1322 lines
28 KiB
Plaintext
1322 lines
28 KiB
Plaintext
|
SNR-ERD-4 DEFINITIONS ::= BEGIN
|
|||
|
|
|||
|
IMPORTS
|
|||
|
MODULE-IDENTITY, OBJECT-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE
|
|||
|
FROM SNMPv2-SMI
|
|||
|
enterprises, IpAddress, Counter
|
|||
|
FROM RFC1155-SMI
|
|||
|
DisplayString
|
|||
|
FROM RFC1213-MIB
|
|||
|
NOTIFICATION-GROUP
|
|||
|
FROM SNMPv2-CONF
|
|||
|
;
|
|||
|
|
|||
|
snr MODULE-IDENTITY
|
|||
|
LAST-UPDATED "201810261200Z"
|
|||
|
ORGANIZATION "NAG "
|
|||
|
CONTACT-INFO "erd@nag.ru"
|
|||
|
DESCRIPTION
|
|||
|
"The MIB module for SNR-ERD"
|
|||
|
REVISION "201504291200Z"
|
|||
|
DESCRIPTION
|
|||
|
"Initial revision."
|
|||
|
::= { enterprises 40418 }
|
|||
|
|
|||
|
|
|||
|
snr-erd OBJECT IDENTIFIER ::= { snr 2 }
|
|||
|
snr-erd-4 OBJECT IDENTIFIER ::= { snr-erd 6 }
|
|||
|
|
|||
|
measurements OBJECT IDENTIFIER ::= { snr-erd-4 1 }
|
|||
|
|
|||
|
dio OBJECT IDENTIFIER ::= { snr-erd-4 2 }
|
|||
|
serial OBJECT IDENTIFIER ::= { snr-erd-4 4 }
|
|||
|
modules OBJECT IDENTIFIER ::= { snr-erd-4 5 }
|
|||
|
options OBJECT IDENTIFIER ::= { snr-erd-4 10 }
|
|||
|
diffparams OBJECT IDENTIFIER ::= { snr-erd-4 11 }
|
|||
|
|
|||
|
|
|||
|
oneWire OBJECT IDENTIFIER ::= { measurements 1 }
|
|||
|
sp OBJECT IDENTIFIER ::= { measurements 30 }
|
|||
|
sensorsTemplate OBJECT IDENTIFIER ::= { measurements 50 }
|
|||
|
|
|||
|
rs485 OBJECT IDENTIFIER ::= { serial 1 }
|
|||
|
rs232 OBJECT IDENTIFIER ::= { serial 2 }
|
|||
|
|
|||
|
gsm OBJECT IDENTIFIER ::= { modules 1 }
|
|||
|
rf OBJECT IDENTIFIER ::= { modules 2 }
|
|||
|
|
|||
|
upsStatus OBJECT IDENTIFIER ::= { diffparams 1 }
|
|||
|
|
|||
|
pid OBJECT IDENTIFIER ::= { diffparams 10 }
|
|||
|
|
|||
|
traps OBJECT IDENTIFIER ::= { snr-erd-4 0 }
|
|||
|
|
|||
|
crit OBJECT IDENTIFIER ::= { options 10 }
|
|||
|
|
|||
|
-- measurements
|
|||
|
|
|||
|
adcSensor OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "ADC sensor value"
|
|||
|
::= { measurements 2 }
|
|||
|
|
|||
|
temperatureDHT OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "DHT temperature value"
|
|||
|
::= { measurements 8 }
|
|||
|
|
|||
|
humidityDHT OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "DHT humidity value"
|
|||
|
::= { measurements 9 }
|
|||
|
|
|||
|
-- dtsTable
|
|||
|
|
|||
|
dtsTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF dtsEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of temperature sensors values"
|
|||
|
::= { oneWire 1 }
|
|||
|
|
|||
|
dtsEntry OBJECT-TYPE
|
|||
|
SYNTAX dtsEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row) in the dtsTable"
|
|||
|
INDEX { dtsId }
|
|||
|
::= { dtsTable 1 }
|
|||
|
|
|||
|
dtsEntry ::=
|
|||
|
SEQUENCE {
|
|||
|
dtsId UInteger32,
|
|||
|
dtsName OctetString,
|
|||
|
dtsTemp Integer,
|
|||
|
tempCritNotif Integer,
|
|||
|
tempCritMin Integer,
|
|||
|
tempCritMax Integer
|
|||
|
}
|
|||
|
|
|||
|
dtsId OBJECT-TYPE
|
|||
|
SYNTAX UInteger32
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature sensor id"
|
|||
|
::= { dtsEntry 1 }
|
|||
|
|
|||
|
dtsName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name (max 20)"
|
|||
|
::= { dtsEntry 2 }
|
|||
|
|
|||
|
dtsTemp OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Temperature value"
|
|||
|
::= { dtsEntry 3 }
|
|||
|
|
|||
|
tempCritNotif OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1),
|
|||
|
}
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Enable notifications on the critical temperature"
|
|||
|
::= { dtsEntry 10 }
|
|||
|
|
|||
|
tempCritMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Minimal critical temperature.
|
|||
|
Up to -55 <20>C"
|
|||
|
::= { dtsEntry 15 }
|
|||
|
|
|||
|
tempCritMax OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Maximum critical temperature.
|
|||
|
Up to +125<32>C"
|
|||
|
::= { dtsEntry 16 }
|
|||
|
|
|||
|
-- shuntTable
|
|||
|
|
|||
|
shuntTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF shuntEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"A list of SNR-SHUNT values"
|
|||
|
::= { oneWire 2 }
|
|||
|
|
|||
|
shuntEntry OBJECT-TYPE
|
|||
|
SYNTAX shuntEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"An entry (conceptual row) in the shuntTable"
|
|||
|
INDEX { shuntId }
|
|||
|
::= { shuntTable 1 }
|
|||
|
|
|||
|
shuntEntry ::=
|
|||
|
SEQUENCE {
|
|||
|
shuntId UInteger32,
|
|||
|
shuntName OctetString,
|
|||
|
shuntTemp Integer,
|
|||
|
shuntVolt Integer,
|
|||
|
shuntCurrent Integer,
|
|||
|
shuntCapacity Integer,
|
|||
|
shuntChrgCap Integer,
|
|||
|
shuntDischCap Integer,
|
|||
|
shuntEndOfChrg OctetString,
|
|||
|
shuntDiscn OctetString,
|
|||
|
shuntBatLive TimeTicks,
|
|||
|
shuntDischTime TimeTicks
|
|||
|
}
|
|||
|
|
|||
|
shuntId OBJECT-TYPE
|
|||
|
SYNTAX UInteger32
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"SNR-SHUNT id"
|
|||
|
::= { shuntEntry 1 }
|
|||
|
|
|||
|
shuntName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Name (max 20)"
|
|||
|
::= { shuntEntry 2 }
|
|||
|
|
|||
|
shuntTemp OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Temperature value"
|
|||
|
::= { shuntEntry 3 }
|
|||
|
|
|||
|
shuntVolt OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Voltage"
|
|||
|
::= { shuntEntry 4 }
|
|||
|
|
|||
|
shuntCurrent OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Current"
|
|||
|
::= { shuntEntry 5 }
|
|||
|
|
|||
|
shuntChrgLvl OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Battery charge level (0..100%)"
|
|||
|
::= { shuntEntry 6 }
|
|||
|
|
|||
|
shuntChrgCap OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Charge capacity"
|
|||
|
::= { shuntEntry 7 }
|
|||
|
|
|||
|
shuntDischCap OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Discharge capacity"
|
|||
|
::= { shuntEntry 8 }
|
|||
|
|
|||
|
shuntEndOfChrg OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"End of charge time"
|
|||
|
::= { shuntEntry 9 }
|
|||
|
|
|||
|
shuntDiscn OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Disconnect time"
|
|||
|
::= { shuntEntry 10 }
|
|||
|
|
|||
|
shuntBatLive OBJECT-TYPE
|
|||
|
SYNTAX TimeTicks
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Battery using period"
|
|||
|
::= { shuntEntry 11 }
|
|||
|
|
|||
|
shuntDischTime OBJECT-TYPE
|
|||
|
SYNTAX TimeTicks
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Time to full discharge"
|
|||
|
::= { shuntEntry 12 }
|
|||
|
|
|||
|
|
|||
|
-- wirelessSensors
|
|||
|
|
|||
|
rfshtpTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF rfshtpEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"A list of wireless sensors values"
|
|||
|
::= { measurements 10 }
|
|||
|
|
|||
|
rfshtpEntry OBJECT-TYPE
|
|||
|
SYNTAX rfshtpEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"An entry (conceptual row)
|
|||
|
in the wrlssSensTable"
|
|||
|
INDEX { wrlssSensIdent }
|
|||
|
::= { rfshtpTable 1 }
|
|||
|
|
|||
|
rfshtpEntry ::=
|
|||
|
SEQUENCE {
|
|||
|
rfshtpId OctetString,
|
|||
|
rfshtpName OctetString,
|
|||
|
rfshtpTemp Integer,
|
|||
|
rfshtpHum Integer,
|
|||
|
rfshtpPres Integer
|
|||
|
}
|
|||
|
|
|||
|
rfshtpId OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Wireless sensor id"
|
|||
|
::= { rfshtpEntry 1 }
|
|||
|
|
|||
|
rfshtpName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Name (max 20)"
|
|||
|
::= { rfshtpEntry 2 }
|
|||
|
|
|||
|
rfshtpTemp OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Temperature value"
|
|||
|
::= { rfshtpEntry 3 }
|
|||
|
|
|||
|
rfshtpHum OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Humidity value"
|
|||
|
::= { rfshtpEntry 4 }
|
|||
|
|
|||
|
rfshtpPres OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION
|
|||
|
"Pressure value"
|
|||
|
::= { rfshtpEntry 5 }
|
|||
|
|
|||
|
-- sp
|
|||
|
|
|||
|
-- rsshtpTable
|
|||
|
rsshtpTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF rsshtpEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of SNR-RSsensor-H/T/P values"
|
|||
|
::= { sp 1 }
|
|||
|
|
|||
|
rsshtpEntry OBJECT-TYPE
|
|||
|
SYNTAX rsshtpEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the rsshtpTable"
|
|||
|
INDEX { rsshtpIdent }
|
|||
|
::= { rsshtpTable 1 }
|
|||
|
|
|||
|
rsshtpEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
rsshtpIdent OctetString,
|
|||
|
rsshtpName OctetString,
|
|||
|
rsshtpTemp Integer,
|
|||
|
rsshtpHum Integer,
|
|||
|
rsshtpPssr Integer,
|
|||
|
tempCritNotif Integer,
|
|||
|
tempCritMin Integer,
|
|||
|
tempCritMax Integer
|
|||
|
}
|
|||
|
|
|||
|
rsshtpIdent OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "SNR-RSsensor-H/T/P id"
|
|||
|
::= { rsshtpEntry 1 }
|
|||
|
|
|||
|
rsshtpName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name (max 20)"
|
|||
|
::= { rsshtpEntry 2 }
|
|||
|
|
|||
|
rsshtpTemp OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature value 1"
|
|||
|
::= { rsshtpEntry 3 }
|
|||
|
|
|||
|
rsshtpHum OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Humidity value"
|
|||
|
::= { rsshtpEntry 4 }
|
|||
|
|
|||
|
rsshtpPssr OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Pressure value"
|
|||
|
::= { rsshtpEntry 6 }
|
|||
|
|
|||
|
tempCritNotif OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1),
|
|||
|
}
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Enable notifications on the critical temperature"
|
|||
|
::= { rsshtpEntry 10 }
|
|||
|
|
|||
|
tempCritMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Minimal critical temperature.
|
|||
|
Up to -55 <20>C"
|
|||
|
::= { rsshtpEntry 15 }
|
|||
|
|
|||
|
tempCritMax OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Maximum critical temperature.
|
|||
|
Up to +125<32>C"
|
|||
|
::= { rsshtpEntry 16 }
|
|||
|
|
|||
|
-- rscounterTable
|
|||
|
|
|||
|
rscounterTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF rscounterEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of SNR-RS-Counter"
|
|||
|
::= { sp 5 }
|
|||
|
|
|||
|
rscounterEntry OBJECT-TYPE
|
|||
|
SYNTAX rscounterEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the rscounterTable"
|
|||
|
INDEX { rscounterIdent }
|
|||
|
::= { rscounterTable 1 }
|
|||
|
|
|||
|
rscounterEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
rscounterIdent OctetString,
|
|||
|
rscounterName OctetString,
|
|||
|
}
|
|||
|
|
|||
|
rscounterIdent OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "SNR-RS-Counter id"
|
|||
|
::= { rscounterEntry 1 }
|
|||
|
|
|||
|
rscounterName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name (max 20)"
|
|||
|
::= { rscounterEntry 2 }
|
|||
|
|
|||
|
|
|||
|
-- rsshtp1WTable
|
|||
|
rsshtp1WTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF rsshtp1WEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of temperature sensors
|
|||
|
are connected to SNR-RSsensor-H/T/P"
|
|||
|
::= { sp 100 }
|
|||
|
|
|||
|
rsshtp1WEntry OBJECT-TYPE
|
|||
|
SYNTAX rsshtp1WEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the rsshtp1WTable"
|
|||
|
INDEX { rsshtp1WIdent }
|
|||
|
::= { rsshtp1WTable 1 }
|
|||
|
|
|||
|
rsshtp1WEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
rsshtp1WIdent UInteger32,
|
|||
|
rsshtp1WName OctetString,
|
|||
|
rsshtp1WTemp Integer,
|
|||
|
rsshtp1WMaster OctetString,
|
|||
|
tempCritNotif Integer,
|
|||
|
tempCritMin Integer,
|
|||
|
tempCritMax Integer
|
|||
|
}
|
|||
|
|
|||
|
rsshtp1WIdent OBJECT-TYPE
|
|||
|
SYNTAX UInteger32
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature sensor id"
|
|||
|
::= { rsshtp1WEntry 1 }
|
|||
|
|
|||
|
rsshtp1WName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name (max 20)"
|
|||
|
::= { rsshtp1WEntry 2 }
|
|||
|
|
|||
|
rsshtp1WTemp OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature value"
|
|||
|
::= { rsshtp1WEntry 3 }
|
|||
|
|
|||
|
rsshtp1WMaster OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name of the SNR-RSsensor-H/T/P
|
|||
|
which this temperature sensor
|
|||
|
is connected to"
|
|||
|
::= { rsshtp1WEntry 4 }
|
|||
|
|
|||
|
tempCritNotif OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1),
|
|||
|
}
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Enable notifications on the critical temperature"
|
|||
|
::= { rsshtp1WEntry 10 }
|
|||
|
|
|||
|
tempCritMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Minimal critical temperature.
|
|||
|
Up to -55 <20>C"
|
|||
|
::= { rsshtp1WEntry 15 }
|
|||
|
|
|||
|
tempCritMax OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Maximum critical temperature.
|
|||
|
Up to +125<32>C"
|
|||
|
::= { rsshtp1WEntry 16 }
|
|||
|
|
|||
|
-- sensorsTemplate
|
|||
|
|
|||
|
sensorsTemplateTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF sensorsTemplateEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of sensors values"
|
|||
|
::= { sensorsTemplate 1 }
|
|||
|
|
|||
|
sensorsTemplateEntry OBJECT-TYPE
|
|||
|
SYNTAX sensorsTemplateEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the rsshtp1WTable"
|
|||
|
INDEX { sensorsTemplateValue }
|
|||
|
::= { sensorsTemplateTable 1 }
|
|||
|
|
|||
|
sensorsTemplateEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
sensorsTemplateValue Integer,
|
|||
|
sensorsTemplateName OctetString
|
|||
|
}
|
|||
|
|
|||
|
sensorsTemplateValue OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Current value"
|
|||
|
::= { sensorsTemplateEntry 1 }
|
|||
|
|
|||
|
sensorsTemplateName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Name"
|
|||
|
::= { sensorsTemplateEntry 2 }
|
|||
|
|
|||
|
sensorsTemplateTotalConnected OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Total value of connected sensors"
|
|||
|
::= { sensorsTemplate 2 }
|
|||
|
|
|||
|
-- dio
|
|||
|
|
|||
|
diTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF diEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of digital inputs values"
|
|||
|
::= { dio 1 }
|
|||
|
|
|||
|
diEntry OBJECT-TYPE
|
|||
|
SYNTAX diEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the diTable"
|
|||
|
::= { diTable 1 }
|
|||
|
|
|||
|
diEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
diName OctetString,
|
|||
|
diAlarmName OctetString,
|
|||
|
diState Integer,
|
|||
|
diCnt Counter
|
|||
|
}
|
|||
|
|
|||
|
diName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital input name"
|
|||
|
::= { diEntry 1 }
|
|||
|
|
|||
|
diAlarmName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Alarm name"
|
|||
|
::= { diEntry 2 }
|
|||
|
|
|||
|
diState OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
low (0),
|
|||
|
high (1),
|
|||
|
off (2)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital input state"
|
|||
|
::= { diEntry 3 }
|
|||
|
|
|||
|
diCnt OBJECT-TYPE
|
|||
|
SYNTAX Counter
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital input impulse counter.
|
|||
|
Writable for reset only. Set 0 to reset"
|
|||
|
::= { diEntry 4 }
|
|||
|
|
|||
|
|
|||
|
doTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF doEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "A list of digital outputs values"
|
|||
|
::= { dio 2 }
|
|||
|
|
|||
|
doEntry OBJECT-TYPE
|
|||
|
SYNTAX doEntry
|
|||
|
MAX-ACCESS not-accessible
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "An entry (conceptual row)
|
|||
|
in the doTable"
|
|||
|
::= { doTable 1 }
|
|||
|
|
|||
|
doEntry ::= SEQUENCE
|
|||
|
{
|
|||
|
doName OctetString,
|
|||
|
doDeviceName OctetString,
|
|||
|
doState Integer,
|
|||
|
doResetTime Integer
|
|||
|
}
|
|||
|
|
|||
|
doName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital output name"
|
|||
|
::= { doEntry 1 }
|
|||
|
|
|||
|
doDeviceName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital output custom name"
|
|||
|
::= { doEntry 2 }
|
|||
|
|
|||
|
doState OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
off (0),
|
|||
|
on (1),
|
|||
|
reload (2)
|
|||
|
}
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Digital output state"
|
|||
|
::= { doEntry 3 }
|
|||
|
|
|||
|
doResetDelay OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Reload period (sec)"
|
|||
|
::= { doEntry 4 }
|
|||
|
|
|||
|
uSenseState OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
off (0),
|
|||
|
on (1)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Voltage sensor state"
|
|||
|
::= { dio 3 }
|
|||
|
|
|||
|
--serial
|
|||
|
|
|||
|
connectStatusRS485 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "RS485 TCP connection status"
|
|||
|
::= { rs485 1 }
|
|||
|
|
|||
|
ipAddrRS485 OBJECT-TYPE
|
|||
|
SYNTAX IPADDRESS
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "RS485 TCP connection IP address"
|
|||
|
::= { rs485 2 }
|
|||
|
|
|||
|
connectStatusRS232 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "RS232 TCP connection status"
|
|||
|
::= { rs232 1 }
|
|||
|
|
|||
|
ipAddrRS232 OBJECT-TYPE
|
|||
|
SYNTAX IPADDRESS
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "RS232 TCP connection IP address"
|
|||
|
::= { rs232 2 }
|
|||
|
|
|||
|
|
|||
|
-- gsm
|
|||
|
|
|||
|
gsmModuleStatus OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1),
|
|||
|
NoSim (2),
|
|||
|
Error (3),
|
|||
|
Connected (4)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "GSM module status"
|
|||
|
::= { gsm 1 }
|
|||
|
|
|||
|
gsmStrength OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signal level (dBm)"
|
|||
|
::= { gsm 2 }
|
|||
|
|
|||
|
gsmReconnCount OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Number of connection attempts"
|
|||
|
::= { gsm 10 }
|
|||
|
|
|||
|
-- rf
|
|||
|
|
|||
|
rfModuleStatus OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
No (0),
|
|||
|
Yes (1)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Status of the rf module"
|
|||
|
::= { rf 1 }
|
|||
|
|
|||
|
-- options
|
|||
|
|
|||
|
dataType OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
integer (0),
|
|||
|
float (1),
|
|||
|
ufloat (2)
|
|||
|
}
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Values data type"
|
|||
|
::= { options 1 }
|
|||
|
|
|||
|
reboot OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS write-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Send 1 to reboot"
|
|||
|
::= { options 300 }
|
|||
|
|
|||
|
-- crit
|
|||
|
|
|||
|
humCrit OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Critical humidity.
|
|||
|
From 0 to 100%"
|
|||
|
::= { crit 20 }
|
|||
|
|
|||
|
adcCritMin OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "ADC IN critical min"
|
|||
|
::= { crit 30 }
|
|||
|
|
|||
|
adcCritMax OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "ADC IN critical max"
|
|||
|
::= { crit 31 }
|
|||
|
|
|||
|
adcHysteresis OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "ADC IN hysteresis"
|
|||
|
::= { crit 35 }
|
|||
|
|
|||
|
-- diffparams
|
|||
|
|
|||
|
-- upsStatus
|
|||
|
|
|||
|
statusUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
{
|
|||
|
fail (1),
|
|||
|
ok (0),
|
|||
|
unknown (2)
|
|||
|
}
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "UPS status"
|
|||
|
::= { upsStatus 1 }
|
|||
|
|
|||
|
beeperStatusUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Beeper status.
|
|||
|
Megatec only"
|
|||
|
::= { upsStatus 8 }
|
|||
|
|
|||
|
shutdownStatusUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Shutdown is active.
|
|||
|
Megatec only"
|
|||
|
::= { upsStatus 10 }
|
|||
|
|
|||
|
lastBatteryChangeUPS OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Last battery change date (mm/dd/yyyy).
|
|||
|
Smart only"
|
|||
|
::= { upsStatus 20 }
|
|||
|
|
|||
|
shutdownTimeUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Shutdown period,
|
|||
|
minutes for Megatec, seconds for Smart.
|
|||
|
Writeble for Megatec only"
|
|||
|
::= { upsStatus 51 }
|
|||
|
|
|||
|
turnOnTimeUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Turn on period, minutes.
|
|||
|
Megatec only"
|
|||
|
::= { upsStatus 52 }
|
|||
|
|
|||
|
startShutdownTurnOnUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS write-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Shutdown after shutdownTimeUPS
|
|||
|
and turn on after turnOnTimeUPS for Megatec.
|
|||
|
Shutdown after shutdownTimeUPS for Smart.
|
|||
|
Send 1 to start, 0 to stop"
|
|||
|
::= { upsStatus 53 }
|
|||
|
|
|||
|
startTurnOnUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS write-only
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Turn on immediately, send 1 to turn on.
|
|||
|
Smart only"
|
|||
|
::= { upsStatus 54 }
|
|||
|
|
|||
|
startLongTestUPS OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
MAX-ACCESS read-write
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Start specified time period test.
|
|||
|
Send period in minutes to start.
|
|||
|
Megatec only"
|
|||
|
::= { upsStatus 71 }
|
|||
|
|
|||
|
-- pid
|
|||
|
|
|||
|
inputPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-write
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "PID SNMP input value"
|
|||
|
|
|||
|
::= { pid 1 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
outputPercentPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "PID output value.
|
|||
|
0 to 100%"
|
|||
|
|
|||
|
::= { pid 2 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
outputRealPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "PID output value
|
|||
|
(voltage if PID runs in analog mode
|
|||
|
or time if PID runs in PWM mode)"
|
|||
|
|
|||
|
::= { pid 3 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
ypPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "Proportional gain"
|
|||
|
|
|||
|
::= { pid 4 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
yiPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "Integral gain"
|
|||
|
|
|||
|
::= { pid 5 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
ydPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "Derivative gain"
|
|||
|
|
|||
|
::= { pid 6 }
|
|||
|
|
|||
|
|
|||
|
|
|||
|
errorPID OBJECT-TYPE
|
|||
|
|
|||
|
SYNTAX INTEGER
|
|||
|
|
|||
|
MAX-ACCESS read-only
|
|||
|
|
|||
|
STATUS current
|
|||
|
|
|||
|
DESCRIPTION "Error. Difference between setpoint
|
|||
|
and input value"
|
|||
|
|
|||
|
::= { pid 7 }
|
|||
|
|
|||
|
|
|||
|
-- Traps
|
|||
|
|
|||
|
DI1Alarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 1 Alarm fires"
|
|||
|
::= { traps 1 }
|
|||
|
|
|||
|
DI1Release NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 1 Alarm released"
|
|||
|
::= { traps 2 }
|
|||
|
|
|||
|
DI2Alarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 2 Alarm fires"
|
|||
|
::= { traps 3 }
|
|||
|
|
|||
|
DI2Release NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 2 Alarm released"
|
|||
|
::= { traps 4 }
|
|||
|
|
|||
|
DI3Alarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 3 Alarm fires"
|
|||
|
::= { traps 5 }
|
|||
|
|
|||
|
DI3Release NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 3 Alarm released"
|
|||
|
::= { traps 6 }
|
|||
|
|
|||
|
DI4Alarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 4 Alarm fires"
|
|||
|
::= { traps 7 }
|
|||
|
|
|||
|
DI4Release NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 4 Alarm released"
|
|||
|
::= { traps 8 }
|
|||
|
|
|||
|
DI5Alarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 5 Alarm fires"
|
|||
|
::= { traps 9 }
|
|||
|
|
|||
|
DI5Release NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Input 5 Alarm released"
|
|||
|
::= { traps 10 }
|
|||
|
|
|||
|
uSenseAlarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Phase sensor
|
|||
|
Alarm fires"
|
|||
|
::= { traps 11 }
|
|||
|
|
|||
|
uSenseRelease NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Phase sensor
|
|||
|
Alarm released"
|
|||
|
::= { traps 12 }
|
|||
|
|
|||
|
reloutOn NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Rele was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 13 }
|
|||
|
|
|||
|
reloutOff NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Rele was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 14 }
|
|||
|
|
|||
|
DO1On NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 1 was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 15 }
|
|||
|
|
|||
|
DO1Off NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 1 was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 16 }
|
|||
|
|
|||
|
DO2On NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 2 was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 17 }
|
|||
|
|
|||
|
DO2Off NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 2 was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 18 }
|
|||
|
|
|||
|
DO3On NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 3 was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 19 }
|
|||
|
|
|||
|
DO3Off NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 3 was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 20 }
|
|||
|
|
|||
|
DO4On NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 4 was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 21 }
|
|||
|
|
|||
|
DO4Off NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 4 was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 22 }
|
|||
|
|
|||
|
DO5On NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 5 was swithed on
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 23 }
|
|||
|
|
|||
|
DO5Off NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Signifies that Output 5 was swithed off
|
|||
|
by Thermostat or Gigrostat mode"
|
|||
|
::= { traps 24 }
|
|||
|
|
|||
|
tempSensorAlarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature alarm"
|
|||
|
::= { traps 29 }
|
|||
|
|
|||
|
tempSensorRelease NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Temperature release"
|
|||
|
::= { traps 30 }
|
|||
|
|
|||
|
adcSensorAlarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Voltage sensor alarm"
|
|||
|
::= { traps 31 }
|
|||
|
|
|||
|
adcSensorRelease NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Voltage sensor release"
|
|||
|
::= { traps 32 }
|
|||
|
|
|||
|
humSensorAlarm NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Humidity alarm"
|
|||
|
::= { traps 33 }
|
|||
|
|
|||
|
humSensorRelease NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Humidity release"
|
|||
|
::= { traps 34 }
|
|||
|
|
|||
|
task1Done NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Task 1 done"
|
|||
|
::= { traps 36 }
|
|||
|
|
|||
|
task2Done NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Task 2 done"
|
|||
|
::= { traps 37 }
|
|||
|
|
|||
|
task3Done NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Task 3 done"
|
|||
|
::= { traps 38 }
|
|||
|
|
|||
|
task4Done NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Task 4 done"
|
|||
|
::= { traps 39 }
|
|||
|
|
|||
|
pingLost NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Ping lost"
|
|||
|
::= { traps 45 }
|
|||
|
|
|||
|
batteryChargeLow NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Battery charge is low"
|
|||
|
::= { traps 47 }
|
|||
|
|
|||
|
upsUtilityFail NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "UPS utility fail"
|
|||
|
::= { traps 50 }
|
|||
|
|
|||
|
upsUtilityOk NOTIFICATION-TYPE
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "UPS utility OK"
|
|||
|
::= { traps 51 }
|
|||
|
|
|||
|
-- erd4Group
|
|||
|
|
|||
|
erd4Group NOTIFICATION-GROUP
|
|||
|
NOTIFICATIONS
|
|||
|
{
|
|||
|
DI1Alarm,
|
|||
|
DI1Release,
|
|||
|
DI2Alarm,
|
|||
|
DI2Release,
|
|||
|
DI3Alarm,
|
|||
|
DI3Release,
|
|||
|
DI4Alarm,
|
|||
|
DI4Release,
|
|||
|
DI5Alarm,
|
|||
|
DI5Release,
|
|||
|
uSenseAlarm,
|
|||
|
uSenseRelease,
|
|||
|
reloutOn,
|
|||
|
reloutOff,
|
|||
|
DO1On,
|
|||
|
DO1Off,
|
|||
|
DO2On,
|
|||
|
DO2Off,
|
|||
|
DO3On,
|
|||
|
DO3Off,
|
|||
|
DO4On,
|
|||
|
DO4Off,
|
|||
|
DO5On,
|
|||
|
DO5Off,
|
|||
|
tempSensorAlarm,
|
|||
|
tempSensorRelease,
|
|||
|
adcSensorAlarm,
|
|||
|
adcSensorRelease,
|
|||
|
humSensorAlarm,
|
|||
|
humSensorRelease,
|
|||
|
task1Done,
|
|||
|
task2Done,
|
|||
|
task3Done,
|
|||
|
task4Done,
|
|||
|
pingLost,
|
|||
|
batteryChargeLow,
|
|||
|
upsUtilityFail,
|
|||
|
upsUtilityOk
|
|||
|
}
|
|||
|
STATUS current
|
|||
|
DESCRIPTION "Notifications"
|
|||
|
::= { snr-erd-4 99 }
|
|||
|
|
|||
|
END
|