							@@ -0,0 +1,635 @@
 | 
			
		||||
--	POSEIDON-MIB 2.06
 | 
			
		||||
--		History:
 | 
			
		||||
--	2.07	7. 10.2009 Marek Koci    - sensorUnitString added, traps renamed
 | 
			
		||||
--	2.06	10. 9.2009 Marek Koci    - universal 1-wire sensor supported
 | 
			
		||||
--	2.05	11. 9.2008 Marek Koci    - new sensor units added
 | 
			
		||||
--	2.04	14. 9.2007 Dusan Ferbas  - outMode added, node rename to reflect new behaviour for outputs
 | 
			
		||||
--	2.03	20. 4.2007 Dusan Ferbas  - inpAlarmState added, also to inpChange trap
 | 
			
		||||
--	2.02	 5. 9.2006 Rosta Hlebak  - unit type and sensor ID, temp -> sens, trap variable list changed
 | 
			
		||||
--	2.01	18. 4.2005 Jiri Sindelar - enterprise changed from 17739 (Embedded Technologies s.r.o.) to 21796 (HW group s.r.o)
 | 
			
		||||
--					 - output name & type added
 | 
			
		||||
--	1.05	 5. 5.2004 Dusan Ferbas  - MIB name changed to Poseidon, input and output variables into tables, their names settable
 | 
			
		||||
--	1.04	 2. 1.2004 Dusan Ferbas  - alarm table added
 | 
			
		||||
--	1.03	21.11.2003 Dusan Ferbas  - Modified
 | 
			
		||||
--	1.01	 5.11.2003 Dusan Ferbas  - Created
 | 
			
		||||
--
 | 
			
		||||
--
 | 
			
		||||
--
 | 
			
		||||
--  This is a MIB file for Poseidon product family - environment sensors & digital I/O over IP via XML, SNMP, Modbus/TCP 
 | 
			
		||||
--  Availabe sensors: Temperature, Humidity, Voltage, Current, Power comsuption (110/230V) Industrial standards 
 | 
			
		||||
--
 | 
			
		||||
--  ---------------------  Poseidon Family ----------------------
 | 
			
		||||
--
 | 
			
		||||
--  Poseidon model 3262:     6 sensors
 | 
			
		||||
--  Poseidon model 3265:     5 sensors,  GSM
 | 
			
		||||
--  Poseidon model 3266:     3 sensors,  4 Inputs
 | 
			
		||||
--  Poseidon model 3268:     4 sensors,  4 Inputs, 2 Outputs
 | 
			
		||||
--  Poseidon model 1250:    42 sensors,  3 Inputs, 2 Outputs, GSM
 | 
			
		||||
--  Poseidon model 2250:    42 sensors,  3 Inputs, 2 Outputs, GSM
 | 
			
		||||
--  Poseidon model 2261:    42 sensors,  3 Inputs, 2 Outputs
 | 
			
		||||
--  Poseidon model 3468:     4 sensors,  4 Inputs, 2 Outputs
 | 
			
		||||
--  Poseidon model Sitemon: 12 sensors, 16 Inputs, 4 Outputs
 | 
			
		||||
--  Poseidon model 4001:    16 sensors,  8 Inputs, 4 Outputs, GSM
 | 
			
		||||
--  Poseidon model 4002:    16 sensors,  6 Inputs, 2 Outputs, GSM
 | 
			
		||||
 | 
			
		||||
POSEIDON-MIB DEFINITIONS ::= BEGIN
 | 
			
		||||
IMPORTS
 | 
			
		||||
	OBJECT-TYPE
 | 
			
		||||
		FROM RFC-1212
 | 
			
		||||
	Gauge, enterprises
 | 
			
		||||
		FROM RFC1155-SMI
 | 
			
		||||
	DisplayString, sysName
 | 
			
		||||
		FROM RFC1213-MIB;
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
--
 | 
			
		||||
-- Type Definitions
 | 
			
		||||
--
 | 
			
		||||
 | 
			
		||||
PositiveInteger ::= INTEGER (1..2147483647)	-- 0x7FFF FFFF
 | 
			
		||||
 | 
			
		||||
OnOff ::= INTEGER {
 | 
			
		||||
		off (0),
 | 
			
		||||
		on (1)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
OutputType ::= INTEGER {
 | 
			
		||||
		onOff (0),
 | 
			
		||||
		rts (1),
 | 
			
		||||
		dtr (2)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
OutputMode ::= INTEGER {
 | 
			
		||||
		manual (0),
 | 
			
		||||
		autoAlarm (1),
 | 
			
		||||
		autoTriggerEq (2),
 | 
			
		||||
		autoTriggerHi (3),
 | 
			
		||||
		autoTriggerLo (4)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
UnitType ::= INTEGER {
 | 
			
		||||
		celsius (0),
 | 
			
		||||
		fahrenheit (1),
 | 
			
		||||
		kelvin (2),
 | 
			
		||||
		percent(3),
 | 
			
		||||
		volt (4),
 | 
			
		||||
		miliAmper (5),
 | 
			
		||||
		noUnit (6),
 | 
			
		||||
		pulse (7),
 | 
			
		||||
		switch (8),
 | 
			
		||||
		dewPoint (9),
 | 
			
		||||
		absoluteHumidity (10),
 | 
			
		||||
		pressure (11),
 | 
			
		||||
		universal (12)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
InputAlarmSetup ::= INTEGER {
 | 
			
		||||
		inactive (0),
 | 
			
		||||
		activeOff (1),
 | 
			
		||||
		activeOn (2)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
InputAlarmState ::= INTEGER {
 | 
			
		||||
		normal (0),
 | 
			
		||||
		alarm (1)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
SensorState ::= INTEGER {
 | 
			
		||||
		invalid (0),
 | 
			
		||||
		normal (1),
 | 
			
		||||
		alarmstate (2),
 | 
			
		||||
		alarm (3)
 | 
			
		||||
	}
 | 
			
		||||
 | 
			
		||||
SensorID ::= INTEGER (0..65535)
 | 
			
		||||
IOName ::= DisplayString (SIZE (0..20))
 | 
			
		||||
SensorName ::= DisplayString (SIZE (0..15))
 | 
			
		||||
 | 
			
		||||
SensorValue ::= INTEGER
 | 
			
		||||
SensorString ::= DisplayString (SIZE (0..10))
 | 
			
		||||
SensorUnitString ::= DisplayString (SIZE (0..4))
 | 
			
		||||
 | 
			
		||||
SensorFlags ::= INTEGER	-- will hold info that this sensor has alarm (trap) enabled
 | 
			
		||||
			-- and/or sets output pin (thermostat functionality)
 | 
			
		||||
 | 
			
		||||
TimeStamp ::= TimeTicks
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
--
 | 
			
		||||
-- Node Definitions
 | 
			
		||||
--
 | 
			
		||||
 | 
			
		||||
hwgroup		OBJECT IDENTIFIER ::= { enterprises 21796 }
 | 
			
		||||
 | 
			
		||||
charonII	OBJECT IDENTIFIER ::= { hwgroup 3 }
 | 
			
		||||
poseidon	OBJECT IDENTIFIER ::= { charonII 3 }
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
-- Application Nodes
 | 
			
		||||
 | 
			
		||||
info	OBJECT IDENTIFIER ::= { poseidon 70 }
 | 
			
		||||
setup	OBJECT IDENTIFIER ::= { poseidon 99 }
 | 
			
		||||
 | 
			
		||||
inpTable OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SEQUENCE OF InpEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A list of binary input entries."
 | 
			
		||||
	::= { poseidon 1 }
 | 
			
		||||
 | 
			
		||||
inpEntry OBJECT-TYPE
 | 
			
		||||
	SYNTAX	InpEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An entry containing information applicable
 | 
			
		||||
		to a particular binary input."
 | 
			
		||||
	INDEX { inpIndex }
 | 
			
		||||
	::= { inpTable 1 }
 | 
			
		||||
 | 
			
		||||
InpEntry ::= SEQUENCE {
 | 
			
		||||
	inpIndex	PositiveInteger,
 | 
			
		||||
	inpValue	OnOff,
 | 
			
		||||
	inpName		IOName,
 | 
			
		||||
	inpAlarmSetup	InputAlarmSetup,
 | 
			
		||||
	inpAlarmState	InputAlarmState
 | 
			
		||||
}
 | 
			
		||||
 | 
			
		||||
inpIndex OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary input index."
 | 
			
		||||
	::= { inpEntry 1 }
 | 
			
		||||
 | 
			
		||||
inpValue OBJECT-TYPE
 | 
			
		||||
	SYNTAX	OnOff
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary input value."
 | 
			
		||||
	::= { inpEntry 2 }
 | 
			
		||||
 | 
			
		||||
inpName OBJECT-TYPE
 | 
			
		||||
	SYNTAX	IOName
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary input name."
 | 
			
		||||
	::= { inpEntry 3 }
 | 
			
		||||
 | 
			
		||||
inpAlarmSetup OBJECT-TYPE
 | 
			
		||||
	SYNTAX	InputAlarmSetup
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"You can enable alarm for this binary input.
 | 
			
		||||
		Alarm can be inactive or active for On/Off state."
 | 
			
		||||
	::= { inpEntry 4 }
 | 
			
		||||
 | 
			
		||||
inpAlarmState OBJECT-TYPE
 | 
			
		||||
	SYNTAX	InputAlarmState
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary input alarm state."
 | 
			
		||||
	::= { inpEntry 5 }
 | 
			
		||||
 | 
			
		||||
--
 | 
			
		||||
outTable OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SEQUENCE OF OutEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A list of binary output entries."
 | 
			
		||||
	::= { poseidon 2 }
 | 
			
		||||
 | 
			
		||||
outEntry OBJECT-TYPE
 | 
			
		||||
	SYNTAX	OutEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An entry containing information applicable
 | 
			
		||||
		to a particular binary output."
 | 
			
		||||
	INDEX { outIndex }
 | 
			
		||||
	::= { outTable 1 }
 | 
			
		||||
 | 
			
		||||
OutEntry ::= SEQUENCE {
 | 
			
		||||
	outIndex	PositiveInteger,
 | 
			
		||||
	outValue	OnOff,
 | 
			
		||||
	outName		IOName,
 | 
			
		||||
	outType		OutputType,
 | 
			
		||||
	outMode		OutputMode
 | 
			
		||||
}
 | 
			
		||||
 | 
			
		||||
outIndex OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary output index."
 | 
			
		||||
	::= { outEntry 1 }
 | 
			
		||||
 | 
			
		||||
outValue OBJECT-TYPE
 | 
			
		||||
	SYNTAX	OnOff
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary output value. 0 off(open), 1 on(close)"
 | 
			
		||||
	::= { outEntry 2 }
 | 
			
		||||
 | 
			
		||||
outName OBJECT-TYPE
 | 
			
		||||
	SYNTAX	IOName
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary output name."
 | 
			
		||||
	::= { outEntry 3 }
 | 
			
		||||
 | 
			
		||||
outType OBJECT-TYPE
 | 
			
		||||
	SYNTAX	OutputType
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary output type. 0 relay (off, on), 1 rts (-10,+10V), 2 dtr (0,10V)"
 | 
			
		||||
	::= { outEntry 4 }
 | 
			
		||||
 | 
			
		||||
outMode OBJECT-TYPE
 | 
			
		||||
	SYNTAX	OutputMode
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The binary output mode. 0 manual, 1 autoAlarm,
 | 
			
		||||
		2 autoTriggerEq, 3 autoTriggerHi, 4 autoTriggerLo"
 | 
			
		||||
	::= { outEntry 5 }
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
-- Table has to be last in a branch to satisfy snmp walk engine implementation
 | 
			
		||||
sensTable OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SEQUENCE OF SensEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A list of sensor table entries. The number
 | 
			
		||||
		of entries corresponds with number of detected sensors."
 | 
			
		||||
	::= { poseidon 3 }
 | 
			
		||||
 | 
			
		||||
sensEntry OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An entry containing information applicable to a
 | 
			
		||||
		particular sensor."
 | 
			
		||||
	INDEX { sensIndex }
 | 
			
		||||
	::= { sensTable 1 }
 | 
			
		||||
 | 
			
		||||
SensEntry ::= SEQUENCE {
 | 
			
		||||
	sensIndex		PositiveInteger,
 | 
			
		||||
	sensName		SensorName,
 | 
			
		||||
	sensState		SensorState,
 | 
			
		||||
	sensString		SensorString,
 | 
			
		||||
	sensValue		SensorValue,
 | 
			
		||||
	sensValueRaw		SensorValue,
 | 
			
		||||
	sensID			SensorID,
 | 
			
		||||
	sensUnit		UnitType,
 | 
			
		||||
	sensUnitString		SensorUnitString
 | 
			
		||||
}
 | 
			
		||||
 | 
			
		||||
sensIndex OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor index."
 | 
			
		||||
	::= { sensEntry 1 }
 | 
			
		||||
 | 
			
		||||
sensName OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorName
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor name."
 | 
			
		||||
	::= { sensEntry 2 }
 | 
			
		||||
 | 
			
		||||
sensState OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorState
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor state."
 | 
			
		||||
	::= { sensEntry 4 }
 | 
			
		||||
 | 
			
		||||
sensString OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorString
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The string representation of sensor value."
 | 
			
		||||
	::= { sensEntry 5 }
 | 
			
		||||
 | 
			
		||||
sensValue OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorValue
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The integer (decimal * 10) representation
 | 
			
		||||
		of sensor value."
 | 
			
		||||
	::= { sensEntry 6 }
 | 
			
		||||
 | 
			
		||||
sensValueRaw OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorValue
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The original raw value of sensor
 | 
			
		||||
		(it differs for each sensor type, especially
 | 
			
		||||
		 1-Wire sensors have different precisions)."
 | 
			
		||||
	::= { sensEntry 7 }
 | 
			
		||||
 | 
			
		||||
sensID OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorID
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor ID."
 | 
			
		||||
	::= { sensEntry 8 }
 | 
			
		||||
 | 
			
		||||
sensUnit OBJECT-TYPE
 | 
			
		||||
	SYNTAX	UnitType
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor unit."
 | 
			
		||||
	::= { sensEntry 9 }
 | 
			
		||||
 | 
			
		||||
sensUnitString OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorUnitString
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The string representation of sensor unit."
 | 
			
		||||
	::= { sensEntry 10 }
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
-- The Alarm group.
 | 
			
		||||
 | 
			
		||||
tsAlarm		OBJECT IDENTIFIER ::= { poseidon 50 }
 | 
			
		||||
 | 
			
		||||
tsAlarmsPresent OBJECT-TYPE
 | 
			
		||||
	SYNTAX	Gauge32
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The present number of active alarm conditions."
 | 
			
		||||
	::= { tsAlarm 1 }
 | 
			
		||||
 | 
			
		||||
tsAlarmTable OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SEQUENCE OF TsAlarmEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A list of alarm table entries.  The table contains
 | 
			
		||||
		zero, one, or many rows at any moment, depending upon
 | 
			
		||||
		the number of alarm conditions in effect.  The table
 | 
			
		||||
		is initially empty at agent startup.  The agent
 | 
			
		||||
		creates a row in the table each time a condition is
 | 
			
		||||
		detected and deletes that row when that condition no
 | 
			
		||||
		longer pertains.  The agent creates the first row with
 | 
			
		||||
		tsAlarmId equal to 1, and increments the value of
 | 
			
		||||
		tsAlarmId each time a new row is created, wrapping to
 | 
			
		||||
		the first free value greater than or equal to 1 when
 | 
			
		||||
		the maximum value of tsAlarmId would otherwise be
 | 
			
		||||
		exceeded.  Consequently, after multiple operations,
 | 
			
		||||
		the table may become sparse, e.g., containing entries
 | 
			
		||||
		for rows 95, 100, 101, and 203 and the entries should
 | 
			
		||||
		not be assumed to be in chronological order because
 | 
			
		||||
		tsAlarmId might have wrapped.
 | 
			
		||||
 | 
			
		||||
		The number of rows in the table at any given time is
 | 
			
		||||
		reflected by the value of tsAlarmsPresent."
 | 
			
		||||
	::= { tsAlarm 2 }
 | 
			
		||||
 | 
			
		||||
tsAlarmEntry OBJECT-TYPE
 | 
			
		||||
	SYNTAX	TsAlarmEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An entry containing information applicable
 | 
			
		||||
		to a particular alarm."
 | 
			
		||||
	INDEX { tsAlarmIdx }
 | 
			
		||||
	::= { tsAlarmTable 1 }
 | 
			
		||||
 | 
			
		||||
TsAlarmEntry ::= SEQUENCE {
 | 
			
		||||
	tsAlarmIdx	PositiveInteger,
 | 
			
		||||
	tsAlarmId	PositiveInteger,
 | 
			
		||||
	tsAlarmDescr	INTEGER,
 | 
			
		||||
	tsAlarmSensName SensorName,
 | 
			
		||||
	tsAlarmTime	TimeStamp
 | 
			
		||||
}
 | 
			
		||||
 | 
			
		||||
tsAlarmIdx OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An index to alarm table."
 | 
			
		||||
	::= { tsAlarmEntry 1 }
 | 
			
		||||
 | 
			
		||||
tsAlarmId OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	read-only	-- (used in trap variables)
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A unique identifier for an alarm condition.
 | 
			
		||||
		This value must remain constant."
 | 
			
		||||
	::= { tsAlarmEntry 2 }
 | 
			
		||||
 | 
			
		||||
tsAlarmDescr OBJECT-TYPE
 | 
			
		||||
	SYNTAX	 INTEGER {
 | 
			
		||||
		inputStateAlarm(1),
 | 
			
		||||
		temperatureOutOfRange(2)
 | 
			
		||||
	}
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"Description of the alarm condition."
 | 
			
		||||
	::= { tsAlarmEntry 3 }
 | 
			
		||||
 | 
			
		||||
-- inputStateAlarm(1)
 | 
			
		||||
-- Binary input reached a state which meets its alarm setting.
 | 
			
		||||
-- This means that no such alarm can happenn if alarm is set to no.
 | 
			
		||||
 | 
			
		||||
-- temperatureOutOfRange(2)
 | 
			
		||||
-- Sensor value is out of limits.
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
tsAlarmSensName OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorName
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"Name of sensor with alarm condition."
 | 
			
		||||
	::= { tsAlarmEntry 4 }
 | 
			
		||||
 | 
			
		||||
tsAlarmTime OBJECT-TYPE
 | 
			
		||||
	SYNTAX	TimeStamp
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The value of sysUpTime when the alarm condition was
 | 
			
		||||
		detected.  If the alarm condition was detected
 | 
			
		||||
		at the time of agent startup and presumably existed
 | 
			
		||||
		before agent startup, the value of tsAlarmTime shall equal 0."
 | 
			
		||||
	::= { tsAlarmEntry 5 }
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
-- Application Info
 | 
			
		||||
 | 
			
		||||
infoAddressMAC OBJECT-TYPE
 | 
			
		||||
	SYNTAX	DisplayString (SIZE (0..17))
 | 
			
		||||
	ACCESS	read-only
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"MAC address in text form.
 | 
			
		||||
		It is here to distinguish devices in trap messages."
 | 
			
		||||
	::= { info 1 }
 | 
			
		||||
 | 
			
		||||
-- Application Setup
 | 
			
		||||
 | 
			
		||||
sensSetup	OBJECT IDENTIFIER ::= { setup 1 }
 | 
			
		||||
 | 
			
		||||
unitType OBJECT-TYPE
 | 
			
		||||
	SYNTAX	UnitType
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"Units for displayed values.
 | 
			
		||||
		All setup values are fixed in Celsius"
 | 
			
		||||
	::= { sensSetup 1 }
 | 
			
		||||
 | 
			
		||||
sensSetupTable OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SEQUENCE OF SensSetupEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"A list of sensor table setup entries. The number
 | 
			
		||||
		of entries corresponds with number of detected sensors."
 | 
			
		||||
	::= { sensSetup 2 }
 | 
			
		||||
 | 
			
		||||
sensSetupEntry OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensSetupEntry
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"An entry containing setup information
 | 
			
		||||
		for a particular sensor."
 | 
			
		||||
	INDEX { sensSetupIndex }
 | 
			
		||||
	::= { sensSetupTable 1 }
 | 
			
		||||
 | 
			
		||||
SensSetupEntry ::= SEQUENCE {
 | 
			
		||||
	sensSetupIndex	PositiveInteger,
 | 
			
		||||
	sensSetupName	SensorName,
 | 
			
		||||
	sensFlags	SensorFlags,
 | 
			
		||||
	sensLimitMin	SensorValue,
 | 
			
		||||
	sensLimitMax	SensorValue,
 | 
			
		||||
	sensHysteresis	SensorValue
 | 
			
		||||
}
 | 
			
		||||
 | 
			
		||||
sensSetupIndex OBJECT-TYPE
 | 
			
		||||
	SYNTAX	PositiveInteger
 | 
			
		||||
	ACCESS	not-accessible
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor setup table index."
 | 
			
		||||
	::= { sensSetupEntry 1 }
 | 
			
		||||
 | 
			
		||||
sensSetupName OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorName
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor name."
 | 
			
		||||
	::= { sensSetupEntry 2 }
 | 
			
		||||
 | 
			
		||||
sensFlags OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorFlags
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The behaviour of sensor
 | 
			
		||||
		- 0x01: range or level detection
 | 
			
		||||
		- 0x02: enable trap sending
 | 
			
		||||
		-- 0x04: output set (thermostat)
 | 
			
		||||
		- 0x08: sensor enabled
 | 
			
		||||
		- 0x10: enable SMS sending
 | 
			
		||||
		- 0x20: enable email sending."
 | 
			
		||||
 | 
			
		||||
	::= { sensSetupEntry 5 }
 | 
			
		||||
 | 
			
		||||
sensLimitMin OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorValue
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor low limit."
 | 
			
		||||
	::= { sensSetupEntry 6 }
 | 
			
		||||
 | 
			
		||||
sensLimitMax OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorValue
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor high limit."
 | 
			
		||||
	::= { sensSetupEntry 7 }
 | 
			
		||||
 | 
			
		||||
sensHysteresis OBJECT-TYPE
 | 
			
		||||
	SYNTAX	SensorValue
 | 
			
		||||
	ACCESS	read-write
 | 
			
		||||
	STATUS	current
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"The sensor hysteresis."
 | 
			
		||||
	::= { sensSetupEntry 8 }
 | 
			
		||||
 | 
			
		||||
-- Trap Definitions ------------------------------------------------------------
 | 
			
		||||
 | 
			
		||||
inpAlarmStateChanged TRAP-TYPE
 | 
			
		||||
	ENTERPRISE	poseidon
 | 
			
		||||
	VARIABLES	{ sysName, infoAddressMAC, inpName, inpValue, inpAlarmState }
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"Input state entered/left alarm condition.
 | 
			
		||||
		This trap always follows tsTrapAlarmStart/tsTrapAlarmEnd."
 | 
			
		||||
	::= 1
 | 
			
		||||
 | 
			
		||||
sensAlarmStateChanged TRAP-TYPE
 | 
			
		||||
	ENTERPRISE	poseidon
 | 
			
		||||
	VARIABLES	{ sysName, infoAddressMAC, sensName, sensID, sensState, sensValue, sensUnit }
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"Nth sensor state entered/left alarm condition.
 | 
			
		||||
		This trap always follows tsTrapAlarmStart/tsTrapAlarmEnd."
 | 
			
		||||
	::= 2
 | 
			
		||||
 | 
			
		||||
tsTrapAlarmStart TRAP-TYPE
 | 
			
		||||
	ENTERPRISE	poseidon
 | 
			
		||||
	VARIABLES	{ sysName, infoAddressMAC, tsAlarmId, tsAlarmDescr }
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"This trap is sent each time an alarm is inserted
 | 
			
		||||
		into to the alarm table.  It is sent on the insertion
 | 
			
		||||
		of all alarms except for powerFailure."
 | 
			
		||||
	::= 3
 | 
			
		||||
 | 
			
		||||
tsTrapAlarmEnd TRAP-TYPE
 | 
			
		||||
	ENTERPRISE	poseidon
 | 
			
		||||
	VARIABLES	{ sysName, infoAddressMAC, tsAlarmId, tsAlarmDescr }
 | 
			
		||||
	DESCRIPTION
 | 
			
		||||
		"This trap is sent each time an alarm is removed
 | 
			
		||||
		from the alarm table.  It is sent on the removal
 | 
			
		||||
		of all alarms."
 | 
			
		||||
	::= 4
 | 
			
		||||
 | 
			
		||||
 | 
			
		||||
END
 | 
			
		||||
 | 
			
		||||