Initial commit
This commit is contained in:
526
MIBS/comet/T3610-MIB
Normal file
526
MIBS/comet/T3610-MIB
Normal file
@ -0,0 +1,526 @@
|
||||
----------------------------------------------------------------------
|
||||
-- MIB table for T3610
|
||||
--
|
||||
-- v3.0 for firmware 1-5-7-2, 2016-04-11
|
||||
-----------------------------------------------------------------------
|
||||
T3610-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
|
||||
IMPORTS
|
||||
enterprises
|
||||
FROM RFC1155-SMI
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
|
||||
DisplayString ::= OCTET STRING
|
||||
|
||||
|
||||
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
|
||||
products OBJECT IDENTIFIER ::= { comet 1 }
|
||||
t3610 OBJECT IDENTIFIER ::= { products 2 }
|
||||
values OBJECT IDENTIFIER ::= { t3610 1 }
|
||||
global OBJECT IDENTIFIER ::= { t3610 2 }
|
||||
valuesInt OBJECT IDENTIFIER ::= { t3610 3 }
|
||||
settings OBJECT IDENTIFIER ::= { t3610 4 }
|
||||
traps OBJECT IDENTIFIER ::= { t3610 5 }
|
||||
tables OBJECT IDENTIFIER ::= { t3610 6 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Measured values - String
|
||||
-----------------------------------------------------------------------
|
||||
temp OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature"
|
||||
::= { values 1 }
|
||||
|
||||
hum OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Relative humidity"
|
||||
::= { values 2 }
|
||||
|
||||
compVal OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value"
|
||||
::= { values 3 }
|
||||
|
||||
tempAlarm OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Temperature; none, high, low"
|
||||
::= { values 5 }
|
||||
|
||||
humAlarm OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Relative humidity; none, high, low"
|
||||
::= { values 6 }
|
||||
|
||||
compValAlarm OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Computed value; none, high, low"
|
||||
::= { values 7 }
|
||||
|
||||
tempUnit OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Unit"
|
||||
::= { values 9 }
|
||||
|
||||
humUnit OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Relative humidity Unit"
|
||||
::= { values 10 }
|
||||
|
||||
compValUnit OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value Unit"
|
||||
::= { values 11 }
|
||||
|
||||
tempMin OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Minimal temperature"
|
||||
::= { values 13 }
|
||||
|
||||
humMin OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Minimal relative humidity"
|
||||
::= { values 14 }
|
||||
|
||||
compValMin OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Minimal computed value"
|
||||
::= { values 15 }
|
||||
|
||||
tempMax OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Maximal temperature"
|
||||
::= { values 17 }
|
||||
|
||||
humMax OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Maximal relative humidity"
|
||||
::= { values 18 }
|
||||
|
||||
compValMax OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Maximal computed value"
|
||||
::= { values 19 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Device informations
|
||||
-----------------------------------------------------------------------
|
||||
sensorName OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..68))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Device name"
|
||||
::= { global 1 }
|
||||
|
||||
serialNumber OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Serial number"
|
||||
::= { global 2 }
|
||||
|
||||
deviceType OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..65534)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Device type"
|
||||
::= { global 3 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Measured values - Integer
|
||||
-----------------------------------------------------------------------
|
||||
tempInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature (value*10)"
|
||||
::= { valuesInt 1 }
|
||||
|
||||
humInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Relative humidity (value*10)"
|
||||
::= { valuesInt 2 }
|
||||
|
||||
compValInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value (value*10)"
|
||||
::= { valuesInt 3 }
|
||||
|
||||
tempAlarmInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..2)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low"
|
||||
::= { valuesInt 5 }
|
||||
|
||||
humAlarmInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..2)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Relative humidity; 0 - No, 1 - High, 2 - Low"
|
||||
::= { valuesInt 6 }
|
||||
|
||||
compValAlarmInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..2)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Computed value; 0 - No, 1 - High, 2 - Low"
|
||||
::= { valuesInt 7 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Alarm settings
|
||||
-----------------------------------------------------------------------
|
||||
tempLowInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Limit Low (value*10)"
|
||||
::= { settings 1 }
|
||||
|
||||
tempHighInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Limit High (value*10)"
|
||||
::= { settings 2 }
|
||||
|
||||
humLowInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Humidity Limit Low (value*10)"
|
||||
::= { settings 3 }
|
||||
|
||||
humHighInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Humidity Limit High (value*10)"
|
||||
::= { settings 4 }
|
||||
|
||||
compValLowInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value Limit Low (value*10)"
|
||||
::= { settings 5 }
|
||||
|
||||
compValHighInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value Limit High (value*10)"
|
||||
::= { settings 6 }
|
||||
|
||||
tempDelayInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..4500)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature alaram delay [sec]"
|
||||
::= { settings 7 }
|
||||
|
||||
humDelayInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..4500)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Humidity alaram delay [sec]"
|
||||
::= { settings 8 }
|
||||
|
||||
compValDelayInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..4500)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value alaram delay [sec]"
|
||||
::= { settings 9 }
|
||||
|
||||
tempHystInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..10000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature hysteresis (value*10)"
|
||||
::= { settings 10 }
|
||||
|
||||
humHystInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..10000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Humidity hysteresis (value*10)"
|
||||
::= { settings 11 }
|
||||
|
||||
compValHystInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..10000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value hysteresis (value*10)"
|
||||
::= { settings 12 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Trap message
|
||||
-----------------------------------------------------------------------
|
||||
messageString OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Message giving more detailed information on alarms"
|
||||
::= { traps 1 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Tables
|
||||
-----------------------------------------------------------------------
|
||||
historyTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF HistoryEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Table of the history values"
|
||||
::= { tables 1 }
|
||||
|
||||
historyEntry OBJECT-TYPE
|
||||
SYNTAX HistoryEntry
|
||||
ACCESS not-accessible
|
||||
STATUS optional
|
||||
DESCRIPTION "History values entries"
|
||||
INDEX { histTemp }
|
||||
::= { historyTable 1 }
|
||||
|
||||
HistoryEntry ::=
|
||||
SEQUENCE {
|
||||
histTemp
|
||||
INTEGER,
|
||||
histHum
|
||||
INTEGER,
|
||||
histCompVal
|
||||
INTEGER
|
||||
}
|
||||
|
||||
histTemp OBJECT-TYPE
|
||||
SYNTAX INTEGER(-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature reading"
|
||||
::= { historyEntry 1 }
|
||||
|
||||
histHum OBJECT-TYPE
|
||||
SYNTAX INTEGER(-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Humidity reading"
|
||||
::= { historyEntry 2 }
|
||||
|
||||
histCompVal OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Computed value reading"
|
||||
::= { historyEntry 3 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Traps definition
|
||||
-----------------------------------------------------------------------
|
||||
|
||||
trapTest TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"Testing trap, testing trap by TSensor software"
|
||||
::= 0
|
||||
|
||||
trapNTPError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"Error on time synchronisation via NTP"
|
||||
::= 1
|
||||
|
||||
trapEmailErrLogin TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - unknown server"
|
||||
::= 2
|
||||
|
||||
trapEmailErrAuth TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - authentication error"
|
||||
::= 3
|
||||
|
||||
trapEmailErrSome TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - error during communication with server, unexpected return code"
|
||||
::= 4
|
||||
|
||||
trapEmailErrSocket TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - socket error, server is not available"
|
||||
::= 5
|
||||
|
||||
trapEmailErrDNS TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - DNS error"
|
||||
::= 6
|
||||
|
||||
trapSOAPErrFile TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - file SOAP not found"
|
||||
::= 7
|
||||
|
||||
trapSOAPErrDNS TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - DNS error"
|
||||
::= 8
|
||||
|
||||
trapSOAPErrSocket TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - socket error, server is not available"
|
||||
::= 9
|
||||
|
||||
trapSOAPErrDelivery TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - delivery error, wrong return code from server"
|
||||
::= 10
|
||||
|
||||
trapTempHighAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for high alarm on temperature"
|
||||
::= 11
|
||||
|
||||
trapHumHighAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, hum, humAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for high alarm on relative humidity"
|
||||
::= 12
|
||||
|
||||
trapCompValHighAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for high alarm on computed value"
|
||||
::= 13
|
||||
|
||||
trapTempLowAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for low alarm on temperature"
|
||||
::= 21
|
||||
|
||||
trapHumLowAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, hum, humAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for low alarm on relative humidity"
|
||||
::= 22
|
||||
|
||||
trapCompValLowAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for low alarm on computed value"
|
||||
::= 23
|
||||
|
||||
trapTempClrAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for clearing alarm on temperature"
|
||||
::= 31
|
||||
|
||||
trapHumClrAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, hum, humAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for clearing alarm on relative humidity"
|
||||
::= 32
|
||||
|
||||
trapCompValClrAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for clearing alarm on computed value"
|
||||
::= 33
|
||||
|
||||
trapTempError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for error on temperature"
|
||||
::= 41
|
||||
|
||||
trapHumError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, hum, humAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for error on relative humidity"
|
||||
::= 42
|
||||
|
||||
trapCompValError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for error on computed value"
|
||||
::= 43
|
||||
|
||||
|
||||
END
|