-- Copyright(C) 2003-2016 Server Technology, Inc.
|
||
|
--
|
||
|
|
||
|
Sentry3-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
MODULE-IDENTITY, NOTIFICATION-TYPE,
|
||
|
OBJECT-TYPE, enterprises FROM SNMPv2-SMI
|
||
|
DisplayString FROM SNMPv2-TC;
|
||
|
|
||
|
|
||
|
sentry3 MODULE-IDENTITY
|
||
|
LAST-UPDATED "201601251630Z" -- 25 January 2016
|
||
|
ORGANIZATION "Server Technology, Inc."
|
||
|
CONTACT-INFO
|
||
|
"Server Technology, Inc.
|
||
|
1040 Sandhill Road
|
||
|
Reno, NV 89521
|
||
|
Tel: (775) 284-2000
|
||
|
Fax: (775) 284-2065
|
||
|
Email: mibmaster@servertech.com"
|
||
|
DESCRIPTION
|
||
|
"This is the MIB module for the third generation of the
|
||
|
Sentry product family. This includes the Sentry Remote
|
||
|
Power Manager (RPM), Sentry Power Distribution Unit (PDU),
|
||
|
Sentry Environmental Monitor (EM), Sentry Smart and
|
||
|
Switched Cabinet Distribution Unit (CDU), and Sentry
|
||
|
Switched -48 VDC."
|
||
|
REVISION "201601251630Z" -- 25 January 2016
|
||
|
DESCRIPTION
|
||
|
"Adjusted the upper limit of infeedLoadValue to 60000.
|
||
|
Adjusted the upper limit of infeedLoadHighThresh to 600.
|
||
|
Adjusted the upper limit of infeedCapacity to 600."
|
||
|
REVISION "201406251200Z" -- 25 June 2014
|
||
|
DESCRIPTION
|
||
|
"Adjusted the upper limit of tempHumidSensorTempRecDelta
|
||
|
to 54."
|
||
|
REVISION "201401161800Z" -- 16 January 2014
|
||
|
DESCRIPTION
|
||
|
"Added an eventInformationGroup with two new objects:
|
||
|
eventStatusText and eventStatusCondition. Added these
|
||
|
objects to all traps and updated the trap annotations
|
||
|
to use the eventStatusText string value instead of the
|
||
|
integer value of the status object in the trap."
|
||
|
REVISION "201311250900Z" -- 25 November 2013
|
||
|
DESCRIPTION
|
||
|
"Added a new object: tempHumidSensorHumidRecDelta."
|
||
|
REVISION "201309161000Z" -- 16 September 2013
|
||
|
DESCRIPTION
|
||
|
"Adjusted the upper limit of infeedLoadValue to 30000.
|
||
|
Adjusted the upper limit of infeedLoadHighThresh to 300.
|
||
|
Adjusted the upper limit of infeedCapacity to 300.
|
||
|
Adjusted the upper limit of branchLoadValue to 4000."
|
||
|
REVISION "201302140930Z" -- 14 February 2013
|
||
|
DESCRIPTION
|
||
|
"Added a branch table with new objects for branch status
|
||
|
and current measurements. Added 'branchOnSense' and
|
||
|
'branchLoadSense' bits to infeedCapabilities. Added
|
||
|
'reading', 'offFuse', and 'onFuse' bits to infeedStatus.
|
||
|
Added branchStatusEvent and branchLoadEvent notifications.
|
||
|
Added 'outOfBalance' to the list of error conditions
|
||
|
enumerated by the towerStatus object."
|
||
|
REVISION "201211071400Z" -- 7 November 2012
|
||
|
DESCRIPTION
|
||
|
"Adjusted the upper limit of systemVersion to 80. Adjusted
|
||
|
the upper limit of infeedOutletCount and outletIndex to 64."
|
||
|
REVISION "201204181400Z" -- 18 April 2012
|
||
|
DESCRIPTION
|
||
|
"Adjusted the upper limit of outletIndex to 32."
|
||
|
REVISION "201201041100Z" -- 4 January 2012
|
||
|
DESCRIPTION
|
||
|
"Added 'nvmFail' to the list of error conditions enumerated
|
||
|
by the towerStatus object."
|
||
|
REVISION "201107111640Z" -- 11 July 2011
|
||
|
DESCRIPTION
|
||
|
"Added 'outletControlInhibit' to the list of key-activated
|
||
|
features enumerated by the systemFeatures object. Changed
|
||
|
the upper limit of tempHumidSensorTempRecDelta to 18 to
|
||
|
accommodate the maximum Fahrenheit value."
|
||
|
REVISION "201106151300Z" -- 15 June 2011
|
||
|
DESCRIPTION
|
||
|
"Added a new object: tempHumidSensorTempRecDelta."
|
||
|
REVISION "201105051100Z" -- 5 May 2011
|
||
|
DESCRIPTION
|
||
|
"Added several new objects: systemOutletSeqInterval,
|
||
|
systemOutletRebootDelay, systemConfigModifiedCount,
|
||
|
outletWakeupState, and outletPostOnDelay. Removed the
|
||
|
'snmpPOPS' feature-key activation requirement from
|
||
|
descriptions of POPS objects."
|
||
|
REVISION "201007071215Z" -- 7 July 2010
|
||
|
DESCRIPTION
|
||
|
"Added support for Per-Inlet Power Sensing (PIPS) hardware.
|
||
|
Added several new objects: towerVACapacity,
|
||
|
towerVACapacityUsed, towerActivePower, towerApparentPower,
|
||
|
towerPowerFactor, towerEnergy, towerLineFrequency,
|
||
|
infeedReactance, infeedPhaseCurrent, infeedPhaseVoltage,
|
||
|
infeedCapacityUsed, infeedLineID, infeedLineToLineID,
|
||
|
infeedPhaseID, infeedVACapacity, and infeedVACapacityUsed.
|
||
|
Changed the UNITS of infeedEnergy. Adjusted the limits of
|
||
|
INTEGER data types for various objects. Updated the
|
||
|
descriptions of various infeedTable objects to distinguish
|
||
|
between line and phase measurements with three-phase PIPS
|
||
|
hardware."
|
||
|
REVISION "200903101600Z" -- 10 March 2009
|
||
|
DESCRIPTION
|
||
|
"Added support for Per-Outlet Power Sensing (POPS) hardware.
|
||
|
Added several new objects: systemFeatures, systemFeatureKey,
|
||
|
infeedApparentPower, infeedPowerFactor, infeedCrestFactor,
|
||
|
infeedEnergy, outletCapacity, outletVoltage, outletPower,
|
||
|
outletApparentPower, outletPowerFactor, outletCrestFactor,
|
||
|
and outletEnergy. Added 'voltageSense' and 'powerSense'
|
||
|
bit definitions to the input feed and outlet capabilities
|
||
|
objects. Increased the size of systemVersion to 50."
|
||
|
REVISION "200805071520Z" -- 7 May 2008
|
||
|
DESCRIPTION
|
||
|
"Added systemAreaUnit and systemPowerFactor objects. Renamed
|
||
|
the systemWattsPerUnitArea object to systemWattsPerAreaUnit.
|
||
|
Changed systemArea from read-only to read-write."
|
||
|
REVISION "200707091445Z" -- 9 July 2007
|
||
|
DESCRIPTION
|
||
|
"Added support for products with fan rotation sensing and
|
||
|
internal temperature sensing. Added 'fanSense' and
|
||
|
'tempSense' bit definitions to the tower capabilities
|
||
|
object. Added 'fanFail' and 'overTemp' states to the
|
||
|
towerStatus object. Modified the description of the
|
||
|
towerStatusEvent trap to reflect these additions."
|
||
|
REVISION "200701091410Z" -- 9 January 2007
|
||
|
DESCRIPTION
|
||
|
"Added several new objects: systemArea, systemTotalPower,
|
||
|
systemWattsPerUnitArea, towerProductSN, towerModelNumber,
|
||
|
towerCapabilities, infeedCapacity, infeedVoltage, and
|
||
|
infeedPower. Added six states to the outletControlState
|
||
|
object."
|
||
|
REVISION "200607201200Z" -- 20 July 2006
|
||
|
DESCRIPTION
|
||
|
"Changed the upper limit of systemTowerCount from 2 to 4."
|
||
|
REVISION "200606120930Z" -- 12 June 2006
|
||
|
DESCRIPTION
|
||
|
"Added a tempHumidSensorTempScale object to select either
|
||
|
Celsius or Fahrenheit as the scale for temperature values.
|
||
|
To accommodate the maximum Fahrenheit value, the upper limit
|
||
|
of tempHumidSensorTempValue was changed to 2540, and the
|
||
|
upper limit of tempHumidSensorTempHighThresh was changed to
|
||
|
254. Removed 'Celsius' from the UNITS clause and description
|
||
|
of temperature objects. Added the tempHumidSensorTempScale
|
||
|
object to the tempHumidSensorTempEvent trap. Changed the
|
||
|
upper limit of towerIndex from 2 to 4, to accommodate new
|
||
|
products with additional link capabilities."
|
||
|
REVISION "200507271105Z" -- 27 July 2005
|
||
|
DESCRIPTION
|
||
|
"Changed the upper limit of tempHumidSensorTempLowThresh to
|
||
|
123. Changed the upper limit of tempHumidSensorTempValue
|
||
|
to 1235."
|
||
|
REVISION "200502181145Z" -- 18 February 2005
|
||
|
DESCRIPTION
|
||
|
"Added CDU products to the MIB description. Corrected syntax
|
||
|
of outletID to specify SIZE(2..4)."
|
||
|
REVISION "200501071220Z" -- 7 January 2005
|
||
|
DESCRIPTION
|
||
|
"Added a 'fusedBranch' bit definition to the outlet
|
||
|
capabilities object. Added 'offFuse' and 'onFuse' states
|
||
|
to the outlet status object. Modified the descriptions of
|
||
|
objects and traps to reflect support for these additions."
|
||
|
REVISION "200412091320Z" -- 9 December 2004
|
||
|
DESCRIPTION
|
||
|
"Corrected spelling errors. Removed product acronyms from the
|
||
|
trap annotations."
|
||
|
REVISION "200411111200Z" -- 11 November 2004
|
||
|
DESCRIPTION
|
||
|
"Changed the upper limit of tempHumidSensorTempHighThresh to
|
||
|
123. Renamed systemSerialNumber to systemNICSerialNumber."
|
||
|
REVISION "200311201300Z" -- 20 November 2003
|
||
|
DESCRIPTION
|
||
|
"Changed the MIB description to reflect that there are
|
||
|
multiple products in the Sentry product family supported by
|
||
|
this MIB."
|
||
|
REVISION "200310231900Z" -- 23 October 2003
|
||
|
DESCRIPTION
|
||
|
"Added annotations to the trap definitions. Added a
|
||
|
'reading' state to the outletStatus object. Renamed
|
||
|
'notificationGroup' to 'sentry3Traps'. Corrected the
|
||
|
the description of the tempHumidSensorStatusEvent trap."
|
||
|
REVISION "200310021100Z" -- 2 October 2003
|
||
|
DESCRIPTION
|
||
|
"Added a 'failSafe' bit definition to the infeed capabilities
|
||
|
object, and corrected the definition of the 'defaultOff'
|
||
|
infeed capabilities bit."
|
||
|
REVISION "200308271600Z" -- 27 August 2003
|
||
|
DESCRIPTION
|
||
|
"Added new bit definitions to the infeed and outlet
|
||
|
capabilities objects."
|
||
|
REVISION "200303281700Z" -- 28 March 2003
|
||
|
DESCRIPTION
|
||
|
"Added environmental monitor objects and traps."
|
||
|
REVISION "200303271700Z" -- 27 March 2003
|
||
|
DESCRIPTION
|
||
|
"Initial release."
|
||
|
::= { serverTech 3 }
|
||
|
|
||
|
serverTech OBJECT IDENTIFIER ::= { enterprises 1718 }
|
||
|
|
||
|
|
||
|
--
|
||
|
-- System Group
|
||
|
--
|
||
|
|
||
|
systemGroup OBJECT IDENTIFIER ::= { sentry3 1 }
|
||
|
|
||
|
systemVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..80))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The firmware version of the system."
|
||
|
::= { systemGroup 1 }
|
||
|
|
||
|
systemNICSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..8))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The serial number of the network interface card in the
|
||
|
system."
|
||
|
::= { systemGroup 2 }
|
||
|
|
||
|
systemLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The location of the system."
|
||
|
::= { systemGroup 3 }
|
||
|
|
||
|
systemTowerCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of towers in the system."
|
||
|
::= { systemGroup 4 }
|
||
|
|
||
|
systemEnvMonCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of environmental monitors in the system."
|
||
|
::= { systemGroup 5 }
|
||
|
|
||
|
systemTotalPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..150000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total power consumption of all of the input feeds in the
|
||
|
system. A non-negative value indicates the total power
|
||
|
consumption in Watts. A negative value indicates that the
|
||
|
total power consumption was not available."
|
||
|
::= { systemGroup 6 }
|
||
|
|
||
|
systemArea OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..1000)
|
||
|
UNITS "tenth area units"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The area that the footprint of the system occupies. A
|
||
|
non-zero non-negative value indicates the area in tenths of
|
||
|
area units as selected by the systemAreaUnit object. A zero
|
||
|
or negative value indicates that the area was not available."
|
||
|
::= { systemGroup 7 }
|
||
|
|
||
|
systemWattsPerAreaUnit OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1500000)
|
||
|
UNITS "Watts per area unit"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The system Watts per area unit. A non-negative value
|
||
|
indicates the power consumption per area unit as selected by
|
||
|
the systemAreaUnit object. A negative value indicates that
|
||
|
the power consumption per area unit was not available."
|
||
|
::= { systemGroup 8 }
|
||
|
|
||
|
systemAreaUnit OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
squareMeter(0),
|
||
|
squareFoot(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The unit of area for the systemArea and systemWattsPerAreaUnit
|
||
|
objects. If the agent does not support this object, then the
|
||
|
unit of area is a square foot."
|
||
|
::= { systemGroup 9 }
|
||
|
|
||
|
systemPowerFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(50..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor used in power calculations performed by the
|
||
|
system."
|
||
|
::= { systemGroup 10 }
|
||
|
|
||
|
systemFeatures OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
smartLoadShedding(0),
|
||
|
snmpPOPS(1),
|
||
|
outletControlInhibit(2)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The key-activated features enabled in the system."
|
||
|
::= { systemGroup 11 }
|
||
|
|
||
|
systemFeatureKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..19))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A valid feature key written to this object will enable a
|
||
|
feature in the system. A valid feature key is in the form
|
||
|
xxxx-xxxx-xxxx-xxxx. A read of this object returns an
|
||
|
empty string."
|
||
|
::= { systemGroup 12 }
|
||
|
|
||
|
systemOutletSeqInterval OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..15)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power-on sequencing interval for all outlets."
|
||
|
::= { systemGroup 13 }
|
||
|
|
||
|
systemOutletRebootDelay OBJECT-TYPE
|
||
|
SYNTAX INTEGER(5..600)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The reboot delay for all outlets."
|
||
|
::= { systemGroup 14 }
|
||
|
|
||
|
systemConfigModifiedCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..2147483647)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of times the system configuration has
|
||
|
changed."
|
||
|
::= { systemGroup 15 }
|
||
|
|
||
|
--
|
||
|
-- System Tables
|
||
|
--
|
||
|
|
||
|
systemTables OBJECT IDENTIFIER ::= { sentry3 2 }
|
||
|
|
||
|
--
|
||
|
-- Tower Table
|
||
|
--
|
||
|
|
||
|
towerTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF TowerEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of towers."
|
||
|
::= { systemTables 1 }
|
||
|
|
||
|
towerEntry OBJECT-TYPE
|
||
|
SYNTAX TowerEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the tower table."
|
||
|
INDEX { towerIndex }
|
||
|
::= { towerTable 1 }
|
||
|
|
||
|
TowerEntry ::= SEQUENCE {
|
||
|
towerIndex INTEGER,
|
||
|
towerID DisplayString,
|
||
|
towerName DisplayString,
|
||
|
towerStatus INTEGER,
|
||
|
towerInfeedCount INTEGER,
|
||
|
towerProductSN DisplayString,
|
||
|
towerModelNumber DisplayString,
|
||
|
towerCapabilities BITS,
|
||
|
towerVACapacity INTEGER,
|
||
|
towerVACapacityUsed INTEGER,
|
||
|
towerActivePower INTEGER,
|
||
|
towerApparentPower INTEGER,
|
||
|
towerPowerFactor INTEGER,
|
||
|
towerEnergy INTEGER,
|
||
|
towerLineFrequency INTEGER
|
||
|
}
|
||
|
|
||
|
towerIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the tower table."
|
||
|
::= { towerEntry 1 }
|
||
|
|
||
|
towerID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(1))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the tower."
|
||
|
::= { towerEntry 2 }
|
||
|
|
||
|
towerName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the tower."
|
||
|
::= { towerEntry 3 }
|
||
|
|
||
|
towerStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
noComm(1),
|
||
|
fanFail(2),
|
||
|
overTemp(3),
|
||
|
nvmFail(4),
|
||
|
outOfBalance(5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The operational status of the tower."
|
||
|
::= { towerEntry 4 }
|
||
|
|
||
|
towerInfeedCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of input feeds on the tower."
|
||
|
::= { towerEntry 5 }
|
||
|
|
||
|
towerProductSN OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..16))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The product serial number of the tower."
|
||
|
::= { towerEntry 6 }
|
||
|
|
||
|
towerModelNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The model number of the tower."
|
||
|
::= { towerEntry 7 }
|
||
|
|
||
|
towerCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
failSafe(0),
|
||
|
fuseSense(1),
|
||
|
directCurrent(2),
|
||
|
threePhase(3),
|
||
|
fanSense(4),
|
||
|
tempSense(5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the tower."
|
||
|
::= { towerEntry 8 }
|
||
|
|
||
|
towerVACapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total apparent power capacity of the tower circuit.
|
||
|
A non-negative value indicates the maximum total apparent
|
||
|
power in Volt-Amps. A negative value indicates that the
|
||
|
total apparent power capacity was not available."
|
||
|
::= { towerEntry 9 }
|
||
|
|
||
|
towerVACapacityUsed OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1500)
|
||
|
UNITS "tenth percentage"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The used percentage of the tower circuit total apparent power
|
||
|
capacity (towerApparentPower / towerVACapacity x 100). A
|
||
|
non-negative value indicates the percentage of capacity used
|
||
|
in tenths. A negative value indicates that the percentage of
|
||
|
capacity used was not available."
|
||
|
::= { towerEntry 10 }
|
||
|
|
||
|
towerActivePower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total active power consumption of the tower circuit.
|
||
|
A non-negative value indicates the total active power
|
||
|
consumption in Watts. A negative value indicates that the
|
||
|
total active power consumption was not available."
|
||
|
::= { towerEntry 11 }
|
||
|
|
||
|
towerApparentPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total apparent power consumption of the tower circuit.
|
||
|
A non-negative value indicates the total apparent power
|
||
|
consumption in Volt-Amps. A negative value indicates that
|
||
|
the total apparent power consumption was not available."
|
||
|
::= { towerEntry 12 }
|
||
|
|
||
|
towerPowerFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The overall power factor of the tower circuit. A non-
|
||
|
negative value indicates the overall power factor in
|
||
|
hundredths. A negative value indicates that the overall
|
||
|
power factor was not able to be measured."
|
||
|
::= { towerEntry 13 }
|
||
|
|
||
|
towerEnergy OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2147483647)
|
||
|
UNITS "Kilowatt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total energy consumption of the tower circuit. A non-
|
||
|
negative value indicates the total energy consumption in
|
||
|
Kilowatt-Hours. A negative value indicates that the total
|
||
|
energy consumption was not available."
|
||
|
::= { towerEntry 14 }
|
||
|
|
||
|
towerLineFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..60)
|
||
|
UNITS "Hertz"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The frequency of the input feed line voltage. A non-
|
||
|
negative value indicates the frequency in Hertz. A negative
|
||
|
value indicates that the frequency was not available."
|
||
|
::= { towerEntry 15 }
|
||
|
|
||
|
--
|
||
|
-- Input Feed Table
|
||
|
--
|
||
|
|
||
|
infeedTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF InfeedEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of input feeds."
|
||
|
::= { systemTables 2 }
|
||
|
|
||
|
infeedEntry OBJECT-TYPE
|
||
|
SYNTAX InfeedEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the input feed table."
|
||
|
INDEX { towerIndex, infeedIndex }
|
||
|
::= { infeedTable 1 }
|
||
|
|
||
|
InfeedEntry ::= SEQUENCE {
|
||
|
infeedIndex INTEGER,
|
||
|
infeedID DisplayString,
|
||
|
infeedName DisplayString,
|
||
|
infeedCapabilities BITS,
|
||
|
infeedStatus INTEGER,
|
||
|
infeedLoadStatus INTEGER,
|
||
|
infeedLoadValue INTEGER,
|
||
|
infeedLoadHighThresh INTEGER,
|
||
|
infeedOutletCount INTEGER,
|
||
|
infeedCapacity INTEGER,
|
||
|
infeedVoltage INTEGER,
|
||
|
infeedPower INTEGER,
|
||
|
infeedApparentPower INTEGER,
|
||
|
infeedPowerFactor INTEGER,
|
||
|
infeedCrestFactor INTEGER,
|
||
|
infeedEnergy INTEGER,
|
||
|
infeedReactance INTEGER,
|
||
|
infeedPhaseVoltage INTEGER,
|
||
|
infeedPhaseCurrent INTEGER,
|
||
|
infeedCapacityUsed INTEGER,
|
||
|
infeedLineID DisplayString,
|
||
|
infeedLineToLineID DisplayString,
|
||
|
infeedPhaseID DisplayString,
|
||
|
infeedVACapacity INTEGER,
|
||
|
infeedVACapacityUsed INTEGER
|
||
|
}
|
||
|
|
||
|
infeedIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the input feed table."
|
||
|
::= { infeedEntry 1 }
|
||
|
|
||
|
infeedID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the input feed."
|
||
|
::= { infeedEntry 2 }
|
||
|
|
||
|
infeedName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the input feed."
|
||
|
::= { infeedEntry 3 }
|
||
|
|
||
|
infeedCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
onSense(0),
|
||
|
loadSense(1),
|
||
|
powerControl(2),
|
||
|
failSafe(3),
|
||
|
defaultOff(4),
|
||
|
voltageSense(5),
|
||
|
powerSense(6),
|
||
|
branchOnSense(7),
|
||
|
branchLoadSense(8)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the input feed."
|
||
|
::= { infeedEntry 4 }
|
||
|
|
||
|
infeedStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off(0),
|
||
|
on(1),
|
||
|
offWait(2),
|
||
|
onWait(3),
|
||
|
offError(4),
|
||
|
onError(5),
|
||
|
noComm(6),
|
||
|
reading(7),
|
||
|
offFuse(8),
|
||
|
onFuse(9)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the input feed line. If the infeedCapabilities
|
||
|
'onSense' bit is TRUE, then all of the states are supported
|
||
|
and indicate the sensed state of the input feed. If the
|
||
|
infeedCapabilities 'onSense' bit is FALSE, then only the
|
||
|
'on' and 'noComm' states are supported, and 'on' indicates
|
||
|
a derived state, not a sensed state."
|
||
|
::= { infeedEntry 5 }
|
||
|
|
||
|
infeedLoadStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
notOn(1),
|
||
|
reading(2),
|
||
|
loadLow(3),
|
||
|
loadHigh(4),
|
||
|
overLoad(5),
|
||
|
readError(6),
|
||
|
noComm(7)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the load measured on the input feed line. If
|
||
|
the infeedCapabilities 'loadSense' bit is TRUE, then all of
|
||
|
the states are supported. If the infeedCapabilities
|
||
|
'loadSense' bit is FALSE, then only the 'normal' and 'noComm'
|
||
|
states are supported."
|
||
|
::= { infeedEntry 6 }
|
||
|
|
||
|
infeedLoadValue OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..60000)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load measured on the input feed line. A non-negative
|
||
|
value indicates the measured load in hundredths of Amps. A
|
||
|
negative value indicates that a load value was not able to
|
||
|
be measured."
|
||
|
::= { infeedEntry 7 }
|
||
|
|
||
|
infeedLoadHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..600)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load high threshold value of the input feed line in Amps."
|
||
|
::= { infeedEntry 8 }
|
||
|
|
||
|
infeedOutletCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..64)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of controlled and/or monitored outlets on the
|
||
|
input feed."
|
||
|
::= { infeedEntry 9 }
|
||
|
|
||
|
infeedCapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..600)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load capacity of the input feed line. A non-negative
|
||
|
value indicates the maximum load in Amps. A negative
|
||
|
value indicates that the capacity was not available."
|
||
|
::= { infeedEntry 10 }
|
||
|
|
||
|
infeedVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..4800)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The line-to-line voltage of the input feed. A non-negative
|
||
|
value indicates the voltage in tenths of Volts. A negative
|
||
|
value indicates that the voltage was not available."
|
||
|
::= { infeedEntry 11 }
|
||
|
|
||
|
infeedPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..25000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power consumption of the input feed phase. A non-
|
||
|
negative value indicates the active power consumption in
|
||
|
Watts. A negative value indicates that the active power
|
||
|
consumption was not available."
|
||
|
::= { infeedEntry 12 }
|
||
|
|
||
|
infeedApparentPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..25000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power consumption of the input feed phase. A
|
||
|
non-negative value indicates the apparent power consumption
|
||
|
in Volt-Amps. A negative value indicates that the apparent
|
||
|
power consumption was not available."
|
||
|
::= { infeedEntry 13 }
|
||
|
|
||
|
infeedPowerFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor of the input feed phase. A non-negative
|
||
|
value indicates the power factor in hundredths. A negative
|
||
|
value indicates that the power factor was not able to be
|
||
|
measured."
|
||
|
::= { infeedEntry 14 }
|
||
|
|
||
|
infeedCrestFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1000)
|
||
|
UNITS "tenths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The crest factor for the load of the input feed phase. A
|
||
|
non-negative value indicates the crest factor in tenths. A
|
||
|
negative value indicates that the crest factor was not able
|
||
|
to be measured."
|
||
|
::= { infeedEntry 15 }
|
||
|
|
||
|
infeedEnergy OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2147483647)
|
||
|
UNITS "tenth Kilowatt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The energy consumption of the input feed phase. A non-
|
||
|
negative value indicates the energy consumption in tenths of
|
||
|
Kilowatt-Hours. A negative value indicates that the energy
|
||
|
consumption was not available."
|
||
|
::= { infeedEntry 16 }
|
||
|
|
||
|
infeedReactance OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(0),
|
||
|
capacitive(1),
|
||
|
inductive(2),
|
||
|
resistive(3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The characterization of the phase relation between the
|
||
|
voltage and current of the input feed phase."
|
||
|
::= { infeedEntry 17 }
|
||
|
|
||
|
infeedPhaseVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2640)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The voltage measured for the input feed phase. A non-
|
||
|
negative value indicates the voltage in tenths of Volts. A
|
||
|
negative value indicates that the voltage was not available."
|
||
|
::= { infeedEntry 18 }
|
||
|
|
||
|
infeedPhaseCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..25500)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current measured for the input feed phase. A non-
|
||
|
negative value indicates the measured load in hundredths of
|
||
|
Amps. A negative value indicates that a load value was not
|
||
|
able to be measured."
|
||
|
::= { infeedEntry 19 }
|
||
|
|
||
|
infeedCapacityUsed OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1500)
|
||
|
UNITS "tenth percentage"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The used percentage of the input feed line load capacity
|
||
|
(infeedLoadValue / infeedCapacity x 100). A non-negative
|
||
|
value indicates the percentage of capacity used in tenths.
|
||
|
A negative value indicates that the percentage of capacity
|
||
|
used was not available."
|
||
|
::= { infeedEntry 20 }
|
||
|
|
||
|
infeedLineID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the input feed line."
|
||
|
::= { infeedEntry 21 }
|
||
|
|
||
|
infeedLineToLineID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..7))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The line-to-line ID of the input feed."
|
||
|
::= { infeedEntry 22 }
|
||
|
|
||
|
infeedPhaseID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..6))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the input feed phase."
|
||
|
::= { infeedEntry 23 }
|
||
|
|
||
|
infeedVACapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..25000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power capacity of the input feed circuit. A
|
||
|
non-negative value indicates the maximum apparent power in
|
||
|
Volt-Amps. A negative value indicates that the apparent
|
||
|
power capacity was not available."
|
||
|
::= { infeedEntry 24 }
|
||
|
|
||
|
infeedVACapacityUsed OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1500)
|
||
|
UNITS "tenth percentage"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The used percentage of the input feed circuit apparent power
|
||
|
capacity (infeedApparentPower / infeedVACapacity x 100). A
|
||
|
non-negative value indicates the percentage of capacity used
|
||
|
in tenths. A negative value indicates that the percentage of
|
||
|
capacity used was not available."
|
||
|
::= { infeedEntry 25 }
|
||
|
|
||
|
--
|
||
|
-- Outlet Table
|
||
|
--
|
||
|
|
||
|
outletTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF OutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of outlets."
|
||
|
::= { systemTables 3 }
|
||
|
|
||
|
outletEntry OBJECT-TYPE
|
||
|
SYNTAX OutletEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the outlet table."
|
||
|
INDEX { towerIndex, infeedIndex, outletIndex }
|
||
|
::= { outletTable 1 }
|
||
|
|
||
|
OutletEntry ::= SEQUENCE {
|
||
|
outletIndex INTEGER,
|
||
|
outletID DisplayString,
|
||
|
outletName DisplayString,
|
||
|
outletCapabilities BITS,
|
||
|
outletStatus INTEGER,
|
||
|
outletLoadStatus INTEGER,
|
||
|
outletLoadValue INTEGER,
|
||
|
outletLoadLowThresh INTEGER,
|
||
|
outletLoadHighThresh INTEGER,
|
||
|
outletControlState INTEGER,
|
||
|
outletControlAction INTEGER,
|
||
|
outletCapacity INTEGER,
|
||
|
outletVoltage INTEGER,
|
||
|
outletPower INTEGER,
|
||
|
outletApparentPower INTEGER,
|
||
|
outletPowerFactor INTEGER,
|
||
|
outletCrestFactor INTEGER,
|
||
|
outletEnergy INTEGER,
|
||
|
outletWakeupState INTEGER,
|
||
|
outletPostOnDelay INTEGER
|
||
|
}
|
||
|
|
||
|
outletIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..64)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the outlet table."
|
||
|
::= { outletEntry 1 }
|
||
|
|
||
|
outletID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the outlet."
|
||
|
::= { outletEntry 2 }
|
||
|
|
||
|
outletName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the outlet."
|
||
|
::= { outletEntry 3 }
|
||
|
|
||
|
outletCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
onSense(0),
|
||
|
loadSense(1),
|
||
|
powerControl(2),
|
||
|
shutdown(3),
|
||
|
defaultOn(4),
|
||
|
ownInfeed(5),
|
||
|
fusedBranch(6),
|
||
|
voltageSense(7),
|
||
|
powerSense(8)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the outlet."
|
||
|
::= { outletEntry 4 }
|
||
|
|
||
|
outletStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off(0),
|
||
|
on(1),
|
||
|
offWait(2),
|
||
|
onWait(3),
|
||
|
offError(4),
|
||
|
onError(5),
|
||
|
noComm(6),
|
||
|
reading(7),
|
||
|
offFuse(8),
|
||
|
onFuse(9)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the outlet. If the outletCapabilities
|
||
|
'onSense' bit is TRUE, then the state indicates the sensed
|
||
|
state of the outlet, not a derived state, and 'offError'
|
||
|
and 'onError' are supported to indicate a mismatch between
|
||
|
the control and sensed state. If the outletCapabilities
|
||
|
'fusedBranch' bit is TRUE, then the outlet is on a fused
|
||
|
branch circuit that can detect the fuse state, and 'offFuse'
|
||
|
and 'onFuse' are supported to indicate a fuse error."
|
||
|
::= { outletEntry 5 }
|
||
|
|
||
|
outletLoadStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
notOn(1),
|
||
|
reading(2),
|
||
|
loadLow(3),
|
||
|
loadHigh(4),
|
||
|
overLoad(5),
|
||
|
readError(6),
|
||
|
noComm(7)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the load measured on the outlet. If the
|
||
|
outletCapabilities 'loadSense' bit is TRUE, then all of the
|
||
|
states are supported. If the outletCapabilities 'loadSense'
|
||
|
bit is FALSE, then only the 'normal' and 'noComm' states are
|
||
|
supported."
|
||
|
::= { outletEntry 6 }
|
||
|
|
||
|
outletLoadValue OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..25500)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load measured on the outlet. A non-negative value
|
||
|
indicates the measured load in hundredths of Amps. A
|
||
|
negative value indicates that a load value was not able to
|
||
|
be measured."
|
||
|
::= { outletEntry 7 }
|
||
|
|
||
|
outletLoadLowThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..255)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load low threshold value of the outlet in Amps."
|
||
|
::= { outletEntry 8 }
|
||
|
|
||
|
outletLoadHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..255)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load high threshold value of the outlet in Amps."
|
||
|
::= { outletEntry 9 }
|
||
|
|
||
|
outletControlState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
idleOff(0),
|
||
|
idleOn(1),
|
||
|
wakeOff(2),
|
||
|
wakeOn(3),
|
||
|
off(4),
|
||
|
on(5),
|
||
|
lockedOff(6),
|
||
|
lockedOn(7),
|
||
|
reboot(8),
|
||
|
shutdown(9),
|
||
|
pendOn(10),
|
||
|
pendOff(11),
|
||
|
minimumOff(12),
|
||
|
minimumOn(13),
|
||
|
eventOff(14),
|
||
|
eventOn(15),
|
||
|
eventReboot(16),
|
||
|
eventShutdown(17)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The control state of the outlet. The supported states are
|
||
|
dependent upon the outletCapabilities 'powerControl' and
|
||
|
'shutdown' bits, as well as the supported features of the
|
||
|
firmware version."
|
||
|
::= { outletEntry 10 }
|
||
|
|
||
|
outletControlAction OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
none(0),
|
||
|
on(1),
|
||
|
off(2),
|
||
|
reboot(3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An action to change the control state of the outlet. If
|
||
|
the outletCapabilities 'powerControl' bit is TRUE, then the
|
||
|
'on', 'off', and 'reboot' actions can be used to change the
|
||
|
control state of the outlet. If the outletCapabilities
|
||
|
'powerControl' bit is FALSE, then the actions have no
|
||
|
effect."
|
||
|
::= { outletEntry 11 }
|
||
|
|
||
|
outletCapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..255)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load capacity of the outlet. A non-negative value
|
||
|
indicates the maximum load in Amps. A negative value
|
||
|
indicates that the capacity was not available."
|
||
|
::= { outletEntry 12 }
|
||
|
|
||
|
outletVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2640)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The voltage of the outlet. A non-negative value indicates
|
||
|
the voltage in tenths of Volts. A negative value indicates
|
||
|
that the voltage was not available."
|
||
|
::= { outletEntry 13 }
|
||
|
|
||
|
outletPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power consumption of the device plugged into the
|
||
|
outlet. A non-negative value indicates the active power
|
||
|
consumption in Watts. A negative value indicates that the
|
||
|
active power consumption was not available."
|
||
|
::= { outletEntry 14 }
|
||
|
|
||
|
outletApparentPower OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..10000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power consumption of the device plugged into
|
||
|
the outlet. A non-negative value indicates the apparent
|
||
|
power consumption in Volt-Amps. A negative value indicates
|
||
|
that the apparent power consumption was not available."
|
||
|
::= { outletEntry 15 }
|
||
|
|
||
|
outletPowerFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor of the device plugged into the outlet. A
|
||
|
non-negative value indicates the power factor in hundredths.
|
||
|
A negative value indicates that the power factor was not able
|
||
|
to be measured."
|
||
|
::= { outletEntry 16 }
|
||
|
|
||
|
outletCrestFactor OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..1000)
|
||
|
UNITS "tenths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The crest factor for the load of the device plugged into the
|
||
|
outlet. A non-negative value indicates the crest factor in
|
||
|
tenths. A negative value indicates that the crest factor
|
||
|
was not able to be measured."
|
||
|
::= { outletEntry 17 }
|
||
|
|
||
|
outletEnergy OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2147483647)
|
||
|
UNITS "Watt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The energy consumption of the device plugged into the outlet.
|
||
|
A non-negative value indicates the energy consumption in
|
||
|
Watt-Hours. A negative value indicates that the energy
|
||
|
consumption was not available."
|
||
|
::= { outletEntry 18 }
|
||
|
|
||
|
outletWakeupState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
last(1),
|
||
|
off(2),
|
||
|
on(3)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The wakeup state of the outlet."
|
||
|
::= { outletEntry 19 }
|
||
|
|
||
|
outletPostOnDelay OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..900)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The post-on delay of the outlet."
|
||
|
::= { outletEntry 20 }
|
||
|
|
||
|
--
|
||
|
-- Environmental Monitor Table
|
||
|
--
|
||
|
|
||
|
envMonTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF EnvMonEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of environmental monitors."
|
||
|
::= { systemTables 4 }
|
||
|
|
||
|
envMonEntry OBJECT-TYPE
|
||
|
SYNTAX EnvMonEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the environmental monitor table."
|
||
|
INDEX { envMonIndex }
|
||
|
::= { envMonTable 1 }
|
||
|
|
||
|
EnvMonEntry ::= SEQUENCE {
|
||
|
envMonIndex INTEGER,
|
||
|
envMonID DisplayString,
|
||
|
envMonName DisplayString,
|
||
|
envMonStatus INTEGER,
|
||
|
envMonWaterSensorName DisplayString,
|
||
|
envMonWaterSensorStatus INTEGER,
|
||
|
envMonADCName DisplayString,
|
||
|
envMonADCStatus INTEGER,
|
||
|
envMonADCCount INTEGER,
|
||
|
envMonADCLowThresh INTEGER,
|
||
|
envMonADCHighThresh INTEGER,
|
||
|
envMonTempHumidSensorCount INTEGER,
|
||
|
envMonContactClosureCount INTEGER
|
||
|
}
|
||
|
|
||
|
envMonIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the environmental monitor table."
|
||
|
::= { envMonEntry 1 }
|
||
|
|
||
|
envMonID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(1))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the environmental monitor."
|
||
|
::= { envMonEntry 2 }
|
||
|
|
||
|
envMonName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the environmental monitor."
|
||
|
::= { envMonEntry 3 }
|
||
|
|
||
|
envMonStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
noComm(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The operational status of the environmental monitor."
|
||
|
::= { envMonEntry 4 }
|
||
|
|
||
|
envMonWaterSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the water sensor."
|
||
|
::= { envMonEntry 5 }
|
||
|
|
||
|
envMonWaterSensorStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
alarm(1),
|
||
|
noComm(2)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the water sensor."
|
||
|
::= { envMonEntry 6 }
|
||
|
|
||
|
envMonADCName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the analog-to-digital converter."
|
||
|
::= { envMonEntry 7 }
|
||
|
|
||
|
envMonADCStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
reading(1),
|
||
|
countLow(2),
|
||
|
countHigh(3),
|
||
|
readError(4),
|
||
|
noComm(5)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the analog-to-digital converter."
|
||
|
::= { envMonEntry 8 }
|
||
|
|
||
|
envMonADCCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit count value from the analog-to-digital converter.
|
||
|
A non-negative value indicates the digital value retrieved
|
||
|
from the ADC. A negative value indicates that a digital
|
||
|
value was not able to be retrieved."
|
||
|
::= { envMonEntry 9 }
|
||
|
|
||
|
envMonADCLowThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit count low threshold value of the analog-to-digital
|
||
|
converter."
|
||
|
::= { envMonEntry 10 }
|
||
|
|
||
|
envMonADCHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit count high threshold value of the analog-to-digital
|
||
|
converter."
|
||
|
::= { envMonEntry 11 }
|
||
|
|
||
|
envMonTempHumidSensorCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..2)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of temperature/humidity sensors on the
|
||
|
environmental monitor."
|
||
|
::= { envMonEntry 12 }
|
||
|
|
||
|
envMonContactClosureCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of contact closures on the environmental
|
||
|
monitor."
|
||
|
::= { envMonEntry 13 }
|
||
|
|
||
|
--
|
||
|
-- Temperature/Humidity Sensor Table
|
||
|
--
|
||
|
|
||
|
tempHumidSensorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF TempHumidSensorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of temperature/humidity sensors."
|
||
|
::= { systemTables 5 }
|
||
|
|
||
|
tempHumidSensorEntry OBJECT-TYPE
|
||
|
SYNTAX TempHumidSensorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the temperature/humidity sensor table."
|
||
|
INDEX { envMonIndex, tempHumidSensorIndex }
|
||
|
::= { tempHumidSensorTable 1 }
|
||
|
|
||
|
TempHumidSensorEntry ::= SEQUENCE {
|
||
|
tempHumidSensorIndex INTEGER,
|
||
|
tempHumidSensorID DisplayString,
|
||
|
tempHumidSensorName DisplayString,
|
||
|
tempHumidSensorStatus INTEGER,
|
||
|
tempHumidSensorTempStatus INTEGER,
|
||
|
tempHumidSensorTempValue INTEGER,
|
||
|
tempHumidSensorTempLowThresh INTEGER,
|
||
|
tempHumidSensorTempHighThresh INTEGER,
|
||
|
tempHumidSensorHumidStatus INTEGER,
|
||
|
tempHumidSensorHumidValue INTEGER,
|
||
|
tempHumidSensorHumidLowThresh INTEGER,
|
||
|
tempHumidSensorHumidHighThresh INTEGER,
|
||
|
tempHumidSensorTempScale INTEGER,
|
||
|
tempHumidSensorTempRecDelta INTEGER,
|
||
|
tempHumidSensorHumidRecDelta INTEGER
|
||
|
}
|
||
|
|
||
|
tempHumidSensorIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..2)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the temperature/humidity sensor table."
|
||
|
::= { tempHumidSensorEntry 1 }
|
||
|
|
||
|
tempHumidSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the temperature/humidity sensor."
|
||
|
::= { tempHumidSensorEntry 2 }
|
||
|
|
||
|
tempHumidSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the temperature/humidity sensor."
|
||
|
::= { tempHumidSensorEntry 3 }
|
||
|
|
||
|
tempHumidSensorStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
found(0),
|
||
|
notFound(1),
|
||
|
lost(2),
|
||
|
noComm(3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The operational status of the temperature/humidity sensor."
|
||
|
::= { tempHumidSensorEntry 4 }
|
||
|
|
||
|
tempHumidSensorTempStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
notFound(1),
|
||
|
reading(2),
|
||
|
tempLow(3),
|
||
|
tempHigh(4),
|
||
|
readError(5),
|
||
|
lost(6),
|
||
|
noComm(7)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the temperature sensor."
|
||
|
::= { tempHumidSensorEntry 5 }
|
||
|
|
||
|
tempHumidSensorTempValue OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..2540)
|
||
|
UNITS "tenth degrees"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature measured by the sensor. A non-negative value
|
||
|
indicates the measured temperature in tenths of degrees, using
|
||
|
the scale selected by tempHumidSensorTempScale. If the agent
|
||
|
does not support the tempHumidSensorTempScale object, then the
|
||
|
temperature scale used is Celsius. A negative value indicates
|
||
|
that a temperature value was not able to be measured."
|
||
|
::= { tempHumidSensorEntry 6 }
|
||
|
|
||
|
tempHumidSensorTempLowThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..254)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature low threshold value of the sensor in degrees,
|
||
|
using the scale selected by tempHumidSensorTempScale. If the
|
||
|
agent does not support the tempHumidSensorTempScale object,
|
||
|
then the temperature scale used is Celsius."
|
||
|
::= { tempHumidSensorEntry 7 }
|
||
|
|
||
|
tempHumidSensorTempHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..254)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature high threshold value of the sensor in degrees,
|
||
|
using the scale selected by tempHumidSensorTempScale. If the
|
||
|
agent does not support the tempHumidSensorTempScale object,
|
||
|
then the temperature scale used is Celsius."
|
||
|
::= { tempHumidSensorEntry 8 }
|
||
|
|
||
|
tempHumidSensorHumidStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
notFound(1),
|
||
|
reading(2),
|
||
|
humidLow(3),
|
||
|
humidHigh(4),
|
||
|
readError(5),
|
||
|
lost(6),
|
||
|
noComm(7)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the humidity sensor."
|
||
|
::= { tempHumidSensorEntry 9 }
|
||
|
|
||
|
tempHumidSensorHumidValue OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity measured by the sensor. A non-negative value
|
||
|
indicates the measured humidity in percentage relative
|
||
|
humidity. A negative value indicates that a humidity value
|
||
|
was not able to be measured."
|
||
|
::= { tempHumidSensorEntry 10 }
|
||
|
|
||
|
tempHumidSensorHumidLowThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity low threshold value of the sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { tempHumidSensorEntry 11 }
|
||
|
|
||
|
tempHumidSensorHumidHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity low threshold value of the sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { tempHumidSensorEntry 12 }
|
||
|
|
||
|
tempHumidSensorTempScale OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
celsius(0),
|
||
|
fahrenheit(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The scale used for temperature values. This is a global
|
||
|
setting for all temperature values in the system. If the
|
||
|
agent does not support this object, then the temperature
|
||
|
scale used is Celsius."
|
||
|
::= { tempHumidSensorEntry 13 }
|
||
|
|
||
|
tempHumidSensorTempRecDelta OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..54)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature recovery delta (hysteresis) value of the
|
||
|
sensor in degrees, using the scale selected by
|
||
|
tempHumidSensorTempScale."
|
||
|
::= { tempHumidSensorEntry 14 }
|
||
|
|
||
|
tempHumidSensorHumidRecDelta OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..20)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity recovery delta (hysteresis) value of the
|
||
|
sensor in percentage relative humidity."
|
||
|
::= { tempHumidSensorEntry 15 }
|
||
|
|
||
|
--
|
||
|
-- Contact Closure Table
|
||
|
--
|
||
|
|
||
|
contactClosureTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF ContactClosureEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of contact closures."
|
||
|
::= { systemTables 6 }
|
||
|
|
||
|
contactClosureEntry OBJECT-TYPE
|
||
|
SYNTAX ContactClosureEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the contact closure table."
|
||
|
INDEX { envMonIndex, contactClosureIndex }
|
||
|
::= { contactClosureTable 1 }
|
||
|
|
||
|
ContactClosureEntry ::= SEQUENCE {
|
||
|
contactClosureIndex INTEGER,
|
||
|
contactClosureID DisplayString,
|
||
|
contactClosureName DisplayString,
|
||
|
contactClosureStatus INTEGER
|
||
|
}
|
||
|
|
||
|
contactClosureIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the contact closure table."
|
||
|
::= { contactClosureEntry 1 }
|
||
|
|
||
|
contactClosureID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the contact closure."
|
||
|
::= { contactClosureEntry 2 }
|
||
|
|
||
|
contactClosureName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the contact closure."
|
||
|
::= { contactClosureEntry 3 }
|
||
|
|
||
|
contactClosureStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
alarm(1),
|
||
|
noComm(2)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the contact closure."
|
||
|
::= { contactClosureEntry 4 }
|
||
|
|
||
|
--
|
||
|
-- Branch Table
|
||
|
--
|
||
|
|
||
|
branchTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF BranchEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A table of branches."
|
||
|
::= { systemTables 7 }
|
||
|
|
||
|
branchEntry OBJECT-TYPE
|
||
|
SYNTAX BranchEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Row definition for the branch table."
|
||
|
INDEX { towerIndex, infeedIndex, branchIndex }
|
||
|
::= { branchTable 1 }
|
||
|
|
||
|
BranchEntry ::= SEQUENCE {
|
||
|
branchIndex INTEGER,
|
||
|
branchID DisplayString,
|
||
|
branchName DisplayString,
|
||
|
branchCapabilities BITS,
|
||
|
branchStatus INTEGER,
|
||
|
branchLoadStatus INTEGER,
|
||
|
branchLoadValue INTEGER,
|
||
|
branchLoadHighThresh INTEGER,
|
||
|
branchCapacity INTEGER
|
||
|
}
|
||
|
|
||
|
branchIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Index for the branch table."
|
||
|
::= { branchEntry 1 }
|
||
|
|
||
|
branchID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The ID of the branch."
|
||
|
::= { branchEntry 2 }
|
||
|
|
||
|
branchName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..24))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the branch."
|
||
|
::= { branchEntry 3 }
|
||
|
|
||
|
branchCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
onSense(0),
|
||
|
loadSense(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the branch."
|
||
|
::= { branchEntry 4 }
|
||
|
|
||
|
branchStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
off(0),
|
||
|
on(1),
|
||
|
offWait(2),
|
||
|
onWait(3),
|
||
|
offError(4),
|
||
|
onError(5),
|
||
|
noComm(6),
|
||
|
reading(7),
|
||
|
offFuse(8),
|
||
|
onFuse(9)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the branch."
|
||
|
::= { branchEntry 5 }
|
||
|
|
||
|
branchLoadStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
notOn(1),
|
||
|
reading(2),
|
||
|
loadLow(3),
|
||
|
loadHigh(4),
|
||
|
overLoad(5),
|
||
|
readError(6),
|
||
|
noComm(7)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the load measured on the branch."
|
||
|
::= { branchEntry 6 }
|
||
|
|
||
|
branchLoadValue OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..4000)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load measured on the branch. A non-negative
|
||
|
value indicates the measured load in hundredths of Amps. A
|
||
|
negative value indicates that a load value was not able to
|
||
|
be measured."
|
||
|
::= { branchEntry 7 }
|
||
|
|
||
|
branchLoadHighThresh OBJECT-TYPE
|
||
|
SYNTAX INTEGER(0..40)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load high threshold value of the branch in Amps."
|
||
|
::= { branchEntry 8 }
|
||
|
|
||
|
branchCapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER(-1..40)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The load capacity of the branch. A non-negative value
|
||
|
indicates the maximum load in Amps. A negative value
|
||
|
indicates that the capacity was not available."
|
||
|
::= { branchEntry 9 }
|
||
|
|
||
|
--
|
||
|
-- Event Information Group
|
||
|
--
|
||
|
|
||
|
eventInformationGroup OBJECT IDENTIFIER ::= { sentry3 99 }
|
||
|
|
||
|
eventStatusText OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..20))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The text representation of the enumerated integer value of
|
||
|
the status object included in a trap. The value of this
|
||
|
object is set only when sent with a trap. A get of this
|
||
|
object will return a NULL string."
|
||
|
::= { eventInformationGroup 1 }
|
||
|
|
||
|
eventStatusCondition OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
nonError(0),
|
||
|
error(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The condition of the enumerated integer value of the status
|
||
|
object included in a trap. The value of this object is set
|
||
|
only when sent with a trap. A get of this object will
|
||
|
return zero."
|
||
|
::= { eventInformationGroup 2 }
|
||
|
|
||
|
--
|
||
|
-- Notifications
|
||
|
--
|
||
|
|
||
|
sentry3Traps OBJECT IDENTIFIER ::= { sentry3 100 }
|
||
|
|
||
|
events OBJECT IDENTIFIER ::= { sentry3Traps 0 }
|
||
|
-- the 0 is for V1 compatibility
|
||
|
|
||
|
-- Tower Traps
|
||
|
|
||
|
towerStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
towerID,
|
||
|
towerName,
|
||
|
towerStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Tower status event. If enabled, this trap is sent when the
|
||
|
towerStatus indicates an error state ('noComm', 'fanFail',
|
||
|
'overTemp', 'nvmFail', or 'outOfBalance'). This trap is
|
||
|
repeated periodically while the towerStatus remains in an
|
||
|
error state. If the towerStatus returns to a non-error
|
||
|
state ('normal'), this trap is sent once more with the
|
||
|
non-error towerStatus, and then stops being repeated.
|
||
|
|
||
|
While the towerStatus indicates a 'noComm' error state, all
|
||
|
status and load traps are suppressed for input feeds and
|
||
|
outlets on the tower."
|
||
|
--#TYPE "Sentry: Tower Status Event."
|
||
|
--#SUMMARY "Status of Tower '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 1 }
|
||
|
|
||
|
-- Input Feed Traps
|
||
|
|
||
|
infeedStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
infeedID,
|
||
|
infeedName,
|
||
|
infeedStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input feed status event. If enabled, this trap is sent when
|
||
|
the infeedStatus indicates an error state ('offError',
|
||
|
'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is
|
||
|
repeated periodically while the infeedStatus remains in an
|
||
|
error state. If the infeedStatus returns to a non-error
|
||
|
state ('off' or 'on'), this trap is sent once more with the
|
||
|
non-error infeedStatus, and then stops being repeated.
|
||
|
|
||
|
While the infeedStatus indicates an error state, load
|
||
|
traps are suppressed for the input feed, and, if the
|
||
|
infeedCapabilities 'failSafe' bit is FALSE, all status and
|
||
|
load traps are suppressed for outlets on the input feed."
|
||
|
--#TYPE "Sentry: Input Feed Status Event."
|
||
|
--#SUMMARY "Status of Input Feed '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 2 }
|
||
|
|
||
|
infeedLoadEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
infeedID,
|
||
|
infeedName,
|
||
|
infeedLoadStatus,
|
||
|
infeedLoadValue,
|
||
|
infeedLoadHighThresh,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input feed load event. If enabled, this trap is sent when
|
||
|
the infeedLoadStatus indicates an error state ('loadLow',
|
||
|
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
|
||
|
trap is repeated periodically while the infeedLoadStatus
|
||
|
remains in an error state. If the infeedLoadStatus returns
|
||
|
to a non-error state ('normal' or 'notOn'), this trap is
|
||
|
sent once more with the non-error infeedLoadStatus, and then
|
||
|
stops being repeated."
|
||
|
--#TYPE "Sentry: Input Feed Load Event."
|
||
|
--#SUMMARY "Load Status of Input Feed '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 6 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 3 }
|
||
|
|
||
|
-- Outlet Traps
|
||
|
|
||
|
outletStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
outletID,
|
||
|
outletName,
|
||
|
outletStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet status event. If enabled, this trap is sent when the
|
||
|
outletStatus indicates an error state ('offError', 'onError',
|
||
|
'noComm', 'offFuse', or 'onFuse'). This trap is repeated
|
||
|
periodically while the outletStatus remains in an error state.
|
||
|
If the outletStatus returns to a non-error state ('off' or
|
||
|
'on'), this trap is sent once more with the non-error
|
||
|
outletStatus, and then stops being repeated.
|
||
|
|
||
|
While the outletStatus indicates an error state, load traps
|
||
|
are suppressed for the outlet."
|
||
|
--#TYPE "Sentry: Outlet Status Event."
|
||
|
--#SUMMARY "Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 4 }
|
||
|
|
||
|
outletLoadEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
outletID,
|
||
|
outletName,
|
||
|
outletLoadStatus,
|
||
|
outletLoadValue,
|
||
|
outletLoadLowThresh,
|
||
|
outletLoadHighThresh,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet load event. If enabled, this trap is sent when the
|
||
|
outletLoadStatus indicates an error state ('loadLow',
|
||
|
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
|
||
|
trap is repeated periodically while the outletLoadStatus
|
||
|
remains in an error state. If the outletLoadStatus returns
|
||
|
to a non-error state ('normal' or 'notOn'), this trap is
|
||
|
sent once more with the non-error outletLoadStatus, and then
|
||
|
stops being repeated."
|
||
|
--#TYPE "Sentry: Outlet Load Event."
|
||
|
--#SUMMARY "Load Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 7 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 5 }
|
||
|
|
||
|
outletChangeEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
outletID,
|
||
|
outletName,
|
||
|
outletStatus,
|
||
|
outletControlState,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet on/off change event. If enabled, this trap is sent
|
||
|
when the outletStatus changes from any 'on' state ('on',
|
||
|
'onWait', 'onError', or 'onFuse') to any 'off' state ('off',
|
||
|
'offWait', 'offError', or 'offFuse'), and vice-versa."
|
||
|
--#TYPE "Sentry: Outlet Change Event."
|
||
|
--#SUMMARY "Outlet '%s' (%s) has changed to '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY INFORMATIONAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Status Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 6 }
|
||
|
|
||
|
-- Environmental Monitor Traps
|
||
|
|
||
|
envMonStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
envMonID,
|
||
|
envMonName,
|
||
|
envMonStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Environmental monitor status event. If enabled, this trap
|
||
|
is sent when the envMonStatus indicates an error state
|
||
|
('noComm'). This trap is repeated periodically while the
|
||
|
envMonStatus remains in an error state. If the envMonStatus
|
||
|
returns to a non-error state ('normal'), this trap is sent
|
||
|
once more with the non-error envMonStatus, and then stops
|
||
|
being repeated.
|
||
|
|
||
|
While the envMonStatus indicates an error state, all status
|
||
|
traps are suppressed for the water sensor, ADC, temperature/
|
||
|
humidity sensors, and contact closures on the environmental
|
||
|
monitor."
|
||
|
--#TYPE "Sentry: Environmental Monitor Status Event."
|
||
|
--#SUMMARY "Status of Environmental Monitor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 7 }
|
||
|
|
||
|
envMonWaterSensorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
envMonID,
|
||
|
envMonWaterSensorName,
|
||
|
envMonWaterSensorStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Environmental monitor water sensor event. If enabled, this
|
||
|
trap is sent when the envMonWaterSensorStatus indicates an
|
||
|
error state ('alarm'). This trap is repeated periodically
|
||
|
while the envMonWaterSensorStatus remains in an error state.
|
||
|
If the envMonWaterSensorStatus returns to a non-error state
|
||
|
('normal'), this trap is sent once more with the non-error
|
||
|
envMonWaterSensorStatus, and then stops being repeated."
|
||
|
--#TYPE "Sentry: Water Sensor Event."
|
||
|
--#SUMMARY "Status of Water Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 8 }
|
||
|
|
||
|
envMonADCEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
envMonID,
|
||
|
envMonADCName,
|
||
|
envMonADCStatus,
|
||
|
envMonADCCount,
|
||
|
envMonADCLowThresh,
|
||
|
envMonADCHighThresh,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Environmental monitor analog-to-digital converter event.
|
||
|
If enabled, this trap is sent when the envMonADCStatus
|
||
|
indicates an error state ('countLow' or 'countHigh'). This
|
||
|
trap is repeated periodically while the envMonADCStatus
|
||
|
remains in an error state. If the envMonADCStatus returns
|
||
|
to a non-error state ('normal'), this trap is sent once more
|
||
|
with the non-error envMonADCStatus, and then stops being
|
||
|
repeated."
|
||
|
--#TYPE "Sentry: ADC Event."
|
||
|
--#SUMMARY "Status of ADC '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 7 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 9 }
|
||
|
|
||
|
tempHumidSensorStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
tempHumidSensorID,
|
||
|
tempHumidSensorName,
|
||
|
tempHumidSensorStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature/humidity sensor status event. If enabled, this
|
||
|
trap is sent when the tempHumidSensorStatus indicates an
|
||
|
error state ('lost'). This trap is repeated periodically
|
||
|
while the tempHumidSensorStatus remains in an error state.
|
||
|
If the tempHumidSensorStatus returns to a non-error state
|
||
|
('found'), this trap is sent once more with the non-error
|
||
|
tempHumidSensorStatus, and then stops being repeated.
|
||
|
|
||
|
While the tempHumidSensorStatus indicates an error state, all
|
||
|
temperature and humidity status traps are suppressed for the
|
||
|
temperature/humidity sensor."
|
||
|
--#TYPE "Sentry: T/H Sensor Status Event."
|
||
|
--#SUMMARY "Status of T/H Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 10 }
|
||
|
|
||
|
tempHumidSensorTempEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
tempHumidSensorID,
|
||
|
tempHumidSensorName,
|
||
|
tempHumidSensorTempStatus,
|
||
|
tempHumidSensorTempValue,
|
||
|
tempHumidSensorTempLowThresh,
|
||
|
tempHumidSensorTempHighThresh,
|
||
|
tempHumidSensorTempScale,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature/humidity sensor temperature event. If enabled,
|
||
|
this trap is sent when the tempHumidSensorTempStatus
|
||
|
indicates an error state ('tempLow' or 'tempHigh').
|
||
|
This trap is repeated periodically while the
|
||
|
tempHumidSensorTempStatus remains in an error state. If
|
||
|
the tempHumidSensorTempStatus returns to a non-error state
|
||
|
('normal'), this trap is sent once more with the non-error
|
||
|
tempHumidSensorTempStatus, and then stops being repeated."
|
||
|
--#TYPE "Sentry: T/H Sensor Temperature Event."
|
||
|
--#SUMMARY "Temperature Status of T/H Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 8 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 11 }
|
||
|
|
||
|
tempHumidSensorHumidEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
tempHumidSensorID,
|
||
|
tempHumidSensorName,
|
||
|
tempHumidSensorHumidStatus,
|
||
|
tempHumidSensorHumidValue,
|
||
|
tempHumidSensorHumidLowThresh,
|
||
|
tempHumidSensorHumidHighThresh,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature/humidity sensor humidity event. If enabled,
|
||
|
this trap is sent when the tempHumidSensorHumidStatus
|
||
|
indicates an error state ('humidLow' or 'humidHigh').
|
||
|
This trap is repeated periodically while the
|
||
|
tempHumidSensorHumidStatus remains in an error state. If
|
||
|
the tempHumidSensorHumidStatus returns to a non-error state
|
||
|
('normal'), this trap is sent once more with the non-error
|
||
|
tempHumidSensorHumidStatus, and then stops being repeated."
|
||
|
--#TYPE "Sentry: T/H Sensor Humidity Event."
|
||
|
--#SUMMARY "Humidity Status of T/H Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 7 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 12 }
|
||
|
|
||
|
contactClosureEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
contactClosureID,
|
||
|
contactClosureName,
|
||
|
contactClosureStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure event. If enabled, this trap is sent when
|
||
|
the contactClosureStatus indicates an error state ('alarm').
|
||
|
This trap is repeated periodically while the
|
||
|
contactClosureStatus remains in an error state. If the
|
||
|
contactClosureStatus returns to a non-error state ('normal'),
|
||
|
this trap is sent once more with the non-error
|
||
|
contactClosureStatus, and then stops being repeated."
|
||
|
--#TYPE "Sentry: Contact Closure Event."
|
||
|
--#SUMMARY "Status of Contact Closure '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 13 }
|
||
|
|
||
|
-- Branch Traps
|
||
|
|
||
|
branchStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
branchID,
|
||
|
branchName,
|
||
|
branchStatus,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch status event. If enabled, this trap is sent when
|
||
|
the branchStatus indicates an error state ('offError',
|
||
|
'onError', 'noComm', 'offFuse', or 'onFuse'). This trap
|
||
|
is repeated periodically while the branchStatus remains in
|
||
|
an error state. If the branchStatus returns to a non-error
|
||
|
state ('off' or 'on'), this trap is sent once more with the
|
||
|
non-error branchStatus, and then stops being repeated.
|
||
|
|
||
|
While the branchStatus indicates an error state, load traps
|
||
|
are suppressed for the branch."
|
||
|
--#TYPE "Sentry: Branch Status Event."
|
||
|
--#SUMMARY "Status of Branch '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 14 }
|
||
|
|
||
|
branchLoadEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
systemLocation,
|
||
|
branchID,
|
||
|
branchName,
|
||
|
branchLoadStatus,
|
||
|
branchLoadValue,
|
||
|
branchLoadHighThresh,
|
||
|
eventStatusText,
|
||
|
eventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch load event. If enabled, this trap is sent when
|
||
|
the branchLoadStatus indicates an error state ('loadLow',
|
||
|
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
|
||
|
trap is repeated periodically while the branchLoadStatus
|
||
|
remains in an error state. If the branchLoadStatus returns
|
||
|
to a non-error state ('normal' or 'notOn'), this trap is
|
||
|
sent once more with the non-error branchLoadStatus, and then
|
||
|
stops being repeated."
|
||
|
--#TYPE "Sentry: Branch Load Event."
|
||
|
--#SUMMARY "Load Status of Branch '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 6 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { events 15 }
|
||
|
|
||
|
END
|