1581 lines
50 KiB
Plaintext
1581 lines
50 KiB
Plaintext
|
-- Jacarta interSeptor MIB
|
||
|
-- MIB for interSeptor Environmental Monitoring System
|
||
|
--
|
||
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) jacarta(19011)
|
||
|
-- product(1) webAppliance(3) inSept(1)
|
||
|
-- ==============================================================================================
|
||
|
---
|
||
|
--- Revision History
|
||
|
---
|
||
|
--- V1.00 - Initial Release - July 03
|
||
|
--- V1.01 - Minor SNMP bug fix - Aug 03
|
||
|
--- v1.10 - Add temperature unit object - Oct, 15 2004
|
||
|
--- Add date format object
|
||
|
--- Add inSeptConfigAccessControlTable
|
||
|
--- Add object
|
||
|
--- v1.11 Change interSeptor-MIB to InterSeptor-MIB - Dec, 20 2004
|
||
|
--- Updated InSeptsensorConfigSensorEntry and SensorMonitorSensorEntry
|
||
|
--- V1.12 - Modified syntax error - May, 10 2005
|
||
|
--- Fixed SYNTAX InSeptConfigTrapsReceiversEntry
|
||
|
--- Changed SYNTAX inSeptConfigTrapsReceiversEntry to SYNTAX InSeptConfigTrapsReceiversEntry
|
||
|
--- V1.13 - Modified syntax error - June, 27 2006
|
||
|
--- Check error form http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/
|
||
|
--- ===========================================================================================
|
||
|
InterSeptor-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
enterprises
|
||
|
FROM RFC1155-SMI
|
||
|
OBJECT-TYPE
|
||
|
FROM RFC-1212
|
||
|
DisplayString
|
||
|
FROM RFC1213-MIB
|
||
|
TRAP-TYPE
|
||
|
FROM RFC-1215;
|
||
|
|
||
|
jacarta OBJECT IDENTIFIER ::= { enterprises 19011 }
|
||
|
product OBJECT IDENTIFIER ::= { jacarta 1 }
|
||
|
webAppliance OBJECT IDENTIFIER ::= { product 3 }
|
||
|
inSept OBJECT IDENTIFIER ::= { webAppliance 1}
|
||
|
inSeptObjects OBJECT IDENTIFIER ::= { inSept 1 }
|
||
|
inSeptTraps OBJECT IDENTIFIER ::= { inSept 2 }
|
||
|
|
||
|
inSeptIdent OBJECT IDENTIFIER ::= { inSeptObjects 1 }
|
||
|
inSeptConfig OBJECT IDENTIFIER ::= { inSeptObjects 2 }
|
||
|
inSeptsensorMonitor OBJECT IDENTIFIER ::= { inSeptObjects 3 }
|
||
|
inSeptsensorConfig OBJECT IDENTIFIER ::= { inSeptObjects 4 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- inSeptIdentification
|
||
|
--
|
||
|
-- All objects in this group except for inSeptIdentName and
|
||
|
-- inSeptIdentAttachedDevices are set at device initialization
|
||
|
-- and remain static.
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
inSeptIdentManufacturer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..31))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of the interSeptor manufacturer."
|
||
|
::= { inSeptIdent 1 }
|
||
|
|
||
|
inSeptIdentModel OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..63))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The interSeptor Model designation."
|
||
|
::= { inSeptIdent 2 }
|
||
|
|
||
|
inSeptIdentAgentSoftwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The interSeptor software/firmware version."
|
||
|
::= { inSeptIdent 3 }
|
||
|
|
||
|
inSeptIdentName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A string identifying the interSeptor. This object should be
|
||
|
set by the administrator."
|
||
|
::= { inSeptIdent 4 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- inSeptConfig
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
inSeptConfigMibVersion OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The version of MIB spec."
|
||
|
::= { inSeptConfig 1}
|
||
|
|
||
|
inSeptConfigNetwork OBJECT IDENTIFIER ::= { inSeptConfig 2 }
|
||
|
|
||
|
inSeptConfigIpAddress OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The ip address that NMS can identify the managed
|
||
|
device"
|
||
|
::= { inSeptConfigNetwork 1 }
|
||
|
|
||
|
inSeptConfigGateway OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The default gateway that allows the device to be managed
|
||
|
through routers "
|
||
|
::= { inSeptConfigNetwork 2 }
|
||
|
|
||
|
inSeptConfigSubnetMask OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" Internet address subnet mask"
|
||
|
::= { inSeptConfigNetwork 3 }
|
||
|
|
||
|
inSeptConfigDateTime OBJECT IDENTIFIER ::= { inSeptConfig 3 }
|
||
|
|
||
|
inSeptConfigDate OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (10..10))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The date in inSept, format is (dd/mm/yyyy)"
|
||
|
::= { inSeptConfigDateTime 1}
|
||
|
|
||
|
inSeptConfigTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (8..8))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time in interSeptor, format is (hh:mm:ss)"
|
||
|
::= { inSeptConfigDateTime 2}
|
||
|
|
||
|
inSeptConfigTimeFromNtp OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable update date/time from NTP server."
|
||
|
::= { inSeptConfigDateTime 3}
|
||
|
|
||
|
inSeptConfigNtpIpAddress OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"NTP IP address."
|
||
|
::= { inSeptConfigDateTime 4}
|
||
|
|
||
|
inSeptConfigNtpTimeZone OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
gMT-1200(1),
|
||
|
gMT-1100(2),
|
||
|
gMT-1000(3),
|
||
|
gMT-0900(4),
|
||
|
gMT-0800(5),
|
||
|
gMT-0700(6),
|
||
|
gMT-0600(7),
|
||
|
gMT-0500(8),
|
||
|
gMT-0400(9),
|
||
|
gMT-0330(10),
|
||
|
gMT-0300(11),
|
||
|
gMT-0200(12),
|
||
|
gMT-0100(13),
|
||
|
gMT-0000(14),
|
||
|
gMT0100(15),
|
||
|
gMT0200(16),
|
||
|
gMT0300(17),
|
||
|
gMT0330(18),
|
||
|
gMT0400(19),
|
||
|
gMT0500(20),
|
||
|
gMT0530(21),
|
||
|
gMT0600(22),
|
||
|
gMT0700(23),
|
||
|
gMT0800(24),
|
||
|
gMT0900(25),
|
||
|
gMT1000(26),
|
||
|
gMT1100(27),
|
||
|
gMT1200(28)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable update date/time from NTP server."
|
||
|
::= { inSeptConfigDateTime 5}
|
||
|
|
||
|
inSeptConfigDayLightSaving OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set
|
||
|
set one hour in advance to reflect daylight saving status."
|
||
|
::= { inSeptConfigDateTime 6}
|
||
|
|
||
|
inSeptConfigLog OBJECT IDENTIFIER ::= { inSeptConfig 4 }
|
||
|
|
||
|
inSeptConfigHistoryLogFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER (5..3600) -- in seconds
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The frequency of the update of the history log. The value
|
||
|
is in seconds"
|
||
|
::= { inSeptConfigLog 1}
|
||
|
|
||
|
inSeptConfigExtHistoryLogFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..1440) -- in minutes
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The frequency of the update of the extended history log.
|
||
|
The value is in seconds"
|
||
|
::= { inSeptConfigLog 2}
|
||
|
|
||
|
inSeptConfigConfigurationLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" Enable/disable inSept to log parameter change."
|
||
|
::= { inSeptConfigLog 3}
|
||
|
|
||
|
inSeptConfigDhcpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable DHCP/BootP capability"
|
||
|
::= { inSeptConfig 5}
|
||
|
|
||
|
inSeptConfigPingStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable Ping Echo capability"
|
||
|
::= { inSeptConfig 6}
|
||
|
|
||
|
inSeptConfigTftpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable TFTP network upgrade capability"
|
||
|
::= { inSeptConfig 7}
|
||
|
|
||
|
inSeptConfigTelnet OBJECT IDENTIFIER ::= { inSeptConfig 8 }
|
||
|
|
||
|
inSeptConfigTelnetStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable telnet access"
|
||
|
::= { inSeptConfigTelnet 1}
|
||
|
|
||
|
inSeptConfigTelnetPortNumber OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..65535)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setting the server port of telnet."
|
||
|
::= { inSeptConfigTelnet 2}
|
||
|
|
||
|
inSeptConfigHttp OBJECT IDENTIFIER ::= { inSeptConfig 9 }
|
||
|
|
||
|
inSeptConfigHttpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable HTTP access"
|
||
|
::= { inSeptConfigHttp 1}
|
||
|
|
||
|
inSeptConfigHttpPortNumber OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..65535)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setting the server port of HTTP."
|
||
|
::= { inSeptConfigHttp 2}
|
||
|
|
||
|
inSeptConfigHttpSecurity OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable HTTP access for read-only users"
|
||
|
::= { inSeptConfigHttp 3}
|
||
|
|
||
|
|
||
|
inSeptConfigSnmp OBJECT IDENTIFIER ::= { inSeptConfig 10 }
|
||
|
inSeptConfigSnmpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable SNMP access"
|
||
|
::= { inSeptConfigSnmp 1}
|
||
|
|
||
|
inSeptConfigSnmpPortNumber OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..65535)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setting the server port of SNMP."
|
||
|
::= { inSeptConfigSnmp 2}
|
||
|
|
||
|
inSeptConfigControl OBJECT IDENTIFIER ::= { inSeptConfig 11 }
|
||
|
inSeptConfigResetToDefault OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
reset(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Reset all parameters of interSeptor to default value"
|
||
|
::= { inSeptConfigControl 1}
|
||
|
|
||
|
inSeptConfigRestart OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
restart(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Restart interSeptor"
|
||
|
::= { inSeptConfigControl 2}
|
||
|
|
||
|
inSeptConfigTrap OBJECT IDENTIFIER ::= { inSeptConfig 12 }
|
||
|
inSeptConfigTrapRetryCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The count of repeat traps to send to NMS before trap
|
||
|
acknowledgement is received."
|
||
|
::= { inSeptConfigTrap 1}
|
||
|
|
||
|
inSeptConfigTrapRetryTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time between retrying to send traps to NMS."
|
||
|
::= { inSeptConfigTrap 2}
|
||
|
|
||
|
inSeptConfigTrapAckSignature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The signature of trap acknowledgement."
|
||
|
::= { inSeptConfigTrap 3}
|
||
|
|
||
|
|
||
|
inSeptConfigPollRate OBJECT-TYPE
|
||
|
SYNTAX INTEGER (3..60)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The frequency that interSeptor updates readings from sensors
|
||
|
(unit : second)."
|
||
|
::= { inSeptConfig 13}
|
||
|
|
||
|
inSeptConfigTrapsReceiversTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF InSeptConfigTrapsReceiversEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of managers to send traps to. The number of
|
||
|
entries is given by the value of inSeptConfigNumTrapReceivers"
|
||
|
::= { inSeptConfig 14}
|
||
|
|
||
|
inSeptConfigTrapsReceiversEntry OBJECT-TYPE
|
||
|
SYNTAX InSeptConfigTrapsReceiversEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The managers to send traps to."
|
||
|
INDEX { inSepttrapsIndex}
|
||
|
::= { inSeptConfigTrapsReceiversTable 1 }
|
||
|
|
||
|
InSeptConfigTrapsReceiversEntry ::=
|
||
|
SEQUENCE {
|
||
|
inSepttrapsIndex
|
||
|
INTEGER,
|
||
|
inSepttrapsReceiverAddr
|
||
|
IpAddress,
|
||
|
inSeptreceiverCommunityString
|
||
|
DisplayString,
|
||
|
inSeptreceiverSeverityLevel
|
||
|
INTEGER,
|
||
|
inSeptreceiverDescription
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
inSepttrapsIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..2147483647)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a trap receiver entry."
|
||
|
::= { inSeptConfigTrapsReceiversEntry 1 }
|
||
|
|
||
|
inSepttrapsReceiverAddr OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The IP address of the manager to send a trap to."
|
||
|
::= { inSeptConfigTrapsReceiversEntry 2 }
|
||
|
|
||
|
inSeptreceiverCommunityString OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..19))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The community name to use in the trap when
|
||
|
sent to the manager."
|
||
|
::= { inSeptConfigTrapsReceiversEntry 3 }
|
||
|
|
||
|
inSeptreceiverSeverityLevel OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
informational(1),
|
||
|
warning(2),
|
||
|
severe(3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The severity level of traps to be received by this manager."
|
||
|
::= { inSeptConfigTrapsReceiversEntry 4 }
|
||
|
|
||
|
inSeptreceiverDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of trap receivers"
|
||
|
::= { inSeptConfigTrapsReceiversEntry 5 }
|
||
|
|
||
|
inSeptConfigAccessControlTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF InSeptConfigAccessControlEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of managers which can access interSeptor with private
|
||
|
community string."
|
||
|
::= { inSeptConfig 15}
|
||
|
|
||
|
inSeptConfigAccessControlEntry OBJECT-TYPE
|
||
|
SYNTAX InSeptConfigAccessControlEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The managers."
|
||
|
INDEX { accessIndex}
|
||
|
::= { inSeptConfigAccessControlTable 1 }
|
||
|
|
||
|
InSeptConfigAccessControlEntry ::=
|
||
|
SEQUENCE {
|
||
|
accessIndex
|
||
|
INTEGER,
|
||
|
accessControlAddr
|
||
|
IpAddress,
|
||
|
accessCommunityString
|
||
|
DisplayString,
|
||
|
accessControlMode
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
accessIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..2147483647)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a access control entry."
|
||
|
::= { inSeptConfigAccessControlEntry 1 }
|
||
|
|
||
|
accessControlAddr OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The IP address of the manager to access interSeptor"
|
||
|
::= { inSeptConfigAccessControlEntry 2 }
|
||
|
|
||
|
accessCommunityString OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..19))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The community name to use in the manager when
|
||
|
access interSeptor"
|
||
|
::= { inSeptConfigAccessControlEntry 3 }
|
||
|
|
||
|
accessControlMode OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
readOnly (1),
|
||
|
read-write (2),
|
||
|
notAccess (3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Access type, only read/Write access type can change parameter
|
||
|
of interSeptor"
|
||
|
::= { inSeptConfigAccessControlEntry 4 }
|
||
|
|
||
|
|
||
|
inSeptConfigTemperatureUnit OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
celsius(1),
|
||
|
fahrenheit(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The temperature unit of the system, can be Celsius or Farenheit"
|
||
|
::= { inSeptConfig 16}
|
||
|
|
||
|
inSeptConfigDateFormat OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
dd-mm-yyyy(1),
|
||
|
mm-dd-yyyy(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
|
||
|
::= { inSeptConfig 17}
|
||
|
|
||
|
|
||
|
-- Sensor Monitoring
|
||
|
|
||
|
inSeptsensorMonitorSensorNumber OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The number of sensors that can be monitored."
|
||
|
::= { inSeptsensorMonitor 1}
|
||
|
|
||
|
inSeptsensorMonitorSensorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF SensorMonitorSensorEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of sensor devices to be monitored."
|
||
|
::= { inSeptsensorMonitor 2}
|
||
|
|
||
|
inSeptsensorMonitorSensorEntry OBJECT-TYPE
|
||
|
SYNTAX SensorMonitorSensorEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The sensor device."
|
||
|
INDEX { inSeptsensorMonitorDeviceIndex}
|
||
|
::= { inSeptsensorMonitorSensorTable 1 }
|
||
|
|
||
|
SensorMonitorSensorEntry ::=
|
||
|
SEQUENCE {
|
||
|
inSeptsensorMonitorDeviceIndex
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorDeviceStatus
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorDeviceTemperature
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorDeviceTemperatureAlarm
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorDeviceHumidity
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorDeviceHumidityAlarm
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorAlarm1
|
||
|
INTEGER,
|
||
|
inSeptsensorMonitorAlarm2
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
inSeptsensorMonitorDeviceIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..2147483647)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a sensor device entry."
|
||
|
::= { inSeptsensorMonitorSensorEntry 1 }
|
||
|
|
||
|
inSeptsensorMonitorDeviceStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
eMD-HT(3),
|
||
|
eMD-T(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device type connected to interSeptor."
|
||
|
::= { inSeptsensorMonitorSensorEntry 2 }
|
||
|
|
||
|
inSeptsensorMonitorDeviceTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The temperature of sensor on device interSeptor, the unit is 0.1 degree."
|
||
|
::= { inSeptsensorMonitorSensorEntry 3 }
|
||
|
|
||
|
inSeptsensorMonitorDeviceTemperatureAlarm OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
normal(3),
|
||
|
lowWarning(4),
|
||
|
lowCritical(5),
|
||
|
highWarning(6),
|
||
|
highCritical(7)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The alarm type of sensor on device interSeptor."
|
||
|
::= { inSeptsensorMonitorSensorEntry 4 }
|
||
|
|
||
|
inSeptsensorMonitorDeviceHumidity OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The humidity of sensor on device interSeptor, the unit is 0.1%."
|
||
|
::= { inSeptsensorMonitorSensorEntry 5 }
|
||
|
|
||
|
inSeptsensorMonitorDeviceHumidityAlarm OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
normal(3),
|
||
|
lowWarning(4),
|
||
|
lowCritical(5),
|
||
|
highWarning(6),
|
||
|
highCritical(7)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The alarm type of sensor on device interSeptor."
|
||
|
::= { inSeptsensorMonitorSensorEntry 6 }
|
||
|
|
||
|
inSeptsensorMonitorAlarm1 OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
active(3),
|
||
|
inactive(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device status of sensor 1 connected to interSeptor."
|
||
|
::= { inSeptsensorMonitorSensorEntry 7 }
|
||
|
|
||
|
inSeptsensorMonitorAlarm2 OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
active(3),
|
||
|
inactive(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device status of sensor 2 connected to interSeptor."
|
||
|
::= { inSeptsensorMonitorSensorEntry 8 }
|
||
|
|
||
|
-- Sensor Configuration
|
||
|
|
||
|
inSeptsensorConfigSensorNumber OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The number of sensors that are connected to interSeptor."
|
||
|
::= { inSeptsensorConfig 1 }
|
||
|
|
||
|
inSeptsensorConfigSensorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF InSeptsensorConfigSensorEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of sensor devices to be configured."
|
||
|
::= { inSeptsensorConfig 2 }
|
||
|
|
||
|
inSeptsensorConfigSensorEntry OBJECT-TYPE
|
||
|
SYNTAX InSeptsensorConfigSensorEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The sensor device."
|
||
|
INDEX { inSeptsensorConfigDeviceIndex }
|
||
|
::= { inSeptsensorConfigSensorTable 1 }
|
||
|
|
||
|
InSeptsensorConfigSensorEntry ::=
|
||
|
SEQUENCE {
|
||
|
inSeptsensorConfigDeviceIndex
|
||
|
INTEGER,
|
||
|
inSeptsensorConfigDeviceName
|
||
|
DisplayString,
|
||
|
inSeptsensorConfigDeviceState
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
inSeptsensorConfigDeviceIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..2147483647)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a sensor device entry."
|
||
|
::= { inSeptsensorConfigSensorEntry 1 }
|
||
|
|
||
|
inSeptsensorConfigDeviceName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of the sensor device for identification."
|
||
|
::= { inSeptsensorConfigSensorEntry 2 }
|
||
|
|
||
|
inSeptsensorConfigDeviceState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
auto(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The setup of sensor device type."
|
||
|
::= { inSeptsensorConfigSensorEntry 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1 OBJECT IDENTIFIER ::= { inSeptsensorConfig 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1DeviceName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of sensor device."
|
||
|
::= { inSeptsensorConfigSensor1 1}
|
||
|
|
||
|
inSeptsensorConfigSensor1DeviceState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
auto(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The setup of sensor device type."
|
||
|
::= { inSeptsensorConfigSensor1 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor name."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureLowWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 2 }
|
||
|
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureLowCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureHighWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureHighCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureHysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to prevent too many alarms when temperature is hovering around the
|
||
|
set threshold."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureCalibration OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
temperatureIncrease0Point0(1),
|
||
|
temperatureIncrease0Point5(2),
|
||
|
temperatureIncrease1Point0(3),
|
||
|
temperatureIncrease1Point5(4),
|
||
|
temperatureIncrease2Point0(5),
|
||
|
temperatureIncrease2Point5(6),
|
||
|
temperatureIncrease3Point0(7),
|
||
|
temperatureMinus0Point5(8),
|
||
|
temperatureMinus1Point0(9),
|
||
|
temperatureMinus1Point5(10),
|
||
|
temperatureMinus2Point0(11),
|
||
|
temperatureMinus2Point5(12),
|
||
|
temperatureMinusPoint0(13)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to get the correct temperature according to your reference temperature."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 7 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureLowWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 8 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureLowCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 9 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureHighWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 10 }
|
||
|
|
||
|
inSeptsensorConfigSensor1TemperatureHighCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Temperature 11 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumdityName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor name."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityLowWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 2 }
|
||
|
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityLowCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshole to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityHighWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityHighCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityHysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to prevent too many alarms when Humidity is hovering around the
|
||
|
set threshold."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityCalibration OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
humidityIncrease0Point0(1),
|
||
|
humidityIncrease1Point0(2),
|
||
|
humidityIncrease2Point0(3),
|
||
|
humidityIncrease3Point0(4),
|
||
|
humidityIncrease4Point0(5),
|
||
|
humidityIncrease5Point0(6),
|
||
|
humidityIncrease6Point0(7),
|
||
|
humidityMinus1Point0(8),
|
||
|
humidityMinus2Point0(9),
|
||
|
humidityMinus3Point0(10),
|
||
|
humidityMinus4Point0(11),
|
||
|
humidityMinus5Point0(12),
|
||
|
humidityMinus6Point0(13)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to get the correct temperature according to your reference temperature."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 7 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityLowWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 8 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityLowCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 9 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityHighWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 10 }
|
||
|
|
||
|
inSeptsensorConfigSensor1HumidityHighCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor1Humidity 11 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of alarm-1."
|
||
|
::= { inSeptsensorConfigSensor1Alarm1 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm1State OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
normalOpen(2),
|
||
|
normalClose(3),
|
||
|
highActive(4),
|
||
|
lowActive(5)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setup the signal type to trigger alarm."
|
||
|
::= { inSeptsensorConfigSensor1Alarm1 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm1Hysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to delay the alarm triggered when event occurs."
|
||
|
::= { inSeptsensorConfigSensor1Alarm1 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of alarm-1."
|
||
|
::= { inSeptsensorConfigSensor1Alarm2 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm2State OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
normalOpen(2),
|
||
|
normalClose(3),
|
||
|
highActive(4),
|
||
|
lowActive(5)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setup the signal type to trigger alarm."
|
||
|
::= { inSeptsensorConfigSensor1Alarm2 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor1Alarm2Hysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to delay the alarm triggered when event occurs."
|
||
|
::= { inSeptsensorConfigSensor1Alarm2 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor2 OBJECT IDENTIFIER ::= { inSeptsensorConfig 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor2DeviceName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of sensor device."
|
||
|
::= { inSeptsensorConfigSensor2 1}
|
||
|
|
||
|
inSeptsensorConfigSensor2DeviceState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
auto(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The setup of sensor device type."
|
||
|
::= { inSeptsensorConfigSensor2 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The temperature sensor name."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureLowWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 2 }
|
||
|
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureLowCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureHighWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureHighCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureHysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to prevent too many alarms when temperature is hovering around the
|
||
|
set threshold."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureCalibration OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
temperatureIncrease0Point0(1),
|
||
|
temperatureIncrease0Point5(2),
|
||
|
temperatureIncrease1Point0(3),
|
||
|
temperatureIncrease1Point5(4),
|
||
|
temperatureIncrease2Point0(5),
|
||
|
temperatureIncrease2Point5(6),
|
||
|
temperatureIncrease3Point0(7),
|
||
|
temperatureMinus0Point5(8),
|
||
|
temperatureMinus1Point0(9),
|
||
|
temperatureMinus1Point5(10),
|
||
|
temperatureMinus2Point0(11),
|
||
|
temperatureMinus2Point5(12),
|
||
|
temperatureMinusPoint0(13)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to get the correct temperature according to your reference temperature."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 7 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureLowWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 8 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureLowCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 9 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureHighWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 10 }
|
||
|
|
||
|
inSeptsensorConfigSensor2TemperatureHighCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Temperature 11 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumdityName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The humidity sensor name."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityLowWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 2 }
|
||
|
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityLowCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityHighWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 4 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityHighCritical OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The threshold to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityHysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to prevent too many alarms when Humidity is hovering around the
|
||
|
set threshold."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityCalibration OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
humidityIncrease0Point0(1),
|
||
|
humidityIncrease1Point0(2),
|
||
|
humidityIncrease2Point0(3),
|
||
|
humidityIncrease3Point0(4),
|
||
|
humidityIncrease4Point0(5),
|
||
|
humidityIncrease5Point0(6),
|
||
|
humidityIncrease6Point0(7),
|
||
|
humidityMinus1Point0(8),
|
||
|
humidityMinus2Point0(9),
|
||
|
humidityMinus3Point0(10),
|
||
|
humidityMinus4Point0(11),
|
||
|
humidityMinus5Point0(12),
|
||
|
humidityMinus6Point0(13)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to get the correct temperature according to your reference temperature."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 7 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityLowWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 8 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityLowCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger low critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 9 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityHighWarningStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high warning alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 10 }
|
||
|
|
||
|
inSeptsensorConfigSensor2HumidityHighCriticalStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable/disable the set point to trigger high critical alarm."
|
||
|
::= { inSeptsensorConfigSensor2Humidity 11 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 5 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of alarm-1."
|
||
|
::= { inSeptsensorConfigSensor2Alarm1 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm1State OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
normalOpen(2),
|
||
|
normalClose(3),
|
||
|
highActive(4),
|
||
|
lowActive(5)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setup the signal type to trigger alarm."
|
||
|
::= { inSeptsensorConfigSensor2Alarm1 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm1Hysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to delay the alarm triggered when event occurs."
|
||
|
::= { inSeptsensorConfigSensor2Alarm1 3 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 6 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of alarm-1."
|
||
|
::= { inSeptsensorConfigSensor2Alarm2 1 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm2State OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
normalOpen(2),
|
||
|
normalClose(3),
|
||
|
highActive(4),
|
||
|
lowActive(5)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setup the signal type to trigger alarm."
|
||
|
::= { inSeptsensorConfigSensor2Alarm2 2 }
|
||
|
|
||
|
inSeptsensorConfigSensor2Alarm2Hysteresis OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set value to delay the alarm triggered when event occurs."
|
||
|
::= { inSeptsensorConfigSensor2Alarm2 3 }
|
||
|
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- inSeptTraps
|
||
|
--
|
||
|
-- Traps group
|
||
|
-- ===========================================================================
|
||
|
-- This section defines the well-known notifications sent by
|
||
|
-- inSept agents.
|
||
|
-- Care must be taken to ensure that no particular notification
|
||
|
-- is sent to a single receiving entity more often than once
|
||
|
-- every five seconds.
|
||
|
|
||
|
inSeptCommunicationRestored TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Communication between interSeptor and sensor has been
|
||
|
established."
|
||
|
::= 1
|
||
|
|
||
|
inSeptCommunicationLost TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: Communication between interSeptor and sensor has been
|
||
|
lost."
|
||
|
::= 2
|
||
|
|
||
|
inSeptAlarm1Inactive TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Alarm1 of sensor has returned from active state."
|
||
|
::= 3
|
||
|
|
||
|
inSeptAlarm1Active TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: Alarm1 has become active."
|
||
|
::= 4
|
||
|
|
||
|
inSeptAlarm2Inactive TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Alarm2 of sensor has returned from active state."
|
||
|
::= 5
|
||
|
|
||
|
inSeptAlarm2Active TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: Alarm2 has become active."
|
||
|
::= 6
|
||
|
|
||
|
inSeptTemperatureNotHighWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The temperature of sensor has returned from High warning to normal."
|
||
|
::= 7
|
||
|
|
||
|
inSeptTemperatureHighWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: The temperature of sensor is higher than High warning set point."
|
||
|
::= 8
|
||
|
|
||
|
inSeptTemperatureNotLowWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The temperature of sensor has returned from low warning to normal."
|
||
|
::= 9
|
||
|
|
||
|
inSeptTemperatureLowWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: The temperature of sensor is lower than low warning set point."
|
||
|
::= 10
|
||
|
|
||
|
inSeptTemperatureNotHighCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The temperature of sensor is lower than high critical set point."
|
||
|
::= 11
|
||
|
|
||
|
inSeptTemperatureHighCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"CRITICAL: The temperature of sensor is higher than high critical set point."
|
||
|
::= 12
|
||
|
|
||
|
inSeptTemperatureNotLowCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The temperature of sensor is higher than low critical set point."
|
||
|
::= 13
|
||
|
|
||
|
inSeptTemperatureLowCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"CRITICAL: The temperature of sensor is lower than low critical set point."
|
||
|
::= 14
|
||
|
|
||
|
inSeptHumidityNotHighWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The humidity of sensor has returned from High warning to normal."
|
||
|
::= 15
|
||
|
|
||
|
inSeptHumidityHighWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: The humidity of sensor is higher than High warning set point."
|
||
|
::= 16
|
||
|
|
||
|
inSeptHumidityNotLowWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The humidity of sensor has returned from low warning to normal."
|
||
|
::= 17
|
||
|
|
||
|
inSeptHumidityLowWarning TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"WARNING: The humidity of sensor is lower than low warning set point."
|
||
|
::= 18
|
||
|
|
||
|
inSeptHumidityNotHighCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The humidity of sensor is lower than high critical set point."
|
||
|
::= 19
|
||
|
|
||
|
inSeptHumidityHighCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"CRITICAL: The humidity of sensor is higher than high critical set point."
|
||
|
::= 20
|
||
|
|
||
|
inSeptHumidityNotLowCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The humidity of sensor is higher than low critical set point."
|
||
|
::= 21
|
||
|
|
||
|
inSeptHumidityLowCritical TRAP-TYPE
|
||
|
ENTERPRISE inSeptTraps
|
||
|
DESCRIPTION
|
||
|
"CRITICAL: The humidity of sensor is lower than low critical set point."
|
||
|
::= 22
|
||
|
|
||
|
END
|
||
|
|