Initial commit
This commit is contained in:
386
MIBS/riello/RIELLOMDU-MIB
Normal file
386
MIBS/riello/RIELLOMDU-MIB
Normal file
@ -0,0 +1,386 @@
|
||||
-- RPS S.p.A enterprise MIB definition
|
||||
|
||||
-- Copyright (c) RPS S.p.A.
|
||||
-- Version: 1.0 by Michele Marcon
|
||||
-- Date: 1.04.2016
|
||||
|
||||
-- Title: RIELLOMDU-MIB
|
||||
|
||||
-- MDU-MIB { iso org(3) dod(6) internet(1) private(4)
|
||||
-- enterprises(1) riello(5491) }
|
||||
|
||||
-- ************************************************************************
|
||||
-- ************************************************************************
|
||||
|
||||
RIELLOMDU-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
DisplayString
|
||||
FROM RFC1213-MIB
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215
|
||||
rielloMIB
|
||||
FROM RIELLO-MIB;
|
||||
|
||||
mduMIB OBJECT IDENTIFIER ::= { rielloMIB 11 }
|
||||
|
||||
mduIdent OBJECT IDENTIFIER ::= { mduMIB 1 }
|
||||
|
||||
mduIdentManufacturer OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The name of the mdu manufacturer."
|
||||
::= { mduIdent 1 }
|
||||
|
||||
mduIdentModel OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu Model designation."
|
||||
::= { mduIdent 2 }
|
||||
|
||||
mduIdentSoftwareVersion OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu Software version."
|
||||
::= { mduIdent 3 }
|
||||
|
||||
mduIdentIOConfiguration OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri)."
|
||||
::= { mduIdent 4 }
|
||||
|
||||
mduIdentInputSockets OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The number of mdu input sockets."
|
||||
::= { mduIdent 5 }
|
||||
|
||||
mduIdentOutputSockets OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The number of mdu output sockets."
|
||||
::= { mduIdent 6 }
|
||||
|
||||
mduIdentNominalCurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu nominal current (A)."
|
||||
::= { mduIdent 7 }
|
||||
|
||||
mduIdentNominalVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu nominal voltage (V)."
|
||||
::= { mduIdent 8 }
|
||||
|
||||
mduIdentNominalFrequency OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The mdu nominal frequency (0.1 Hz)."
|
||||
::= { mduIdent 9 }
|
||||
|
||||
mduStatus OBJECT IDENTIFIER ::= { mduMIB 2 }
|
||||
|
||||
mduLineAFrequency OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The frequency of source A (0.1 Hz)."
|
||||
::= { mduStatus 1 }
|
||||
|
||||
mduLineAVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The voltage of source 1 (V)."
|
||||
::= { mduStatus 2 }
|
||||
|
||||
mduLineACurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The current of line A (0.1 A)."
|
||||
::= { mduStatus 3 }
|
||||
|
||||
mduOutput OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF MduOutputSockets
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"A list of output table entries."
|
||||
::= { mduStatus 4 }
|
||||
|
||||
mduOutputSockets OBJECT-TYPE
|
||||
SYNTAX MduOutputSockets
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"An entry containing information applicable to a
|
||||
particular output line."
|
||||
INDEX { mduOutputLineIndex }
|
||||
::= { mduOutput 1 }
|
||||
|
||||
|
||||
MduOutputSockets ::=
|
||||
SEQUENCE {
|
||||
mduOutputLineIndex
|
||||
INTEGER,
|
||||
|
||||
mduOutputCurrent
|
||||
INTEGER,
|
||||
|
||||
mduOutputDisabled
|
||||
INTEGER,
|
||||
|
||||
mduOutputOverload
|
||||
INTEGER,
|
||||
|
||||
mduOutputStatus
|
||||
INTEGER
|
||||
}
|
||||
|
||||
mduOutputLineIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..2147483647)
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The line identifier."
|
||||
::= { mduOutputSockets 1 }
|
||||
|
||||
mduOutputCurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Output current (0.1 A)"
|
||||
::= { mduOutputSockets 2 }
|
||||
|
||||
mduOutputDisabled OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
no(1),
|
||||
yes(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1->line active, 2->line deactivated"
|
||||
::= { mduOutputSockets 3 }
|
||||
|
||||
mduOutputOverload OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1->line ok, 2->line deactivated for overload"
|
||||
::= { mduOutputSockets 4 }
|
||||
|
||||
mduOutputStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER{
|
||||
off(0),
|
||||
on(1),
|
||||
shutdownActive(2),
|
||||
shutdownImminent(3),
|
||||
restoreActive(4),
|
||||
overload(5),
|
||||
locked(6)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"0=OFF
|
||||
1=ON
|
||||
2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the "Imminent time" is not reached)
|
||||
3= Shutdown imminent (S01 ÷ S08 code)
|
||||
4= Restore active (when after that a CR command is received and the shutdown has been acted but the restore delay time is not expired)
|
||||
5= Overload alarm (F01 ÷ F08 code)
|
||||
6= Locked: OFF for overload (L01 ÷ L08 code)"
|
||||
::= { mduOutputSockets 5 }
|
||||
|
||||
mduLowInputVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 5 }
|
||||
|
||||
mduHighInputVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 6 }
|
||||
|
||||
mduLowInputCurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 7 }
|
||||
|
||||
mduHighInputCurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 8 }
|
||||
|
||||
mduPowerFailAux1 OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 9 }
|
||||
|
||||
mduPowerFailAux2 OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= yes, 0= no."
|
||||
::= { mduStatus 10 }
|
||||
|
||||
mduManualBypass OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"1= on manual bypass, 0= no."
|
||||
::= { mduStatus 11 }
|
||||
|
||||
mduTemperature OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The temperature (°C)."
|
||||
::= { mduStatus 12 }
|
||||
|
||||
mduCommand OBJECT IDENTIFIER ::= { mduMIB 3 }
|
||||
|
||||
mduCommandCode OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
shutdown(1),
|
||||
restore(2),
|
||||
commandDelete(3),
|
||||
testPanel(22)
|
||||
}
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"This object determines the nature of the action to be
|
||||
taken at the time when the countdown of the
|
||||
mduShutdownDelay and mduRestoreDelay objects reaches zero.
|
||||
Setting this object to shutdown(1) indicates that
|
||||
the specified sockets mduOutputSocketApplyCommand will yurn off.
|
||||
Setting this object to restore(2) indicates that the specified output
|
||||
sockets will turn on.
|
||||
command delete(3) will delete the applied command, test panel will perform
|
||||
a test of LCD panel and audible alarm"
|
||||
::= { mduCommand 1 }
|
||||
|
||||
mduShutdownDelay OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Setting this object will shutdown (i.e., turn off)
|
||||
either the MDU output socket by the value of mduCommandCode
|
||||
at the time of shutdown after the indicated number of seconds.
|
||||
Setting this object to 0 will cause the shutdown to occur
|
||||
immediately"
|
||||
::= { mduCommand 2 }
|
||||
|
||||
mduRestoreDelay OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The restore delay."
|
||||
::= { mduCommand 3 }
|
||||
|
||||
mduOutputSocketApplyCommand OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Specify the socket to apply the command, the value 0 apply to all sockets."
|
||||
::= { mduCommand 4 }
|
||||
|
||||
mduCommandResult OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The command result, refer to the follow codes:
|
||||
0+mduCommandCode Command in progress
|
||||
256+mduCommandCode Wrong Command code
|
||||
512+mduCommandCode Command is not handled
|
||||
768+mduCommandCode Parameter out of range
|
||||
3584+mduCommandCode Command sent to MDU
|
||||
3840+mduCommandCode Command executed"
|
||||
::= { mduCommand 5 }
|
||||
|
||||
mduTraps OBJECT IDENTIFIER ::= { mduMIB 4 }
|
||||
|
||||
-- This section defines the well-known notifications sent by
|
||||
-- MDU agents.
|
||||
-- Care must be taken to insure that no particular notification
|
||||
-- is sent to a single receiving entity more often than once
|
||||
-- every minute.
|
||||
|
||||
mduNormal TRAP-TYPE
|
||||
ENTERPRISE mduTraps
|
||||
DESCRIPTION "This trap is sent when MDU is on normal status"
|
||||
::= 1
|
||||
|
||||
mduAnomaly TRAP-TYPE
|
||||
ENTERPRISE mduTraps
|
||||
DESCRIPTION "This trap is sent when MDU is has some anomaly and is resent every minute"
|
||||
::= 2
|
||||
|
||||
mduFault TRAP-TYPE
|
||||
ENTERPRISE mduTraps
|
||||
DESCRIPTION "This trap is sent when MDU is has some fault and is resent every minute"
|
||||
::= 3
|
||||
|
||||
mduLock TRAP-TYPE
|
||||
ENTERPRISE mduTraps
|
||||
DESCRIPTION "This trap is sent when MDU is locked and is resent every minute"
|
||||
::= 4
|
||||
|
||||
mduManualBypassEnabled TRAP-TYPE
|
||||
ENTERPRISE mduTraps
|
||||
DESCRIPTION "This trap is sent when MDU is on manual bypass and is resent every minute"
|
||||
::= 5
|
||||
|
||||
END
|
||||
|
Reference in New Issue
Block a user