Initial commit
This commit is contained in:
553
MIBS/avtech/ROOMALERT12E-MIB
Normal file
553
MIBS/avtech/ROOMALERT12E-MIB
Normal file
@ -0,0 +1,553 @@
|
||||
--
|
||||
--defines ROOMALERT12E-MIB for SNMP agent extension of Room Alert 12E
|
||||
--Contents: Global Registration Module
|
||||
-- Room Alert OIDs - Enterprise 20916
|
||||
--Version: 3.3.0
|
||||
--Date: 28 May 2021
|
||||
--Developed By: AVTECH Software, Inc.
|
||||
|
||||
--
|
||||
--Copyright (c) 2021 AVTECH Software, Inc.
|
||||
--
|
||||
|
||||
ROOMALERT12E-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
|
||||
IMPORTS
|
||||
enterprises, IpAddress, Counter, TimeTicks
|
||||
FROM RFC1155-SMI
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
|
||||
|
||||
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
||||
products OBJECT IDENTIFIER ::= { avtech 1 }
|
||||
roomalert12E OBJECT IDENTIFIER ::= { products 10 }
|
||||
sensors OBJECT IDENTIFIER ::= { roomalert12E 1 }
|
||||
lightTower OBJECT IDENTIFIER ::= { roomalert12E 2 }
|
||||
internal-sen OBJECT IDENTIFIER ::= { sensors 1 }
|
||||
digital-sen1 OBJECT IDENTIFIER ::= { sensors 2 }
|
||||
digital-sen2 OBJECT IDENTIFIER ::= { sensors 3 }
|
||||
digital-sen3 OBJECT IDENTIFIER ::= { sensors 4 }
|
||||
switch1 OBJECT IDENTIFIER ::= { sensors 5 }
|
||||
switch2 OBJECT IDENTIFIER ::= { sensors 6 }
|
||||
switch3 OBJECT IDENTIFIER ::= { sensors 7 }
|
||||
switch4 OBJECT IDENTIFIER ::= { sensors 8 }
|
||||
analog OBJECT IDENTIFIER ::= { sensors 9 }
|
||||
relay OBJECT IDENTIFIER ::= { sensors 10 }
|
||||
traps OBJECT IDENTIFIER ::= { roomalert12E 3 }
|
||||
|
||||
-- Room Alert 12E MIB
|
||||
-- Parameters
|
||||
|
||||
|
||||
|
||||
|
||||
internal-sen-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "This value represents the current internal temperature in Celsius"
|
||||
::= { internal-sen 1 }
|
||||
|
||||
internal-sen-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "This value represents the current internal temperature in Fahrenheit."
|
||||
::= { internal-sen 2 }
|
||||
|
||||
internal-sen-3 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The internal sensor's label"
|
||||
::= { internal-sen 3 }
|
||||
|
||||
analog-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The current status of the Room Alert 12E analog input (0-5VDC)."
|
||||
::= { analog 1 }
|
||||
|
||||
analog-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The analog sensor's label."
|
||||
::= { analog 2 }
|
||||
|
||||
analog-3 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The current status of the Room Alert 12E analog input (user-defined scale)."
|
||||
::= { analog 3 }
|
||||
|
||||
relay-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The current status of the Room Alert 12E relay output."
|
||||
::= { relay 1 }
|
||||
|
||||
relay-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The relay output's label."
|
||||
::= { relay 2 }
|
||||
|
||||
digital-sen1-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
||||
::= { digital-sen1 1 }
|
||||
|
||||
digital-sen1-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
||||
::= { digital-sen1 2 }
|
||||
|
||||
digital-sen1-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
||||
::= { digital-sen1 3 }
|
||||
|
||||
digital-sen1-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
||||
::= { digital-sen1 4 }
|
||||
|
||||
digital-sen1-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
||||
::= { digital-sen1 5 }
|
||||
|
||||
digital-sen1-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
||||
::= { digital-sen1 6 }
|
||||
|
||||
digital-sen1-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
||||
::= { digital-sen1 7 }
|
||||
|
||||
digital-sen1-8 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The sensor's label"
|
||||
::= { digital-sen1 8 }
|
||||
|
||||
digital-sen2-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
||||
::= { digital-sen2 1 }
|
||||
|
||||
digital-sen2-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
||||
::= { digital-sen2 2 }
|
||||
|
||||
digital-sen2-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
||||
::= { digital-sen2 3 }
|
||||
|
||||
digital-sen2-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
||||
::= { digital-sen2 4 }
|
||||
|
||||
digital-sen2-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
||||
::= { digital-sen2 5 }
|
||||
|
||||
digital-sen2-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
||||
::= { digital-sen2 6 }
|
||||
|
||||
digital-sen2-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
||||
::= { digital-sen2 7 }
|
||||
|
||||
digital-sen2-8 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The sensor's label"
|
||||
::= { digital-sen2 8 }
|
||||
|
||||
digital-sen3-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
||||
::= { digital-sen3 1 }
|
||||
|
||||
digital-sen3-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
||||
::= { digital-sen3 2 }
|
||||
|
||||
digital-sen3-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
||||
::= { digital-sen3 3 }
|
||||
|
||||
digital-sen3-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
||||
::= { digital-sen3 4 }
|
||||
|
||||
digital-sen3-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
||||
::= { digital-sen3 5 }
|
||||
|
||||
digital-sen3-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
||||
::= { digital-sen3 6 }
|
||||
|
||||
digital-sen3-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
||||
::= { digital-sen3 7 }
|
||||
|
||||
digital-sen3-8 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The sensor's label"
|
||||
::= { digital-sen3 8 }
|
||||
|
||||
switch-sen1-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { switch1 1 }
|
||||
|
||||
switch-sen1-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 1."
|
||||
::= { switch1 2 }
|
||||
|
||||
switch-sen2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { switch2 1 }
|
||||
|
||||
switch-sen2-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 2."
|
||||
::= { switch2 2 }
|
||||
|
||||
switch-sen3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { switch3 1 }
|
||||
|
||||
switch-sen3-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 3."
|
||||
::= { switch3 2 }
|
||||
|
||||
switch-sen4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { switch4 1 }
|
||||
|
||||
switch-sen4-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 4."
|
||||
::= { switch4 2 }
|
||||
|
||||
alarmmessage OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Last Alarm Message"
|
||||
::= { traps 1 }
|
||||
|
||||
|
||||
-- Light Tower
|
||||
|
||||
lightTower-RE OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the red LED on the Light Tower."
|
||||
::= { lightTower 1 }
|
||||
|
||||
lightTower-OR OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the orange LED on the Light Tower."
|
||||
::= { lightTower 2 }
|
||||
|
||||
lightTower-GR OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the green LED on the Light Tower."
|
||||
::= { lightTower 3 }
|
||||
|
||||
lightTower-WH OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the white LED on the Light Tower."
|
||||
::= { lightTower 4 }
|
||||
|
||||
lightTower-BL OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the blue LED on the Light Tower."
|
||||
::= { lightTower 5 }
|
||||
|
||||
lightTower-A1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the 1st audio alarm on the Light Tower."
|
||||
::= { lightTower 6 }
|
||||
|
||||
lightTower-A2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the 2nd audio alarm on the Light Tower."
|
||||
::= { lightTower 7 }
|
||||
|
||||
lightTower-RL OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of the LTA's on-board relay output"
|
||||
::= { lightTower 8 }
|
||||
|
||||
|
||||
-- ROOMALERT12E TRAPS
|
||||
|
||||
tempalarm1-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A tempalarm1 trap signifies that the current
|
||||
temperature on external sensor 1 is outside the
|
||||
defined high or low threshold."
|
||||
::= 1
|
||||
|
||||
room-alert-12E-snmp-trap TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A room-alert-12E-snmp-trap indicates that an alarm
|
||||
condition has occurred on the sensor inidcated
|
||||
by the alarmMessage variable."
|
||||
::= 2
|
||||
|
||||
tempalarm2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A tempalarm2 trap signifies that the current
|
||||
temperature on external sensor 2 is outside the
|
||||
defined high or low threshold."
|
||||
::= 3
|
||||
|
||||
tempclear2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A tempclear2 trap signifies that the current
|
||||
temperature on external sensor 2 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 4
|
||||
|
||||
tempalarm3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A tempalarm3 trap signifies that the current
|
||||
temperature on external sensor 3 is outside the
|
||||
defined high or low threshold."
|
||||
::= 5
|
||||
|
||||
tempclear3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A tempclear3 trap signifies that the current
|
||||
temperature on external sensor 3 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 6
|
||||
|
||||
humidityalarm1-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityalarm1 trap signifies that the current
|
||||
humidity on external sensor 1 is outside the
|
||||
defined high or low threshold."
|
||||
::= 7
|
||||
|
||||
humidityclear1-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityclear1 trap signifies that the current
|
||||
humidity on external sensor 1 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 8
|
||||
|
||||
humidityalarm2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityalarm2 trap signifies that the current
|
||||
humidity on external sensor 2 is outside the
|
||||
defined high or low threshold."
|
||||
::= 9
|
||||
|
||||
humidityclear2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityclear2 trap signifies that the current
|
||||
humidity on external sensor 2 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 10
|
||||
|
||||
humidityalarm3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityalarm3 trap signifies that the current
|
||||
humidity on external sensor 3 is outside the
|
||||
defined high or low threshold."
|
||||
::= 11
|
||||
|
||||
humidityclear3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A humidityclear3 trap signifies that the current
|
||||
humidity on external sensor 3 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 12
|
||||
|
||||
switchalarm1-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchalarm1 trap signifies that switch sensor 1
|
||||
is in an alarm state."
|
||||
::= 13
|
||||
|
||||
switchclear1-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchclear1 trap signifies that the switch sensor 1
|
||||
has returned to a normal state."
|
||||
::= 14
|
||||
|
||||
switchalarm2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchalarm2 trap signifies that switch sensor 2
|
||||
is in an alarm state."
|
||||
::= 15
|
||||
|
||||
switchclear2-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchclear2 trap signifies that the switch sensor 2
|
||||
has returned to a normal state."
|
||||
::= 16
|
||||
|
||||
switchalarm3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchalarm3 trap signifies that switch sensor 3
|
||||
is in an alarm state."
|
||||
::= 17
|
||||
|
||||
switchclear3-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchclear3 trap signifies that the switch sensor 3
|
||||
has returned to a normal state."
|
||||
::= 18
|
||||
|
||||
switchalarm4-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchalarm4 trap signifies that switch sensor 4
|
||||
is in an alarm state."
|
||||
::= 19
|
||||
|
||||
switchclear4-12E TRAP-TYPE
|
||||
ENTERPRISE roomalert12E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A switchclear4 trap signifies that the switch sensor 4
|
||||
has returned to a normal state."
|
||||
::= 20
|
||||
END
|
Reference in New Issue
Block a user