Initial commit

This commit is contained in:
David Leutgeb
2023-12-05 12:25:34 +01:00
commit 98a672123c
4378 changed files with 8817503 additions and 0 deletions

View File

@ -0,0 +1,85 @@
-- ICT MIB file for ICT Digital Series.
--
-- Date Version
-- =============================
-- 10/4/12 v1.00
--
-- Renamed from ICT-MIB to ICT-DIGITAL-SERIES-MIB
ICT-DIGITAL-SERIES-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
digitalSeries OBJECT IDENTIFIER ::= { ictPower 11 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Model Number"
::= { digitalSeries 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device Name"
::= { digitalSeries 2 }
deviceHardware OBJECT-TYPE
SYNTAX INTEGER (0..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Hardware Version"
::= { digitalSeries 3 }
deviceFirmware OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Firmware Version"
::= { digitalSeries 4 }
deviceMacAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "MAC Address"
::= { digitalSeries 5 }
inputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Input Voltage (VAC)"
::= { digitalSeries 6 }
outputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Voltage (VDC)"
::= { digitalSeries 7 }
outputCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "System Current (Amps)"
::= { digitalSeries 8 }
outputEnable OBJECT-TYPE
SYNTAX INTEGER { ENABLED(1), DISABLED(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Enable Status (a value of 1 indicates Output is Enabled, and a value of 2 indicates Output is Disabled)"
::= { digitalSeries 9 }
END

View File

@ -0,0 +1,321 @@
-- MIB file for ICT Distribution Panel Series
--
-- Date Version
-- =============================
-- 9/5/13 1.01
--
-- Renamed from ICT-MIB to ICT-DISTRIBUTION-PANEL-MIB
ICT-DISTRIBUTION-PANEL-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
distPanel OBJECT IDENTIFIER ::= { ictPower 10 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Model Number"
::= { distPanel 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Site Name"
::= { distPanel 2 }
deviceHardware OBJECT-TYPE
SYNTAX INTEGER (0..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Hardware Version"
::= { distPanel 3 }
deviceFirmware OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Firmware Version"
::= { distPanel 4 }
deviceMacAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "MAC Address"
::= { distPanel 5 }
systemVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "System Voltage (Volts)"
::= { distPanel 6 }
systemCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "System Current (Amps)"
::= { distPanel 7 }
outputTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Output Table"
::= { distPanel 8 }
outputEntry OBJECT-TYPE
SYNTAX OutputEntry
ACCESS not-accessible
STATUS mandatory
INDEX { outputNumber }
::= { outputTable 1 }
OutputEntry ::=
SEQUENCE {
outputNumber INTEGER,
outputName DisplayString,
outputCurrent DisplayString,
outputFuseStatus INTEGER,
outputEnable INTEGER
}
outputNumber OBJECT-TYPE
SYNTAX INTEGER (0..11)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Number"
::= { outputEntry 1 }
outputName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Label"
::= { outputEntry 2 }
outputCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Current (Amps)"
::= { outputEntry 3 }
outputFuseStatus OBJECT-TYPE
SYNTAX INTEGER { OK(1), OPEN(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Fuse Status ('1' indicates Fuse is OK, and '2' indicates Fuse is OPEN)"
::= { outputEntry 4 }
outputEnable OBJECT-TYPE
SYNTAX INTEGER { ENABLED(1), DISABLED(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Output Relay Enable ('1' indicates the Output is ENABLED, and '2' indicates the Output is DISABLED)"
::= { outputEntry 5 }
alarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Alarm Input Table"
::= { distPanel 9 }
alarmEntry OBJECT-TYPE
SYNTAX AlarmEntry
ACCESS not-accessible
STATUS mandatory
INDEX { alarmNumber }
::= { alarmTable 1 }
AlarmEntry ::=
SEQUENCE {
alarmNumber INTEGER,
alarmName DisplayString,
alarmStatus INTEGER
}
alarmNumber OBJECT-TYPE
SYNTAX INTEGER (0..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Number"
::= { alarmEntry 1 }
alarmName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Name"
::= { alarmEntry 2 }
alarmStatus OBJECT-TYPE
SYNTAX INTEGER { INACTIVE(1), READY(2), ALARM(3) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)"
::= { alarmEntry 3 }
busTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Output Table"
::= { distPanel 10 }
busEntry OBJECT-TYPE
SYNTAX BusEntry
ACCESS not-accessible
STATUS mandatory
INDEX { busNumber }
::= { busTable 1 }
BusEntry ::=
SEQUENCE {
busNumber INTEGER,
busName DisplayString,
busVoltage DisplayString,
busCurrent DisplayString
}
busNumber OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Bus Number"
::= { busEntry 1 }
busName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Bus Name"
::= { busEntry 2 }
busVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Bus Voltage (Volts)"
::= { busEntry 3 }
busCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Total Bus Current (Amps)"
::= { busEntry 4 }
--
-- Trap definitions:
--
sysUndervoltageAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Undervoltage Alarm is triggered"
::= 101
sysOvervoltageAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Overvoltage Alarm is triggered"
::= 102
sysOvercurrentAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Overcurrent Alarm is triggered"
::= 103
fuseAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Fuse Alarm is triggered"
::= 104
undercurrentAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Undercurrent Alarm is triggered"
::= 105
overcurrentAlarmTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Overcurrent Alarm is triggered"
::= 106
loadshedTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when Load-Shedding is activated on an Output"
::= 107
alarmInputTrap TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is activated"
::= 108
sysUndervoltageAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Undervoltage Alarm is cleared"
::= 111
sysOvervoltageAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Overvoltage Alarm is cleared"
::= 112
sysOvercurrentAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { busNumber }
DESCRIPTION "Trap generated when a System/Bus Overcurrent Alarm is cleared"
::= 113
fuseAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Fuse Alarm is cleared"
::= 114
undercurrentAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Undercurrent Alarm is cleared"
::= 115
overcurrentAlarmClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output Overcurrent Alarm is cleared"
::= 116
loadshedClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { outputNumber }
DESCRIPTION "Trap generated when an Output has recovered from a Load-Shedding condition"
::= 117
alarmInputClear TRAP-TYPE
ENTERPRISE distPanel
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is cleared"
::= 118
END

View File

@ -0,0 +1,313 @@
-- ICT MIB file for ICT Modular Power System.
--
-- Date Version
-- =============================
-- 1/5/18 v1.01
--
ICT-MODULAR-POWER-SYSTEM-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
powerSystem OBJECT IDENTIFIER ::= { ictPower 13 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Model Number"
::= { powerSystem 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device Name"
::= { powerSystem 2 }
deviceHardware OBJECT-TYPE
SYNTAX INTEGER (0..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Hardware Version"
::= { powerSystem 3 }
deviceFirmware OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Firmware Version"
::= { powerSystem 4 }
deviceMacAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "MAC Address"
::= { powerSystem 5 }
inputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Input Voltage (VAC)"
::= { powerSystem 6 }
outputVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Output Voltage (VDC)"
::= { powerSystem 7 }
outputCurrent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Total System Current (Amps)"
::= { powerSystem 8 }
outputEnable OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Output Enable Status (a value of '1' indicates Output is Enabled, and a value of '2' indicates Output is Disabled. Output cannot be disabled during an AC Failure)"
::= { powerSystem 9 }
moduleTable OBJECT-TYPE
SYNTAX SEQUENCE OF ModuleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Module Table"
::= { powerSystem 10 }
moduleEntry OBJECT-TYPE
SYNTAX ModuleEntry
ACCESS not-accessible
STATUS mandatory
INDEX { moduleNumber }
::= { moduleTable 1 }
ModuleEntry ::=
SEQUENCE {
moduleNumber INTEGER,
moduleStatus INTEGER,
moduleType INTEGER,
moduleVoltage DisplayString,
moduleCurrentA DisplayString,
moduleCurrentB DisplayString,
moduleCurrentC DisplayString,
moduleCurrentD DisplayString,
moduleControlA INTEGER,
moduleControlB INTEGER,
moduleControlC INTEGER,
moduleControlD INTEGER
}
moduleNumber OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Number"
::= { moduleEntry 1 }
moduleStatus OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), ok(2), alarm(3) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Status"
::= { moduleEntry 2 }
moduleType OBJECT-TYPE
SYNTAX INTEGER { notInstalled(1), power(2), battery(3), distribution(4) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Type ('1' indicates Module is NOT INSTALLED,'2' indicates POWER Module,'3' indicates BATTERY Module, and '4' indicates DISTRIBUTION Module)"
::= { moduleEntry 3 }
moduleVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Module Voltage (VDC)"
::= { moduleEntry 4 }
moduleCurrentA OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 1 Current (Amps)"
::= { moduleEntry 5 }
moduleCurrentB OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 2 Current (Amps)"
::= { moduleEntry 6 }
moduleCurrentC OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 3 Current (Amps)"
::= { moduleEntry 7 }
moduleCurrentD OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Channel 4 Current (Amps)"
::= { moduleEntry 8 }
moduleControlA OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 1 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 9 }
moduleControlB OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 2 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 10 }
moduleControlC OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 3 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 11 }
moduleControlD OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Channel 4 Control (a value of '1' indicates Channel is Enabled, and a value of '2' indicates Channel is Disabled)"
::= { moduleEntry 12 }
alarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Alarm Input Table"
::= { powerSystem 11 }
alarmEntry OBJECT-TYPE
SYNTAX AlarmEntry
ACCESS not-accessible
STATUS mandatory
INDEX { alarmNumber }
::= { alarmTable 1 }
AlarmEntry ::=
SEQUENCE {
alarmNumber INTEGER,
alarmName DisplayString,
alarmStatus INTEGER
}
alarmNumber OBJECT-TYPE
SYNTAX INTEGER (1..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Number"
::= { alarmEntry 1 }
alarmName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Name"
::= { alarmEntry 2 }
alarmStatus OBJECT-TYPE
SYNTAX INTEGER { inactive(1), ready(2), alarm(3) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)"
::= { alarmEntry 3 }
--
-- Trap definitions:
--
moduleAlarmTrap TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { moduleNumber }
DESCRIPTION "Trap generated when a Module Alarm is triggered"
::= 101
alarmInputTrap TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is activated"
::= 102
acFailAlarmTrap TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the AC Failure Alarm is triggered"
::= 103
sysCurrentLimitTrap TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the System Current Limit Alarm is triggered"
::= 104
moduleAlarmClear TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { moduleNumber }
DESCRIPTION "Trap generated when a Module Alarm is cleared"
::= 111
alarmInputClear TRAP-TYPE
ENTERPRISE powerSystem
VARIABLES { alarmNumber }
DESCRIPTION "Trap generated when an Alarm Input is cleared"
::= 112
acFailAlarmClear TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the AC Failure Alarm is cleared"
::= 113
sysCurrentLimitClear TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when the System Current Limit Alarm is cleared"
::= 114
batteryTestStart TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test is started"
::= 121
batteryTestComplete TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test completes successfully"
::= 122
batteryTestFail TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Discharge Test fails"
::= 123
batteryEqualiseStart TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Equalise Charge is started"
::= 124
batteryEqualiseComplete TRAP-TYPE
ENTERPRISE powerSystem
DESCRIPTION "Trap generated when a Battery Equalise Charge completes"
::= 125
END

View File

@ -0,0 +1,172 @@
-- MIB file for ICT Sine Wave Inverter.
--
-- Date Version
-- =============================
-- 3/7/18 1.01
--
ICT-SINE-WAVE-INVERTER-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
inverter OBJECT IDENTIFIER ::= { ictPower 12 }
deviceModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Model Number"
::= { inverter 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Site Name"
::= { inverter 2 }
deviceHardware OBJECT-TYPE
SYNTAX INTEGER (0..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Hardware Version"
::= { inverter 3 }
deviceFirmware OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Firmware Version"
::= { inverter 4 }
deviceMacAddress OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "MAC Address"
::= { inverter 5 }
batteryVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Battery Voltage (VDC)"
::= { inverter 6 }
inverterVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Inverter Output Voltage (VAC)"
::= { inverter 7 }
inverterPower OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION "Inverter Output Power (%)"
::= { inverter 8 }
inverterStatus OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Inverter Output Status ('1' indicates the Inverter Output is ENABLED, and '2' indicates the Inverter Output is DISABLED)"
::= { inverter 9 }
inverterControl OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Inverter Output Control (set to '1' to ENABLE the Inverter Output if no alarms are active, set to '2' to DISABLE the Inverter Output)"
::= { inverter 10 }
transferRelayStatus OBJECT-TYPE
SYNTAX INTEGER { inverter(1), grid(2) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Transfer Relay Status ('1' indicates the Output is connected to the INVERTER, and '2' indicates the Output is connected to the GRID)"
::= { inverter 11 }
--
-- Trap definitions:
--
undervoltageAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Battery Input Undervoltage Alarm is triggered"
::= 101
overvoltageAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Battery Input Overvoltage Alarm is triggered"
::= 102
overtemperatureAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Overtemperature Alarm is triggered"
::= 103
outputFaultAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Inverter Output Fault Alarm is triggered"
::= 104
systemFaultAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the System Fault Alarm is triggered"
::= 105
remoteSwitchAlarmTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Remote Switch accessory is activated"
::= 106
undervoltageAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Battery Input Undervoltage Alarm is cleared"
::= 111
overvoltageAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Battery Input Overvoltage Alarm is cleared"
::= 112
overtemperatureAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Overtemperature Alarm is cleared"
::= 113
outputFaultAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Inverter Output Fault Alarm is cleared"
::= 114
systemFaultAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the System Fault Alarm is cleared"
::= 115
remoteSwitchAlarmClear TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Remote Switch accessory is deactivated"
::= 116
inverterPowerTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Output switches to Inverter (Battery) Power"
::= 121
gridPowerTrap TRAP-TYPE
ENTERPRISE inverter
DESCRIPTION "Trap generated when the Output switches to Grid Power"
::= 122
END