--defines ROOMALERT12E-MIB for SNMP agent extension of Room Alert 12E
--Contents: Global Registration Module
-- Room Alert OIDs - Enterprise 20916
--Version: 3.3.0
--Date: 28 May 2021
--Developed By: AVTECH Software, Inc.
--
--Copyright (c) 2021 AVTECH Software, Inc.
--
ROOMALERT12E-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Counter, TimeTicks
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
products OBJECT IDENTIFIER ::= { avtech 1 }
roomalert12E OBJECT IDENTIFIER ::= { products 10 }
sensors OBJECT IDENTIFIER ::= { roomalert12E 1 }
lightTower OBJECT IDENTIFIER ::= { roomalert12E 2 }
internal-sen OBJECT IDENTIFIER ::= { sensors 1 }
digital-sen1 OBJECT IDENTIFIER ::= { sensors 2 }
digital-sen2 OBJECT IDENTIFIER ::= { sensors 3 }
digital-sen3 OBJECT IDENTIFIER ::= { sensors 4 }
switch1 OBJECT IDENTIFIER ::= { sensors 5 }
switch2 OBJECT IDENTIFIER ::= { sensors 6 }
switch3 OBJECT IDENTIFIER ::= { sensors 7 }
switch4 OBJECT IDENTIFIER ::= { sensors 8 }
analog OBJECT IDENTIFIER ::= { sensors 9 }
relay OBJECT IDENTIFIER ::= { sensors 10 }
traps OBJECT IDENTIFIER ::= { roomalert12E 3 }
-- Room Alert 12E MIB
-- Parameters
internal-sen-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "This value represents the current internal temperature in Celsius"
::= { internal-sen 1 }
internal-sen-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "This value represents the current internal temperature in Fahrenheit."
::= { internal-sen 2 }
internal-sen-3 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal sensor's label"
::= { internal-sen 3 }
analog-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The current status of the Room Alert 12E analog input (0-5VDC)."
::= { analog 1 }
analog-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The analog sensor's label."
::= { analog 2 }
analog-3 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The current status of the Room Alert 12E analog input (user-defined scale)."
::= { analog 3 }
relay-1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The current status of the Room Alert 12E relay output."
::= { relay 1 }
relay-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The relay output's label."
::= { relay 2 }
digital-sen1-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
::= { digital-sen1 1 }
digital-sen1-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
::= { digital-sen1 2 }
digital-sen1-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
::= { digital-sen1 3 }
digital-sen1-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
::= { digital-sen1 4 }
digital-sen1-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen1 5 }
digital-sen1-6 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
::= { digital-sen1 6 }
digital-sen1-7 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
::= { digital-sen1 7 }
digital-sen1-8 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The sensor's label"
::= { digital-sen1 8 }
digital-sen2-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
::= { digital-sen2 1 }
digital-sen2-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
::= { digital-sen2 2 }
digital-sen2-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
::= { digital-sen2 3 }
digital-sen2-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
::= { digital-sen2 4 }
digital-sen2-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen2 5 }
digital-sen2-6 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
::= { digital-sen2 6 }
digital-sen2-7 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
::= { digital-sen2 7 }
digital-sen2-8 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The sensor's label"
::= { digital-sen2 8 }
digital-sen3-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
::= { digital-sen3 1 }
digital-sen3-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
::= { digital-sen3 2 }
digital-sen3-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
::= { digital-sen3 3 }
digital-sen3-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
::= { digital-sen3 4 }
digital-sen3-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen3 5 }
digital-sen3-6 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
::= { digital-sen3 6 }
digital-sen3-7 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
::= { digital-sen3 7 }
digital-sen3-8 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The sensor's label"
::= { digital-sen3 8 }
switch-sen1-1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
::= { switch1 1 }
switch-sen1-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 1."
::= { switch1 2 }
switch-sen2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
::= { switch2 1 }
switch-sen2-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 2."
::= { switch2 2 }
switch-sen3 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
::= { switch3 1 }
switch-sen3-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 3."
::= { switch3 2 }
switch-sen4 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
::= { switch4 1 }
switch-sen4-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 4."
::= { switch4 2 }
alarmmessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Last Alarm Message"
::= { traps 1 }
-- Light Tower
lightTower-RE OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the red LED on the Light Tower."
::= { lightTower 1 }
lightTower-OR OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the orange LED on the Light Tower."
::= { lightTower 2 }
lightTower-GR OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the green LED on the Light Tower."
::= { lightTower 3 }
lightTower-WH OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the white LED on the Light Tower."
::= { lightTower 4 }
lightTower-BL OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the blue LED on the Light Tower."
::= { lightTower 5 }
lightTower-A1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the 1st audio alarm on the Light Tower."
::= { lightTower 6 }
lightTower-A2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the 2nd audio alarm on the Light Tower."
::= { lightTower 7 }
lightTower-RL OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "The status of the LTA's on-board relay output"
::= { lightTower 8 }
-- ROOMALERT12E TRAPS
tempalarm1-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm1 trap signifies that the current
temperature on external sensor 1 is outside the
defined high or low threshold."
::= 1
room-alert-12E-snmp-trap TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A room-alert-12E-snmp-trap indicates that an alarm
condition has occurred on the sensor inidcated
by the alarmMessage variable."
::= 2
tempalarm2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm2 trap signifies that the current
temperature on external sensor 2 is outside the
defined high or low threshold."
::= 3
tempclear2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A tempclear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 4
tempalarm3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm3 trap signifies that the current
temperature on external sensor 3 is outside the
defined high or low threshold."
::= 5
tempclear3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A tempclear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 6
humidityalarm1-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm1 trap signifies that the current
humidity on external sensor 1 is outside the
defined high or low threshold."
::= 7
humidityclear1-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined
high or low threshold."
::= 8
humidityalarm2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm2 trap signifies that the current
humidity on external sensor 2 is outside the
defined high or low threshold."
::= 9
humidityclear2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 10
humidityalarm3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm3 trap signifies that the current
humidity on external sensor 3 is outside the
defined high or low threshold."
::= 11
humidityclear3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 12
switchalarm1-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm1 trap signifies that switch sensor 1
is in an alarm state."
::= 13
switchclear1-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear1 trap signifies that the switch sensor 1
has returned to a normal state."
::= 14
switchalarm2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm2 trap signifies that switch sensor 2
is in an alarm state."
::= 15
switchclear2-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear2 trap signifies that the switch sensor 2
has returned to a normal state."
::= 16
switchalarm3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm3 trap signifies that switch sensor 3
is in an alarm state."
::= 17
switchclear3-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear3 trap signifies that the switch sensor 3
has returned to a normal state."
::= 18
switchalarm4-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm4 trap signifies that switch sensor 4
is in an alarm state."
::= 19
switchclear4-12E TRAP-TYPE
ENTERPRISE roomalert12E
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear4 trap signifies that the switch sensor 4
has returned to a normal state."
::= 20
END