Initial commit
This commit is contained in:
161
MIBS/opengear/OG-UPS-MIB
Normal file
161
MIBS/opengear/OG-UPS-MIB
Normal file
@ -0,0 +1,161 @@
|
||||
-- =====================================================================
|
||||
-- == OG-UPS-MIB: ==
|
||||
-- == Opengear UPS status notification Management Information Base ==
|
||||
-- == ==
|
||||
-- == (c) Copyright 2005-2014 Opengear Inc. ==
|
||||
-- =====================================================================
|
||||
|
||||
OG-UPS-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
ogMgmt
|
||||
FROM OG-SMI-MIB
|
||||
MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-TYPE, Integer32
|
||||
FROM SNMPv2-SMI
|
||||
MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
|
||||
FROM SNMPv2-CONF
|
||||
DisplayString
|
||||
FROM SNMPv2-TC;
|
||||
|
||||
ogNetUpsMib MODULE-IDENTITY
|
||||
LAST-UPDATED "201308110000Z"
|
||||
ORGANIZATION "Opengear Inc."
|
||||
CONTACT-INFO
|
||||
"Opengear Inc.
|
||||
630 West 9560 South,
|
||||
Sandy, UT 84070
|
||||
support@opengear.com"
|
||||
DESCRIPTION
|
||||
"Opengear UPS status MIB"
|
||||
REVISION "201308110000Z"
|
||||
DESCRIPTION
|
||||
"Renamed from OPENGEAR-UPS-MIB to OG-UPS-MIB to
|
||||
fix naming discrepancy."
|
||||
REVISION "201003221127Z"
|
||||
DESCRIPTION
|
||||
"Syntax corrections by Opengear Inc."
|
||||
REVISION "200806131100Z"
|
||||
DESCRIPTION
|
||||
"Initial version."
|
||||
::= { ogMgmt 16 }
|
||||
|
||||
ogNetUpsMibObjects OBJECT IDENTIFIER ::= { ogNetUpsMib 10 }
|
||||
|
||||
-- Subgroups
|
||||
|
||||
ognupsEvent OBJECT IDENTIFIER ::= { ogNetUpsMibObjects 1 }
|
||||
|
||||
ognupsEventTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF OgNUpsEventEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A table of serial signal events generated by this device."
|
||||
::= { ognupsEvent 1 }
|
||||
|
||||
ognupsEventEntry OBJECT-TYPE
|
||||
SYNTAX OgNUpsEventEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A console connection event occuring at this
|
||||
device. Each entry is indexed by a message index."
|
||||
INDEX { ognupsEventIndex }
|
||||
::= { ognupsEventTable 1 }
|
||||
|
||||
OgNUpsEventEntry ::=
|
||||
SEQUENCE {
|
||||
ognupsEventIndex Integer32,
|
||||
ognupsEventName DisplayString,
|
||||
ognupsEventType DisplayString
|
||||
}
|
||||
|
||||
ognupsEventIndex OBJECT-TYPE
|
||||
SYNTAX Integer32 (1..2147483647)
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A monotonically increasing integer for the sole
|
||||
purpose of indexing messages. When it reaches the
|
||||
maximum value the agent flushes the table and wraps
|
||||
the value back to 1."
|
||||
::= { ognupsEventEntry 1 }
|
||||
|
||||
ognupsEventName OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The name of the UPS pertaining to the status event"
|
||||
::= { ognupsEventEntry 10 }
|
||||
|
||||
ognupsEventType OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The type of status event"
|
||||
::= { ognupsEventEntry 11 }
|
||||
|
||||
-- notifications
|
||||
|
||||
ogNetUpsMibNotificationPrefix OBJECT IDENTIFIER ::= {
|
||||
ogNetUpsMib 2
|
||||
}
|
||||
|
||||
ognupsMibNotifications OBJECT IDENTIFIER ::= {
|
||||
ogNetUpsMibNotificationPrefix 0
|
||||
}
|
||||
|
||||
ognupsEventOccurred NOTIFICATION-TYPE
|
||||
OBJECTS { ognupsEventName, ognupsEventType }
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The notification sent when a UPS status event occurs"
|
||||
::= { ognupsMibNotifications 200 }
|
||||
-- conformance information
|
||||
|
||||
ogNetUpsMibConformance OBJECT IDENTIFIER ::= { ogNetUpsMib 3 }
|
||||
ogNetUpsMibCompliances OBJECT IDENTIFIER ::= { ogNetUpsMibConformance 1 }
|
||||
ogNetUpsMibGroups OBJECT IDENTIFIER ::= { ogNetUpsMibConformance 2 }
|
||||
|
||||
-- compliance statements
|
||||
|
||||
ogNetUpsMibCompliance MODULE-COMPLIANCE
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The compliance statement for entities which implement
|
||||
the Opengear UPS MIB."
|
||||
MODULE -- this module
|
||||
MANDATORY-GROUPS { ogNetUpsMibGroup }
|
||||
|
||||
GROUP ognupsNotificationsGroup
|
||||
DESCRIPTION
|
||||
"The implementation of this group is
|
||||
mandatory for those systems where
|
||||
sensor notification is supported."
|
||||
|
||||
::= { ogNetUpsMibCompliances 1 }
|
||||
|
||||
-- Units of conformance
|
||||
|
||||
ogNetUpsMibGroup OBJECT-GROUP
|
||||
OBJECTS {
|
||||
ognupsEventName,
|
||||
ognupsEventType
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A collection of objects providing the sensor MIB capability."
|
||||
::= { ogNetUpsMibGroups 1 }
|
||||
|
||||
ognupsNotificationsGroup NOTIFICATION-GROUP
|
||||
NOTIFICATIONS {
|
||||
ognupsEventOccurred
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A collection of notification(s) for sensor system."
|
||||
::= { ogNetUpsMibGroups 2 }
|
||||
|
||||
END
|