DKSF-70-6-X-X-1 DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
Counter32,
Gauge32,
Counter64,
Integer32,
TimeTicks,
NOTIFICATION-TYPE
FROM SNMPv2-SMI
TEXTUAL-CONVENTION,
DisplayString,
TruthValue,
TimeStamp
FROM SNMPv2-TC
snmpTraps
FROM SNMPv2-MIB ;
uniPingServerSolutionV3 MODULE-IDENTITY
LAST-UPDATED "201608240000Z"
ORGANIZATION "Alentis Electronics"
CONTACT-INFO
"developers@netping.ru"
DESCRIPTION
"Generic MIB for NetPing remote sensing and control"
REVISION "201608240000Z"
DESCRIPTION
"npThermoValuePrecise added
npGsmSendSms renamed to npGsmSendSmsUtf8
npGsmSendWin1251 added"
REVISION "201507140000Z"
DESCRIPTION
"npSmoke branch added, npRelHum branch extended"
REVISION "201505290000Z"
DESCRIPTION
"npIoTrapLevelLegend added, npIrStatus values redefined"
REVISION "201412030000Z"
DESCRIPTION
"npRelayMode, npIoLevelOut values changed"
REVISION "201411260000Z"
DESCRIPTION
"npRelayN, npRelayMode, npIoLineN, npRelHumSensorStatusH, npRelHumSensorStatus values changed"
REVISION "201402020000Z"
DESCRIPTION
"npRelayMode valid values changed, (3) excluded "
REVISION "201401290000Z"
DESCRIPTION
"npCurLoop, npRelHumidity, npIr branches has added"
REVISION "201401210000Z"
DESCRIPTION
"partial rewrite for DKSF 70"
REVISION "201304110000Z"
DESCRIPTION
"partial rewrite for DKSF 48"
REVISION "201205310000Z"
DESCRIPTION
"npPwrRelayState branch was added"
REVISION "201204170000Z"
DESCRIPTION
"npReboot branch was added"
REVISION "201203230000Z"
DESCRIPTION
"Minor changes to IR module for IRC-TRv2"
REVISION "201109230000Z"
DESCRIPTION
"4 IO lines,
Identification is changed from DKSF 52.4 to DKSF 52.5"
REVISION "201103240000Z"
DESCRIPTION
"npIoPulseCounter, npIoSinglePulseDuration, npIoSinglePulseStart is added
Identification is changed from DKSF 52.3 to DKSF 52.4"
REVISION "201010140000Z"
DESCRIPTION
"IR module support"
REVISION "201009200000Z"
DESCRIPTION
"dksf 52.3 subversion"
REVISION "201005310000Z"
DESCRIPTION
"dksf 51.3 subversion"
REVISION "201004140000Z"
DESCRIPTION
"SMIv2-style rewrite"
::= { lightcom 70 }
lightcom OBJECT IDENTIFIER::={enterprises 25728 }
FixedPoint1000 ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION "Fixed-point value as Integer, 3 decimal gigits after point (i.e. value*1000 rounded to Integer)"
SYNTAX INTEGER
npTrapInfo OBJECT IDENTIFIER::={lightcom 90}
npTrapEmailTo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "user-specified e-mail for NetPing Trap Forwarding Service"
::={npTrapInfo 1}
npRelay OBJECT IDENTIFIER::={ lightcom 5500 }
npRelayTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Watchdog and outlet/relay control table"
::= { npRelay 5 }
npRelayEntry OBJECT-TYPE
SYNTAX NpRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Relay/outlet table row"
INDEX { npRelayN }
::= { npRelayTable 1 }
NpRelayEntry ::= SEQUENCE {
npRelayN INTEGER,
npRelayMode INTEGER,
npRelayStartReset INTEGER,
npRelayMemo DisplayString,
npRelayState INTEGER
-- not in dksf70 npRelayPowered INTEGER
}
npRelayN OBJECT-TYPE
SYNTAX INTEGER (1..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The N of output relay"
::= { npRelayEntry 1 }
npRelayMode OBJECT-TYPE
SYNTAX INTEGER {
flip(-1),
off(0),
on(1),
watchdog(2),
schedule(3),
scheduleAndWatchdog(4),
logic(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Control of relay:
-1 - flip between on(1) and off(0)
0 - manual off
1 - manual on
2 - watchdog
3 - schedule
4 - both schedule and watchdog (while switched on by schedule)
5 - logic"
::={npRelayEntry 2}
npRelayStartReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to start reset (switch relay off for some time)"
::={npRelayEntry 3}
npRelayMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relay memo"
::={npRelayEntry 6}
npRelayState OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Actual relay state at the moment,
regardless of source of control.
0 - relay is off
1 - relay is on"
::={npRelayEntry 15}
-- npRelayPowered OBJECT-TYPE
-- SYNTAX INTEGER {
-- no(0),
-- yes(1)
-- }
-- MAX-ACCESS read-only
-- STATUS current
-- DESCRIPTION "AC presence on output.
-- 0 - no AC dew to relay switched off or no ac on input
-- 1 - AC is present"
-- ::={npRelayEntry 16}
npThermo OBJECT IDENTIFIER::={lightcom 8800}
npThermoTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpThermoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Thermo Sensors Table"
::= { npThermo 1 }
npThermoEntry OBJECT-TYPE
SYNTAX NpThermoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Thermo Sensors Table Row"
INDEX { npThermoSensorN }
::= { npThermoTable 1 }
NpThermoEntry ::= SEQUENCE {
npThermoSensorN INTEGER,
npThermoValue INTEGER,
npThermoStatus INTEGER,
npThermoLow INTEGER,
npThermoHigh INTEGER,
npThermoMemo DisplayString,
npThermoValuePrecise FixedPoint1000
}
npThermoSensorN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of temperature sensor, 1 to 8"
::= { npThermoEntry 1 }
npThermoValue OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature, deg.C"
::= { npThermoEntry 2 }
npThermoStatus OBJECT-TYPE
SYNTAX INTEGER {
failed(0),
low(1),
norm(2),
high(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
::= { npThermoEntry 3 }
npThermoLow OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
::= { npThermoEntry 4 }
npThermoHigh OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Top margin of normal temperature range, deg.C"
::= { npThermoEntry 5 }
npThermoMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T channel memo"
::= { npThermoEntry 6 }
npThermoValuePrecise OBJECT-TYPE
SYNTAX FixedPoint1000
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature, deg.C, with fractional part 3 digits after point"
::= { npThermoEntry 7 }
npThermoTraps OBJECT IDENTIFIER::={npThermo 2}
npThermoTrapPrefix OBJECT IDENTIFIER::={npThermoTraps 0}
npThermoTrapSensorN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of temperature sensor, 1 to 8"
::= { npThermoTraps 1 }
npThermoTrapValue OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature, deg.C"
::= { npThermoTraps 2 }
npThermoTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
failed(0),
low(1),
norm(2),
high(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
::= { npThermoTraps 3 }
npThermoTrapLow OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
::= { npThermoTraps 4 }
npThermoTrapHigh OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Top margin of normal temperature range, deg.C"
::= { npThermoTraps 5 }
npThermoTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T channel memo"
::= { npThermoTraps 6 }
npThermoTrap NOTIFICATION-TYPE
OBJECTS {
npThermoTrapSensorN,
npThermoTrapValue,
npThermoTrapStatus,
npThermoTrapLow,
npThermoTrapHigh,
npThermoTrapMemo
}
STATUS current
DESCRIPTION
"Status of Thermo sensor is changed (crossing of normal temp. range)"
::= { npThermoTrapPrefix 1 }
npIo OBJECT IDENTIFIER::={lightcom 8900}
npIoTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpIoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Digital Input/output Table"
::= { npIo 1 }
npIoEntry OBJECT-TYPE
SYNTAX NpIoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Digital Input/output Table Row"
INDEX { npIoLineN }
::= { npIoTable 1 }
NpIoEntry ::= SEQUENCE {
npIoLineN INTEGER,
npIoLevelIn INTEGER,
npIoLevelOut INTEGER,
npIoMemo DisplayString,
npIoPulseCounter Counter32,
npIoSinglePulseDuration INTEGER,
npIoSinglePulseStart INTEGER
}
npIoLineN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of IO line, from 1 to max supported"
::= { npIoEntry 1 }
npIoLevelIn OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Input level, 0 or 1"
::= { npIoEntry 2 }
npIoLevelOut OBJECT-TYPE
SYNTAX INTEGER {
flip(-1),
low(0),
high(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Output level, 0 or 1.
Write -1 to flip output."
::= { npIoEntry 3 }
npIoMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IO line memo"
::= { npIoEntry 6 }
npIoPulseCounter OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Pulse Counter on IO input line (counts positive fronts)
Write 0 to reset."
::= { npIoEntry 9 }
npIoSinglePulseDuration OBJECT-TYPE
SYNTAX INTEGER (100..25500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set duration of single pulse on IO output line,
100ms to 25500ms, min. step is 100ms"
::= { npIoEntry 12 }
npIoSinglePulseStart OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to start single pulse on IO output.
Output will be inverted for time, specified by npIoSinglePulseDuration"
::= { npIoEntry 13 }
npIoTraps OBJECT IDENTIFIER::={npIo 2}
npIoTrapPrefix OBJECT IDENTIFIER::={npIoTraps 0}
npIoTrapLineN OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, Number of IO line"
::= { npIoTraps 1 }
npIoTrapLevelIn OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, new Input level, 0 or 1"
::= { npIoTraps 2 }
npIoTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, IO line memo"
::= { npIoTraps 6 }
npIoTrapLevelLegend OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Legend for current logic level on the IO line"
::= { npIoTraps 7 }
npIoTrap NOTIFICATION-TYPE
OBJECTS {
npIoTrapLineN,
npIoTrapLevelIn,
npIoTrapMemo,
npIoTrapLevelLegend
}
STATUS current
DESCRIPTION
"Input state of IO line is changed"
::= { npIoTrapPrefix 1 }
npCurLoop OBJECT IDENTIFIER::={lightcom 8300}
npCurLoopTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpCurLoopEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Current loop sensors Table"
::= { npCurLoop 1 }
npCurLoopEntry OBJECT-TYPE
SYNTAX NpCurLoopEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Current loop sensors Table Row"
INDEX { npCurLoopN }
::= { npCurLoopTable 1 }
NpCurLoopEntry ::= SEQUENCE {
npCurLoopN INTEGER,
npCurLoopStatus INTEGER,
npCurLoopI INTEGER,
npCurLoopV INTEGER,
npCurLoopR INTEGER,
npCurLoopPower INTEGER
}
npCurLoopN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of current loop, 1 to max supported"
::= { npCurLoopEntry 1 }
npCurLoopStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alert(1),
cut(2),
short(3),
notPowered(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of the loop
0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered"
::= { npCurLoopEntry 2 }
npCurLoopI OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Loop current, mA"
::= { npCurLoopEntry 3 }
npCurLoopV OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Voltage drop on the loop, mV"
::= { npCurLoopEntry 4 }
npCurLoopR OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Resistance of the loop, Ohm"
::= { npCurLoopEntry 5 }
npCurLoopPower OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1),
cyclePower(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Control of loop power
0=Off, 1=On, 2=reset by off/on power"
::= { npCurLoopEntry 7 }
npCurLoopTraps OBJECT IDENTIFIER::={npCurLoop 2}
npCurLoopTrapPrefix OBJECT IDENTIFIER::={npCurLoopTraps 0}
npCurLoopTrapN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of current loop, which status has changed"
::= { npCurLoopTraps 1 }
npCurLoopTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alert(1),
cut(2),
short(3),
notPowered(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of the loop
0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered"
::= { npCurLoopTraps 2 }
npCurLoopTrapI OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Loop current, mA"
::= { npCurLoopTraps 3 }
npCurLoopTrapV OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Voltage drop on the loop, mV"
::= { npCurLoopTraps 4 }
npCurLoopTrapR OBJECT-TYPE
SYNTAX INTEGER (0..99999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Resistance of the loop, Ohm"
::= { npCurLoopTraps 5 }
npCurLoopTrapPower OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Status of loop power
0=Off, 1=On"
::= { npCurLoopTraps 7 }
npCurLoopTrap NOTIFICATION-TYPE
OBJECTS {
npCurLoopTrapN,
npCurLoopTrapStatus,
npCurLoopTrapI,
npCurLoopTrapV,
npCurLoopTrapR,
npCurLoopTrapPower,
npTrapEmailTo
}
STATUS current
DESCRIPTION
"Status of current loop N has changed!"
::= { npCurLoopTrapPrefix 1 }
npSmoke OBJECT IDENTIFIER::={lightcom 8200}
npSmokeTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpSmokeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Smoke Sensors Table"
::= { npSmoke 1 }
npSmokeEntry OBJECT-TYPE
SYNTAX NpSmokeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Smoke Sensors Table Row"
INDEX { npSmokeSensorN }
::= { npSmokeTable 1 }
NpSmokeEntry ::= SEQUENCE {
npSmokeSensorN INTEGER,
npSmokeStatus INTEGER,
npSmokePower INTEGER,
npSmokeReset INTEGER,
npSmokeMemo DisplayString
}
npSmokeSensorN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
::= { npSmokeEntry 1 }
npSmokeStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alarm(1),
off(4),
failed(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of Smoke sensor"
::= { npSmokeEntry 2 }
npSmokePower OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Controls power on Smoke sensor current loop"
::= { npSmokeEntry 3 }
npSmokeReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to switch off for approx. 10s to reset sensor"
::= { npSmokeEntry 4 }
npSmokeMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Smoke sensor memo"
::= { npSmokeEntry 6 }
npSmokeTraps OBJECT IDENTIFIER::={npSmoke 2}
npSmokeTrapPrefix OBJECT IDENTIFIER::={npSmokeTraps 0}
npSmokeTrapSensorN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
::= { npSmokeTraps 1 }
npSmokeTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alarm(1),
off(4),
failed(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "New status of Smoke sensor"
::= { npSmokeTraps 2 }
npSmokeTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Smoke sensor memo"
::= { npSmokeTraps 6 }
npSmokeTrap NOTIFICATION-TYPE
OBJECTS {
npSmokeTrapSensorN,
npSmokeTrapStatus,
npSmokeTrapMemo
}
STATUS current
DESCRIPTION
"Status of 1W Smoke sensor has changed"
::= { npSmokeTrapPrefix 1 }
npRelHumidity OBJECT IDENTIFIER::={lightcom 8400}
npRelHumTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpRelHumEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Humidity+Temperature Sensors Table"
::= { npRelHumidity 1 }
npRelHumEntry OBJECT-TYPE
SYNTAX NpRelHumEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Humidity+Temperature Sensors Table Row"
INDEX { npRelHumN }
::= { npRelHumTable 1 }
NpRelHumEntry ::= SEQUENCE {
npRelHumN INTEGER,
npRelHumValue INTEGER,
npRelHumStatus INTEGER,
npRelHumTempValue INTEGER,
npRelHumTempStatus INTEGER,
npRelHumMemo DisplayString,
npRelHumSafeRangeHigh INTEGER,
npRelHumSafeRangeLow INTEGER,
npRelHumTempSafeRangeHigh INTEGER,
npRelHumTempSafeRangeLow INTEGER
}
npRelHumN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported"
::= { npRelHumEntry 1 }
npRelHumValue OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative humidity value, %"
::= { npRelHumEntry 2 }
npRelHumStatus OBJECT-TYPE
SYNTAX INTEGER {
sensorFailed(0),
belowSafeRange(1),
inSafeRange(2),
aboveSafeRange(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of Relative Humiduty"
::= { npRelHumEntry 3 }
npRelHumTempValue OBJECT-TYPE
SYNTAX INTEGER (-60..200)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor temperature, deg.C"
::= { npRelHumEntry 4 }
npRelHumTempStatus OBJECT-TYPE
SYNTAX INTEGER {
sensorFailed(0),
belowSafeRange(1),
inSafeRange(2),
aboveSafeRange(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of Relative Humiduty"
::= { npRelHumEntry 5 }
npRelHumMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Memo/Location"
::= { npRelHumEntry 6 }
npRelHumSafeRangeHigh OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, top margin, %RH"
::= { npRelHumEntry 7 }
npRelHumSafeRangeLow OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH"
::= { npRelHumEntry 8 }
npRelHumTempSafeRangeHigh OBJECT-TYPE
SYNTAX INTEGER (-55..150)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature safe range, top margin, deg.C"
::= { npRelHumEntry 9 }
npRelHumTempSafeRangeLow OBJECT-TYPE
SYNTAX INTEGER (-55..150)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature safe range, bottom margin, deg.C"
::= { npRelHumEntry 10 }
npRelHumTrapData OBJECT IDENTIFIER::={npRelHumidity 3}
npRelHumTrapDataN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of Humidity+Temperature sensor, 1 to max supported"
::= { npRelHumTrapData 1 }
npRelHumTrapDataValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor humidity, %RH, or temperature, deg.C"
::= { npRelHumTrapData 2 }
npRelHumTrapDataStatus OBJECT-TYPE
SYNTAX INTEGER {
sensorFailed(0),
belowSafeRange(1),
inSafeRange(2),
aboveSafeRange(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of humidity or temperature"
::= { npRelHumTrapData 4 }
npRelHumTrapDataMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Memo/Location"
::= { npRelHumTrapData 6 }
npRelHumTrapDataSafeRangeHigh OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, top margin, %RH or deg.C"
::= { npRelHumTrapData 7 }
npRelHumTrapDataSafeRangeLow OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH or deg.C"
::= { npRelHumTrapData 8 }
npRelHumTrap OBJECT IDENTIFIER::={npRelHumidity 6}
npRelHumTrapAllEvents OBJECT IDENTIFIER::={npRelHumTrap 127}
npRelHumTrapTemp OBJECT IDENTIFIER::={npRelHumidity 7}
npRelHumTrapTempAllEvents OBJECT IDENTIFIER::={npRelHumTrapTemp 127}
npRelHumTrapAllChannels NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Status of Humidity has changed!"
::= { npRelHumTrapAllEvents 99 }
npRelHumTrapAboveSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Humidity above the Safe range"
::= { npRelHumTrap 103 }
npRelHumTrapSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Humidity in the Safe range"
::= { npRelHumTrap 102 }
npRelHumTrapBelowSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Humidity below the Safe range"
::= { npRelHumTrap 101 }
npRelHumTrapFail NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Rel.Humidity sensor failed!"
::= { npRelHumTrap 100 }
npRelHumTrapTempAllChannels NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Status of Temperature has changed!"
::= { npRelHumTrapTempAllEvents 99 }
npRelHumTrapTempAboveSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Temperature above the Safe range"
::= { npRelHumTrapTemp 103 }
npRelHumTrapTempSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Temperature in the Safe range"
::= { npRelHumTrapTemp 102 }
npRelHumTrapTempBelowSafe NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Temperature below the Safe range"
::= { npRelHumTrapTemp 101 }
npRelHumTrapTempFail NOTIFICATION-TYPE
OBJECTS {
npRelHumTrapDataN,
npRelHumTrapDataStatus,
npRelHumTrapDataValue,
npRelHumTrapDataMemo,
npRelHumTrapDataSafeRangeHigh,
npRelHumTrapDataSafeRangeLow
}
STATUS current
DESCRIPTION
"Sensor failed!"
::= { npRelHumTrapTemp 100 }
npGsm OBJECT IDENTIFIER::={lightcom 3800}
npGsmInfo OBJECT IDENTIFIER::={npGsm 1}
npGsmFailed OBJECT-TYPE
SYNTAX INTEGER {
ok (0),
failed (1),
fatalError (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Firmware's GSM module status"
::= { npGsmInfo 1 }
npGsmRegistration OBJECT-TYPE
SYNTAX INTEGER {
impossible (0),
homeNetwork (1),
searching (2),
denied (3),
unknown (4),
roaming (5),
infoUpdate (255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of modem registration in GSM network (AT+CREG? result)"
::= { npGsmInfo 2 }
npGsmStrength OBJECT-TYPE
SYNTAX INTEGER (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GSM signal strength.
0..31 = 0..100%,
99 = unknown or n/a,
255 = updating info"
::= { npGsmInfo 3 }
npGsmSendSmsUtf8 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Send arbitrary SMS.
Format: [phone_number,phone_number,...] Message
One to four destination phone numbers
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
Cyrillic characters must be in UTF8 encoding."
::= { npGsmInfo 9 }
npGsmSendSmsWin1251 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Send arbitrary SMS.
Format: [phone_number,phone_number,...] Message
One to four destination phone numbers
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
Cyrillic characters must be in Win1251 encoding."
::= { npGsmInfo 10 }
npGsmTraps OBJECT IDENTIFIER::={npGsm 2}
npGsmTrapPrefix OBJECT IDENTIFIER::={npGsmTraps 0}
npGsmTrap NOTIFICATION-TYPE
OBJECTS {
npGsmFailed,
npGsmRegistration,
npGsmStrength
}
STATUS current
DESCRIPTION
"GSM modem or SMS firmware problems"
::= { npGsmTrapPrefix 1 }
npIr OBJECT IDENTIFIER::={lightcom 7900}
npIrCtrl OBJECT IDENTIFIER::={npIr 1}
npIrPlayCmd OBJECT-TYPE
SYNTAX INTEGER (1..16)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write IR command number to send IR command"
::= { npIrCtrl 1 }
npIrReset OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to reset IR transiever.
After reset, send IR command and check npIrStatus."
::= { npIrCtrl 2 }
npIrStatus OBJECT-TYPE
SYNTAX INTEGER {
commandCompleted (0),
protocolError (1),
commandAccepted (2),
errorUnknown (16),
errorBadNumber (17),
errorEmptyRecord (18),
errorFlashChip (19),
errorTimeout (20),
errorExtBusBusy (21)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IR transiever status"
::= { npIrCtrl 3 }
npReboot OBJECT IDENTIFIER::={ lightcom 911 }
npSoftReboot OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to reboot device after
current operations completition"
::= { npReboot 1 }
npResetStack OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to re-initialize network
stack"
::= { npReboot 2 }
npForcedReboot OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to immediate forced reboot"
::= { npReboot 3 }
END