ALGPOWER-v2-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 enterprises FROM RFC1155-SMI; algcom OBJECT IDENTIFIER ::= { enterprises 49136 } upsObjects OBJECT IDENTIFIER ::= { algcom 1 } output OBJECT IDENTIFIER ::= { upsObjects 1 } battery OBJECT IDENTIFIER ::= { upsObjects 2 } input OBJECT IDENTIFIER ::= { upsObjects 3 } temperature OBJECT IDENTIFIER ::= { upsObjects 4 } watchdog OBJECT IDENTIFIER ::= { upsObjects 5 } supply OBJECT IDENTIFIER ::= { upsObjects 6 } installation OBJECT IDENTIFIER ::= { upsObjects 7 } bat-tst OBJECT IDENTIFIER ::= { upsObjects 8 } outputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Numeric value of instantaneous output voltage from the source in tenths of a volt. To get the value actual in volt should be divided by 10. Example: Read value 241, actual value 24.1V." ::= { output 1 } outputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Numeric value of current output of converter AC/DC. Real value reading in milli ampere. Example: Read value 1087, Actual value 1.087 milli ampere or 1.087A. If the output is '0' the AC/DC is off and the output for the equipments is provide from batteries" ::= { output 2 } oidNotUsed0 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "OID not used." ::= { output 3 } oidNotUsed1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "OID not used." ::= { output 4 } batteryVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Numeric value of instantaneous voltage of battery bank. To get the actual value in volt must be divided by 10. Example: Read value 240, actual value 24.0V." ::= { battery 1 } batteryCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Numeric value of current in Battery bank. Real value reading in milli ampere. If the value is negative the Battery bank is provide energy for the output. If the value is positive the Battery bank is under charger Example: Read value -2230, Actual value 2,230 ampere and the battery bank is provide this current. Read value 3000, Actual value 3.000 milli ampere and the battery bank is absorve this current." ::= { battery 2 } chargerStatus OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the status of battery charger: 0 - The battery is not connected in DC UPS; 1 - The battery is voltage incompatible with DC UPS; 2 - The DC UPS is in nobreak mode; 3 - The charger of Battery is in Bulk stage; 4 - The charger of Battery is Absorption stage; 5 - The charger of Battery is Float stage; 6 - The Battery will be disconnected in 30s due to low voltage and the DC-UPS output will be turned off. 7 - The Battery is under test" ::= { battery 3 } alarmOnBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Shows the operation mode of DC-UPS: 0 - The DC-UPS output is provide by AC energy. 1 - The DC-UPS output is provide by Battery" ::= { input 1 } acFail OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm that alert about AC outages in the last 10 minutes: 0 - DC-UPS in normal operation. 1 - Occur a AC fail in the last 10 minutes." ::= { input 2 } batteryCharging OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the status of charging Battery: 1 - The battery is on charging. 0 - The battery is on discharging." ::= { input 3 } batteryDischarging OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the status of discharging Battery: 1 - The battery is on discharging. 0 - The battery is on charging." ::= { input 4 } overheat OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm that alert about overtemperature of DC-UPS 1 - The DC-UPS is in condition of overtemperature. 0 - The DC-UPS is in normal condition." ::= { input 5 } overload OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm that alert about overload of DC-UPS 1 - The DC-UPS is in condition of overload. 0 - The DC-UPS is in normal condition." ::= { input 6 } fanAfail OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm that alert about fail in internal FAN A 1 - Internal FAN with fail. 0 - Internal FAN ok" ::= { input 7 } fanBfail OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm that alert about fail in internal FAN B 1 - Internal FAN with fail. 0 - Internal FAN ok" ::= { input 8 } oidNotUsed2 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "OID not used." ::= { input 9 } oidNotUsed3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "OID not used." ::= { input 10 } upTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "System Up time in hours" ::= {input 11} innerTemperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the internal temperature of power supply. Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC." ::= { temperature 1 } outerTemperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the temperature of external sensor (cable that comes with power supply). Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC." ::= { temperature 2 } heatSinkTemperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Show the temperature of sensor in the heatsink of power supply use the unit degree Celsius. Example Read value: 25, temperature is 25degC." ::= { temperature 3 } watchdogPing1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 1 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 1 acted on the output the last 10 minutes. 0 - The Watchdog 1 has not acted in the last 10 minutes." ::= { watchdog 1 } watchdogPing2 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 2 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 2 acted on the output the last 10 minutes. 0 - The Watchdog 2 has not acted in the last 10 minutes." ::= { watchdog 2 } watchdogPing3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 3 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 3 acted on the output the last 10 minutes. 0 - The Watchdog 3 has not acted in the last 10 minutes." ::= { watchdog 3 } watchdogPing4 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 4 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 4 acted on the output the last 10 minutes. 0 - The Watchdog 4 has not acted in the last 10 minutes." ::= { watchdog 4 } watchdogPing5 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 5 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 5 acted on the output the last 10 minutes. 0 - The Watchdog 5 has not acted in the last 10 minutes." ::= { watchdog 5 } watchdogPing6 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 6 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 6 acted on the output the last 10 minutes. 0 - The Watchdog 6 has not acted in the last 10 minutes." ::= { watchdog 6 } watchdogPing7 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 7 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 7 acted on the output the last 10 minutes. 0 - The Watchdog 7 has not acted in the last 10 minutes." ::= { watchdog 7 } watchdogPing8 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 8 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 8 acted on the output the last 10 minutes. 0 - The Watchdog 8 has not acted in the last 10 minutes." ::= { watchdog 8 } watchdogPing9 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 9 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 9 acted on the output the last 10 minutes. 0 - The Watchdog 9 has not acted in the last 10 minutes." ::= { watchdog 9 } watchdogPing10 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Alarm indicating the action of watchdog 10 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 10 acted on the output the last 10 minutes. 0 - The Watchdog 10 has not acted in the last 10 minutes." ::= { watchdog 10 } supplyVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The supply AC voltage decivolt [dV] Numeric value of instantaneous input voltage. An optional sensor is required to read this value. To get the actual value in volt it should be divided by 10. Example: Read value 2410, actual value 241 Vac." ::= {supply 1} popName OBJECT-TYPE SYNTAX DisplayString (SIZE (30)) ACCESS read-only STATUS mandatory DESCRIPTION "PoP name" ::= {installation 1} facilityAddr OBJECT-TYPE SYNTAX DisplayString (SIZE (40)) ACCESS read-only STATUS mandatory DESCRIPTION "Facility address" ::= {installation 2} facilityCity OBJECT-TYPE SYNTAX DisplayString (SIZE (30)) ACCESS read-only STATUS mandatory DESCRIPTION "Facility city" ::= {installation 3} instDate OBJECT-TYPE SYNTAX DisplayString (SIZE (10)) ACCESS read-only STATUS mandatory DESCRIPTION "Installation date" ::= {installation 4} batCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery capacity" ::= {installation 5} batBrand OBJECT-TYPE SYNTAX DisplayString (SIZE (30)) ACCESS read-only STATUS mandatory DESCRIPTION "Battery brand" ::= {installation 6} batInstDate OBJECT-TYPE SYNTAX DisplayString (SIZE (10)) ACCESS read-only STATUS mandatory DESCRIPTION "Battery installation date" ::= {installation 7} respPers OBJECT-TYPE SYNTAX DisplayString (SIZE (50)) ACCESS read-only STATUS mandatory DESCRIPTION "Responsible person" ::= {installation 8} btst-date OBJECT-TYPE SYNTAX DisplayString (SIZE (10)) ACCESS read-only STATUS mandatory DESCRIPTION "Battery test execution date (dd/mm/yyyy)" ::= {bat-tst 1} btst-status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Battery test status 0 - NEVER DONE 1 - Passed 2 - Running 3 - Aborted 4 - Failed" ::= {bat-tst 2} btst-duration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Programmed test duration in minutes * 999 - Perform the test until battery is fully discharged" ::= {bat-tst 3} btst-elapsed OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Elapsed time in current\last battery test" ::= {bat-tst 4} btst-volt-i OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery initial voltage [dV] Numeric value of battery voltage when starting the battery test. Example: Read value 241, actual value 24.1 V." ::= {bat-tst 5} btst-amp-i OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery initial cuurent [mA] Numeric value of battery current when starting the battery test. Example: Read value 1522, actual value 1.55 A." ::= {bat-tst 6} btst-volt-f OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery final voltage [dV] Numeric value of battery voltage when the battery test is done. Example: Read value 225, actual value 22.5 V." ::= {bat-tst 7} btst-amp-f OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery initial cuurent [mA] Numeric value of battery current when the battery test is done. Example: Read value 1485, actual value 1.48 A." ::= {bat-tst 8} END