-- Copyright(C) 2019 Panduit
-- G5 PDU SNMP MIB DEFINITIONS
-- ****************************************************************************
-- ====================================================================================
PANDUIT-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises FROM RFC1155-SMI
Counter FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
ifIndex FROM RFC1213-MIB
ifDescr FROM RFC1213-MIB
sysName FROM RFC1213-MIB
sysDescr FROM RFC1213-MIB
sysContact FROM RFC1213-MIB
sysLocation FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
NOTIFICATION-TYPE FROM RFC-1215;
panduit OBJECT IDENTIFIER ::= { enterprises 19536 }
g5 MODULE-IDENTITY
LAST-UPDATED "201902021200Z" -- 2 February 2019
ORGANIZATION "Panduit"
CONTACT-INFO "Panduit
Postal: Panduit
18900 Panduit Drive
Tinley Park, IL 60487
USA
Tel: +1 708 532-1800/888-506-5400
E-mail: techsupport@panduit.com"
DESCRIPTION
"SmartZone G5 iPDU"
REVISION "201902021200Z" -- 12 February 2019
DESCRIPTION
"Fix the index and access hub and added the Energy Thresholds"
REVISION "201801121200Z" -- 12 January 2018
DESCRIPTION
"First Major Release"
::= { panduit 10 }
--
-- pdug5 Monitored Managed PDU object identifiers
--
pdug5 OBJECT IDENTIFIER ::= {g5 1}
pdug5Ident OBJECT IDENTIFIER ::= { pdug5 1 }
pdug5Input OBJECT IDENTIFIER ::= { pdug5 2 }
pdug5Group OBJECT IDENTIFIER ::= { pdug5 3 }
pdug5Environment OBJECT IDENTIFIER ::= { pdug5 4 }
pdug5Outlet OBJECT IDENTIFIER ::= { pdug5 5 }
pdug5Traps OBJECT IDENTIFIER ::= { pdug5 6 }
pdug5TrapInfo OBJECT IDENTIFIER ::= { pdug5 7 }
-- ====================================================================================
-- ====================================================================================
-- pdug5 - monitored and managed PDU line
-- pdug5 (Panduit PDU) - Metered PDU - Switched PDU - Metered+Switched PDU
-- ====================================================================================
--
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Ident OBJECT IDENTIFIER ::= { pdug5 1 }
-- PDU identification group
-- OID= .1.3.6.1.4.1.19536.10.1.1
pdug5NumberPDU OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of PDUs detected (in its daisy chain)."
::= { pdug5Ident 1 }
-- ======= pdug5 Identification ===========
pdug5IdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5IdentEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Aggregate Object with number of entries equal to pdug5NumberPDU ."
::= { pdug5Ident 2 }
pdug5IdentEntry OBJECT-TYPE
SYNTAX pdug5IdentEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The Identity table entry containing the name, model, manufacturer,
firmware version, part number, etc."
INDEX { pdug5IdentIndex }
::= { pdug5IdentTable 1 }
pdug5IdentEntry ::= SEQUENCE {
pdug5IdentIndex INTEGER,
pdug5Name DisplayString,
pdug5Model DisplayString,
pdug5Manufacturer DisplayString,
pdug5FirmwareVersion DisplayString,
pdug5FirmwareVersionTimeStamp DisplayString,
pdug5PartNumber DisplayString,
pdug5SerialNumber DisplayString,
pdug5Status INTEGER,
pdug5Controllable INTEGER,
pdug5InputPhaseCount INTEGER,
pdug5GroupCount INTEGER,
pdug5OutletCount INTEGER,
pdug5MACAddress DisplayString,
pdug5IPv4Address DisplayString,
pdug5IPv6Address DisplayString
}
pdug5IdentIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the pdug5IdentEntry table."
::= { pdug5IdentEntry 1 }
pdug5Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The string identify the device in daisy chain. Example PDU A."
::= { pdug5IdentEntry 2 }
pdug5Model OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Device Model."
::= { pdug5IdentEntry 3 }
pdug5Manufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Device Manufacturer Name."
::= { pdug5IdentEntry 4 }
pdug5FirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware revision level of the device."
::= { pdug5IdentEntry 5 }
pdug5FirmwareVersionTimeStamp OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Timestamp of when the PDU firmware was last updated"
::= { pdug5IdentEntry 6 }
pdug5PartNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device part number. Example P36E09M."
::= { pdug5IdentEntry 7 }
pdug5SerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device serial number, 10-digit."
::= { pdug5IdentEntry 8 }
pdug5Status OBJECT-TYPE
SYNTAX INTEGER
{
other(1),
ok(2),
degraded(3),
failed(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of
failed(4) indicates the device is operating with critical indicators."
::= { pdug5IdentEntry 9 }
pdug5Controllable OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object indicates whether or not the device is controllable."
::= { pdug5IdentEntry 10 }
pdug5InputPhaseCount OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of input phase on this pdu 1 or 3."
::= { pdug5IdentEntry 11 }
pdug5GroupCount OBJECT-TYPE
SYNTAX INTEGER (0..12)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of groups (breakers) on this pdu."
::= { pdug5IdentEntry 12 }
pdug5OutletCount OBJECT-TYPE
SYNTAX INTEGER (1..48)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of outlets in this PDU."
::= { pdug5IdentEntry 13 }
pdug5MACAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The assigned MAC address for this PDU."
::={ pdug5IdentEntry 14 }
pdug5IPv4Address OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current IPv4 Address.
A value of 0.0.0.0 indicates an error or an unset option."
::={ pdug5IdentEntry 15 }
pdug5IPv6Address OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current IPv6 Address.
A vale of 0.0.0.0.0.0 indicates an error or an unset option."
::={ pdug5IdentEntry 16 }
-- ============ pdug5 Configuration =======
pdug5ConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5ConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Aggregate Object with number of entries equal to pdug5NumberPDU."
::= { pdug5Ident 3 }
pdug5ConfigEntry OBJECT-TYPE
SYNTAX pdug5ConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Read Configuration data from the PDU being queried."
INDEX {pdug5ConfigIndex}
::= {pdug5ConfigTable 1}
pdug5ConfigEntry ::= SEQUENCE{
pdug5ConfigIndex INTEGER,
pdug5ConfigSsh INTEGER,
pdug5ConfigFtps INTEGER,
pdug5ConfigHttp INTEGER,
pdug5ConfigHttps INTEGER,
pdug5ConfigIPv4IPv6Switch INTEGER,
pdug5ConfigRedfishAPI INTEGER,
pdug5ConfigOledDispalyOrientation INTEGER,
pdug5ConfigEnergyReset INTEGER,
pdug5ConfigNetworkManagementCardReset INTEGER,
pdug5ConfigDaisyChainStatus INTEGER
}
pdug5ConfigIndex OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The index of PDU configuration entry."
::={pdug5ConfigEntry 1}
pdug5ConfigSsh OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to off(0) will disable the SSH conneciton.
Setting this OID to on(1) will enable the SSH connection. iNC reboot will be required for the settings to take effect."
::={pdug5ConfigEntry 2}
pdug5ConfigFtps OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to off(0) will disable the FTPS connection.
Setting this OID to on(1) will enable the FTPS connection. iNC reboot will be required for the settings to take effect"
::={pdug5ConfigEntry 3}
pdug5ConfigHttp OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to off(0) will disable the HTTP connection.
Setting this OID to on(1) will enable the HTTP connection.iNC reboot will be required for the settings to take effect"
::={pdug5ConfigEntry 4}
pdug5ConfigHttps OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to off(0) will disable the HTTPS connection.
Setting this OID to on(1) will enable the HTTPS connection.iNC reboot will be required for the settings to take effect"
::={pdug5ConfigEntry 5}
pdug5ConfigIPv4IPv6Switch OBJECT-TYPE
SYNTAX INTEGER{
iPv4(1),
iPv6(2),
iPv4IPv6(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to IPv4(1) will enable the IPv4 configuration.
Setting this OID to IPv6(2) will enable the IPv6 configuration.
Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.iNC reboot will be required for the settings to take effect"
::={pdug5ConfigEntry 6}
pdug5ConfigRedfishAPI OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to off(0) will disable the Redfish API.
Setting this OID to on(1) will enable the Redfish API.iNC reboot will be required for the settings to take effect"
::={pdug5ConfigEntry 7}
pdug5ConfigOledDispalyOrientation OBJECT-TYPE
SYNTAX INTEGER{
displayNormal(1),
displayReverse(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicates the intended physical orientation of OLED display.
displayNormal(1) indicates normal orientation.
displayReverse(2) indicates upside down orientation."
::={pdug5ConfigEntry 8}
pdug5ConfigEnergyReset OBJECT-TYPE
SYNTAX INTEGER{
noOperation(1),
reset(2),
notSupported(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to reset(2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this feature
will do nothing and return the noOperation(1) value. Models that do not
supported this feature will respond to this OID with a value of notSupported(3).
Attempts to set this OID in these models will fail."
::={pdug5ConfigEntry 9}
pdug5ConfigNetworkManagementCardReset OBJECT-TYPE
SYNTAX INTEGER{
noOperation(0),
reset(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Getting this OID will return noOperation(0).
Getting this OID to reset(1) will reset iNC."
::={pdug5ConfigEntry 10}
pdug5ConfigDaisyChainStatus OBJECT-TYPE
SYNTAX INTEGER{
daisychain(0),
rna(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID will change daisychain mode. 0:QNA,1:DNA."
::={pdug5ConfigEntry 11}
-- ====================================================================================--
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Ident OBJECT IDENTIFIER ::= { pdug5 2 }
-- PDU input group
-- OID= .1.3.6.1.4.1.19536.10.1.2
pdug5InputTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5InputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Aggregate Object with number of entries equal to pdug5NumberPDU ."
::= { pdug5Input 1 }
pdug5InputEntry OBJECT-TYPE
SYNTAX pdug5InputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The ident table entry containing the VA, Watts, WH, etc."
INDEX { pdug5IdentIndex }
::= { pdug5InputTable 1 }
pdug5InputEntry ::= SEQUENCE {
pdug5InputType INTEGER,
pdug5InputFrequency INTEGER,
pdug5InputFrequencyStatus INTEGER,
pdug5InputPowerVA INTEGER,
pdug5InputPowerWatts INTEGER,
pdug5InputTotalEnergy INTEGER,
pdug5InputPowerWattHourTimer DisplayString,
pdug5InputResettableEnergy INTEGER,
pdug5InputPowerFactor INTEGER,
pdug5InputPowerVAR INTEGER,
pdug5InputTotalCurrent INTEGER
}
pdug5InputType OBJECT-TYPE
SYNTAX INTEGER {
singlePhase (1),
splitPhase (2),
threePhaseDelta (3),
threePhaseWye (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of input - single phase, split phase, three phase delta, or three
phase wye."
::= { pdug5InputEntry 1 }
pdug5InputFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483647) -- UNITS RMS 0.001 Hz
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The measured input frequency from the PDU meters in tenths of Hz."
::= { pdug5InputEntry 2 }
pdug5InputFrequencyStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
outOfRange (2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured input frequency relative to the nominal frequency and the admitted tolerance."
::= { pdug5InputEntry 3 }
pdug5InputPowerVA OBJECT-TYPE
SYNTAX INTEGER -- Units in VA
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A total input VA of all phases. Units are VA. A negative value indicates
that this object is not available."
::= { pdug5InputEntry 4 }
pdug5InputPowerWatts OBJECT-TYPE
SYNTAX INTEGER -- Units in Watts
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A total input Watts of all phases. Units are Watts. A negative value indicates
that this object is not available."
::= { pdug5InputEntry 5 }
pdug5InputTotalEnergy OBJECT-TYPE
SYNTAX INTEGER -- Units in KWh
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service.
A negative value indicates that this object is not available."
::= { pdug5InputEntry 6 }
pdug5InputPowerWattHourTimer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..22)) -- display Date Time Since Last Reset
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A Timestamp of when the Total Input WH was last reset."
::= { pdug5InputEntry 7 }
pdug5InputResettableEnergy OBJECT-TYPE
SYNTAX INTEGER -- Units in Wh
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A total input Watt-Hour value for all phases. Units are Wh. This value can be reset to 0
using GUI. In that case, the pdug5InputPowerWattHourTimer will be reset as well
A negative value indicates that this object is not available."
::= { pdug5InputEntry 8 }
pdug5InputPowerFactor OBJECT-TYPE
SYNTAX INTEGER -- units 0.01
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input PF value. Units are in thousandths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92.
A negative value indicates that this object is not available."
::= { pdug5InputEntry 9 }
pdug5InputPowerVAR OBJECT-TYPE
SYNTAX INTEGER -- Units in VAR
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input VAR value. Units are VAR. A negative value indicates
that this object is not available."
::= { pdug5InputEntry 10 }
pdug5InputTotalCurrent OBJECT-TYPE
SYNTAX INTEGER -- Units are 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"All phases total current value. Units are 0.01 amps.
For 3 phase, mathematically add totally 3 phase current together."
::= { pdug5InputEntry 11 }
-- ==========Input per Phase =============
pdug5InputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5InputPhaseEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and
number of input phase (pdug5InputPhaseCount)."
::= {pdug5Input 2}
pdug5InputPhaseEntry OBJECT-TYPE
SYNTAX pdug5InputPhaseEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3."
INDEX { pdug5IdentIndex, pdug5InputPhaseIndex }
::= { pdug5InputPhaseTable 1 }
pdug5InputPhaseEntry ::= SEQUENCE {
pdug5InputPhaseIndex INTEGER,
pdug5InputPhaseVoltageMeasType INTEGER,
pdug5InputPhaseVoltage INTEGER,
pdug5InputPhaseVoltageThStatus INTEGER,
pdug5InputPhaseVoltageThLowerWarning INTEGER,
pdug5InputPhaseVoltageThLowerCritical INTEGER,
pdug5InputPhaseVoltageThUpperWarning INTEGER,
pdug5InputPhaseVoltageThUpperCritical INTEGER,
pdug5InputPhaseCurrentMeasType INTEGER,
pdug5InputPhaseCurrentRating INTEGER,
pdug5InputPhaseCurrent INTEGER,
pdug5InputPhaseCurrentThStatus INTEGER,
pdug5InputPhaseCurrentThLowerWarning INTEGER,
pdug5InputPhaseCurrentThLowerCritical INTEGER,
pdug5InputPhaseCurrentThUpperWarning INTEGER,
pdug5InputPhaseCurrentThUpperCritical INTEGER,
pdug5InputPhaseCurrentPercentLoad INTEGER,
pdug5InputPhasePowerMeasType INTEGER,
pdug5InputPhasePowerVA INTEGER,
pdug5InputPhasePowerWatts INTEGER,
pdug5InputPhasePowerWattHour INTEGER,
pdug5InputPhasePowerWattHourTimer DisplayString,
pdug5InputPhasePowerFactor INTEGER,
pdug5InputPhasePowerVAR INTEGER,
pdug5InputPhaseVoltageThResetThld INTEGER,
pdug5InputPhaseVoltageThChangeDelay INTEGER,
pdug5InputPhaseVoltageThCtrl INTEGER,
pdug5InputPhaseCurrentThResetThld INTEGER,
pdug5InputPhaseCurrentThChangeDelay INTEGER,
pdug5InputPhaseCurrentThCtrl INTEGER,
pdug5InputPowerThresholdThLowerWarning INTEGER,
pdug5InputPowerThresholdThLowerCritical INTEGER,
pdug5InputPowerThresholdThUpperWarning INTEGER,
pdug5InputPowerThresholdThUpperCritical INTEGER,
pdug5InputPowerThresholdThResetThld INTEGER,
pdug5InputPowerThresholdThChangeDelay INTEGER,
pdug5InputPowerThresholdThCtrl INTEGER,
pdug5InputEnergyThresholdThUpperWarning INTEGER,
pdug5InputEnergyThresholdThUpperCritical INTEGER,
pdug5InputEnergyThresholdThResetThld INTEGER,
pdug5InputEnergyThresholdThChangeDelay INTEGER,
pdug5InputEnergyThresholdThCtrl INTEGER
}
pdug5InputPhaseIndex OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the pdug5InputEntry table."
::= { pdug5InputPhaseEntry 1}
pdug5InputPhaseVoltageMeasType OBJECT-TYPE
SYNTAX INTEGER {
singlePhase (1),
phase1toN (2),
phase2toN (3),
phase3toN (4),
phase1to2 (5),
phase2to3 (6),
phase3to1 (7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1."
::= { pdug5InputPhaseEntry 2 }
pdug5InputPhaseVoltage OBJECT-TYPE
SYNTAX INTEGER -- UNITS RMS 0.1 V
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input voltage measurement value. Values is in 0.1 V."
::= {pdug5InputPhaseEntry 3}
pdug5InputPhaseVoltageThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured input voltage relative to the configured thresholds."
::= { pdug5InputPhaseEntry 4 }
pdug5InputPhaseVoltageThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 5 }
pdug5InputPhaseVoltageThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 6 }
pdug5InputPhaseVoltageThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 7 }
pdug5InputPhaseVoltageThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 8 }
pdug5InputPhaseCurrentMeasType OBJECT-TYPE
SYNTAX INTEGER {
singlePhase (1),
neutral (2),
phase1 (3),
phase2 (4),
phase3 (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3."
::= { pdug5InputPhaseEntry 9 }
pdug5InputPhaseCurrentRating OBJECT-TYPE
SYNTAX INTEGER -- Units in 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are 0.01 amps."
::= { pdug5InputPhaseEntry 10 }
pdug5InputPhaseCurrent OBJECT-TYPE
SYNTAX INTEGER -- Units in 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input current measurement value. Units are 0.01 amps."
::= { pdug5InputPhaseEntry 11 }
pdug5InputPhaseCurrentThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured input current relative to the configured thresholds."
::= { pdug5InputPhaseEntry 12 }
pdug5InputPhaseCurrentThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 13 }
pdug5InputPhaseCurrentThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 14 }
pdug5InputPhaseCurrentThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 15 }
pdug5InputPhaseCurrentThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 16 }
pdug5InputPhaseCurrentPercentLoad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available."
::= { pdug5InputPhaseEntry 17 }
pdug5InputPhasePowerMeasType OBJECT-TYPE
SYNTAX INTEGER {
singlePhase (1),
neutral (2),
phase1 (3),
phase2 (4),
phase3 (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3."
::= { pdug5InputPhaseEntry 18 }
pdug5InputPhasePowerVA OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input VA value. Units are VA. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 19 }
pdug5InputPhasePowerWatts OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input Watts value. Units are Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 20 }
pdug5InputPhasePowerWattHour OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 21 }
pdug5InputPhasePowerWattHourTimer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..22)) -- display Date Time
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Timestamp of when input Watt-hours (inputWh) was last reset."
::= { pdug5InputPhaseEntry 22 }
pdug5InputPhasePowerFactor OBJECT-TYPE
SYNTAX INTEGER -- units 0.01
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input PF value. Units are in thousandths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned
as 92. A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 23 }
pdug5InputPhasePowerVAR OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input VAR value. Units are VAR. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 24 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.25
pdug5InputPhaseVoltageThResetThld OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase voltage alarm reset threshold. Units are 0.1 volts.
A negative value indicates that this object is not available."
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 25 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.26
pdug5InputPhaseVoltageThChangeDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase voltage alarm change delay. Units are 0.1 volts.
A negative value indicates that this object is not available."
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 26 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.27
pdug5InputPhaseVoltageThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase voltage alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 27 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.28
pdug5InputPhaseCurrentThResetThld OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase current alarm reset threshold. Units are 0.01 amps.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 28 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.29
pdug5InputPhaseCurrentThChangeDelay OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase current alarm change delay. Units are 0.01 amps.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 29 }
-- 1.3.6.1.4.1.19536.10.1.2.2.1.30
pdug5InputPhaseCurrentThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Input phase current alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 30 }
pdug5InputPowerThresholdThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 31 }
pdug5InputPowerThresholdThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 32 }
pdug5InputPowerThresholdThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 33 }
pdug5InputPowerThresholdThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 34 }
pdug5InputPowerThresholdThResetThld OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Power alarm reset threshold. Units are in Watts.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 35 }
pdug5InputPowerThresholdThChangeDelay OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Power alarm change delay. Units are in Watts.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 36 }
pdug5InputPowerThresholdThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Power alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 37 }
pdug5InputEnergyThresholdThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning Energy threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 38 }
pdug5InputEnergyThresholdThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical Energy threshold. Units are in Watts. A negative value indicates
that this object is not available."
::= { pdug5InputPhaseEntry 39 }
pdug5InputEnergyThresholdThResetThld OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Energy alarm reset threshold. Units are in Watts.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 40 }
pdug5InputEnergyThresholdThChangeDelay OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units in W
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Energy alarm change delay. Units are in Watts.
A negative value indicates that this object is not available."
::= { pdug5InputPhaseEntry 41 }
pdug5InputEnergyThresholdThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Energy alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5InputPhaseEntry 42 }
-- ====================================================================================
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Group OBJECT IDENTIFIER ::= { pdug5 3 }
-- pdug5 Output groups of outlets
-- OID= .1.3.6.1.4.1.19536.10.1.3
pdug5GroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5GroupEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Aggregate Object with number of entries equal to number of PDUs
and number of breakers (pdug5GroupCount)."
::= { pdug5Group 1 }
pdug5GroupEntry OBJECT-TYPE
SYNTAX pdug5GroupEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The input table entry containing the name, voltages, currents, power, etc."
INDEX { pdug5IdentIndex, pdug5GroupIndex }
::= { pdug5GroupTable 1 }
pdug5GroupEntry ::= SEQUENCE {
pdug5GroupIndex INTEGER,
pdug5GroupName DisplayString,
pdug5GroupType INTEGER,
pdug5GroupVoltageMeasType INTEGER,
pdug5GroupVoltage INTEGER,
pdug5GroupVoltageThStatus INTEGER,
pdug5GroupVoltageThLowerWarning INTEGER,
pdug5GroupVoltageThLowerCritical INTEGER,
pdug5GroupVoltageThUpperWarning INTEGER,
pdug5GroupVoltageThUpperCritical INTEGER,
pdug5groupCurrentRating INTEGER,
pdug5GroupCurrent INTEGER,
pdug5GroupCurrentThStatus INTEGER,
pdug5GroupCurrentThLowerWarning INTEGER,
pdug5GroupCurrentThLowerCritical INTEGER,
pdug5GroupCurrentThUpperWarning INTEGER,
pdug5GroupCurrentThUpperCritical INTEGER,
pdug5GroupCurrentPercentLoad INTEGER,
pdug5GroupPowerVA INTEGER,
pdug5GroupPowerWatts INTEGER,
pdug5GroupPowerWattHour INTEGER,
pdug5GroupPowerWattHourTimer DisplayString,
pdug5GroupPowerFactor INTEGER,
pdug5GroupPowerVAR INTEGER,
pdug5GroupOutletCount INTEGER,
pdug5GroupBreakerStatus INTEGER,
pdug5GroupVoltageThCtrl INTEGER,
pdug5GroupCurrentThCtrl INTEGER
}
pdug5GroupIndex OBJECT-TYPE
SYNTAX INTEGER (0..12)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the pdug5GroupEntry table."
::= { pdug5GroupEntry 1 }
pdug5GroupName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the group."
::= { pdug5GroupEntry 2 }
pdug5GroupType OBJECT-TYPE
SYNTAX INTEGER {
breaker1pole (2),
breaker2pole (3),
breaker3pole (4),
outletSection (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The type of the group. (5) has no breaker"
::= { pdug5GroupEntry 3 }
pdug5GroupVoltageMeasType OBJECT-TYPE
SYNTAX INTEGER {
singlePhase (1),
phase1toN (2),
phase2toN (3),
phase3toN (4),
phase1to2 (5),
phase2to3 (6),
phase3to1 (7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1."
::= { pdug5GroupEntry 4 }
pdug5GroupVoltage OBJECT-TYPE
SYNTAX INTEGER -- Units 0.1 V
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Units are 0.1 volts."
::= { pdug5GroupEntry 5 }
pdug5GroupVoltageThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured group voltage relative to the configured thresholds."
::= { pdug5GroupEntry 6 }
pdug5GroupVoltageThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 7 }
pdug5GroupVoltageThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 8 }
pdug5GroupVoltageThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 9 }
pdug5GroupVoltageThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..500000) -- Units 0.1 V
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 10 }
pdug5groupCurrentRating OBJECT-TYPE
SYNTAX INTEGER -- Units 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Rated current capacity of the group. Units are 0.01 amps. A negative
value indicates that the hardware current capacity is unknown (it
will always be unknown for custom groups)."
::= { pdug5GroupEntry 11 }
pdug5GroupCurrent OBJECT-TYPE
SYNTAX INTEGER -- Units 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A group current measurement value. Units are 0.01 amps."
::= { pdug5GroupEntry 12 }
pdug5GroupCurrentThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured group current relative to the configured thresholds."
::= { pdug5GroupEntry 13 }
pdug5GroupCurrentThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 14 }
pdug5GroupCurrentThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 15 }
pdug5GroupCurrentThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 16 }
pdug5GroupCurrentThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..100000) -- Units 0.01 A
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 17 }
pdug5GroupCurrentPercentLoad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available."
::= { pdug5GroupEntry 18 }
pdug5GroupPowerVA OBJECT-TYPE
SYNTAX INTEGER -- units in VA
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A group VA value. Units are VA. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 19 }
pdug5GroupPowerWatts OBJECT-TYPE
SYNTAX INTEGER -- units in Watt
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A group power value. Units are Watts. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 20 }
pdug5GroupPowerWattHour OBJECT-TYPE
SYNTAX INTEGER -- Units in Watt-Hour
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A Watt-Hour value for each section. Units are WH. This value can be reset to 0
using GUI. In that case, the pdug5GroupPowerWattHourTimer will be reset as well.
A negative value indicates that this object is not available."
::= { pdug5GroupEntry 21 }
pdug5GroupPowerWattHourTimer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..22)) -- display Date and Time
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Timestamp of when group Watt-hours (groupWh) was last reset."
::= { pdug5GroupEntry 22 }
pdug5GroupPowerFactor OBJECT-TYPE
SYNTAX INTEGER -- Value is in 0.01
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A group PF value. Units are in thousandths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92.
A negative value indicates that this object is not available."
::= { pdug5GroupEntry 23 }
pdug5GroupPowerVAR OBJECT-TYPE
SYNTAX INTEGER -- Units in VAR
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A group VAR value. Units are VAR. A negative value indicates
that this object is not available."
::= { pdug5GroupEntry 24 }
pdug5GroupOutletCount OBJECT-TYPE
SYNTAX INTEGER (0..48)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of outlets in each group (breaker)."
::= { pdug5GroupEntry 25 }
pdug5GroupBreakerStatus OBJECT-TYPE
SYNTAX INTEGER {
notApplicable (1),
breakerOn (2),
breakerOff (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on."
::= { pdug5GroupEntry 26 }
-- 1.3.6.1.4.1.19536.10.1.3.1.1.27
pdug5GroupVoltageThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Circuit Breaker voltage alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5GroupEntry 27 }
-- 1.3.6.1.4.1.19536.10.1.3.1.1.28
pdug5GroupCurrentThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Circuit Breaker current alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
::= { pdug5GroupEntry 28 }
-- ====================================================================================
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Environment OBJECT IDENTIFIER ::= { pdug5 4 }
-- pdug5 Environment group
-- PDU identification group
-- OID= .1.3.6.1.4.1.19536.10.1.4
pdug5EnvProbeTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5EnvProbeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of environment probe (1 per PDU) for temperature, humidity, and contacts.
The number of entries is given by number of PDUs in daisy chain."
::= { pdug5Environment 1 }
pdug5EnvProbeEntry OBJECT-TYPE
SYNTAX pdug5EnvProbeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Aggregate entries equal to number of PDUs."
INDEX { pdug5IdentIndex }
::= { pdug5EnvProbeTable 1 }
pdug5EnvProbeEntry ::= SEQUENCE {
pdug5TemperatureScale INTEGER,
pdug5TemperatureCount INTEGER,
pdug5HumidityCount INTEGER,
pdug5DoorCount INTEGER,
pdug5DryCount INTEGER,
pdug5SpotCount INTEGER,
pdug5RopeCount INTEGER,
pdug5HidCount INTEGER
}
pdug5TemperatureScale OBJECT-TYPE
SYNTAX INTEGER {
celsius (1),
fahrenheit (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Scale used to return temperature objects."
::= { pdug5EnvProbeEntry 1 }
pdug5TemperatureCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of temperature measurements.The MAX is 6 (1 per probe)."
::= { pdug5EnvProbeEntry 2 }
pdug5HumidityCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of humidity measurements.The MAX is 6(1 per probe)."
::= { pdug5EnvProbeEntry 3 }
pdug5DoorCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of door sensors.The MAX is 6(1 per probe)."
::= { pdug5EnvProbeEntry 4 }
pdug5DryCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of dry sensors.The MAX is 2(1 per probe)."
::= { pdug5EnvProbeEntry 5 }
pdug5SpotCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of spot sensors.The MAX is 2(1 per probe)."
::= { pdug5EnvProbeEntry 6 }
pdug5RopeCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of rope sensors.The MAX is 2(1 per probe)."
::= { pdug5EnvProbeEntry 7 }
pdug5HidCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of hid sensors. The MAX is 2(1 per probe)."
::= { pdug5EnvProbeEntry 10 }
-- ========Temperature Measurements ============
pdug5TemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5TemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of temperature probe measurements. The number of entries are
given by number of pdu and pdug5TemperatureCount."
::= { pdug5Environment 2 }
pdug5TemperatureEntry OBJECT-TYPE
SYNTAX pdug5TemperatureEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a temperature measurement."
INDEX { pdug5IdentIndex, pdug5TemperatureIndex }
::= { pdug5TemperatureTable 1 }
pdug5TemperatureEntry ::= SEQUENCE {
pdug5TemperatureIndex INTEGER,
pdug5TemperatureName DisplayString,
pdug5TemperatureProbeStatus INTEGER,
pdug5TemperatureValue INTEGER,
pdug5TemperatureThStatus INTEGER,
pdug5TemperatureThLowerWarning INTEGER,
pdug5TemperatureThLowerCritical INTEGER,
pdug5TemperatureThUpperWarning INTEGER,
pdug5TemperatureThUpperCritical INTEGER,
pdug5TemperatureThCtrl INTEGER
}
pdug5TemperatureIndex OBJECT-TYPE
SYNTAX INTEGER (1..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount."
::= { pdug5TemperatureEntry 1 }
pdug5TemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the temperature probe."
::= { pdug5TemperatureEntry 2 }
pdug5TemperatureProbeStatus OBJECT-TYPE
SYNTAX INTEGER {
disconnected (1),
connected (2),
bad (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not."
::= { pdug5TemperatureEntry 3 }
pdug5TemperatureValue OBJECT-TYPE
SYNTAX INTEGER --0.1 Fahrenheit or Celsius
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Units are degree(either Fahrenheit or Celsius)."
::= { pdug5TemperatureEntry 4 }
pdug5TemperatureThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured temperature relative to the configured thresholds."
::= { pdug5TemperatureEntry 5 }
pdug5TemperatureThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..150000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are degrees. A negative value
indicates that this object is not available."
::= { pdug5TemperatureEntry 6 }
pdug5TemperatureThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..150000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are degrees. A negative value
indicates that this object is not available."
::= { pdug5TemperatureEntry 7 }
pdug5TemperatureThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..150000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are degrees. A negative value
indicates that this object is not available."
::= { pdug5TemperatureEntry 8 }
pdug5TemperatureThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..150000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are degrees. A negative value
indicates that this object is not available."
::= { pdug5TemperatureEntry 9 }
-- 1.3.6.1.4.1.19536.10.1.4.2.1.10
pdug5TemperatureThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Temperature alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5TemperatureEntry 10 }
-- ==========Humidity Measurements ==========
pdug5HumidityTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5HumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of humidity probe measurements. The number of entries are
given by number of pdu and pdug5HumidityCount."
::= { pdug5Environment 3 }
pdug5HumidityEntry OBJECT-TYPE
SYNTAX pdug5HumidityEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a humidity measurement."
INDEX { pdug5IdentIndex, pdug5HumidityIndex }
::= { pdug5HumidityTable 1 }
pdug5HumidityEntry ::= SEQUENCE {
pdug5HumidityIndex INTEGER,
pdug5HumidityName DisplayString,
pdug5HumidityProbeStatus INTEGER,
pdug5HumidityValue INTEGER,
pdug5HumidityThStatus INTEGER,
pdug5HumidityThLowerWarning INTEGER,
pdug5HumidityThLowerCritical INTEGER,
pdug5HumidityThUpperWarning INTEGER,
pdug5HumidityThUpperCritical INTEGER,
pdug5HumidityThCtrl INTEGER
}
pdug5HumidityIndex OBJECT-TYPE
SYNTAX INTEGER (1..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each humidity probe measurement. Its value
ranges from 1 to pdug5HumidityCount per PDU."
::= { pdug5HumidityEntry 1 }
pdug5HumidityName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the humidity probe."
::= { pdug5HumidityEntry 2 }
pdug5HumidityProbeStatus OBJECT-TYPE
SYNTAX INTEGER {
disconnected (1),
connected (2),
bad (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not."
::= { pdug5HumidityEntry 3 }
pdug5HumidityValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Units are %RH."
::= { pdug5HumidityEntry 4 }
pdug5HumidityThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured humidity relative to the configured thresholds."
::= { pdug5HumidityEntry 5 }
pdug5HumidityThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are %RH. A negative value
indicates that this object is not available."
::= { pdug5HumidityEntry 6 }
pdug5HumidityThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are %RH. A negative value
indicates that this object is not available."
::= { pdug5HumidityEntry 7 }
pdug5HumidityThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are %RH. A negative value
indicates that this object is not available."
::= { pdug5HumidityEntry 8 }
pdug5HumidityThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are %RH. A negative value
indicates that this object is not available."
::= { pdug5HumidityEntry 9 }
-- 1.3.6.1.4.1.19536.10.1.4.3.1.10
pdug5HumidityThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Humidity alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5HumidityEntry 10 }
-- ======Door sensor Status==========
pdug5DoorTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5DoorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of door sensors. The number of entries are
given by number of PDU and pdug5DoorCount."
::= { pdug5Environment 4 }
pdug5DoorEntry OBJECT-TYPE
SYNTAX pdug5DoorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a door sensor"
INDEX { pdug5IdentIndex, pdug5DoorIndex }
::= { pdug5DoorTable 1 }
pdug5DoorEntry ::= SEQUENCE {
pdug5DoorIndex INTEGER,
pdug5DoorName DisplayString,
pdug5DoorProbeStatus INTEGER,
pdug5DoorState INTEGER
}
pdug5DoorIndex OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each door sensor. Its value ranges from 1 to
doorCount."
::= { pdug5DoorEntry 1 }
pdug5DoorName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the door sensor."
::= { pdug5DoorEntry 2 }
pdug5DoorProbeStatus OBJECT-TYPE
SYNTAX INTEGER {
disconnected (1),
connected (2),
bad (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not.
Will not be returned if the door sensor is internal to the ePDU,
in that case only doorState should be read."
::= { pdug5DoorEntry 3 }
pdug5DoorState OBJECT-TYPE
SYNTAX INTEGER {
doorOpen (1),
doorClosed (2),
BaddoorSensor (3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The state of the door sensor."
::= { pdug5DoorEntry 4 }
-- ======Dry Sensor Status==========
-- 1.3.6.1.4.1.19536.10.1.4.5
pdug5DryTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5DryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of dry sensors. The number of entries are
given by number of pdu and pdug5DryCount."
::= { pdug5Environment 5 }
-- 1.3.6.1.4.1.19536.10.1.4.5.1
pdug5DryEntry OBJECT-TYPE
SYNTAX pdug5DryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a contact sensor"
INDEX { pdug5IdentIndex, pdug5DryIndex }
::= { pdug5DryTable 1 }
pdug5DryEntry ::=
SEQUENCE {
pdug5DryIndex
INTEGER,
pdug5DryName
DisplayString,
pdug5DryProbeStatus
INTEGER,
pdug5DryState
INTEGER
}
-- 1.3.6.1.4.1.19536.10.1.4.5.1.1
pdug5DryIndex OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each dry sensor. Its value ranges from 1 to
dryCount."
::= { pdug5DryEntry 1 }
-- 1.3.6.1.4.1.19536.10.1.4.5.1.2
pdug5DryName OBJECT-TYPE
SYNTAX DisplayString (SIZE (1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the dry sensor."
::= { pdug5DryEntry 2 }
-- 1.3.6.1.4.1.19536.10.1.4.5.1.3
pdug5DryProbeStatus OBJECT-TYPE
SYNTAX INTEGER
{
disconnected(1),
connected(2),
bad(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not."
::= { pdug5DryEntry 3 }
-- 1.3.6.1.4.1.19536.10.1.4.5.1.4
pdug5DryState OBJECT-TYPE
SYNTAX INTEGER
{
good(1),
alarmed(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The state of the dry sensor."
::= { pdug5DryEntry 4 }
-- ====== Water Spot Sensor Status==========
-- 1.3.6.1.4.1.19536.10.1.4.6
pdug5SpotTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5SpotEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact sensors. The number of entries are
given by number of pdu and pdug5SpotCount."
::= { pdug5Environment 6 }
-- 1.3.6.1.4.1.19536.10.1.4.6.1
pdug5SpotEntry OBJECT-TYPE
SYNTAX pdug5SpotEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a contact sensor"
INDEX { pdug5IdentIndex, pdug5SpotIndex }
::= { pdug5SpotTable 1 }
pdug5SpotEntry ::=
SEQUENCE {
pdug5SpotIndex
INTEGER,
pdug5SpotName
DisplayString,
pdug5SpotProbeStatus
INTEGER,
pdug5SpotState
INTEGER
}
-- 1.3.6.1.4.1.19536.10.1.4.6.1.1
pdug5SpotIndex OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each spot sensor. Its value ranges from 1 to
spotCount."
::= { pdug5SpotEntry 1 }
-- 1.3.6.1.4.1.19536.10.1.4.6.1.2
pdug5SpotName OBJECT-TYPE
SYNTAX DisplayString (SIZE (1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the spot sensor."
::= { pdug5SpotEntry 2 }
-- 1.3.6.1.4.1.19536.10.1.4.6.1.3
pdug5SpotProbeStatus OBJECT-TYPE
SYNTAX INTEGER
{
disconnected(1),
connected(2),
bad(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not."
::= { pdug5SpotEntry 3 }
-- 1.3.6.1.4.1.19536.10.1.4.6.1.4
pdug5SpotState OBJECT-TYPE
SYNTAX INTEGER
{
noleak(1),
leak(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The state of the spot sensor."
::= { pdug5SpotEntry 4 }
-- ======Water Rope Sensor Status==========
-- 1.3.6.1.4.1.19536.10.1.4.7
pdug5RopeTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5RopeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of rope sensors. The number of entries are
given by number of pdu and pdug5RopeCount."
::= { pdug5Environment 7 }
-- 1.3.6.1.4.1.19536.10.1.4.7.1
pdug5RopeEntry OBJECT-TYPE
SYNTAX pdug5RopeEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a contact sensor"
INDEX { pdug5IdentIndex, pdug5RopeIndex }
::= { pdug5RopeTable 1 }
pdug5RopeEntry ::=
SEQUENCE {
pdug5RopeIndex
INTEGER,
pdug5RopeName
DisplayString,
pdug5RopeProbeStatus
INTEGER,
pdug5RopeState
INTEGER
}
-- 1.3.6.1.4.1.19536.10.1.4.7.1.1
pdug5RopeIndex OBJECT-TYPE
SYNTAX INTEGER (1..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique value for each rope sensor. Its value ranges from 1 to
ropeCount."
::= { pdug5RopeEntry 1 }
-- 1.3.6.1.4.1.19536.10.1.4.7.1.2
pdug5RopeName OBJECT-TYPE
SYNTAX DisplayString (SIZE (1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the rope sensor."
::= { pdug5RopeEntry 2 }
-- 1.3.6.1.4.1.19536.10.1.4.7.1.3
pdug5RopeProbeStatus OBJECT-TYPE
SYNTAX INTEGER
{
disconnected(1),
connected(2),
bad(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether a probe is connected or not."
::= { pdug5RopeEntry 3 }
-- 1.3.6.1.4.1.19536.10.1.4.7.1.4
pdug5RopeState OBJECT-TYPE
SYNTAX INTEGER
{
noleak(1),
leak(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The state of the rope sensor."
::= { pdug5RopeEntry 4 }
-- 1.3.6.1.4.1.19536.10.1.4.10
pdug5EnvHID OBJECT IDENTIFIER ::= { pdug5Environment 10 }
-- ======Hid Sensor Status==========
-- 1.3.6.1.4.1.19536.10.1.4.10.1
pdug5EnvHidTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5EnvHidEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contact sensors. The number of entries are
given by number of pdu and pdug5HidCount."
::= { pdug5EnvHID 1 }
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1
pdug5EnvHidEntry OBJECT-TYPE
SYNTAX pdug5EnvHidEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry for a contact sensor"
INDEX { pdug5IdentIndex, pdug5HIDIndex }
::= { pdug5EnvHidTable 1 }
pdug5EnvHidEntry ::=
SEQUENCE {
pdug5HIDIndex
INTEGER,
pdug5HidAisle
INTEGER,
pdug5HidHandleOperation
INTEGER
}
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1.1
pdug5HIDIndex OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of the PDU HID table entry"
::= { pdug5EnvHidEntry 1 }
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1.2
pdug5HidAisle OBJECT-TYPE
SYNTAX INTEGER
{
COLD(1),
HOT(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Aisle of HID handle. "
::= { pdug5EnvHidEntry 2 }
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1.3
pdug5HidHandleOperation OBJECT-TYPE
SYNTAX INTEGER
{
unlock(1),
lock(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID handle control opterations "
::= { pdug5EnvHidEntry 3 }
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1.4
pduHIDVer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware revision level of the HID"
::= { pdug5EnvHidEntry 4 }
-- 1.3.6.1.4.1.19536.10.1.4.10.1.1.5
pdug5MechanicalLock OBJECT-TYPE
SYNTAX INTEGER
{
unlock(1),
lock(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"HID Mechanical opterations "
::= { pdug5EnvHidEntry 5 }
-- ======Hid hid control table==========
-- 1.3.6.1.4.1.19536.10.1.4.10.2
pdug5EnvHidControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5EnvHidControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of smartcard. The number of entries are
given by number of pdu and pdug5HidCount."
::= { pdug5EnvHID 2 }
-- 1.3.6.1.4.1.19536.10.1.4.10.2.1
pdug5EnvHidControlEntry OBJECT-TYPE
SYNTAX pdug5EnvHidControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The smartcard table entry containing the usrname, cardid, cardaisle etc."
INDEX { pdug5IdentIndex, pdug5HidControlIndex }
::= { pdug5EnvHidControlTable 1 }
pdug5EnvHidControlEntry ::=
SEQUENCE {
pdug5HidControlIndex INTEGER,
pdug5HidControlUserName DisplayString,
pdug5HidControlCardID INTEGER,
pdug5HidControlTimestamp DisplayString,
pdug5HidControlCardAisle INTEGER
}
-- 1.3.6.1.4.1.19536.10.1.4.10.2.1.1
pdug5HidControlIndex OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of the PDU smartcard table entry"
::= { pdug5EnvHidControlEntry 1 }
-- 1.3.6.1.4.1.19536.10.1.4.10.2.1.2
pdug5HidControlUserName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User name of smartcard"
::= { pdug5EnvHidControlEntry 2 }
-- 1.3.6.1.4.19536.10.1.4.10.2.1.3
pdug5HidControlCardID OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HID smartcard ID."
::= { pdug5EnvHidControlEntry 3 }
-- 1.3.6.1.4.19536.10.1.4.10.2.1.4
pdug5HidControlTimestamp OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicates the date and time of accessing"
::= { pdug5EnvHidControlEntry 4 }
-- 1.3.6.1.4.19536.10.1.4.10.2.1.5
pdug5HidControlCardAisle OBJECT-TYPE
SYNTAX INTEGER
{
COLD(1),
HOT(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Aisle of authorized card. "
::= { pdug5EnvHidControlEntry 5 }
-- ====================================================================================
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Outlet OBJECT IDENTIFIER ::= { pdug5 5 }
-- OID= .1.3.6.1.4.1.19536.10.1.5
pdug5OutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5OutletEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex)
and Number of outlet per PDU (pdug5OutletIndex)."
::= { pdug5Outlet 1 }
pdug5OutletEntry OBJECT-TYPE
SYNTAX pdug5OutletEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The Outlet table entry containing the type, voltage, current etc."
INDEX { pdug5IdentIndex, pdug5OutletIndex }
::= { pdug5OutletTable 1 }
pdug5OutletEntry ::= SEQUENCE {
pdug5OutletIndex INTEGER,
pdug5OutletName DisplayString,
pdug5OutletType INTEGER,
pdug5OutletCurrentRating INTEGER,
pdug5OutletCurrent INTEGER,
pdug5OutletActivePowerThStatus INTEGER,
pdug5OutletActivePowerThLowerWarning INTEGER,
pdug5OutletActivePowerThLowerCritical INTEGER,
pdug5OutletActivePowerThUpperWarning INTEGER,
pdug5OutletActivePowerThUpperCritical INTEGER,
pdug5OutletCurrentPercentLoad INTEGER,
pdug5OutletVA INTEGER,
pdug5OutletWatts INTEGER,
pdug5OutletWh INTEGER,
pdug5OutletWhTimer DisplayString,
pdug5OutletPowerFactor INTEGER,
pdug5OutletVAR INTEGER,
pdug5OutletBranch INTEGER,
pdug5OutletActivePowerThResetThld INTEGER,
pdug5OutletActivePowerThChangeDelay INTEGER,
pdug5OutletActivePowerThCtrl INTEGER
}
pdug5OutletIndex OBJECT-TYPE
SYNTAX INTEGER (0..48)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for each outlet, value from 1 to the number of outlets per PDU."
::= { pdug5OutletEntry 1 }
pdug5OutletName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A descriptive name for the outlet."
::= { pdug5OutletEntry 2 }
pdug5OutletType OBJECT-TYPE
SYNTAX INTEGER {
iecC13 (1),
iecC19 (2),
i5-20R (3),
uk (10),
french (11),
schuko (12),
nema515 (20),
nema51520 (21),
nema520 (22),
nemaL520 (23),
nemaL530 (24),
nema615 (25),
nema620 (26),
nemaL620 (27),
nemaL630 (28),
nemaL715 (29),
rf203p277 (30)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of this outlet - C13, C19 ,5-20R."
::= { pdug5OutletEntry 3 }
pdug5OutletCurrentRating OBJECT-TYPE
SYNTAX INTEGER -- Units 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Rated current capacity of this outlet. Units are 0.01 amps. A negative
value indicates that the hardware current capacity is unknown."
::= { pdug5OutletEntry 4 }
pdug5OutletCurrent OBJECT-TYPE
SYNTAX INTEGER -- Units 0.01 A
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A outlet current measurement value. Units are 0.01 amps."
::= { pdug5OutletEntry 5 }
pdug5OutletActivePowerThStatus OBJECT-TYPE
SYNTAX INTEGER {
good (1),
lowWarning (2),
lowCritical (3),
highWarning (4),
highCritical (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of the measured outlet active power relative to the configured thresholds."
::= { pdug5OutletEntry 6 }
pdug5OutletActivePowerThLowerWarning OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower warning threshold. Units are Watts(W). A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 7 }
pdug5OutletActivePowerThLowerCritical OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lower critical threshold. Units are Watts(W). A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 8 }
pdug5OutletActivePowerThUpperWarning OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper warning threshold. Units are Watts(W). A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 9 }
pdug5OutletActivePowerThUpperCritical OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Upper critical threshold. Units are Watts(W). A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 10 }
pdug5OutletCurrentPercentLoad OBJECT-TYPE
SYNTAX INTEGER -- unit in percentage
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available."
::= { pdug5OutletEntry 11 }
pdug5OutletVA OBJECT-TYPE
SYNTAX INTEGER -- units in VA
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A outlet VA value. Units are VA. A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 12 }
pdug5OutletWatts OBJECT-TYPE
SYNTAX INTEGER -- units in Watt
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A outlet Watts value. Units are Watts. A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 13 }
pdug5OutletWh OBJECT-TYPE
SYNTAX INTEGER -- Units in Watt-Hour
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A Watt-Hour value for each outlet. Units are WH.
This object is writable so that it can be reset to 0. When it is
written to, the pdug5OutletWhTimer will be reset updated as well
A negative value indicates that this object is not available."
::= { pdug5OutletEntry 14 }
pdug5OutletWhTimer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..22)) -- display Date and Time
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Timestamp (date and time) of outlet Watt-hours was last reset."
::= { pdug5OutletEntry 15 }
pdug5OutletPowerFactor OBJECT-TYPE
SYNTAX INTEGER -- units are in 0.01
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An outlet PF value. Units are in thousandths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned
as 92. A negative value indicates that this object is not available."
::= { pdug5OutletEntry 16 }
pdug5OutletVAR OBJECT-TYPE
SYNTAX INTEGER -- Units in VAR
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available."
::= { pdug5OutletEntry 17 }
pdug5OutletBranch OBJECT-TYPE
SYNTAX INTEGER -- Units in VAR
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The branch number outlet located."
::= { pdug5OutletEntry 18 }
-- 1.3.6.1.4.1.19536.10.1.5.1.1.19
pdug5OutletActivePowerThResetThld OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Outlet Active Power alarm reset threshold. Units are Watts(W).
A negative value indicates that this object is not available."
::= { pdug5OutletEntry 19 }
-- 1.3.6.1.4.1.19536.10.1.5.1.1.20
pdug5OutletActivePowerThChangeDelay OBJECT-TYPE
SYNTAX INTEGER (-1..10000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Outlet Active Power generates alarm every outlet alarm times.
A negative value indicates that this object is not available."
::= { pdug5OutletEntry 20 }
-- 1.3.6.1.4.1.19536.10.1.5.1.1.21
pdug5OutletActivePowerThCtrl OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Outlet Active Power alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable
bit 1: up warning alarm control bit, 0 - enable, 1 - disable
bit 2: low warning alarm control bit, 0 - enable, 1 - disable
bit 3: low critical alarm control bit, 0 - enable, 1 - disable"
DEFVAL { 0 }
::= { pdug5OutletEntry 21 }
-- ====================== PDU Outlet Control=====================
pdug5OutletControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF pdug5OutletControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex)
and Number of outlets per PDU (pdug5OutletIndex)."
::= { pdug5Outlet 2 }
pdug5OutletControlEntry OBJECT-TYPE
SYNTAX pdug5OutletControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The Outlet table entry containing the type, voltage, current etc."
INDEX { pdug5IdentIndex, pdug5OutletIndex }
::= { pdug5OutletControlTable 1 }
pdug5OutletControlEntry ::= SEQUENCE {
pdug5OutletControlStatus INTEGER,
pdug5OutletControlOffCmd INTEGER,
pdug5OutletControlOnCmd INTEGER,
pdug5OutletControlRebootCmd INTEGER,
pdug5OutletControlPowerOnState INTEGER,
pdug5OutletControlSequenceDelay INTEGER,
pdug5OutletControlRebootOffTime INTEGER,
pdug5OutletControlSwitchable INTEGER,
pdug5OutletControlShutoffDelay INTEGER,
pdug5OutletControlCommand INTEGER
}
pdug5OutletControlStatus OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
pendingOff (3),
pendingOn (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"current state of a control outlet."
::= { pdug5OutletControlEntry 1 }
pdug5OutletControlOffCmd OBJECT-TYPE
SYNTAX INTEGER (-1..99999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the current downcount in
seconds of a pending command."
::= { pdug5OutletControlEntry 2 }
pdug5OutletControlOnCmd OBJECT-TYPE
SYNTAX INTEGER (-1..99999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet On command
When read, returns -1 if no command is pending, or the current downcount in
seconds of a pending command."
::= { pdug5OutletControlEntry 3 }
pdug5OutletControlRebootCmd OBJECT-TYPE
SYNTAX INTEGER (-1..99999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for
outletControlRebootOffTime seconds, and then turn back On.
For outlets that are Off prior to the Reboot command, they will turn On after
a delay of outletControlRebootOffTime seconds from when the command is issued.
0-n : Time in seconds until the Reboot command is issued
-1 : Cancel a pending outlet Reboot command
When read, returns -1 if no command is pending, or the current downcount in
seconds of a pending command."
::= { pdug5OutletControlEntry 4 }
pdug5OutletControlPowerOnState OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lastState (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Determines the outlet state when power is applied to the unit.
1 : not restart at device startup
2 : should sequence back ON in line with outletControlSequenceTime
3 : should take the state the outlet had when power was lost.
If the state was ON, should sequence back ON in line with outletControlSequenceTime."
::= { pdug5OutletControlEntry 5 }
pdug5OutletControlSequenceDelay OBJECT-TYPE
SYNTAX INTEGER (-1..7200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to exclude this outlet from Global Sequence On commands."
::= { pdug5OutletControlEntry 6 }
pdug5OutletControlRebootOffTime OBJECT-TYPE
SYNTAX INTEGER (-1..7200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command."
::= { pdug5OutletControlEntry 7 }
pdug5OutletControlSwitchable OBJECT-TYPE
SYNTAX INTEGER {
switchable (1),
notSwitchable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled."
::= { pdug5OutletControlEntry 8 }
pdug5OutletControlShutoffDelay OBJECT-TYPE
SYNTAX INTEGER (-1..7200)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then write it to the command pdug5OutletControlOffCmd."
::= { pdug5OutletControlEntry 9 }
pdug5OutletControlCommand OBJECT-TYPE
SYNTAX INTEGER {
immediateOff (1),
immediateOn (2),
delayedOff (3),
delayedOn (4),
immediateReboot (5),
delayedReboot (6),
outletUnknown (7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (2)
value will be returned. If the outlet is off,
the immediateOff (1) value will be returned.
If the state of the outlet cannot be determined, the
outletUnknown (7) value will be returned. If the
outletUnknown condition should occur, all devices
powered by the PDU should be shut down. The PDU's
power should then be cycled to clear this condition.
Setting this variable to immediateOn (2) will immediately
turn the outlet on. Setting this variable to
immediateOff (1) will immediately turn the outlet off.
Setting this variable to immediateReboot (5)
will cause the Switched PDU to perform an immediateOff
command, wait the pdug5OutletControlRebootOffTime
OID time, and then perform an immediateOn command.
Setting this variable to delayedOn (4) will turn the
outlet on after the pdug5OutletControlSequenceDelay
OID time has elapsed. Setting this variable to
delayedOff (3) will turn the outlet off after the
pdug5OutletControlShutoffDelay OID time has elapsed.
Setting this variable to delayedReboot (6) will cause
the Switched PDU to perform a delayedOff command, wait
the pdug5OutletControlRebootOffTime OID time, and
then perform a delayedOn command."
::= { pdug5OutletControlEntry 10 }
-- ====================================================================================
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5Traps OBJECT IDENTIFIER ::= { pdug5 6 }
-- PDU identification group
-- OID= .1.3.6.1.4.1.19536.10.1.6
trapCritical NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address}
STATUS current
DESCRIPTION
"A critical alarm has occurred."
::= {pdug5Traps 1}
trapWarning NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address }
STATUS current
DESCRIPTION
"A warning alarm has occurred."
::= {pdug5Traps 2}
trapInformation NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address }
STATUS current
DESCRIPTION
"An informational alarm has occurred."
::= {pdug5Traps 3}
trapCleared NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address }
STATUS current
DESCRIPTION
"An alarm has cleared."
::= {pdug5Traps 4}
trapTest NOTIFICATION-TYPE
OBJECTS {
trapCode,
trapDescription,
sysDescr,
pdug5IPv4Address }
STATUS current
DESCRIPTION
"Test trap sent to a trap receiver to check proper reception of traps"
::= {pdug5Traps 5}
-- ====================================================================================
-- g5 OBJECT IDENTIFIER ::= { panduit 10}
-- pdug5 OBJECT IDENTIFIER ::= { g5 1}
-- pdug5TrapInfo OBJECT IDENTIFIER ::= { pdug5 7 }
-- PDU identification group
-- OID= .1.3.6.1.4.1.19536.10.1.7
pdug5TrapInfoEntry OBJECT IDENTIFIER ::= { pdug5TrapInfo 1 }
trapCode OBJECT-TYPE
SYNTAX INTEGER
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A number identifying the event for the trap that was sent."
::= { pdug5TrapInfoEntry 1 }
trapDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A string identifying the event for that last trap that was sent."
::= { pdug5TrapInfoEntry 2 }
END