mibs/MIBS/riello/RIELLOMTS-MIB

593 lines
14 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
-- RPS S.p.A enterprise MIB definition
-- Copyright (c) RPS S.p.A.
-- Version: 1.0.1 by Michele Marcon
-- Date: 07.06.2017
-- Title: RIELLOMTS-MIB
-- MDU-MIB { iso org(3) dod(6) internet(1) private(4)
-- enterprises(1) riello(5491) }
-- ************************************************************************
-- ************************************************************************
RIELLOMTS-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString
FROM RFC1213-MIB
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215
rielloMIB
FROM RIELLO-MIB;
mtsMIB OBJECT IDENTIFIER ::= { rielloMIB 12 }
mtsIdent OBJECT IDENTIFIER ::= { mtsMIB 1 }
mtsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the mts manufacturer."
::= { mtsIdent 1 }
mtsIdentModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts Model designation."
::= { mtsIdent 2 }
mtsIdentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts Software version."
::= { mtsIdent 3 }
mtsIdentIOConfiguration OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts input/output configuration (1 for Mono/mono, 4 for Tri/tri)."
::= { mtsIdent 4 }
mtsIdentType OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts type (5 for ATS, 6 for STS)."
::= { mtsIdent 5 }
mtsIdentInputSockets OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of mts input sockets."
::= { mtsIdent 6 }
mtsIdentOutputSockets OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of mts output sockets."
::= { mtsIdent 7 }
mtsIdentNominalCurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts nominal current (A)."
::= { mtsIdent 8 }
mtsIdentNominalVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts nominal voltage (V)."
::= { mtsIdent 9 }
mtsIdentNominalFrequency OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The mts nominal frequency (0.1 Hz)."
::= { mtsIdent 10 }
mtsStatus OBJECT IDENTIFIER ::= { mtsMIB 2 }
mtsS1Frequency OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The frequency of source 1 (0.1 Hz)."
::= { mtsStatus 1 }
mtsS1VoltageL1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 1, line 1 (V)."
::= { mtsStatus 2 }
mtsS1VoltageL2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 1, line 2 (V)."
::= { mtsStatus 3 }
mtsS1VoltageL3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 1, line 3 (V)."
::= { mtsStatus 4 }
mtsS2Frequency OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The frequency of source 2 (0.1 Hz)."
::= { mtsStatus 5 }
mtsS2VoltageL1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 2, line 1 (V)."
::= { mtsStatus 6 }
mtsS2VoltageL2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 2, line 2 (V)."
::= { mtsStatus 7 }
mtsS2VoltageL3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of source 2, line 3 (V)."
::= { mtsStatus 8 }
mtsPhaseDifference OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Phase difference between sources (degrees)."
::= { mtsStatus 9 }
mtsLoadL1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load of line 1 (%)."
::= { mtsStatus 10 }
mtsLoadL2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load of line 2 (%)."
::= { mtsStatus 11 }
mtsLoadL3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load of line 3 (%)."
::= { mtsStatus 12 }
mtsOutputCurrentL1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load current of line 1 (0.1 A)."
::= { mtsStatus 13 }
mtsOutputCurrentL2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load current of line 2 (0.1 A)."
::= { mtsStatus 14 }
mtsOutputCurrentL3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load current of line 3 (0.1 A)."
::= { mtsStatus 15 }
mtsTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature (degrees C)."
::= { mtsStatus 16 }
mtsSoundOff OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= sound on, 0= sound off."
::= { mtsStatus 17 }
mtsTestInProgress OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= test in progress, 0= test not in progress."
::= { mtsStatus 18 }
mtsAuxPower2fail OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= fail, 0= not fail."
::= { mtsStatus 19 }
mtsAuxPower1fail OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= fail, 0= not fail."
::= { mtsStatus 20 }
mtsSynchrobad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= bad, 0= not bad."
::= { mtsStatus 21 }
mtsPreferredSource OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= S2, 0= S1."
::= { mtsStatus 22 }
mtsTransferhinibit OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= hinibit, 0= not hinibit."
::= { mtsStatus 23 }
mtsNonSynchInibit OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 24 }
mtsSourceS2bad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= bad, 0= not bad."
::= { mtsStatus 25 }
mtsSourceS1bad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= bad, 0= not bad."
::= { mtsStatus 26 }
mtsOnSourceS2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 27 }
mtsOnSourceS1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 28 }
mtsLocked OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= locked, 0= not locked."
::= { mtsStatus 29 }
mtsOutputSwitchOff OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 30 }
mtsS2Blackout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= blackout, 0= no blackout."
::= { mtsStatus 31 }
mtsS2PhaseseqNotok OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 32 }
mtsS2VoltOutoftolerance OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 33 }
mtsS1SCRAlternateLoss OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 34 }
mtsS1InputSWOff OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 35 }
mtsS1Frequencybad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= bad, 0= not bad."
::= { mtsStatus 36 }
mtsS1Balancebad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 37 }
mtsS1Blackout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 38 }
mtsS1PhaseseqNotok OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 39 }
mtsS1VoltOutoftolerance OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 40 }
mtsUserlogin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 41 }
mtsAlarmTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 42 }
mtsAlarmOverload OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 43 }
mtsGeneralFailure OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 44 }
mtsS2InputMCCBtrip OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 45 }
mtsS1InputMCCBtrip OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 46 }
mtsServicelogin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 47 }
mtsOutputSCRalternanceloss OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 48 }
mtsManBypassS2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 49 }
mtsManBypassS1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 50 }
mtsManTransferS2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 51 }
mtsManTransferS1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 52 }
mtsS2SCRalternanceloss OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 53 }
mtsS2InputSWoff OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 54 }
mtsS2Frequencybad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 55 }
mtsS2Balancebad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"1= yes, 0= no."
::= { mtsStatus 56 }
mtsTraps OBJECT IDENTIFIER ::= { mtsMIB 4 }
mtsNormal TRAP-TYPE
ENTERPRISE mtsTraps
DESCRIPTION "This trap is sent when STS is on normal status"
::= 1
mtsAnomaly TRAP-TYPE
ENTERPRISE mtsTraps
DESCRIPTION "This trap is sent when STS is has some anomaly and is resent every minute"
::= 2
mtsFault TRAP-TYPE
ENTERPRISE mtsTraps
DESCRIPTION "This trap is sent when STS is has some fault and is resent every minute"
::= 3
mtsLock TRAP-TYPE
ENTERPRISE mtsTraps
DESCRIPTION "This trap is sent when STS is locked and is resent every minute"
::= 4
mtsManualBypassEnabled TRAP-TYPE
ENTERPRISE mtsTraps
DESCRIPTION "This trap is sent when STS is on manual bypass and is resent every minute"
::= 5
END