LIEBERT-GP-SYSTEM-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE,
MODULE-IDENTITY,
OBJECT-IDENTITY,
NOTIFICATION-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
lgpSystem,
liebertSystemModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
sysUpTime
FROM RFC1213-MIB
lgpAgentConnectedDeviceCount,
lgpAgentDeviceIndex
FROM LIEBERT-GP-AGENT-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
--
liebertSystemModule MODULE-IDENTITY
LAST-UPDATED "200811170000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Gregory M. Hoge"
DESCRIPTION
"The MIB module used to specify Liebert Controller OIDs
Copyright 2000-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "200811170000Z"
DESCRIPTION
"Added support for NXL unit."
REVISION "200807020000Z"
DESCRIPTION
"Added missing items to the IMPORT statement"
REVISION "200801100000Z"
DESCRIPTION
"Add system notifications sub-tree and modified contact email address."
REVISION "200705290000Z"
DESCRIPTION
"Added support for XDF Unit."
REVISION "200602220000Z"
DESCRIPTION
"Added support for Liebert DS Unit."
::= { liebertSystemModuleReg 1 }
-- =============================================================================
-- lgpSystem - Liebert System Groups
-- =============================================================================
lgpSysStatistics OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Statistics object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Statistics
Group."
::= { lgpSystem 1 }
lgpSysStatus OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Status object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Status
Group."
::= { lgpSystem 2 }
lgpSysSettings OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Settings object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Settings
Group."
::= { lgpSystem 3 }
lgpSysControl OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Control object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Control
Group."
::= { lgpSystem 4 }
lgpSysTime OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Time object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Time
Group."
::= { lgpSystem 5 }
lgpSysMaintenance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Maintenance object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert System Maintenance
Group."
::= { lgpSystem 6 }
lgpSysEventDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An ASCII textual description for the event. This object is
primarily used in the varbind of some notifications to provide
a simple human-readable description."
::= { lgpSystem 7 }
lgpSysEventNotifications OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert System Notification object
identifiers."
::= { lgpSystem 8 }
-- -----------------------------------------------------------------------------
-- Device Component Group
-- -----------------------------------------------------------------------------
lgpSysDeviceComponentGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known device components."
REFERENCE
"These well known components are referenced in the
'lgpSysDeviceComponentDescr' column in the
'lgpSysDeviceComponentTable'."
::= { lgpSystem 9 }
-- -----------------------------------------------------------------------------
-- Device Component Table
-- -----------------------------------------------------------------------------
lgpSysDeviceComponentTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpSysDeviceComponentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of components of devices identified by their serial number and
or model number.
This table contains zero, one, or many rows. The NMS cannot create or
delete rows from the table. The rows are created by the agent based upon
the capabilities of the managed device."
::= { lgpSysDeviceComponentGroup 1 }
lgpSysDeviceComponentEntry OBJECT-TYPE
SYNTAX LgpSysDeviceComponentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpSysDeviceComponentTable'."
INDEX { lgpAgentDeviceIndex, lgpSysDeviceComponentIndex }
::= { lgpSysDeviceComponentTable 1 }
LgpSysDeviceComponentEntry ::= SEQUENCE
{
lgpSysDeviceComponentIndex Unsigned32,
lgpSysDeviceComponentDescr OBJECT IDENTIFIER,
lgpSysDeviceComponentSerialNum DisplayString (SIZE (255)),
lgpSysDeviceComponentModelNum DisplayString (SIZE (255))
}
lgpSysDeviceComponentIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row in the table
'lgpSysDeviceComponentTable' for a component entry."
::= { lgpSysDeviceComponentEntry 1 }
lgpSysDeviceComponentDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a component of the device indicated by the
index lgpAgentDeviceIndex."
REFERENCE
"The object identifiers in this column can be found in the
sub-tree 'lgpSysDeviceComponentWellknown'."
::= { lgpSysDeviceComponentEntry 2 }
lgpSysDeviceComponentSerialNum OBJECT-TYPE
SYNTAX DisplayString (SIZE (255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the serial number of the component described by the OID
'lgpSysDeviceComponentDescr'. This data is intended for
display / human consumption. Do not use this field for determining
programmatic behavior."
::= { lgpSysDeviceComponentEntry 3 }
lgpSysDeviceComponentModelNum OBJECT-TYPE
SYNTAX DisplayString (SIZE (255))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the model identifier of the component described by the OID
'lgpSysDeviceComponentDescr'. This data is intended for
display / human consumption. Do not use this field for determining
programmatic behavior."
::= { lgpSysDeviceComponentEntry 4 }
lgpSysDeviceComponentWellknown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert System Components."
REFERENCE
"These well known measurement identifiers are referenced in the
'lgpSysDeviceComponentDescr' column in the
'lgpSysDeviceComponentTable'."
::= { lgpSysDeviceComponentGroup 5 }
lgpSysDeviceBatCabinet OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a battery cabinet component.
To determine the cabinet being described in a
multi-cabinet system, this point implements an additional
two indexes. The first index describes the module the cabinet
is located in. The second index describes the cabinet
number. In an SMS (Single-Module System) the first index is
always 1.
Example: lgpSysDeviceComponentCabinet.2.4
'lgpSysDeviceCabinet' = Point is a battery cabinet.
'.2' = Cabinet is in the second module.
'.4' = Cabinet number 4 in second module"
::= { lgpSysDeviceComponentWellknown 5 }
lgpSysDeviceParallelCabinet OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a parallel cabinet."
::= { lgpSysDeviceComponentWellknown 6 }
lgpSysDeviceMaintBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register the maintenance bypass."
::= { lgpSysDeviceComponentWellknown 7 }
-- =============================================================================
-- lgpSysNotifications - Liebert System Notifications Group
-- =============================================================================
lgpSysNotification NOTIFICATION-TYPE
OBJECTS { sysUpTime, lgpSysEventDescription }
STATUS current
DESCRIPTION
"This notification is a generic notification intended for direct user
visibility. The user event description identifies the system
condition that has occurred. This text will be prefixed with either
'Active:', 'Cleared:', or 'Message:' depending on the state of the
event. Note: That a prefix of 'Message:' identifies a stateless event
and as such there will be no corresponding 'Cleared:' trap sent."
::= { lgpSysEventNotifications 1 }
lgpSysNormal NOTIFICATION-TYPE
OBJECTS { sysUpTime, lgpAgentConnectedDeviceCount }
STATUS current
DESCRIPTION
"The system has returned to a normal operating state. This implies
prior to the generation of this event the system was operating in a
state where one or more alarm or warning conditions were present.
All of those alarms or conditions have now cleared.
NOTE: This notification may be generated after a short delay during a
cold boot of the system -- if no alarms or conditions are present in the
monitored device(s) at that time."
::= { lgpSysEventNotifications 2 }
-- =============================================================================
-- lgpSysStatistics - Liebert System Statistics Group
-- =============================================================================
lgpSysStatisticsRunHrs OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated run hours of the system."
::= { lgpSysStatistics 1 }
-- =============================================================================
-- lgpSysStatus - Liebert System Status Group
-- =============================================================================
lgpSysSelfTestResult OBJECT-TYPE
SYNTAX INTEGER
{
unknown(1),
passed(2),
failed(3),
inProgress(4),
sysFailure(5),
inhibited(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outcome of the previous self-test."
::= { lgpSysStatus 1 }
lgpSysState OBJECT-TYPE
SYNTAX INTEGER
{
normalOperation(1),
startUp(2),
normalWithWarning(3),
normalWithAlarm(4),
abnormalOperation(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operating status for the system. The intent of this data
is to provide a high level status of the system.
The possible states are:
normalOperation(1)
The system is operating normally with no active warnings or
alarms.
startUp(2)
The system is in a startup state (initializing). Monitoring
operations and information may not be fully supported at this
time. This state will clear automatically when the system is
fully initialized and ready to accept monitoring commands.
normalWithWarning(3)
The system is operating normally with one or more active
warnings. Appropriate personnel should investigate the
warning(s) as soon as possible and take appropriate action.
normalWithAlarm(4)
The system is operating normally with one or more active
alarms. Appropriate personnel should investigate the alarm(s)
as soon as possible and take appropriate action.
abnormalOperation(5)
They system is operating abnormally. There is a
failure within the system that is unexpected under normal
operating conditions. Appropriate personnel should investigate
the cause as soon as possible. The normal functioning of
the system is likely inhibited."
::= { lgpSysStatus 2 }
-- =============================================================================
-- lgpSysSettings - Liebert System Settings Group
-- =============================================================================
lgpSysAudibleAlarm OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state of the audible alarm of the device."
::= { lgpSysSettings 1 }
-- =============================================================================
-- lgpSysControl - Liebert System Control Group
-- =============================================================================
lgpSysSelfTest OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Self-Test Command. This command will initiate a system self-test of
the system. If already initiated, this command will abort the
self-test. This command should be sent with a parameter of 1. This
variable doesn't return a value when read."
::= { lgpSysControl 1 }
lgpSysControlOperationOnOff OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object allows control of the system functionality. This will not
affect the communications or control of the system, so that once turned
off, the system operation can be restored by setting this value to
'on'."
::= { lgpSysControl 2 }
-- =============================================================================
-- lgpSysTime - Liebert System Time Group
-- =============================================================================
lgpSysTimeEpoch OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present time of the system. This time is represented as the
number of seconds since the epoch of 1970-01-01 00:00:00 GMT."
::= { lgpSysTime 1 }
-- =============================================================================
-- lgpSysMaintenance - Liebert System Maintenance Group
-- =============================================================================
lgpSysMaintenanceCapacity OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The relative percentage of time that has elapsed since the last
scheduled maintenance was performed. When this value reaches 100%,
the device is due for another scheduled maintenance procedure."
::= { lgpSysMaintenance 1 }
lgpSysMaintenanceYear OBJECT-TYPE
SYNTAX Unsigned32
UNITS "year"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The year in which the next scheduled service is due"
::= { lgpSysMaintenance 2 }
lgpSysMaintenanceMonth OBJECT-TYPE
SYNTAX Unsigned32
UNITS "month"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The month in which the next scheduled service is due"
::= { lgpSysMaintenance 3 }
END