Initial commit
This commit is contained in:
		
							
								
								
									
										801
									
								
								MIBS/carel/CAREL-RITTAL-LCP-3311-MIB
									
									
									
									
									
										Normal file
									
								
							
							
						
						
									
										801
									
								
								MIBS/carel/CAREL-RITTAL-LCP-3311-MIB
									
									
									
									
									
										Normal file
									
								
							@@ -0,0 +1,801 @@
 | 
			
		||||
-- *****************************************************************
 | 
			
		||||
--  CAREL-RITTAL-LCP-3311-MIB
 | 
			
		||||
--  MIB for rittal 3311 lcp chillers using a carel pcoweb card (SK 3311.320)
 | 
			
		||||
--
 | 
			
		||||
-- June, 2021 Gregory Bers, Limburg, Belgium
 | 
			
		||||
--  
 | 
			
		||||
-- System OID found under .1.3.6.1.2.1.1.2.0
 | 
			
		||||
-- 
 | 
			
		||||
-- Documentation: https://github.com/epiecs/carel-pco-mibs
 | 
			
		||||
--
 | 
			
		||||
-- PCO settings
 | 
			
		||||
-- System OID:		1.3.6.1.4.1.9839.2606.1
 | 
			
		||||
-- Enterprise OID:	9839.2606
 | 
			
		||||
-- *****************************************************************
 | 
			
		||||
 | 
			
		||||
CAREL-RITTAL-LCP-3311-MIB DEFINITIONS ::= BEGIN
 | 
			
		||||
 | 
			
		||||
IMPORTS
 | 
			
		||||
	MODULE-IDENTITY, enterprises, OBJECT-TYPE, Integer32
 | 
			
		||||
				FROM SNMPv2-SMI
 | 
			
		||||
        OBJECT-GROUP
 | 
			
		||||
                FROM SNMPv2-CONF
 | 
			
		||||
        TEXTUAL-CONVENTION
 | 
			
		||||
                FROM SNMPv2-TC        
 | 
			
		||||
        ;
 | 
			
		||||
 | 
			
		||||
carel	MODULE-IDENTITY
 | 
			
		||||
		LAST-UPDATED "202106290000Z"
 | 
			
		||||
		ORGANIZATION "Epiecs"
 | 
			
		||||
                CONTACT-INFO
 | 
			
		||||
			"EPIECS
 | 
			
		||||
                        epiecs.be
 | 
			
		||||
 | 
			
		||||
			Email:	gregorybers@epiecs.be"
 | 
			
		||||
		DESCRIPTION
 | 
			
		||||
			"Custom MIB for Rittal LCP 3311 chillers connected to a pco web card"
 | 
			
		||||
 | 
			
		||||
		REVISION
 | 
			
		||||
			"202106290000Z"
 | 
			
		||||
 | 
			
		||||
		DESCRIPTION
 | 
			
		||||
			"First draft containing the values outlined in the 3311.320 docs 
 | 
			
		||||
                        https://www.rittal.com/imf/none/3_4342/3311320_Instructions_spec__EN"
 | 
			
		||||
 | 
			
		||||
	::= { enterprises 9839 }
 | 
			
		||||
 | 
			
		||||
-- tree under 9839
 | 
			
		||||
     rittal                      OBJECT IDENTIFIER ::= { carel 2606 }
 | 
			
		||||
       rittalLCP3311               OBJECT IDENTIFIER ::= { rittal 2 }
 | 
			
		||||
         sensors                     OBJECT IDENTIFIER ::= { rittalLCP3311 1 }
 | 
			
		||||
           digital                   OBJECT IDENTIFIER ::= { sensors  1 }
 | 
			
		||||
           analog                    OBJECT IDENTIFIER ::= { sensors  2 }
 | 
			
		||||
           integer                   OBJECT IDENTIFIER ::= { sensors  3 }
 | 
			
		||||
 | 
			
		||||
-- 
 | 
			
		||||
-- object groups
 | 
			
		||||
-- 
 | 
			
		||||
 | 
			
		||||
-- integerSensors OBJECT-GROUP
 | 
			
		||||
--     OBJECTS { fanSpeedPercent, fanSpeedRpm }
 | 
			
		||||
--     STATUS  current
 | 
			
		||||
--     DESCRIPTION
 | 
			
		||||
--             "A collection of all sensors providing integer values"
 | 
			
		||||
--     ::= { integer 1 }
 | 
			
		||||
 | 
			
		||||
-- 
 | 
			
		||||
-- conversions
 | 
			
		||||
-- 
 | 
			
		||||
 | 
			
		||||
DivBy10 ::= TEXTUAL-CONVENTION
 | 
			
		||||
    DISPLAY-HINT "d-1"
 | 
			
		||||
    STATUS       current
 | 
			
		||||
    DESCRIPTION  "Fixed point, one decimal"
 | 
			
		||||
    SYNTAX       Integer32
 | 
			
		||||
 | 
			
		||||
-- 
 | 
			
		||||
-- digital objects
 | 
			
		||||
-- 
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.2
 | 
			
		||||
compressorOverloadAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor overload alarm
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 2 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.3
 | 
			
		||||
highPressureAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "High pressure alarm
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 3 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.8
 | 
			
		||||
remoteOnOff               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		off (0),
 | 
			
		||||
		on (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Remote On/Off
 | 
			
		||||
                off (0),
 | 
			
		||||
		on (1)"
 | 
			
		||||
	::= { digital 8 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.11
 | 
			
		||||
inverterAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Inverter alarm
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 11 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.12
 | 
			
		||||
driveAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Power+ drive off-line alarm
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 12 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.17
 | 
			
		||||
inverterOnOff               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		off (0),
 | 
			
		||||
		on (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Inverter On/Off
 | 
			
		||||
                off (0),
 | 
			
		||||
		on (1)"
 | 
			
		||||
	::= { digital 17 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.23
 | 
			
		||||
generalAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "General alarm
 | 
			
		||||
        alarm (0),
 | 
			
		||||
		ok (1)"
 | 
			
		||||
	::= { digital 23 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.29
 | 
			
		||||
resetAllAlarms               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		no (0),
 | 
			
		||||
		yes (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-write
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Reset all alarms
 | 
			
		||||
                no (0),
 | 
			
		||||
		yes (1)"
 | 
			
		||||
	::= { digital 29 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.30
 | 
			
		||||
compressorEnvelopeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor forced off working out envelope
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 30 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.31
 | 
			
		||||
compressorStartupFailureAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor startup failure alarm, reached max retries
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 31 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.33
 | 
			
		||||
maxDischargeTemperatureAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Maximum discharge temperature has been reached
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 33 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.35
 | 
			
		||||
compressorDeltaPressureAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Delta pressure too big to startup compressor
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 35 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.36
 | 
			
		||||
oilReturnAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Oil return alarm for when the compressor is running. Lubrication issue.
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 36 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.38
 | 
			
		||||
outputTemperatureTopProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Top output temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 38 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.39
 | 
			
		||||
outputTemperatureMidProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Mid output temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 39 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.40
 | 
			
		||||
outputTemperatureBottomProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Bottom output temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 40 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.42
 | 
			
		||||
inputTemperatureTopProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Top input temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 42 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.43
 | 
			
		||||
inputTemperatureMidProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Mid input temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 43 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.44
 | 
			
		||||
inputTemperatureBottomProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Bottom input temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 44 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.45
 | 
			
		||||
compressorDischargeTemperatureProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor discharge temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 45 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.46
 | 
			
		||||
compressorSuctionTemperatureProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor suction temperature probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 46 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.47
 | 
			
		||||
compressorDischargePressureProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor discharge pressure probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 47 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.48
 | 
			
		||||
compressorSuctionPressureProbeAlarm               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		ok (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor suction pressure probe broken
 | 
			
		||||
        ok (0),
 | 
			
		||||
		alarm (1)"
 | 
			
		||||
	::= { digital 48 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.1.100
 | 
			
		||||
reboot               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		no (0),
 | 
			
		||||
		yes (1)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-write
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Reboot the system
 | 
			
		||||
                no (0),
 | 
			
		||||
		yes (1)"
 | 
			
		||||
	::= { digital 100 }
 | 
			
		||||
 | 
			
		||||
-- 
 | 
			
		||||
-- integer objects
 | 
			
		||||
-- 
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.1
 | 
			
		||||
compressorRotorSpeedHz            OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..9999)
 | 
			
		||||
        UNITS           "Hz"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor rotor speed in Hz"
 | 
			
		||||
	::= { integer 1 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.2
 | 
			
		||||
driverPowerStatus               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		stop (1),
 | 
			
		||||
		run (2),
 | 
			
		||||
		alarm (3)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Driver power status
 | 
			
		||||
                stop (1),
 | 
			
		||||
		run (2),
 | 
			
		||||
		alarm (3)"
 | 
			
		||||
	::= { integer 2 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.3
 | 
			
		||||
currentErrorCode                OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
		OK (0),
 | 
			
		||||
		ALA02 (2),
 | 
			
		||||
		ALA03 (3),
 | 
			
		||||
		ALA04 (4),
 | 
			
		||||
		ALA05 (5),
 | 
			
		||||
		ALA06 (6),
 | 
			
		||||
		ALA07 (7),
 | 
			
		||||
		ALA08 (8),
 | 
			
		||||
		ALA09 (9),
 | 
			
		||||
		ALA10 (10),
 | 
			
		||||
		ALA11 (11),
 | 
			
		||||
		ALA12 (12),
 | 
			
		||||
		ALB01 (13),
 | 
			
		||||
		ALB02 (14),
 | 
			
		||||
		ALB03 (15),
 | 
			
		||||
		ALC01 (16),
 | 
			
		||||
		ALC03 (17),
 | 
			
		||||
		ALC04 (18),
 | 
			
		||||
		ALC05 (19),
 | 
			
		||||
		ALC06 (20),
 | 
			
		||||
		ALF01 (21),
 | 
			
		||||
		ALD02 (22),
 | 
			
		||||
		ALD03 (23),
 | 
			
		||||
		ALD04 (24),
 | 
			
		||||
		ALD05 (25),
 | 
			
		||||
		ALD06 (26),
 | 
			
		||||
		ALD07 (27),
 | 
			
		||||
		ALD08 (28),
 | 
			
		||||
		ALD09 (29),
 | 
			
		||||
		ALL01 (30),
 | 
			
		||||
		ALL02 (31),
 | 
			
		||||
		ALL99 (32),
 | 
			
		||||
		ALW04 (33)
 | 
			
		||||
	}
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Current error code"
 | 
			
		||||
	::= { integer 3 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.4
 | 
			
		||||
driverTemperature               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Driver Power+ Temperature"
 | 
			
		||||
	::= { integer 4 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.5
 | 
			
		||||
dcBusVoltage               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "V"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Power+ DC Voltage"
 | 
			
		||||
	::= { integer 5 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.6
 | 
			
		||||
motorVoltage               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "V"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Motor Voltage"
 | 
			
		||||
	::= { integer 6 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.7
 | 
			
		||||
powerRequest               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "%"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Request of power for inverter after envelop"
 | 
			
		||||
	::= { integer 7 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.13
 | 
			
		||||
unitOnOff               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
                off (0),
 | 
			
		||||
		on (1),
 | 
			
		||||
		energy-save (2),
 | 
			
		||||
		auto (3)
 | 
			
		||||
        }
 | 
			
		||||
	MAX-ACCESS	read-write
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Unit on/off state
 | 
			
		||||
          off (0),
 | 
			
		||||
          on (1),
 | 
			
		||||
          energy-save (2),
 | 
			
		||||
          auto (3)
 | 
			
		||||
          "
 | 
			
		||||
	::= { integer 13 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.14
 | 
			
		||||
envelopeZone               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER {
 | 
			
		||||
        ok (0),
 | 
			
		||||
		maximum-compression-ratio (1),
 | 
			
		||||
		maximum-discharge-power (2),
 | 
			
		||||
		current-limit (3),
 | 
			
		||||
		maximum-suction-power(4),
 | 
			
		||||
		minimum-compression-ratio (5),
 | 
			
		||||
		minimum-delta-power (6),
 | 
			
		||||
		minimum-discharge-power(7),
 | 
			
		||||
		minimum-suction-power (8)
 | 
			
		||||
        }
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "envelope zone
 | 
			
		||||
          ok (0),
 | 
			
		||||
	  maximum compression ratio (1),
 | 
			
		||||
	  maximum discharge power (2),
 | 
			
		||||
	  current limit (3),
 | 
			
		||||
	  maximum suction power(4),
 | 
			
		||||
	  minimum compression ratio (5),
 | 
			
		||||
	  minimum delta power (6),
 | 
			
		||||
	  minimum discharge power(7),
 | 
			
		||||
	  minimum suction power (8)
 | 
			
		||||
          "
 | 
			
		||||
	::= { integer 14 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.16
 | 
			
		||||
coolingCapacity               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..100)
 | 
			
		||||
        UNITS           "%"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Actual EVD valve cooling capacity"
 | 
			
		||||
	::= { integer 16 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.17
 | 
			
		||||
evdValveSteps               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..540)
 | 
			
		||||
        UNITS           "steps"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "EVD valve steps position"
 | 
			
		||||
	::= { integer 17 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.28
 | 
			
		||||
fanSpeedPercent                 OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..100)
 | 
			
		||||
        UNITS           "%"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "The fan speed percentage"
 | 
			
		||||
	::= { integer 28 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.29
 | 
			
		||||
fanSpeedRpm                     OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..3700)
 | 
			
		||||
        UNITS           "rpm"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "The fan speed rpm"
 | 
			
		||||
	::= { integer 29 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.3.30
 | 
			
		||||
evdValveOpening               OBJECT-TYPE
 | 
			
		||||
	SYNTAX		INTEGER (0..100)
 | 
			
		||||
        UNITS           "%"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Actual EVD valve opening"
 | 
			
		||||
	::= { integer 30 }
 | 
			
		||||
 | 
			
		||||
--
 | 
			
		||||
-- analog objects
 | 
			
		||||
--
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.2
 | 
			
		||||
outputTemperatureTopSensor       OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Top sensor output temperature in Celcius"
 | 
			
		||||
	::= { analog 2 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.3
 | 
			
		||||
outputTemperatureMidSensor       OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Mid sensor output temperature in Celcius"
 | 
			
		||||
	::= { analog 3 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.4
 | 
			
		||||
outputTemperatureBottomSensor    OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Bottom sensor output temperature in Celcius"
 | 
			
		||||
	::= { analog 4 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.6
 | 
			
		||||
inputTemperatureTopSensor       OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Top sensor input temperature in Celcius"
 | 
			
		||||
	::= { analog 6 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.7
 | 
			
		||||
inputTemperatureMidSensor       OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Mid sensor input temperature in Celcius"
 | 
			
		||||
	::= { analog 7 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.8
 | 
			
		||||
inputTemperatureBottomSensor    OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Bottom sensor input temperature in Celcius"
 | 
			
		||||
	::= { analog 8 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.9
 | 
			
		||||
compressorDischargeTemperature  OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor discharge temperature"
 | 
			
		||||
	::= { analog 9 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.10
 | 
			
		||||
compressorSuctionTemperature    OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor suction temperature"
 | 
			
		||||
	::= { analog 10 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.11
 | 
			
		||||
compressorDischargePressure  OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "bar"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor discharge pressure"
 | 
			
		||||
	::= { analog 11 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.12
 | 
			
		||||
compressorSuctionPressure    OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "bar"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor suction pressure"
 | 
			
		||||
	::= { analog 12 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.13
 | 
			
		||||
evaporatorTemperature    OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Evaporator temperature from Low pressure conversion"
 | 
			
		||||
	::= { analog 13 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.14
 | 
			
		||||
condensingTemperature  OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Condensing temperature from High pressure conversion"
 | 
			
		||||
	::= { analog 14 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.21
 | 
			
		||||
inputTemperatureAverage         OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Average input temperature in Celcius"
 | 
			
		||||
	::= { analog 21 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.22
 | 
			
		||||
outputTemperatureAverage        OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Average output temperature in Celcius"
 | 
			
		||||
	::= { analog 22 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.45
 | 
			
		||||
compressorRotorSpeed        OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "rps"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor rotor speed"
 | 
			
		||||
	::= { analog 45 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.46
 | 
			
		||||
compressorMotorCurrent        OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "A"
 | 
			
		||||
	MAX-ACCESS	read-only
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Compressor motor current"
 | 
			
		||||
	::= { analog 46 }
 | 
			
		||||
 | 
			
		||||
        --  .1.3.6.1.4.1.9839.2606.2.1.2.48
 | 
			
		||||
lcpSetpoint        OBJECT-TYPE
 | 
			
		||||
	SYNTAX		DivBy10
 | 
			
		||||
        UNITS           "C"
 | 
			
		||||
	MAX-ACCESS	read-write
 | 
			
		||||
	STATUS		current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
	  "Main LCP setpoint"
 | 
			
		||||
	::= { analog 48 }
 | 
			
		||||
 | 
			
		||||
END
 | 
			
		||||
		Reference in New Issue
	