@ -0,0 +1,321 @@
|
||||
-- MIB file for ICT Distribution Panel Series
|
||||
--
|
||||
-- Date Version
|
||||
-- =============================
|
||||
-- 9/5/13 1.01
|
||||
--
|
||||
-- Renamed from ICT-MIB to ICT-DISTRIBUTION-PANEL-MIB
|
||||
|
||||
ICT-DISTRIBUTION-PANEL-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
enterprises, IpAddress FROM RFC1155-SMI
|
||||
DisplayString FROM RFC1213-MIB
|
||||
OBJECT-TYPE FROM RFC-1212
|
||||
TRAP-TYPE FROM RFC-1215;
|
||||
|
||||
ictPower OBJECT IDENTIFIER ::= { enterprises 39145 }
|
||||
|
||||
distPanel OBJECT IDENTIFIER ::= { ictPower 10 }
|
||||
|
||||
deviceModel OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Model Number"
|
||||
::= { distPanel 1 }
|
||||
|
||||
deviceName OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Site Name"
|
||||
::= { distPanel 2 }
|
||||
|
||||
deviceHardware OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..127)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Hardware Version"
|
||||
::= { distPanel 3 }
|
||||
|
||||
deviceFirmware OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Firmware Version"
|
||||
::= { distPanel 4 }
|
||||
|
||||
deviceMacAddress OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "MAC Address"
|
||||
::= { distPanel 5 }
|
||||
|
||||
systemVoltage OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "System Voltage (Volts)"
|
||||
::= { distPanel 6 }
|
||||
|
||||
systemCurrent OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "System Current (Amps)"
|
||||
::= { distPanel 7 }
|
||||
|
||||
outputTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF OutputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Table"
|
||||
::= { distPanel 8 }
|
||||
|
||||
outputEntry OBJECT-TYPE
|
||||
SYNTAX OutputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
INDEX { outputNumber }
|
||||
::= { outputTable 1 }
|
||||
|
||||
OutputEntry ::=
|
||||
SEQUENCE {
|
||||
outputNumber INTEGER,
|
||||
outputName DisplayString,
|
||||
outputCurrent DisplayString,
|
||||
outputFuseStatus INTEGER,
|
||||
outputEnable INTEGER
|
||||
}
|
||||
|
||||
outputNumber OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..11)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Number"
|
||||
::= { outputEntry 1 }
|
||||
|
||||
outputName OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Label"
|
||||
::= { outputEntry 2 }
|
||||
|
||||
outputCurrent OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Current (Amps)"
|
||||
::= { outputEntry 3 }
|
||||
|
||||
outputFuseStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER { OK(1), OPEN(2) }
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Fuse Status ('1' indicates Fuse is OK, and '2' indicates Fuse is OPEN)"
|
||||
::= { outputEntry 4 }
|
||||
|
||||
outputEnable OBJECT-TYPE
|
||||
SYNTAX INTEGER { ENABLED(1), DISABLED(2) }
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Relay Enable ('1' indicates the Output is ENABLED, and '2' indicates the Output is DISABLED)"
|
||||
::= { outputEntry 5 }
|
||||
|
||||
alarmTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF AlarmEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Input Table"
|
||||
::= { distPanel 9 }
|
||||
|
||||
alarmEntry OBJECT-TYPE
|
||||
SYNTAX AlarmEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
INDEX { alarmNumber }
|
||||
::= { alarmTable 1 }
|
||||
|
||||
AlarmEntry ::=
|
||||
SEQUENCE {
|
||||
alarmNumber INTEGER,
|
||||
alarmName DisplayString,
|
||||
alarmStatus INTEGER
|
||||
}
|
||||
|
||||
alarmNumber OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..4)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Input Number"
|
||||
::= { alarmEntry 1 }
|
||||
|
||||
alarmName OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Input Name"
|
||||
::= { alarmEntry 2 }
|
||||
|
||||
alarmStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER { INACTIVE(1), READY(2), ALARM(3) }
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)"
|
||||
::= { alarmEntry 3 }
|
||||
|
||||
busTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF OutputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Output Table"
|
||||
::= { distPanel 10 }
|
||||
|
||||
busEntry OBJECT-TYPE
|
||||
SYNTAX BusEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
INDEX { busNumber }
|
||||
::= { busTable 1 }
|
||||
|
||||
BusEntry ::=
|
||||
SEQUENCE {
|
||||
busNumber INTEGER,
|
||||
busName DisplayString,
|
||||
busVoltage DisplayString,
|
||||
busCurrent DisplayString
|
||||
}
|
||||
|
||||
busNumber OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Bus Number"
|
||||
::= { busEntry 1 }
|
||||
|
||||
busName OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Bus Name"
|
||||
::= { busEntry 2 }
|
||||
|
||||
busVoltage OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Bus Voltage (Volts)"
|
||||
::= { busEntry 3 }
|
||||
|
||||
busCurrent OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Total Bus Current (Amps)"
|
||||
::= { busEntry 4 }
|
||||
|
||||
|
||||
--
|
||||
-- Trap definitions:
|
||||
--
|
||||
|
||||
sysUndervoltageAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Undervoltage Alarm is triggered"
|
||||
::= 101
|
||||
|
||||
sysOvervoltageAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Overvoltage Alarm is triggered"
|
||||
::= 102
|
||||
|
||||
sysOvercurrentAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Overcurrent Alarm is triggered"
|
||||
::= 103
|
||||
|
||||
fuseAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Fuse Alarm is triggered"
|
||||
::= 104
|
||||
|
||||
undercurrentAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Undercurrent Alarm is triggered"
|
||||
::= 105
|
||||
|
||||
overcurrentAlarmTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Overcurrent Alarm is triggered"
|
||||
::= 106
|
||||
|
||||
loadshedTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when Load-Shedding is activated on an Output"
|
||||
::= 107
|
||||
|
||||
alarmInputTrap TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { alarmNumber }
|
||||
DESCRIPTION "Trap generated when an Alarm Input is activated"
|
||||
::= 108
|
||||
|
||||
sysUndervoltageAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Undervoltage Alarm is cleared"
|
||||
::= 111
|
||||
|
||||
sysOvervoltageAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Overvoltage Alarm is cleared"
|
||||
::= 112
|
||||
|
||||
sysOvercurrentAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { busNumber }
|
||||
DESCRIPTION "Trap generated when a System/Bus Overcurrent Alarm is cleared"
|
||||
::= 113
|
||||
|
||||
fuseAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Fuse Alarm is cleared"
|
||||
::= 114
|
||||
|
||||
undercurrentAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Undercurrent Alarm is cleared"
|
||||
::= 115
|
||||
|
||||
overcurrentAlarmClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output Overcurrent Alarm is cleared"
|
||||
::= 116
|
||||
|
||||
loadshedClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { outputNumber }
|
||||
DESCRIPTION "Trap generated when an Output has recovered from a Load-Shedding condition"
|
||||
::= 117
|
||||
|
||||
alarmInputClear TRAP-TYPE
|
||||
ENTERPRISE distPanel
|
||||
VARIABLES { alarmNumber }
|
||||
DESCRIPTION "Trap generated when an Alarm Input is cleared"
|
||||
::= 118
|
||||
|
||||
END
|