TRIPPLITE-12X DEFINITIONS ::= BEGIN
IMPORTS
TRAP-TYPE
FROM RFC-1215
DisplayString,
TruthValue,
TimeStamp,
TimeInterval,
DateAndTime,
AutonomousType,
VariablePointer,
RowStatus
FROM SNMPv2-TC
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Gauge32,
Integer32,
IpAddress
FROM SNMPv2-SMI
PositiveInteger,
NonNegativeInteger
FROM UPS-MIB
tripplite
FROM TRIPPLITE;
tlPowerAlert MODULE-IDENTITY
LAST-UPDATED "201702281600Z"
ORGANIZATION "Tripp Lite"
CONTACT-INFO
"Software Engineering
Tripp Lite
1111 W. 35th St.
Chicago, IL 60609"
DESCRIPTION
"This MIB module defines MIB objects which provide mechanisms for
remote management capabilities of Tripplite PowerAlert and related
software."
REVISION "201702281600Z"
"Corrected spelling errors"
REVISION "201507290000Z"
DESCRIPTION
"Removed obsolete legacy PowerAlert 11 sections"
REVISION "201410170930Z"
DESCRIPTION
"Added tlUpsAggregatePowerFactor"
REVISION "201409181000Z"
DESCRIPTION
"Added additional tlUpsInputSource... elements"
REVISION "201408060830Z"
DESCRIPTION
"Added additional elements to tlUpsOutputCircuitTable"
REVISION "201405080830Z"
DESCRIPTION
"Added tlUpsInputSourceSelect"
REVISION "201404091000Z"
DESCRIPTION
"Added missing well known alarms"
REVISION "201310301300Z"
DESCRIPTION
"Consolidated and Released for PAL v12.06.006x"
::= { tripplite 90 }
--------------------------------------------------------------------------
-- Enumerations
--------------------------------------------------------------------------
tlEnumerations OBJECT IDENTIFIER ::= { tripplite 2 }
tlOperatingSystems OBJECT IDENTIFIER ::= { tlEnumerations 1 }
hpux9 OBJECT IDENTIFIER ::= { tlOperatingSystems 1 }
sunos4 OBJECT IDENTIFIER ::= { tlOperatingSystems 2 }
solaris OBJECT IDENTIFIER ::= { tlOperatingSystems 3 }
osf OBJECT IDENTIFIER ::= { tlOperatingSystems 4 }
ultrix OBJECT IDENTIFIER ::= { tlOperatingSystems 5 }
hpux10 OBJECT IDENTIFIER ::= { tlOperatingSystems 6 }
netbsd1 OBJECT IDENTIFIER ::= { tlOperatingSystems 7 }
freebsd OBJECT IDENTIFIER ::= { tlOperatingSystems 8 }
irix OBJECT IDENTIFIER ::= { tlOperatingSystems 9 }
linux OBJECT IDENTIFIER ::= { tlOperatingSystems 10 }
bsdi OBJECT IDENTIFIER ::= { tlOperatingSystems 11 }
openbsd OBJECT IDENTIFIER ::= { tlOperatingSystems 12 }
win32 OBJECT IDENTIFIER ::= { tlOperatingSystems 13 }
hpux11 OBJECT IDENTIFIER ::= { tlOperatingSystems 14 }
win9x OBJECT IDENTIFIER ::= { tlOperatingSystems 50 }
winnt OBJECT IDENTIFIER ::= { tlOperatingSystems 51 }
solspark OBJECT IDENTIFIER ::= { tlOperatingSystems 52 }
solintel OBJECT IDENTIFIER ::= { tlOperatingSystems 53 }
aix OBJECT IDENTIFIER ::= { tlOperatingSystems 54 }
sco OBJECT IDENTIFIER ::= { tlOperatingSystems 55 }
osx OBJECT IDENTIFIER ::= { tlOperatingSystems 56 }
unknown OBJECT IDENTIFIER ::= { tlOperatingSystems 255 }
--------------------------------------------------------------------------
-- Power Alert System Settings
--------------------------------------------------------------------------
-- tlPowerAlert OBJECT IDENTIFIER ::= { tripplite 90 }
tlPASystem OBJECT IDENTIFIER ::= { tlPowerAlert 1 }
tlPAContacts OBJECT IDENTIFIER ::= { tlPASystem 1 }
tlPAEmailContacts OBJECT IDENTIFIER ::= { tlPAContacts 1 }
tlPANumberOfEmailContacts OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number email contacts currently defined."
::= { tlPAEmailContacts 1 }
tlPAEmailContactsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlPAEmailContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list email contact entries. The number of entries is
given by the value of tlPANumberOfEmailContacts."
::= { tlPAEmailContacts 2 }
tlPAEmailContactEntry OBJECT-TYPE
SYNTAX TlPAEmailContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing email contacts information."
INDEX { tlPAEmailContactIndex }
::= { tlPAEmailContactsTable 1 }
TlPAEmailContactEntry ::= SEQUENCE {
tlPAEmailContactIndex PositiveInteger,
tlPAEmailContactRowStatus RowStatus,
tlPAEmailContactName DisplayString,
tlPAEmailContactAddress DisplayString
}
tlPAEmailContactIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the index number of the email contact."
::= { tlPAEmailContactEntry 1 }
tlPAEmailContactRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The row status for the tlPAEmailContactTable row"
::= { tlPAEmailContactEntry 2 }
tlPAEmailContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the email contact."
::= { tlPAEmailContactEntry 3 }
tlPAEmailContactAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The address of the email contact."
::= { tlPAEmailContactEntry 4 }
tlPASnmpContacts OBJECT IDENTIFIER ::= { tlPAContacts 2 }
tlPANumberOfSnmpContacts OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number SNMP contacts currently defined."
::= { tlPASnmpContacts 1 }
tlPASnmpContactsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlPASnmpContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list SNMP contact entries. The number of entries is
given by the value of tlPANumberOfSnmpContacts."
::= { tlPASnmpContacts 2 }
tlPASnmpContactEntry OBJECT-TYPE
SYNTAX TlPASnmpContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing SNMP contacts information."
INDEX { tlPASnmpContactIndex }
::= { tlPASnmpContactsTable 1 }
TlPASnmpContactEntry ::= SEQUENCE {
tlPASnmpContactIndex PositiveInteger,
tlPASnmpContactRowStatus RowStatus,
tlPASnmpContactName DisplayString,
tlPASnmpContactIpAddress DisplayString,
tlPASnmpContactPort PositiveInteger,
tlPASnmpContactSnmpVersion INTEGER,
tlPASnmpContactSecurityName DisplayString,
tlPASnmpContactPrivPassword DisplayString,
tlPASnmpContactAuthPassword DisplayString
}
tlPASnmpContactIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the index number of this SNMP contact."
::= { tlPASnmpContactEntry 1 }
tlPASnmpContactRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The row status for the tlPASnmpContactTable row"
::= { tlPASnmpContactEntry 2 }
tlPASnmpContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the SNMP contact."
::= { tlPASnmpContactEntry 3 }
tlPASnmpContactIpAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The IP address of the SNMP contact."
::= { tlPASnmpContactEntry 4 }
tlPASnmpContactPort OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The port of the SNMP contact."
::= { tlPASnmpContactEntry 5 }
tlPASnmpContactSnmpVersion OBJECT-TYPE
SYNTAX INTEGER {
snmpv1(1),
snmpv2c(2),
snmpv3(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The SNMP contact version to use for sending traps."
::= { tlPASnmpContactEntry 6 }
tlPASnmpContactSecurityName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The SNMP contact security name."
::= { tlPASnmpContactEntry 7 }
tlPASnmpContactPrivPassword OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The SNMP contact priv password to use for sending V3 traps."
::= { tlPASnmpContactEntry 8 }
tlPASnmpContactAuthPassword OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The SNMP contact auth password to use for sending V3 traps."
::= { tlPASnmpContactEntry 9 }
--------------------------------------------------------------------------
-- UPS Device
--------------------------------------------------------------------------
tlUPS OBJECT IDENTIFIER ::= { tripplite 100 }
tlUpsObjects OBJECT IDENTIFIER ::= { tlUPS 1 }
tlUpsIdent OBJECT IDENTIFIER ::= { tlUpsObjects 1 }
tlUpsIdentUpsSoftwareChecksum OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A checksum for the UPS software."
::= { tlUpsIdent 1 }
tlUpsIdentSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number for the UPS."
::= { tlUpsIdent 2 }
tlUpsIdentID OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied ID for the UPS."
::= { tlUpsIdent 3 }
tlUpsSnmpCardSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number for the UPS."
::= { tlUpsIdent 4 }
tlUpsSelectedDeviceID OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device ID selected to be used for retrieving data for this mib.
As the snmp web card has only one device, this is read only for it"
::= { tlUpsIdent 5 }
tlUpsLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device location string."
::= { tlUpsIdent 6 }
tlUpsBattery OBJECT IDENTIFIER ::= { tlUpsObjects 2 }
tlUpsBatteryAge OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The age of the battery in years. This is equal to
the current date minus tlConfigBattReplDate."
::= { tlUpsBattery 1 }
tlUpsTemperatureF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the battery, in Farenheight degrees. This is
calculated from upsBatteryTemperature, which is in Celsius degrees."
::= { tlUpsBattery 2 }
tlUpsExternalBatteryAge OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The age of external battery in years. This is equal to
the current date minus tlConfigExternalBattReplDate."
::= { tlUpsBattery 3 }
tlUpsInput OBJECT IDENTIFIER ::= { tlUpsObjects 3 }
tlUpsInputNumVoltages OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input voltages. Phase to phase
or phase to neutral. This variable indicates the
number of rows in the input table."
::= { tlUpsInput 1 }
tlUpsInputVoltageTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlUpsInputVoltageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of voltage input table entries. The number of entries
is given by the value of tlUpsInputNumVoltages."
::= { tlUpsInput 2 }
tlUpsInputVoltageEntry OBJECT-TYPE
SYNTAX TlUpsInputVoltageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular input voltage."
INDEX { tlUpsInputVoltageIndex }
::= { tlUpsInputVoltageTable 1 }
TlUpsInputVoltageEntry ::= SEQUENCE {
tlUpsInputVoltageIndex PositiveInteger,
tlUpsInputVoltageType NonNegativeInteger,
tlUpsInputVoltage NonNegativeInteger
}
tlUpsInputVoltageIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input voltage identifier."
::= { tlUpsInputVoltageEntry 1 }
tlUpsInputVoltageType OBJECT-TYPE
SYNTAX INTEGER {
phaseToNeutral(0),
phaseToPhase(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Whether voltage measured is phase to
phase or phase to neutral."
::= { tlUpsInputVoltageEntry 2 }
tlUpsInputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage.
A value of 6553 indicates Unknown."
::= { tlUpsInputVoltageEntry 3 }
tlUpsInputSourceSelect OBJECT-TYPE
SYNTAX INTEGER {
inputSourceA(0),
inputSourceB(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The determination as to which of two AC input
lines is designated as the primary input source.
The other is designated as the secondary input
source. This value will always return inputSourceA(0)
for devices with a single input source. Setting
this value is supported only on selected models."
::= { tlUpsInput 3 }
tlUpsPhaseImbalance OBJECT-TYPE
SYNTAX INTEGER
UNITS "Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Percentage of imbalance of the 3 phases."
::= { tlUpsInput 4 }
tlUpsInputSourceAvailability OBJECT-TYPE
SYNTAX INTEGER {
none(0),
inputSourceA(1),
inputSourceB(2),
inputSourceAB(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The determination as to which of two AC input lines
are available. The agent will return either inputSourceA(1)
or inputSourceB(2) if only one line is available, or
inputSourceAB(3) if both lines are available. The agent
will never return none(0) since the device will be powered
off if neither line is available."
::= { tlUpsInput 5 }
tlUpsInputSourceInUse OBJECT-TYPE
SYNTAX INTEGER {
inputSourceA(0),
inputSourceB(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The determination as to which one of two AC input lines is
in use."
::= { tlUpsInput 6 }
tlUpsInputSourceTransitionCount OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the device transitions between primary and
secondary sources. Most devices are limied to 65533 transitions,
after which the value will not increment."
::= { tlUpsInput 7 }
tlUpsOutput OBJECT IDENTIFIER ::= { tlUpsObjects 4 }
tlUpsOutputPowerTotal OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power capacity of the device."
::= { tlUpsOutput 5 }
tlUpsOutputCircuits OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output circuits. This variable
indicates the number of rows in the output circuit table."
::= { tlUpsOutput 6 }
tlUpsOutputCircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlUpsOutputCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of output currents table entries. The number of entries
is given by the value of tlUpsOutputNumCircuits."
::= { tlUpsOutput 7 }
tlUpsOutputCircuitEntry OBJECT-TYPE
SYNTAX TlUpsOutputCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular output circuit."
INDEX { tlUpsOutputCircuitIndex }
::= { tlUpsOutputCircuitTable 1 }
TlUpsOutputCircuitEntry ::= SEQUENCE {
tlUpsOutputCircuitIndex PositiveInteger,
tlUpsOutputCircuitStatus INTEGER,
tlUpsOutputCircuitLoadCurrent NonNegativeInteger,
tlUpsOutputCircuitVoltage NonNegativeInteger,
tlUpsOutputCircuitPower NonNegativeInteger,
tlUpsOutputCircuitPowerFactor NonNegativeInteger
}
tlUpsOutputCircuitIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output circuit identifier."
::= { tlUpsOutputCircuitEntry 1 }
tlUpsOutputCircuitStatus OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Whether the breaker is open or closed."
::= { tlUpsOutputCircuitEntry 2 }
tlUpsOutputCircuitLoadCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Amperes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output current in
tenths of an amp. A value of 65534 indicates Unknown."
::= { tlUpsOutputCircuitEntry 3 }
tlUpsOutputCircuitVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present circuit voltage in
tenths of an volt."
::= { tlUpsOutputCircuitEntry 4 }
tlUpsOutputCircuitPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present power in watts.
tenths of an amp."
::= { tlUpsOutputCircuitEntry 5 }
tlUpsOutputCircuitPowerFactor OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor of all receptacles in a given circuit as
a %."
::= { tlUpsOutputCircuitEntry 6 }
tlUpsAggregatePowerFactor OBJECT-TYPE
SYNTAX PositiveInteger
UNITS "0.1 Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregrate power factor of all phases."
::= { tlUpsOutput 8 }
-- tlUpsBypass [unused] OBJECT IDENTIFIER ::= { tlUpsObjects 5 }
tlUpsAlarm OBJECT IDENTIFIER ::= { tlUpsObjects 6 }
tlUpsAlarmsPresent OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of active alarm conditions."
::= { tlUpsAlarm 1 }
tlUpsAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlUpsAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of alarm table entries."
::= { tlUpsAlarm 2 }
tlUpsAlarmEntry OBJECT-TYPE
SYNTAX TlUpsAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular alarm."
INDEX { tlUpsAlarmId }
::= { tlUpsAlarmTable 1 }
TlUpsAlarmEntry ::= SEQUENCE {
tlUpsAlarmId PositiveInteger,
tlUpsAlarmDescr AutonomousType,
tlUpsAlarmTime TimeStamp,
tlUpsAlarmDetail DisplayString,
tlUpsAlarmDeviceId PositiveInteger,
tlUpsAlarmDeviceName DisplayString,
tlUpsAlarmLocation DisplayString,
tlUpsAlarmGroup INTEGER,
tlUpsAlarmIp IpAddress,
tlUpsAlarmMac DisplayString
}
tlUpsAlarmId OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique identifier for an alarm condition."
::= { tlUpsAlarmEntry 1 }
tlUpsAlarmDescr OBJECT-TYPE
SYNTAX AutonomousType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A description of the alarm condition."
::= { tlUpsAlarmEntry 2 }
tlUpsAlarmTime OBJECT-TYPE
SYNTAX TimeStamp
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime when the alarm condition was detected."
::= { tlUpsAlarmEntry 3 }
tlUpsAlarmDetail OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A textual description of the alarm condition."
::= { tlUpsAlarmEntry 4 }
tlUpsAlarmDeviceId OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A numeric identifier for the device on which the alarm is active."
::= { tlUpsAlarmEntry 5 }
tlUpsAlarmDeviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A string identifier for the device on which the alarm is active."
::= { tlUpsAlarmEntry 6 }
tlUpsAlarmLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The location of the device on which the alarm is active."
::= { tlUpsAlarmEntry 7 }
tlUpsAlarmGroup OBJECT-TYPE
SYNTAX INTEGER {
critical(1),
warning(2),
info(3),
status(4),
offline(5),
custom(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The category/group of this alarm."
::= { tlUpsAlarmEntry 8 }
tlUpsAlarmIp OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The originating IP address associated with this alarm."
::= { tlUpsAlarmEntry 9 }
tlUpsAlarmMac OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The originating mac address associated with this alarm."
::= { tlUpsAlarmEntry 10 }
tlUpsWellKnownAlarms OBJECT IDENTIFIER ::= { tlUpsAlarm 3 }
tlUpsAlarmPrimaryPowerOutage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The primary power source is not present."
::= { tlUpsWellKnownAlarms 1 }
tlUpsAlarmSecondaryPowerOutage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The secondary power source is not present."
::= { tlUpsWellKnownAlarms 2 }
tlUpsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load level is above the designated threshold."
::= { tlUpsWellKnownAlarms 3 }
tlUpsAlarmOutputCurrentChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current changed from its last known value."
::= { tlUpsWellKnownAlarms 4 }
tlUpsAlarmBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more batteries have been determined to require
replacement."
::= { tlUpsWellKnownAlarms 5 }
tlUpsAlarmLoadOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load is off."
::= { tlUpsWellKnownAlarms 6 }
tlUpsAlarmUserDefined OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A user-defined event is in alarm."
::= { tlUpsWellKnownAlarms 7 }
tlUpsAlarmBatteryBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more batteries have been determined to require
replacement."
::= { tlUpsWellKnownAlarms 8 }
tlUpsAlarmOnBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS is drawing power from the batteries."
::= { tlUpsWellKnownAlarms 9 }
tlUpsAlarmLowBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The remaining battery run-time is less than or equal
to upsConfigLowBattTime."
::= { tlUpsWellKnownAlarms 10 }
tlUpsAlarmDepletedBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS will be unable to sustain the present load
when and if the utility power is lost."
::= { tlUpsWellKnownAlarms 11 }
tlUpsAlarmTempBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature is out of tolerance."
::= { tlUpsWellKnownAlarms 12 }
tlUpsAlarmInputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An input condition is out of tolerance."
::= { tlUpsWellKnownAlarms 13 }
tlUpsAlarmOutputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is
out of tolerance."
::= { tlUpsWellKnownAlarms 14 }
tlUpsAlarmOutputOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output load exceeds the UPS output capacity."
::= { tlUpsWellKnownAlarms 15 }
tlUpsAlarmOnBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is presently engaged on the UPS."
::= { tlUpsWellKnownAlarms 16 }
tlUpsAlarmBypassBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is out of tolerance."
::= { tlUpsWellKnownAlarms 17 }
tlUpsAlarmOutputOffAsRequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS has shutdown as requested, i.e., the output
is off."
::= { tlUpsWellKnownAlarms 18 }
tlUpsAlarmUpsOffAsRequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The entire UPS has shutdown as commanded."
::= { tlUpsWellKnownAlarms 19 }
tlUpsAlarmChargerFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An uncorrected problem has been detected within the
UPS charger subsystem."
::= { tlUpsWellKnownAlarms 20 }
tlUpsAlarmUpsOutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output of the UPS is in the off state."
::= { tlUpsWellKnownAlarms 21 }
tlUpsAlarmUpsSystemOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS system is in the off state."
::= { tlUpsWellKnownAlarms 22 }
tlUpsAlarmFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fans in the UPS has been
detected."
::= { tlUpsWellKnownAlarms 23 }
tlUpsAlarmFuseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fuses has been detected."
::= { tlUpsWellKnownAlarms 24 }
tlUpsAlarmGeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the UPS has been detected."
::= { tlUpsWellKnownAlarms 25 }
tlUpsAlarmDiagnosticTestFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The result of the last diagnostic test indicates a
failure."
::= { tlUpsWellKnownAlarms 26 }
tlUpsAlarmCommunicationsLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem has been encountered in the communications
between the agent and the UPS."
::= { tlUpsWellKnownAlarms 27 }
tlUpsAlarmAwaitingPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS output is off and the UPS is awaiting the
return of input power."
::= { tlUpsWellKnownAlarms 28 }
tlUpsAlarmShutdownPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A upsShutdownAfterDelay countdown is underway."
::= { tlUpsWellKnownAlarms 29 }
tlUpsAlarmShutdownImminent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown."
::= { tlUpsWellKnownAlarms 30 }
tlUpsAlarmTestInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the alarm table, if
desired, via a OBJECT-IDENTITY macro in the MIB
document specific to that implementation and are
outside the scope of this OBJECT-IDENTITY."
::= { tlUpsWellKnownAlarms 31 }
tlUpsAlarmCircuitBreaker1Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #1 is open."
::= { tlUpsWellKnownAlarms 32 }
tlUpsAlarmCircuitBreaker2Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #2 is open."
::= { tlUpsWellKnownAlarms 33 }
tlUpsAlarmCircuitBreaker3Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #3 is open."
::= { tlUpsWellKnownAlarms 34 }
tlUpsAlarmCircuitBreaker4Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #4 is open."
::= { tlUpsWellKnownAlarms 35 }
tlUpsAlarmCircuitBreaker5Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #5 is open."
::= { tlUpsWellKnownAlarms 36 }
tlUpsAlarmCircuitBreaker6Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #6 is open."
::= { tlUpsWellKnownAlarms 37 }
tlUpsAlarmCircuitBreaker7Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #7 is open."
::= { tlUpsWellKnownAlarms 38 }
tlUpsAlarmCircuitBreaker8Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breakers #8 is open."
::= { tlUpsWellKnownAlarms 39 }
tlUpsAlarmCurrent1AboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on line 1 exceeds load limits."
::= { tlUpsWellKnownAlarms 40 }
tlUpsAlarmCurrent2AboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on line 2 exceeds load limits."
::= { tlUpsWellKnownAlarms 41 }
tlUpsAlarmCurrent3AboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on line 3 exceeds load limits."
::= { tlUpsWellKnownAlarms 42 }
tlUpsAlarmRuntimeBelowWarningLevel OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery seconds remaining is below warning level."
::= { tlUpsWellKnownAlarms 43 }
tlUpsAlarmBusStartVoltageLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter start up bus voltage is too low."
::= { tlUpsWellKnownAlarms 44 }
tlUpsAlarmBusOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is too high."
::= { tlUpsWellKnownAlarms 45 }
tlUpsAlarmBusUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is too low."
::= { tlUpsWellKnownAlarms 46 }
tlUpsAlarmBusVoltageUnbalanced OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is not balanced."
::= { tlUpsWellKnownAlarms 47 }
tlUpsAlarmInverterSoftStartBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage cannot reach desired voltage within a
specified duration."
::= { tlUpsWellKnownAlarms 48 }
tlUpsAlarmInverterOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter voltage is too high."
::= { tlUpsWellKnownAlarms 49 }
tlUpsAlarmInverterUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter voltage is too low."
::= { tlUpsWellKnownAlarms 50 }
tlUpsAlarmInverterCircuitBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter output is shorted."
::= { tlUpsWellKnownAlarms 51 }
tlUpsAlarmBatteryOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery voltage is too high."
::= { tlUpsWellKnownAlarms 52 }
tlUpsAlarmBatteryUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery voltage is too low."
::= { tlUpsWellKnownAlarms 53 }
tlUpsAlarmSiteWiringFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The utility input wiring is faulty."
::= { tlUpsWellKnownAlarms 54 }
tlUpsAlarmOverTemperatureProtection OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The over temperature protection is activated."
::= { tlUpsWellKnownAlarms 55 }
tlUpsAlarmOverCharged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS is over charged."
::= { tlUpsWellKnownAlarms 56 }
tlUpsAlarmEPOActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The EPO is currently activate."
::= { tlUpsWellKnownAlarms 57 }
tlUpsAlarmBypassFrequencyBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass frequency is out of tolerance."
::= { tlUpsWellKnownAlarms 58 }
tlUpsAlarmExternalSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more external smart batteries have been determined to require
replacement."
::= { tlUpsWellKnownAlarms 59 }
tlUpsAlarmExternalNonSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more external non-smart batteries have been determined to require
replacement."
::= { tlUpsWellKnownAlarms 60 }
tlUpsAlarmSmartBatteryCommLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communications with the smart batteries was lost."
::= { tlUpsWellKnownAlarms 61 }
tlUpsAlarmSourceAOutage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input power source A is not present."
::= { tlUpsWellKnownAlarms 62 }
tlUpsAlarmSourceBOutage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input power source B is not present."
::= { tlUpsWellKnownAlarms 63 }
tlUpsAlarmWatchdogReset OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The internal watchdog triggered a reset of the device."
::= { tlUpsWellKnownAlarms 64 }
tlUpsAlarmDevName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The name of the device, tlDevName, corresponding to the device that is
associated with this alarm."
::= { tlUpsAlarm 7 }
tlUpsAlarmDevLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The location of the device, tlDevLocation, corresponding to the device
that is associated with this alarm."
::= { tlUpsAlarm 8 }
tlUpsAlarmCategory OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The category, tlDevEvtCategory, of this alarm."
::= { tlUpsAlarm 9 }
tlUpsTest OBJECT IDENTIFIER ::= { tlUpsObjects 7 }
tlUpsTestDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The date of the last self-test run on the ups, in the
format YYYYMMDD."
::= { tlUpsTest 1 }
tlUpsTestResultsDetail OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Result of the last self-test run on the ups."
::= { tlUpsTest 2 }
tlUpsControl OBJECT IDENTIFIER ::= { tlUpsObjects 8 }
tlUpsWatchdogSupported OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not this UPS supports a watchdog reboot."
::= { tlUpsControl 1 }
tlUpsWatchdogSecsBeforeReboot OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum number of seconds that can expire between polls that
the engine makes to the UPS for data. If this time runs out, then
the UPS will cycle its outputs. Set this to zero to turns disable
this feature."
::= { tlUpsControl 2 }
tlUpsWellKnownControls OBJECT IDENTIFIER ::= { tlUpsControl 3 }
tlUpsControlSelfTest OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate Self Test"
::= { tlUpsWellKnownControls 1 }
tlUpsControlRamp OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate Ramp"
::= { tlUpsWellKnownControls 2 }
tlUpsControlShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate Shed"
::= { tlUpsWellKnownControls 3 }
tlUpsControlUpsOn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn UPS on"
::= { tlUpsWellKnownControls 4 }
tlUpsControlUpsOff OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn UPS off"
::= { tlUpsWellKnownControls 5 }
tlUpsConfig OBJECT IDENTIFIER ::= { tlUpsObjects 9 }
tlUpsConfigBattReplDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The date on which the battery was last replaced, in the format
YYYYMMDD."
::= { tlUpsConfig 1 }
-- Deprecated, interface no longer supported.
--
-- tlUpsConfigTftpGetAddr OBJECT-TYPE
-- SYNTAX IpAddress
-- MAX-ACCESS read-write
-- STATUS current
-- DESCRIPTION
-- "The IP address of the TFTP server you wish to acquire a config ini file from, non persistent, 0.0.0.0 when empty"
-- ::= { tlUpsConfig 2 }
--
-- tlUpsConfigTftpGetAcction OBJECT-TYPE
-- SYNTAX INTEGER {
-- get(1),
-- getting(2),
-- idle(3) }
-- MAX-ACCESS read-write
-- STATUS current
-- DESCRIPTION
-- "setting this entry to get(1) will start a down load from the specified address, during the download this entry
-- will read getting(2), when finished, the card will reboot to the new ini supplied parms. At all other times this
-- entry will read idle(3)"
-- ::= { tlUpsConfig 3 }
tlUpsConfigDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
english(0),
metric(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects English or Metric display for all readings. This selection may not
be available on all devices. Further, some devices may support this selection,
but not via a software selector. In this latter case, selections must be
performed on the device itself."
::= { tlUpsConfig 4 }
tlUpsConfigExternalBattReplDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The date on which the external battery was last replaced, in the format
YYYYMMDD."
::= { tlUpsConfig 5 }
tlUpsOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 10 }
tlUpsOutletNumOutlets OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of available Outlets in this device."
::= { tlUpsOutlet 1 }
tlUpsOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlUpsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of all device Outlets for all devices."
::= { tlUpsOutlet 2 }
tlUpsOutletEntry OBJECT-TYPE
SYNTAX TlUpsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing Outlet information applicable to a particular
device managed by this agent."
INDEX {
tlUpsOutletIndex }
::= { tlUpsOutletTable 1 }
TlUpsOutletEntry ::= SEQUENCE {
tlUpsOutletIndex PositiveInteger,
tlUpsOutletState INTEGER,
tlUpsOutletType Integer32,
tlUpsOutletControl INTEGER,
tlUpsOutletName DisplayString,
tlUpsOutletRampAction INTEGER,
tlUpsOutletRampDataType INTEGER,
tlUpsOutletRampData Integer32,
tlUpsOutletShedAction INTEGER,
tlUpsOutletShedDataType INTEGER,
tlUpsOutletShedData Integer32,
tlUpsOutletGroupNdx Integer32,
tlUpsOutletCurrent PositiveInteger,
tlUpsOutletPower PositiveInteger }
tlUpsOutletIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the index number of this Outlet for the device
indicated by tlDeviceIndex."
::= { tlUpsOutletEntry 1 }
tlUpsOutletState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the Outlet."
::= { tlUpsOutletEntry 2 }
tlUpsOutletType OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a bit field that indicates the type of this Outlet.
When 0, the outlet is not controllable and has none of the
other features indicated in the bit map. When non-zero,
the features present for this outlet can be interpreted with the
definition.
Bit Display
0 Reserved, may be 1 or 0
1 Controllable
2
3
4
5
6
7
8
9
10
11
12
13
14
15
"
::= { tlUpsOutletEntry 3 }
tlUpsOutletControl OBJECT-TYPE
SYNTAX INTEGER {
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Controls the state of the Outlet."
::= { tlUpsOutletEntry 4 }
tlUpsOutletName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the device."
::= { tlUpsOutletEntry 5 }
tlUpsOutletRampAction OBJECT-TYPE
SYNTAX INTEGER {
remainOff(0),
turnOnAfterDelay(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The ramp action to take on the Outlet."
::= { tlUpsOutletEntry 6 }
tlUpsOutletRampDataType OBJECT-TYPE
SYNTAX INTEGER {
delayInSeconds(0)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The type of data associated with ramp action."
::= { tlUpsOutletEntry 7 }
tlUpsOutletRampData OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The data value associated with type of ramp data."
::= { tlUpsOutletEntry 8 }
tlUpsOutletShedAction OBJECT-TYPE
SYNTAX INTEGER {
remainOn(0),
turnOffAfterDelay(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The shed action to take on the Outlet."
::= { tlUpsOutletEntry 9 }
tlUpsOutletShedDataType OBJECT-TYPE
SYNTAX INTEGER {
delayInSeconds(0)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The type of data associated with shed action."
::= { tlUpsOutletEntry 10 }
tlUpsOutletShedData OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The data value associated with type of shed data."
::= { tlUpsOutletEntry 11 }
tlUpsOutletGroupNdx OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"tlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped."
::= { tlUpsOutletEntry 12 }
tlUpsOutletCurrent OBJECT-TYPE
SYNTAX PositiveInteger
UNITS "0.1 RMS Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of this outlet's current, represented as 0.1A."
::= { tlUpsOutletEntry 13 }
tlUpsOutletPower OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of this outlet's power in watts."
::= { tlUpsOutletEntry 14 }
tlUpsOutletGroup OBJECT IDENTIFIER ::= { tlUpsObjects 11 }
tlUpsOutletNumOutletGroups OBJECT-TYPE
SYNTAX NonNegativeInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of available Outlet Groups in this device."
::= { tlUpsOutletGroup 1 }
tlUpsOutletGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlUpsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of device outlet group entries. The number of entries is
given by the value of tlUpsOutletNumOutletGroups."
::= { tlUpsOutletGroup 2 }
tlUpsOutletGroupEntry OBJECT-TYPE
SYNTAX TlUpsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing outlet group information applicable
to a particular device managed by this agent"
INDEX { tlUpsOutletGroupIndex }
::= { tlUpsOutletGroupTable 1 }
TlUpsOutletGroupEntry ::= SEQUENCE {
tlUpsOutletGroupIndex PositiveInteger,
tlUpsOutletGroupRowStatus RowStatus,
tlUpsOutletGroupName DisplayString,
tlUpsOutletGroupDesc DisplayString,
tlUpsOutletGroupState INTEGER,
tlUpsOutletGroupControl INTEGER }
tlUpsOutletGroupIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the index number of this load group for the device."
::= { tlUpsOutletGroupEntry 1 }
tlUpsOutletGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlUpsOutletGroupTable"
::= { tlUpsOutletGroupEntry 2 }
tlUpsOutletGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this outlet group."
::= { tlUpsOutletGroupEntry 3 }
tlUpsOutletGroupDesc OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A description for this outlet group."
::= { tlUpsOutletGroupEntry 4 }
tlUpsOutletGroupState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2),
mixed(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet group."
::= { tlUpsOutletGroupEntry 5 }
tlUpsOutletGroupControl OBJECT-TYPE
SYNTAX INTEGER {
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Controls the state of every outlet associated with the group."
::= { tlUpsOutletGroupEntry 6 }
tlUpsMainOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 12 }
tlUpsMainOutletState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2),
mixed(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the main output of the device."
::= { tlUpsMainOutlet 1 }
tlUpsMainOutletControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates if this device has controllable outlets"
::= { tlUpsMainOutlet 2 }
tlUpsMainOutletControl OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Controls the state of the main outlet of the device."
::= { tlUpsMainOutlet 3 }
tlUpsEnvironment OBJECT IDENTIFIER ::= { tlUpsObjects 13 }
tlUpsTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature. The measurement returned will either be in
units of Celsius (C) or Fahrenheit (F) depending upon whether Metric
or English was selected for the reading by tlUpsConfigDisplayUnits."
::= { tlUpsEnvironment 1 }
---------------------------------------------------------------
-- UPS traps
---------------------------------------------------------------
tlUpsTraps OBJECT IDENTIFIER ::= { tlUPS 2 }
tlUpsTrapAlarmEntryAddedV1 TRAP-TYPE
ENTERPRISE tlUpsTraps
VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
DESCRIPTION
"This trap is sent each time an alarm is inserted into
to the alarm table."
--#SUMMARY "UPS Alarm: %s - %s."
--#ARGUMENTS {6, 2}
--#SEVERITY WARNING
::= 3
tlUpsTrapAlarmEntryAdded NOTIFICATION-TYPE
OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
STATUS current
DESCRIPTION
"This trap is sent each time an alarm is inserted into
to the alarm table."
--#SUMMARY "UPS Alarm: %s - %s."
--#ARGUMENTS {6, 2}
--#SEVERITY WARNING
::= { tlUpsTraps 3 }
tlUpsTrapAlarmEntryRemovedV1 TRAP-TYPE
ENTERPRISE tlUpsTraps
VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
DESCRIPTION
"This trap is sent each time an alarm is removed from
the alarm table."
--#SUMMARY "UPS Alarm: %s - %s."
--#ARGUMENTS {6, 2}
--#SEVERITY WARNING
::= 4
tlUpsTrapAlarmEntryRemoved NOTIFICATION-TYPE
OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
STATUS current
DESCRIPTION
"This trap is sent each time an alarm is removed from
the alarm table."
--#SUMMARY "UPS Alarm: %s - %s."
--#ARGUMENTS {6, 2}
--#SEVERITY WARNING
::= { tlUpsTraps 4 }
--------------------------------------------------------------------------
--------------------------------------------------------------------------
-- begin new traps
--------------------------------------------------------------------------
--------------------------------------------------------------------------
tlUpsTrapSystemStartup NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used to inform another entity of an engine's startup. The varbinds that follow are:
OBJ1 = tlEngineType
Obj1Value = The type of engine providing this data
OBJ2 = tlEngineSoftwareVersion
Obj2Value = The current version of the engine
OBJ3 = tlEngineMACAddr
Obj3Value = The MAC address of the engine
OBJ4 = tlUpsSnmpCardSerialNum
Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
--- if this trap is extended, place all static OIDs above this mark. all objects below
--- the number of devices (tlNumDevices) is explicit as per device for enumeration by
--- the target receiver
OBJ5 = tlNumDevices
Obj5Value = The number of devices attached
--- The following objects will be replicated per each device:
OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
Obj6Value = The device's manufacturer
OBJ7 = The OID for an entry of tlDevModel, indexed by device
Obj7Value = The device's model name
OBJ8 = The OID for an entry of tlDevName, indexed by device
Obj8Value = The device's display name
OBJ9 = The OID for an entry of tlDevLocation, indexed by device
Obj9Value = The device's location
OBJ10 = The OID for an entry of tlDevRegion, indexed by device
Obj10Value= The device's region
OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
Obj11Value= The device's protocol (display string format)
"
::= { tlUpsTraps 5 }
tlUpsTrapSystemShutdown NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used to inform another entity of an engine's startup. The varbinds that follow are:
OBJ1 = tlEngineType
Obj1Value = The type of engine providing this data
OBJ2 = tlEngineSoftwareVersion
Obj2Value = The current version of the engine
OBJ3 = tlEngineMACAddr
Obj3Value = The MAC address of the engine
OBJ4 = tlUpsSnmpCardSerialNum
Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
--- if this trap is extended, place all static OIDs above this mark. all objects below
--- the number of devices (tlNumDevices) is explicit as per device for enumeration by
--- the target receiver
OBJ5 = tlNumDevices
Obj5Value = The number of devices attached
--- The following objects will be replicated per each device:
OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
Obj6Value = The device's manufacturer
OBJ7 = The OID for an entry of tlDevModel, indexed by device
Obj7Value = The device's model name
OBJ8 = The OID for an entry of tlDevName, indexed by device
Obj8Value = The device's display name
OBJ9 = The OID for an entry of tlDevLocation, indexed by device
Obj9Value = The device's location
OBJ10 = The OID for an entry of tlDevRegion, indexed by device
Obj10Value= The device's region
OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
Obj11Value= The device's protocol (display string format)
"
::= { tlUpsTraps 6 }
--------------------------------------------------------------------------
--------------------------------------------------------------------------
--- end new traps
--------------------------------------------------------------------------
--------------------------------------------------------------------------
--------------------------------------------------------------------------
-- EnviroSense Device
--------------------------------------------------------------------------
tlEnviroSense OBJECT IDENTIFIER ::= { tripplite 101 }
tlEnvEnvironment OBJECT IDENTIFIER ::= { tlEnviroSense 1 }
tlEnvTemperatureData OBJECT IDENTIFIER ::= { tlEnvEnvironment 1 }
tlEnvTemperatureC OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature (C)."
::= { tlEnvTemperatureData 1 }
tlEnvTemperatureF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature (F)."
::= { tlEnvTemperatureData 2 }
tlEnvTemperatureLowLimit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower alarm limit for ambient temperature (F)."
::= { tlEnvTemperatureData 3 }
tlEnvTemperatureHighLimit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper alarm limit for ambient temperature (F)."
::= { tlEnvTemperatureData 4 }
tlEnvTemperatureInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not temperature is in alarm."
::= { tlEnvTemperatureData 5 }
tlEnvHumidityData OBJECT IDENTIFIER ::= { tlEnvEnvironment 2 }
tlEnvHumidity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient humidity (%)."
::= { tlEnvHumidityData 1 }
tlEnvHumidityLowLimit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower alarm limit for ambient humidity (%)."
::= { tlEnvHumidityData 2 }
tlEnvHumidityHighLimit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper alarm limit for ambient humidity (%)."
::= { tlEnvHumidityData 3 }
tlEnvHumidityInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not humidity is in alarm."
::= { tlEnvHumidityData 4 }
tlEnvContacts OBJECT IDENTIFIER ::= { tlEnviroSense 2 }
tlEnvContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlEnvContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table of contacts."
::= { tlEnvContacts 1 }
tlEnvContactEntry OBJECT-TYPE
SYNTAX TlEnvContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular contact."
INDEX {
tlEnvContactIndex }
::= { tlEnvContactTable 1 }
TlEnvContactEntry ::= SEQUENCE {
tlEnvContactIndex PositiveInteger,
tlEnvContactName DisplayString,
tlEnvContactStatus INTEGER,
tlEnvContactConfig INTEGER }
tlEnvContactIndex OBJECT-TYPE
SYNTAX PositiveInteger
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the contact."
::= { tlEnvContactEntry 1 }
tlEnvContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name or description of the contact."
::= { tlEnvContactEntry 2 }
tlEnvContactStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
alarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current status of the contact."
::= { tlEnvContactEntry 3 }
tlEnvContactConfig OBJECT-TYPE
SYNTAX INTEGER {
normallyOpen(0),
normallyClosed(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration of the contact."
::= { tlEnvContactEntry 4 }
--------------------------------------------------------------------------
-- KVM over IP Device
--------------------------------------------------------------------------
-- this is a 3rd party MIB structure located at { tripplite 102 }
--------------------------------------------------------------------------
-- SR Cooling Device
--------------------------------------------------------------------------
tlCooling OBJECT IDENTIFIER ::= { tripplite 103 }
tlCoolingEnvironment OBJECT IDENTIFIER ::= { tlCooling 1 }
tlCoolingIdent OBJECT IDENTIFIER ::= { tlCoolingEnvironment 1 }
tlCoolingModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model name for the AC Unit."
::= { tlCoolingIdent 1}
tlCoolingManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The manufacturer of the AC Unit."
::= { tlCoolingIdent 2 }
tlCoolingSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the AC unit."
::= { tlCoolingIdent 3 }
tlCoolingFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of the AC Unit."
::= { tlCoolingIdent 4 }
tlCoolingHostSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hardware version of the AC unit."
::= { tlCoolingIdent 5 }
tlCoolingName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user defined name for the AC Unit."
::= { tlCoolingIdent 6 }
tlCoolingLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user defined location of the AC Unit."
::= { tlCoolingIdent 7 }
tlCoolingStatus OBJECT IDENTIFIER ::= { tlCoolingEnvironment 2 }
tlCoolingCondOutletTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The condenser outlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 1 }
tlCoolingCondInletTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The condenser inlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 2 }
tlCoolingRefrigerantTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 3 }
tlCoolingEvapSurfaceTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The surface temperature of the evaporator in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 4}
tlCoolingSuctionPressure OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
::= { tlCoolingStatus 5}
tlCoolingDischargePressure OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
::= { tlCoolingStatus 6}
tlCoolingEvapFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
medLow(2),
med (3),
medHi (4),
hi (5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the evaporator fan."
::= { tlCoolingStatus 7}
tlCoolingCondFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
hi (2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the condenser fan."
::= { tlCoolingStatus 8}
tlCoolingCompFrequency OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operating frequency of the compressor in tenths of Arms."
::= { tlCoolingStatus 9}
tlCoolingEEVPercentage OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The opening percentage of the EEV."
::= { tlCoolingStatus 10}
tlCoolingUnitCurrent OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The the total current draw of the unit in tenths of Arms."
::= { tlCoolingStatus 11}
tlCoolingFanCurrent OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Thethe current draw of the Evaporator and Condenser fans in tents of Arms."
::= { tlCoolingStatus 12 }
tlCoolingCompCurrent OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operating current of the compressor in Arms."
::= { tlCoolingStatus 13}
tlCoolingReturnAirTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The return air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 14 }
tlCoolingSuctionTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the compressor suction line in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 15 }
tlCoolingSupplyAirTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The supply air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
::= { tlCoolingStatus 16 }
tlCoolingRunTimes OBJECT IDENTIFIER ::= { tlCoolingEnvironment 3 }
tlCoolingAirFilterRunHours OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total hours the air filter has been under operation."
::= { tlCoolingRunTimes 1 }
tlCoolingEvapFanRunDays OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the evaporator fan has been under operation."
::= { tlCoolingRunTimes 2 }
tlCoolingCondFanRunDays OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the condenser fan has been under operation."
::= { tlCoolingRunTimes 3 }
tlCoolingCompressorRunDays OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the compressor has been under operation."
::= { tlCoolingRunTimes 4 }
tlCoolingCondPumpRunDays OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the condensate pump has been under operation."
::= { tlCoolingRunTimes 5 }
tlCoolingAtomizerRunDays OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the atomizer has been under operation."
::= { tlCoolingRunTimes 6 }
tlCoolingConfig OBJECT IDENTIFIER ::= { tlCoolingEnvironment 4 }
tlCoolingOnOff OBJECT-TYPE
SYNTAX INTEGER {
turnOffUnit(0),
turnOnUnit(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Turn the unit off or on."
::= { tlCoolingConfig 1 }
tlCoolingSetPointTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The set point temperature the unit will control the temperature to in tenths of degrees in Celsius or Fahrenheit based upon tleCoolDisplayUnits."
::= { tlCoolingConfig 2 }
tlCoolingAutoStart OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Specified if the unit should start automatically on power up."
::= { tlCoolingConfig 3 }
tlCoolingFanSpeedOverride OBJECT-TYPE
SYNTAX INTEGER {
autoFanSpeed(0),
low(1),
medLow(2),
med(3),
medHi(4),
hi(5) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Speed of evaporator fan set by the user."
::= { tlCoolingConfig 4 }
tlCoolingControlType OBJECT-TYPE
SYNTAX INTEGER {
returnAirTemp(0),
remoteTemperature(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Which temperature to be used as a control point."
::= { tlCoolingConfig 5 }
tlCoolingCurrentRemoteTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The external remote temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlCoolingDisplayUnits"
::= { tlCoolingConfig 6 }
tlCoolingDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
metric(0),
english(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects English or Metric display for all readings."
::= { tlCoolingConfig 7 }
tlCoolingBeepOnKey OBJECT-TYPE
SYNTAX INTEGER {
noBeep(0),
beepOn(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates if the display sounds a beep when a key is pressed."
::= { tlCoolingConfig 8 }
tlCoolingOutputRelaySource OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
allAlarmsAndWarnings(1),
criticalAlarmsOnly(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The alarm level that causes the ouput relay to activate."
::= { tlCoolingConfig 9 }
tlCoolingOffOnLeak OBJECT-TYPE
SYNTAX INTEGER {
turnOff(0),
alarmOnly(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates if the unit should stop cooling when leak input is activated."
::= { tlCoolingConfig 10 }
tlCoolingOffOnInputContact OBJECT-TYPE
SYNTAX INTEGER {
turnOff(0),
alarmOnly(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates if the unit should stop cooling when input contact is activated."
::= { tlCoolingConfig 11 }
tlCoolingInputContactType OBJECT-TYPE
SYNTAX INTEGER {
ncRelay(0),
noRelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The input contact type."
::= { tlCoolingConfig 12 }
tlCoolingOutputRelayDefault OBJECT-TYPE
SYNTAX INTEGER {
nc(0),
no(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Type of contact to make when output relay is activated."
::= { tlCoolingConfig 13 }
tlCoolingAirFilterInterval OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of weeks before the air filter needs to be changed."
::= { tlCoolingConfig 14 }
tlCoolingWaterLeakContactType OBJECT-TYPE
SYNTAX INTEGER {
noRelay(0),
ncRelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The input contact type."
::= { tlCoolingConfig 15 }
tlCoolingThresholds OBJECT IDENTIFIER ::= { tlCoolingEnvironment 5 }
tlCoolingMaxAirFilterRunHours OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum interval for air filter run hours before warning is annunciated."
::= { tlCoolingThresholds 1 }
tlCoolingEnableAirFilterAlarm OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
::= { tlCoolingThresholds 2 }
tlCoolingMaxSupplyTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed supply air temperature before firing an alarm."
::= { tlCoolingThresholds 3 }
tlCoolingMinSupplyTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum allowed supply air temperature allowed before firing an alarm."
::= { tlCoolingThresholds 4 }
tlCoolingTempDiffAlarm OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed air temperature deviation from set allowed before firing an alarm."
::= { tlCoolingThresholds 5 }
tlCoolingMaxReturnAirTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
::= { tlCoolingThresholds 6 }
tlCoolingAlarm OBJECT IDENTIFIER ::= { tlCooling 6 }
tlCoolingWellKnownAlarms OBJECT IDENTIFIER ::= { tlCoolingAlarm 3 }
tlCoolingSupplyAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply air sensor is in fault."
::= { tlCoolingWellKnownAlarms 1 }
tlCoolingReturnAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return air sensor is in fault."
::= { tlCoolingWellKnownAlarms 2 }
tlCoolingCondenserInletAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser inlet air sensor is in fault."
::= { tlCoolingWellKnownAlarms 3 }
tlCoolingCondenserOutletAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser outlet air sensor is in fault."
::= { tlCoolingWellKnownAlarms 4 }
tlCoolingSuctionTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction temperature sensor is in fault."
::= { tlCoolingWellKnownAlarms 5 }
tlCoolingEvaporatorTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator temperature sensor is in fault."
::= { tlCoolingWellKnownAlarms 6 }
tlCoolingAirFilterClogged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air filter is clogged."
::= { tlCoolingWellKnownAlarms 7 }
tlCoolingAirFilterRunHoursViolation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air filter run hours was violated."
::= { tlCoolingWellKnownAlarms 8 }
tlCoolingSuctionPressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure sensor is in fault."
::= { tlCoolingWellKnownAlarms 9 }
tlCoolingInverterCommunicationsFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter communications is in fault."
::= { tlCoolingWellKnownAlarms 10 }
tlCoolingRemoteShutdownViaInputContact OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A remote shutdown was triggerd by an input contact."
::= { tlCoolingWellKnownAlarms 11 }
tlCoolingCondensatePumpFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condensate pump is in fault."
::= { tlCoolingWellKnownAlarms 12 }
tlCoolingLowRefrigerantStartupFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The low refrigerant startup is in fault."
::= { tlCoolingWellKnownAlarms 13 }
tlCoolingCondenserFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser fan is in fault."
::= { tlCoolingWellKnownAlarms 14 }
tlCoolingCondenserFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser has failed."
::= { tlCoolingWellKnownAlarms 15 }
tlCoolingEvaporatorCoolingFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator cooling is in fault."
::= { tlCoolingWellKnownAlarms 16 }
tlCoolingReturnAirTempHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return air temperature is high."
::= { tlCoolingWellKnownAlarms 17 }
tlCoolingSupplyAirTempHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply air temperature is high."
::= { tlCoolingWellKnownAlarms 18 }
tlCoolingEvaporatorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator has failed."
::= { tlCoolingWellKnownAlarms 19 }
tlCoolingEvaporatorFreezeUp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator is frozen."
::= { tlCoolingWellKnownAlarms 20 }
tlCoolingDischargePressureHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure is high."
::= { tlCoolingWellKnownAlarms 21 }
tlCoolingPressureGaugeFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure gauge has failed."
::= { tlCoolingWellKnownAlarms 22 }
tlCoolingDischargePressurePersistentHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure is persistently high."
::= { tlCoolingWellKnownAlarms 23 }
tlCoolingSuctionPressureLowStartFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Cannot start due to low suction pressure."
::= { tlCoolingWellKnownAlarms 24 }
tlCoolingSuctionPressureLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure is low."
::= { tlCoolingWellKnownAlarms 25 }
tlCoolingSuctionPressurePersistentLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure is persistently low."
::= { tlCoolingWellKnownAlarms 26 }
tlCoolingStartupLinePressureImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The startup line pressure is in imbalance."
::= { tlCoolingWellKnownAlarms 27 }
tlCoolingCompressorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The compressor has failed."
::= { tlCoolingWellKnownAlarms 28 }
tlCoolingCurrentLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current is out of range."
::= { tlCoolingWellKnownAlarms 29 }
tlCoolingWaterLeak OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water is leaking."
::= { tlCoolingWellKnownAlarms 30 }
tlCoolingFanUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan is under current."
::= { tlCoolingWellKnownAlarms 31 }
tlCoolingFanOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan is over current."
::= { tlCoolingWellKnownAlarms 32 }
tlCoolingDischargePressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure sensor is in fault."
::= { tlCoolingWellKnownAlarms 33 }
tlCoolingWaterFull OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water is Full."
::= { tlCoolingWellKnownAlarms 34 }
tlCoolingAutoCoolingOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic cooling was activated to lower the temperature below the
remote set point."
::= { tlCoolingWellKnownAlarms 35 }
tlCoolingPowerButtonPressed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power button was pressed on the front panel."
::= { tlCoolingWellKnownAlarms 36 }
tlCoolingDisconnectedFromDevice OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The device communications is disconnected."
::= { tlCoolingWellKnownAlarms 37 }
--------------------------------------------------------------------------
-- SRCOOLNET Device
--------------------------------------------------------------------------
tlSrCoolNet OBJECT IDENTIFIER ::= { tripplite 104}
tlSrCoolNetData OBJECT IDENTIFIER ::= { tlSrCoolNet 1 }
tlSrCoolNetIdent OBJECT IDENTIFIER ::= { tlSrCoolNetData 1 }
tlSrCoolNetModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model name for the device attached to the SRCOOLNET."
::= { tlSrCoolNetIdent 1}
tlSrCoolNetManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The manufacturer of the AC Unit."
::= { tlSrCoolNetIdent 2 }
tlSrCoolNetSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the SRCOOLNET device."
::= { tlSrCoolNetIdent 3 }
tlSrCoolNetHostSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The software version of the SRCOOLNET device."
::= { tlSrCoolNetIdent 4 }
tlSrCoolNetName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user defined name for the AC Unit."
::= { tlSrCoolNetIdent 5 }
tlSrCoolNetLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user defined location of the AC Unit."
::= { tlSrCoolNetIdent 6 }
tlSrCoolNetStatus OBJECT IDENTIFIER ::= { tlSrCoolNetData 2 }
tlSrCoolNetMode OBJECT-TYPE
SYNTAX INTEGER {
off (0),
idle (1),
cooling (2),
unknown (3),
dehumidifying (4),
defrost (5),
notconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current mode of SRCOOLNET."
::= { tlSrCoolNetStatus 1}
tlSrCoolNetFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off (0),
low (1),
med (2),
hi (3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the fan."
::= { tlSrCoolNetStatus 2}
tlSrCoolNetReturnAirTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The return air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlSrCoolNetDisplayUnits."
::= { tlSrCoolNetStatus 3 }
tlSrCoolNetWaterFull OBJECT-TYPE
SYNTAX INTEGER {
waterNotFull(0),
waterFull(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the water reservoir is full or not full."
::= { tlSrCoolNetStatus 4 }
tlSrCoolNetCurrentRemoteTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The EnviroSense temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlSrCoolNetDisplayUnits.
Only available if EnviroSense is connected to SRCOOLNET."
::= { tlSrCoolNetStatus 5 }
tlSrCoolNetDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
metric(0),
english(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Selects English or Metric display for all readings. AC unit must be manually configured to match this setting."
::= { tlSrCoolNetStatus 6 }
tlSrCoolNetConfig OBJECT IDENTIFIER ::= { tlSrCoolNetData 3 }
tlSrCoolNetOnOff OBJECT-TYPE
SYNTAX INTEGER {
turnOffUnit(0),
turnOnUnit (1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Turn the unit off or on."
::= { tlSrCoolNetConfig 1 }
tlSrCoolSetMode OBJECT-TYPE
SYNTAX INTEGER {
cooling(0),
dehumidifying (1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set the operating mode of cooling unit. Unit must be ON to set mode."
::= { tlSrCoolNetConfig 2 }
tlSrCoolNetSetPointTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The local set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits."
::= { tlSrCoolNetConfig 3 }
tlSrCoolNetRemoteSetPointTemp OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The remote set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits.
Only available when EnviroSense is connected to SRCOOLNET."
::= { tlSrCoolNetConfig 4 }
tlSrCoolNetFanSpeedSetting OBJECT-TYPE
SYNTAX INTEGER {
auto(0),
low(1),
med(2),
high(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set the fan speed of the AC unit."
::= { tlSrCoolNetConfig 5 }
tlSrCoolNetRemoteSetpointEnable OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Use remote temperature setpoint for control point versus return air temp. Only available when EnviroSense is connected
to SRCOOLNET."
::= { tlSrCoolNetConfig 6 }
tlSrCoolNetFanAlwaysOn OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Leave fans on when not cooling. Only available when EnviroSense is connected to SRCOOLNET."
::= { tlSrCoolNetConfig 7 }
tlSrCoolNetAlarm OBJECT IDENTIFIER ::= { tlSrCoolNet 2 }
tlSrCoolNetWellKnownAlarms OBJECT IDENTIFIER ::= { tlSrCoolNetAlarm 1 }
tlSrCoolNetWaterFullAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water reservoir full."
::= { tlSrCoolNetWellKnownAlarms 1 }
--------------------------------------------------------------------------
-- Conformance definitions
--------------------------------------------------------------------------
tlConformance OBJECT IDENTIFIER ::= { tripplite 20 }
tlCompliances OBJECT IDENTIFIER ::= { tlConformance 1 }
tlGroups OBJECT IDENTIFIER ::= { tlConformance 2 }
tlSubsetGroups OBJECT IDENTIFIER ::= { tlGroups 1 }
tlBasicGroups OBJECT IDENTIFIER ::= { tlGroups 2 }
tlFullGroups OBJECT IDENTIFIER ::= { tlGroups 3 }
tlUpsFullGroups OBJECT IDENTIFIER ::= { tlFullGroups 100 }
tlUpsFullIdentGroup OBJECT-GROUP
OBJECTS {
tlUpsIdentUpsSoftwareChecksum,
tlUpsIdentSerialNum,
tlUpsIdentID,
tlUpsSelectedDeviceID }
STATUS current
DESCRIPTION
"The tlUpsFullIdentGroup defines objects which are common to the Ident
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 1 }
tlUpsFullBatteryGroup OBJECT-GROUP
OBJECTS {
tlUpsBatteryAge,
tlUpsTemperatureF }
STATUS current
DESCRIPTION
"The tlUpsFullBatteryGroup defines objects which are common to the Battery
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 2 }
tlUpsFullAlarmGroup OBJECT IDENTIFIER ::= { tlUpsFullGroups 6 }
tlUpsFullAlarmObjsGroup OBJECT-GROUP
OBJECTS {
tlUpsAlarmDevName,
tlUpsAlarmDevLocation,
tlUpsAlarmCategory }
STATUS current
DESCRIPTION
"The tlUpsFullAlarmObjsGroup defines objects which are common to
the Alarm group of fully compliant Tripplite UPS's"
::= { tlUpsFullAlarmGroup 1 }
--tlUpsFullAlarmsGroup NOTIFICATION-GROUP
-- NOTIFICATIONS { }
-- STATUS current
-- DESCRIPTION
-- "The tlUpsFullAlarmGroup defines notifications which are
-- common to the Alarm group of fully compliant Tripplite UPS's"
-- ::= { tlUpsFullAlarmGroup 2 }
tlUpsFullTestGroup OBJECT-GROUP
OBJECTS {
tlUpsTestDate,
tlUpsTestResultsDetail }
STATUS current
DESCRIPTION
"The tlUpsFullTestGroup defines objects which are common to the Test
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 7 }
tlUpsFullControlGroup OBJECT-GROUP
OBJECTS {
tlUpsWatchdogSupported,
tlUpsWatchdogSecsBeforeReboot }
STATUS current
DESCRIPTION
"The tlUpsFullControlGroup defines objects which are common to the Control
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 8 }
tlUpsFullConfigGroup OBJECT-GROUP
OBJECTS {
tlUpsConfigBattReplDate }
STATUS current
DESCRIPTION
"The tlUpsFullConfigGroup defines objects which are common to the Config
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 9 }
tlUpsFullOutletGroup OBJECT-GROUP
OBJECTS {
tlUpsOutletNumOutlets }
STATUS current
DESCRIPTION
"The tlUpsFullOutletGroup defines objects which are common to the Outlet
group of fully compliant Tripplite UPS's"
::= { tlUpsFullGroups 10 }
END