LIEBERT-GP-SRC-MIB DEFINITIONS ::= BEGIN
IMPORTS
sysUpTime
FROM RFC1213-MIB
MODULE-IDENTITY,
OBJECT-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
lgpSrc,
liebertSrcModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsSrcModule MODULE-IDENTITY
LAST-UPDATED "201711100000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Colby Lin "
DESCRIPTION
"The MIB module used to register Liebert POWER related SNMP OIDs.
Copyright 2008-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "201711100000Z"
DESCRIPTION
"Added unknown(2147483647) for invalid SRC device readings"
REVISION "201710160000Z"
DESCRIPTION
"Added Temperature High/Low Threshold"
REVISION "201708180000Z"
DESCRIPTION
"Initial Version"
::= { liebertSrcModuleReg 1 }
lgpSrcTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpSrcEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A table containing information about SRC device."
::= { lgpSrc 1 }
lgpSrcEntry OBJECT-TYPE
SYNTAX LgpSrcEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the rows for the table
'lgpSrcTable'. A row in this table cannot be created or deleted by
SNMP operations on columns of the table."
INDEX { lgpSrcDevId }
::= { lgpSrcTable 1 }
LgpSrcEntry ::= SEQUENCE {
lgpSrcDevId Unsigned32,
lgpSrcDevAddress Unsigned32,
lgpSrcDevState INTEGER,
lgpSrcDevTemperatureDegF INTEGER,
lgpSrcDevTemperatureSetpointDegF INTEGER,
lgpSrcDevTemperatureDegC INTEGER,
lgpSrcDevTemperatureSetpointDegC INTEGER,
lgpSrcDevFanSpeed INTEGER,
lgpSrcDevPowerStatus INTEGER,
lgpSrcDevOperatingMode INTEGER,
lgpSrcDevTemperatureHighThresholdDegF INTEGER,
lgpSrcDevTemperatureLowThresholdDegF INTEGER,
lgpSrcDevTemperatureHighThresholdDegC INTEGER,
lgpSrcDevTemperatureLowThresholdDegC INTEGER
}
lgpSrcDevId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value must remain constant between agent initializations.
This Device ID is used as an index of the table
'lgpSrcTable'."
::= { lgpSrcEntry 1 }
lgpSrcDevAddress OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value must remain constant between agent initializations.
This Device Address is used as an index of the table
'lgpSrcTable'."
::= { lgpSrcEntry 2 }
lgpSrcDevState OBJECT-TYPE
SYNTAX INTEGER
{
enabled(1),
standbyOffline(2),
unavailableOffline(3),
absent(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the current state of SRC device. The value of this
object is set to enabled(1) if the SRC device has been enabled.
The value of this object is set to standbyOffline(2) if the SRC
device is waiting for an external action to activate it. The value
of this object is set to unavailableOffline(3) if the SRC device is
present but cannot be used. The value of this object is set to
absent(4) if the SRC device is not present or not detected. The
value of this object will be one of the valid device state:
enabled(1), standbyOffline(2), unavailableOffline(3), or
absent(4)."
::= { lgpSrcEntry 3 }
lgpSrcDevTemperatureDegF OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value in Fahrenheit. The value of this
object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 4 }
lgpSrcDevTemperatureSetpointDegF OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting in Fahrenheit for SRC. This setting may
or may not be the setting used from control. Some systems have the
capability to dynamically change the control setting based on
environmental conditions and/or user configuration. The value of
this object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 5 }
lgpSrcDevTemperatureDegC OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured temperature value in Celsius. The value of this
object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 6 }
lgpSrcDevTemperatureSetpointDegC OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The temperature setting in Celsius for SRC. This setting may or
may not be the setting used from control. Some systems have the
capability to dynamically change the control setting based on
environmental conditions and/or user configuration. The value of
this object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 7 }
lgpSrcDevFanSpeed OBJECT-TYPE
SYNTAX INTEGER
{
low(1),
middle(2),
high(3),
auto(4),
unknown(2147483647)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present fan speed of the SRC device. This object will be one
of the valid fan speed: low(1), middle(2), high(3) or auto(4) if
the value of lgpSrcDevState object is set to enabled(1). The value
of this object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 8 }
lgpSrcDevPowerStatus OBJECT-TYPE
SYNTAX INTEGER
{
off(0),
on(1),
unknown(2147483647)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of this object specifies the power status of SRC device.
Power status cannot be configured by an operator. The value of
this object is set to off(0) if the SRC device is powered off.
The value of this object is set to on(1) if the SRC device is
powered on. The value of this object will be one of the valid power
status: off(0) or on(1) if lgpSrcDevState is enabled(1). The value
of this object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 9 }
lgpSrcDevOperatingMode OBJECT-TYPE
SYNTAX INTEGER
{
cooling(0),
dehumidify(1),
fan(2),
ai(3),
heating(4),
unknown(2147483647)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present operating mode of the SRC device. This object will be
one of the valid operating mode: cooling(0), dehumidify(1), fan(2),
ai(3) or heating(4) if the value of lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 10 }
lgpSrcDevTemperatureHighThresholdDegF OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpSrcDevTemperatureDegF' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 11 }
lgpSrcDevTemperatureLowThresholdDegF OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpSrcDevTemperatureDegF' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 12 }
lgpSrcDevTemperatureHighThresholdDegC OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature notification threshold. This is the maximum
value of 'lgpSrcDevTemperatureDegC' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 13 }
lgpSrcDevTemperatureLowThresholdDegC OBJECT-TYPE
SYNTAX INTEGER
{
unknown(2147483647)
}
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low temperature notification threshold. This is the minimum
value of 'lgpSrcDevTemperatureDegC' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4)."
::= { lgpSrcEntry 14 }
END