5192 lines
146 KiB
Plaintext
5192 lines
146 KiB
Plaintext
|
ENLOGIC-PDU-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
||
|
enterprises, Integer32, Unsigned32, IpAddress FROM SNMPv2-SMI
|
||
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
||
|
TEXTUAL-CONVENTION, DisplayString, MacAddress, TruthValue FROM SNMPv2-TC
|
||
|
InetAddressType, InetAddress FROM INET-ADDRESS-MIB
|
||
|
sysContact, sysName, sysLocation FROM RFC1213-MIB;
|
||
|
|
||
|
enlogic MODULE-IDENTITY
|
||
|
|
||
|
LAST-UPDATED "201506180000Z" -- June 18, 2015
|
||
|
|
||
|
ORGANIZATION "Enlogic"
|
||
|
|
||
|
CONTACT-INFO ""
|
||
|
|
||
|
DESCRIPTION "This MIB describes the SNMP functions of the Enlogic PDU."
|
||
|
|
||
|
REVISION "201410280000Z" -- October 28, 2014
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add Smart Cabinet related MIB nodes.
|
||
|
"
|
||
|
|
||
|
REVISION "201406050000Z" -- June 5, 2014
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add new trap named espNetworkUp for ES PDU.
|
||
|
"
|
||
|
|
||
|
REVISION "201404300000Z" -- April 30, 2014
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Modify description of MIB node pduInputPhaseStatusCurrentState, pduInputPhaseStatusCurrent, pduInputPhaseStatusVoltage, pduInputPhaseStatusActivePower,
|
||
|
pduInputPhaseStatusApparentPower and pduInputPhaseStatusPowerFactor.
|
||
|
"
|
||
|
|
||
|
REVISION "201306050000Z" -- June 5, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Change node pduExternalSensorStatusAisle to be writable.
|
||
|
"
|
||
|
|
||
|
REVISION "201305310000Z" -- May 31, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add MIB node for daisy chain state.
|
||
|
"
|
||
|
|
||
|
REVISION "201303280000Z" -- March 28, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add one more attribute for all trap oids indicating pdu idx in case of daisy chain.
|
||
|
2. Add one more MIB node in order to reset network management card
|
||
|
"
|
||
|
|
||
|
REVISION "201303210000Z" -- March 21, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add MIB node for external sensor unique identifier.
|
||
|
2. Add MIB node for external sensor readings with higher Pricision.
|
||
|
"
|
||
|
|
||
|
REVISION "201301240000Z" -- January 24, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. change external sensor name doorContact to doorSwitch
|
||
|
"
|
||
|
|
||
|
REVISION "201301060000Z" -- January 6, 2013
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. change the enum value definition of external sensor threshold setting
|
||
|
2. Add a new node to enable/disable SSH connection
|
||
|
3. Add one more external sensor unit
|
||
|
"
|
||
|
|
||
|
REVISION "201212280000Z" -- December 28, 2012
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Add one more node to enable/disable sensor
|
||
|
"
|
||
|
|
||
|
REVISION "201209280000Z" -- September 28, 2012
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Added additional indexes.
|
||
|
|
||
|
"
|
||
|
REVISION "201209250000Z" -- September 25, 2012
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Changed descriptions for status readings.
|
||
|
|
||
|
"
|
||
|
REVISION "201209180000Z" -- September 18, 2012
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Changed descriptions for alarm thresholds.
|
||
|
2. Renamed pduOutletMeteredStatusEnergy to pduOutletMeteredStatusResettableEnergy.
|
||
|
3. Added pduUnitConfigOutletPeakPowerReset
|
||
|
|
||
|
"
|
||
|
REVISION "201209130000Z" -- September 13, 2012
|
||
|
|
||
|
DESCRIPTION "
|
||
|
1. Changed SYNTAX of pduUnitConfigUpperWarningThreshold SEQUENCE to Unsigned32
|
||
|
2. Changed SYNTAX of pduOutletSwitchedStateOnStartup to Integer32
|
||
|
3. Changed SYNTAX of pduServerPingEnabled to TruthValue
|
||
|
4. Added trapsInformationIndex to SEQUENCE of TrapsInformationEntry
|
||
|
|
||
|
"
|
||
|
::= { enterprises 38446 }
|
||
|
|
||
|
|
||
|
pdu OBJECT IDENTIFIER ::= { enlogic 1 }
|
||
|
pduNamePlate OBJECT IDENTIFIER ::= { pdu 1 }
|
||
|
pduUnit OBJECT IDENTIFIER ::= { pdu 2 }
|
||
|
pduInputPhase OBJECT IDENTIFIER ::= { pdu 3 }
|
||
|
pduCircuitBreaker OBJECT IDENTIFIER ::= { pdu 4 }
|
||
|
pduOutlet OBJECT IDENTIFIER ::= { pdu 5 }
|
||
|
pduExternalSensor OBJECT IDENTIFIER ::= { pdu 6 }
|
||
|
pduServerPing OBJECT IDENTIFIER ::= { pdu 7 }
|
||
|
pduSmartCabinet OBJECT IDENTIFIER ::= { pdu 8 }
|
||
|
pduTraps OBJECT IDENTIFIER ::= { pdu 9 }
|
||
|
|
||
|
-- Start pduNamePlate
|
||
|
|
||
|
pduNamePlateTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of PDUs"
|
||
|
::= { pduNamePlate 1 }
|
||
|
|
||
|
-- pduNamePlateTable
|
||
|
pduNamePlateTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU nameplate data"
|
||
|
::= { pduNamePlate 2 }
|
||
|
|
||
|
pduNamePlateEntry OBJECT-TYPE
|
||
|
SYNTAX PduNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize."
|
||
|
INDEX { pduNamePlateIndex }
|
||
|
::= { pduNamePlateTable 1 }
|
||
|
|
||
|
PduNamePlateEntry ::= SEQUENCE {
|
||
|
pduNamePlateIndex
|
||
|
Integer32,
|
||
|
pduNamePlateName
|
||
|
DisplayString,
|
||
|
pduNamePlateLocation
|
||
|
DisplayString,
|
||
|
pduNamePlateInetAddressType
|
||
|
InetAddressType,
|
||
|
pduNamePlateIPAddress
|
||
|
InetAddress,
|
||
|
pduNamePlateInetNetMask
|
||
|
InetAddress,
|
||
|
pduNamePlateInetGateway
|
||
|
InetAddress,
|
||
|
pduNamePlateMACAddress
|
||
|
MacAddress,
|
||
|
pduNamePlateUTCTimeOffset
|
||
|
DisplayString,
|
||
|
pduNamePlateModelNumber
|
||
|
DisplayString,
|
||
|
pduNamePlateSerialNumber
|
||
|
DisplayString,
|
||
|
pduNamePlateDateofManufacture
|
||
|
DisplayString,
|
||
|
pduNamePlateFirmwareVersion
|
||
|
DisplayString,
|
||
|
pduNamePlateFirmwareVersionTimeStamp
|
||
|
DisplayString,
|
||
|
pduNamePlateType
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduNamePlateIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU nameplate table entry"
|
||
|
::= { pduNamePlateEntry 1 }
|
||
|
|
||
|
pduNamePlateName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { pduNamePlateEntry 2 }
|
||
|
|
||
|
pduNamePlateLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the location of PDU"
|
||
|
::= { pduNamePlateEntry 3 }
|
||
|
|
||
|
pduNamePlateInetAddressType OBJECT-TYPE
|
||
|
SYNTAX InetAddressType
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of address format"
|
||
|
::= { pduNamePlateEntry 4 }
|
||
|
|
||
|
pduNamePlateIPAddress OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current IP address. A value of 0.0.0.0 indicates an error or an unset option"
|
||
|
::= { pduNamePlateEntry 5 }
|
||
|
|
||
|
pduNamePlateInetNetMask OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current netmask. A value of 0.0.0.0 indiates an error or an unset option"
|
||
|
::= { pduNamePlateEntry 6 }
|
||
|
|
||
|
pduNamePlateInetGateway OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current gateway. A value of 0.0.0.0 indicates an error or an unset option"
|
||
|
::= { pduNamePlateEntry 7 }
|
||
|
|
||
|
pduNamePlateMACAddress OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The assigned MAC address for the PDU"
|
||
|
::= { pduNamePlateEntry 8 }
|
||
|
|
||
|
pduNamePlateUTCTimeOffset OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The difference in hours and minutes from Coordinated Universal
|
||
|
Time(UTC) for the time used in a particular time zone"
|
||
|
::= { pduNamePlateEntry 9 }
|
||
|
|
||
|
pduNamePlateModelNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU model number"
|
||
|
::= { pduNamePlateEntry 10 }
|
||
|
|
||
|
pduNamePlateSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU serial number"
|
||
|
::= { pduNamePlateEntry 11 }
|
||
|
|
||
|
pduNamePlateDateofManufacture OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The date the PDU was manufactured in mm/dd/yyyy format"
|
||
|
::= { pduNamePlateEntry 12 }
|
||
|
|
||
|
pduNamePlateFirmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU firmware version"
|
||
|
::= { pduNamePlateEntry 13 }
|
||
|
|
||
|
pduNamePlateFirmwareVersionTimeStamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Timestamp of when the PDU firmware was last updated"
|
||
|
::= { pduNamePlateEntry 14 }
|
||
|
|
||
|
pduNamePlateType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
pdu (0),
|
||
|
inlineMeter (1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of Unit, PDU or Inline Meter"
|
||
|
::= { pduNamePlateEntry 15 }
|
||
|
|
||
|
|
||
|
-- Start pduUnit
|
||
|
|
||
|
pduUnitTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of units."
|
||
|
::= { pduUnit 1 }
|
||
|
|
||
|
pduUnitConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduUnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU configuration data"
|
||
|
::= { pduUnit 2 }
|
||
|
|
||
|
pduUnitConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduUnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize"
|
||
|
INDEX { pduUnitConfigIndex }
|
||
|
::= { pduUnitConfigTable 1 }
|
||
|
|
||
|
PduUnitConfigEntry ::= SEQUENCE {
|
||
|
pduUnitConfigIndex
|
||
|
Integer32,
|
||
|
pduUnitConfigName
|
||
|
DisplayString,
|
||
|
pduUnitConfigLocation
|
||
|
DisplayString,
|
||
|
pduUnitConfigDisplayOrientation
|
||
|
INTEGER,
|
||
|
pduUnitConfigColdstartDelay
|
||
|
Unsigned32,
|
||
|
pduUnitConfigGlobalOutletStateOnStartup
|
||
|
INTEGER,
|
||
|
pduUnitConfigLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduUnitConfigLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduUnitConfigUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduUnitConfigUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduUnitConfigAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduUnitConfigAlarmStateChangeDelay
|
||
|
Unsigned32,
|
||
|
pduUnitConfigEnabledThresholds
|
||
|
BITS,
|
||
|
pduUnitConfigPeakPowerReset
|
||
|
INTEGER,
|
||
|
pduUnitConfigEnergyReset
|
||
|
INTEGER,
|
||
|
pduUnitConfigOutletPeakPowerReset
|
||
|
INTEGER,
|
||
|
pduUnitConfigOutletEnergyReset
|
||
|
INTEGER,
|
||
|
pduUnitConfigUsb
|
||
|
INTEGER,
|
||
|
pduUnitConfigSsh
|
||
|
INTEGER,
|
||
|
pduUnitConfigResetNetworkManagementCard
|
||
|
INTEGER,
|
||
|
pduUnitConfigDaisyChainState
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduUnitConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Unit Config Entry"
|
||
|
::= { pduUnitConfigEntry 1 }
|
||
|
|
||
|
pduUnitConfigName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { pduUnitConfigEntry 2 }
|
||
|
|
||
|
pduUnitConfigLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the location of the PDU"
|
||
|
::= { pduUnitConfigEntry 3 }
|
||
|
|
||
|
pduUnitConfigDisplayOrientation OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
displayNormal (1),
|
||
|
displayReverse (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the intended physical orientation of the oLED display
|
||
|
displayNormal (1) indicates normal orientation.
|
||
|
displayReverse (2) indicates upside down orientation"
|
||
|
::= { pduUnitConfigEntry 4 }
|
||
|
|
||
|
pduUnitConfigColdstartDelay OBJECT-TYPE
|
||
|
SYNTAX Unsigned32 (0..3600)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of time, specified in seconds, between when power
|
||
|
is provided to the PDU and when the PDU start providing basic master
|
||
|
power to the outlets"
|
||
|
::= { pduUnitConfigEntry 5 }
|
||
|
|
||
|
pduUnitConfigGlobalOutletStateOnStartup OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off (0),
|
||
|
on (1),
|
||
|
lastKnownState (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The outlet state on device startup; applies to all outlets
|
||
|
unless overridden at the outlet level"
|
||
|
::= { pduUnitConfigEntry 6 }
|
||
|
|
||
|
pduUnitConfigLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical unit active power alarm threshold measured in Watts"
|
||
|
::= { pduUnitConfigEntry 7 }
|
||
|
|
||
|
pduUnitConfigLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts"
|
||
|
::= { pduUnitConfigEntry 8 }
|
||
|
|
||
|
pduUnitConfigUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical unit active power alarm threshold measured in Watts"
|
||
|
::= { pduUnitConfigEntry 9 }
|
||
|
|
||
|
pduUnitConfigUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts"
|
||
|
::= { pduUnitConfigEntry 10 }
|
||
|
|
||
|
pduUnitConfigAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for deassertions in Watts"
|
||
|
::= { pduUnitConfigEntry 11 }
|
||
|
|
||
|
pduUnitConfigAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported."
|
||
|
::= { pduUnitConfigEntry 12 }
|
||
|
|
||
|
pduUnitConfigEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which alarm thresholds are enabled"
|
||
|
::= { pduUnitConfigEntry 13 }
|
||
|
|
||
|
pduUnitConfigPeakPowerReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (1),
|
||
|
reset (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to reset (2) will cause the existing peak power value
|
||
|
to be replaced by the current load power value. Getting this OID will
|
||
|
do nothing and return the noOperation(1) value. "
|
||
|
::= { pduUnitConfigEntry 14 }
|
||
|
|
||
|
pduUnitConfigEnergyReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (1),
|
||
|
reset (2),
|
||
|
notSupported (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to reset (2) will cause the device energy meter value
|
||
|
to be reset to zero. Getting this OID in models that support this
|
||
|
feature will do nothing and return the noOperation(1) value. Models
|
||
|
that do not support this feature will respond to this OID with a
|
||
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
||
|
::= { pduUnitConfigEntry 15 }
|
||
|
|
||
|
pduUnitConfigOutletPeakPowerReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (1),
|
||
|
reset (2),
|
||
|
notSupported (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to reset (2) will cause the outlet peak power meter value
|
||
|
to be reset to zero. Getting this OID in models that support this
|
||
|
feature will do nothing and return the noOperation(1) value. Models
|
||
|
that do not support this feature will respond to this OID with a
|
||
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
||
|
::= { pduUnitConfigEntry 16 }
|
||
|
|
||
|
pduUnitConfigOutletEnergyReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (1),
|
||
|
reset (2),
|
||
|
notSupported (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to reset (2) will cause the outlet energy meter value
|
||
|
to be reset to zero. Getting this OID in models that support this
|
||
|
feature will do nothing and return the noOperation(1) value. Models
|
||
|
that do not support this feature will respond to this OID with a
|
||
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
||
|
::= { pduUnitConfigEntry 17 }
|
||
|
|
||
|
pduUnitConfigUsb OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off (0),
|
||
|
on (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port."
|
||
|
::= { pduUnitConfigEntry 18 }
|
||
|
|
||
|
pduUnitConfigSsh OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off (0),
|
||
|
on (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection."
|
||
|
::= { pduUnitConfigEntry 19 }
|
||
|
|
||
|
pduUnitConfigResetNetworkManagementCard OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (0),
|
||
|
reset (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC."
|
||
|
::= { pduUnitConfigEntry 20 }
|
||
|
|
||
|
pduUnitConfigDaisyChainState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
daisychain (0)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to daisychain(0) will enable daisychain mode."
|
||
|
::= { pduUnitConfigEntry 21 }
|
||
|
|
||
|
pduUnitPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduUnitPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU properties"
|
||
|
::= { pduUnit 3 }
|
||
|
|
||
|
pduUnitPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX PduUnitPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unit properties entry containing objects for a particular unit."
|
||
|
INDEX { pduUnitPropertiesIndex }
|
||
|
::= { pduUnitPropertiesTable 1 }
|
||
|
|
||
|
PduUnitPropertiesEntry ::= SEQUENCE {
|
||
|
pduUnitPropertiesIndex
|
||
|
Integer32,
|
||
|
pduUnitPropertiesName
|
||
|
DisplayString,
|
||
|
pduUnitPropertiesOutletCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesSwitchedOutletCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesMeteredOutletCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesInputPhaseCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesCircuitBreakerCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesMaxExternalSensorCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesConnExternalSensorCount
|
||
|
Integer32,
|
||
|
pduUnitPropertiesRatedVoltage
|
||
|
DisplayString,
|
||
|
pduUnitPropertiesRatedMaxCurrent
|
||
|
DisplayString,
|
||
|
pduUnitPropertiesRatedFrequency
|
||
|
DisplayString,
|
||
|
pduUnitPropertiesRatedPower
|
||
|
DisplayString,
|
||
|
pduUnitPropertiesOrientation
|
||
|
INTEGER,
|
||
|
pduUnitPropertiesOutletLayout
|
||
|
INTEGER,
|
||
|
pduUnitPropertiesDaisyChainMemberType
|
||
|
INTEGER,
|
||
|
pduUnitPropertiesServerCount
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduUnitPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU properties table entry"
|
||
|
::= { pduUnitPropertiesEntry 1 }
|
||
|
|
||
|
pduUnitPropertiesName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { pduUnitPropertiesEntry 2 }
|
||
|
|
||
|
pduUnitPropertiesOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of outlets on the PDU"
|
||
|
::= { pduUnitPropertiesEntry 3 }
|
||
|
|
||
|
pduUnitPropertiesSwitchedOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of switched outlets on the PDU"
|
||
|
::= { pduUnitPropertiesEntry 4 }
|
||
|
|
||
|
pduUnitPropertiesMeteredOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of metered outlets on the PDU"
|
||
|
::= { pduUnitPropertiesEntry 5 }
|
||
|
|
||
|
pduUnitPropertiesInputPhaseCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of phases on the PDU"
|
||
|
::= { pduUnitPropertiesEntry 6 }
|
||
|
|
||
|
pduUnitPropertiesCircuitBreakerCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of circuit breaker on the PDU"
|
||
|
::= { pduUnitPropertiesEntry 7 }
|
||
|
|
||
|
pduUnitPropertiesMaxExternalSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The maximum number of external sensors that can be connected to the PDU"
|
||
|
::= { pduUnitPropertiesEntry 8 }
|
||
|
|
||
|
pduUnitPropertiesConnExternalSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current number of external sensors connected to the PDU"
|
||
|
::= { pduUnitPropertiesEntry 9 }
|
||
|
|
||
|
pduUnitPropertiesRatedVoltage OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU voltage rating in Volts"
|
||
|
::= { pduUnitPropertiesEntry 10 }
|
||
|
|
||
|
pduUnitPropertiesRatedMaxCurrent OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU current rating in Amps"
|
||
|
::= { pduUnitPropertiesEntry 11 }
|
||
|
|
||
|
pduUnitPropertiesRatedFrequency OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU frequency rating in Hz"
|
||
|
::= { pduUnitPropertiesEntry 12 }
|
||
|
|
||
|
pduUnitPropertiesRatedPower OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU VA (VoltAmps) rating."
|
||
|
::= { pduUnitPropertiesEntry 13 }
|
||
|
|
||
|
pduUnitPropertiesOrientation OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
horizontal (1),
|
||
|
vertical (2)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU orientation "
|
||
|
::= { pduUnitPropertiesEntry 14 }
|
||
|
|
||
|
pduUnitPropertiesOutletLayout OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
seqPhaseToNuetral (1),
|
||
|
seqPhaseToPhase (2),
|
||
|
seqPhToNeu21PhToPh (3),
|
||
|
seqPhToPhGrouped (4),
|
||
|
seqPhToNGrouped (5),
|
||
|
seqPToN1516PToPGrouped (6),
|
||
|
seqPhToPh2xGrouped (7),
|
||
|
seqPhToN2xGrouped (8),
|
||
|
seqNotApplicable (9)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The outlet layout for the PDU. Getting this OID will return outlet layout for the device.
|
||
|
seqPhaseToNeutral(1) indicates outlet layout as follows:
|
||
|
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
|
||
|
seqPhaseToPhase(2) indicates outlet layout as follows:
|
||
|
1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
|
||
|
seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
|
||
|
1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
|
||
|
seqPhToPhGrouped(4) indicates outlet layout as follows:
|
||
|
This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1.
|
||
|
seqPhToNGrouped(5) indicates outlet layout as follows:
|
||
|
This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
|
||
|
seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
|
||
|
This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
|
||
|
Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
|
||
|
seqPhToPh2xGrouped(7) indicates outlet layout as follows:
|
||
|
This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
|
||
|
Group 4:2-3, Group 5:3-1, Group 6:3-1.
|
||
|
seqPhToN2xGrouped(8) indicates outlet layout as follows:
|
||
|
This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
|
||
|
Group 4:2-N, Group 5:3-N, Group 6:3-N.
|
||
|
seqNotApplicable(9):"
|
||
|
::= { pduUnitPropertiesEntry 15 }
|
||
|
|
||
|
pduUnitPropertiesDaisyChainMemberType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
standalone (1),
|
||
|
parent (2),
|
||
|
child (3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The daisy-chain member type"
|
||
|
::= { pduUnitPropertiesEntry 16 }
|
||
|
|
||
|
pduUnitPropertiesServerCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of servers"
|
||
|
::= { pduUnitPropertiesEntry 17 }
|
||
|
|
||
|
pduUnitStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduUnitStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU status information"
|
||
|
::= { pduUnit 4 }
|
||
|
|
||
|
pduUnitStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduUnitStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status information from the PDU being queried"
|
||
|
INDEX { pduUnitStatusIndex }
|
||
|
::= { pduUnitStatusTable 1 }
|
||
|
|
||
|
PduUnitStatusEntry ::= SEQUENCE {
|
||
|
pduUnitStatusIndex
|
||
|
Integer32,
|
||
|
pduUnitStatusName
|
||
|
DisplayString,
|
||
|
pduUnitStatusLoadState
|
||
|
INTEGER,
|
||
|
pduUnitStatusActivePower
|
||
|
Integer32,
|
||
|
pduUnitStatusApparentPower
|
||
|
Integer32,
|
||
|
pduUnitStatusPeakPower
|
||
|
Integer32,
|
||
|
pduUnitStatusPeakPowerTimestamp
|
||
|
DisplayString,
|
||
|
pduUnitStatusPeakPowerStartTime
|
||
|
DisplayString,
|
||
|
pduUnitStatusEnergy
|
||
|
Integer32,
|
||
|
pduUnitStatusResettableEnergy
|
||
|
Integer32,
|
||
|
pduUnitStatusEnergyStartTime
|
||
|
DisplayString,
|
||
|
pduUnitStatusOutletsEnergyStartTime
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
pduUnitStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU status table entry"
|
||
|
::= { pduUnitStatusEntry 1 }
|
||
|
|
||
|
pduUnitStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { pduUnitStatusEntry 2 }
|
||
|
|
||
|
pduUnitStatusLoadState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the present load status of the PDU based on Active Power."
|
||
|
::= { pduUnitStatusEntry 3 }
|
||
|
|
||
|
pduUnitStatusActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Watts(W),
|
||
|
of the PDU being queried."
|
||
|
::= { pduUnitStatusEntry 4 }
|
||
|
|
||
|
pduUnitStatusApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Volt-Amps(VA)
|
||
|
of the PDU load being queried."
|
||
|
::= { pduUnitStatusEntry 5 }
|
||
|
|
||
|
pduUnitStatusPeakPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns peak power consumption, in Watts(W),
|
||
|
of the PDU being queried."
|
||
|
::= { pduUnitStatusEntry 6 }
|
||
|
|
||
|
pduUnitStatusPeakPowerTimestamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time that peak power consumption occurred"
|
||
|
::= { pduUnitStatusEntry 7 }
|
||
|
|
||
|
pduUnitStatusPeakPowerStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of the last device peak power reset"
|
||
|
::= { pduUnitStatusEntry 8 }
|
||
|
|
||
|
pduUnitStatusEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime."
|
||
|
::= { pduUnitStatusEntry 9 }
|
||
|
|
||
|
pduUnitStatusResettableEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user resettable energy meter measuring PDU energy consumption
|
||
|
in tenths of kilowatt-hours(kWh)."
|
||
|
::= { pduUnitStatusEntry 10 }
|
||
|
|
||
|
pduUnitStatusEnergyStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of the last device energy meter reset"
|
||
|
::= { pduUnitStatusEntry 11 }
|
||
|
|
||
|
pduUnitStatusOutletsEnergyStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of the last outlets energy meter reset"
|
||
|
::= { pduUnitStatusEntry 12 }
|
||
|
|
||
|
-- Start pduInputPhase
|
||
|
pduInputPhaseTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of PDU Input Phases "
|
||
|
::= { pduInputPhase 1 }
|
||
|
|
||
|
pduInputPhaseConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduInputPhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Input Phase configuration data"
|
||
|
::= { pduInputPhase 2 }
|
||
|
|
||
|
pduInputPhaseConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduInputPhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An input phase entry containing objects for a particular input phase."
|
||
|
INDEX { pduUnitConfigIndex, pduInputPhaseConfigIndex }
|
||
|
::= { pduInputPhaseConfigTable 1 }
|
||
|
|
||
|
PduInputPhaseConfigEntry ::= SEQUENCE {
|
||
|
pduInputPhaseConfigIndex
|
||
|
Integer32,
|
||
|
pduInputPhaseConfigCount
|
||
|
Integer32,
|
||
|
pduInputPhaseConfigOverloadRestriction
|
||
|
INTEGER,
|
||
|
pduInputPhaseConfigCurrentLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigCurrentLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigCurrentUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigCurrentUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigVoltageLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigVoltageLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigVoltageUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigVoltageUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigCurrentAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigCurrentAlarmStateChangeDelay
|
||
|
Integer32,
|
||
|
pduInputPhaseConfigCurrentEnabledThresholds
|
||
|
BITS,
|
||
|
pduInputPhaseConfigVoltageAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduInputPhaseConfigVoltageAlarmStateChangeDelay
|
||
|
Integer32,
|
||
|
pduInputPhaseConfigVoltageEnabledThresholds
|
||
|
BITS
|
||
|
}
|
||
|
|
||
|
pduInputPhaseConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Input Phase configuration table entry"
|
||
|
::= { pduInputPhaseConfigEntry 1 }
|
||
|
|
||
|
pduInputPhaseConfigCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of Input Phases"
|
||
|
::= { pduInputPhaseConfigEntry 2 }
|
||
|
|
||
|
pduInputPhaseConfigOverloadRestriction OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
alwaysAllowTurnOn (1),
|
||
|
restrictOnUpperWarning (2),
|
||
|
restrictOnUpperCritical (3),
|
||
|
notSupported (4)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID controls the behavior of a Switched PDU Input Phase when an
|
||
|
overload condition is possible and additional outlets are requested
|
||
|
to be turned on. Setting this OID to alwaysAllowTurnON (1) will always
|
||
|
allow the outlets on the corresponding Input Phase to turn on. Setting
|
||
|
this OID to restrictOnUpperWarning (2) will not allow outlets on the
|
||
|
corresponding Input Phase to turn on if the
|
||
|
pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting
|
||
|
this OID to restrictOnUpperCritical (3) will not allow outlets on
|
||
|
the corresponding Input Phase to turn on if the
|
||
|
pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models
|
||
|
that do not support this feature will respond to this OID with a
|
||
|
value of notSupported (4). Attempts to set this OID in these
|
||
|
models will fail. "
|
||
|
::= { pduInputPhaseConfigEntry 3 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical input phase current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduInputPhaseConfigEntry 4 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduInputPhaseConfigEntry 5 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical input phase current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduInputPhaseConfigEntry 6 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduInputPhaseConfigEntry 7 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical input phase voltage alarm threshold in Volts(V)."
|
||
|
::= { pduInputPhaseConfigEntry 8 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V)."
|
||
|
::= { pduInputPhaseConfigEntry 9 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical input phase voltage alarm threshold in Volts(V)."
|
||
|
::= { pduInputPhaseConfigEntry 10 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V)."
|
||
|
::= { pduInputPhaseConfigEntry 11 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for current alarm deassertions in hundredths of Amps(A)."
|
||
|
::= { pduInputPhaseConfigEntry 12 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a current state is asserted. If the
|
||
|
value is zero, then the state is asserted as soon as it is
|
||
|
detected; if it is non-zero, say n, then the assertion condition
|
||
|
must exist for n+1 consecutive samples before the corresponding
|
||
|
assertion event is reported. "
|
||
|
::= { pduInputPhaseConfigEntry 13 }
|
||
|
|
||
|
pduInputPhaseConfigCurrentEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which current alarm thresholds are enabled."
|
||
|
::= { pduInputPhaseConfigEntry 14 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for voltage alarm deassertions in Volts(V)."
|
||
|
::= { pduInputPhaseConfigEntry 15 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a voltage state is asserted. If the
|
||
|
value is zero, then the state is asserted as soon as it is
|
||
|
detected; if it is non-zero, say n, then the assertion condition
|
||
|
must exist for n+1 consecutive samples before the corresponding
|
||
|
assertion event is reported. "
|
||
|
::= { pduInputPhaseConfigEntry 16 }
|
||
|
|
||
|
pduInputPhaseConfigVoltageEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which voltage alarm thresholds are enabled."
|
||
|
::= { pduInputPhaseConfigEntry 17 }
|
||
|
|
||
|
pduInputPhasePropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduInputPhasePropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Input Phase properties"
|
||
|
::= { pduInputPhase 3 }
|
||
|
|
||
|
pduInputPhasePropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX PduInputPhasePropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An input phase properties entry containing objects for a particular input phase."
|
||
|
INDEX { pduUnitPropertiesIndex, pduInputPhasePropertiesIndex }
|
||
|
::= { pduInputPhasePropertiesTable 1 }
|
||
|
|
||
|
PduInputPhasePropertiesEntry ::= SEQUENCE {
|
||
|
pduInputPhasePropertiesIndex
|
||
|
Integer32,
|
||
|
pduInputPhasePropertiesCount
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduInputPhasePropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Input Phase status entry"
|
||
|
::= { pduInputPhasePropertiesEntry 1 }
|
||
|
|
||
|
pduInputPhasePropertiesCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Input Phase ID"
|
||
|
::= { pduInputPhasePropertiesEntry 2 }
|
||
|
|
||
|
pduInputPhaseStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduInputPhaseStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Input Phase status data"
|
||
|
::= { pduInputPhase 4 }
|
||
|
|
||
|
pduInputPhaseStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduInputPhaseStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An input phase status entry containing objects for a particular input phase."
|
||
|
INDEX { pduUnitStatusIndex, pduInputPhaseStatusIndex }
|
||
|
::= { pduInputPhaseStatusTable 1 }
|
||
|
|
||
|
PduInputPhaseStatusEntry ::= SEQUENCE {
|
||
|
pduInputPhaseStatusIndex
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusCount
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusCurrentState
|
||
|
INTEGER,
|
||
|
pduInputPhaseStatusVoltageState
|
||
|
INTEGER,
|
||
|
pduInputPhaseStatusCurrent
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusVoltage
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusActivePower
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusApparentPower
|
||
|
Integer32,
|
||
|
pduInputPhaseStatusPowerFactor
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduInputPhaseStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Input Phase status entry"
|
||
|
::= { pduInputPhaseStatusEntry 1 }
|
||
|
|
||
|
pduInputPhaseStatusCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Input Phase ID"
|
||
|
::= { pduInputPhaseStatusEntry 2 }
|
||
|
|
||
|
pduInputPhaseStatusCurrentState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton."
|
||
|
::= { pduInputPhaseStatusEntry 3 }
|
||
|
|
||
|
pduInputPhaseStatusVoltageState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present voltage status of the PDU Input Phase being queried"
|
||
|
::= { pduInputPhaseStatusEntry 4 }
|
||
|
|
||
|
pduInputPhaseStatusCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the current draw, in hundredths of Amps(A), of the load on the
|
||
|
PDU Phase/Line being queried. Nodes with
|
||
|
pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values,
|
||
|
and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
|
||
|
"
|
||
|
::= { pduInputPhaseStatusEntry 5 }
|
||
|
|
||
|
pduInputPhaseStatusVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the voltage, in Volts(V), of the PDU Phase/Line being queried.
|
||
|
Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values,
|
||
|
and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
|
||
|
"
|
||
|
::= { pduInputPhaseStatusEntry 6 }
|
||
|
|
||
|
pduInputPhaseStatusActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Watts(W), consumed on the PDU Phase/Line
|
||
|
being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection
|
||
|
Phase values or Delta connection Line values, and nodes with
|
||
|
pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
|
||
|
"
|
||
|
::= { pduInputPhaseStatusEntry 7 }
|
||
|
|
||
|
pduInputPhaseStatusApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Volt-Amps(VA), of the PDU Phase/Line being queried.
|
||
|
Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values,
|
||
|
and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
|
||
|
"
|
||
|
::= { pduInputPhaseStatusEntry 8 }
|
||
|
|
||
|
pduInputPhaseStatusPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the ratio of active to apparent power of the PDU Phase/Line being queried.
|
||
|
Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values,
|
||
|
and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
|
||
|
"
|
||
|
::= { pduInputPhaseStatusEntry 9 }
|
||
|
|
||
|
-- Start pduCircuitBreaker
|
||
|
pduCircuitBreakerTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of PDU Circuit Breakers"
|
||
|
::= { pduCircuitBreaker 1 }
|
||
|
|
||
|
pduCircuitBreakerConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduCircuitBreakerConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Circuit Breaker configuration data"
|
||
|
::= { pduCircuitBreaker 2 }
|
||
|
|
||
|
pduCircuitBreakerConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduCircuitBreakerConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker configuration entry containing objects for a particular circuit breaker."
|
||
|
INDEX { pduUnitConfigIndex, pduCircuitBreakerConfigIndex }
|
||
|
::= { pduCircuitBreakerConfigTable 1 }
|
||
|
|
||
|
PduCircuitBreakerConfigEntry ::= SEQUENCE {
|
||
|
pduCircuitBreakerConfigIndex
|
||
|
Integer32,
|
||
|
pduCircuitBreakerConfigCount
|
||
|
Integer32,
|
||
|
pduCircuitBreakerName
|
||
|
DisplayString,
|
||
|
pduCircuitBreakerConfigOverloadRestriction
|
||
|
INTEGER,
|
||
|
pduCircuitBreakerConfigLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigAlarmStateChangeDelay
|
||
|
Unsigned32,
|
||
|
pduCircuitBreakerConfigEnabledThresholds
|
||
|
BITS
|
||
|
}
|
||
|
|
||
|
pduCircuitBreakerConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker configuration table entry"
|
||
|
::= { pduCircuitBreakerConfigEntry 1 }
|
||
|
|
||
|
pduCircuitBreakerConfigCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of circuit breakers on the PDU"
|
||
|
::= { pduCircuitBreakerConfigEntry 2 }
|
||
|
|
||
|
pduCircuitBreakerName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The label of the circuit breaker"
|
||
|
::= { pduCircuitBreakerConfigEntry 3 }
|
||
|
|
||
|
pduCircuitBreakerConfigOverloadRestriction OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
alwaysAllowTurnOn (1),
|
||
|
restrictOnUpperWarning (2),
|
||
|
restrictOnUpperCritical (3),
|
||
|
notSupported (4)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID controls the behavior of a Switched PDU Circuit
|
||
|
Breaker when an overload condition is possible and additional
|
||
|
outlets are requested to be turned on. Setting this OID to
|
||
|
alwaysAllowTurnON (1) will always allow the outlets on the
|
||
|
corresponding Circuit Breaker to turn on. Setting this OID
|
||
|
to restrictOnUpperWarning (2) will not allow outlets on the
|
||
|
corresponding Circuit Breaker to turn on if the
|
||
|
pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded.
|
||
|
Setting this OID to restrictOnUpperCritical (3) will not
|
||
|
allow outlets on the corresponding Circuit Breaker to turn
|
||
|
on if the pduCircuitBreakerConfigUpperCriticalThreshold OID
|
||
|
is exceeded. Models that do not support this feature will
|
||
|
respond to this OID with a value of notSupported (4).
|
||
|
Attempts to set this OID in these models will fail. "
|
||
|
::= { pduCircuitBreakerConfigEntry 4 }
|
||
|
|
||
|
pduCircuitBreakerConfigLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduCircuitBreakerConfigEntry 5 }
|
||
|
|
||
|
pduCircuitBreakerConfigLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduCircuitBreakerConfigEntry 6 }
|
||
|
|
||
|
pduCircuitBreakerConfigUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduCircuitBreakerConfigEntry 7 }
|
||
|
|
||
|
pduCircuitBreakerConfigUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
|
||
|
::= { pduCircuitBreakerConfigEntry 8 }
|
||
|
|
||
|
pduCircuitBreakerConfigAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for deassertions in hundredths of Amps(A)."
|
||
|
::= { pduCircuitBreakerConfigEntry 9 }
|
||
|
|
||
|
pduCircuitBreakerConfigAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a state is asserted.
|
||
|
If the value is zero, then the state is asserted as soon
|
||
|
as it is detected; if it is non-zero, say n, then the
|
||
|
assertion condition must exist for n+1 consecutive samples
|
||
|
before the corresponding assertion event is reported."
|
||
|
::= { pduCircuitBreakerConfigEntry 10 }
|
||
|
|
||
|
pduCircuitBreakerConfigEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which alarm thresholds are enabled."
|
||
|
::= { pduCircuitBreakerConfigEntry 11 }
|
||
|
|
||
|
pduCircuitBreakerPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduCircuitBreakerPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU circuit breaker properties"
|
||
|
::= { pduCircuitBreaker 3 }
|
||
|
|
||
|
pduCircuitBreakerPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX PduCircuitBreakerPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker properties entry containing objects for a particular circuit breaker."
|
||
|
INDEX { pduUnitPropertiesIndex, pduCircuitBreakerPropertiesIndex }
|
||
|
::= { pduCircuitBreakerPropertiesTable 1 }
|
||
|
|
||
|
PduCircuitBreakerPropertiesEntry ::= SEQUENCE {
|
||
|
pduCircuitBreakerPropertiesIndex
|
||
|
Integer32,
|
||
|
pduCircuitBreakerPropertiesCount
|
||
|
Integer32,
|
||
|
pduCircuitBreakerPropertiesInputLayout
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduCircuitBreakerPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker properties table entry"
|
||
|
::= { pduCircuitBreakerPropertiesEntry 1 }
|
||
|
|
||
|
pduCircuitBreakerPropertiesCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of Circuit Breakers"
|
||
|
::= { pduCircuitBreakerPropertiesEntry 2 }
|
||
|
|
||
|
pduCircuitBreakerPropertiesInputLayout OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
seqPhase1ToNeutral (1),
|
||
|
seqPhase2ToNeutral (2),
|
||
|
seqPhase3ToNeutral (3),
|
||
|
seqPhase1ToPhase2 (4),
|
||
|
seqPhase2ToPhase3 (5),
|
||
|
seqPhase3ToPhase1 (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID describes the outlet phase connections on
|
||
|
the referenced bank as follows:
|
||
|
seqPhase1ToNeutral(1) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 1 to Neutral.
|
||
|
seqPhase2ToNeutral(2) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 2 to Neutral.
|
||
|
seqPhase3ToNeutral(3) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 3 to Neutral.
|
||
|
seqPhase1ToPhase2(4) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 1 to Phase2.
|
||
|
seqPhase2ToPhase3(5) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 2 to Phase3.
|
||
|
seqPhase3ToPhase1(6) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 3 to Phase1. "
|
||
|
::= { pduCircuitBreakerPropertiesEntry 3 }
|
||
|
|
||
|
pduCircuitBreakerStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduCircuitBreakerStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU circuit breaker status data"
|
||
|
::= { pduCircuitBreaker 4 }
|
||
|
|
||
|
pduCircuitBreakerStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduCircuitBreakerStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker status entry containing objects for a particular circuit breaker."
|
||
|
INDEX { pduUnitStatusIndex, pduCircuitBreakerStatusIndex }
|
||
|
::= { pduCircuitBreakerStatusTable 1 }
|
||
|
|
||
|
PduCircuitBreakerStatusEntry ::= SEQUENCE {
|
||
|
pduCircuitBreakerStatusIndex
|
||
|
Integer32,
|
||
|
pduCircuitBreakerStatusCount
|
||
|
Integer32,
|
||
|
pduCircuitBreakerLabel
|
||
|
DisplayString,
|
||
|
pduCircuitBreakerStatusLoadState
|
||
|
INTEGER,
|
||
|
pduCircuitBreakerStatusCurrent
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduCircuitBreakerStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker status table entry"
|
||
|
::= { pduCircuitBreakerStatusEntry 1 }
|
||
|
|
||
|
pduCircuitBreakerStatusCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of Circuit Breakers"
|
||
|
::= { pduCircuitBreakerStatusEntry 2 }
|
||
|
|
||
|
pduCircuitBreakerLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The label on the PDU identifying the circuit breaker"
|
||
|
::= { pduCircuitBreakerStatusEntry 3 }
|
||
|
|
||
|
pduCircuitBreakerStatusLoadState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5),
|
||
|
off (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present load status of the PDU Circuit
|
||
|
Breaker being queried"
|
||
|
::= { pduCircuitBreakerStatusEntry 4 }
|
||
|
|
||
|
pduCircuitBreakerStatusCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the current draw, in hundredths of Amps(A), of the load on
|
||
|
the PDU Circuit Breaker being queried."
|
||
|
::= { pduCircuitBreakerStatusEntry 5 }
|
||
|
|
||
|
-- Start pduOutlet
|
||
|
pduOutletSwitchedTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of PDU Outlets"
|
||
|
::= { pduOutlet 1 }
|
||
|
|
||
|
pduOutletSwitchedConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletSwitchedConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Switched Outlet configuration data"
|
||
|
::= { pduOutlet 2 }
|
||
|
|
||
|
pduOutletSwitchedConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletSwitchedConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An outlet configuration entry containing objects for a particular outlet."
|
||
|
INDEX { pduUnitConfigIndex, pduOutletSwitchedConfigIndex }
|
||
|
::= { pduOutletSwitchedConfigTable 1 }
|
||
|
|
||
|
PduOutletSwitchedConfigEntry ::= SEQUENCE {
|
||
|
pduOutletSwitchedConfigIndex
|
||
|
Integer32,
|
||
|
pduOutletSwitchedName
|
||
|
DisplayString,
|
||
|
pduOutletSwitchedStateOnStartup
|
||
|
INTEGER,
|
||
|
pduOutletSwitchedConfigPowerOnTime
|
||
|
Integer32,
|
||
|
pduOutletSwitchedConfigPowerOffTime
|
||
|
Integer32,
|
||
|
pduOutletSwitchedConfigRebootDuration
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduOutletSwitchedConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Switched Outlet configuration table entry"
|
||
|
::= { pduOutletSwitchedConfigEntry 1 }
|
||
|
|
||
|
pduOutletSwitchedName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined name for the Switched Outlet"
|
||
|
::= { pduOutletSwitchedConfigEntry 2 }
|
||
|
|
||
|
pduOutletSwitchedStateOnStartup OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off (0),
|
||
|
on (1),
|
||
|
lastKnownState (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The outlet state on device startup; overrides
|
||
|
the global value pduUnitConfigGlobalOutletStateOnStartup."
|
||
|
::= { pduOutletSwitchedConfigEntry 3 }
|
||
|
|
||
|
pduOutletSwitchedConfigPowerOnTime OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of delay, in seconds, between when power is
|
||
|
provided to outlets the outlet and when this outlet
|
||
|
starts providing power"
|
||
|
::= { pduOutletSwitchedConfigEntry 4 }
|
||
|
|
||
|
pduOutletSwitchedConfigPowerOffTime OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of time, in seconds, this outlet will delay
|
||
|
powering off"
|
||
|
::= { pduOutletSwitchedConfigEntry 5 }
|
||
|
|
||
|
pduOutletSwitchedConfigRebootDuration OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of time, in seconds, this outlet will remain
|
||
|
in powered off state before returning to power on state
|
||
|
during a reboot action."
|
||
|
::= { pduOutletSwitchedConfigEntry 6 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletSwitchedPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Switched Outlet properties"
|
||
|
::= { pduOutlet 3 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletSwitchedPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An outlet properties entry containing objects for a particular outlet."
|
||
|
INDEX { pduUnitPropertiesIndex, pduOutletSwitchedPropertiesIndex }
|
||
|
::= { pduOutletSwitchedPropertiesTable 1 }
|
||
|
|
||
|
PduOutletSwitchedPropertiesEntry ::= SEQUENCE {
|
||
|
pduOutletSwitchedPropertiesIndex
|
||
|
Integer32,
|
||
|
pduOutletSwitchedPropertiesNumber
|
||
|
Integer32,
|
||
|
pduOutletSwitchedPropertiesName
|
||
|
DisplayString,
|
||
|
pduOutletSwitchedPropertiesInputPhaseLayout
|
||
|
INTEGER,
|
||
|
pduOutletSwitchedPropertiesCircuitBreaker
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduOutletSwitchedPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Switched Outlet properties table entry"
|
||
|
::= { pduOutletSwitchedPropertiesEntry 1 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesNumber OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Switched Outlet ID"
|
||
|
::= { pduOutletSwitchedPropertiesEntry 2 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined switched outlet ID string"
|
||
|
::= { pduOutletSwitchedPropertiesEntry 3 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesInputPhaseLayout OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
seqPhase1ToNeutral (1),
|
||
|
seqPhase2ToNeutral (2),
|
||
|
seqPhase3ToNeutral (3),
|
||
|
seqPhase1ToPhase2 (4),
|
||
|
seqPhase2ToPhase3 (5),
|
||
|
seqPhase3ToPhase1 (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID describes the outlet phase connections
|
||
|
on the referenced bank as follows:
|
||
|
seqPhase1ToNeutral(1) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 1 to Neutral.
|
||
|
seqPhase2ToNeutral(2) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 2 to Neutral.
|
||
|
seqPhase3ToNeutral(3) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 3 to Neutral.
|
||
|
seqPhase1ToPhase2(4) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 1 to Phase2.
|
||
|
seqPhase2ToPhase3(5) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 2 to Phase3.
|
||
|
seqPhase3ToPhase1(6) indicates that outlets
|
||
|
attached to Switched Outlet are connected from Phase 3 to Phase1. "
|
||
|
::= { pduOutletSwitchedPropertiesEntry 4 }
|
||
|
|
||
|
pduOutletSwitchedPropertiesCircuitBreaker OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Circuit Breaker ID"
|
||
|
::= { pduOutletSwitchedPropertiesEntry 5 }
|
||
|
|
||
|
pduOutletSwitchedStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletSwitchedStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Switched Outlet status data"
|
||
|
::= { pduOutlet 4 }
|
||
|
|
||
|
pduOutletSwitchedStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletSwitchedStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status data from the PDU Switched Outlet being queried"
|
||
|
INDEX { pduUnitStatusIndex, pduOutletSwitchedStatusIndex }
|
||
|
::= { pduOutletSwitchedStatusTable 1 }
|
||
|
|
||
|
PduOutletSwitchedStatusEntry ::= SEQUENCE {
|
||
|
pduOutletSwitchedStatusIndex
|
||
|
Integer32,
|
||
|
pduOutletSwitchedStatusNumber
|
||
|
Integer32,
|
||
|
pduOutletSwitchedStatusName
|
||
|
DisplayString,
|
||
|
pduOutletSwitchedStatusState
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduOutletSwitchedStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Switched Outlet status table entry"
|
||
|
::= { pduOutletSwitchedStatusEntry 1 }
|
||
|
|
||
|
pduOutletSwitchedStatusNumber OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Switched Outlet ID"
|
||
|
::= { pduOutletSwitchedStatusEntry 2 }
|
||
|
|
||
|
pduOutletSwitchedStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined switched outlet ID string"
|
||
|
::= { pduOutletSwitchedStatusEntry 3 }
|
||
|
|
||
|
pduOutletSwitchedStatusState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off (0),
|
||
|
on (1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present switch state of the
|
||
|
PDU switched outlet being queried"
|
||
|
::= { pduOutletSwitchedStatusEntry 4 }
|
||
|
|
||
|
pduOutletSwitchedControlTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletSwitchedControlEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Switched Outlet status data"
|
||
|
::= { pduOutlet 5 }
|
||
|
|
||
|
pduOutletSwitchedControlEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletSwitchedControlEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status data from the PDU Switched Outlet
|
||
|
being queried"
|
||
|
INDEX { pduUnitConfigIndex, pduOutletSwitchedControlIndex }
|
||
|
::= { pduOutletSwitchedControlTable 1 }
|
||
|
|
||
|
PduOutletSwitchedControlEntry ::= SEQUENCE {
|
||
|
pduOutletSwitchedControlIndex
|
||
|
Integer32,
|
||
|
pduOutletSwitchedControlNumber
|
||
|
Integer32,
|
||
|
pduOutletSwitchedControlName
|
||
|
DisplayString,
|
||
|
pduOutletSwitchedControlCommand
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduOutletSwitchedControlIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index to the PDU switched outlet
|
||
|
control data table entry"
|
||
|
::= { pduOutletSwitchedControlEntry 1 }
|
||
|
|
||
|
pduOutletSwitchedControlNumber OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Switched Outlet ID"
|
||
|
::= { pduOutletSwitchedControlEntry 2 }
|
||
|
|
||
|
pduOutletSwitchedControlName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined switched outlet ID string"
|
||
|
::= { pduOutletSwitchedControlEntry 3 }
|
||
|
|
||
|
pduOutletSwitchedControlCommand OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
immediateOff (1),
|
||
|
immediateOn (2),
|
||
|
delayedOff (3),
|
||
|
delayedOn (4),
|
||
|
immediateReboot (5),
|
||
|
delayedReboot (6),
|
||
|
outletUnknown (7)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Getting this variable will return the outlet state.
|
||
|
If the outlet is on, the immediateOn (2)
|
||
|
value will be returned. If the outlet is off,
|
||
|
the immediateOff (1) value will be returned.
|
||
|
If the state of the outlet cannot be determined, the
|
||
|
outletUnknown (7) value will be returned. If the
|
||
|
outletUnknown condition should occur, all devices
|
||
|
powered by the PDU should be shut down. The PDU's
|
||
|
power should then be cycled to clear this condition.
|
||
|
Setting this variable to immediateOn (2) will immediately
|
||
|
turn the outlet on. Setting this variable to
|
||
|
immediateOff (1) will immediately turn the outlet off.
|
||
|
Setting this variable to immediateReboot (5)
|
||
|
will cause the Switched PDU to perform an immediateOff
|
||
|
command, wait the pduOutletSwitchedConfigRebootDuration
|
||
|
OID time, and then perform an immediateOn command.
|
||
|
Setting this variable to delayedOn (4) will turn the
|
||
|
outlet on after the pduOutletSwitchedConfigPowerOnTime
|
||
|
OID time has elapsed. Setting this variable to
|
||
|
delayedOff (3) will turn the outlet off after the
|
||
|
pduOutletSwitchedConfigPowerOffTime OID time has elapsed.
|
||
|
Setting this variable to delayedReboot (6) will cause
|
||
|
the Switched PDU to perform a delayedOff command, wait
|
||
|
the pduOutletSwitchedConfigRebootDuration OID time, and
|
||
|
then perform a delayedOn command."
|
||
|
::= { pduOutletSwitchedControlEntry 4 }
|
||
|
|
||
|
pduOutletMeteredTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of PDU Outlets"
|
||
|
::= { pduOutlet 6 }
|
||
|
|
||
|
pduOutletMeteredConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletMeteredConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Metered Outlet configuration data"
|
||
|
::= { pduOutlet 7 }
|
||
|
|
||
|
pduOutletMeteredConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletMeteredConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An outlet configuration entry containing objects for a particular outlet."
|
||
|
INDEX { pduUnitConfigIndex, pduOutletMeteredConfigIndex }
|
||
|
::= { pduOutletMeteredConfigTable 1 }
|
||
|
|
||
|
PduOutletMeteredConfigEntry ::= SEQUENCE {
|
||
|
pduOutletMeteredConfigIndex
|
||
|
Integer32,
|
||
|
pduOutletMeteredName
|
||
|
DisplayString,
|
||
|
pduOutletMeteredConfigLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigAlarmStateChangeDelay
|
||
|
Unsigned32,
|
||
|
pduOutletMeteredConfigEnabledThresholds
|
||
|
BITS
|
||
|
}
|
||
|
|
||
|
pduOutletMeteredConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Metered Outlet
|
||
|
configuration table entry"
|
||
|
::= { pduOutletMeteredConfigEntry 1 }
|
||
|
|
||
|
pduOutletMeteredName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined name for the Metered Outlet"
|
||
|
::= { pduOutletMeteredConfigEntry 2 }
|
||
|
|
||
|
pduOutletMeteredConfigLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical outlet active power alarm threshold in Watts(W)."
|
||
|
::= { pduOutletMeteredConfigEntry 3 }
|
||
|
|
||
|
pduOutletMeteredConfigLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W)."
|
||
|
::= { pduOutletMeteredConfigEntry 4 }
|
||
|
|
||
|
pduOutletMeteredConfigUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical outlet active power alarm threshold in Watts(W)."
|
||
|
::= { pduOutletMeteredConfigEntry 5 }
|
||
|
|
||
|
pduOutletMeteredConfigUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W)."
|
||
|
::= { pduOutletMeteredConfigEntry 6 }
|
||
|
|
||
|
pduOutletMeteredConfigAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for deassertions in Watts(W)."
|
||
|
::= { pduOutletMeteredConfigEntry 7 }
|
||
|
|
||
|
pduOutletMeteredConfigAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a state
|
||
|
is asserted. If the value is zero, then the state
|
||
|
is asserted as soon as it is detected; if it is
|
||
|
non-zero, say n, then the assertion condition must
|
||
|
exist for n+1 consecutive samples before the
|
||
|
corresponding assertion event is reported."
|
||
|
::= { pduOutletMeteredConfigEntry 8 }
|
||
|
|
||
|
pduOutletMeteredConfigEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which alarm
|
||
|
thresholds are enabled."
|
||
|
::= { pduOutletMeteredConfigEntry 9 }
|
||
|
|
||
|
pduOutletMeteredPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletMeteredPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Metered Outlet properties"
|
||
|
::= { pduOutlet 8 }
|
||
|
|
||
|
pduOutletMeteredPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletMeteredPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration data from the PDU Metered
|
||
|
Outlet being queried"
|
||
|
INDEX { pduUnitPropertiesIndex, pduOutletMeteredPropertiesIndex }
|
||
|
::= { pduOutletMeteredPropertiesTable 1 }
|
||
|
|
||
|
PduOutletMeteredPropertiesEntry ::= SEQUENCE {
|
||
|
pduOutletMeteredPropertiesIndex
|
||
|
Integer32,
|
||
|
pduOutletMeteredPropertiesNumber
|
||
|
Integer32,
|
||
|
pduOutletMeteredPropertiesName
|
||
|
DisplayString,
|
||
|
pduOutletMeteredPropertiesInputPhaseLayout
|
||
|
INTEGER,
|
||
|
pduOutletMeteredPropertiesCircuitBreaker
|
||
|
Integer32,
|
||
|
pduOutletMeteredPropertiesPowerRating
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduOutletMeteredPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Metered Outlet
|
||
|
properties table entry"
|
||
|
::= { pduOutletMeteredPropertiesEntry 1 }
|
||
|
|
||
|
pduOutletMeteredPropertiesNumber OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Metered Outlet ID"
|
||
|
::= { pduOutletMeteredPropertiesEntry 2 }
|
||
|
|
||
|
pduOutletMeteredPropertiesName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined Metered outlet ID string"
|
||
|
::= { pduOutletMeteredPropertiesEntry 3 }
|
||
|
|
||
|
pduOutletMeteredPropertiesInputPhaseLayout OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
seqPhase1ToNeutral (1),
|
||
|
seqPhase2ToNeutral (2),
|
||
|
seqPhase3ToNeutral (3),
|
||
|
seqPhase1ToPhase2 (4),
|
||
|
seqPhase2ToPhase3 (5),
|
||
|
seqPhase3ToPhase1 (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID describes the outlet phase connections
|
||
|
on the referenced bank as follows:
|
||
|
seqPhase1ToNeutral(1) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 1 to Neutral.
|
||
|
seqPhase2ToNeutral(2) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 2 to Neutral.
|
||
|
seqPhase3ToNeutral(3) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 3 to Neutral.
|
||
|
seqPhase1ToPhase2(4) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 1 to Phase2.
|
||
|
seqPhase2ToPhase3(5) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 2 to Phase3.
|
||
|
seqPhase3ToPhase1(6) indicates that outlets attached
|
||
|
to Metered Outlet are connected from Phase 3 to Phase1. "
|
||
|
::= { pduOutletMeteredPropertiesEntry 4 }
|
||
|
|
||
|
pduOutletMeteredPropertiesCircuitBreaker OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Circuit Breaker ID"
|
||
|
::= { pduOutletMeteredPropertiesEntry 5 }
|
||
|
|
||
|
pduOutletMeteredPropertiesPowerRating OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Maximum power rating of the PDU metered outlet"
|
||
|
::= { pduOutletMeteredPropertiesEntry 6 }
|
||
|
|
||
|
pduOutletMeteredStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduOutletMeteredStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Metered Outlet status data"
|
||
|
::= { pduOutlet 9 }
|
||
|
|
||
|
pduOutletMeteredStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduOutletMeteredStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status data from the PDU Metered Outlet being queried"
|
||
|
INDEX { pduUnitStatusIndex, pduOutletMeteredStatusIndex }
|
||
|
::= { pduOutletMeteredStatusTable 1 }
|
||
|
|
||
|
PduOutletMeteredStatusEntry ::= SEQUENCE {
|
||
|
pduOutletMeteredStatusIndex
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusNumber
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusName
|
||
|
DisplayString,
|
||
|
pduOutletMeteredStatusLoadState
|
||
|
INTEGER,
|
||
|
pduOutletMeteredStatusCurrent
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusActivePower
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusPowerFactor
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusPeakPower
|
||
|
Integer32,
|
||
|
pduOutletMeteredStatusPeakPowerTimeStamp
|
||
|
DisplayString,
|
||
|
pduOutletMeteredStatusPeakPowerStartTime
|
||
|
DisplayString,
|
||
|
pduOutletMeteredStatusResettableEnergy
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduOutletMeteredStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Metered Outlet status table entry"
|
||
|
::= { pduOutletMeteredStatusEntry 1 }
|
||
|
|
||
|
pduOutletMeteredStatusNumber OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Metered Outlet ID"
|
||
|
::= { pduOutletMeteredStatusEntry 2 }
|
||
|
|
||
|
pduOutletMeteredStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined Metered outlet ID string"
|
||
|
::= { pduOutletMeteredStatusEntry 3 }
|
||
|
|
||
|
pduOutletMeteredStatusLoadState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the present load status of the PDU metered outlet being queried."
|
||
|
::= { pduOutletMeteredStatusEntry 4 }
|
||
|
|
||
|
pduOutletMeteredStatusCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the current draw, in hundredths of Amps(A), of the load on the PDU
|
||
|
outlet being queried."
|
||
|
::= { pduOutletMeteredStatusEntry 5 }
|
||
|
|
||
|
pduOutletMeteredStatusActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the power draw, in Watts(W), of the load
|
||
|
on the PDU outlet being queried."
|
||
|
::= { pduOutletMeteredStatusEntry 6 }
|
||
|
|
||
|
pduOutletMeteredStatusPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the ratio of active to apparent power
|
||
|
of the PDU Outlet being queried"
|
||
|
::= { pduOutletMeteredStatusEntry 7 }
|
||
|
|
||
|
pduOutletMeteredStatusPeakPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns peak power consumption, in Watts(W),
|
||
|
of the Rack PDU outlet being queried."
|
||
|
::= { pduOutletMeteredStatusEntry 8 }
|
||
|
|
||
|
pduOutletMeteredStatusPeakPowerTimeStamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time that this metered
|
||
|
outlet's peak power consumption occurred"
|
||
|
::= { pduOutletMeteredStatusEntry 9 }
|
||
|
|
||
|
pduOutletMeteredStatusPeakPowerStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the start date and time that this metered
|
||
|
outlet began recording peak power observations"
|
||
|
::= { pduOutletMeteredStatusEntry 10 }
|
||
|
|
||
|
pduOutletMeteredStatusResettableEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user resettable energy meter measuring outlet load energy
|
||
|
consumption in tenths of Kilowatt-Hours(kWh)."
|
||
|
::= { pduOutletMeteredStatusEntry 11 }
|
||
|
|
||
|
-- Start pduExternalSensor
|
||
|
pduExternalSensorTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of External Sensors"
|
||
|
::= { pduExternalSensor 1 }
|
||
|
|
||
|
pduExternalSensorNamePlateTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduExternalSensorNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU ExternalSensorNamePlate data"
|
||
|
::= { pduExternalSensor 2 }
|
||
|
|
||
|
pduExternalSensorNamePlateEntry OBJECT-TYPE
|
||
|
SYNTAX PduExternalSensorNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"External Sensor Name Plate data from the external
|
||
|
sensor being queried. The number of entries equals
|
||
|
the value of pduExternalSensorNamePlateTableSize."
|
||
|
INDEX { pduNamePlateIndex, pduExternalSensorNamePlateIndex }
|
||
|
::= { pduExternalSensorNamePlateTable 1 }
|
||
|
|
||
|
PduExternalSensorNamePlateEntry ::= SEQUENCE {
|
||
|
pduExternalSensorNamePlateIndex
|
||
|
Integer32,
|
||
|
pduExternalSensorNamePlateName
|
||
|
DisplayString,
|
||
|
pduExternalSensorNamePlateDescription
|
||
|
DisplayString,
|
||
|
pduExternalSensorNamePlateLocation
|
||
|
DisplayString,
|
||
|
pduExternalSensorNamePlateSerialNumber
|
||
|
DisplayString,
|
||
|
pduExternalSensorNamePlateType
|
||
|
INTEGER,
|
||
|
pduExternalSensorNamePlateUnits
|
||
|
INTEGER,
|
||
|
pduExternalSensorNamePlateIdentifier
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduExternalSensorNamePlateIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor status table entry"
|
||
|
::= { pduExternalSensorNamePlateEntry 1 }
|
||
|
|
||
|
pduExternalSensorNamePlateName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the external sensor"
|
||
|
::= { pduExternalSensorNamePlateEntry 2 }
|
||
|
|
||
|
pduExternalSensorNamePlateDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined description of the external sensor"
|
||
|
::= { pduExternalSensorNamePlateEntry 3 }
|
||
|
|
||
|
pduExternalSensorNamePlateLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the location of the PDU"
|
||
|
::= { pduExternalSensorNamePlateEntry 4 }
|
||
|
|
||
|
pduExternalSensorNamePlateSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The serial number of the external sensor being queried"
|
||
|
::= { pduExternalSensorNamePlateEntry 5 }
|
||
|
|
||
|
pduExternalSensorNamePlateType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
temperature (1),
|
||
|
humidity (2),
|
||
|
doorSwitch (3),
|
||
|
dryContact (4),
|
||
|
spotFluid (5),
|
||
|
ropeFluid (6),
|
||
|
smoke (7),
|
||
|
beacon (8),
|
||
|
airVelocity (9),
|
||
|
modbusAdapter (17),
|
||
|
hidAdapter (18)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of external sensor."
|
||
|
::= { pduExternalSensorNamePlateEntry 6 }
|
||
|
|
||
|
pduExternalSensorNamePlateUnits OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
logic (0),
|
||
|
degreeC (1),
|
||
|
degreeF (2),
|
||
|
percent (3),
|
||
|
mps (4)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The base units the external sensor is measured in.
|
||
|
This parameter does not apply to onOff, trip, vibration,
|
||
|
waterDetection, smokeDetection sensors. "
|
||
|
::= { pduExternalSensorNamePlateEntry 7 }
|
||
|
|
||
|
pduExternalSensorNamePlateIdentifier OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unique identifier of the external sensor."
|
||
|
::= { pduExternalSensorNamePlateEntry 8 }
|
||
|
|
||
|
pduExternalSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduExternalSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU External Sensor configuration data"
|
||
|
::= { pduExternalSensor 3 }
|
||
|
|
||
|
pduExternalSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX PduExternalSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration data from the PDU External
|
||
|
Sensor being queried"
|
||
|
INDEX { pduUnitConfigIndex, pduExternalSensorConfigIndex }
|
||
|
::= { pduExternalSensorConfigTable 1 }
|
||
|
|
||
|
PduExternalSensorConfigEntry ::= SEQUENCE {
|
||
|
pduExternalSensorConfigIndex
|
||
|
Integer32,
|
||
|
pduExternalSensorConfigLowerCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigLowerWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigUpperCriticalThreshold
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigUpperWarningThreshold
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigAlarmResetThreshold
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigAlarmStateChangeDelay
|
||
|
Unsigned32,
|
||
|
pduExternalSensorConfigEnabledThresholds
|
||
|
BITS,
|
||
|
pduExternalSensorConfigAlarmState
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduExternalSensorConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor
|
||
|
configuration table entry"
|
||
|
::= { pduExternalSensorConfigEntry 1 }
|
||
|
|
||
|
pduExternalSensorConfigLowerCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits."
|
||
|
::= { pduExternalSensorConfigEntry 2 }
|
||
|
|
||
|
pduExternalSensorConfigLowerWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
|
||
|
::= { pduExternalSensorConfigEntry 3 }
|
||
|
|
||
|
pduExternalSensorConfigUpperCriticalThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits."
|
||
|
::= { pduExternalSensorConfigEntry 4 }
|
||
|
|
||
|
pduExternalSensorConfigUpperWarningThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
|
||
|
::= { pduExternalSensorConfigEntry 5 }
|
||
|
|
||
|
pduExternalSensorConfigAlarmResetThreshold OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The hysteresis used for deassertions."
|
||
|
::= { pduExternalSensorConfigEntry 6 }
|
||
|
|
||
|
pduExternalSensorConfigAlarmStateChangeDelay OBJECT-TYPE
|
||
|
SYNTAX Unsigned32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The delay measured in samples before a state is
|
||
|
asserted. If the value is zero, then the state is
|
||
|
asserted as soon as it is detected; if it is non-zero,
|
||
|
say n, then the assertion condition must exist for n+1
|
||
|
consecutive samples before the corresponding assertion
|
||
|
event is reported."
|
||
|
::= { pduExternalSensorConfigEntry 7 }
|
||
|
|
||
|
pduExternalSensorConfigEnabledThresholds OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
lowerCritical (0),
|
||
|
lowerWarning (1),
|
||
|
upperWarning (2),
|
||
|
upperCritical (3),
|
||
|
binarySensorAlarm (4)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A bit string indicating which alarm
|
||
|
thresholds are enabled."
|
||
|
::= { pduExternalSensorConfigEntry 8 }
|
||
|
|
||
|
pduExternalSensorConfigAlarmState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
on (1),
|
||
|
off (0)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User defined alarm state of external sensor"
|
||
|
::= { pduExternalSensorConfigEntry 9 }
|
||
|
|
||
|
pduExternalSensorStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduExternalSensorStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU External Sensor status data"
|
||
|
::= { pduExternalSensor 4 }
|
||
|
|
||
|
pduExternalSensorStatusEntry OBJECT-TYPE
|
||
|
SYNTAX PduExternalSensorStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status data from the PDU External Sensor
|
||
|
being queried"
|
||
|
INDEX { pduUnitStatusIndex, pduExternalSensorStatusIndex }
|
||
|
::= { pduExternalSensorStatusTable 1 }
|
||
|
|
||
|
PduExternalSensorStatusEntry ::= SEQUENCE {
|
||
|
pduExternalSensorStatusIndex
|
||
|
Integer32,
|
||
|
pduExternalSensorStatusName
|
||
|
DisplayString,
|
||
|
pduExternalSensorStatusAisle
|
||
|
INTEGER,
|
||
|
pduExternalSensorStatusCommStatus
|
||
|
INTEGER,
|
||
|
pduExternalSensorStatusState
|
||
|
INTEGER,
|
||
|
pduExternalSensorStatusValue
|
||
|
Integer32,
|
||
|
pduExternalSensorStatusTimeStamp
|
||
|
DisplayString,
|
||
|
pduExternalSensorStatusHighPrecisionValue
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduExternalSensorStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor status table entry"
|
||
|
::= { pduExternalSensorStatusEntry 1 }
|
||
|
|
||
|
pduExternalSensorStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined name for the External Sensor"
|
||
|
::= { pduExternalSensorStatusEntry 2 }
|
||
|
|
||
|
pduExternalSensorStatusAisle OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
hotAisle (1),
|
||
|
coldAisle (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates whether the external sensor is
|
||
|
in a hot or cold aisle"
|
||
|
::= { pduExternalSensorStatusEntry 3 }
|
||
|
|
||
|
pduExternalSensorStatusCommStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
notInstalled (1),
|
||
|
commsOk (2),
|
||
|
commsLost (3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The communications status of the sensor"
|
||
|
::= { pduExternalSensorStatusEntry 4 }
|
||
|
|
||
|
pduExternalSensorStatusState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
notPresent (0), alarmed (1), normal (2), belowLowerCritical (3), belowLowerWarning (4), aboveUpperWarning (5), aboveUpperCritical (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID reports the current state of the sensor.
|
||
|
A notPresent (0) response indicates that no sensor is attached.
|
||
|
An alarmed (1) response indicates that the sensor is present
|
||
|
and its measured reading indicates alarmed.
|
||
|
A normal (2) response indicates that the sensor is present
|
||
|
and its measured reading lies within all thresholds.
|
||
|
A belowLowerCritical (3) response indicates that the sensor
|
||
|
is present and its measured reading lies below the lower critical threshold.
|
||
|
A belowLowerWarning (4) response indicates that the sensor
|
||
|
is present and its measured reading lies below the lower warning threshold.
|
||
|
An aboveUpperWarning (5) response indicates that the sensor
|
||
|
is present and its measured reading lies above the upper warning threshold.
|
||
|
An aboveUpperCritical (6) response indicates that the sensor
|
||
|
is present and its measured reading lies above the upper critical threshold."
|
||
|
::= { pduExternalSensorStatusEntry 5 }
|
||
|
|
||
|
pduExternalSensorStatusValue OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Sensor reading in pduExternalSensorConfigUnits value."
|
||
|
::= { pduExternalSensorStatusEntry 6 }
|
||
|
|
||
|
pduExternalSensorStatusTimeStamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The sensor reading timestamp."
|
||
|
::= { pduExternalSensorStatusEntry 7 }
|
||
|
|
||
|
pduExternalSensorStatusHighPrecisionValue OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor reading in tenths of pduExternalSensorConfigUnits value.
|
||
|
This OID is applied to temperature sensor only"
|
||
|
::= { pduExternalSensorStatusEntry 8 }
|
||
|
|
||
|
-- Start pduServerPing
|
||
|
pduServerPingTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of Servers"
|
||
|
::= { pduServerPing 1 }
|
||
|
|
||
|
pduServerPingTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduServerPingEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of Server Ping data"
|
||
|
::= { pduServerPing 2 }
|
||
|
|
||
|
pduServerPingEntry OBJECT-TYPE
|
||
|
SYNTAX PduServerPingEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Server Ping data from the server being queried.
|
||
|
The number of entries equals the value of pduServerPingTableSize."
|
||
|
INDEX { pduUnitConfigIndex, pduServerPingIndex }
|
||
|
::= { pduServerPingTable 1 }
|
||
|
|
||
|
PduServerPingEntry ::= SEQUENCE {
|
||
|
pduServerPingIndex
|
||
|
Integer32,
|
||
|
pduServerPingServerIPAddress
|
||
|
DisplayString,
|
||
|
pduServerPingEnabled
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
pduServerPingIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU pduServerPing table entry"
|
||
|
::= { pduServerPingEntry 1 }
|
||
|
|
||
|
pduServerPingServerIPAddress OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The IP Address/host name of the server "
|
||
|
::= { pduServerPingEntry 2 }
|
||
|
|
||
|
pduServerPingEnabled OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
false (0), true (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Is ping enabled for this server?"
|
||
|
::= { pduServerPingEntry 3 }
|
||
|
|
||
|
-- Smart Cabinet
|
||
|
|
||
|
pduUnitSmartCabinetTableSize OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of Smart Cabinet Configuration "
|
||
|
::= { pduSmartCabinet 1 }
|
||
|
|
||
|
pduUnitSmartCabinetTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF PduUnitSmartCabinetEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of Smart Cabinet information"
|
||
|
::= { pduSmartCabinet 2 }
|
||
|
|
||
|
|
||
|
pduUnitSmartCabinetEntry OBJECT-TYPE
|
||
|
SYNTAX PduUnitSmartCabinetEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Information of Smart Cabinet"
|
||
|
INDEX { pduUnitConfigIndex, pduUnitSmartCabinetIndex }
|
||
|
::= { pduUnitSmartCabinetTable 1 }
|
||
|
|
||
|
PduUnitSmartCabinetEntry ::= SEQUENCE {
|
||
|
pduUnitSmartCabinetIndex
|
||
|
Integer32,
|
||
|
pduUnitSmartCabinetCardUserName
|
||
|
DisplayString,
|
||
|
pduUnitSmartCabinetCardID
|
||
|
Integer32,
|
||
|
pduUnitSmartCabinetTimestamp
|
||
|
DisplayString,
|
||
|
pduUnitSmartCabinetDoor
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
pduUnitSmartCabinetIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Smart Cabinet table entry"
|
||
|
::= { pduUnitSmartCabinetEntry 1 }
|
||
|
|
||
|
pduUnitSmartCabinetCardUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User name of ID card"
|
||
|
::= { pduUnitSmartCabinetEntry 2 }
|
||
|
|
||
|
pduUnitSmartCabinetCardID OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Card ID."
|
||
|
::= { pduUnitSmartCabinetEntry 3 }
|
||
|
|
||
|
pduUnitSmartCabinetTimestamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of information update"
|
||
|
::= { pduUnitSmartCabinetEntry 4 }
|
||
|
|
||
|
pduUnitSmartCabinetDoor OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
HotAisle (1),
|
||
|
ColdAisle (2) }
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Aisle of Smart Cabinet. "
|
||
|
::= { pduUnitSmartCabinetEntry 5 }
|
||
|
|
||
|
pduUnitSmartCabinetControl OBJECT IDENTIFIER ::= { pduSmartCabinet 3 }
|
||
|
|
||
|
pduUnitSmartCabinetControlUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User name of ID card"
|
||
|
::= { pduUnitSmartCabinetControl 1 }
|
||
|
|
||
|
pduUnitSmartCabinetControlCardID OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Card ID."
|
||
|
::= { pduUnitSmartCabinetControl 2 }
|
||
|
|
||
|
pduUnitSmartCabinetControlTimestamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of information update"
|
||
|
::= { pduUnitSmartCabinetControl 3 }
|
||
|
|
||
|
pduUnitSmartCabinetControlDoor OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
HotAisle (1),
|
||
|
ColdAisle (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Aisle of Smart Cabinet. "
|
||
|
::= { pduUnitSmartCabinetControl 4 }
|
||
|
|
||
|
pduUnitSmartCabinetCardIDEdit OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
grant (0), remove (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Smart Cabinet edit CardID "
|
||
|
::= { pduUnitSmartCabinetControl 5 }
|
||
|
|
||
|
pduUnitSmartCabinetColdAisleLockState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unlock (0), lock (1), notPresent (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Smart Cabinet ColdAisle lock state "
|
||
|
::= { pduUnitSmartCabinetControl 6 }
|
||
|
|
||
|
pduUnitSmartCabinetHotAisleLockState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unlock (0), lock (1), notPresent (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Smart Cabinet HotAisle lock state "
|
||
|
::= { pduUnitSmartCabinetControl 7 }
|
||
|
|
||
|
-- Traps Information
|
||
|
trapsInfo OBJECT IDENTIFIER ::= { pduTraps 1 }
|
||
|
|
||
|
trapsInfoTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF TrapsInfoEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A list of Trap Information entries. The number of
|
||
|
entries are given by the value of pduUnitTableSize."
|
||
|
::= { trapsInfo 1 }
|
||
|
|
||
|
trapsInfoEntry OBJECT-TYPE
|
||
|
SYNTAX TrapsInfoEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An entry containing objects used in traps"
|
||
|
INDEX { trapsInfoIndex }
|
||
|
::= { trapsInfoTable 1 }
|
||
|
|
||
|
TrapsInfoEntry ::= SEQUENCE {
|
||
|
trapsInfoIndex
|
||
|
Integer32,
|
||
|
userName
|
||
|
DisplayString,
|
||
|
userUpdated
|
||
|
DisplayString,
|
||
|
firmwareVersion
|
||
|
DisplayString,
|
||
|
roleUpdated
|
||
|
DisplayString,
|
||
|
smtpRecipients
|
||
|
DisplayString,
|
||
|
smtpServer
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
trapsInfoIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the traps table entry"
|
||
|
::= { trapsInfoEntry 1 }
|
||
|
|
||
|
|
||
|
userName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user currently logged in."
|
||
|
::= { trapsInfoEntry 2 }
|
||
|
|
||
|
userUpdated OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user added, deleted, or modified."
|
||
|
::= { trapsInfoEntry 3 }
|
||
|
|
||
|
firmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The version of Firmware."
|
||
|
::= { trapsInfoEntry 4 }
|
||
|
|
||
|
roleUpdated OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The role added, deleted, or modified."
|
||
|
::= { trapsInfoEntry 5 }
|
||
|
|
||
|
smtpRecipients OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Comma separated list of SMTP recipients"
|
||
|
::= { trapsInfoEntry 6 }
|
||
|
|
||
|
smtpServer OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The IP address/host name of the SMTP server"
|
||
|
::= { trapsInfoEntry 7 }
|
||
|
|
||
|
pduIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unique value for PDU. Its value ranges between 1
|
||
|
and the value of PDU count"
|
||
|
::= { trapsInfo 2 }
|
||
|
|
||
|
externalSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unique value for each sensor. Its value ranges between 1
|
||
|
and the value of external sensor count."
|
||
|
::= { trapsInfo 3 }
|
||
|
|
||
|
serverPing OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
pingEnable (1),
|
||
|
pingDisable (2),
|
||
|
serverReachable (3),
|
||
|
serverNotReachable (4)
|
||
|
}
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Whether server ping has been enabled or disabled and
|
||
|
whether the server is reachable or not reachable"
|
||
|
::= { trapsInfo 4 }
|
||
|
|
||
|
usbDevice OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
connected (1),
|
||
|
disconnected (2)
|
||
|
}
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Whether a USB device has been connected or disconnected"
|
||
|
::= { trapsInfo 5 }
|
||
|
|
||
|
errorDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Description of the Error"
|
||
|
::= { trapsInfo 6 }
|
||
|
|
||
|
daisyChain OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
connected (1),
|
||
|
disconnected (2)
|
||
|
}
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Whether a daisy chain member has been connected or disconnected"
|
||
|
::= { trapsInfo 7 }
|
||
|
|
||
|
systemCommunication OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
ok (1),
|
||
|
lost (2)
|
||
|
}
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Whether the Network management card has lost contact with daisy a chain member."
|
||
|
::= { trapsInfo 8 }
|
||
|
|
||
|
networkCardStart NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The network card has started"
|
||
|
::= { pduTraps 2 }
|
||
|
|
||
|
networkCardReset NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The network card was reset via the web or command line interface."
|
||
|
::= { pduTraps 3 }
|
||
|
|
||
|
userLogin NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user logged in"
|
||
|
::= { pduTraps 4 }
|
||
|
|
||
|
userLogoff NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
" A user logged off"
|
||
|
::= { pduTraps 5 }
|
||
|
|
||
|
userAuthenticationFailed NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user authentication attempt failed."
|
||
|
::= { pduTraps 6 }
|
||
|
|
||
|
userSessionTimeout NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user session timed out"
|
||
|
::= { pduTraps 7 }
|
||
|
|
||
|
userAdded NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
userUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user account was added to system."
|
||
|
::= { pduTraps 8 }
|
||
|
|
||
|
userModified NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
userUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user account was modified."
|
||
|
::= { pduTraps 9 }
|
||
|
|
||
|
userDeleted NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
userUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user account was deleted."
|
||
|
::= { pduTraps 10 }
|
||
|
|
||
|
roleAdded NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
roleUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user role was added."
|
||
|
::= { pduTraps 11 }
|
||
|
|
||
|
roleModified NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
roleUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user role was modified."
|
||
|
::= { pduTraps 12 }
|
||
|
|
||
|
roleDeleted NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
roleUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user role was deleted."
|
||
|
::= { pduTraps 13 }
|
||
|
|
||
|
firmwareUpdateStarted NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
firmwareVersion,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A firmware update has started."
|
||
|
::= { pduTraps 14 }
|
||
|
|
||
|
firmwareUpdateCompleted NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
firmwareVersion,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The firmware update has completed."
|
||
|
::= { pduTraps 15 }
|
||
|
|
||
|
userBlocked NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user is blocked."
|
||
|
::= { pduTraps 16 }
|
||
|
|
||
|
outletControl NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduOutletSwitchedControlNumber,
|
||
|
pduOutletSwitchedStatusState,
|
||
|
pduOutletSwitchedControlCommand,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet control operation applied."
|
||
|
::= { pduTraps 17 }
|
||
|
|
||
|
userPasswordChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
userUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user password was changed. "
|
||
|
::= { pduTraps 18 }
|
||
|
|
||
|
passwordSettingsChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"One or more password policy settings were changed."
|
||
|
::= { pduTraps 19 }
|
||
|
|
||
|
logFileCleared NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The log file has been cleared."
|
||
|
::= { pduTraps 21 }
|
||
|
|
||
|
pduConfigurationFileImported NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU configuration file was imported."
|
||
|
::= { pduTraps 22 }
|
||
|
|
||
|
pduConfigurationFileExported NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU configuration file was exported"
|
||
|
::= { pduTraps 23 }
|
||
|
|
||
|
pduUnitActivePowerStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitStatusLoadState,
|
||
|
pduUnitStatusActivePower,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU unit active power state changes."
|
||
|
::= { pduTraps 24 }
|
||
|
|
||
|
pduInputphaseVoltageStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduInputPhaseStatusCount,
|
||
|
pduInputPhaseStatusVoltageState,
|
||
|
pduInputPhaseStatusVoltage,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU input phase voltage state changes."
|
||
|
::= { pduTraps 25 }
|
||
|
|
||
|
pduInputphaseCurrentStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduInputPhaseStatusCount,
|
||
|
pduInputPhaseStatusCurrentState,
|
||
|
pduInputPhaseStatusCurrent,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU input phase Current state changes."
|
||
|
::= { pduTraps 26 }
|
||
|
|
||
|
pduCircuitBreakerCurrentStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduCircuitBreakerStatusIndex,
|
||
|
pduCircuitBreakerStatusLoadState,
|
||
|
pduCircuitBreakerStatusCurrent,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Circuit Breaker Current state changes."
|
||
|
::= { pduTraps 27 }
|
||
|
|
||
|
pduOutletActivePowerStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduOutletMeteredStatusIndex,
|
||
|
pduOutletMeteredStatusLoadState,
|
||
|
pduOutletMeteredStatusActivePower,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Metered Outlet Active Power state changes."
|
||
|
::= { pduTraps 28 }
|
||
|
|
||
|
pduExternalSensorStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduExternalSensorStatusIndex,
|
||
|
pduExternalSensorStatusName,
|
||
|
pduExternalSensorNamePlateType,
|
||
|
pduExternalSensorStatusAisle,
|
||
|
pduExternalSensorNamePlateUnits,
|
||
|
pduExternalSensorStatusState,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU External Sensor state changes."
|
||
|
::= { pduTraps 29 }
|
||
|
|
||
|
smtpTransmissionFailure NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
smtpRecipients,
|
||
|
smtpServer,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"SMTP message transmission failed."
|
||
|
::= { pduTraps 30 }
|
||
|
|
||
|
ldapError NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
errorDescription,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A LDAP error occurred"
|
||
|
::= { pduTraps 31 }
|
||
|
|
||
|
firmwareUpdateFailed NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
firmwareVersion,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A firmware update has failed."
|
||
|
::= { pduTraps 32 }
|
||
|
|
||
|
serverPingState NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
userName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduServerPingServerIPAddress,
|
||
|
serverPing,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The Ping feature has been enabled."
|
||
|
::= { pduTraps 33 }
|
||
|
|
||
|
bootloaderState NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enter into Bootloader mode"
|
||
|
::= { pduTraps 34 }
|
||
|
|
||
|
daisyChainState NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
daisyChain,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A daisy chain member has been connected or disconnected."
|
||
|
::= { pduTraps 35 }
|
||
|
|
||
|
systemInternalCommunicationLost NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
systemCommunication,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Network management card has lost contaction with internal boards."
|
||
|
::= { pduTraps 36 }
|
||
|
|
||
|
|
||
|
SmartCabinetLockUnlocked NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitSmartCabinetDoor,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The Cabinet lock is unlocked."
|
||
|
::= { pduTraps 37 }
|
||
|
|
||
|
SmartCabinetLockLocked NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitSmartCabinetDoor,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The Cabinet lock is locked"
|
||
|
::= { pduTraps 38 }
|
||
|
|
||
|
SmartCabinetSwapCard NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitSmartCabinetDoor,
|
||
|
pduUnitSmartCabinetCardID,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Card is swapped"
|
||
|
::= { pduTraps 39 }
|
||
|
|
||
|
SmartCabinetLockerLockDoorOpen NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitSmartCabinetDoor,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Locker locked but door open"
|
||
|
::= { pduTraps 40 }
|
||
|
|
||
|
SmartCabinetLockerUnlockDoorClose NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
pduUnitSmartCabinetDoor,
|
||
|
pduExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Locker unlocked but door close"
|
||
|
::= { pduTraps 41 }
|
||
|
|
||
|
systemReboot NOTIFICATION-TYPE
|
||
|
OBJECTS { pduIndex,
|
||
|
pduNamePlateName,
|
||
|
pduNamePlateInetAddressType,
|
||
|
pduNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"System has rebooted"
|
||
|
::= { pduTraps 50 }
|
||
|
|
||
|
esp OBJECT IDENTIFIER ::= { enlogic 2 }
|
||
|
espNamePlate OBJECT IDENTIFIER ::= { esp 1 }
|
||
|
espUnit OBJECT IDENTIFIER ::= { esp 2 }
|
||
|
espInputPhase OBJECT IDENTIFIER ::= { esp 3 }
|
||
|
espCircuitBreaker OBJECT IDENTIFIER ::= { esp 4 }
|
||
|
espExternalSensor OBJECT IDENTIFIER ::= { esp 6 }
|
||
|
espTraps OBJECT IDENTIFIER ::= { esp 9 }
|
||
|
|
||
|
-- Start espNamePlate
|
||
|
|
||
|
-- espNamePlateTable
|
||
|
espNamePlateTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of es PDU nameplate data"
|
||
|
::= { espNamePlate 2 }
|
||
|
|
||
|
espNamePlateEntry OBJECT-TYPE
|
||
|
SYNTAX EspNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Nameplate data from the PDU being queried. The numbers of entries equals the value of espNamePlateTableSize."
|
||
|
INDEX { espNamePlateIndex }
|
||
|
::= { espNamePlateTable 1 }
|
||
|
|
||
|
EspNamePlateEntry ::= SEQUENCE {
|
||
|
espNamePlateIndex
|
||
|
Integer32,
|
||
|
espNamePlateName
|
||
|
DisplayString,
|
||
|
espNamePlateLocation
|
||
|
DisplayString,
|
||
|
espNamePlateInetAddressType
|
||
|
InetAddressType,
|
||
|
espNamePlateIPAddress
|
||
|
InetAddress,
|
||
|
espNamePlateInetNetMask
|
||
|
InetAddress,
|
||
|
espNamePlateInetGateway
|
||
|
InetAddress,
|
||
|
espNamePlateMACAddress
|
||
|
MacAddress,
|
||
|
espNamePlateUTCTimeOffset
|
||
|
DisplayString,
|
||
|
espNamePlateModelNumber
|
||
|
DisplayString,
|
||
|
espNamePlateSerialNumber
|
||
|
DisplayString,
|
||
|
espNamePlateDateofManufacture
|
||
|
DisplayString,
|
||
|
espNamePlateFirmwareVersion
|
||
|
DisplayString,
|
||
|
espNamePlateFirmwareVersionTimeStamp
|
||
|
DisplayString,
|
||
|
espNamePlateType
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
espNamePlateIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the es PDU nameplate table entry"
|
||
|
::= { espNamePlateEntry 1 }
|
||
|
|
||
|
espNamePlateName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the es PDU"
|
||
|
::= { espNamePlateEntry 2 }
|
||
|
|
||
|
espNamePlateLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the location of PDU"
|
||
|
::= { espNamePlateEntry 3 }
|
||
|
|
||
|
espNamePlateInetAddressType OBJECT-TYPE
|
||
|
SYNTAX InetAddressType
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of address format"
|
||
|
::= { espNamePlateEntry 4 }
|
||
|
|
||
|
espNamePlateIPAddress OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current IP address. A value of 0.0.0.0 indicates an error or an unset option"
|
||
|
::= { espNamePlateEntry 5 }
|
||
|
|
||
|
espNamePlateInetNetMask OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current netmask. A value of 0.0.0.0 indiates an error or an unset option"
|
||
|
::= { espNamePlateEntry 6 }
|
||
|
|
||
|
espNamePlateInetGateway OBJECT-TYPE
|
||
|
SYNTAX InetAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current gateway. A value of 0.0.0.0 indicates an error or an unset option"
|
||
|
::= { espNamePlateEntry 7 }
|
||
|
|
||
|
espNamePlateMACAddress OBJECT-TYPE
|
||
|
SYNTAX MacAddress
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The assigned MAC address for the PDU"
|
||
|
::= { espNamePlateEntry 8 }
|
||
|
|
||
|
espNamePlateUTCTimeOffset OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The difference in hours and minutes from Coordinated Universal
|
||
|
Time(UTC) for the time used in a particular time zone"
|
||
|
::= { espNamePlateEntry 9 }
|
||
|
|
||
|
espNamePlateModelNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU model number"
|
||
|
::= { espNamePlateEntry 10 }
|
||
|
|
||
|
espNamePlateSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU serial number"
|
||
|
::= { espNamePlateEntry 11 }
|
||
|
|
||
|
espNamePlateDateofManufacture OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The date the PDU was manufactured in mm/dd/yyyy format"
|
||
|
::= { espNamePlateEntry 12 }
|
||
|
|
||
|
espNamePlateFirmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU firmware version"
|
||
|
::= { espNamePlateEntry 13 }
|
||
|
|
||
|
espNamePlateFirmwareVersionTimeStamp OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Timestamp of when the PDU firmware was last updated"
|
||
|
::= { espNamePlateEntry 14 }
|
||
|
|
||
|
espNamePlateType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
pdu (0),
|
||
|
inlineMeter (1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of Unit, PDU or Inline Meter"
|
||
|
::= { espNamePlateEntry 15 }
|
||
|
|
||
|
|
||
|
-- Start espUnit
|
||
|
|
||
|
espUnitConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspUnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU configuration data"
|
||
|
::= { espUnit 2 }
|
||
|
|
||
|
espUnitConfigEntry OBJECT-TYPE
|
||
|
SYNTAX EspUnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration data from the PDU being queried. The number of entries equals the value of espUnitTableSize"
|
||
|
INDEX { espUnitConfigIndex }
|
||
|
::= { espUnitConfigTable 1 }
|
||
|
|
||
|
EspUnitConfigEntry ::= SEQUENCE {
|
||
|
espUnitConfigIndex
|
||
|
Integer32,
|
||
|
espUnitConfigName
|
||
|
DisplayString,
|
||
|
espUnitConfigLocation
|
||
|
DisplayString,
|
||
|
espUnitConfigEnergyReset
|
||
|
INTEGER,
|
||
|
espUnitConfigResetNetworkManagementCard
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
espUnitConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Unit Config Entry"
|
||
|
::= { espUnitConfigEntry 1 }
|
||
|
|
||
|
espUnitConfigName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { espUnitConfigEntry 2 }
|
||
|
|
||
|
espUnitConfigLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the location of the PDU"
|
||
|
::= { espUnitConfigEntry 3 }
|
||
|
|
||
|
espUnitConfigEnergyReset OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (1),
|
||
|
reset (2),
|
||
|
notSupported (3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Setting this OID to reset (2) will cause the device energy meter value
|
||
|
to be reset to zero. Getting this OID in models that support this
|
||
|
feature will do nothing and return the noOperation(1) value. Models
|
||
|
that do not support this feature will respond to this OID with a
|
||
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
||
|
::= { espUnitConfigEntry 15 }
|
||
|
|
||
|
espUnitConfigResetNetworkManagementCard OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
noOperation (0),
|
||
|
reset (1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC."
|
||
|
::= { espUnitConfigEntry 20 }
|
||
|
|
||
|
espUnitPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspUnitPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU properties"
|
||
|
::= { espUnit 3 }
|
||
|
|
||
|
espUnitPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX EspUnitPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unit properties entry containing objects for a particular unit."
|
||
|
INDEX { espUnitPropertiesIndex }
|
||
|
::= { espUnitPropertiesTable 1 }
|
||
|
|
||
|
EspUnitPropertiesEntry ::= SEQUENCE {
|
||
|
espUnitPropertiesIndex
|
||
|
Integer32,
|
||
|
espUnitPropertiesName
|
||
|
DisplayString,
|
||
|
espUnitPropertiesOutletCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesSwitchedOutletCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesMeteredOutletCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesInputPhaseCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesCircuitBreakerCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesMaxExternalSensorCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesConnExternalSensorCount
|
||
|
Integer32,
|
||
|
espUnitPropertiesRatedVoltage
|
||
|
DisplayString,
|
||
|
espUnitPropertiesRatedMaxCurrent
|
||
|
DisplayString,
|
||
|
espUnitPropertiesRatedFrequency
|
||
|
DisplayString,
|
||
|
espUnitPropertiesRatedPower
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
espUnitPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU properties table entry"
|
||
|
::= { espUnitPropertiesEntry 1 }
|
||
|
|
||
|
espUnitPropertiesName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { espUnitPropertiesEntry 2 }
|
||
|
|
||
|
espUnitPropertiesOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of outlets on the PDU"
|
||
|
::= { espUnitPropertiesEntry 3 }
|
||
|
|
||
|
espUnitPropertiesSwitchedOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of switched outlets on the PDU"
|
||
|
::= { espUnitPropertiesEntry 4 }
|
||
|
|
||
|
espUnitPropertiesMeteredOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of metered outlets on the PDU"
|
||
|
::= { espUnitPropertiesEntry 5 }
|
||
|
|
||
|
espUnitPropertiesInputPhaseCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of phases on the PDU"
|
||
|
::= { espUnitPropertiesEntry 6 }
|
||
|
|
||
|
espUnitPropertiesCircuitBreakerCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of circuit breaker on the PDU"
|
||
|
::= { espUnitPropertiesEntry 7 }
|
||
|
|
||
|
espUnitPropertiesMaxExternalSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The maximum number of external sensors that can be connected to the PDU"
|
||
|
::= { espUnitPropertiesEntry 8 }
|
||
|
|
||
|
espUnitPropertiesConnExternalSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current number of external sensors connected to the PDU"
|
||
|
::= { espUnitPropertiesEntry 9 }
|
||
|
|
||
|
espUnitPropertiesRatedVoltage OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU voltage rating in Volts"
|
||
|
::= { espUnitPropertiesEntry 10 }
|
||
|
|
||
|
espUnitPropertiesRatedMaxCurrent OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU current rating in Amps"
|
||
|
::= { espUnitPropertiesEntry 11 }
|
||
|
|
||
|
espUnitPropertiesRatedFrequency OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU frequency rating in Hz"
|
||
|
::= { espUnitPropertiesEntry 12 }
|
||
|
|
||
|
espUnitPropertiesRatedPower OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The PDU VA (VoltAmps) rating."
|
||
|
::= { espUnitPropertiesEntry 13 }
|
||
|
|
||
|
espUnitStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspUnitStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU status information"
|
||
|
::= { espUnit 4 }
|
||
|
|
||
|
espUnitStatusEntry OBJECT-TYPE
|
||
|
SYNTAX EspUnitStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status information from the PDU being queried"
|
||
|
INDEX { espUnitStatusIndex }
|
||
|
::= { espUnitStatusTable 1 }
|
||
|
|
||
|
EspUnitStatusEntry ::= SEQUENCE {
|
||
|
espUnitStatusIndex
|
||
|
Integer32,
|
||
|
espUnitStatusName
|
||
|
DisplayString,
|
||
|
espUnitStatusLoadState
|
||
|
INTEGER,
|
||
|
espUnitStatusActivePower
|
||
|
Integer32,
|
||
|
espUnitStatusApparentPower
|
||
|
Integer32,
|
||
|
espUnitStatusEnergy
|
||
|
Integer32,
|
||
|
espUnitStatusResettableEnergy
|
||
|
Integer32,
|
||
|
espUnitStatusEnergyStartTime
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
espUnitStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU status table entry"
|
||
|
::= { espUnitStatusEntry 1 }
|
||
|
|
||
|
espUnitStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the PDU"
|
||
|
::= { espUnitStatusEntry 2 }
|
||
|
|
||
|
espUnitStatusLoadState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the present load status of the PDU based on Active Power."
|
||
|
::= { espUnitStatusEntry 3 }
|
||
|
|
||
|
espUnitStatusActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Watts(W),
|
||
|
of the PDU being queried."
|
||
|
::= { espUnitStatusEntry 4 }
|
||
|
|
||
|
espUnitStatusApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Volt-Amps(VA)
|
||
|
of the PDU load being queried."
|
||
|
::= { espUnitStatusEntry 5 }
|
||
|
|
||
|
espUnitStatusEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime."
|
||
|
::= { espUnitStatusEntry 9 }
|
||
|
|
||
|
espUnitStatusResettableEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user resettable energy meter measuring PDU energy consumption
|
||
|
in tenths of kilowatt-hours(kWh)."
|
||
|
::= { espUnitStatusEntry 10 }
|
||
|
|
||
|
espUnitStatusEnergyStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the date and time of the last device energy meter reset"
|
||
|
::= { espUnitStatusEntry 11 }
|
||
|
|
||
|
|
||
|
-- Start espInputPhase
|
||
|
espInputPhaseConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspInputPhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Input Phase configuration data"
|
||
|
::= { espInputPhase 2 }
|
||
|
|
||
|
espInputPhaseConfigEntry OBJECT-TYPE
|
||
|
SYNTAX EspInputPhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An input phase entry containing objects for a particular input phase."
|
||
|
INDEX { espUnitConfigIndex, espInputPhaseConfigIndex }
|
||
|
::= { espInputPhaseConfigTable 1 }
|
||
|
|
||
|
EspInputPhaseConfigEntry ::= SEQUENCE {
|
||
|
espInputPhaseConfigIndex
|
||
|
Integer32,
|
||
|
espInputPhaseConfigCount
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
espInputPhaseConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Input Phase configuration table entry"
|
||
|
::= { espInputPhaseConfigEntry 1 }
|
||
|
|
||
|
espInputPhaseConfigCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of Input Phases"
|
||
|
::= { espInputPhaseConfigEntry 2 }
|
||
|
|
||
|
espInputPhaseStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspInputPhaseStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Input Phase status data"
|
||
|
::= { espInputPhase 4 }
|
||
|
|
||
|
espInputPhaseStatusEntry OBJECT-TYPE
|
||
|
SYNTAX EspInputPhaseStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An input phase status entry containing objects for a particular input phase."
|
||
|
INDEX { espUnitStatusIndex, espInputPhaseStatusIndex }
|
||
|
::= { espInputPhaseStatusTable 1 }
|
||
|
|
||
|
EspInputPhaseStatusEntry ::= SEQUENCE {
|
||
|
espInputPhaseStatusIndex
|
||
|
Integer32,
|
||
|
espInputPhaseStatusCount
|
||
|
Integer32,
|
||
|
espInputPhaseStatusCurrentState
|
||
|
INTEGER,
|
||
|
espInputPhaseStatusVoltageState
|
||
|
INTEGER,
|
||
|
espInputPhaseStatusCurrent
|
||
|
Integer32,
|
||
|
espInputPhaseStatusVoltage
|
||
|
Integer32,
|
||
|
espInputPhaseStatusActivePower
|
||
|
Integer32,
|
||
|
espInputPhaseStatusApparentPower
|
||
|
Integer32,
|
||
|
espInputPhaseStatusPowerFactor
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
espInputPhaseStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Input Phase status entry"
|
||
|
::= { espInputPhaseStatusEntry 1 }
|
||
|
|
||
|
espInputPhaseStatusCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The numeric Input Phase ID"
|
||
|
::= { espInputPhaseStatusEntry 2 }
|
||
|
|
||
|
espInputPhaseStatusCurrentState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present current status of the PDU Input Phase being queried"
|
||
|
::= { espInputPhaseStatusEntry 3 }
|
||
|
|
||
|
espInputPhaseStatusVoltageState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present voltage status of the PDU Input Phase being queried"
|
||
|
::= { espInputPhaseStatusEntry 4 }
|
||
|
|
||
|
espInputPhaseStatusCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the current draw, in hundredths of Amps(A), of the load on the
|
||
|
PDU Input Phase being queried."
|
||
|
::= { espInputPhaseStatusEntry 5 }
|
||
|
|
||
|
espInputPhaseStatusVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the voltage, in Volts(V), of the PDU Input Phase being queried."
|
||
|
::= { espInputPhaseStatusEntry 6 }
|
||
|
|
||
|
espInputPhaseStatusActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Watts(W),
|
||
|
consumed on the PDU Input Phase being queried."
|
||
|
::= { espInputPhaseStatusEntry 7 }
|
||
|
|
||
|
espInputPhaseStatusApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns power consumption, in Volt-Amps(VA),
|
||
|
of the PDU Input Phase being queried."
|
||
|
::= { espInputPhaseStatusEntry 8 }
|
||
|
|
||
|
espInputPhaseStatusPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the ratio of active to apparent power of the PDU Input Phase being queried."
|
||
|
::= { espInputPhaseStatusEntry 9 }
|
||
|
|
||
|
-- Start espCircuitBreaker
|
||
|
espCircuitBreakerConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspCircuitBreakerConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU Circuit Breaker configuration data"
|
||
|
::= { espCircuitBreaker 2 }
|
||
|
|
||
|
espCircuitBreakerConfigEntry OBJECT-TYPE
|
||
|
SYNTAX EspCircuitBreakerConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker configuration entry containing objects for a particular circuit breaker."
|
||
|
INDEX { espUnitConfigIndex, espCircuitBreakerConfigIndex }
|
||
|
::= { espCircuitBreakerConfigTable 1 }
|
||
|
|
||
|
EspCircuitBreakerConfigEntry ::= SEQUENCE {
|
||
|
espCircuitBreakerConfigIndex
|
||
|
Integer32,
|
||
|
espCircuitBreakerConfigCount
|
||
|
Integer32,
|
||
|
espCircuitBreakerName
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
espCircuitBreakerConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker configuration table entry"
|
||
|
::= { espCircuitBreakerConfigEntry 1 }
|
||
|
|
||
|
espCircuitBreakerConfigCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of circuit breakers on the PDU"
|
||
|
::= { espCircuitBreakerConfigEntry 2 }
|
||
|
|
||
|
espCircuitBreakerName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The label of the circuit breaker"
|
||
|
::= { espCircuitBreakerConfigEntry 3 }
|
||
|
|
||
|
espCircuitBreakerPropertiesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspCircuitBreakerPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU circuit breaker properties"
|
||
|
::= { espCircuitBreaker 3 }
|
||
|
|
||
|
espCircuitBreakerPropertiesEntry OBJECT-TYPE
|
||
|
SYNTAX EspCircuitBreakerPropertiesEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker properties entry containing objects for a particular circuit breaker."
|
||
|
INDEX { espUnitPropertiesIndex, espCircuitBreakerPropertiesIndex }
|
||
|
::= { espCircuitBreakerPropertiesTable 1 }
|
||
|
|
||
|
EspCircuitBreakerPropertiesEntry ::= SEQUENCE {
|
||
|
espCircuitBreakerPropertiesIndex
|
||
|
Integer32,
|
||
|
espCircuitBreakerPropertiesCount
|
||
|
Integer32,
|
||
|
espCircuitBreakerPropertiesInputLayout
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
espCircuitBreakerPropertiesIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker properties table entry"
|
||
|
::= { espCircuitBreakerPropertiesEntry 1 }
|
||
|
|
||
|
espCircuitBreakerPropertiesCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of Circuit Breakers"
|
||
|
::= { espCircuitBreakerPropertiesEntry 2 }
|
||
|
|
||
|
espCircuitBreakerPropertiesInputLayout OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
seqPhase1ToNeutral (1),
|
||
|
seqPhase2ToNeutral (2),
|
||
|
seqPhase3ToNeutral (3),
|
||
|
seqPhase1ToPhase2 (4),
|
||
|
seqPhase2ToPhase3 (5),
|
||
|
seqPhase3ToPhase1 (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID describes the outlet phase connections on
|
||
|
the referenced bank as follows:
|
||
|
seqPhase1ToNeutral(1) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 1 to Neutral.
|
||
|
seqPhase2ToNeutral(2) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 2 to Neutral.
|
||
|
seqPhase3ToNeutral(3) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 3 to Neutral.
|
||
|
seqPhase1ToPhase2(4) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 1 to Phase2.
|
||
|
seqPhase2ToPhase3(5) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 2 to Phase3.
|
||
|
seqPhase3ToPhase1(6) indicates that outlets attached
|
||
|
to circuit breaker are connected from Phase 3 to Phase1. "
|
||
|
::= { espCircuitBreakerPropertiesEntry 3 }
|
||
|
|
||
|
espCircuitBreakerStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspCircuitBreakerStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU circuit breaker status data"
|
||
|
::= { espCircuitBreaker 4 }
|
||
|
|
||
|
espCircuitBreakerStatusEntry OBJECT-TYPE
|
||
|
SYNTAX EspCircuitBreakerStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A circuit breaker status entry containing objects for a particular circuit breaker."
|
||
|
INDEX { espUnitStatusIndex, espCircuitBreakerStatusIndex }
|
||
|
::= { espCircuitBreakerStatusTable 1 }
|
||
|
|
||
|
EspCircuitBreakerStatusEntry ::= SEQUENCE {
|
||
|
espCircuitBreakerStatusIndex
|
||
|
Integer32,
|
||
|
espCircuitBreakerStatusCount
|
||
|
Integer32,
|
||
|
espCircuitBreakerLabel
|
||
|
DisplayString,
|
||
|
espCircuitBreakerStatusLoadState
|
||
|
INTEGER,
|
||
|
espCircuitBreakerStatusCurrent
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
espCircuitBreakerStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU Circuit Breaker status table entry"
|
||
|
::= { espCircuitBreakerStatusEntry 1 }
|
||
|
|
||
|
espCircuitBreakerStatusCount OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of Circuit Breakers"
|
||
|
::= { espCircuitBreakerStatusEntry 2 }
|
||
|
|
||
|
espCircuitBreakerLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The label on the PDU identifying the circuit breaker"
|
||
|
::= { espCircuitBreakerStatusEntry 3 }
|
||
|
|
||
|
espCircuitBreakerStatusLoadState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
upperCritical (1),
|
||
|
upperWarning (2),
|
||
|
lowerWarning (3),
|
||
|
lowerCritical (4),
|
||
|
normal (5),
|
||
|
off (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates the present load status of the PDU Circuit
|
||
|
Breaker being queried"
|
||
|
::= { espCircuitBreakerStatusEntry 4 }
|
||
|
|
||
|
espCircuitBreakerStatusCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Returns the current draw, in hundredths of Amps(A), of the load on
|
||
|
the PDU Circuit Breaker being queried."
|
||
|
::= { espCircuitBreakerStatusEntry 5 }
|
||
|
|
||
|
-- Start espExternalSensor
|
||
|
espExternalSensorNamePlateTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspExternalSensorNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU ExternalSensorNamePlate data"
|
||
|
::= { espExternalSensor 2 }
|
||
|
|
||
|
espExternalSensorNamePlateEntry OBJECT-TYPE
|
||
|
SYNTAX EspExternalSensorNamePlateEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"External Sensor Name Plate data from the external
|
||
|
sensor being queried. The number of entries equals
|
||
|
the value of espExternalSensorNamePlateTableSize."
|
||
|
INDEX { espNamePlateIndex, espExternalSensorNamePlateIndex }
|
||
|
::= { espExternalSensorNamePlateTable 1 }
|
||
|
|
||
|
EspExternalSensorNamePlateEntry ::= SEQUENCE {
|
||
|
espExternalSensorNamePlateIndex
|
||
|
Integer32,
|
||
|
espExternalSensorNamePlateName
|
||
|
DisplayString,
|
||
|
espExternalSensorNamePlateSerialNumber
|
||
|
DisplayString,
|
||
|
espExternalSensorNamePlateType
|
||
|
INTEGER,
|
||
|
espExternalSensorNamePlateUnits
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
espExternalSensorNamePlateIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor status table entry"
|
||
|
::= { espExternalSensorNamePlateEntry 1 }
|
||
|
|
||
|
espExternalSensorNamePlateName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user-defined string identifying the external sensor"
|
||
|
::= { espExternalSensorNamePlateEntry 2 }
|
||
|
|
||
|
espExternalSensorNamePlateSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The serial number of the external sensor being queried"
|
||
|
::= { espExternalSensorNamePlateEntry 5 }
|
||
|
|
||
|
espExternalSensorNamePlateType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
temperature (1),
|
||
|
humidity (2),
|
||
|
doorSwitch (3),
|
||
|
dryContact (4),
|
||
|
spotFluid (5),
|
||
|
ropeFluid (6),
|
||
|
smoke (7),
|
||
|
beacon (8)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of external sensor."
|
||
|
::= { espExternalSensorNamePlateEntry 6 }
|
||
|
|
||
|
espExternalSensorNamePlateUnits OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
logic (0),
|
||
|
degreeC (1),
|
||
|
degreeF (2),
|
||
|
percent (3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The base units the external sensor is measured in.
|
||
|
This parameter does not apply to onOff, trip, vibration,
|
||
|
waterDetection, smokeDetection sensors. "
|
||
|
::= { espExternalSensorNamePlateEntry 7 }
|
||
|
|
||
|
espExternalSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspExternalSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU External Sensor configuration data"
|
||
|
::= { espExternalSensor 3 }
|
||
|
|
||
|
espExternalSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX EspExternalSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration data from the PDU External
|
||
|
Sensor being queried"
|
||
|
INDEX { espUnitConfigIndex, espExternalSensorConfigIndex }
|
||
|
::= { espExternalSensorConfigTable 1 }
|
||
|
|
||
|
EspExternalSensorConfigEntry ::= SEQUENCE {
|
||
|
espExternalSensorConfigIndex
|
||
|
Integer32,
|
||
|
espExternalSensorConfigAlarmState
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
espExternalSensorConfigIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor
|
||
|
configuration table entry"
|
||
|
::= { espExternalSensorConfigEntry 1 }
|
||
|
|
||
|
espExternalSensorConfigAlarmState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
on (1),
|
||
|
off (0)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"User defined alarm state of external sensor"
|
||
|
::= { espExternalSensorConfigEntry 9 }
|
||
|
|
||
|
espExternalSensorStatusTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EspExternalSensorStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of PDU External Sensor status data"
|
||
|
::= { espExternalSensor 4 }
|
||
|
|
||
|
espExternalSensorStatusEntry OBJECT-TYPE
|
||
|
SYNTAX EspExternalSensorStatusEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status data from the PDU External Sensor
|
||
|
being queried"
|
||
|
INDEX { espUnitStatusIndex, espExternalSensorStatusIndex }
|
||
|
::= { espExternalSensorStatusTable 1 }
|
||
|
|
||
|
EspExternalSensorStatusEntry ::= SEQUENCE {
|
||
|
espExternalSensorStatusIndex
|
||
|
Integer32,
|
||
|
espExternalSensorStatusName
|
||
|
DisplayString,
|
||
|
espExternalSensorStatusAisle
|
||
|
INTEGER,
|
||
|
espExternalSensorStatusCommStatus
|
||
|
INTEGER,
|
||
|
espExternalSensorStatusState
|
||
|
INTEGER,
|
||
|
espExternalSensorStatusValue
|
||
|
Integer32,
|
||
|
espExternalSensorStatusHighPrecisionValue
|
||
|
Integer32
|
||
|
}
|
||
|
|
||
|
espExternalSensorStatusIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (0..255)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the PDU External Sensor status table entry"
|
||
|
::= { espExternalSensorStatusEntry 1 }
|
||
|
|
||
|
espExternalSensorStatusName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-defined name for the External Sensor"
|
||
|
::= { espExternalSensorStatusEntry 2 }
|
||
|
|
||
|
espExternalSensorStatusAisle OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
hotAisle (1),
|
||
|
coldAisle (2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Indicates whether the external sensor is
|
||
|
in a hot or cold aisle"
|
||
|
::= { espExternalSensorStatusEntry 3 }
|
||
|
|
||
|
espExternalSensorStatusCommStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
notInstalled (1),
|
||
|
commsOk (2),
|
||
|
commsLost (3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The communications status of the sensor"
|
||
|
::= { espExternalSensorStatusEntry 4 }
|
||
|
|
||
|
espExternalSensorStatusState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
notPresent (0), alarmed (1), normal (2), belowLowerCritical (3), belowLowerWarning (4), aboveUpperWarning (5), aboveUpperCritical (6)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"This OID reports the current state of the sensor.
|
||
|
A notPresent (0) response indicates that no sensor is attached.
|
||
|
An alarmed (1) response indicates that the sensor is present
|
||
|
and its measured reading indicates alarmed.
|
||
|
A normal (2) response indicates that the sensor is present
|
||
|
and its measured reading lies within all thresholds.
|
||
|
A belowLowerCritical (3) response indicates that the sensor
|
||
|
is present and its measured reading lies below the lower critical threshold.
|
||
|
A belowLowerWarning (4) response indicates that the sensor
|
||
|
is present and its measured reading lies below the lower warning threshold.
|
||
|
An aboveUpperWarning (5) response indicates that the sensor
|
||
|
is present and its measured reading lies above the upper warning threshold.
|
||
|
An aboveUpperCritical (6) response indicates that the sensor
|
||
|
is present and its measured reading lies above the upper critical threshold."
|
||
|
::= { espExternalSensorStatusEntry 5 }
|
||
|
|
||
|
espExternalSensorStatusValue OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Sensor reading in espExternalSensorConfigUnits value."
|
||
|
::= { espExternalSensorStatusEntry 6 }
|
||
|
|
||
|
espExternalSensorStatusHighPrecisionValue OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor reading in tenths of espExternalSensorConfigUnits value.
|
||
|
This OID is applied to temperature sensor only"
|
||
|
::= { espExternalSensorStatusEntry 8 }
|
||
|
|
||
|
|
||
|
-- Traps Information
|
||
|
|
||
|
espTrapsInfoIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32 (1..256)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The index of the traps table entry"
|
||
|
::= { espTraps 1 }
|
||
|
|
||
|
|
||
|
espUserName OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user currently logged in."
|
||
|
::= { espTraps 2 }
|
||
|
|
||
|
espFirmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The version of Firmware."
|
||
|
::= { espTraps 4 }
|
||
|
|
||
|
espIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unique value for PDU. Its value ranges between 1
|
||
|
and the value of PDU count"
|
||
|
::= { espTraps 5 }
|
||
|
|
||
|
espExternalSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A unique value for each sensor. Its value ranges between 1
|
||
|
and the value of external sensor count."
|
||
|
::= { espTraps 6 }
|
||
|
|
||
|
espErrorDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
MAX-ACCESS accessible-for-notify
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Description of the Error"
|
||
|
::= { espTraps 7 }
|
||
|
|
||
|
espNetworkCardStart NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The network card has started"
|
||
|
::= { espTraps 8 }
|
||
|
|
||
|
espNetworkCardReset NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The network card was reset via the web or command line interface."
|
||
|
::= { espTraps 9}
|
||
|
|
||
|
|
||
|
espFirmwareUpdateCompleted NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
firmwareVersion,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The firmware update has completed."
|
||
|
::= { espTraps 10 }
|
||
|
|
||
|
espUserPasswordChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
userUpdated,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A user password was changed. "
|
||
|
::= { espTraps 11 }
|
||
|
|
||
|
|
||
|
espLogFileCleared NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The log file has been cleared."
|
||
|
::= { espTraps 12 }
|
||
|
|
||
|
espConfigurationFileExported NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU configuration file was exported"
|
||
|
::= { espTraps 13 }
|
||
|
|
||
|
espUnitActivePowerStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
espUnitStatusLoadState,
|
||
|
espUnitStatusActivePower,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU unit active power state changes."
|
||
|
::= { espTraps 14 }
|
||
|
|
||
|
espInputphaseVoltageStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
espInputPhaseStatusCount,
|
||
|
espInputPhaseStatusVoltageState,
|
||
|
espInputPhaseStatusVoltage,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU input phase voltage state changes."
|
||
|
::= { espTraps 15 }
|
||
|
|
||
|
espInputphaseCurrentStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
espInputPhaseStatusCount,
|
||
|
espInputPhaseStatusCurrentState,
|
||
|
espInputPhaseStatusCurrent,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU input phase Current state changes."
|
||
|
::= { espTraps 16 }
|
||
|
|
||
|
espCircuitBreakerCurrentStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
espCircuitBreakerStatusIndex,
|
||
|
espCircuitBreakerStatusLoadState,
|
||
|
espCircuitBreakerStatusCurrent,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Circuit Breaker Current state changes."
|
||
|
::= { espTraps 17 }
|
||
|
|
||
|
espExternalSensorStateChange NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
espExternalSensorStatusIndex,
|
||
|
espExternalSensorStatusName,
|
||
|
espExternalSensorNamePlateType,
|
||
|
espExternalSensorStatusAisle,
|
||
|
espExternalSensorNamePlateUnits,
|
||
|
espExternalSensorStatusState,
|
||
|
espExternalSensorStatusValue,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU External Sensor state changes."
|
||
|
::= { espTraps 18 }
|
||
|
|
||
|
espConfigurationFileImported NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU configuration file was imported"
|
||
|
::= { espTraps 19 }
|
||
|
espNetworkUp NOTIFICATION-TYPE
|
||
|
OBJECTS { espIndex,
|
||
|
espNamePlateName,
|
||
|
userName,
|
||
|
espNamePlateInetAddressType,
|
||
|
espNamePlateIPAddress,
|
||
|
sysContact,
|
||
|
sysName,
|
||
|
sysLocation }
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"PDU Network is up "
|
||
|
::= { espTraps 20 }
|
||
|
END
|