4777 lines
156 KiB
Plaintext
4777 lines
156 KiB
Plaintext
|
--
|
||
|
-- Copyright(C) 2003-2017 Server Technology, Inc.
|
||
|
--
|
||
|
|
||
|
Sentry4-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
MODULE-IDENTITY, enterprises, Integer32,
|
||
|
OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
||
|
OBJECT-GROUP, NOTIFICATION-GROUP, MODULE-COMPLIANCE FROM SNMPv2-CONF
|
||
|
TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC;
|
||
|
|
||
|
|
||
|
sentry4 MODULE-IDENTITY
|
||
|
LAST-UPDATED "201706151830Z" -- 15 June 2017
|
||
|
ORGANIZATION "Server Technology, Inc."
|
||
|
CONTACT-INFO
|
||
|
"Server Technology, Inc.
|
||
|
1040 Sandhill Road
|
||
|
Reno, NV 89521
|
||
|
Tel: (775) 284-2000
|
||
|
Fax: (775) 284-2065
|
||
|
Email: mibmaster@servertech.com"
|
||
|
DESCRIPTION
|
||
|
"This is the MIB module for the fourth generation of the
|
||
|
Sentry product family. This includes the PRO1 and PRO2
|
||
|
series of Smart and Switched Cabinet Distribution Unit (CDU)
|
||
|
and Power Distribution Unit (PDU) products."
|
||
|
REVISION "201706151830Z" -- 15 June 2017
|
||
|
DESCRIPTION
|
||
|
"Added support for fan sensors, including objects for installed
|
||
|
count, identification, speed and status monitoring, threshold
|
||
|
and hysteresis configuration, and a notification for events.
|
||
|
Added the st4UnitOutletDisplayOrder object."
|
||
|
REVISION "201611182340Z" -- 18 November 2016
|
||
|
DESCRIPTION
|
||
|
"Added the st4UnitProductMfrDate object. Adjusted the upper
|
||
|
limit of voltage objects to 600 Volts."
|
||
|
REVISION "201609212300Z" -- 21 September 2016
|
||
|
DESCRIPTION
|
||
|
"Fixed the st4InputCordOutOfBalanceEvent notification
|
||
|
definition to include the correct objects."
|
||
|
REVISION "201604252140Z" -- 25 April 2016
|
||
|
DESCRIPTION
|
||
|
"Added support for the PRO1 product series. Added the
|
||
|
st4SystemProductSeries and st4InputCordNominalPowerFactor
|
||
|
objects. Adjusted the upper limit of cord and line current
|
||
|
objects to 600 Amps. Adjusted the lower limit of nominal
|
||
|
voltage objects to 0 Volts. Corrected the lower limit of
|
||
|
several configuration objects from -1 to 0."
|
||
|
REVISION "201502191000Z" -- 19 February 2015
|
||
|
DESCRIPTION
|
||
|
"Corrected the UNITS and value range of temperature sensor
|
||
|
threshold objects."
|
||
|
REVISION "201412231130Z" -- 23 December 2014
|
||
|
DESCRIPTION
|
||
|
"Initial release."
|
||
|
::= { serverTech 4 }
|
||
|
|
||
|
serverTech OBJECT IDENTIFIER ::= { enterprises 1718 }
|
||
|
|
||
|
|
||
|
-- Common Definitions
|
||
|
|
||
|
DeviceStatus ::= TEXTUAL-CONVENTION
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Status returned by devices."
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0), -- operating properly
|
||
|
disabled(1), -- disabled
|
||
|
purged(2), -- purged
|
||
|
reading(5), -- read in process
|
||
|
settle(6), -- is settling
|
||
|
notFound(7), -- never connected
|
||
|
lost(8), -- disconnected
|
||
|
readError(9), -- read failure
|
||
|
noComm(10), -- unreachable
|
||
|
pwrError(11), -- power detection error
|
||
|
breakerTripped(12), -- breaker error
|
||
|
fuseBlown(13), -- fuse error
|
||
|
lowAlarm(14), -- under low alarm threshold
|
||
|
lowWarning(15), -- under low warning threshold
|
||
|
highWarning(16), -- over high warning threshold
|
||
|
highAlarm(17), -- over high alarm threshold
|
||
|
alarm(18), -- general alarm
|
||
|
underLimit(19), -- under limit alarm
|
||
|
overLimit(20), -- over limit alarm
|
||
|
nvmFail(21), -- NVM failure
|
||
|
profileError(22), -- profile error
|
||
|
conflict(23) -- conflict
|
||
|
}
|
||
|
|
||
|
DeviceState ::= TEXTUAL-CONVENTION
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"On or off state of devices."
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(0), -- on / off state is unknown
|
||
|
on(1), -- is on
|
||
|
off(2) -- is off
|
||
|
}
|
||
|
|
||
|
EventNotificationMethods ::= TEXTUAL-CONVENTION
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Bits to enable event notification methods."
|
||
|
SYNTAX BITS {
|
||
|
snmpTrap(0), -- enables notifications by SNMP traps
|
||
|
email(1) -- enables notifications by Email
|
||
|
}
|
||
|
|
||
|
-- Object Definitions
|
||
|
|
||
|
st4Objects OBJECT IDENTIFIER ::= { sentry4 1 }
|
||
|
|
||
|
-- System
|
||
|
|
||
|
st4System OBJECT IDENTIFIER ::= { st4Objects 1 }
|
||
|
|
||
|
-- System Configuration
|
||
|
|
||
|
st4SystemConfig OBJECT IDENTIFIER ::= { st4System 1 }
|
||
|
|
||
|
st4SystemProductName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..63))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The product name."
|
||
|
::= { st4SystemConfig 1 }
|
||
|
|
||
|
st4SystemLocation OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..63))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The location of the system."
|
||
|
::= { st4SystemConfig 2 }
|
||
|
|
||
|
st4SystemFirmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..63))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The firmware version."
|
||
|
::= { st4SystemConfig 3 }
|
||
|
|
||
|
st4SystemFirmwareBuildInfo OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..63))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The firmware build information."
|
||
|
::= { st4SystemConfig 4 }
|
||
|
|
||
|
st4SystemNICSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..8))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The serial number of the network interface card."
|
||
|
::= { st4SystemConfig 5 }
|
||
|
|
||
|
st4SystemNICHardwareInfo OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..63))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Hardware information about the network interface card."
|
||
|
::= { st4SystemConfig 6 }
|
||
|
|
||
|
st4SystemProductSeries OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
pro1(0),
|
||
|
pro2(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The product series."
|
||
|
::= { st4SystemConfig 7 }
|
||
|
|
||
|
st4SystemFeatures OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
smartLoadShedding(0),
|
||
|
reserved(1),
|
||
|
outletControlInhibit(2)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The key-activated features enabled in the system."
|
||
|
::= { st4SystemConfig 10 }
|
||
|
|
||
|
st4SystemFeatureKey OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..19))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"A valid feature key written to this object will enable a
|
||
|
feature in the system. A valid feature key is in the form
|
||
|
xxxx-xxxx-xxxx-xxxx. A read of this object returns an
|
||
|
empty string."
|
||
|
::= { st4SystemConfig 11 }
|
||
|
|
||
|
st4SystemConfigModifiedCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..2147483647)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total number of times the system configuration has changed."
|
||
|
::= { st4SystemConfig 20 }
|
||
|
|
||
|
st4SystemUnitCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..8)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of units in the system."
|
||
|
::= { st4SystemConfig 21 }
|
||
|
|
||
|
-- Units
|
||
|
|
||
|
st4Units OBJECT IDENTIFIER ::= { st4Objects 2 }
|
||
|
|
||
|
-- Unit Common Configuration
|
||
|
|
||
|
st4UnitCommonConfig OBJECT IDENTIFIER ::= { st4Units 1 }
|
||
|
|
||
|
-- Unit Configuration Table
|
||
|
|
||
|
st4UnitConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4UnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit configuration table."
|
||
|
::= { st4Units 2 }
|
||
|
|
||
|
st4UnitConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4UnitConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular unit."
|
||
|
INDEX { st4UnitIndex }
|
||
|
::= { st4UnitConfigTable 1 }
|
||
|
|
||
|
St4UnitConfigEntry ::= SEQUENCE {
|
||
|
st4UnitIndex Integer32,
|
||
|
st4UnitID DisplayString,
|
||
|
st4UnitName DisplayString,
|
||
|
st4UnitProductSN DisplayString,
|
||
|
st4UnitModel DisplayString,
|
||
|
st4UnitAssetTag DisplayString,
|
||
|
st4UnitType INTEGER,
|
||
|
st4UnitCapabilities BITS,
|
||
|
st4UnitProductMfrDate DisplayString,
|
||
|
st4UnitDisplayOrientation INTEGER,
|
||
|
st4UnitOutletSequenceOrder INTEGER,
|
||
|
st4UnitOutletDisplayOrder INTEGER,
|
||
|
st4UnitInputCordCount Integer32,
|
||
|
st4UnitTempSensorCount Integer32,
|
||
|
st4UnitHumidSensorCount Integer32,
|
||
|
st4UnitWaterSensorCount Integer32,
|
||
|
st4UnitCcSensorCount Integer32,
|
||
|
st4UnitAdcSensorCount Integer32,
|
||
|
st4UnitFanSensorCount Integer32
|
||
|
}
|
||
|
|
||
|
st4UnitIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..6)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit index. A=1, B=2, C=3, D=4, E=5, F=6."
|
||
|
::= { st4UnitConfigEntry 1 }
|
||
|
|
||
|
st4UnitID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(1))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the unit. Format=A."
|
||
|
::= { st4UnitConfigEntry 2 }
|
||
|
|
||
|
st4UnitName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the unit."
|
||
|
::= { st4UnitConfigEntry 3 }
|
||
|
|
||
|
st4UnitProductSN OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The product serial number of the unit."
|
||
|
::= { st4UnitConfigEntry 4 }
|
||
|
|
||
|
st4UnitModel OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The model of the unit."
|
||
|
::= { st4UnitConfigEntry 5 }
|
||
|
|
||
|
st4UnitAssetTag OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The asset tag of the unit."
|
||
|
::= { st4UnitConfigEntry 6 }
|
||
|
|
||
|
st4UnitType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
masterPdu(0),
|
||
|
linkPdu(1),
|
||
|
controller(2),
|
||
|
emcu(3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of the unit."
|
||
|
::= { st4UnitConfigEntry 7 }
|
||
|
|
||
|
st4UnitCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
dc(0), -- unit is DC
|
||
|
phase3(1), -- unit is 3 phase
|
||
|
wye(2), -- unit has Wye circuits
|
||
|
delta(3) -- unit has Delta circuits
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the unit."
|
||
|
::= { st4UnitConfigEntry 8 }
|
||
|
|
||
|
st4UnitProductMfrDate OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..10))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The product manufacture date in YYYY-MM-DD (ISO 8601 format) of
|
||
|
the unit."
|
||
|
::= { st4UnitConfigEntry 9 }
|
||
|
|
||
|
st4UnitDisplayOrientation OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
inverted(1),
|
||
|
auto(2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The orientation of all displays in the unit."
|
||
|
::= { st4UnitConfigEntry 20 }
|
||
|
|
||
|
st4UnitOutletSequenceOrder OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
reversed(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The sequencing order of all outlets in the unit."
|
||
|
::= { st4UnitConfigEntry 21 }
|
||
|
|
||
|
st4UnitOutletDisplayOrder OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
normal(0),
|
||
|
reversed(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The display order in the user interfaces of all outlets in the
|
||
|
unit."
|
||
|
::= { st4UnitConfigEntry 22 }
|
||
|
|
||
|
st4UnitInputCordCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of power input cords into the unit."
|
||
|
::= { st4UnitConfigEntry 30 }
|
||
|
|
||
|
st4UnitTempSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..2)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of external temperature sensors supported by the unit."
|
||
|
::= { st4UnitConfigEntry 31 }
|
||
|
|
||
|
st4UnitHumidSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..2)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of external humidity sensors supported by the unit."
|
||
|
::= { st4UnitConfigEntry 32 }
|
||
|
|
||
|
st4UnitWaterSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of external water sensors supported by the unit."
|
||
|
::= { st4UnitConfigEntry 33 }
|
||
|
|
||
|
st4UnitCcSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of external contact closure sensors supported by the
|
||
|
unit."
|
||
|
::= { st4UnitConfigEntry 34 }
|
||
|
|
||
|
st4UnitAdcSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of analog-to-digital converter sensors supported by the
|
||
|
unit."
|
||
|
::= { st4UnitConfigEntry 35 }
|
||
|
|
||
|
st4UnitFanSensorCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of fan sensors supported by the unit."
|
||
|
::= { st4UnitConfigEntry 36 }
|
||
|
|
||
|
-- Unit Monitor Table
|
||
|
|
||
|
st4UnitMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4UnitMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit monitor table."
|
||
|
::= { st4Units 3 }
|
||
|
|
||
|
st4UnitMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4UnitMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular unit."
|
||
|
INDEX { st4UnitIndex }
|
||
|
::= { st4UnitMonitorTable 1 }
|
||
|
|
||
|
St4UnitMonitorEntry ::= SEQUENCE {
|
||
|
st4UnitStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4UnitStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the unit."
|
||
|
::= { st4UnitMonitorEntry 1 }
|
||
|
|
||
|
-- Unit Event Configuration Table
|
||
|
|
||
|
st4UnitEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4UnitEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit event configuration table."
|
||
|
::= { st4Units 4 }
|
||
|
|
||
|
st4UnitEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4UnitEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular unit."
|
||
|
INDEX { st4UnitIndex }
|
||
|
::= { st4UnitEventConfigTable 1 }
|
||
|
|
||
|
St4UnitEventConfigEntry ::= SEQUENCE {
|
||
|
st4UnitNotifications EventNotificationMethods
|
||
|
}
|
||
|
|
||
|
st4UnitNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for unit events."
|
||
|
::= { st4UnitEventConfigEntry 1 }
|
||
|
|
||
|
-- Input Cords
|
||
|
|
||
|
st4InputCords OBJECT IDENTIFIER ::= { st4Objects 3 }
|
||
|
|
||
|
-- Input Cord Common Configuration
|
||
|
|
||
|
st4InputCordCommonConfig OBJECT IDENTIFIER ::= { st4InputCords 1 }
|
||
|
|
||
|
st4InputCordActivePowerHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power hysteresis of the input cord in Watts."
|
||
|
::= { st4InputCordCommonConfig 1 }
|
||
|
|
||
|
st4InputCordApparentPowerHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power hysteresis of the input cord in Volt-Amps."
|
||
|
::= { st4InputCordCommonConfig 2 }
|
||
|
|
||
|
st4InputCordPowerFactorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..20)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor hysteresis of the input cord in hundredths."
|
||
|
::= { st4InputCordCommonConfig 3 }
|
||
|
|
||
|
st4InputCordOutOfBalanceHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10)
|
||
|
UNITS "percent"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 3 phase out-of-balance hysteresis of the input cord in
|
||
|
percent."
|
||
|
::= { st4InputCordCommonConfig 4 }
|
||
|
|
||
|
-- Input Cord Configuration Table
|
||
|
|
||
|
st4InputCordConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4InputCordConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord configuration table."
|
||
|
::= { st4InputCords 2 }
|
||
|
|
||
|
st4InputCordConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4InputCordConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular input cord."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
||
|
::= { st4InputCordConfigTable 1 }
|
||
|
|
||
|
St4InputCordConfigEntry ::= SEQUENCE {
|
||
|
st4InputCordIndex Integer32,
|
||
|
st4InputCordID DisplayString,
|
||
|
st4InputCordName DisplayString,
|
||
|
st4InputCordInletType DisplayString,
|
||
|
st4InputCordNominalVoltage Integer32,
|
||
|
st4InputCordNominalVoltageMin Integer32,
|
||
|
st4InputCordNominalVoltageMax Integer32,
|
||
|
st4InputCordCurrentCapacity Integer32,
|
||
|
st4InputCordCurrentCapacityMax Integer32,
|
||
|
st4InputCordPowerCapacity Integer32,
|
||
|
st4InputCordNominalPowerFactor Integer32,
|
||
|
st4InputCordLineCount Integer32,
|
||
|
st4InputCordPhaseCount Integer32,
|
||
|
st4InputCordOcpCount Integer32,
|
||
|
st4InputCordBranchCount Integer32,
|
||
|
st4InputCordOutletCount Integer32
|
||
|
}
|
||
|
|
||
|
st4InputCordIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord index. A=1, B=2, C=3, D=4."
|
||
|
::= { st4InputCordConfigEntry 1 }
|
||
|
|
||
|
st4InputCordID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the input cord. Format=AA."
|
||
|
::= { st4InputCordConfigEntry 2 }
|
||
|
|
||
|
st4InputCordName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the input cord."
|
||
|
::= { st4InputCordConfigEntry 3 }
|
||
|
|
||
|
st4InputCordInletType OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of plug on the input cord, or socket for the input cord."
|
||
|
::= { st4InputCordConfigEntry 6}
|
||
|
|
||
|
st4InputCordNominalVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-configured nominal voltage of the input cord in tenth
|
||
|
Volts."
|
||
|
::= { st4InputCordConfigEntry 7 }
|
||
|
|
||
|
st4InputCordNominalVoltageMin OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..600)
|
||
|
UNITS "Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The factory-set minimum allowed for the user-configured nominal
|
||
|
voltage of the input cord in Volts."
|
||
|
::= { st4InputCordConfigEntry 8 }
|
||
|
|
||
|
st4InputCordNominalVoltageMax OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..600)
|
||
|
UNITS "Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The factory-set maximum allowed for the user-configured nominal
|
||
|
voltage of the input cord in Volts."
|
||
|
::= { st4InputCordConfigEntry 9 }
|
||
|
|
||
|
st4InputCordCurrentCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..600)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-configured current capacity of the input cord in Amps."
|
||
|
::= { st4InputCordConfigEntry 10 }
|
||
|
|
||
|
st4InputCordCurrentCapacityMax OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..600)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The factory-set maximum allowed for the user-configured current
|
||
|
capacity of the input cord in Amps."
|
||
|
::= { st4InputCordConfigEntry 11 }
|
||
|
|
||
|
st4InputCordPowerCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power capacity of the input cord in Volt-Amps. For DC
|
||
|
products, this is identical to power capacity in Watts."
|
||
|
::= { st4InputCordConfigEntry 12 }
|
||
|
|
||
|
st4InputCordNominalPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-configured estimated nominal power factor of the input
|
||
|
cord in hundredths."
|
||
|
::= { st4InputCordConfigEntry 13 }
|
||
|
|
||
|
st4InputCordLineCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of current-carrying lines in the input cord."
|
||
|
::= { st4InputCordConfigEntry 20 }
|
||
|
|
||
|
st4InputCordPhaseCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of active phases from the lines in the input cord."
|
||
|
::= { st4InputCordConfigEntry 21 }
|
||
|
|
||
|
st4InputCordOcpCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..12)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of over-current protectors downstream from the input
|
||
|
cord."
|
||
|
::= { st4InputCordConfigEntry 22 }
|
||
|
|
||
|
st4InputCordBranchCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..12)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of branches downstream from the input cord."
|
||
|
::= { st4InputCordConfigEntry 23 }
|
||
|
|
||
|
st4InputCordOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..128)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of outlets powered from the input cord."
|
||
|
::= { st4InputCordConfigEntry 24 }
|
||
|
|
||
|
-- Input Cord Monitor Table
|
||
|
|
||
|
st4InputCordMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4InputCordMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord monitor table."
|
||
|
::= { st4InputCords 3 }
|
||
|
|
||
|
st4InputCordMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4InputCordMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular input cord."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
||
|
::= { st4InputCordMonitorTable 1 }
|
||
|
|
||
|
St4InputCordMonitorEntry ::= SEQUENCE {
|
||
|
st4InputCordState DeviceState,
|
||
|
st4InputCordStatus DeviceStatus,
|
||
|
st4InputCordActivePower Integer32,
|
||
|
st4InputCordActivePowerStatus DeviceStatus,
|
||
|
st4InputCordApparentPower Integer32,
|
||
|
st4InputCordApparentPowerStatus DeviceStatus,
|
||
|
st4InputCordPowerUtilized Integer32,
|
||
|
st4InputCordPowerFactor Integer32,
|
||
|
st4InputCordPowerFactorStatus DeviceStatus,
|
||
|
st4InputCordEnergy Integer32,
|
||
|
st4InputCordFrequency Integer32,
|
||
|
st4InputCordOutOfBalance Integer32,
|
||
|
st4InputCordOutOfBalanceStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4InputCordState OBJECT-TYPE
|
||
|
SYNTAX DeviceState
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The on/off state of the input cord."
|
||
|
::= { st4InputCordMonitorEntry 1 }
|
||
|
|
||
|
st4InputCordStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the input cord."
|
||
|
::= { st4InputCordMonitorEntry 2 }
|
||
|
|
||
|
st4InputCordActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured active power of the input cord in Watts."
|
||
|
::= { st4InputCordMonitorEntry 3 }
|
||
|
|
||
|
st4InputCordActivePowerStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured active power of the input cord."
|
||
|
::= { st4InputCordMonitorEntry 4 }
|
||
|
|
||
|
st4InputCordApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured apparent power of the input cord in Volt-Amps."
|
||
|
::= { st4InputCordMonitorEntry 5 }
|
||
|
|
||
|
st4InputCordApparentPowerStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured apparent power of the input cord."
|
||
|
::= { st4InputCordMonitorEntry 6 }
|
||
|
|
||
|
st4InputCordPowerUtilized OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..1200)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of the input cord power capacity used in tenth percent.
|
||
|
For AC products, this is the ratio of the apparent power to the
|
||
|
power capacity. For DC products, this is the ratio of the active
|
||
|
power to the power capacity."
|
||
|
::= { st4InputCordMonitorEntry 7 }
|
||
|
|
||
|
st4InputCordPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured power factor of the input cord in hundredths."
|
||
|
::= { st4InputCordMonitorEntry 8 }
|
||
|
|
||
|
st4InputCordPowerFactorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured power factor of the input cord."
|
||
|
::= { st4InputCordMonitorEntry 9 }
|
||
|
|
||
|
st4InputCordEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..2147483647)
|
||
|
UNITS "tenth Kilowatt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total energy consumption of loads through the input cord in
|
||
|
tenth Kilowatt-Hours."
|
||
|
::= { st4InputCordMonitorEntry 10 }
|
||
|
|
||
|
st4InputCordFrequency OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..1000)
|
||
|
UNITS "tenth Hertz"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The frequency of the input cord voltage in tenth Hertz."
|
||
|
::= { st4InputCordMonitorEntry 11 }
|
||
|
|
||
|
st4InputCordOutOfBalance OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..2000)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current imbalance on the lines of the input cord in tenth
|
||
|
percent."
|
||
|
::= { st4InputCordMonitorEntry 12 }
|
||
|
|
||
|
st4InputCordOutOfBalanceStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the current imbalance on the lines of the input
|
||
|
cord."
|
||
|
::= { st4InputCordMonitorEntry 13 }
|
||
|
|
||
|
-- Input Cord Event Configuration Table
|
||
|
|
||
|
st4InputCordEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4InputCordEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord event configuration table."
|
||
|
::= { st4InputCords 4 }
|
||
|
|
||
|
st4InputCordEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4InputCordEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular input cord."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
||
|
::= { st4InputCordEventConfigTable 1 }
|
||
|
|
||
|
St4InputCordEventConfigEntry ::= SEQUENCE {
|
||
|
st4InputCordNotifications EventNotificationMethods,
|
||
|
st4InputCordActivePowerLowAlarm Integer32,
|
||
|
st4InputCordActivePowerLowWarning Integer32,
|
||
|
st4InputCordActivePowerHighWarning Integer32,
|
||
|
st4InputCordActivePowerHighAlarm Integer32,
|
||
|
st4InputCordApparentPowerLowAlarm Integer32,
|
||
|
st4InputCordApparentPowerLowWarning Integer32,
|
||
|
st4InputCordApparentPowerHighWarning Integer32,
|
||
|
st4InputCordApparentPowerHighAlarm Integer32,
|
||
|
st4InputCordPowerFactorLowAlarm Integer32,
|
||
|
st4InputCordPowerFactorLowWarning Integer32,
|
||
|
st4InputCordOutOfBalanceHighWarning Integer32,
|
||
|
st4InputCordOutOfBalanceHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4InputCordNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for input cord events."
|
||
|
::= { st4InputCordEventConfigEntry 1 }
|
||
|
|
||
|
st4InputCordActivePowerLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power low alarm threshold of the input cord in Watts."
|
||
|
::= { st4InputCordEventConfigEntry 2 }
|
||
|
|
||
|
st4InputCordActivePowerLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power low warning threshold of the input cord in
|
||
|
Watts."
|
||
|
::= { st4InputCordEventConfigEntry 3 }
|
||
|
|
||
|
st4InputCordActivePowerHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power high warning threshold of the input cord in
|
||
|
Watts."
|
||
|
::= { st4InputCordEventConfigEntry 4 }
|
||
|
|
||
|
st4InputCordActivePowerHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power high alarm threshold of the input cord in Watts."
|
||
|
::= { st4InputCordEventConfigEntry 5 }
|
||
|
|
||
|
st4InputCordApparentPowerLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power low alarm threshold of the input cord in
|
||
|
Volt-Amps."
|
||
|
::= { st4InputCordEventConfigEntry 6 }
|
||
|
|
||
|
st4InputCordApparentPowerLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power low warning threshold of the input cord in
|
||
|
Volt-Amps."
|
||
|
::= { st4InputCordEventConfigEntry 7 }
|
||
|
|
||
|
st4InputCordApparentPowerHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power high warning threshold of the input cord in
|
||
|
Volt-Amps."
|
||
|
::= { st4InputCordEventConfigEntry 8 }
|
||
|
|
||
|
st4InputCordApparentPowerHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..50000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The apparent power high alarm threshold of the input cord in
|
||
|
Volt-Amps."
|
||
|
::= { st4InputCordEventConfigEntry 9 }
|
||
|
|
||
|
st4InputCordPowerFactorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor low alarm threshold of the input cord in
|
||
|
hundredths."
|
||
|
::= { st4InputCordEventConfigEntry 10 }
|
||
|
|
||
|
st4InputCordPowerFactorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor low warning threshold of the input cord in
|
||
|
hundredths."
|
||
|
::= { st4InputCordEventConfigEntry 11 }
|
||
|
|
||
|
st4InputCordOutOfBalanceHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percent"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 3 phase out-of-balance high warning threshold of the input
|
||
|
cord in percent."
|
||
|
::= { st4InputCordEventConfigEntry 12 }
|
||
|
|
||
|
st4InputCordOutOfBalanceHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percent"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 3 phase out-of-balance high alarm threshold of the input cord
|
||
|
in percent."
|
||
|
::= { st4InputCordEventConfigEntry 13 }
|
||
|
|
||
|
-- Lines
|
||
|
|
||
|
st4Lines OBJECT IDENTIFIER ::= { st4Objects 4 }
|
||
|
|
||
|
-- Line Common Configuration
|
||
|
|
||
|
st4LineCommonConfig OBJECT IDENTIFIER ::= { st4Lines 1 }
|
||
|
|
||
|
st4LineCurrentHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current hysteresis of the line in tenth Amps."
|
||
|
::= { st4LineCommonConfig 1 }
|
||
|
|
||
|
-- Line Configuration Table
|
||
|
|
||
|
st4LineConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4LineConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line configuration table."
|
||
|
::= { st4Lines 2 }
|
||
|
|
||
|
st4LineConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4LineConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular line."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
||
|
::= { st4LineConfigTable 1 }
|
||
|
|
||
|
St4LineConfigEntry ::= SEQUENCE {
|
||
|
st4LineIndex Integer32,
|
||
|
st4LineID DisplayString,
|
||
|
st4LineLabel DisplayString,
|
||
|
st4LineCurrentCapacity Integer32
|
||
|
}
|
||
|
|
||
|
st4LineIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line index. L1=1, L2=2, L3=3, N=4."
|
||
|
::= { st4LineConfigEntry 1 }
|
||
|
|
||
|
st4LineID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the line. Format=AAN."
|
||
|
::= { st4LineConfigEntry 2 }
|
||
|
|
||
|
st4LineLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The system label assigned to the line for identification."
|
||
|
::= { st4LineConfigEntry 4 }
|
||
|
|
||
|
st4LineCurrentCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..600)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current capacity of the line in Amps."
|
||
|
::= { st4LineConfigEntry 6 }
|
||
|
|
||
|
-- Line Monitor Table
|
||
|
|
||
|
st4LineMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4LineMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line monitor table."
|
||
|
::= { st4Lines 3 }
|
||
|
|
||
|
st4LineMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4LineMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular line."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
||
|
::= { st4LineMonitorTable 1 }
|
||
|
|
||
|
St4LineMonitorEntry ::= SEQUENCE {
|
||
|
st4LineState DeviceState,
|
||
|
st4LineStatus DeviceStatus,
|
||
|
st4LineCurrent Integer32,
|
||
|
st4LineCurrentStatus DeviceStatus,
|
||
|
st4LineCurrentUtilized Integer32
|
||
|
}
|
||
|
|
||
|
st4LineState OBJECT-TYPE
|
||
|
SYNTAX DeviceState
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The on/off state of the line."
|
||
|
::= { st4LineMonitorEntry 1 }
|
||
|
|
||
|
st4LineStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the line."
|
||
|
::= { st4LineMonitorEntry 2 }
|
||
|
|
||
|
st4LineCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..60000)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured current on the line in hundredth Amps."
|
||
|
::= { st4LineMonitorEntry 3 }
|
||
|
|
||
|
st4LineCurrentStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured current on the line."
|
||
|
::= { st4LineMonitorEntry 4 }
|
||
|
|
||
|
st4LineCurrentUtilized OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..1200)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of the line current capacity used in tenth percent."
|
||
|
::= { st4LineMonitorEntry 5 }
|
||
|
|
||
|
-- Line Event Configuration Table
|
||
|
|
||
|
st4LineEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4LineEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line event configuration table."
|
||
|
::= { st4Lines 4 }
|
||
|
|
||
|
st4LineEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4LineEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular line."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
||
|
::= { st4LineEventConfigTable 1 }
|
||
|
|
||
|
St4LineEventConfigEntry ::= SEQUENCE {
|
||
|
st4LineNotifications EventNotificationMethods,
|
||
|
st4LineCurrentLowAlarm Integer32,
|
||
|
st4LineCurrentLowWarning Integer32,
|
||
|
st4LineCurrentHighWarning Integer32,
|
||
|
st4LineCurrentHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4LineNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for line events."
|
||
|
::= { st4LineEventConfigEntry 1 }
|
||
|
|
||
|
st4LineCurrentLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low alarm threshold of the line in tenth Amps."
|
||
|
::= { st4LineEventConfigEntry 2 }
|
||
|
|
||
|
st4LineCurrentLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low warning threshold of the line in tenth Amps."
|
||
|
::= { st4LineEventConfigEntry 3 }
|
||
|
|
||
|
st4LineCurrentHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high warning threshold of the line in tenth Amps."
|
||
|
::= { st4LineEventConfigEntry 4 }
|
||
|
|
||
|
st4LineCurrentHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high alarm threshold of the line in tenth Amps."
|
||
|
::= { st4LineEventConfigEntry 5 }
|
||
|
|
||
|
-- Phases
|
||
|
|
||
|
st4Phases OBJECT IDENTIFIER ::= { st4Objects 5 }
|
||
|
|
||
|
-- Phase Common Configuration
|
||
|
|
||
|
st4PhaseCommonConfig OBJECT IDENTIFIER ::= { st4Phases 1 }
|
||
|
|
||
|
st4PhaseVoltageHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..200)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The voltage hysteresis of the phase in tenth Volts."
|
||
|
::= { st4PhaseCommonConfig 1 }
|
||
|
|
||
|
st4PhasePowerFactorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..20)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor hysteresis of the phase in hundredths."
|
||
|
::= { st4PhaseCommonConfig 2 }
|
||
|
|
||
|
-- Phase Configuration Table
|
||
|
|
||
|
st4PhaseConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4PhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase configuration table."
|
||
|
::= { st4Phases 2 }
|
||
|
|
||
|
st4PhaseConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4PhaseConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular phase."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
||
|
::= { st4PhaseConfigTable 1 }
|
||
|
|
||
|
St4PhaseConfigEntry ::= SEQUENCE {
|
||
|
st4PhaseIndex Integer32,
|
||
|
st4PhaseID DisplayString,
|
||
|
st4PhaseLabel DisplayString,
|
||
|
st4PhaseNominalVoltage Integer32,
|
||
|
st4PhaseBranchCount Integer32,
|
||
|
st4PhaseOutletCount Integer32
|
||
|
}
|
||
|
|
||
|
st4PhaseIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..6)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3;
|
||
|
Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase:
|
||
|
L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2,
|
||
|
L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6."
|
||
|
::= { st4PhaseConfigEntry 1 }
|
||
|
|
||
|
st4PhaseID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the phase. Format=AAN."
|
||
|
::= { st4PhaseConfigEntry 2 }
|
||
|
|
||
|
st4PhaseLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The system label assigned to the phase for identification."
|
||
|
::= { st4PhaseConfigEntry 4 }
|
||
|
|
||
|
st4PhaseNominalVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The nominal voltage of the phase in tenth Volts."
|
||
|
::= { st4PhaseConfigEntry 6 }
|
||
|
|
||
|
st4PhaseBranchCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..12)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of branches downstream from the phase."
|
||
|
::= { st4PhaseConfigEntry 20 }
|
||
|
|
||
|
st4PhaseOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..128)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of outlets powered from the phase."
|
||
|
::= { st4PhaseConfigEntry 21 }
|
||
|
|
||
|
-- Phase Monitor Table
|
||
|
|
||
|
st4PhaseMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4PhaseMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase monitor table."
|
||
|
::= { st4Phases 3 }
|
||
|
|
||
|
st4PhaseMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4PhaseMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular phase."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
||
|
::= { st4PhaseMonitorTable 1 }
|
||
|
|
||
|
St4PhaseMonitorEntry ::= SEQUENCE {
|
||
|
st4PhaseState DeviceState,
|
||
|
st4PhaseStatus DeviceStatus,
|
||
|
st4PhaseVoltage Integer32,
|
||
|
st4PhaseVoltageStatus DeviceStatus,
|
||
|
st4PhaseVoltageDeviation Integer32,
|
||
|
st4PhaseCurrent Integer32,
|
||
|
st4PhaseCurrentCrestFactor Integer32,
|
||
|
st4PhaseActivePower Integer32,
|
||
|
st4PhaseApparentPower Integer32,
|
||
|
st4PhasePowerFactor Integer32,
|
||
|
st4PhasePowerFactorStatus DeviceStatus,
|
||
|
st4PhaseReactance Integer32,
|
||
|
st4PhaseEnergy Integer32
|
||
|
}
|
||
|
|
||
|
st4PhaseState OBJECT-TYPE
|
||
|
SYNTAX DeviceState
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The on/off state of the phase."
|
||
|
::= { st4PhaseMonitorEntry 1 }
|
||
|
|
||
|
st4PhaseStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the phase."
|
||
|
::= { st4PhaseMonitorEntry 2 }
|
||
|
|
||
|
st4PhaseVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured voltage on the phase in tenth Volts."
|
||
|
::= { st4PhaseMonitorEntry 3 }
|
||
|
|
||
|
st4PhaseVoltageStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured voltage on the phase."
|
||
|
::= { st4PhaseMonitorEntry 4 }
|
||
|
|
||
|
st4PhaseVoltageDeviation OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1000..1000)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The deviation from the nominal voltage on the phase in tenth
|
||
|
percent."
|
||
|
::= { st4PhaseMonitorEntry 5 }
|
||
|
|
||
|
st4PhaseCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..30000)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured current on the phase in hundredth Amps."
|
||
|
::= { st4PhaseMonitorEntry 6 }
|
||
|
|
||
|
st4PhaseCurrentCrestFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..250)
|
||
|
UNITS "tenths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured crest factor of the current waveform on the phase in
|
||
|
tenths."
|
||
|
::= { st4PhaseMonitorEntry 7 }
|
||
|
|
||
|
st4PhaseActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..25000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured active power on the phase in Watts."
|
||
|
::= { st4PhaseMonitorEntry 8 }
|
||
|
|
||
|
st4PhaseApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..25000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured apparent power on the phase in Volt-Amps."
|
||
|
::= { st4PhaseMonitorEntry 9 }
|
||
|
|
||
|
st4PhasePowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured power factor on the phase in hundredths."
|
||
|
::= { st4PhaseMonitorEntry 10 }
|
||
|
|
||
|
st4PhasePowerFactorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured power factor on the phase."
|
||
|
::= { st4PhaseMonitorEntry 11 }
|
||
|
|
||
|
st4PhaseReactance OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(0),
|
||
|
capacitive(1),
|
||
|
inductive(2),
|
||
|
resistive(3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured reactance of the phase."
|
||
|
::= { st4PhaseMonitorEntry 12 }
|
||
|
|
||
|
st4PhaseEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..2147483647)
|
||
|
UNITS "tenth Kilowatt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total energy consumption of loads through the phase in tenth
|
||
|
Kilowatt-Hours."
|
||
|
::= { st4PhaseMonitorEntry 13 }
|
||
|
|
||
|
-- Phase Event Configuration Table
|
||
|
|
||
|
st4PhaseEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4PhaseEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase event configuration table."
|
||
|
::= { st4Phases 4 }
|
||
|
|
||
|
st4PhaseEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4PhaseEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular phase."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
||
|
::= { st4PhaseEventConfigTable 1 }
|
||
|
|
||
|
St4PhaseEventConfigEntry ::= SEQUENCE {
|
||
|
st4PhaseNotifications EventNotificationMethods,
|
||
|
st4PhaseVoltageLowAlarm Integer32,
|
||
|
st4PhaseVoltageLowWarning Integer32,
|
||
|
st4PhaseVoltageHighWarning Integer32,
|
||
|
st4PhaseVoltageHighAlarm Integer32,
|
||
|
st4PhasePowerFactorLowAlarm Integer32,
|
||
|
st4PhasePowerFactorLowWarning Integer32
|
||
|
}
|
||
|
|
||
|
st4PhaseNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for phase events."
|
||
|
::= { st4PhaseEventConfigEntry 1 }
|
||
|
|
||
|
st4PhaseVoltageLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low alarm threshold of the phase in tenth Volts."
|
||
|
::= { st4PhaseEventConfigEntry 2 }
|
||
|
|
||
|
st4PhaseVoltageLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low warning threshold of the phase in tenth Volts."
|
||
|
::= { st4PhaseEventConfigEntry 3 }
|
||
|
|
||
|
st4PhaseVoltageHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high warning threshold of the phase in tenth Volts."
|
||
|
::= { st4PhaseEventConfigEntry 4 }
|
||
|
|
||
|
st4PhaseVoltageHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high alarm threshold of the phase in tenth Volts."
|
||
|
::= { st4PhaseEventConfigEntry 5 }
|
||
|
|
||
|
st4PhasePowerFactorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low power factor alarm threshold of the phase in hundredths."
|
||
|
::= { st4PhaseEventConfigEntry 6 }
|
||
|
|
||
|
st4PhasePowerFactorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low power factor warning threshold of the phase in
|
||
|
hundredths."
|
||
|
::= { st4PhaseEventConfigEntry 7 }
|
||
|
|
||
|
-- Over-Current Protectors
|
||
|
|
||
|
st4OverCurrentProtectors OBJECT IDENTIFIER ::= { st4Objects 6 }
|
||
|
|
||
|
-- Over-Current Protector Common Configuration
|
||
|
|
||
|
st4OcpCommonConfig OBJECT IDENTIFIER ::= { st4OverCurrentProtectors 1 }
|
||
|
|
||
|
-- Over-Current Protector Configuration Table
|
||
|
|
||
|
st4OcpConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OcpConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector configuration table."
|
||
|
::= { st4OverCurrentProtectors 2 }
|
||
|
|
||
|
st4OcpConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4OcpConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular over-current protector."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
||
|
::= { st4OcpConfigTable 1 }
|
||
|
|
||
|
St4OcpConfigEntry ::= SEQUENCE {
|
||
|
st4OcpIndex Integer32,
|
||
|
st4OcpID DisplayString,
|
||
|
st4OcpLabel DisplayString,
|
||
|
st4OcpType INTEGER,
|
||
|
st4OcpCurrentCapacity Integer32,
|
||
|
st4OcpCurrentCapacityMax Integer32,
|
||
|
st4OcpBranchCount Integer32,
|
||
|
st4OcpOutletCount Integer32
|
||
|
}
|
||
|
|
||
|
st4OcpIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..64)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector index."
|
||
|
::= { st4OcpConfigEntry 1 }
|
||
|
|
||
|
st4OcpID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the over-current protector. Format=AAN[N]."
|
||
|
::= { st4OcpConfigEntry 2 }
|
||
|
|
||
|
st4OcpLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The system label assigned to the over-current protector for
|
||
|
identification."
|
||
|
::= { st4OcpConfigEntry 4 }
|
||
|
|
||
|
st4OcpType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
fuse(0),
|
||
|
breaker(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The type of over-current protector."
|
||
|
::= { st4OcpConfigEntry 6 }
|
||
|
|
||
|
st4OcpCurrentCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..125)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The user-configured current capacity of the over-current protector
|
||
|
in Amps."
|
||
|
::= { st4OcpConfigEntry 7 }
|
||
|
|
||
|
st4OcpCurrentCapacityMax OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..125)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The factory-set maximum allowed for the user-configured current
|
||
|
capacity of the over-current protector in Amps."
|
||
|
::= { st4OcpConfigEntry 8 }
|
||
|
|
||
|
st4OcpBranchCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..12)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of branches downstream from the over-current
|
||
|
protector."
|
||
|
::= { st4OcpConfigEntry 20 }
|
||
|
|
||
|
st4OcpOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..128)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of outlets powered from the over-current protector."
|
||
|
::= { st4OcpConfigEntry 21 }
|
||
|
|
||
|
-- Over-Current Protector Monitor Table
|
||
|
|
||
|
st4OcpMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OcpMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector monitor table."
|
||
|
::= { st4OverCurrentProtectors 3 }
|
||
|
|
||
|
st4OcpMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4OcpMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular over-current protector."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
||
|
::= { st4OcpMonitorTable 1 }
|
||
|
|
||
|
St4OcpMonitorEntry ::= SEQUENCE {
|
||
|
st4OcpStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4OcpStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the over-current protector."
|
||
|
::= { st4OcpMonitorEntry 1 }
|
||
|
|
||
|
-- Over-Current Protector Event Configuration Table
|
||
|
|
||
|
st4OcpEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OcpEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector event configuration table."
|
||
|
::= { st4OverCurrentProtectors 4 }
|
||
|
|
||
|
st4OcpEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4OcpEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular over-current
|
||
|
protector."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
||
|
::= { st4OcpEventConfigTable 1 }
|
||
|
|
||
|
St4OcpEventConfigEntry ::= SEQUENCE {
|
||
|
st4OcpNotifications EventNotificationMethods
|
||
|
}
|
||
|
|
||
|
st4OcpNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for over-current protector
|
||
|
events."
|
||
|
::= { st4OcpEventConfigEntry 1 }
|
||
|
|
||
|
-- Branches
|
||
|
|
||
|
st4Branches OBJECT IDENTIFIER ::= { st4Objects 7 }
|
||
|
|
||
|
-- Branch Common Configuration
|
||
|
|
||
|
st4BranchCommonConfig OBJECT IDENTIFIER ::= { st4Branches 1 }
|
||
|
|
||
|
st4BranchCurrentHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current hysteresis of the branch in tenth Amps."
|
||
|
::= { st4BranchCommonConfig 1 }
|
||
|
|
||
|
-- Branch Configuration Table
|
||
|
|
||
|
st4BranchConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4BranchConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch configuration table."
|
||
|
::= { st4Branches 2 }
|
||
|
|
||
|
st4BranchConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4BranchConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular branch."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
||
|
::= { st4BranchConfigTable 1 }
|
||
|
|
||
|
St4BranchConfigEntry ::= SEQUENCE {
|
||
|
st4BranchIndex Integer32,
|
||
|
st4BranchID DisplayString,
|
||
|
st4BranchLabel DisplayString,
|
||
|
st4BranchCurrentCapacity Integer32,
|
||
|
st4BranchPhaseID DisplayString,
|
||
|
st4BranchOcpID DisplayString,
|
||
|
st4BranchOutletCount Integer32
|
||
|
}
|
||
|
|
||
|
st4BranchIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..64)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch index."
|
||
|
::= { st4BranchConfigEntry 1 }
|
||
|
|
||
|
st4BranchID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the branch. Format=AAN[N]."
|
||
|
::= { st4BranchConfigEntry 2 }
|
||
|
|
||
|
st4BranchLabel OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The system label assigned to the branch for identification."
|
||
|
::= { st4BranchConfigEntry 4 }
|
||
|
|
||
|
st4BranchCurrentCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..125)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current capacity of the branch in Amps."
|
||
|
::= { st4BranchConfigEntry 6 }
|
||
|
|
||
|
st4BranchPhaseID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the phase powering this branch.
|
||
|
Format=AAN."
|
||
|
::= { st4BranchConfigEntry 20 }
|
||
|
|
||
|
st4BranchOcpID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the over-current protector powering this
|
||
|
outlet. Format=AAN[N]."
|
||
|
::= { st4BranchConfigEntry 21 }
|
||
|
|
||
|
st4BranchOutletCount OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..128)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The number of outlets powered from the branch."
|
||
|
::= { st4BranchConfigEntry 30 }
|
||
|
|
||
|
-- Branch Monitor Table
|
||
|
|
||
|
st4BranchMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4BranchMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch monitor table."
|
||
|
::= { st4Branches 3 }
|
||
|
|
||
|
st4BranchMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4BranchMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular branch."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
||
|
::= { st4BranchMonitorTable 1 }
|
||
|
|
||
|
St4BranchMonitorEntry ::= SEQUENCE {
|
||
|
st4BranchState DeviceState,
|
||
|
st4BranchStatus DeviceStatus,
|
||
|
st4BranchCurrent Integer32,
|
||
|
st4BranchCurrentStatus DeviceStatus,
|
||
|
st4BranchCurrentUtilized Integer32
|
||
|
}
|
||
|
|
||
|
st4BranchState OBJECT-TYPE
|
||
|
SYNTAX DeviceState
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The on/off state of the branch."
|
||
|
::= { st4BranchMonitorEntry 1 }
|
||
|
|
||
|
st4BranchStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the branch."
|
||
|
::= { st4BranchMonitorEntry 2 }
|
||
|
|
||
|
st4BranchCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..12500)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured current on the branch in hundredth Amps."
|
||
|
::= { st4BranchMonitorEntry 3 }
|
||
|
|
||
|
st4BranchCurrentStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured current on the branch."
|
||
|
::= { st4BranchMonitorEntry 4 }
|
||
|
|
||
|
st4BranchCurrentUtilized OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..1200)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of the branch current capacity used in tenth percent."
|
||
|
::= { st4BranchMonitorEntry 5 }
|
||
|
|
||
|
-- Branch Event Configuration Table
|
||
|
|
||
|
st4BranchEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4BranchEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch event configuration table."
|
||
|
::= { st4Branches 4 }
|
||
|
|
||
|
st4BranchEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4BranchEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular branch."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
||
|
::= { st4BranchEventConfigTable 1 }
|
||
|
|
||
|
St4BranchEventConfigEntry ::= SEQUENCE {
|
||
|
st4BranchNotifications EventNotificationMethods,
|
||
|
st4BranchCurrentLowAlarm Integer32,
|
||
|
st4BranchCurrentLowWarning Integer32,
|
||
|
st4BranchCurrentHighWarning Integer32,
|
||
|
st4BranchCurrentHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4BranchNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for branch events."
|
||
|
::= { st4BranchEventConfigEntry 1 }
|
||
|
|
||
|
st4BranchCurrentLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low alarm threshold of the branch in tenth Amps."
|
||
|
::= { st4BranchEventConfigEntry 2 }
|
||
|
|
||
|
st4BranchCurrentLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low warning threshold of the branch in tenth Amps."
|
||
|
::= { st4BranchEventConfigEntry 3 }
|
||
|
|
||
|
st4BranchCurrentHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high warning threshold of the branch in tenth Amps."
|
||
|
::= { st4BranchEventConfigEntry 4 }
|
||
|
|
||
|
st4BranchCurrentHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high alarm threshold of the branch in tenth Amps."
|
||
|
::= { st4BranchEventConfigEntry 5 }
|
||
|
|
||
|
-- Outlets
|
||
|
|
||
|
st4Outlets OBJECT IDENTIFIER ::= { st4Objects 8 }
|
||
|
|
||
|
-- Outlet Common Configuration
|
||
|
|
||
|
st4OutletCommonConfig OBJECT IDENTIFIER ::= { st4Outlets 1 }
|
||
|
|
||
|
st4OutletCurrentHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current hysteresis of the outlet in tenth Amps."
|
||
|
::= { st4OutletCommonConfig 1 }
|
||
|
|
||
|
st4OutletActivePowerHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power hysteresis of the outlet in Watts."
|
||
|
::= { st4OutletCommonConfig 2 }
|
||
|
|
||
|
st4OutletPowerFactorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..20)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power factor hysteresis of the outlet in hundredths."
|
||
|
::= { st4OutletCommonConfig 3 }
|
||
|
|
||
|
st4OutletSequenceInterval OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..15)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power-on sequencing interval for all outlets in seconds."
|
||
|
::= { st4OutletCommonConfig 10 }
|
||
|
|
||
|
st4OutletRebootDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32(5..600)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The reboot delay for all outlets in seconds."
|
||
|
::= { st4OutletCommonConfig 11 }
|
||
|
|
||
|
st4OutletStateChangeLogging OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(0),
|
||
|
enabled(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Enables or disables informational Outlet State Change event
|
||
|
logging."
|
||
|
::= { st4OutletCommonConfig 12 }
|
||
|
|
||
|
-- Outlet Configuration Table
|
||
|
|
||
|
st4OutletConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OutletConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet configuration table."
|
||
|
::= { st4Outlets 2 }
|
||
|
|
||
|
st4OutletConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4OutletConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular outlet."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
||
|
::= { st4OutletConfigTable 1 }
|
||
|
|
||
|
St4OutletConfigEntry ::= SEQUENCE {
|
||
|
st4OutletIndex Integer32,
|
||
|
st4OutletID DisplayString,
|
||
|
st4OutletName DisplayString,
|
||
|
st4OutletCapabilities BITS,
|
||
|
st4OutletSocketType DisplayString,
|
||
|
st4OutletCurrentCapacity Integer32,
|
||
|
st4OutletPowerCapacity Integer32,
|
||
|
st4OutletWakeupState INTEGER,
|
||
|
st4OutletPostOnDelay Integer32,
|
||
|
st4OutletPhaseID DisplayString,
|
||
|
st4OutletOcpID DisplayString,
|
||
|
st4OutletBranchID DisplayString
|
||
|
}
|
||
|
|
||
|
st4OutletIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(1..128)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet index."
|
||
|
::= { st4OutletConfigEntry 1 }
|
||
|
|
||
|
st4OutletID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..5))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the outlet. Format=AAN[N[N]]."
|
||
|
::= { st4OutletConfigEntry 2 }
|
||
|
|
||
|
st4OutletName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the outlet."
|
||
|
::= { st4OutletConfigEntry 3 }
|
||
|
|
||
|
st4OutletCapabilities OBJECT-TYPE
|
||
|
SYNTAX BITS {
|
||
|
switched(0), -- outlet supports power control
|
||
|
pops(1) -- outlet has pops
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The capabilities of the outlet."
|
||
|
::= { st4OutletConfigEntry 5 }
|
||
|
|
||
|
st4OutletSocketType OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The socket type of the outlet."
|
||
|
::= { st4OutletConfigEntry 6 }
|
||
|
|
||
|
st4OutletCurrentCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..125)
|
||
|
UNITS "Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current capacity of the outlet in Amps."
|
||
|
::= { st4OutletConfigEntry 7 }
|
||
|
|
||
|
st4OutletPowerCapacity OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The power capacity of the outlet in Volt-Amps. For DC products,
|
||
|
this is identical to power capacity in Watts."
|
||
|
::= { st4OutletConfigEntry 8 }
|
||
|
|
||
|
st4OutletWakeupState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
on(0),
|
||
|
off(1),
|
||
|
last(2)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The wakeup state of the outlet."
|
||
|
::= { st4OutletConfigEntry 20 }
|
||
|
|
||
|
st4OutletPostOnDelay OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..900)
|
||
|
UNITS "seconds"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The post-on delay of the outlet in seconds."
|
||
|
::= { st4OutletConfigEntry 21 }
|
||
|
|
||
|
st4OutletPhaseID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the phase powering this outlet.
|
||
|
Format=AAN."
|
||
|
::= { st4OutletConfigEntry 30 }
|
||
|
|
||
|
st4OutletOcpID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the over-current protector powering this
|
||
|
outlet. Format=AAN[N]."
|
||
|
::= { st4OutletConfigEntry 31 }
|
||
|
|
||
|
st4OutletBranchID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(3..4))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the branch powering this outlet.
|
||
|
Format=AAN[N]."
|
||
|
::= { st4OutletConfigEntry 32 }
|
||
|
|
||
|
-- Outlet Monitor Table
|
||
|
|
||
|
st4OutletMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OutletMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet monitor table."
|
||
|
::= { st4Outlets 3 }
|
||
|
|
||
|
st4OutletMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4OutletMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular outlet."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
||
|
::= { st4OutletMonitorTable 1 }
|
||
|
|
||
|
St4OutletMonitorEntry ::= SEQUENCE {
|
||
|
st4OutletState DeviceState,
|
||
|
st4OutletStatus DeviceStatus,
|
||
|
st4OutletCurrent Integer32,
|
||
|
st4OutletCurrentStatus DeviceStatus,
|
||
|
st4OutletCurrentUtilized Integer32,
|
||
|
st4OutletVoltage Integer32,
|
||
|
st4OutletActivePower Integer32,
|
||
|
st4OutletActivePowerStatus DeviceStatus,
|
||
|
st4OutletApparentPower Integer32,
|
||
|
st4OutletPowerFactor Integer32,
|
||
|
st4OutletPowerFactorStatus DeviceStatus,
|
||
|
st4OutletCurrentCrestFactor Integer32,
|
||
|
st4OutletReactance INTEGER,
|
||
|
st4OutletEnergy Integer32
|
||
|
}
|
||
|
|
||
|
st4OutletState OBJECT-TYPE
|
||
|
SYNTAX DeviceState
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The on/off state of the outlet."
|
||
|
::= { st4OutletMonitorEntry 1 }
|
||
|
|
||
|
st4OutletStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the outlet."
|
||
|
::= { st4OutletMonitorEntry 2 }
|
||
|
|
||
|
st4OutletCurrent OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..12500)
|
||
|
UNITS "hundredth Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured current on the outlet in hundredth Amps."
|
||
|
::= { st4OutletMonitorEntry 3 }
|
||
|
|
||
|
st4OutletCurrentStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured current on the outlet."
|
||
|
::= { st4OutletMonitorEntry 4 }
|
||
|
|
||
|
st4OutletCurrentUtilized OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..1200)
|
||
|
UNITS "tenth percent"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The amount of the outlet current capacity used in tenth percent."
|
||
|
::= { st4OutletMonitorEntry 5 }
|
||
|
|
||
|
st4OutletVoltage OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..6000)
|
||
|
UNITS "tenth Volts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured voltage of the outlet in tenth Volts."
|
||
|
::= { st4OutletMonitorEntry 6 }
|
||
|
|
||
|
st4OutletActivePower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured active power of the outlet in Watts."
|
||
|
::= { st4OutletMonitorEntry 7 }
|
||
|
|
||
|
st4OutletActivePowerStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured active power of the outlet."
|
||
|
::= { st4OutletMonitorEntry 8 }
|
||
|
|
||
|
st4OutletApparentPower OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..10000)
|
||
|
UNITS "Volt-Amps"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured apparent power of the outlet in Volt-Amps."
|
||
|
::= { st4OutletMonitorEntry 9 }
|
||
|
|
||
|
st4OutletPowerFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured power factor of the outlet in hundredths."
|
||
|
::= { st4OutletMonitorEntry 10 }
|
||
|
|
||
|
st4OutletPowerFactorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured power factor of the outlet."
|
||
|
::= { st4OutletMonitorEntry 11 }
|
||
|
|
||
|
st4OutletCurrentCrestFactor OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..250)
|
||
|
UNITS "tenths"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured crest factor of the outlet in tenths."
|
||
|
::= { st4OutletMonitorEntry 12 }
|
||
|
|
||
|
st4OutletReactance OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(0),
|
||
|
capacitive(1),
|
||
|
inductive(2),
|
||
|
resistive(3)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the measured reactance of the outlet."
|
||
|
::= { st4OutletMonitorEntry 13 }
|
||
|
|
||
|
st4OutletEnergy OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..2147483647)
|
||
|
UNITS "Watt-Hours"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The total energy consumption of the device plugged into the outlet
|
||
|
in Watt-Hours."
|
||
|
::= { st4OutletMonitorEntry 14 }
|
||
|
|
||
|
-- Outlet Event Configuration Table
|
||
|
|
||
|
st4OutletEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OutletEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet event configuration table."
|
||
|
::= { st4Outlets 4 }
|
||
|
|
||
|
st4OutletEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4OutletEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular outlet."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
||
|
::= { st4OutletEventConfigTable 1 }
|
||
|
|
||
|
St4OutletEventConfigEntry ::= SEQUENCE {
|
||
|
st4OutletNotifications EventNotificationMethods,
|
||
|
st4OutletCurrentLowAlarm Integer32,
|
||
|
st4OutletCurrentLowWarning Integer32,
|
||
|
st4OutletCurrentHighWarning Integer32,
|
||
|
st4OutletCurrentHighAlarm Integer32,
|
||
|
st4OutletActivePowerLowAlarm Integer32,
|
||
|
st4OutletActivePowerLowWarning Integer32,
|
||
|
st4OutletActivePowerHighWarning Integer32,
|
||
|
st4OutletActivePowerHighAlarm Integer32,
|
||
|
st4OutletPowerFactorLowAlarm Integer32,
|
||
|
st4OutletPowerFactorLowWarning Integer32
|
||
|
}
|
||
|
|
||
|
st4OutletNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for outlet events."
|
||
|
::= { st4OutletEventConfigEntry 1 }
|
||
|
|
||
|
st4OutletCurrentLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low alarm threshold of the outlet in tenth Amps."
|
||
|
::= { st4OutletEventConfigEntry 2 }
|
||
|
|
||
|
st4OutletCurrentLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current low warning threshold of the outlet in tenth Amps."
|
||
|
::= { st4OutletEventConfigEntry 3 }
|
||
|
|
||
|
st4OutletCurrentHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high warning threshold of the outlet in tenth Amps."
|
||
|
::= { st4OutletEventConfigEntry 4 }
|
||
|
|
||
|
st4OutletCurrentHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1250)
|
||
|
UNITS "tenth Amps"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current high alarm threshold of the outlet in tenth Amps."
|
||
|
::= { st4OutletEventConfigEntry 5 }
|
||
|
|
||
|
st4OutletActivePowerLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power low alarm threshold of the outlet in Watts."
|
||
|
::= { st4OutletEventConfigEntry 6 }
|
||
|
|
||
|
st4OutletActivePowerLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power low warning threshold of the outlet in Watts."
|
||
|
::= { st4OutletEventConfigEntry 7 }
|
||
|
|
||
|
st4OutletActivePowerHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power high warning threshold of the outlet in Watts."
|
||
|
::= { st4OutletEventConfigEntry 8 }
|
||
|
|
||
|
st4OutletActivePowerHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..10000)
|
||
|
UNITS "Watts"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The active power high alarm threshold of the outlet in Watts."
|
||
|
::= { st4OutletEventConfigEntry 9 }
|
||
|
|
||
|
st4OutletPowerFactorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low power factor alarm threshold of the outlet in hundredths."
|
||
|
::= { st4OutletEventConfigEntry 10 }
|
||
|
|
||
|
st4OutletPowerFactorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "hundredths"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low power factor warning threshold of the outlet in
|
||
|
hundredths."
|
||
|
::= { st4OutletEventConfigEntry 11 }
|
||
|
|
||
|
-- Outlet Control Table
|
||
|
|
||
|
st4OutletControlTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4OutletControlEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet control table."
|
||
|
::= { st4Outlets 5 }
|
||
|
|
||
|
st4OutletControlEntry OBJECT-TYPE
|
||
|
SYNTAX St4OutletControlEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects for control of a particular outlet."
|
||
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
||
|
::= { st4OutletControlTable 1 }
|
||
|
|
||
|
St4OutletControlEntry ::= SEQUENCE {
|
||
|
st4OutletControlState INTEGER,
|
||
|
st4OutletControlAction INTEGER
|
||
|
}
|
||
|
|
||
|
st4OutletControlState OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
notSet(0), -- outlet state is unknown
|
||
|
fixedOn(1), -- outlet is uncontrolled (assumed on)
|
||
|
idleOff(2), -- outlet has defaulted to off state
|
||
|
idleOn(3), -- outlet has defaulted to on state
|
||
|
wakeOff(4), -- outlet has been set to off by wakeup
|
||
|
wakeOn(5), -- outlet has been set to on by wakeup
|
||
|
ocpOff(6), -- outlet is off due to OCP failure
|
||
|
ocpOn(7), -- outlet had OCP power loss
|
||
|
pendOn(8), -- outlet is off, but will be turning on
|
||
|
pendOff(9), -- outlet is on, but will be turning off
|
||
|
off(10), -- outlet was turned off by user
|
||
|
on(11), -- outlet was turned on by user or reboot event
|
||
|
reboot(12), -- outlet is preparing to turn on
|
||
|
shutdown(13), -- outlet is preparing to turn off
|
||
|
lockedOff(14), -- outlet was locked off by admin
|
||
|
lockedOn(15), -- outlet was locked on by admin
|
||
|
eventOff(16), -- outlet was turned off by an event
|
||
|
eventOn(17), -- outlet was turned on by an event
|
||
|
eventReboot(18), -- outlet rebooting due to an event
|
||
|
eventShutdown(19) -- outlet shutting down due to an event
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The control state of the outlet."
|
||
|
::= { st4OutletControlEntry 1 }
|
||
|
|
||
|
st4OutletControlAction OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
none(0),
|
||
|
on(1),
|
||
|
off(2),
|
||
|
reboot(3),
|
||
|
queueOn(4),
|
||
|
queueOff(5),
|
||
|
queueReboot(6)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An action to change the control state of the outlet, or to queue
|
||
|
an action."
|
||
|
::= { st4OutletControlEntry 2 }
|
||
|
|
||
|
-- Outlet Common Control
|
||
|
|
||
|
st4OutletCommonControl OBJECT IDENTIFIER ::= { st4Outlets 6 }
|
||
|
|
||
|
st4OutletQueueControl OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
clear(0),
|
||
|
commit(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"An action to clear or commit queued outlet control actions. A
|
||
|
read of this object returns clear(0) if queue is empty, and
|
||
|
commit(1) if the queue is not empty."
|
||
|
::= { st4OutletCommonControl 1 }
|
||
|
|
||
|
-- Temperature Sensors
|
||
|
|
||
|
st4TemperatureSensors OBJECT IDENTIFIER ::= { st4Objects 9 }
|
||
|
|
||
|
-- Temperature Sensor Common Configuration
|
||
|
|
||
|
st4TempSensorCommonConfig OBJECT IDENTIFIER ::= { st4TemperatureSensors 1 }
|
||
|
|
||
|
st4TempSensorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..54)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The temperature hysteresis of the sensor in degrees, using the
|
||
|
scale selected by st4TempSensorScale."
|
||
|
::= { st4TempSensorCommonConfig 1 }
|
||
|
|
||
|
st4TempSensorScale OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
celsius(0),
|
||
|
fahrenheit(1)
|
||
|
}
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The current scale used for all temperature values."
|
||
|
::= { st4TempSensorCommonConfig 10 }
|
||
|
|
||
|
-- Temperature Sensor Configuration Table
|
||
|
|
||
|
st4TempSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4TempSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor configuration table."
|
||
|
::= { st4TemperatureSensors 2 }
|
||
|
|
||
|
st4TempSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4TempSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular temperature sensor."
|
||
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
||
|
::= { st4TempSensorConfigTable 1 }
|
||
|
|
||
|
St4TempSensorConfigEntry ::= SEQUENCE {
|
||
|
st4TempSensorIndex Integer32,
|
||
|
st4TempSensorID DisplayString,
|
||
|
st4TempSensorName DisplayString,
|
||
|
st4TempSensorValueMin Integer32,
|
||
|
st4TempSensorValueMax Integer32
|
||
|
}
|
||
|
|
||
|
st4TempSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..2)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor index."
|
||
|
::= { st4TempSensorConfigEntry 1 }
|
||
|
|
||
|
st4TempSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the temperature sensor. Format=AN."
|
||
|
::= { st4TempSensorConfigEntry 2 }
|
||
|
|
||
|
st4TempSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the temperature sensor."
|
||
|
::= { st4TempSensorConfigEntry 3 }
|
||
|
|
||
|
st4TempSensorValueMin OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The minimum temperature limit of the sensor in degrees, using the
|
||
|
scale selected by st4TempSensorScale."
|
||
|
::= { st4TempSensorConfigEntry 4 }
|
||
|
|
||
|
st4TempSensorValueMax OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The maximum temperature limit of the sensor in degrees, using the
|
||
|
scale selected by st4TempSensorScale."
|
||
|
::= { st4TempSensorConfigEntry 5 }
|
||
|
|
||
|
-- Temperature Sensor Monitor Table
|
||
|
|
||
|
st4TempSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4TempSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor monitor table."
|
||
|
::= { st4TemperatureSensors 3 }
|
||
|
|
||
|
st4TempSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4TempSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular temperature sensor."
|
||
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
||
|
::= { st4TempSensorMonitorTable 1 }
|
||
|
|
||
|
St4TempSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4TempSensorValue Integer32,
|
||
|
st4TempSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4TempSensorValue OBJECT-TYPE
|
||
|
SYNTAX Integer32(-410..2540)
|
||
|
UNITS "tenth degrees"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured temperature on the sensor in tenth degrees using the
|
||
|
scale selected by st4TempSensorScale. -410 means the temperature
|
||
|
reading is invalid."
|
||
|
::= { st4TempSensorMonitorEntry 1 }
|
||
|
|
||
|
st4TempSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the temperature sensor."
|
||
|
::= { st4TempSensorMonitorEntry 2 }
|
||
|
|
||
|
-- Temperature Sensor Event Configuration Table
|
||
|
|
||
|
st4TempSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4TempSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor event configuration table."
|
||
|
::= { st4TemperatureSensors 4 }
|
||
|
|
||
|
st4TempSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4TempSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular temperature sensor."
|
||
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
||
|
::= { st4TempSensorEventConfigTable 1 }
|
||
|
|
||
|
St4TempSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4TempSensorNotifications EventNotificationMethods,
|
||
|
st4TempSensorLowAlarm Integer32,
|
||
|
st4TempSensorLowWarning Integer32,
|
||
|
st4TempSensorHighWarning Integer32,
|
||
|
st4TempSensorHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4TempSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for temperature sensor events."
|
||
|
::= { st4TempSensorEventConfigEntry 1 }
|
||
|
|
||
|
st4TempSensorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low alarm threshold of the temperature sensor in degrees."
|
||
|
::= { st4TempSensorEventConfigEntry 2 }
|
||
|
|
||
|
st4TempSensorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low warning threshold of the temperature sensor in degrees."
|
||
|
::= { st4TempSensorEventConfigEntry 3 }
|
||
|
|
||
|
st4TempSensorHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high warning threshold of the temperature sensor in degrees."
|
||
|
::= { st4TempSensorEventConfigEntry 4 }
|
||
|
|
||
|
st4TempSensorHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(-40..253)
|
||
|
UNITS "degrees"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high alarm threshold of the temperature sensor in degrees."
|
||
|
::= { st4TempSensorEventConfigEntry 5 }
|
||
|
|
||
|
-- Humidity Sensors
|
||
|
|
||
|
st4HumiditySensors OBJECT IDENTIFIER ::= { st4Objects 10 }
|
||
|
|
||
|
-- Humidity Sensor Common Configuration
|
||
|
|
||
|
st4HumidSensorCommonConfig OBJECT IDENTIFIER ::= { st4HumiditySensors 1 }
|
||
|
|
||
|
st4HumidSensorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..20)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The humidity hysteresis of the sensor in percent relative
|
||
|
humidity."
|
||
|
::= { st4HumidSensorCommonConfig 1 }
|
||
|
|
||
|
-- Humidity Sensor Configuration Table
|
||
|
|
||
|
st4HumidSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4HumidSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor configuration table."
|
||
|
::= { st4HumiditySensors 2 }
|
||
|
|
||
|
st4HumidSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4HumidSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular humidity sensor."
|
||
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
||
|
::= { st4HumidSensorConfigTable 1 }
|
||
|
|
||
|
St4HumidSensorConfigEntry ::= SEQUENCE {
|
||
|
st4HumidSensorIndex Integer32,
|
||
|
st4HumidSensorID DisplayString,
|
||
|
st4HumidSensorName DisplayString
|
||
|
}
|
||
|
|
||
|
st4HumidSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..2)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor index."
|
||
|
::= { st4HumidSensorConfigEntry 1 }
|
||
|
|
||
|
st4HumidSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the humidity sensor. Format=AN."
|
||
|
::= { st4HumidSensorConfigEntry 2 }
|
||
|
|
||
|
st4HumidSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the humidity sensor."
|
||
|
::= { st4HumidSensorConfigEntry 3 }
|
||
|
|
||
|
-- Humidity Sensor Monitor Table
|
||
|
|
||
|
st4HumidSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4HumidSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor monitor table."
|
||
|
::= { st4HumiditySensors 3 }
|
||
|
|
||
|
st4HumidSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4HumidSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular humidity sensor."
|
||
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
||
|
::= { st4HumidSensorMonitorTable 1 }
|
||
|
|
||
|
St4HumidSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4HumidSensorValue Integer32,
|
||
|
st4HumidSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4HumidSensorValue OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured humidity on the sensor in percentage relative
|
||
|
humidity."
|
||
|
::= { st4HumidSensorMonitorEntry 1 }
|
||
|
|
||
|
st4HumidSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the humidity sensor."
|
||
|
::= { st4HumidSensorMonitorEntry 2 }
|
||
|
|
||
|
-- Humidity Sensor Event Configuration Table
|
||
|
|
||
|
st4HumidSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4HumidSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor event configuration table."
|
||
|
::= { st4HumiditySensors 4 }
|
||
|
|
||
|
st4HumidSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4HumidSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular humidity sensor."
|
||
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
||
|
::= { st4HumidSensorEventConfigTable 1 }
|
||
|
|
||
|
St4HumidSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4HumidSensorNotifications EventNotificationMethods,
|
||
|
st4HumidSensorLowAlarm Integer32,
|
||
|
st4HumidSensorLowWarning Integer32,
|
||
|
st4HumidSensorHighWarning Integer32,
|
||
|
st4HumidSensorHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4HumidSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for humidity sensor events."
|
||
|
::= { st4HumidSensorEventConfigEntry 1 }
|
||
|
|
||
|
st4HumidSensorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low alarm threshold of the humidity sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { st4HumidSensorEventConfigEntry 2 }
|
||
|
|
||
|
st4HumidSensorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low warning threshold of the humidity sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { st4HumidSensorEventConfigEntry 3 }
|
||
|
|
||
|
st4HumidSensorHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high warning threshold of the humidity sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { st4HumidSensorEventConfigEntry 4 }
|
||
|
|
||
|
st4HumidSensorHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..100)
|
||
|
UNITS "percentage relative humidity"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high alarm threshold of the humidity sensor in percentage
|
||
|
relative humidity."
|
||
|
::= { st4HumidSensorEventConfigEntry 5 }
|
||
|
|
||
|
-- Water Sensors
|
||
|
|
||
|
st4WaterSensors OBJECT IDENTIFIER ::= { st4Objects 11 }
|
||
|
|
||
|
-- Water Sensor Common Configuration
|
||
|
|
||
|
st4WaterSensorCommonConfig OBJECT IDENTIFIER ::= { st4WaterSensors 1 }
|
||
|
|
||
|
-- Water Sensor Configuration Table
|
||
|
|
||
|
st4WaterSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4WaterSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor configuration table."
|
||
|
::= { st4WaterSensors 2 }
|
||
|
|
||
|
st4WaterSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4WaterSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular water sensor."
|
||
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
||
|
::= { st4WaterSensorConfigTable 1 }
|
||
|
|
||
|
St4WaterSensorConfigEntry ::= SEQUENCE {
|
||
|
st4WaterSensorIndex Integer32,
|
||
|
st4WaterSensorID DisplayString,
|
||
|
st4WaterSensorName DisplayString
|
||
|
}
|
||
|
|
||
|
st4WaterSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor index."
|
||
|
::= { st4WaterSensorConfigEntry 1 }
|
||
|
|
||
|
st4WaterSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the water sensor. Format=AN."
|
||
|
::= { st4WaterSensorConfigEntry 2 }
|
||
|
|
||
|
st4WaterSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the water sensor."
|
||
|
::= { st4WaterSensorConfigEntry 3 }
|
||
|
|
||
|
-- Water Sensor Monitor Table
|
||
|
|
||
|
st4WaterSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4WaterSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor monitor table."
|
||
|
::= { st4WaterSensors 3 }
|
||
|
|
||
|
st4WaterSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4WaterSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular water sensor."
|
||
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
||
|
::= { st4WaterSensorMonitorTable 1 }
|
||
|
|
||
|
St4WaterSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4WaterSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4WaterSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the water sensor."
|
||
|
::= { st4WaterSensorMonitorEntry 1 }
|
||
|
|
||
|
-- Water Sensor Event Configuration Table
|
||
|
|
||
|
st4WaterSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4WaterSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor event configuration table."
|
||
|
::= { st4WaterSensors 4 }
|
||
|
|
||
|
st4WaterSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4WaterSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular water sensor."
|
||
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
||
|
::= { st4WaterSensorEventConfigTable 1 }
|
||
|
|
||
|
St4WaterSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4WaterSensorNotifications EventNotificationMethods
|
||
|
}
|
||
|
|
||
|
st4WaterSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for water sensor events."
|
||
|
::= { st4WaterSensorEventConfigEntry 1 }
|
||
|
|
||
|
-- Contact Closures Sensors
|
||
|
|
||
|
st4ContactClosureSensors OBJECT IDENTIFIER ::= { st4Objects 12 }
|
||
|
|
||
|
-- Contact Closure Sensor Common Configuration
|
||
|
|
||
|
st4CcSensorCommonConfig OBJECT IDENTIFIER ::= { st4ContactClosureSensors 1 }
|
||
|
|
||
|
-- Contact Closure Sensor Configuration Table
|
||
|
|
||
|
st4CcSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4CcSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor configuration table."
|
||
|
::= { st4ContactClosureSensors 2 }
|
||
|
|
||
|
st4CcSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4CcSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular contact closure sensor."
|
||
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
||
|
::= { st4CcSensorConfigTable 1 }
|
||
|
|
||
|
St4CcSensorConfigEntry ::= SEQUENCE {
|
||
|
st4CcSensorIndex Integer32,
|
||
|
st4CcSensorID DisplayString,
|
||
|
st4CcSensorName DisplayString
|
||
|
}
|
||
|
|
||
|
st4CcSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor index."
|
||
|
::= { st4CcSensorConfigEntry 1 }
|
||
|
|
||
|
st4CcSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the contact closure sensor. Format=AN."
|
||
|
::= { st4CcSensorConfigEntry 2 }
|
||
|
|
||
|
st4CcSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the contact closure sensor."
|
||
|
::= { st4CcSensorConfigEntry 3 }
|
||
|
|
||
|
-- Contact Closure Sensor Monitor Table
|
||
|
|
||
|
st4CcSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4CcSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor monitor table."
|
||
|
::= { st4ContactClosureSensors 3 }
|
||
|
|
||
|
st4CcSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4CcSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular contact closure sensor."
|
||
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
||
|
::= { st4CcSensorMonitorTable 1 }
|
||
|
|
||
|
St4CcSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4CcSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4CcSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the contact closure."
|
||
|
::= { st4CcSensorMonitorEntry 1 }
|
||
|
|
||
|
-- Contact Closure Sensor Event Configuration Table
|
||
|
|
||
|
st4CcSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4CcSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor event configuration table."
|
||
|
::= { st4ContactClosureSensors 4 }
|
||
|
|
||
|
st4CcSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4CcSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular contact closure
|
||
|
sensor."
|
||
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
||
|
::= { st4CcSensorEventConfigTable 1 }
|
||
|
|
||
|
St4CcSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4CcSensorNotifications EventNotificationMethods
|
||
|
}
|
||
|
|
||
|
st4CcSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for contact closure sensor
|
||
|
events."
|
||
|
::= { st4CcSensorEventConfigEntry 1 }
|
||
|
|
||
|
-- Analog-to-Digital Converter Sensors
|
||
|
|
||
|
st4AnalogToDigitalConvSensors OBJECT IDENTIFIER ::= { st4Objects 13 }
|
||
|
|
||
|
-- Analog-to-Digital Converter Sensor Common Configuration
|
||
|
|
||
|
st4AdcSensorCommonConfig OBJECT IDENTIFIER ::= { st4AnalogToDigitalConvSensors 1 }
|
||
|
|
||
|
st4AdcSensorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..20)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit count hysteresis of the analog-to-digital converter
|
||
|
sensor."
|
||
|
::= { st4AdcSensorCommonConfig 1 }
|
||
|
|
||
|
-- Analog-to-Digital Converter Sensor Configuration Table
|
||
|
|
||
|
st4AdcSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4AdcSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor configuration table."
|
||
|
::= { st4AnalogToDigitalConvSensors 2 }
|
||
|
|
||
|
st4AdcSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4AdcSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular analog-to-digital
|
||
|
converter sensor."
|
||
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
||
|
::= { st4AdcSensorConfigTable 1 }
|
||
|
|
||
|
St4AdcSensorConfigEntry ::= SEQUENCE {
|
||
|
st4AdcSensorIndex Integer32,
|
||
|
st4AdcSensorID DisplayString,
|
||
|
st4AdcSensorName DisplayString
|
||
|
}
|
||
|
|
||
|
st4AdcSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor index."
|
||
|
::= { st4AdcSensorConfigEntry 1 }
|
||
|
|
||
|
st4AdcSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the analog-to-digital converter sensor.
|
||
|
Format=AN."
|
||
|
::= { st4AdcSensorConfigEntry 2 }
|
||
|
|
||
|
st4AdcSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorConfigEntry 3 }
|
||
|
|
||
|
-- Analog-to-Digital Converter Sensor Monitor Table
|
||
|
|
||
|
st4AdcSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4AdcSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor monitor table."
|
||
|
::= { st4AnalogToDigitalConvSensors 3 }
|
||
|
|
||
|
st4AdcSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4AdcSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular analog-to-digital converter
|
||
|
sensor."
|
||
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
||
|
::= { st4AdcSensorMonitorTable 1 }
|
||
|
|
||
|
St4AdcSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4AdcSensorValue Integer32,
|
||
|
st4AdcSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4AdcSensorValue OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..255)
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit value from the analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorMonitorEntry 1 }
|
||
|
|
||
|
st4AdcSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorMonitorEntry 2 }
|
||
|
|
||
|
-- Analog-to-Digital Converter Sensor Event Configuration Table
|
||
|
|
||
|
st4AdcSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4AdcSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor event configuration table."
|
||
|
::= { st4AnalogToDigitalConvSensors 4 }
|
||
|
|
||
|
st4AdcSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4AdcSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular
|
||
|
analog-to-digital converter sensor."
|
||
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
||
|
::= { st4AdcSensorEventConfigTable 1 }
|
||
|
|
||
|
St4AdcSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4AdcSensorNotifications EventNotificationMethods,
|
||
|
st4AdcSensorLowAlarm Integer32,
|
||
|
st4AdcSensorLowWarning Integer32,
|
||
|
st4AdcSensorHighWarning Integer32,
|
||
|
st4AdcSensorHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4AdcSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for analog-to-digital converter
|
||
|
sensor events."
|
||
|
::= { st4AdcSensorEventConfigEntry 1 }
|
||
|
|
||
|
st4AdcSensorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit value for the low alarm threshold of the
|
||
|
analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorEventConfigEntry 2 }
|
||
|
|
||
|
st4AdcSensorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit value for the low warning threshold of the
|
||
|
analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorEventConfigEntry 3 }
|
||
|
|
||
|
st4AdcSensorHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit value for the high warning threshold of the
|
||
|
analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorEventConfigEntry 4 }
|
||
|
|
||
|
st4AdcSensorHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..255)
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The 8-bit value for the high alarm threshold of the
|
||
|
analog-to-digital converter sensor."
|
||
|
::= { st4AdcSensorEventConfigEntry 5 }
|
||
|
|
||
|
-- Fan Sensors
|
||
|
|
||
|
st4FanSensors OBJECT IDENTIFIER ::= { st4Objects 14 }
|
||
|
|
||
|
-- Fan Sensor Common Configuration
|
||
|
|
||
|
st4FanSensorCommonConfig OBJECT IDENTIFIER ::= { st4FanSensors 1 }
|
||
|
|
||
|
st4FanSensorHysteresis OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..1200)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The fan speed hysteresis of the sensor in rotations per minute."
|
||
|
::= { st4FanSensorCommonConfig 1 }
|
||
|
|
||
|
-- Fan Sensor Configuration Table
|
||
|
|
||
|
st4FanSensorConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4FanSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor configuration table."
|
||
|
::= { st4FanSensors 2 }
|
||
|
|
||
|
st4FanSensorConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4FanSensorConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Configuration objects for a particular fan sensor."
|
||
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
||
|
::= { st4FanSensorConfigTable 1 }
|
||
|
|
||
|
St4FanSensorConfigEntry ::= SEQUENCE {
|
||
|
st4FanSensorIndex Integer32,
|
||
|
st4FanSensorID DisplayString,
|
||
|
st4FanSensorName DisplayString
|
||
|
}
|
||
|
|
||
|
st4FanSensorIndex OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..4)
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor index."
|
||
|
::= { st4FanSensorConfigEntry 1 }
|
||
|
|
||
|
st4FanSensorID OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(2))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The internal ID of the fan sensor. Format=AN."
|
||
|
::= { st4FanSensorConfigEntry 2 }
|
||
|
|
||
|
st4FanSensorName OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..32))
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The name of the fan sensor."
|
||
|
::= { st4FanSensorConfigEntry 3 }
|
||
|
|
||
|
-- Fan Sensor Monitor Table
|
||
|
|
||
|
st4FanSensorMonitorTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4FanSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor monitor table."
|
||
|
::= { st4FanSensors 3 }
|
||
|
|
||
|
st4FanSensorMonitorEntry OBJECT-TYPE
|
||
|
SYNTAX St4FanSensorMonitorEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Objects to monitor for a particular fan sensor."
|
||
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
||
|
::= { st4FanSensorMonitorTable 1 }
|
||
|
|
||
|
St4FanSensorMonitorEntry ::= SEQUENCE {
|
||
|
st4FanSensorValue Integer32,
|
||
|
st4FanSensorStatus DeviceStatus
|
||
|
}
|
||
|
|
||
|
st4FanSensorValue OBJECT-TYPE
|
||
|
SYNTAX Integer32(-1..15300)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The measured fan speed of the sensor in rotations per minute."
|
||
|
::= { st4FanSensorMonitorEntry 1 }
|
||
|
|
||
|
st4FanSensorStatus OBJECT-TYPE
|
||
|
SYNTAX DeviceStatus
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The status of the fan sensor."
|
||
|
::= { st4FanSensorMonitorEntry 2 }
|
||
|
|
||
|
-- Fan Sensor Event Configuration Table
|
||
|
|
||
|
st4FanSensorEventConfigTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF St4FanSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor event configuration table."
|
||
|
::= { st4FanSensors 4 }
|
||
|
|
||
|
st4FanSensorEventConfigEntry OBJECT-TYPE
|
||
|
SYNTAX St4FanSensorEventConfigEntry
|
||
|
MAX-ACCESS not-accessible
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event configuration objects for a particular fan sensor."
|
||
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
||
|
::= { st4FanSensorEventConfigTable 1 }
|
||
|
|
||
|
St4FanSensorEventConfigEntry ::= SEQUENCE {
|
||
|
st4FanSensorNotifications EventNotificationMethods,
|
||
|
st4FanSensorLowAlarm Integer32,
|
||
|
st4FanSensorLowWarning Integer32,
|
||
|
st4FanSensorHighWarning Integer32,
|
||
|
st4FanSensorHighAlarm Integer32
|
||
|
}
|
||
|
|
||
|
st4FanSensorNotifications OBJECT-TYPE
|
||
|
SYNTAX EventNotificationMethods
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The notification methods enabled for fan sensor events."
|
||
|
::= { st4FanSensorEventConfigEntry 1 }
|
||
|
|
||
|
st4FanSensorLowAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..15300)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low alarm threshold of the fan sensor in rotations per
|
||
|
minute."
|
||
|
::= { st4FanSensorEventConfigEntry 2 }
|
||
|
|
||
|
st4FanSensorLowWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..15300)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The low warning threshold of the fan sensor in rotations per
|
||
|
minute."
|
||
|
::= { st4FanSensorEventConfigEntry 3 }
|
||
|
|
||
|
st4FanSensorHighWarning OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..15300)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high warning threshold of the fan sensor in rotations per
|
||
|
minute."
|
||
|
::= { st4FanSensorEventConfigEntry 4 }
|
||
|
|
||
|
st4FanSensorHighAlarm OBJECT-TYPE
|
||
|
SYNTAX Integer32(0..15300)
|
||
|
UNITS "rotations per minute"
|
||
|
MAX-ACCESS read-write
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The high alarm threshold of the fan sensor in rotations per
|
||
|
minute."
|
||
|
::= { st4FanSensorEventConfigEntry 5 }
|
||
|
|
||
|
-- Event Information
|
||
|
|
||
|
st4EventInformation OBJECT IDENTIFIER ::= { st4Objects 99 }
|
||
|
|
||
|
st4EventStatusText OBJECT-TYPE
|
||
|
SYNTAX DisplayString(SIZE(0..20))
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The text representation of the enumerated integer value of
|
||
|
the most-relevant status or state object included in a trap.
|
||
|
The value of this object is set only when sent with a trap.
|
||
|
A read of this object will return a NULL string."
|
||
|
::= { st4EventInformation 1 }
|
||
|
|
||
|
st4EventStatusCondition OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
nonError(0),
|
||
|
error(1)
|
||
|
}
|
||
|
MAX-ACCESS read-only
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The condition of the enumerated integer value of the status
|
||
|
object included in a trap. The value of this object is set
|
||
|
only when sent with a trap. A read of this object will
|
||
|
return zero."
|
||
|
::= { st4EventInformation 2 }
|
||
|
|
||
|
-- Notification Definitions
|
||
|
|
||
|
st4Notifications OBJECT IDENTIFIER ::= { sentry4 100 }
|
||
|
|
||
|
-- Events
|
||
|
|
||
|
st4Events OBJECT IDENTIFIER ::= { st4Notifications 0 }
|
||
|
-- The 0 is for V1 compatibility
|
||
|
|
||
|
st4UnitStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4UnitID,
|
||
|
st4UnitName,
|
||
|
st4UnitStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit status event."
|
||
|
--#TYPE "Sentry: Unit Status Event."
|
||
|
--#SUMMARY "Status of Unit '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 1 }
|
||
|
|
||
|
st4InputCordStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordState,
|
||
|
st4InputCordStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord status event."
|
||
|
--#TYPE "Sentry: Input Cord Status Event."
|
||
|
--#SUMMARY "Status of Input Cord '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 2 }
|
||
|
|
||
|
st4InputCordActivePowerEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordActivePower,
|
||
|
st4InputCordActivePowerStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord active power event."
|
||
|
--#TYPE "Sentry: Input Cord Active Power Event."
|
||
|
--#SUMMARY "Active Power Status of Input Cord '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 3 }
|
||
|
|
||
|
st4InputCordApparentPowerEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordApparentPower,
|
||
|
st4InputCordApparentPowerStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord apparent power event."
|
||
|
--#TYPE "Sentry: Input Cord Apparent Power Event."
|
||
|
--#SUMMARY "Apparent Power Status of Input Cord '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 4 }
|
||
|
|
||
|
st4InputCordPowerFactorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordPowerFactor,
|
||
|
st4InputCordPowerFactorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord power factor event."
|
||
|
--#TYPE "Sentry: Input Cord Power Factor Event."
|
||
|
--#SUMMARY "Power Factor Status of Input Cord '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 5 }
|
||
|
|
||
|
st4InputCordOutOfBalanceEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordOutOfBalance,
|
||
|
st4InputCordOutOfBalanceStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord out-of-balance event."
|
||
|
--#TYPE "Sentry: Input Cord Out-of-Balance Event."
|
||
|
--#SUMMARY "Out-of-Balance Status of Input Cord '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 6 }
|
||
|
|
||
|
st4LineStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4LineID,
|
||
|
st4LineLabel,
|
||
|
st4LineState,
|
||
|
st4LineStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line status event."
|
||
|
--#TYPE "Sentry: Line Status Event."
|
||
|
--#SUMMARY "Status of Line '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 7 }
|
||
|
|
||
|
st4LineCurrentEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4LineID,
|
||
|
st4LineLabel,
|
||
|
st4LineCurrent,
|
||
|
st4LineCurrentStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line current event."
|
||
|
--#TYPE "Sentry: Line Current Event."
|
||
|
--#SUMMARY "Current Status of Line '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 8 }
|
||
|
|
||
|
st4PhaseStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4PhaseID,
|
||
|
st4PhaseLabel,
|
||
|
st4PhaseState,
|
||
|
st4PhaseStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase status event."
|
||
|
--#TYPE "Sentry: Phase Status Event."
|
||
|
--#SUMMARY "Status of Phase '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 9 }
|
||
|
|
||
|
st4PhaseVoltageEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4PhaseID,
|
||
|
st4PhaseLabel,
|
||
|
st4PhaseVoltage,
|
||
|
st4PhaseVoltageStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase voltage event."
|
||
|
--#TYPE "Sentry: Phase Voltage Event."
|
||
|
--#SUMMARY "Voltage Status of Phase '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 10 }
|
||
|
|
||
|
st4PhasePowerFactorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4PhaseID,
|
||
|
st4PhaseLabel,
|
||
|
st4PhasePowerFactor,
|
||
|
st4PhasePowerFactorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase voltage event."
|
||
|
--#TYPE "Sentry: Phase Power Factor Event."
|
||
|
--#SUMMARY "Power Factor Status of Phase '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 11 }
|
||
|
|
||
|
st4OcpStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OcpID,
|
||
|
st4OcpLabel,
|
||
|
st4OcpStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector status event."
|
||
|
--#TYPE "Sentry: Over-current Protector Status Event."
|
||
|
--#SUMMARY "Status of Over-current Protector '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 12 }
|
||
|
|
||
|
st4BranchStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4BranchID,
|
||
|
st4BranchLabel,
|
||
|
st4BranchState,
|
||
|
st4BranchStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch status event."
|
||
|
--#TYPE "Sentry: Branch Status Event."
|
||
|
--#SUMMARY "Status of Branch '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 13 }
|
||
|
|
||
|
st4BranchCurrentEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4BranchID,
|
||
|
st4BranchLabel,
|
||
|
st4BranchCurrent,
|
||
|
st4BranchCurrentStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch current event."
|
||
|
--#TYPE "Sentry: Branch Current Event."
|
||
|
--#SUMMARY "Current Status of Branch '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 14 }
|
||
|
|
||
|
st4OutletStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletState,
|
||
|
st4OutletStatus,
|
||
|
st4OutletControlState,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet status event."
|
||
|
--#TYPE "Sentry: Outlet Status Event."
|
||
|
--#SUMMARY "Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 6 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 15 }
|
||
|
|
||
|
st4OutletStateChangeEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletState,
|
||
|
st4OutletStatus,
|
||
|
st4OutletControlState,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet state change event."
|
||
|
--#TYPE "Sentry: Outlet State Change Event."
|
||
|
--#SUMMARY "Outlet '%s' (%s) state has changed to '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 6 }
|
||
|
--#SEVERITY INFORMATIONAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Information Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 16 }
|
||
|
|
||
|
st4OutletCurrentEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletCurrent,
|
||
|
st4OutletCurrentStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet current event."
|
||
|
--#TYPE "Sentry: Outlet Current Event."
|
||
|
--#SUMMARY "Current Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 17 }
|
||
|
|
||
|
st4OutletActivePowerEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletActivePower,
|
||
|
st4OutletActivePowerStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet active power event."
|
||
|
--#TYPE "Sentry: Outlet Active Power Event."
|
||
|
--#SUMMARY "Active Power Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 18 }
|
||
|
|
||
|
st4OutletPowerFactorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletPowerFactor,
|
||
|
st4OutletPowerFactorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet power factor event."
|
||
|
--#TYPE "Sentry: Outlet Power Factor Event."
|
||
|
--#SUMMARY "Power Factor Status of Outlet '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 19 }
|
||
|
|
||
|
st4TempSensorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4TempSensorID,
|
||
|
st4TempSensorName,
|
||
|
st4TempSensorValue,
|
||
|
st4TempSensorStatus,
|
||
|
st4TempSensorScale,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor event."
|
||
|
--#TYPE "Sentry: Temperature Sensor Event."
|
||
|
--#SUMMARY "Status of Temperature Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 6 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 20 }
|
||
|
|
||
|
st4HumidSensorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4HumidSensorID,
|
||
|
st4HumidSensorName,
|
||
|
st4HumidSensorValue,
|
||
|
st4HumidSensorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor event."
|
||
|
--#TYPE "Sentry: Humidity Sensor Event."
|
||
|
--#SUMMARY "Status of Humidity Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 21 }
|
||
|
|
||
|
st4WaterSensorStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4WaterSensorID,
|
||
|
st4WaterSensorName,
|
||
|
st4WaterSensorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor status event."
|
||
|
--#TYPE "Sentry: Water Sensor Status Event."
|
||
|
--#SUMMARY "Status of Water Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 22 }
|
||
|
|
||
|
st4CcSensorStatusEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4CcSensorID,
|
||
|
st4CcSensorName,
|
||
|
st4CcSensorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor status event."
|
||
|
--#TYPE "Sentry: Contact Closure Sensor Status Event."
|
||
|
--#SUMMARY "Status of Contact Closure Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 23 }
|
||
|
|
||
|
st4AdcSensorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4AdcSensorID,
|
||
|
st4AdcSensorName,
|
||
|
st4AdcSensorValue,
|
||
|
st4AdcSensorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor event."
|
||
|
--#TYPE "Sentry: Analog-to-Digital Converter Sensor Event."
|
||
|
--#SUMMARY "Status of Analog-to-Digital Converter Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 5 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 24 }
|
||
|
|
||
|
st4FanSensorEvent NOTIFICATION-TYPE
|
||
|
OBJECTS {
|
||
|
st4SystemLocation,
|
||
|
st4FanSensorID,
|
||
|
st4FanSensorName,
|
||
|
st4FanSensorValue,
|
||
|
st4FanSensorStatus,
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor event."
|
||
|
--#TYPE "Sentry: Fan Sensor Event."
|
||
|
--#SUMMARY "Status of Fan Sensor '%s' (%s) is '%s'."
|
||
|
--#ARGUMENTS { 2, 1, 4 }
|
||
|
--#SEVERITY CRITICAL
|
||
|
--#GENERIC 6
|
||
|
--#CATEGORY "Error Events"
|
||
|
--#SOURCE_ID "A"
|
||
|
--#TIMEINDEX 255
|
||
|
--#HELP ""
|
||
|
--#HELPTAG 0
|
||
|
--#STATE UNKNOWN
|
||
|
::= { st4Events 25 }
|
||
|
|
||
|
-- Conformance Definitions
|
||
|
|
||
|
st4Conformance OBJECT IDENTIFIER ::= { sentry4 200 }
|
||
|
|
||
|
-- Object/Notification Groups
|
||
|
|
||
|
st4Groups OBJECT IDENTIFIER ::= { st4Conformance 1 }
|
||
|
|
||
|
st4SystemObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4SystemProductName,
|
||
|
st4SystemLocation,
|
||
|
st4SystemFirmwareVersion,
|
||
|
st4SystemFirmwareBuildInfo,
|
||
|
st4SystemNICSerialNumber,
|
||
|
st4SystemNICHardwareInfo,
|
||
|
st4SystemProductSeries,
|
||
|
st4SystemFeatures,
|
||
|
st4SystemFeatureKey,
|
||
|
st4SystemConfigModifiedCount,
|
||
|
st4SystemUnitCount
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"System objects group."
|
||
|
::= { st4Groups 1 }
|
||
|
|
||
|
st4UnitObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4UnitID,
|
||
|
st4UnitName,
|
||
|
st4UnitProductSN,
|
||
|
st4UnitModel,
|
||
|
st4UnitAssetTag,
|
||
|
st4UnitType,
|
||
|
st4UnitCapabilities,
|
||
|
st4UnitProductMfrDate,
|
||
|
st4UnitDisplayOrientation,
|
||
|
st4UnitOutletSequenceOrder,
|
||
|
st4UnitOutletDisplayOrder,
|
||
|
st4UnitInputCordCount,
|
||
|
st4UnitTempSensorCount,
|
||
|
st4UnitHumidSensorCount,
|
||
|
st4UnitWaterSensorCount,
|
||
|
st4UnitCcSensorCount,
|
||
|
st4UnitAdcSensorCount,
|
||
|
st4UnitFanSensorCount,
|
||
|
st4UnitStatus,
|
||
|
st4UnitNotifications
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Unit objects group."
|
||
|
::= { st4Groups 2 }
|
||
|
|
||
|
st4InputCordObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4InputCordActivePowerHysteresis,
|
||
|
st4InputCordApparentPowerHysteresis,
|
||
|
st4InputCordPowerFactorHysteresis,
|
||
|
st4InputCordOutOfBalanceHysteresis,
|
||
|
st4InputCordID,
|
||
|
st4InputCordName,
|
||
|
st4InputCordInletType,
|
||
|
st4InputCordNominalVoltage,
|
||
|
st4InputCordNominalVoltageMin,
|
||
|
st4InputCordNominalVoltageMax,
|
||
|
st4InputCordCurrentCapacity,
|
||
|
st4InputCordCurrentCapacityMax,
|
||
|
st4InputCordPowerCapacity,
|
||
|
st4InputCordNominalPowerFactor,
|
||
|
st4InputCordLineCount,
|
||
|
st4InputCordPhaseCount,
|
||
|
st4InputCordOcpCount,
|
||
|
st4InputCordBranchCount,
|
||
|
st4InputCordOutletCount,
|
||
|
st4InputCordState,
|
||
|
st4InputCordStatus,
|
||
|
st4InputCordActivePower,
|
||
|
st4InputCordActivePowerStatus,
|
||
|
st4InputCordApparentPower,
|
||
|
st4InputCordApparentPowerStatus,
|
||
|
st4InputCordPowerUtilized,
|
||
|
st4InputCordPowerFactor,
|
||
|
st4InputCordPowerFactorStatus,
|
||
|
st4InputCordEnergy,
|
||
|
st4InputCordFrequency,
|
||
|
st4InputCordOutOfBalance,
|
||
|
st4InputCordOutOfBalanceStatus,
|
||
|
st4InputCordNotifications,
|
||
|
st4InputCordActivePowerLowAlarm,
|
||
|
st4InputCordActivePowerLowWarning,
|
||
|
st4InputCordActivePowerHighWarning,
|
||
|
st4InputCordActivePowerHighAlarm,
|
||
|
st4InputCordApparentPowerLowAlarm,
|
||
|
st4InputCordApparentPowerLowWarning,
|
||
|
st4InputCordApparentPowerHighWarning,
|
||
|
st4InputCordApparentPowerHighAlarm,
|
||
|
st4InputCordPowerFactorLowAlarm,
|
||
|
st4InputCordPowerFactorLowWarning,
|
||
|
st4InputCordOutOfBalanceHighWarning,
|
||
|
st4InputCordOutOfBalanceHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Input cord objects group."
|
||
|
::= { st4Groups 3 }
|
||
|
|
||
|
st4LineObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4LineCurrentHysteresis,
|
||
|
st4LineID,
|
||
|
st4LineLabel,
|
||
|
st4LineCurrentCapacity,
|
||
|
st4LineState,
|
||
|
st4LineStatus,
|
||
|
st4LineCurrent,
|
||
|
st4LineCurrentStatus,
|
||
|
st4LineCurrentUtilized,
|
||
|
st4LineNotifications,
|
||
|
st4LineCurrentLowAlarm,
|
||
|
st4LineCurrentLowWarning,
|
||
|
st4LineCurrentHighWarning,
|
||
|
st4LineCurrentHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Line objects group."
|
||
|
::= { st4Groups 4 }
|
||
|
|
||
|
st4PhaseObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4PhaseVoltageHysteresis,
|
||
|
st4PhasePowerFactorHysteresis,
|
||
|
st4PhaseID,
|
||
|
st4PhaseLabel,
|
||
|
st4PhaseNominalVoltage,
|
||
|
st4PhaseBranchCount,
|
||
|
st4PhaseOutletCount,
|
||
|
st4PhaseState,
|
||
|
st4PhaseStatus,
|
||
|
st4PhaseVoltage,
|
||
|
st4PhaseVoltageStatus,
|
||
|
st4PhaseVoltageDeviation,
|
||
|
st4PhaseCurrent,
|
||
|
st4PhaseCurrentCrestFactor,
|
||
|
st4PhaseActivePower,
|
||
|
st4PhaseApparentPower,
|
||
|
st4PhasePowerFactor,
|
||
|
st4PhasePowerFactorStatus,
|
||
|
st4PhaseReactance,
|
||
|
st4PhaseEnergy,
|
||
|
st4PhaseNotifications,
|
||
|
st4PhaseVoltageLowAlarm,
|
||
|
st4PhaseVoltageLowWarning,
|
||
|
st4PhaseVoltageHighWarning,
|
||
|
st4PhaseVoltageHighAlarm,
|
||
|
st4PhasePowerFactorLowAlarm,
|
||
|
st4PhasePowerFactorLowWarning
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Phase objects group."
|
||
|
::= { st4Groups 5 }
|
||
|
|
||
|
st4OcpObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4OcpID,
|
||
|
st4OcpLabel,
|
||
|
st4OcpType,
|
||
|
st4OcpCurrentCapacity,
|
||
|
st4OcpCurrentCapacityMax,
|
||
|
st4OcpBranchCount,
|
||
|
st4OcpOutletCount,
|
||
|
st4OcpStatus,
|
||
|
st4OcpNotifications
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Over-current protector objects group."
|
||
|
::= { st4Groups 6 }
|
||
|
|
||
|
st4BranchObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4BranchCurrentHysteresis,
|
||
|
st4BranchID,
|
||
|
st4BranchLabel,
|
||
|
st4BranchCurrentCapacity,
|
||
|
st4BranchPhaseID,
|
||
|
st4BranchOcpID,
|
||
|
st4BranchOutletCount,
|
||
|
st4BranchState,
|
||
|
st4BranchStatus,
|
||
|
st4BranchCurrent,
|
||
|
st4BranchCurrentStatus,
|
||
|
st4BranchCurrentUtilized,
|
||
|
st4BranchNotifications,
|
||
|
st4BranchCurrentLowAlarm,
|
||
|
st4BranchCurrentLowWarning,
|
||
|
st4BranchCurrentHighWarning,
|
||
|
st4BranchCurrentHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Branch objects group."
|
||
|
::= { st4Groups 7 }
|
||
|
|
||
|
st4OutletObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4OutletCurrentHysteresis,
|
||
|
st4OutletActivePowerHysteresis,
|
||
|
st4OutletPowerFactorHysteresis,
|
||
|
st4OutletSequenceInterval,
|
||
|
st4OutletRebootDelay,
|
||
|
st4OutletStateChangeLogging,
|
||
|
st4OutletID,
|
||
|
st4OutletName,
|
||
|
st4OutletCapabilities,
|
||
|
st4OutletSocketType,
|
||
|
st4OutletCurrentCapacity,
|
||
|
st4OutletPowerCapacity,
|
||
|
st4OutletWakeupState,
|
||
|
st4OutletPostOnDelay,
|
||
|
st4OutletPhaseID,
|
||
|
st4OutletOcpID,
|
||
|
st4OutletBranchID,
|
||
|
st4OutletState,
|
||
|
st4OutletStatus,
|
||
|
st4OutletCurrent,
|
||
|
st4OutletCurrentStatus,
|
||
|
st4OutletCurrentUtilized,
|
||
|
st4OutletVoltage,
|
||
|
st4OutletActivePower,
|
||
|
st4OutletActivePowerStatus,
|
||
|
st4OutletApparentPower,
|
||
|
st4OutletPowerFactor,
|
||
|
st4OutletPowerFactorStatus,
|
||
|
st4OutletCurrentCrestFactor,
|
||
|
st4OutletReactance,
|
||
|
st4OutletEnergy,
|
||
|
st4OutletNotifications,
|
||
|
st4OutletCurrentLowAlarm,
|
||
|
st4OutletCurrentLowWarning,
|
||
|
st4OutletCurrentHighWarning,
|
||
|
st4OutletCurrentHighAlarm,
|
||
|
st4OutletActivePowerLowAlarm,
|
||
|
st4OutletActivePowerLowWarning,
|
||
|
st4OutletActivePowerHighWarning,
|
||
|
st4OutletActivePowerHighAlarm,
|
||
|
st4OutletPowerFactorLowAlarm,
|
||
|
st4OutletPowerFactorLowWarning,
|
||
|
st4OutletControlState,
|
||
|
st4OutletControlAction,
|
||
|
st4OutletQueueControl
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Outlet objects group."
|
||
|
::= { st4Groups 8 }
|
||
|
|
||
|
st4TempSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4TempSensorHysteresis,
|
||
|
st4TempSensorScale,
|
||
|
st4TempSensorID,
|
||
|
st4TempSensorName,
|
||
|
st4TempSensorValueMin,
|
||
|
st4TempSensorValueMax,
|
||
|
st4TempSensorValue,
|
||
|
st4TempSensorStatus,
|
||
|
st4TempSensorNotifications,
|
||
|
st4TempSensorLowAlarm,
|
||
|
st4TempSensorLowWarning,
|
||
|
st4TempSensorHighWarning,
|
||
|
st4TempSensorHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor objects group."
|
||
|
::= { st4Groups 9 }
|
||
|
|
||
|
st4HumidSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4HumidSensorHysteresis,
|
||
|
st4HumidSensorID,
|
||
|
st4HumidSensorName,
|
||
|
st4HumidSensorValue,
|
||
|
st4HumidSensorStatus,
|
||
|
st4HumidSensorNotifications,
|
||
|
st4HumidSensorLowAlarm,
|
||
|
st4HumidSensorLowWarning,
|
||
|
st4HumidSensorHighWarning,
|
||
|
st4HumidSensorHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor objects group."
|
||
|
::= { st4Groups 10 }
|
||
|
|
||
|
st4WaterSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4WaterSensorID,
|
||
|
st4WaterSensorName,
|
||
|
st4WaterSensorStatus,
|
||
|
st4WaterSensorNotifications
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Water sensor objects group."
|
||
|
::= { st4Groups 11 }
|
||
|
|
||
|
st4CcSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4CcSensorID,
|
||
|
st4CcSensorName,
|
||
|
st4CcSensorStatus,
|
||
|
st4CcSensorNotifications
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor objects group."
|
||
|
::= { st4Groups 12 }
|
||
|
|
||
|
st4AdcSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4AdcSensorHysteresis,
|
||
|
st4AdcSensorID,
|
||
|
st4AdcSensorName,
|
||
|
st4AdcSensorValue,
|
||
|
st4AdcSensorStatus,
|
||
|
st4AdcSensorNotifications,
|
||
|
st4AdcSensorLowAlarm,
|
||
|
st4AdcSensorLowWarning,
|
||
|
st4AdcSensorHighWarning,
|
||
|
st4AdcSensorHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor objects group."
|
||
|
::= { st4Groups 13 }
|
||
|
|
||
|
st4FanSensorObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4FanSensorHysteresis,
|
||
|
st4FanSensorID,
|
||
|
st4FanSensorName,
|
||
|
st4FanSensorValue,
|
||
|
st4FanSensorStatus,
|
||
|
st4FanSensorNotifications,
|
||
|
st4FanSensorLowAlarm,
|
||
|
st4FanSensorLowWarning,
|
||
|
st4FanSensorHighWarning,
|
||
|
st4FanSensorHighAlarm
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Fan sensor objects group."
|
||
|
::= { st4Groups 14 }
|
||
|
|
||
|
st4EventInfoObjectsGroup OBJECT-GROUP
|
||
|
OBJECTS {
|
||
|
st4EventStatusText,
|
||
|
st4EventStatusCondition
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event information objects group."
|
||
|
::= { st4Groups 99 }
|
||
|
|
||
|
st4EventNotificationsGroup NOTIFICATION-GROUP
|
||
|
NOTIFICATIONS {
|
||
|
st4UnitStatusEvent,
|
||
|
st4InputCordStatusEvent,
|
||
|
st4InputCordActivePowerEvent,
|
||
|
st4InputCordApparentPowerEvent,
|
||
|
st4InputCordPowerFactorEvent,
|
||
|
st4InputCordOutOfBalanceEvent,
|
||
|
st4LineStatusEvent,
|
||
|
st4LineCurrentEvent,
|
||
|
st4PhaseStatusEvent,
|
||
|
st4PhaseVoltageEvent,
|
||
|
st4PhasePowerFactorEvent,
|
||
|
st4OcpStatusEvent,
|
||
|
st4BranchStatusEvent,
|
||
|
st4BranchCurrentEvent,
|
||
|
st4OutletStatusEvent,
|
||
|
st4OutletStateChangeEvent,
|
||
|
st4OutletCurrentEvent,
|
||
|
st4OutletActivePowerEvent,
|
||
|
st4OutletPowerFactorEvent,
|
||
|
st4TempSensorEvent,
|
||
|
st4HumidSensorEvent,
|
||
|
st4WaterSensorStatusEvent,
|
||
|
st4CcSensorStatusEvent,
|
||
|
st4AdcSensorEvent,
|
||
|
st4FanSensorEvent
|
||
|
}
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"Event notifications group."
|
||
|
::= { st4Groups 100 }
|
||
|
|
||
|
-- Compliance Statements
|
||
|
|
||
|
st4Compliances OBJECT IDENTIFIER ::= { st4Conformance 2 }
|
||
|
|
||
|
st4ModuleCompliances MODULE-COMPLIANCE
|
||
|
STATUS current
|
||
|
DESCRIPTION
|
||
|
"The requirements for conformance to the Sentry4-MIB."
|
||
|
MODULE
|
||
|
GROUP st4SystemObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"System objects group."
|
||
|
GROUP st4UnitObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Unit objects group."
|
||
|
GROUP st4InputCordObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Input cord objects group."
|
||
|
GROUP st4LineObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Line objects group."
|
||
|
GROUP st4PhaseObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Phase objects group."
|
||
|
GROUP st4OcpObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Over-current protector objects group."
|
||
|
GROUP st4BranchObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Branch objects group."
|
||
|
GROUP st4OutletObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Outlet objects group."
|
||
|
GROUP st4TempSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Temperature sensor objects group."
|
||
|
GROUP st4HumidSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Humidity sensor objects group."
|
||
|
GROUP st4WaterSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Water sensor objects group."
|
||
|
GROUP st4CcSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Contact closure sensor objects group."
|
||
|
GROUP st4AdcSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Analog-to-digital converter sensor objects group."
|
||
|
GROUP st4FanSensorObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Fan sensor objects group."
|
||
|
GROUP st4EventInfoObjectsGroup
|
||
|
DESCRIPTION
|
||
|
"Event information objects group."
|
||
|
GROUP st4EventNotificationsGroup
|
||
|
DESCRIPTION
|
||
|
"Event notifications group."
|
||
|
::= { st4Compliances 1 }
|
||
|
|
||
|
END
|