConditionDcBus1UnderVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage failure condition
on DC Bus 1."
::= { lgpConditionDcBusUnderVoltage 3 }
lgpConditionDcBus2UnderVoltageFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an under voltage failure condition
on DC Bus 2."
::= { lgpConditionDcBusUnderVoltage 4 }
lgpConditionOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an overload condition."
::= { lgpConditionsWellKnown 40 }
lgpConditionSource1Overload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition on source 1. The
power requirement for this source has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverload 1 }
lgpConditionSystemOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an overload condition."
::= { lgpConditionOverload 2 }
lgpConditionSource1PeakCurrentOverLoad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected source 1 in is experiencing a peak over load
condition. The current has risen above a pre-determined threshold for
a specified amount of time."
::= { lgpConditionOverload 3 }
lgpConditionSource2PeakCurrentOverLoad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected source 2 in is experiencing a peak over load
condition. The current has risen above a pre-determined threshold for
a specified amount of time."
::= { lgpConditionOverload 4 }
lgpConditionOutputToLoadOverLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected that the output to the load has exceeded the
lgpPwrOutputToLoadUserOverloadLimit."
::= { lgpConditionOverload 5 }
lgpConditionOutputToLoadOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an output overload condition."
::= { lgpConditionOverload 6 }
lgpConditionParallelSysOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected an overload condition."
::= { lgpConditionOverload 7 }
lgpConditionBypassCurrentOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"With the load on bypass static switch, the measured output
RMS current has exceeded a specified percentage of the nominal
RMS current."
::= { lgpConditionOverload 8 }
lgpConditionBypassCurrentOverloadPhsA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"With the load on bypass static switch, the measured phase A output
RMS current has exceeded a specified percentage of the nominal
per-phase RMS current."
::= { lgpConditionBypassCurrentOverload 1 }
lgpConditionBypassCurrentOverloadPhsB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"With the load on bypass static switch, the measured phase B output
RMS current has exceeded a specified percentage of the nominal
per-phase RMS current."
::= { lgpConditionBypassCurrentOverload 2 }
lgpConditionBypassCurrentOverloadPhsC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"With the load on bypass static switch, the measured phase C output
RMS current has exceeded a specified percentage of the nominal
per-phase RMS current."
::= { lgpConditionBypassCurrentOverload 3 }
lgpConditionScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a Silicon Controlled Rectifier (SCR)
short condition."
::= { lgpConditionsWellKnown 41 }
lgpConditionSource1ScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 Silicon Controlled Rectifier
(SCR) short condition."
::= { lgpConditionScrShort 1 }
lgpConditionSource2ScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 Silicon Controlled Rectifier
(SCR) short condition."
::= { lgpConditionScrShort 2 }
lgpConditionBypassScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a Silicon Controlled Rectifier (SCR) short
condition on the bypass."
::= { lgpConditionScrShort 3 }
lgpConditionInvStaticSwScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short across one or more inverter static
switch Silicon Controlled Rectifiers (SCRs)."
::= { lgpConditionScrShort 4 }
lgpConditionSource1NeutralScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 Silicon Controlled Rectifier
(SCR) short condition on the neutral line."
::= { lgpConditionScrShort 5 }
lgpConditionSource2NeutralScrShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 Silicon Controlled Rectifier
(SCR) short condition on the neutral line."
::= { lgpConditionScrShort 6 }
lgpConditionScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a Silicon Controlled Rectifier (SCR)
open condition."
::= { lgpConditionsWellKnown 42 }
lgpConditionSource1ScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 Silicon Controlled Rectifier
(SCR) open condition."
::= { lgpConditionScrOpen 1 }
lgpConditionSource2ScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 Silicon Controlled Rectifier
(SCR) open condition."
::= { lgpConditionScrOpen 2 }
lgpConditionBypassScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a Silicon Controlled Rectifier (SCR) open
condition on the bypass."
::= { lgpConditionScrOpen 3 }
lgpConditionSource1NeutralScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 Silicon Controlled Rectifier
(SCR) open condition on the neutral line."
::= { lgpConditionScrOpen 4 }
lgpConditionSource2NeutralScrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 Silicon Controlled Rectifier
(SCR) open condition on the neutral line."
::= { lgpConditionScrOpen 5 }
lgpConditionFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a fan failure condition."
::= { lgpConditionsWellKnown 43 }
lgpConditionFan1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a fan 1 failure condition."
::= { lgpConditionFanFailure 1 }
lgpConditionRedundantFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A failure has occurred in a fan that cools the system's internal
components and has resulted in a loss of fan redundancy."
::= { lgpConditionFanFailure 2 }
lgpConditionMultipleFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multiple fans have failed resulting in a decreased ability to cool
the system's internal components."
::= { lgpConditionFanFailure 3 }
lgpConditionBlowerFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a problem with one or more of the blower
fans. These are not the system internal cooling fans."
::= { lgpConditionFanFailure 4 }
lgpConditionBottomBlowerFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bottom environmental unit blower fan is not operating
within its normal parameters."
::= { lgpConditionBlowerFanFailure 1 }
lgpConditionTopBlowerFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The top environmental unit blower fan is not operating
within its normal parameters."
::= { lgpConditionBlowerFanFailure 2 }
lgpConditionCondenserFanVFDFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a problem with the Variable Frequency
Drive system for the condenser fan."
::= { lgpConditionFanFailure 5 }
lgpConditionFanPowerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a power failure on one or more fans."
::= { lgpConditionFanFailure 6 }
lgpConditionTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is preventing a transfer of the load to the alternate
source."
::= { lgpConditionsWellKnown 44 }
lgpConditionAutoReTransferPrimed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is capable to retransfer to the preferred source."
::= { lgpConditionsWellKnown 45 }
lgpConditionSourcesOutOfSync OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that the input sources are not within the
specified phase difference (synchronization window)."
::= { lgpConditionsWellKnown 46 }
lgpConditionSourceFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an input source failure condition."
::= { lgpConditionsWellKnown 47 }
lgpConditionSource1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected source 1 has failed."
::= { lgpConditionSourceFailure 1 }
lgpConditionSource2Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected source 2 has failed."
::= { lgpConditionSourceFailure 2 }
lgpConditionAutoReTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is preventing a retransfer of the load back to the
preferred source."
::= { lgpConditionsWellKnown 48 }
lgpConditionAutoReTransferFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is failing to automatically retransfer the load back to the
preferred source."
::= { lgpConditionsWellKnown 49 }
lgpConditionFuseOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an open fuse condition."
::= { lgpConditionsWellKnown 50 }
lgpConditionControlFuse1Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control power fuse 1 open condition."
::= { lgpConditionFuseOpen 1 }
lgpConditionControlFuse2Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control power fuse 2 open condition."
::= { lgpConditionFuseOpen 2 }
lgpConditionRectifierFuseOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier fuse open condition."
::= { lgpConditionFuseOpen 3 }
lgpConditionInverterFuseOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter fuse open condition."
::= { lgpConditionFuseOpen 4 }
lgpConditionOutputToLoadFuseOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an output to load fuse open condition."
::= { lgpConditionFuseOpen 5 }
lgpConditionDcCapacitorFuseOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a DC capacitor fuse open condition."
::= { lgpConditionFuseOpen 6 }
lgpConditionDisconnect OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a disconnect condition."
::= { lgpConditionsWellKnown 51 }
lgpConditionSource1DisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 1 disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 1 }
lgpConditionSource2DisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 2 disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 2 }
lgpConditionSource1PduDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 1 PDU (Power Distribution Unit)
disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 3 }
lgpConditionSource2PduDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 2 PDU (Power Distribution Unit)
disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 4 }
lgpConditionOutputToLoadDisconnect1Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected Output to load disconnect 1 is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 5 }
lgpConditionOutputToLoadDisconnect2Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected Output to load disconnect 2 is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 6 }
lgpConditionSource1BypassDisconnectClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 1 bypass disconnect is closed.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 7 }
lgpConditionSource2BypassDisconnectClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the source 2 bypass disconnect is closed.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 8 }
lgpConditionOutputToLoadNeutralDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load neutral disconnect is
open. A disconnect is a device which disconnects a conductor of a
circuit from its supply (ex. circuit breaker, contactor, isolating
switch, disconnecting switch, etc.)."
::= { lgpConditionDisconnect 9 }
lgpConditionBatteryDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the battery disconnect is open.
A disconnect is a device which disconnects a conductor of a
circuit from its supply (ex. circuit breaker, contactor, isolating
switch, disconnecting switch, etc.)."
::= { lgpConditionDisconnect 10 }
lgpConditionBatteryDiscOpenCab01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 1 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 1 }
lgpConditionBatteryDiscOpenCab02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 2 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 2 }
lgpConditionBatteryDiscOpenCab03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 3 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 3 }
lgpConditionBatteryDiscOpenCab04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 4 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 4 }
lgpConditionBatteryDiscOpenCab05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 5 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 5 }
lgpConditionBatteryDiscOpenCab06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 6 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 6 }
lgpConditionBatteryDiscOpenCab07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 7 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 7 }
lgpConditionBatteryDiscOpenCab08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the cabinet 8 battery disconnect is
open."
::= { lgpConditionBatteryDisconnectOpen 8 }
lgpConditionInputDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the input disconnect is open.
A disconnect is a device which disconnects a conductor of a
circuit from its supply (ex. circuit breaker, contactor, isolating
switch, disconnecting switch, etc.)."
::= { lgpConditionDisconnect 11 }
lgpConditionOutputToLoadDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the Output to load disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 12 }
lgpConditionBypassDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the bypass disconnect is open. A
disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 13 }
lgpConditionStaticSwitchDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the static switch disconnect is open.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnect 14 }
lgpConditionBreakerOpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A breaker in the system has failed to respond to an Open signal."
::= { lgpConditionDisconnect 15 }
lgpConditionBreakerCloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A breaker in the system has failed to respond to a Close signal."
::= { lgpConditionDisconnect 16 }
lgpConditionFrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a frequency deviation condition.
The frequency of a source is outside of the pre-determined thresholds
for a specified amount of time."
::= { lgpConditionsWellKnown 52 }
lgpConditionSource1FrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The frequency for source 1 has been outside of the pre-determined
thresholds for a specified period of time."
::= { lgpConditionFrequencyDeviation 1 }
lgpConditionSource2FrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The frequency for source 2 has been outside of the pre-determined
thresholds for a specified period of time."
::= { lgpConditionFrequencyDeviation 2 }
lgpConditionInputFrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The frequency for the input has been outside of the pre-determined
thresholds for a specified period of time."
::= { lgpConditionFrequencyDeviation 3 }
lgpConditionOutputToLoadFrequencyDeviation
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The frequency for the output has been outside of the pre-determined
thresholds for a specified period of time."
::= { lgpConditionFrequencyDeviation 4 }
lgpConditionBypassFrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The frequency for the bypass input has been outside of the
pre-determined thresholds for a specified period of time."
::= { lgpConditionFrequencyDeviation 5 }
lgpConditionOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an over-current condition. The current of a
source has risen above a pre-determined threshold for a device,
or system, defined amount of time."
::= { lgpConditionsWellKnown 53 }
lgpConditionSource1OverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on source 1.
The current of a source has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 1 }
lgpConditionSource2OverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on source 2.
The current of a source has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 2 }
lgpConditionOutputToLoadOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load is in an over-current
condition. The current for the load has risen above a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverCurrent 3 }
lgpConditionOutputToLoadOverCurrentPhsA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load on phase A is in an
over-current condition. The current on this phase has risen above
a pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOutputToLoadOverCurrent 1 }
lgpConditionOutputToLoadOverCurrentPhsB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load on phase B is in an
over-current condition. The current on this phase has risen above
a pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOutputToLoadOverCurrent 2 }
lgpConditionOutputToLoadOverCurrentPhsC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load on phase C is in an
over-current condition. The current on this phase has risen above
a pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOutputToLoadOverCurrent 3 }
lgpConditionGroundOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A ground source is experiencing an over-current condition. The
current for the ground line has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 4 }
lgpConditionRectifierOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier over current condition.
The current for the rectifier has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 5 }
lgpConditionInverterOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter over current condition.
The current for the inverter has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 6 }
lgpConditionInverterOverCurrentPhsA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter over current condition on
phase A. The current for the this phase in the inverter has risen
above a pre-determined threshold for a device, or system, defined
amount of time."
::= { lgpConditionInverterOverCurrent 1 }
lgpConditionInverterOverCurrentPhsB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter over current condition on
phase B. The current for the this phase in the inverter has risen
above a pre-determined threshold for a device, or system, defined
amount of time."
::= { lgpConditionInverterOverCurrent 2 }
lgpConditionInverterOverCurrentPhsC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter over current condition on
phase C. The current for the this phase in the inverter has risen
above a pre-determined threshold for a device, or system, defined
amount of time."
::= { lgpConditionInverterOverCurrent 3 }
lgpConditionBatteryConverterOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on the battery
converter. The current of the converter has risen above a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverCurrent 7 }
lgpConditionBatteryBalancerOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery balancer over current condition.
The current at this point has risen above a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverCurrent 8 }
lgpConditionHumidifierOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on the
humidifier. The current of the humidifier has risen above
a pre-determined threshold for a defined amount of time."
::= { lgpConditionOverCurrent 9 }
lgpConditionInputOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"There is an over current condition on the system input power.
The input current has risen above a pre-determined threshold for
a pre-defined amount of time."
::= { lgpConditionOverCurrent 10 }
lgpConditionSource1NeutralOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on the neutral
line of source 1. The neutral current at source 1 has risen above
a pre-determined threshold for a pre-defined amount of time."
::= { lgpConditionOverCurrent 11 }
lgpConditionSource2NeutralOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over current condition on the neutral
line of source 2. The neutral current at source 2 has risen above
a pre-determined threshold for a pre-defined amount of time."
::= { lgpConditionOverCurrent 12 }
lgpConditionSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a sensor failure condition."
::= { lgpConditionsWellKnown 54 }
lgpConditionOutputToLoadVoltageSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected an output to load voltage sensor failure."
::= { lgpConditionSensorFailure 1 }
lgpConditionSource1VoltageSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected a source 1 voltage sensor failure."
::= { lgpConditionSensorFailure 2 }
lgpConditionSource2VoltageSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected a source 2 voltage sensor failure."
::= { lgpConditionSensorFailure 3 }
lgpConditionSource1ScrSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected a source 1 SCR (Silicon Controlled
Rectifier) sensor failure."
::= { lgpConditionSensorFailure 4 }
lgpConditionSource2ScrSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected a source 2 SCR (Silicon Controlled
Rectifier) sensor failure."
::= { lgpConditionSensorFailure 5 }
lgpConditionSource1CurrentSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 current sensor failure."
::= { lgpConditionSensorFailure 6 }
lgpConditionSource2CurrentSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 current sensor failure."
::= { lgpConditionSensorFailure 7 }
lgpConditionRoomTempHumiditySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a device temperature and humidity sensor
failure."
::= { lgpConditionSensorFailure 8 }
lgpConditionGlycolTempSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a glycol temperature sensor failure."
::= { lgpConditionSensorFailure 9 }
lgpConditionLocal1SensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a local 1 sensor failure."
::= { lgpConditionSensorFailure 10 }
lgpConditionCompressor1SensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a compressor 1 digital scroll sensor
failure condition."
::= { lgpConditionSensorFailure 11 }
lgpConditionCompressor2SensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a compressor 2 digital scroll sensor
failure condition."
::= { lgpConditionSensorFailure 12 }
lgpConditionSupplySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a supply sensor failure."
::= { lgpConditionSensorFailure 13 }
lgpConditionCabinetTemperatureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a cabinet temperature sensor failure."
::= { lgpConditionSensorFailure 14 }
lgpConditionCabinetHumiditySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a cabinet humidity sensor failure."
::= { lgpConditionSensorFailure 15 }
lgpConditionRoomTempSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a room temperature sensor failure."
::= { lgpConditionSensorFailure 16 }
lgpConditionBatteryTempSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery temperature sensor failure."
::= { lgpConditionSensorFailure 17 }
lgpConditionAirSensorAFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a failure with air sensor A. The sensor
may have been disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 18 }
lgpConditionAirSensorBFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a failure with air sensor B. The sensor
may have been disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 19 }
lgpConditionChilledWaterSupplySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a failure with the chilled water supply
sensor. The sensor may have been disconnected or the signal is out
of range."
::= { lgpConditionSensorFailure 20 }
lgpConditionRefrigerantSupplySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a failure with the refrigerant supply
sensor. The sensor may have been disconnected or the signal is out
of range."
::= { lgpConditionSensorFailure 21 }
lgpConditionFluidSupplySensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a failure with the fluid supply
sensor. The sensor may have been disconnected or the signal is out
of range."
::= { lgpConditionSensorFailure 22 }
lgpConditionCompressorLowPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that a compressor low pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 23 }
lgpConditionCompressor1LowPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 1 low pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionCompressorLowPressureSensorFailure 1 }
lgpConditionRemoteSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that a remote sensor is disconnected
or the signal is out of range."
::= { lgpConditionSensorFailure 24 }
lgpConditionAirSupplyTempSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that the supply air temperature sensor is
disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 25 }
lgpConditionAirReturnTempSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that the return air temperature sensor is
disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 26 }
lgpConditionCompressorHighPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that a compressor high pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionSensorFailure 27 }
lgpConditionCompressor2HighPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 2 high pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionCompressorHighPressureSensorFailure 2 }
lgpConditionCompressor3HighPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 3 high pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionCompressorHighPressureSensorFailure 3 }
lgpConditionCompressor4HighPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 4 high pressure
transducer is disconnected or the signal is out of range."
::= { lgpConditionCompressorHighPressureSensorFailure 4 }
lgpConditionInternalCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an internal communication failure condition."
::= { lgpConditionsWellKnown 55 }
lgpConditionExternalCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an external communication failure condition."
::= { lgpConditionsWellKnown 56 }
lgpConditionSourceGateDriveFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a source gate drive failure condition."
::= { lgpConditionsWellKnown 57 }
lgpConditionSource1GateDriveFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 1 gate drive failure."
::= { lgpConditionSourceGateDriveFailure 1 }
lgpConditionSource2GateDriveFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a source 2 gate drive failure."
::= { lgpConditionSourceGateDriveFailure 2 }
lgpConditionDisconnectFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a disconnect failure condition.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionsWellKnown 58 }
lgpConditionOutputToLoadNeutralDisconnectFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the output to load neutral disconnect has
failed.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 1 }
lgpConditionSource1DisconnectShuntTripFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a shunt trip failure of a disconnecting device
on source 1.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 2 }
lgpConditionSource2DisconnectShuntTripFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a shunt trip failure of a disconnecting device
on source 2.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 3 }
lgpConditionInverterDisconnectFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter disconnect failure. A disconnect
is a device which disconnects a conductor of a circuit from its
supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 4 }
lgpConditionBatteryDisconnectFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery disconnect failure. A disconnect
is a device which disconnects a conductor of a circuit from its
supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 5 }
lgpConditionRectifierDisconnectFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier disconnect failure. A disconnect
is a device which disconnects a conductor of a circuit from its
supply (ex. circuit breaker, contactor, isolating switch,
disconnecting switch, etc.)."
::= { lgpConditionDisconnectFailure 6 }
lgpConditionOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an over temperature condition."
::= { lgpConditionsWellKnown 59 }
lgpConditionHeatSink1OverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a heat sink 1 over temperature condition."
::= { lgpConditionOverTemperature 1 }
lgpConditionAmbient1OverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an ambient over temperature condition at
location 1."
::= { lgpConditionOverTemperature 2 }
lgpConditionSystemOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system or a component of the system has detected an over
temperature condition. The temperature measurement has risen
above a pre-determined threshold for a device, or system, defined
amount of time."
::= { lgpConditionOverTemperature 3 }
lgpConditionTransformerOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The transformer is experiencing an over temperature condition.
The transformer's temperature has exceeded a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverTemperature 4 }
lgpConditionBatteryOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is experiencing an over temperature condition.
The battery's temperature has exceeded a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionOverTemperature 5 }
lgpConditionRectifierOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier over temperature condition.
The rectifier's temperature has exceeded a pre-determined threshold
for a device, or system, defined amount of time."
::= { lgpConditionOverTemperature 6 }
lgpConditionInverterOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter over temperature condition.
The inverter's temperature has exceeded a pre-determined
threshold for a device, or system, defined amount of time."
::= { lgpConditionOverTemperature 7 }
lgpConditionRectifierInductorOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier inductor over temperature
condition. The rectifier's inductor temperature has exceeded a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverTemperature 8 }
lgpConditionInverterInductorOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter inductor over temperature
condition. The inverter's inductor temperature has exceeded a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverTemperature 9 }
lgpConditionBatteryConverterOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery converter over temperature
condition. The battery converter's temperature has exceeded a
pre-determined threshold for a device, or system, defined amount
of time."
::= { lgpConditionOverTemperature 10 }
lgpConditionBatteryBalancerInductorOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery balancer Inductor over
temperature condition. The battery balancer Inductor's temperature
has exceeded a pre-determined threshold for a specified amount of
time."
::= { lgpConditionOverTemperature 11 }
lgpConditionChilledWaterOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a chilled water over temperature
condition."
::= { lgpConditionOverTemperature 12 }
lgpConditionElectricHeatersOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an electric heater over temperature
condition."
::= { lgpConditionOverTemperature 13 }
lgpConditionInletAirOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inlet air over temperature condition."
::= { lgpConditionOverTemperature 14 }
lgpConditionSystemOverTempWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system or a component of the system has detected an over
temperature condition. The temperature measurement has risen
above a normal operating range for a device, or system, defined
amount of time. The system is still operational but a threshold has
been exceeded."
::= { lgpConditionOverTemperature 15 }
lgpConditionHighTemperatureBattString OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high temperature on a battery string.
The temperature has exceeded a specified temperature threshold."
::= { lgpConditionOverTemperature 16 }
lgpConditionLoadOnAlternateSource OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that the load is being supplied by the
alternate source."
::= { lgpConditionsWellKnown 60 }
lgpConditionPhaseRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a phase rotation error condition."
::= { lgpConditionsWellKnown 61 }
lgpConditionSource1PhaseRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a phase rotation error on source 1."
::= { lgpConditionPhaseRotationError 1 }
lgpConditionSource2PhaseRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a phase rotation error on source 2."
::= { lgpConditionPhaseRotationError 2 }
lgpConditionBypassPhaseRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a phase rotation error on the bypass."
::= { lgpConditionPhaseRotationError 3 }
lgpConditionInputPhaseRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a phase rotation error on the input."
::= { lgpConditionPhaseRotationError 4 }
lgpConditionControlModuleFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a control module failure condition."
::= { lgpConditionsWellKnown 62 }
lgpConditionControlModule1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control module 1 failure."
::= { lgpConditionControlModuleFailure 1 }
lgpConditionHistoryLogFull OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the history log is full."
::= { lgpConditionsWellKnown 63 }
lgpConditionConfigurationModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the configuration has been modified."
::= { lgpConditionsWellKnown 64 }
lgpConditionPasswordModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the password has been modified."
::= { lgpConditionsWellKnown 65 }
lgpConditionTimeModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the time has been modified."
::= { lgpConditionsWellKnown 66 }
lgpConditionDateModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the date has been modified."
::= { lgpConditionsWellKnown 67 }
lgpConditionEventLogCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the event log has been cleared."
::= { lgpConditionsWellKnown 68 }
lgpConditionHistoryLogCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the history log has been cleared."
::= { lgpConditionsWellKnown 69 }
lgpConditionUtilityFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a utility failure."
::= { lgpConditionsWellKnown 70 }
lgpConditionBatteryTestInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is performing a battery test at this time."
::= { lgpConditionsWellKnown 71 }
lgpConditionLoadOnBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system load is being supported by the battery."
::= { lgpConditionsWellKnown 72 }
lgpConditionReplaceBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the batteries are due to be replaced."
::= { lgpConditionsWellKnown 74 }
lgpConditionUpsShutdownPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is in a shutdown pending condition."
::= { lgpConditionsWellKnown 75 }
lgpConditionBatteryChargerFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the battery charger has failed."
::= { lgpConditionsWellKnown 76 }
lgpConditionBypassVoltageUnqualified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the bypass voltage is unqualified.
The voltage measurement is outside a pre-determined threshold range for
a specified amount of time."
::= { lgpConditionsWellKnown 77 }
lgpConditionCheckAirFilter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected it is time to check the air filter."
::= { lgpConditionsWellKnown 78 }
lgpConditionBrownOut OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a brown out condition."
::= { lgpConditionsWellKnown 79 }
lgpConditionMultipleTransferLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has locked out transfers to bypass. Too many transfers
have occurred over a specified amount of time."
::= { lgpConditionsWellKnown 80 }
lgpConditionBypassPhaseLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected one or more bypass phases are missing."
::= { lgpConditionsWellKnown 81 }
lgpConditionMaintenceBypassInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is preventing a transfer of the load to maintenance bypass."
::= { lgpConditionsWellKnown 82 }
lgpConditionLoadLockedOnBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An error has been detected requiring the system to be put into a
'locked on bypass' state."
::= { lgpConditionsWellKnown 83 }
lgpConditionOutputToLoadShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an output to load short circuit condition."
::= { lgpConditionsWellKnown 84 }
lgpConditionEmergencyTransferToInverter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an emergency transfer of the load to
inverter."
::= { lgpConditionsWellKnown 85 }
lgpConditonEmergencyPowerOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an Emergency Power Off (EPO) condition.
An external EPO switch has cut off the power source to the system."
::= { lgpConditionsWellKnown 86 }
lgpConditionInverterBackFeed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter back-feed condition. The inverter
is feeding power through the bypass back to the input."
::= { lgpConditionsWellKnown 87 }
lgpConditionDcGroundFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a DC ground fault."
::= { lgpConditionsWellKnown 88 }
lgpConditionDcGroundFaultPos OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ground fault current has been detected in the positive DC link to
ground."
::= { lgpConditionDcGroundFault 1 }
lgpConditionDcGroundFaultNeg OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ground fault current has been detected in the negative DC link to
ground."
::= { lgpConditionDcGroundFault 2 }
lgpConditionStaticTransferSwitchInhibited
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is preventing the use of the static transfer switch."
::= { lgpConditionsWellKnown 89 }
lgpConditionBatteryLogFullWarning
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the battery log is approaching the maximum
record limit."
::= { lgpConditionsWellKnown 90 }
lgpConditionInputCurrentUnbalanced
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an unbalanced input current condition.
The currents of input phases are out of tolerance."
::= { lgpConditionsWellKnown 91 }
lgpConditionSelfTestFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a self-test failure."
::= { lgpConditionsWellKnown 92 }
lgpConditionInverterOutOfSynchronization
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an Inverter out of sync condition."
::= { lgpConditionsWellKnown 93 }
lgpConditionModuleAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected an alarm within the multi-module system."
::= { lgpConditionsWellKnown 94 }
lgpConditioniModuleUnit1Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 1."
::= { lgpConditionModuleAlarm 1 }
lgpConditioniModuleUnit2Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 2."
::= { lgpConditionModuleAlarm 2 }
lgpConditioniModuleUnit3Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 3."
::= { lgpConditionModuleAlarm 3 }
lgpConditioniModuleUnit4Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 4."
::= { lgpConditionModuleAlarm 4 }
lgpConditioniModuleUnit5Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 5."
::= { lgpConditionModuleAlarm 5 }
lgpConditioniModuleUnit6Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 6."
::= { lgpConditionModuleAlarm 6 }
lgpConditioniModuleUnit7Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 7."
::= { lgpConditionModuleAlarm 7 }
lgpConditioniModuleUnit8Alarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system has detected an alarm condition on
unit 8."
::= { lgpConditionModuleAlarm 8 }
lgpConditionActiveModuleAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an active alarm in one, or more, of the
sub-modules of the multi-module system."
::= { lgpConditionsWellKnown 95 }
lgpConditionControlFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a control failure condition."
::= { lgpConditionsWellKnown 96 }
lgpConditionMainControlFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a main control failure condition."
::= { lgpConditionControlFailure 1 }
lgpConditionRedundantControlFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a redundant control failure condition."
::= { lgpConditionControlFailure 2 }
lgpConditionParallelSysControlFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected a control failure condition with
one of the controls."
::= { lgpConditionControlFailure 3 }
lgpConditionMainControlCommFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more communications failures have occurred in the main
control."
::= { lgpConditionControlFailure 4 }
lgpConditionControlBoardFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control board failure."
::= { lgpConditionControlFailure 5 }
lgpConditionHumidifierControlBdFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidifier control board is required to be connected,
but no signal is detected."
::= { lgpConditionControlBoardFailure 1 }
lgpConditionControlWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This system has detected a control warning conditions."
::= { lgpConditionsWellKnown 97 }
lgpConditionMainControlWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a main control warning condition."
::= { lgpConditionControlWarning 1 }
lgpConditionRedundantControlWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a redundant control warning condition."
::= { lgpConditionControlWarning 2 }
lgpConditionUserInterfaceFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a user interface control failure condition."
::= { lgpConditionsWellKnown 98 }
lgpConditionLostPowerRedundancy OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the number of redundant power modules has
fallen below the minimum redundant power module setting."
::= { lgpConditionsWellKnown 99 }
lgpConditionPowerModuleFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a power module failure condition in the
system."
::= { lgpConditionsWellKnown 100 }
lgpConditionBatteryModuleFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery module failure condition in the
system."
::= { lgpConditionsWellKnown 101 }
lgpConditionOutputToLoadOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that there is no power being supplied to the
load."
::= { lgpConditionsWellKnown 102 }
lgpConditionSystemOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is off."
::= { lgpConditionsWellKnown 103 }
lgpConditionRectifierStartupFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier under voltage start-up failure
condition."
::= { lgpConditionsWellKnown 104 }
lgpConditionRectifierFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a rectifier fault condition."
::= { lgpConditionsWellKnown 105 }
lgpConditionInverterShutdownLowDc OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has shutdown the inverter due to a DC bus under voltage."
::= { lgpConditionsWellKnown 106 }
lgpConditionInverterFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an inverter fault condition."
::= { lgpConditionsWellKnown 107 }
lgpConditionInverterDcOffsetOverrun OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an over run of the inverter DC offset
voltage."
::= { lgpConditionsWellKnown 108 }
lgpConditionParallelSysLowBatteryWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected a low battery warning condition."
::= { lgpConditionsWellKnown 109 }
lgpConditionParallelSysLoadShareFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected a load share fault condition."
::= { lgpConditionsWellKnown 110 }
lgpConditionBatteryFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery fault condition. The battery
conductors are either reversed or disconnected."
::= { lgpConditionsWellKnown 111 }
lgpConditionBatteryConverterFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery converter failure condition."
::= { lgpConditionsWellKnown 112 }
lgpConditionBatteryBalancerFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery balancer fault condition."
::= { lgpConditionsWellKnown 113 }
lgpConditionpsUpsOperationFault OBJECT-IDENTITY
STATUS deprecated
DESCRIPTION
"The system has detected an operation fault. The UPS attempted to
transfer to maintenance bypass without following the proper sequence."
::= { lgpConditionsWellKnown 114 }
lgpConditionOutputToLoadOnJointMode OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system load is being supported by both the battery and rectifier."
::= { lgpConditionsWellKnown 115 }
lgpConditionInputNeutralLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system had detected the main input neutral is disconnected."
::= { lgpConditionsWellKnown 116 }
lgpConditionLowBatteryWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery's remaining charge is less than or equal to the
configured low threshold."
::= { lgpConditionsWellKnown 117 }
lgpConditionInternalFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an internal fault."
::= { lgpConditionsWellKnown 118 }
lgpConditionBatteryTestFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery self-test failure."
::= { lgpConditionsWellKnown 119 }
lgpConditionPowerModuleWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an alarm condition on one, or more,
power modules."
::= { lgpConditionsWellKnown 120 }
lgpConditionBatteryModuleWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an alarm condition on one, or more,
battery modules."
::= { lgpConditionsWellKnown 121 }
lgpConditionControlModuleWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a control module warning."
::= { lgpConditionsWellKnown 122 }
lgpConditionUpsOperationFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an operation fault. The UPS attempted to
transfer to maintenance bypass without following the proper sequence."
::= { lgpConditionsWellKnown 123 }
lgpConditionActiveAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an alarm condition."
::= { lgpConditionsWellKnown 124 }
lgpConditionRectifierCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an internal communication failure
condition with the rectifier."
::= { lgpConditionsWellKnown 125 }
lgpConditionInverterCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an internal communication failure
condition with the inverter."
::= { lgpConditionsWellKnown 126 }
lgpConditionParallelSysConnectionFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected a connection fault.
One or more of the devices are not properly connected."
::= { lgpConditionsWellKnown 127 }
lgpConditionParallelSysCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The parallel system has detected a communication failure."
::= { lgpConditionsWellKnown 128 }
lgpConditionLostBatteryRedundancy OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the number of redundant battery modules has
fallen below the configured redundant battery module threshold."
::= { lgpConditionsWellKnown 129 }
lgpConditionCompPumpDownFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that a compressor has failed to pump down."
::= { lgpConditionsWellKnown 130 }
lgpConditionComp1PumpDownFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 1 has failed to pump
down."
::= { lgpConditionCompPumpDownFailure 1 }
lgpConditionComp2PumpDownFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 2 has failed to pump
down."
::= { lgpConditionCompPumpDownFailure 2 }
lgpConditionComp3PumpDownFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 3 has failed to pump
down."
::= { lgpConditionCompPumpDownFailure 3 }
lgpConditionComp4PumpDownFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that compressor 4 has failed to pump
down."
::= { lgpConditionCompPumpDownFailure 4 }
lgpConditionChilledWaterLowWaterFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a chilled water low water flow condition."
::= { lgpConditionsWellKnown 131 }
lgpConditionChilledWaterLowWaterFlowCircuit2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a chilled water low water flow condition for circuit 2."
::= { lgpConditionChilledWaterLowWaterFlow 2 }
lgpConditionAirFilterClogged OBJECT-IDENTITY
STATUS deprecated
DESCRIPTION
"The system has detected a air filter clogged condition."
::= { lgpConditionsWellKnown 132 }
lgpConditionHumidifierFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a humidifier failure condition."
::= { lgpConditionsWellKnown 133 }
lgpConditionRunHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a pre-determined run hours threshold has been
exceeded."
::= { lgpConditionsWellKnown 134 }
lgpConditionUnitRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the system run hours has exceeded the
pre-determined threshold."
::= { lgpConditionRunHoursExceeded 1 }
lgpConditionComp1RunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the compressor 1 run hours has exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 2 }
lgpConditionComp2RunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the compressor 2 run hours has exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 3 }
lgpConditionFreeCoolRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the free cooling run hours has exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 4 }
lgpConditionElectricalHeater1RunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the electrical heater's run hours have
exceeded the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 5 }
lgpConditionElectricalHeater2RunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the electrical heater's run hours have
exceeded the pre-determined limit."
::= { lgpConditionRunHoursExceeded 6 }
lgpConditionElectricalHeater3RunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the electrical heater's run hours have
exceeded the pre-determined limit."
::= { lgpConditionRunHoursExceeded 7 }
lgpConditionHotWaterRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the hot water run hours have exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 8 }
lgpConditionHotGasRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the hot gas run hours have exceeded the
pre-determined threshold."
::= { lgpConditionRunHoursExceeded 9 }
lgpConditionHumidifierRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the humidifier run hours have exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 10 }
lgpConditionDehumidiferRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the dehumidifier run hours have exceeded
the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 11 }
lgpConditionFanRunHrsExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the unit blower fan run hours have
exceeded the pre-determined threshold."
::= { lgpConditionRunHoursExceeded 12 }
lgpConditionCommWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with another
module."
::= { lgpConditionsWellKnown 135 }
lgpConditionCommWarningUnit1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 1."
::= { lgpConditionCommWarning 1 }
lgpConditionCommWarningUnit2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 2."
::= { lgpConditionCommWarning 2 }
lgpConditionCommWarningUnit3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 3."
::= { lgpConditionCommWarning 3 }
lgpConditionCommWarningUnit4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 4."
::= { lgpConditionCommWarning 4 }
lgpConditionCommWarningUnit5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 5."
::= { lgpConditionCommWarning 5 }
lgpConditionCommWarningUnit6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 6."
::= { lgpConditionCommWarning 6 }
lgpConditionCommWarningUnit7 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 7."
::= { lgpConditionCommWarning 7 }
lgpConditionCommWarningUnit8 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 8."
::= { lgpConditionCommWarning 8 }
lgpConditionCommWarningUnit9 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 9."
::= { lgpConditionCommWarning 9 }
lgpConditionCommWarningUnit10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 10."
::= { lgpConditionCommWarning 10 }
lgpConditionCommWarningUnit11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 11."
::= { lgpConditionCommWarning 11 }
lgpConditionCommWarningUnit12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 12."
::= { lgpConditionCommWarning 12 }
lgpConditionCommWarningUnit13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 13."
::= { lgpConditionCommWarning 13 }
lgpConditionCommWarningUnit14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 14."
::= { lgpConditionCommWarning 14 }
lgpConditionCommWarningUnit15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 15."
::= { lgpConditionCommWarning 15 }
lgpConditionCommWarningUnit16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of communications with unit 16."
::= { lgpConditionCommWarning 16 }
lgpConditionUnitOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The unit is on."
::= { lgpConditionsWellKnown 136 }
lgpConditionUnitOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The unit is off."
::= { lgpConditionsWellKnown 137 }
lgpConditionSleepModeOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system sleep mode operation has been turned off."
::= { lgpConditionsWellKnown 138 }
lgpConditionPowerOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system power is on."
::= { lgpConditionsWellKnown 139 }
lgpConditionSystemOnStanby OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is on standby."
::= { lgpConditionsWellKnown 140 }
lgpConditionPowerOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system power is off."
::= { lgpConditionsWellKnown 141 }
lgpConditionHighTemperatureGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high temperature condition. This group
contains various high temperature conditions."
::= { lgpConditionsWellKnown 142 }
lgpConditionHighTemperatureSensor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for sensor 1."
::= { lgpConditionHighTemperatureGroup 1 }
lgpConditionHighTemperatureDigitalScroll1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high temperature event on Digital
Scroll Compressor 1. The temperature has exceeded a specified
temperature threshold."
::= { lgpConditionHighTemperatureGroup 2 }
lgpConditionHighTemperatureDigitalScroll2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high temperature event on Digital
Scroll Compressor 2. The temperature has exceeded a specified
temperature threshold."
::= { lgpConditionHighTemperatureGroup 3 }
lgpConditionHighTemperatureUser1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for user configured temperature sensor 1."
::= { lgpConditionHighTemperatureGroup 4 }
lgpConditionHighTemperatureInternal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high internal temperature condition.
The temperature has exceeded a specified temperature threshold."
::= { lgpConditionHighTemperatureGroup 5 }
lgpConditionHighTemperatureExternalAirSensorA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for external air sensor A."
::= { lgpConditionHighTemperatureGroup 6 }
lgpConditionHighTemperatureExternalAirSensorB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for external air sensor B."
::= { lgpConditionHighTemperatureGroup 7 }
lgpConditionHighTemperatureRefrigerantSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for the refrigerant supply."
::= { lgpConditionHighTemperatureGroup 8 }
lgpConditionHighTemperatureFluidSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for the fluid supply."
::= { lgpConditionHighTemperatureGroup 9 }
lgpConditionHighTemperatureSupplyAir OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for the supply air."
::= { lgpConditionHighTemperatureGroup 10 }
lgpConditionHighTemperatureReturnAir OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature has exceeded the high temperature threshold
for the return air."
::= { lgpConditionHighTemperatureGroup 11 }
lgpConditionLowTemperatureGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low temperature condition. This group
contains various low temperature conditions."
::= { lgpConditionsWellKnown 143 }
lgpConditionLowTemperatureSensor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
sensor 1."
::= { lgpConditionLowTemperatureGroup 1 }
lgpConditionLowTemperatureInternal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low internal temperature condition.
The temperature is below a specified temperature threshold."
::= { lgpConditionLowTemperatureGroup 2 }
lgpConditionLowTemperatureExternalAirSensorA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
external air sensor A."
::= { lgpConditionLowTemperatureGroup 3 }
lgpConditionLowTemperatureExternalAirSensorB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
external air sensor B."
::= { lgpConditionLowTemperatureGroup 4 }
lgpConditionLowTemperatureRefrigerantSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
the refrigerant supply."
::= { lgpConditionLowTemperatureGroup 5 }
lgpConditionLowTemperatureFluidSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
the fluid supply."
::= { lgpConditionLowTemperatureGroup 6 }
lgpConditionLowTemperatureSupplyAir OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature is below the low temperature threshold for
the supply air."
::= { lgpConditionLowTemperatureGroup 7 }
lgpConditionHighHumidityGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high humidity condition. This group
contains various high humidity conditions."
::= { lgpConditionsWellKnown 144 }
lgpConditionHighHumiditySensor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity has exceeded the high humidity threshold for
sensor 1."
::= { lgpConditionHighHumidityGroup 1 }
lgpConditionHighHumidityReturnAir OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity has exceeded the high humidity threshold for
the return air."
::= { lgpConditionHighHumidityGroup 2 }
lgpConditionLowHumidityGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low humidity condition. This group
contains various high humidity conditions."
::= { lgpConditionsWellKnown 145 }
lgpConditionLowHumiditySensor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity is below the low humidity threshold for sensor 1."
::= { lgpConditionLowHumidityGroup 1 }
lgpConditionLowHumidityReturnAir OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity is below the low humidity threshold for the return
air."
::= { lgpConditionLowHumidityGroup 2 }
lgpConditionPeerNetworkNoMaster OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is unable to communicate with the master on the peer to
peer network."
::= { lgpConditionsWellKnown 146 }
lgpConditionNoOnOffPermissions OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system lacks the permissions to execute the on/off operation."
::= { lgpConditionsWellKnown 147 }
lgpConditionPeerNetworkFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a communication failure on the peer to
peer network."
::= { lgpConditionsWellKnown 148 }
lgpConditionUnitDisabled OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The unit is disabled."
::= { lgpConditionsWellKnown 149 }
lgpConditionUnitShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has shutdown."
::= { lgpConditionsWellKnown 150 }
lgpConditionPeerNetworkDiscovered OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has established communications on the peer to peer
network."
::= { lgpConditionsWellKnown 151 }
lgpConditionLossOfWaterFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of water flow condition."
::= { lgpConditionsWellKnown 152 }
lgpConditionCondensatePumpHighWater OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected high water in the condensate pump."
::= { lgpConditionsWellKnown 153 }
lgpConditionGeneralAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a general alarm condition."
::= { lgpConditionsWellKnown 154 }
lgpConditionProductSpecific OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a product specific condition. This condition
is not currently available via the agent card."
::= { lgpConditionsWellKnown 155 }
lgpConditionReheatLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has locked out the electrical reheat operation for a
specified amount of time."
::= { lgpConditionsWellKnown 156 }
lgpConditionHumidifierLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has locked out the humidifier operation for a
specified amount of time."
::= { lgpConditionsWellKnown 157 }
lgpConditionCompressorsLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has locked out compressor operation for a specified amount
of time."
::= { lgpConditionsWellKnown 158 }
lgpConditionCallService OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a condition that requires a service
representative be contacted."
::= { lgpConditionsWellKnown 159 }
lgpConditionLowMemoryGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various low memory conditions."
::= { lgpConditionsWellKnown 160 }
lgpConditionLowMemory1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low memory condition. The control
board is low in memory resources."
::= { lgpConditionLowMemoryGroup 1 }
lgpConditionMemoryFailureGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various memory device failure conditions."
::= { lgpConditionsWellKnown 161 }
lgpConditionMemory1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a memory 1 module failure."
::= { lgpConditionMemoryFailureGroup 1 }
lgpConditionMemory2Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a memory 2 module failure."
::= { lgpConditionMemoryFailureGroup 2 }
lgpConditionUnitCodeErrorGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various memory device failure conditions."
::= { lgpConditionsWellKnown 162 }
lgpConditionUnitCodeNotConfigured OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the unit code is not configured. The unit
code must be configured before system start-up."
::= { lgpConditionUnitCodeErrorGroup 1 }
lgpConditionUnitCode01OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 2 }
lgpConditionUnitCode02OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 3 }
lgpConditionUnitCode03OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 4 }
lgpConditionUnitCode04OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 5 }
lgpConditionUnitCode05OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 6 }
lgpConditionUnitCode06OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 7 }
lgpConditionUnitCode07OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 8 }
lgpConditionUnitCode08OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 9 }
lgpConditionUnitCode09OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 10 }
lgpConditionUnitCode10OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 11 }
lgpConditionUnitCode11OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 12 }
lgpConditionUnitCode12OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 13 }
lgpConditionUnitCode13OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 14 }
lgpConditionUnitCode14OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 15 }
lgpConditionUnitCode15OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 16 }
lgpConditionUnitCode16OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 17 }
lgpConditionUnitCode17OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 18 }
lgpConditionUnitCode18OutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a unit code error. This digit of the unit
code value is out of range."
::= { lgpConditionUnitCodeErrorGroup 19 }
lgpConditionHighExternalDewPoint OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high external dew point condition.
The room dew point has exceeded the specified threshold."
::= { lgpConditionsWellKnown 163 }
lgpConditionHcbDisconnected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the humidifier control board is disconnected
or not installed."
::= { lgpConditionsWellKnown 164 }
lgpConditionBmsResetTimerExpired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The BMS fan speed control reset counter has timed out."
::= { lgpConditionsWellKnown 165 }
lgpConditionAgentFirmwareCorrupt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The firmware update to the agent card has failed and the firmware is now
corrupt."
::= { lgpConditionsWellKnown 166 }
lgpConditionSystemAccessGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various system access conditions. An examples is
an open access panel."
::= { lgpConditionsWellKnown 175 }
lgpConditionFrontAccessOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the front access panel/door is open."
::= { lgpConditionSystemAccessGroup 1 }
lgpConditionRearAccessOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the rear access panel/door is open."
::= { lgpConditionSystemAccessGroup 2 }
lgpConditionsDamperFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various damper failure conditions."
::= { lgpConditionsWellKnown 176 }
lgpConditionEmergencyDamperFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an emergency damper failure. The damper is
in the wrong position."
::= { lgpConditionsDamperFailure 1 }
lgpConditionRemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A remote shutdown occurred."
::= { lgpConditionsWellKnown 177 }
lgpConditionFireAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fire Alarm."
::= { lgpConditionsWellKnown 178 }
lgpConditionHeatersOverheated OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Heaters Overheated."
::= { lgpConditionsWellKnown 179 }
lgpConditionCondenserFailureGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains condenser failure conditions."
::= { lgpConditionsWellKnown 180 }
lgpConditionCondenser1Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser 1 Failure."
::= { lgpConditionCondenserFailureGroup 1 }
lgpConditionCondenser2Failure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser 2 Failure."
::= { lgpConditionCondenserFailureGroup 2 }
lgpConditionCondenserTVSSFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed."
::= { lgpConditionCondenserFailureGroup 3 }
lgpConditionHumidifierCyclinderWorn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the humidifier cylinder is worn."
::= { lgpConditionsWellKnown 181 }
lgpConditionUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low current condition. The current of
one or more sources in the system has fallen below a threshold for
a specified amount of time. The threshold and time that triggered
this condition is system dependent."
::= { lgpConditionsWellKnown 182 }
lgpConditionHumidifierUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low current condition on the
humidifier. The current of the humidifier has fallen below
a pre-determined threshold for a defined amount of time."
::= { lgpConditionUnderCurrent 1 }
lgpConditionInputUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"There is a low current condition on the input power source. The
current of the input power source has fallen below a
pre-determined threshold for a defined amount of time."
::= { lgpConditionUnderCurrent 2 }
lgpConditionHeatRejectorGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains failure conditions for the heat rejection unit."
::= { lgpConditionsWellKnown 183 }
lgpConditionHeatRejectorFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The heat rejecter fan has failed."
::= { lgpConditionHeatRejectorGroup 1 }
lgpConditionHeatRejectorVoltageSuppressionFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The heat rejecter voltage suppression has failed and is no longer
able to protect the unit from power fluctuations."
::= { lgpConditionHeatRejectorGroup 2 }
lgpConditionFreeCoolLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The free cooling capability has been disabled."
::= { lgpConditionsWellKnown 184 }
lgpConditionWaterLeakSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The sensor used to detect water leaks is not connected or has failed."
::= { lgpConditionsWellKnown 185 }
lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"There is no load detected on the output. This can be an indication
that the output is being powered by an external bypass source and has
inadvertently been left on external bypass. This warning is triggered
after a delay. The delay is specified by the object
'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output
current falls below a certain threshold specified by the object
'lgpPwrNoLoadWarningLimit'"
::= { lgpConditionsWellKnown 186 }
lgpConditionFirmwareGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Grouping level for firmware related conditions."
::= { lgpConditionsWellKnown 187 }
lgpConditionFirmwareUpdateRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The firmware on the system or one or more components of the
system must be updated. This typically indicates that one or more
components of the system contain corrupted firmware or the
firmware on one or more components are incompatible with one
another. When this condition is active the system may not be able
to function to its full capacity or may not be able to function at
all."
::= { lgpConditionFirmwareGroup 3 }
lgpConditionTestGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Objects in this group of conditions are related to testing or test
events. This object is never active."
::= { lgpConditionsWellKnown 188 }
lgpConditionTest01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This is a 'test' condition. It is a generic test event that can
be utilized to evaluate system handling of events. Some products
will support the activation of this event upon user request so that
user management stations can execute end-to-end event handling
tests."
::= { lgpConditionTestGroup 5 }
lgpConditionReceptacleBranchGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Grouping level for receptacle branch conditions."
::= { lgpConditionsWellKnown 190 }
lgpConditionRcpBranchFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle branch module or control system has failed.
Service is required."
::= { lgpConditionReceptacleBranchGroup 5 }
lgpConditionRcpBranchBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle branch breaker is open."
::= { lgpConditionReceptacleBranchGroup 10 }
lgpConditionInputUnqualified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input is not qualified to provide power to the system. This may
be due to system input over-voltage, system input under-voltage,
system input frequency out of range, or other similar issues."
::= { lgpConditionsWellKnown 192 }
lgpConditionBypassUnavailable OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This summary event is asserted when the bypass is not available.
Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass
Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or
other similar causes."
::= { lgpConditionsWellKnown 193 }
lgpConditionAutoTransferFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is failing to automatically transfer the load to the
alternate source."
::= { lgpConditionsWellKnown 194 }
lgpConditionSBSUnavailable OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A Static Bypass Switch (SBS) Failure has been detected. Possible
causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier)
Shorted, SBS Overload Exceeded, Bypass Power Supply
Fail, Static Bypass Switch Fuse Failure, or other similar causes."
::= { lgpConditionsWellKnown 195 }
lgpConditionSBSOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"On at least one phase of the static bypass switch (SBS), the power
dissipation limit has been exceeded."
::= { lgpConditionsWellKnown 196 }
lgpConditionExcessPulseParallel OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has performed too many pulse parallel operations within
the specified time interval. A pulse parallel operation is a
momentary operation of the static bypass switch (SBS) in parallel with
the inverter."
::= { lgpConditionsWellKnown 197 }
lgpConditionRemoteBypassSwitchOffExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The static bypass switch is off due to the state of an external
signal."
::= { lgpConditionsWellKnown 198 }
lgpConditionManTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Manual transfer from inverter to bypass is inhibited. Bypass is not
qualified."
::= { lgpConditionsWellKnown 199 }
lgpConditionManReTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Manual retransfer from bypass to inverter is inhibited."
::= { lgpConditionsWellKnown 200 }
lgpConditionBatteryChargeError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is not charging properly. Some reasons for this condition
include, but are not limited to: battery charger failure,
battery failure, etc."
::= { lgpConditionsWellKnown 201 }
lgpConditionBatteryAutoTestInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic (scheduled) battery tests are inhibited."
::= { lgpConditionsWellKnown 202 }
lgpConditionBatteryChargeReducedExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A reduced battery charging algorithm is being used due to an external
signal."
::= { lgpConditionsWellKnown 203 }
lgpConditionBatteryCapacityLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery capacity is low. Some reasons for this condition include,
but are not limited to: a battery is offline, the battery age has
reduced its capabilities, etc."
::= { lgpConditionsWellKnown 204 }
lgpConditionBatteryTempImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature difference between two batteries in the system
exceeds the predefined threshold."
::= { lgpConditionsWellKnown 205 }
lgpConditionBatteryEqualize OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The rectifier output voltage has been increased to equalize the battery
voltage level."
::= { lgpConditionsWellKnown 206 }
lgpConditionBatteryChargeInhibitedExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery charging is inhibited due to an external inhibit signal."
::= { lgpConditionsWellKnown 207 }
lgpConditionServiceExtBatteryMonitorGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains battery monitor service conditions."
::= { lgpConditionsWellKnown 208 }
lgpConditionServiceExtBatteryMonitor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External battery monitor 1 indicates battery maintenance is
required."
::= { lgpConditionServiceExtBatteryMonitorGroup 1 }
lgpConditionServiceExtBatteryMonitor2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External battery monitor 2 indicates battery maintenance is
required."
::= { lgpConditionServiceExtBatteryMonitorGroup 2 }
lgpConditionBatteryGroundFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery system ground fault amperage exceeds the threshold."
::= { lgpConditionsWellKnown 209 }
lgpConditionBatteryLowShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"With the battery breaker closed, the battery voltage has dropped
below the calculated End-Of-Discharge (EOD) limit."
::= { lgpConditionsWellKnown 210 }
lgpConditionEmergencyPowerOffLocal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an Emergency Power Off (EPO) condition.
The local EPO switch has cut off the power source to the system."
::= { lgpConditionsWellKnown 211 }
lgpConditionOutputLowPFLagging OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a lagging output power factor below the
threshold, resulting in reduced load capacity."
::= { lgpConditionsWellKnown 212 }
lgpConditionOutputLowPFLeading OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a leading output power factor below the
threshold, resulting in reduced load capacity."
::= { lgpConditionsWellKnown 213 }
lgpConditionOutputToLoadFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an output to load fault. This could be
caused by over or under voltage, or by over or under frequency."
::= { lgpConditionsWellKnown 214 }
lgpConditionInvRestartInhibitedExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Restart of the inverter is inhibited by an external signal."
::= { lgpConditionsWellKnown 215 }
lgpConditionInverterShutdownOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has shutdown the inverter due to a sustained overload.
This event does not indicate if the load has been dropped or
transferred to bypass. At least one phase of the inverter power
dissipation limit has been exceeded."
::= { lgpConditionsWellKnown 216 }
lgpConditionInverterOffExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter is off due to the state of an external signal."
::= { lgpConditionsWellKnown 217 }
lgpConditionInputContactGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an active input contact."
::= { lgpConditionsWellKnown 218 }
lgpConditionInputContact01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 1 is active."
::= { lgpConditionInputContactGroup 1 }
lgpConditionInputContact02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 2 is active."
::= { lgpConditionInputContactGroup 2 }
lgpConditionInputContact03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 3 is active."
::= { lgpConditionInputContactGroup 3 }
lgpConditionInputContact04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 4 is active."
::= { lgpConditionInputContactGroup 4 }
lgpConditionInputContact05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 5 is active."
::= { lgpConditionInputContactGroup 5 }
lgpConditionInputContact06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 6 is active."
::= { lgpConditionInputContactGroup 6 }
lgpConditionInputContact07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 7 is active."
::= { lgpConditionInputContactGroup 7 }
lgpConditionInputContact08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 8 is active."
::= { lgpConditionInputContactGroup 8 }
lgpConditionInputContact09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 9 is active."
::= { lgpConditionInputContactGroup 9 }
lgpConditionInputContact10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 10 is active."
::= { lgpConditionInputContactGroup 10 }
lgpConditionInputContact11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 11 is active."
::= { lgpConditionInputContactGroup 11 }
lgpConditionInputContact12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 12 is active."
::= { lgpConditionInputContactGroup 12 }
lgpConditionInputContact13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 13 is active."
::= { lgpConditionInputContactGroup 13 }
lgpConditionInputContact14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 14 is active."
::= { lgpConditionInputContactGroup 14 }
lgpConditionInputContact15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 15 is active."
::= { lgpConditionInputContactGroup 15 }
lgpConditionInputContact16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that input contact 16 is active."
::= { lgpConditionInputContactGroup 16 }
lgpConditionRectifierOperInhibited
OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The operation of the rectifier is inhibited by an external signal."
::= { lgpConditionsWellKnown 219 }
lgpConditionBypassBackFeedBrkrOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass backfeed breaker is in the open position."
::= { lgpConditionsWellKnown 220 }
lgpConditionAutoRestartInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Auto restart is in progress. Becomes inactive when auto restart
completes or fails."
::= { lgpConditionsWellKnown 221 }
lgpConditionAutoRestartInhibitedExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Auto restart is inhibited due to an external signal."
::= { lgpConditionsWellKnown 222 }
lgpConditionAutoRestartFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Auto restart has failed."
::= { lgpConditionsWellKnown 223 }
lgpConditionInputOnGenerator OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A generator is supplying the power to the system."
::= { lgpConditionsWellKnown 224 }
lgpConditionInputFilterCycleLock OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input filter disconnect has opened too many times within a given
period of time."
::= { lgpConditionsWellKnown 225 }
lgpConditionServiceCodeActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is in an operational mode intended for testing. In normal
operating conditions, the system should not be in this state."
::= { lgpConditionsWellKnown 226 }
lgpConditionLoadBusSyncActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load Bus Sync Operation is active. This synchronizes the UPS output
with the output of another UPS."
::= { lgpConditionsWellKnown 227 }
lgpConditionLoadBusSyncInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that conditions to perform Load Bus Sync
Operation are not satisfied."
::= { lgpConditionsWellKnown 228 }
lgpConditionControlsResetRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A controls reset is required because one or more critical settings
have changed."
::= { lgpConditionsWellKnown 229 }
lgpConditionEquipTempSensorFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature sensor is reporting a value outside the bounds of a
properly operating sensor."
::= { lgpConditionsWellKnown 230 }
lgpConditionInputCurrentImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current on one input phase is much greater or lower than the
average current of all the phases. This may indicate improper operation
of the rectifier or input filter."
::= { lgpConditionsWellKnown 231 }
lgpConditionPumpGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an alarm with one of the pumps."
::= { lgpConditionsWellKnown 232 }
lgpConditionPumpFlowLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of flow with one or more pumps."
::= { lgpConditionPumpGroup 1 }
lgpConditionPump1FlowLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of flow with pump 1."
::= { lgpConditionPumpFlowLoss 1 }
lgpConditionPump2FlowLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a loss of flow with pump 2."
::= { lgpConditionPumpFlowLoss 2 }
lgpConditionPumpShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycling of the pumps. One or more
of the pumps has been turned on and off a number of times within a
specified time period."
::= { lgpConditionPumpGroup 2 }
lgpConditionPumpInverterShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycling of one or more pump
inverters and has temporarily locked out further pump operation
to protect from thermal overload. A short cycle is defined as
powering on and off a number of times over a set time period."
::= { lgpConditionPumpGroup 3 }
lgpConditionPump1InverterShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycling of the inverter for
pump 1 and has temporarily locked out further pump operation
to protect from thermal overload. A short cycle is defined as
powering on and off a number of times over a set time period."
::= { lgpConditionPumpInverterShortCycle 1 }
lgpConditionPump2InverterShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short cycling of the inverter for
pump 2 and has temporarily locked out further pump operation
to protect from thermal overload. A short cycle is defined as
powering on and off a number of times over a set time period."
::= { lgpConditionPumpInverterShortCycle 2 }
lgpConditionValveGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an alarm with one of the valves."
::= { lgpConditionsWellKnown 233 }
lgpConditionChilledWaterValvePosition OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a problem with the chilled water valve
position. The position of the chilled water control valve does not
match an expected value."
::= { lgpConditionValveGroup 1 }
lgpConditionCondensationDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected condensation."
::= { lgpConditionsWellKnown 234 }
lgpConditionMaintenanceGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a maintenance condition. This group
contains various maintenance conditions."
::= { lgpConditionsWellKnown 235 }
lgpConditionMaintenanceDue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System is due for maintenance."
::= { lgpConditionMaintenanceGroup 1 }
lgpConditionMaintenanceComplete OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system maintenance has been completed."
::= { lgpConditionMaintenanceGroup 2 }
lgpConditionExternalEventSignalGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains various conditions signalled by external inputs.
Each event is deactivated when the signal is inactive."
::= { lgpConditionsWellKnown 236 }
lgpConditionExternalFireDetect OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fire detected, as indicated by an external input signal."
::= { lgpConditionExternalEventSignalGroup 1 }
lgpConditionExternalFlowLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of flow is detected, as indicated by an external input signal."
::= { lgpConditionExternalEventSignalGroup 2 }
lgpConditionExternalReheatLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The reheater is shut down and disabled by an external input signal."
::= { lgpConditionExternalEventSignalGroup 3 }
lgpConditionExternalOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature has exceeded its threshold, as indicated by an
external input signal."
::= { lgpConditionExternalEventSignalGroup 4 }
lgpConditionExternalCompLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The compressor is shut down and disabled by an external input signal."
::= { lgpConditionExternalEventSignalGroup 5 }
lgpConditionExternalHumidifierLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidifier is shut down and disabled by an external input signal."
::= { lgpConditionExternalEventSignalGroup 6 }
lgpConditionComponentShutdownGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains conditions signaling shutdown of various system
components."
::= { lgpConditionsWellKnown 237 }
lgpConditionComponentShutdownPartial OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An event has occurred requiring some system components to be
shutdown and disabled."
::= { lgpConditionComponentShutdownGroup 1 }
lgpConditionComponentShutdownHighPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply to high power components has been shutdown."
::= { lgpConditionComponentShutdownGroup 2 }
lgpConditionCondenserProblemGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains condenser conditions."
::= { lgpConditionsWellKnown 238 }
lgpConditionCondenser1Problem OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser 1 is not operating within its normal parameters."
::= { lgpConditionCondenserProblemGroup 1 }
lgpConditionHumidityOutOfPropBand OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a humidity reading that remained outside of
the proportional control band for an extended period of time."
::= { lgpConditionsWellKnown 239 }
lgpConditionEnvRemoteSensorGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains remote sensors."
::= { lgpConditionsWellKnown 240 }
lgpConditionEnvRemoteSensor1Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 1 }
lgpConditionEnvRemoteSensor2Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 2 }
lgpConditionEnvRemoteSensor3Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 3 }
lgpConditionEnvRemoteSensor4Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 4 }
lgpConditionEnvRemoteSensor5Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 5 }
lgpConditionEnvRemoteSensor6Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 6 }
lgpConditionEnvRemoteSensor7Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 7 }
lgpConditionEnvRemoteSensor8Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 8 }
lgpConditionEnvRemoteSensor9Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 9 }
lgpConditionEnvRemoteSensor10Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range. The
event is deactivated when sensor signal is re-established."
::= { lgpConditionEnvRemoteSensorGroup 10 }
lgpConditionNeutralSnubberBoardCommFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Neutral Snubber board has stopped communicating."
::= { lgpConditionsWellKnown 241 }
lgpConditionRedundantChargerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The redundant charger has failed."
::= { lgpConditionsWellKnown 242 }
lgpConditionBoardInputContactorPowerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Board input contactor power failure."
::= { lgpConditionsWellKnown 243 }
lgpConditionBoard1InputContactorPowerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Board1 input contactor power failure."
::= { lgpConditionBoardInputContactorPowerFailure 1 }
lgpConditionBoard2InputContactorPowerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Board2 input contactor power failure."
::= { lgpConditionBoardInputContactorPowerFailure 2 }
lgpConditionTooManySensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The number of sensors installed on the device has exceeded the
pre-determined limit."
::= { lgpConditionsWellKnown 5423 }
lgpConditionDoorSwitchOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An open door has been detected."
::= { lgpConditionsWellKnown 5471 }
lgpConditionContactClosureOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An open circuit has been detected."
::= { lgpConditionsWellKnown 5479 }
lgpConditionContactClosureClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A closed circuit has been detected."
::= { lgpConditionsWellKnown 5480 }
lgpConditionSensorsNotDisplayed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The number of sensors that can be displayed (monitored) on the
device has exceeded the pre-determined limit. Note this condition
differs from the lgpConditionTooManySensors in that the system may
currently have less than the maximum of installed sensors present but
one or more of those sensors can not be displayed because the display
order table (lgpPduAuxMeasOrderTable) contains entries for sensors
that are not currently installed. This condition effectively
prevents one or more installed sensors from being presented in the
lgpPduAuxMeasTable. It is possible for both this condition and the
lgpConditionTooManySensors condition to be active at the same time."
::= { lgpConditionsWellKnown 6119 }
END