mibs/MIBS/packetlight/SL-DRY-CON-MIB

292 lines
7.8 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
-- *****************************************************************
-- Dry Contacts MIB
-- *****************************************************************
SL-DRY-CON-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE,
NOTIFICATION-TYPE, Counter64,
Gauge32 FROM SNMPv2-SMI
DisplayString, TruthValue, RowStatus
FROM SNMPv2-TC
MODULE-COMPLIANCE, OBJECT-GROUP,
NOTIFICATION-GROUP FROM SNMPv2-CONF
InterfaceIndex, ifIndex FROM IF-MIB
PerfCurrentCount, PerfIntervalCount,
PerfTotalCount FROM PerfHist-TC-MIB
sitelight FROM SL-NE-MIB;
slDryConMib MODULE-IDENTITY
LAST-UPDATED "200108070000Z"
ORGANIZATION "PacketLight Networks Ltd."
CONTACT-INFO
"Omri_Viner@PacketLight.com"
DESCRIPTION
"This MIB module describes the Dry Contacts."
::= { sitelight 7 }
slDryConOut OBJECT IDENTIFIER ::= { slDryConMib 1}
slDryConIn OBJECT IDENTIFIER ::= { slDryConMib 2}
slDryConTraps OBJECT IDENTIFIER ::= { slDryConMib 3}
-- *******************************************
-- Dry Contact Outputs
-- *******************************************
slDryConAlarmCutoff OBJECT-TYPE
SYNTAX INTEGER {
dummy(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this variable cause to Alarms Cutoff."
::= {slDryConOut 1}
slDryConOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF SlDryConOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The Dry Contact Out table configure the dry contact outputs."
::= { slDryConOut 2 }
slDryConOutEntry OBJECT-TYPE
SYNTAX SlDryConOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"There is an entry for each Output Dry Contact"
INDEX { slDryConOutIndex }
::= { slDryConOutTable 1 }
SlDryConOutEntry ::=
SEQUENCE {
slDryConOutIndex INTEGER,
slDryConOutCommand INTEGER,
slDryConOutActiveStatus TruthValue
}
slDryConOutIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the output dry contact."
::= {slDryConOutEntry 1}
slDryConOutCommand OBJECT-TYPE
SYNTAX INTEGER {
activate(1),
deactivate(2),
clear(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object controls the output dry contact state:
activate(1) - activate the output dry contact
deactivate(2) - dectivate the output dry contact
clear(3) - clears the output dry contact command
The object value can also be read by the management.
In this case the agent should return the current command
to the management. The object value should not be kept in
the NVRAM because it is used only for testing.
The intial value should be clear(3)."
::= {slDryConOutEntry 2}
slDryConOutActiveStatus OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current status of the output dry contact:
TRUE - means that it is currently active
FLASE - means that it is not active"
::= {slDryConOutEntry 3}
-- *******************************************
-- Dry Contact Inputs
-- *******************************************
slDryConLastChange OBJECT-TYPE
SYNTAX INTEGER {
dummy(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Sys Uptime at the last input change."
::= {slDryConIn 1}
slDryConInTable OBJECT-TYPE
SYNTAX SEQUENCE OF SlDryConInEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The Dry Contact In table describes the dry contacts inputs."
::= { slDryConIn 2 }
slDryConInEntry OBJECT-TYPE
SYNTAX SlDryConInEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"There is an entry for each Input Dry Contact"
INDEX { slDryConInIndex }
::= { slDryConInTable 1 }
SlDryConInEntry ::=
SEQUENCE {
slDryConInIndex INTEGER,
slDryConInDescription DisplayString,
slDryConInSeverity INTEGER,
slDryConInEnable INTEGER,
slDryConInPolarity INTEGER,
slDryConInStatus INTEGER,
slDryConInAlmType INTEGER
}
slDryConInIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the input dry contact."
::= {slDryConInEntry 1}
slDryConInDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A textual description of the input dry contact alarm."
REFERENCE
"GR-833-CORE Appendix L (<almmsg>)."
::= {slDryConInEntry 2}
slDryConInSeverity OBJECT-TYPE
SYNTAX INTEGER {
critical(1),
major(2),
minor(3),
cleared(4),
notification(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A severity of the input dry contact alarm."
::= {slDryConInEntry 3}
slDryConInEnable OBJECT-TYPE
SYNTAX INTEGER {
enable(1),
disable(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enable/Disable the input dry contact alarm report generation."
::= {slDryConInEntry 4}
slDryConInPolarity OBJECT-TYPE
SYNTAX INTEGER {
activeClose(1),
activeOpen(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines the input dry contact alarm polarity."
::= {slDryConInEntry 5}
slDryConInStatus OBJECT-TYPE
SYNTAX INTEGER {
active(1),
inactive(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describe the current input dry contact alarm status."
::= {slDryConInEntry 6}
slDryConInAlmType OBJECT-TYPE
SYNTAX INTEGER {
aircompr(1), -- Air compressor failure
aircond(2), -- Air conditioning failure
airdryd(3), -- Air dryer failure
batdschrg(4), -- Battery discharging
battery(5), -- Battery failure
clfan(6), -- Cooling fan failure
cpmajor(7), -- Centralized Power Major Environmental Alarm or Major Equipment Failure
cpminor(8), -- Centralized Power Minor Environmental Alarm or Minor Equipment Failure
engine(9), -- Engine failure
engoprg(10), -- Engine operating
explgs(11), -- Explosive gas
firdetr(12), -- Fire detector failure
fire(13), -- Fire
flood(14), -- Flood
fuse(15), -- Fuse failure
gen(16), -- Generator failure
hiair(17), -- High airflow
hihum(18), -- High humidity
hitemp(19), -- High temperature
hiwtr(20), -- High water
intruder(21), -- Intrusion
lwbatvg(22), -- Low battery voltage
lwfuel(23), -- Low fuel
lwhum(24), -- Low humidity
lwpres(25), -- Low cable pressure
lwtemp(26), -- Low temperature
lwwtr(27), -- Low water
misc(28), -- Miscellaneous
opendr(29), -- Open door
pump(30), -- Pump failure
power(31), -- Commercial power failure
pwrX(32), -- X Volt power supply failure (X is a positive integer)
rect(33), -- Rectifier failure
recthi(34), -- Rectifier high voltage
rectlo(35), -- Rectifier low voltage
smoke(36), -- Smoke
toxicgas(37), -- Toxic gas
ventn(38) -- Ventilation system failure
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Describe the current input dry contact alarm type."
REFERENCE
"GR-833-CORE Appendix F Table 1."
::= {slDryConInEntry 7}
-- *******************************************
-- Dry Contact Traps
-- *******************************************
slDryConStatusChangeTrap NOTIFICATION-TYPE
OBJECTS { slDryConInIndex, slDryConInStatus, slDryConInAlmType }
STATUS current
DESCRIPTION
"An slDryConStatusChangeTrap notification is sent when
the the Status of an input dry contact is changed and the
corresponding alarm is enabled.
In order to shoten the Trap, the DisplayString that
describes the alarm is not sent. To find out this string
the NMS should use the index and get it from the table."
::= { slDryConTraps 1 }
END