mibs/MIBS/orvaldi/companyMIB

2763 lines
65 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
-- company power MIB
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) company(2111)
-- products(1) ups(1)
--
-- ==============================================================================================
companyMIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
TRAP-TYPE
FROM RFC-1215
PositiveInteger, NonNegativeInteger
FROM UPS-MIB;
companyMIB MODULE-IDENTITY
LAST-UPDATED "201005060000Z"
ORGANIZATION "company Power Technology"
CONTACT-INFO " "
DESCRIPTION
"The MIB module to describe UPS"
::= { enterprises 21111 }
products OBJECT IDENTIFIER ::= { companyMIB 1 }
ups OBJECT IDENTIFIER ::= { products 1 }
inverter OBJECT IDENTIFIER ::= { products 2 }
charger OBJECT IDENTIFIER ::= { products 3 }
ATS OBJECT IDENTIFIER ::= { products 4 }
upsIdent OBJECT IDENTIFIER ::= { ups 1 }
upsRating OBJECT IDENTIFIER ::= { ups 2 }
upsBattery OBJECT IDENTIFIER ::= { ups 3 }
upsInput OBJECT IDENTIFIER ::= { ups 4 }
upsOutput OBJECT IDENTIFIER ::= { ups 5 }
upsBypass OBJECT IDENTIFIER ::= { ups 6 }
upsTest OBJECT IDENTIFIER ::= { ups 7 }
upsControl OBJECT IDENTIFIER ::= { ups 8 }
agentConfig OBJECT IDENTIFIER ::= { ups 9 }
commConfig OBJECT IDENTIFIER ::= { ups 10 }
upsConfig OBJECT IDENTIFIER ::= { ups 11 }
upsTraps OBJECT IDENTIFIER ::= { ups 12 }
extend OBJECT IDENTIFIER ::= { ups 13 }
solarIdent OBJECT IDENTIFIER ::= { inverter 1 }
solarRating OBJECT IDENTIFIER ::= { inverter 2 }
solarBattery OBJECT IDENTIFIER ::= { inverter 3 }
solarGrid OBJECT IDENTIFIER ::= { inverter 4 }
solarACOutput OBJECT IDENTIFIER ::= { inverter 5 }
solarPV OBJECT IDENTIFIER ::= { inverter 6 }
solarEnergy OBJECT IDENTIFIER ::= { inverter 7 }
solarTest OBJECT IDENTIFIER ::= { inverter 8 }
solarDefValue OBJECT IDENTIFIER ::= { inverter 9 }
solarFaultInfo OBJECT IDENTIFIER ::= { inverter 10 }
solarControl OBJECT IDENTIFIER ::= { inverter 11 }
solarAgentConfig OBJECT IDENTIFIER ::= { inverter 12 }
solarCommConfig OBJECT IDENTIFIER ::= { inverter 13 }
solarConfig OBJECT IDENTIFIER ::= { inverter 14 }
solarTraps OBJECT IDENTIFIER ::= { inverter 15 }
solarExtend OBJECT IDENTIFIER ::= { inverter 16 }
ATSIdent OBJECT IDENTIFIER ::= { ATS 1 }
ATSRating OBJECT IDENTIFIER ::= { ATS 2 }
ATSInformation OBJECT IDENTIFIER ::= { ATS 3 }
ATSControl OBJECT IDENTIFIER ::= { ATS 4 }
ATSAgentConfig OBJECT IDENTIFIER ::= { ATS 5 }
ATSCommConfig OBJECT IDENTIFIER ::= { ATS 6 }
ATSConfig OBJECT IDENTIFIER ::= { ATS 7 }
ATSTraps OBJECT IDENTIFIER ::= { ATS 8 }
ATSExtend OBJECT IDENTIFIER ::= { ATS 9 }
---=======================================================
---upsIdent
--- prefix =upsId
---========================================================
upsIdManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the UPS manufacturer."
::= { upsIdent 1 }
upsIdProtocol OBJECT-TYPE
SYNTAX INTEGER {
unknown(-1),
pmv(99),
p00(0),
p01(1),
p02(2),
p03(3),
p04(4),
p05(5),
p06(6),
p07(7),
p08(8),
p09(9),
p10(10),
sec(80)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS Protocol id."
::= { upsIdent 2 }
upsIdModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS Model designation."
::= { upsIdent 3 }
upsIdSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS serial no."
::= { upsIdent 4 }
upsIdName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the UPS. This object should be
set by the administrator."
::= { upsIdent 5 }
upsIdFWVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Main CPU firmware version."
::= { upsIdent 6 }
upsIdUPSType OBJECT-TYPE
SYNTAX INTEGER {
standy(0),
line-interactive(1),
on-line(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UPS type."
::= { upsIdent 7 }
--===========================================================================
--upsRating
--prefix =upsRat
--the rating info of ups
--==========================================================================
upsRatinVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Volt DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating input voltage of UPS"
::= { upsRating 1 }
upsRatoutVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Volt DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating output voltage of UPS"
::= { upsRating 2 }
upsRatoutFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 HZ"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating output frequency of UPS"
::= { upsRating 3 }
upsRatoutCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating output current of UPS"
::= { upsRating 4 }
upsRatoutApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 VA"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating output apparent power of UPS"
::= { upsRating 5 }
upsRatoutTruePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Wt"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating output true power of UPS"
::= { upsRating 6 }
upsRatBatVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 vol"
ACCESS read-only
STATUS current
DESCRIPTION
"The rating battery voltage of UPS"
::= { upsRating 7 }
-- ===========================================================================
-- upsBattery
-- prefix = upsBat
-- The Battery group.
-- est=estimated
-- ===========================================================================
upsBatStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4),
batteryDischarging(5),
batteryFailure(6),
batteryReplace(7),
batterysilence(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The indication of the status in the UPS system's batteries."
::= { upsBattery 1 }
upsBatSecondsOnBattery OBJECT-TYPE
SYNTAX INTEGER
UNITS "seconds"
ACCESS read-only
STATUS current
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. -1 shall be returned
if the unit is not on battery power."
::= { upsBattery 2 }
upsBatEstMinutesRemaining OBJECT-TYPE
SYNTAX INTEGER
UNITS "minutes"
ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { upsBattery 3 }
upsBatEstChargeRemaining OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the battery charge remaining expressed
as a percent of full charge."
::= { upsBattery 4 }
upsBatPBatVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Volt DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present Positive battery voltage."
::= { upsBattery 5 }
upsBatNBatVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Volt DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present negative battery voltage."
::= { upsBattery 6 }
upsBatPBatCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The positive battery present current."
::= { upsBattery 7 }
upsBatNBatCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The present negative battery current."
::= { upsBattery 8 }
upsBatPBatChargCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The Positive battery charging current."
::= { upsBattery 9 }
upsBatNBatchargCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The present negative battery charging current."
::= { upsBattery 10 }
upsBatPBatDischargCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The present positive battery discharging current."
::= { upsBattery 11 }
upsBatNBatDischargCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The present negative battery discharging current."
::= { upsBattery 12 }
upsBatTemperature OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees 0.1 Centigrade"
ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the UPS Battery
casing."
::= { upsBattery 13 }
upsBatNumberInSeries OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery in series."
::= { upsBattery 14 }
upsBatNumberInParallel OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery in Parallel."
::= { upsBattery 15 }
upsBatPBatDischargCurrent2 OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"The present positive battery pipe2 discharging current."
::= { upsBattery 16 }
-- ===========================================================================
-- upsInput
-- prefix = upsIn
-- Input group.
-- ===========================================================================
upsInLineBads OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS current
DESCRIPTION
"A count of the number of times the input entered an
out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each
time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance."
::= { upsInput 1 }
upsInTtlApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1VA"
ACCESS read-only
STATUS current
DESCRIPTION
"Total input apparent power ."
::= { upsInput 2 }
upsInTtlTruePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1WT"
ACCESS read-only
STATUS current
DESCRIPTION
"Total input active(true) power ."
::= { upsInput 3 }
upsInNumLines OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS current
DESCRIPTION
"The number of input lines utilized in this device.
This variable indicates the number of rows in the
input table."
::= { upsInput 4 }
upsInTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsInEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of input table entries. The number of entries
is given by the value of upsInputNumLines."
::= { upsInput 5 }
upsInTtlVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The input utility line tatol voltage ."
::= { upsInput 6 }
upsInTtlCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 A"
ACCESS read-only
STATUS current
DESCRIPTION
"The input utility line tatol current."
::= { upsInput 7 }
upsInEntry OBJECT-TYPE
SYNTAX UpsInEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular input line."
INDEX { upsInLineIndex }
::= { upsInTable 1 }
UpsInEntry ::=
SEQUENCE {
upsInLineIndex PositiveInteger,
upsInFrequency NonNegativeInteger,
upsInVoltage NonNegativeInteger,
upsInCurrent NonNegativeInteger,
upsInApparentPower NonNegativeInteger,
upsInTruePower NonNegativeInteger,
upsInPowerFactor NonNegativeInteger,
upsInLineVoltage NonNegativeInteger
}
upsInLineIndex OBJECT-TYPE
SYNTAX INTEGER (0..10)
ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines"
::= { upsInEntry 1 }
upsInFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency."
::= { upsInEntry 2 }
upsInVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The input utility line voltage ."
::= { upsInEntry 3 }
upsInCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1Amp"
ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input current "
::= { upsInEntry 4 }
upsInApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1VA"
ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input Apparent power."
::= { upsInEntry 5 }
upsInTruePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1Watts"
ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input true power."
::= { upsInEntry 6 }
upsInPowerFactor OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.01"
ACCESS read-only
STATUS current
DESCRIPTION
"Input true power/apparent power factor "
::= { upsInEntry 7 }
upsInLineVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The input utility line voltage .
if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase;
if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase;
if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase."
::= { upsInEntry 8 }
-- ===========================================================================
-- upsOutput
-- prefix= upsOut
-- Output group
-- ===========================================================================
upsOutSource OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7),
batterytest(8),
fault(9),
HE-ECOmode(10),
convertermode(11)
}
ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.==UPS standby mode"
::= { upsOutput 1 }
upsOutFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hertz"
ACCESS read-only
STATUS current
DESCRIPTION
"The current output frequency of the UPS system "
::= { upsOutput 2 }
upsOutTtlApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1VA"
ACCESS read-only
STATUS current
DESCRIPTION
"Total output apparent power ."
::= { upsOutput 3 }
upsOutTtlTruePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1Watts"
ACCESS read-only
STATUS current
DESCRIPTION
"Total output active(true) power ."
::= { upsOutput 4 }
upsOutTtlPercentLoad OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA."
::= { upsOutput 5 }
upsOutNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table."
::= { upsOutput 6 }
upsOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsOutEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of output table entries. The number of
entries is given by the value of upsOutputNumLines."
::= { upsOutput 7 }
upsOutTtlVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1vot"
ACCESS read-only
STATUS current
DESCRIPTION
"Total output voltage ."
::= { upsOutput 8 }
upsOutTtlCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1A"
ACCESS read-only
STATUS current
DESCRIPTION
"Total output current."
::= { upsOutput 9 }
upsOutStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (4..4))
ACCESS read-only
STATUS current
DESCRIPTION
" For HVDC device.
char status[4];
status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
status[2]status[3]:00, no output2; 01, line output2; 02, bat output2
"
::= { upsOutput 10 }
upsOutSource2 OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7),
batterytest(8),
fault(9),
HE-ECOmode(10),
convertermode(11)
}
ACCESS read-only
STATUS current
DESCRIPTION
"For HVDC(protocol:P12) machine. The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.==UPS standby mode"
::= { upsOutput 11 }
upsOutEntry OBJECT-TYPE
SYNTAX UpsOutEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular output line."
INDEX { upsOutLineIndex }
::= { upsOutTable 1 }
UpsOutEntry ::=
SEQUENCE {
upsOutLineIndex PositiveInteger,
upsOutVoltage NonNegativeInteger,
upsOutCurrent NonNegativeInteger,
upsOutApparentPower NonNegativeInteger,
upsOutTruePower NonNegativeInteger,
upsOutPowerFactor NonNegativeInteger,
upsOutPercentLoad INTEGER,
upsOutLineVoltage NonNegativeInteger
}
upsOutLineIndex OBJECT-TYPE
SYNTAX INTEGER (0..10)
ACCESS read-only
STATUS current
DESCRIPTION
"The output line identifier."
::= { upsOutEntry 1 }
upsOutVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The output voltage of the UPS system."
::= { upsOutEntry 2 }
upsOutCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp"
ACCESS read-only
STATUS current
DESCRIPTION
"The output current of the UPS system"
::= { upsOutEntry 3 }
upsOutApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1VA"
ACCESS read-only
STATUS current
DESCRIPTION
"The present output apparent power."
::= { upsOutEntry 4 }
upsOutTruePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1Watts"
ACCESS read-only
STATUS current
DESCRIPTION
"The present output true power."
::= { upsOutEntry 5 }
upsOutPowerFactor OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.01"
ACCESS read-only
STATUS current
DESCRIPTION
"Output true power/apparent power factor "
::= { upsOutEntry 6 }
upsOutPercentLoad OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA."
::= { upsOutEntry 7 }
upsOutLineVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The output line voltage of the UPS system.
if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase;
if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase;
if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase."
::= { upsOutEntry 8 }
upsOutFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1Hertz"
ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency."
::= { upsOutEntry 9 }
-- ===========================================================================
-- upsBypass
-- prefix =upsBy
-- ===========================================================================
upsByFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hertz"
ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass frequency."
::= { upsBypass 1 }
upsByNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS current
DESCRIPTION
"The number of bypass lines utilized in this device.
This entry indicates the number of rows in the bypass
table."
::= { upsBypass 2 }
upsByTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsByEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of bypass table entries. The number of
entries is given by the value of upsBypassNumLines."
::= { upsBypass 3 }
upsByEntry OBJECT-TYPE
SYNTAX UpsByEntry
ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular bypass input."
INDEX { upsByLineIndex }
::= { upsByTable 1 }
UpsByEntry ::=
SEQUENCE {
upsByLineIndex PositiveInteger,
upsByVoltage NonNegativeInteger,
upsByCurrent NonNegativeInteger,
upsByPower NonNegativeInteger,
upsByLineVoltage INTEGER
}
upsByLineIndex OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS current
DESCRIPTION
"The bypass line identifier."
::= { upsByEntry 1 }
upsByVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass voltage."
::= { upsByEntry 2 }
upsByCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 RMS Amp"
ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass current."
::= { upsByEntry 3 }
upsByPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1Watts"
ACCESS read-only
STATUS current
DESCRIPTION
"The present true power conveyed by the bypass."
::= { upsByEntry 4 }
upsByLineVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass line voltage.
if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase;
if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase;
if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase."
::= { upsByEntry 5 }
-- ===========================================================================
-- upsTest
-- prefix=upsTst
-- ===========================================================================
upsTstBatteryTest OBJECT-TYPE
SYNTAX INTEGER {
none(1),
battTest10sec(2),
battTestUntilLow(3),
battTestWithTime(4),
battTestCancelTest(5),
battTestClearInfo(6)
}
ACCESS read-write
STATUS current
DESCRIPTION
"This object specify the battery test type and initiate
battery test. If battTestWithTime selected, the test
time is refer to upsTestBatteryTestTime."
::= { upsTest 1 }
upsTstBatteryTestResult OBJECT-TYPE
SYNTAX INTEGER {
donePassed(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The results of the current or last UPS diagnostics
test performed. The values for donePassed(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results."
::= { upsTest 2 }
upsTstBatteryTestStartTime OBJECT-TYPE
SYNTAX DisplayString (SIZE(19..19))
ACCESS read-only
STATUS current
DESCRIPTION
"The value of the time the test in progress was initiated,
or, if no test is in progress, the time the previous test
was initiated. If the value of upsTestBatteryTestResult
is noTestsInitiated(6), upsTestStartTime has the value
01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)"
::= { upsTest 3 }
upsTstBatterySettingTime OBJECT-TYPE
SYNTAX INTEGER (12..5940)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The object specify the test time for battery test, the unit is seconds"
::= { upsTest 4 }
--below 1 minute 0.2-1.0 ,larger than 1 minutes ,1,2,3..99;
-- ===========================================================================
-- upsControl
-- prefix=upsCtl
-- ===========================================================================
upsCtlShutdownDelay OBJECT-TYPE
SYNTAX INTEGER (-2..2147483648)
UNITS "seconds"
ACCESS read-write
STATUS current
DESCRIPTION
"The delay in seconds the UPS remains on after being told
to turn off. if value=-2 cancel shutdown, if value=-1 donothing,
value=0 shutdown ups immediately"
::= { upsControl 1 }
upsCtlSleepTime OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "minutes"
ACCESS read-write
STATUS current
DESCRIPTION
"The time in minutes for the UPS to go to sleep when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable
value, the highest acceptable value is used."
::= { upsControl 2 }
upsCtlStartupAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. -1 mean not startup.
must set upsCtlStartupAfterDelay before upsCtlShutdownDelay ,
the value must larger than 59 if the value not equal -1 "
::= { upsControl 3 }
upsCtlbuzzer OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to 'on' or 'off' to enable or disable buzzer"
::= { upsControl 4 }
upsCtlRemoteControlUPS OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to turn 'on' or 'off' UPS "
::= { upsControl 5 }
upsCtloutletPoweron OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS write-only
STATUS current
DESCRIPTION
"Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process"
::= { upsControl 6 }
upsCtloutletPoweroff OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS write-only
STATUS current
DESCRIPTION
"Setting this object to 1 means 1st outlet,
2 means 2nd outlet , immediately process"
::= { upsControl 7 }
upsCtlOutlet1Powerofftime OBJECT-TYPE
SYNTAX INTEGER (-1..999)
ACCESS read-write
STATUS current
DESCRIPTION
"setting this object to -1 means this control not effect,
0 means immediately process,
>0 means wait times unit is minutes
use in battery mode"
::= { upsControl 8 }
upsCtlOutlet2Powerofftime OBJECT-TYPE
SYNTAX INTEGER (-1..999)
ACCESS read-write
STATUS current
DESCRIPTION
"setting this object to -1 means this control not effect,
0 means immediately process ,
>0 means wait times unit is minutes .use in battery mode"
::= { upsControl 9 }
upsCtlResetConfigure OBJECT-TYPE
SYNTAX INTEGER {
none(0),
reset(1)
}
ACCESS read-write
STATUS current
DESCRIPTION
" reset all configure para to default."
::= { upsControl 10 }
--===========================================================================
--
-- agentConfig
-- prefix=agent
-- ===========================================================================
agentConfigDatetime OBJECT-TYPE
SYNTAX DisplayString (SIZE (19..19))
ACCESS read-write
STATUS current
DESCRIPTION
"The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)"
::= { agentConfig 1 }
---======================================================================
-- commConfig
-- prefix =comm
---======================================================================
commBaudRate OBJECT-TYPE
SYNTAX INTEGER {
B1200(1),
B2400(2),
B4800(3),
B9600(4),
B19200(5)
}
ACCESS read-write
STATUS current
DESCRIPTION
"The UPS communicate baudrate"
::= { commConfig 1 }
commDatabits OBJECT-TYPE
SYNTAX INTEGER (8..9)
ACCESS read-write
STATUS current
DESCRIPTION
"The UPS communicate data bits"
::= { commConfig 2 }
commStopbits OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-write
STATUS current
DESCRIPTION
"The UPS communicate stop bits "
::= { commConfig 3 }
commParity OBJECT-TYPE
SYNTAX INTEGER {
none(0),
odd(1),
even(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"The UPS communicate Parity "
::= { commConfig 4 }
commTimeout OBJECT-TYPE
SYNTAX INTEGER (100..1000)
ACCESS read-write
STATUS current
DESCRIPTION
"The UPS communicate timeout"
::= { commConfig 5 }
--===========================================================================
--
-- upsConfig
--prefix=upsCfg
-- ===========================================================================
upsCfgAlarmbypass OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object enable /disable alarm bypass mode"
::= { upsConfig 1 }
upsCfgAlarmbattery OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object enable/disable alarm battery mode"
::= { upsConfig 2 }
upsCfgAutoReboot OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object enable/disable auto reboot"
::= { upsConfig 3 }
upsCfgBypasswhenupsoff OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object start/stop bypass when ups off"
::= { upsConfig 4 }
upsCfgBatterDDP OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable battery deep-discharge protection"
::= { upsConfig 5 }
upsCfgConvertermode OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable converter mode "
::= { upsConfig 6 }
upsCfgECOmode OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable ECO mode"
::= { upsConfig 7 }
upsCfgAdvanceECOmode OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable advance ECO mode"
::= { upsConfig 8 }
upsCfgGreenPowerFunction OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable green power function"
::= { upsConfig 9 }
upsCfgBatteryOSC OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable battery open status check"
::= { upsConfig 10 }
upsCfgAllowShort3times OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable short 3 times"
::= { upsConfig 11 }
upsCfgColdstart OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to cold start ups"
::= { upsConfig 12 }
upsCfgBypassNotAllowed OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable bypass mode"
::= { upsConfig 13 }
upsCfgBatterylowprotect OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable battery low protect"
::= { upsConfig 14 }
upsCfgP1progoutletcontrol OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable p1 programmable outlet control (battery mode)"
::= { upsConfig 15 }
upsCfgP2progoutletcontrol OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable p2 programmable outlet control (battery mode)"
::= { upsConfig 16 }
upsCfgInverterShortClear OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable Inverter short clear function"
::= { upsConfig 17 }
upsCfgSitefaildetection OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to enable/disable site fail detection"
::= { upsConfig 18 }
upsCfgBatNumInParallel OBJECT-TYPE
SYNTAX INTEGER (1..99)
ACCESS read-write
STATUS current
DESCRIPTION
"Battery numbers in parallel (battery numbers setting)"
::= { upsConfig 19 }
upsCfgBatNumInSeries OBJECT-TYPE
SYNTAX INTEGER (1..20)
ACCESS read-write
STATUS current
DESCRIPTION
"Battery numbers in series (battery numbers setting)"
::= { upsConfig 20 }
upsCfgBypassmaxvoltage OBJECT-TYPE
SYNTAX INTEGER (1760..2760)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"Bypass mode max voltage"
::= { upsConfig 21 }
upsCfgBypassminvoltage OBJECT-TYPE
SYNTAX INTEGER (1760..2640)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"Bypass mode min voltage"
::= { upsConfig 22 }
upsCfgBypassmaxfrequency OBJECT-TYPE
SYNTAX INTEGER (510..700) -- ( 510..600 ,610..700)
UNITS "0.1 Hertz"
ACCESS read-write
STATUS current
DESCRIPTION
"Bypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)"
::= { upsConfig 23 }
upsCfgBypassminfrequency OBJECT-TYPE
SYNTAX INTEGER (400..590) --(400..490,500..590)
UNITS "0.1 Hertz"
ACCESS read-write
STATUS current
DESCRIPTION
"Bypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)"
::= { upsConfig 24 }
upsCfgECOmaxvoltage OBJECT-TYPE
SYNTAX INTEGER (10..3000)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"ECO mode max voltage"
::= { upsConfig 25 }
upsCfgECOminvoltage OBJECT-TYPE
SYNTAX INTEGER (10..3000)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"ECO mode min voltage"
::= { upsConfig 26 }
upsCfgFreeRunMaxFrequency OBJECT-TYPE
SYNTAX INTEGER (400..700)
UNITS "0.1 Hertz "
ACCESS read-write
STATUS current
DESCRIPTION
"Free run mode max frequency"
::= { upsConfig 27 }
upsCfgFreeRunMinFrequency OBJECT-TYPE
SYNTAX INTEGER (400..700)
UNITS "0.1 Hertz "
ACCESS read-write
STATUS current
DESCRIPTION
"Free run mode min frequency"
::= { upsConfig 28 }
upsCfgEPOStatus OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Get EPO status,configured by mamual"
::= { upsConfig 29 }
upsCfgQSK1Status OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Get QSK 1 status"
::= { upsConfig 30 }
upsCfgQSK2Status OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Get QSK 2 status"
::= { upsConfig 31 }
upsCfgQSKT1Delaytime OBJECT-TYPE
SYNTAX INTEGER (0..999)
UNITS "minutes "
ACCESS read-only
STATUS current
DESCRIPTION
"Get QSKT 1 time delay"
::= { upsConfig 32 }
upsCfgQSKT2Delaytime OBJECT-TYPE
SYNTAX INTEGER (0..999)
UNITS "minutes "
ACCESS read-only
STATUS current
DESCRIPTION
"Get QSKT 2 time delay"
::= { upsConfig 33 }
upsCfgConstantPhaseAngle OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1)
}
ACCESS read-write
STATUS current
DESCRIPTION
"setting this object to Enable/disable Constant Phase Angle function"
::= { upsConfig 34 }
---PE/PD q
upsCfgInPhaseAngle OBJECT-TYPE
SYNTAX INTEGER {
Angle000(0),
Angle120(120),
Angle180(180),
Angle240(240)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Get input phase angle"
::= { upsConfig 35 }
---QPD
upsCfgOutPhaseAngle OBJECT-TYPE
SYNTAX INTEGER {
Angle000(0),
Angle120(120),
Angle180(180),
Angle240(240)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Set output phase angle"
::= { upsConfig 36 }
---QPD PPD<NNN>
upsCfgLimiRunOnBatMode OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Enable/disable limited runtime on battery mode"
::= { upsConfig 37 }
upsCfgChargingCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS current
DESCRIPTION
"Set charging current to battery ."
::= { upsConfig 38 }
upsCfgBatSeftCheckVolt OBJECT-TYPE
SYNTAX INTEGER (2400..2800)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"BatTest until battery voltage lower than <nnn>"
::= { upsConfig 39 }
upsCfgOverChargVolt OBJECT-TYPE
SYNTAX INTEGER (130..143)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set over charging voltage to per battery"
::= { upsConfig 40 }
upsCfgBattUnderVolt OBJECT-TYPE
SYNTAX INTEGER (2000..2400)
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set battery under voltage of setting value.value is a number ranging from 200V to 240V"
::= { upsConfig 41 }
upsCfgBattLowVolt OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set battery low voltage of setting value.it is 10 to 40V high than battery under voltage.
it is 10 to 40V high than battery under voltage.default 20.
it means that the battery low point is battery under add 20.
for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
"
::= { upsConfig 42 }
upsCfgIn1VoltHLoss OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set input1 voltage high loss point."
::= { upsConfig 43 }
upsCfgIn1VoltLLoss OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set input1 voltage low loss point."
::= { upsConfig 44 }
upsCfgIn2VoltHLoss OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set input2 voltage high loss point."
::= { upsConfig 45 }
upsCfgIn2VoltLLoss OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volts"
ACCESS read-write
STATUS current
DESCRIPTION
"set input2 voltage low loss point."
::= { upsConfig 46 }
upsCfgBatteryTurnOn OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1),
notsupport(2)
}
ACCESS read-write
STATUS current
DESCRIPTION
"Enable/disable battery turn on."
::= { upsConfig 47 }
-- ===========================================================================
-- upsTraps
-- prefix = upsTraps
-- Traps group
-- ===========================================================================
-- This section defines the well-known notifications sent by
-- UPS agents.
-- this traps use one share trap-node for send traps ,the trap-node vlaue between 1 and 127.
-- the share trap-node name is trapleafnodev1v2;
-- if failure or warning occur ,traps send immediately , if question not resolved,agent will resend every 4 seconds.
-- info only send once
trapleafnodev103 OBJECT-TYPE
SYNTAX DisplayString (SIZE (16..16))
ACCESS not-accessible
STATUS current
DESCRIPTION
"The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node
char trap[16];
trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap"
::= { upsTraps 998 }
trapleafnodev1v2 OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS not-accessible
STATUS current
DESCRIPTION
"The share trap-node for send all traps"
::= { upsTraps 999 }
cmpACFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"AC failure"
::= 1
cmpFanFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Fan failure"
::= 2
cmpUPSFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"UPS failure"
::= 3
cmpChargerFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Charger failure"
::= 4
cmpOverloadFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Overload failure"
::= 5
cmpOvertempFailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Over temperature fault."
::= 6
cmpInvertershortcircuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter short-circuited"
::= 7
cmpbatteryfusebeingoc TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery fuse being open-dcircuited failure"
::= 8
cmpLowbattery TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"The UPS has returned from a low battery
condition."
::= 9
cmpSysgotoshutdown TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"System is going to shutdown"
::= 10
cmpSitefault TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Site fault"
::= 11
cmpPhasesequenceincorrect TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Phase sequence incorrect"
::= 12
cmpPhasesequenceincorrectbypass TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Phase sequence incorrect in bypass"
::= 13
cmpFanalarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Fan alarm."
::= 14
cmpEPOenabled TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EPO enabled"
::= 15
cmpUnabletotrunonUPS TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Unalbe to turn on UPS"
::= 16
cmpOvertemperaturealarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Over temperature alarm"
::= 17
cmpInputfrequnstablebypass TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Input frequency unstable in bypass"
::= 18
cmpChargeralarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Charger alarm"
::= 19
cmpL1inputfusenotwork TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L1 input fuse not working"
::= 20
cmpNeutralnotConnected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Neutral not connected"
::= 21
cmpL2inputfusenotwork TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L2 input fuse not working"
::= 22
cmpL3inputfusenotwork TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L3 input fuse not working"
::= 23
cmpPositivePFCabnormalL1 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Positive PFC abnormal in L1"
::= 24
cmpNegativePFCabnormalL1 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Negative PFC abnormal in L1"
::= 25
cmpPositivePFCabnormalL2 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Positive PFC abnormal in L2"
::= 26
cmpNegativePFCabnormalL2 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Negative PFC abnormal in L2"
::= 27
cmpPositivePFCabnormalL3 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Positive PFC abnormal in L3"
::= 28
cmpNegativePFCabnormalL3 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Negative PFC abnormal in L3"
::= 29
cmpBusvoltagenotwds TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bus voltage not within default setting"
::= 30
cmpBusvoltageovermaxvalue TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bus voltage over maxinum value"
::= 31
cmpBusvoltagebelowminvalue TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bus voltage below mininum value"
::= 32
cmpBusvoltagediffoutofrange TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bus voltage differences out fo acceptable range"
::= 33
cmpBusvoltageofsloperatetoofast TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bus voltage of slope rate drops too fast"
::= 34
cmpOvercurrentinPFCII TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"WARNING:Over current in PFC input inductor."
::= 35
cmpInvertervoloutofrange TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter voltage not within default setting."
::= 36
cmpInvertervolovermaxvalue TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter voltage over maximum value."
::= 37
cmpInvertervolbelowminvalue TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter voltage below minimum value."
::= 38
cmpBatteryoppositelyconnected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery oppositely connected."
::= 39
cmpL2phaseshortcicuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L2Phase inverter short-cicuited."
::= 40
cmpL3phaseshortcicuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L3Phase inverter short-cicuited."
::= 41
cmpL1L2invertershortcicuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L1L2Inverter short-cicuited."
::= 42
cmpL2L3invertershortcicuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L2L3Inverter short-cicuited."
::= 43
cmpL3L1invertershortcicuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L3L1Inverter short-cicuited."
::= 44
cmpL1negativepoweroutofrange TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L1 inverter negative powere out of acceptable range."
::= 45
cmpL2negativepoweroutofrange TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L2 inverter negative powere out of acceptable range."
::= 46
cmpL3negativepoweroutofrange TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"L3 inverter negative powere out of acceptable range."
::= 47
cmpBatterySCRshortcircuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery SCR short-circuited."
::= 48
cmpLineSCRshortcircuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Line SCR short-circuited."
::= 49
cmpInverterrelayopenfault TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter relay open fault."
::= 50
cmpInverterrelayshortcircuited TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter relay short-circuited."
::= 51
cmpInoutwiresoppositelyconnected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Input and output wires oppositely connected."
::= 52
cmpabnormalcanbuscommunication TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Abnormal in CAN-bus communication."
::= 53
cmpcommfailurebcupsboard TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Communication failure between cpus in control board.Or DSP and MCU communication error"
::= 54
cmpabnormalsyncsignalcircuit TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Abnomal in synchronous signal circuit."
::= 55
cmpabnormalsyncpulsesignalcircuit TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Abnomal in synchronous pulse signal circuit."
::= 56
cmpcurrent3punbalancedetected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Warning for a three-phase input current unbalance detected."
::= 57
cmpbatteryselftestfailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery self-test failure."
::= 58
cmpintercurrentunbalance TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Inverter inter-current unbalance."
::= 59
cmpbatterydisconnected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery disconnected."
::= 60
cmpabnormalhostsignalcircuit TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Abnormal in host signal circuit."
::= 61
cmpbatteryovercharged TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bettery overcharged."
::= 62
cmpbatteryvoltoohigh TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bettery voltage is too high."
::= 63
cmpbatteryvoltoolow TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bettery voltage is too low."
::= 64
cmpfemaleconnectornotconnwell TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Female connector of parallel cable not connected well."
::= 65
cmpmaleconnectornotconnwell TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Male connector of parallel cable not connected well."
::= 66
cmplockingbypassA3COW30M TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Locking inbypass mode after 3 consecutive overloads within 30 minutes"
::= 67
cmpparallelcabledisconnected TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Parallel cable disconnected"
::= 68
cmpsyncpulsecircuitfault TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Synchronous pulse signal circuit fault"
::= 69
cmpsyncsignalcircuitfalt TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Synchronous signal circuit fault"
::= 70
cmphostsignalcircuitfault TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Host signal circuit fault"
::= 71
cmpcanbuscommunicationfault TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Can-bus communication fault"
::= 72
cmplowlosspointforvolinACmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Low loss point for voltage in ac mode not consistent in parallel systems"
::= 73
cmphighlosspointforvolinACmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"High loss point for voltage in ac mode not consistent in parallel systems"
::= 74
cmplowlosspointforfreqinACmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Low loss point for frequency in ac mode not consistent in parallel systems"
::= 75
cmphighlosspointforfreqinACmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"High loss point for frequency in ac mode not consistent in parallel systems"
::= 76
cmplowlosspointforvolinbypassmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Low loss point for voltage in bypass mode not consistent in parallel systems"
::= 77
cmphighlosspointforvolinbypassmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"High loss point for voltage in bypass mode not consistent in parallel systems"
::= 78
cmplowlosspointforfreqinbypassmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Low loss point for frequency in bypass mode not consistent in parallel systems"
::= 79
cmphighlosspointforfreqinbypassmode TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"High loss point for frequency in bypass mode not consistent in parallel systems"
::= 80
cmploadunbalanced TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Load unbalanced"
::= 81
cmpoverloadalarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Overload alarm"
::= 82
cmpparallelnotconnectedwell TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Parallel cable not connected well"
::= 83
cmpcommunicationlost TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Communication lost"
::= 84
cmpbatteryconnnotsonsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery connection not consistent in parallel systems"
::= 85
cmpconverternotconsisstent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Converter setting not consistent in parallel systems"
::= 86
cmpbypassnotallownotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bypass not allowed setting not consistent in parallel systems"
::= 87
cmpACconnnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"AC connection not consistent in parallel systems"
::= 88
cmpinput3pcurrentunbalance TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Warning for three-phase ac input current unbalance"
::= 89
cmpbypassconnnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bypass connection not consistent in parallel systems"
::= 90
cmpbatteryprotectionnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery protection setting not consistent in parallel systems"
::= 91
cmpbatterydetectionnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery detection setting not consistent in parallel systems"
::= 92
cmpupsmodeltypesnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"UPS model types not consistent in parallel systems"
::= 93
cmpbypassnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bypass setting not consistent in parallel systems"
::= 94
cmpcapacitynotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Capacity of upss not consistent in parallel systems"
::= 95
cmpautorestartnotconsistent TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Auto restart setting not consistent in parallel systems"
::= 96
cmpBatteryReplace TRAP-TYPE ENTERPRISE upsTraps
DESCRIPTION
"Battery need to be replace"
::= 97
cmpACNormal TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"AC normal"
::= 100
cmpOutputBadAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Output bad alarm"
::= 103
cmpBypassBadAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Bypass bad alarm"
::= 104
cmpOutputOffAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Output off alarm"
::= 105
cmpUPSShutAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"UPS shutdown alarm"
::= 106
cmpSystemOffAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"System off alarm"
::= 107
cmpFuseFailureAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Fuse failure alarm"
::= 108
cmpGenFailureAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"General failure alarm"
::= 109
cmpAwaitPowerAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Awaiting power alarm"
::= 110
cmpShutPendingAlarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Shutdown pending alarm"
::= 111
cmpBatDepleted TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery depleted"
::= 112
cmpUnknowStatus TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery unknow status"
::= 113
cmpOutputOn TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Output on"
::= 114
cmpTurntobypass TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Ups turn to bypass mode"
::= 115
cmpTurntobattery TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Ups turn to battery mode"
::= 116
cmpOutBooster TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Turn to booster"
::= 117
cmpOutReducer TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Turn to reducer"
::= 118
cmpOutBattest TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Turn to battery test mode"
::= 119
cmpOtherSource TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Other source"
::= 120
cmpBatfailure TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery failure"
::= 121
cmpBatTestDonePassed TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery test passed"
::= 122
cmpBatTestDoneWarning TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery test done warning "
::= 123
cmpBatTestDoneAborted TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery test done Aborted"
::= 124
cmpBatteryNormal TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery normal"
::= 125
cmpBatteryDischarging TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Battery Discharging "
::= 126
cmpP1cutoffprealarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"P1 cut off pre-alarm "
::= 127
cmpInputPhaseError TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Warning for input phase error for LV 6-10K UPS"
::= 128
cmpMaintainSwitchOpenalarm TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"Warning for maintain switch open"
::= 129
cmpEMDChAbnormal1 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 1 Abnormal"
::= 130
cmpEMDChAbnormal2 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 2 Abnormal"
::= 131
cmpEMDChAbnormal3 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 3 Abnormal"
::= 132
cmpEMDChAbnormal4 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 4 Abnormal"
::= 133
cmpEMDChAbnormal5 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 5 Abnormal: smoke alarm"
::= 134
cmpEMDChAbnormal6 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 6 Abnormal"
::= 135
cmpEMDChAbnormal7 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 7 Abnormal"
::= 136
cmpEMDChAbnormal8 TRAP-TYPE
ENTERPRISE upsTraps
DESCRIPTION
"EMD Channels 8 Abnormal"
::= 137
--===============================================================================
--extend
--===============================================================================
extendWorkTemperature OBJECT-TYPE
SYNTAX INTEGER (-2200..2200)
UNITS "degrees 0.1 Centigrade"
ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of work environment"
::= { extend 1 }
extendWorkhumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
ACCESS read-only
STATUS current
DESCRIPTION
"The humidity of work environment"
::= { extend 2 }
extendSmokeScope OBJECT-TYPE
SYNTAX INTEGER (0..1000000)
UNITS "%/FOOT"
ACCESS read-only
STATUS current
DESCRIPTION
"The smokeScope of work environment"
::= { extend 3 }
extendEMDAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(0)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Environment detector alarm 1"
::= { extend 4 }
extendEMDAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(0)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Environment detector alarm 2"
::= { extend 5 }
extendEMDAlarm3 OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(0)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Environment detector alarm 3"
::= { extend 6 }
extendEMDAlarm4 OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(0)
}
ACCESS read-only
STATUS current
DESCRIPTION
"Environment detector alarm 4"
::= { extend 7 }
END