-- SiteBoss 550 MIB -- v 4.66 Mar 8 2019 -- Copyright (c) 2019 by Asentria Corporation. All rights reserved. SITEBOSS-550-STD-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM SNMPv2-TC IpAddress, TimeTicks, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-TYPE FROM SNMPv2-SMI asentria FROM ASENTRIA-ROOT-MIB; --*************************************************************************************** --MODULE IDENTITY --*************************************************************************************** s550 MODULE-IDENTITY LAST-UPDATED "201903081530Z" ORGANIZATION "Asentria Corporation" CONTACT-INFO "Phone: 206-344-8800 Fax: 206-344-2116 Email: support@asentria.com" DESCRIPTION "MIB module for managing Asentria SiteBoss 550" REVISION "201903081530Z" DESCRIPTION "-v4.66 -Add objects for Power Meter line-to-line voltage (OMX-2143) and modified OID numbering for ACMON. -Applicable since unit version 2.11.760." REVISION "201902111345Z" DESCRIPTION "-v4.65 -Added objects for Site Security (OMX-2021). -Applicable since unit version 2.11.760." REVISION "201710311049Z" DESCRIPTION "-v4.64 -Added objects for Bard HVAC controller (OMX-1852). -Applicable since unit version 2.11.550." REVISION "201705251028Z" DESCRIPTION "-v4.63 -Added trap 545 and 548 to the mibs -Applicable since unit version 2.11.500." REVISION "201704260945Z" DESCRIPTION "-v4.62 -Added ACMON Alarm datetime to the mibs -Applicable since unit version 2.11.490." REVISION "201603160850Z" DESCRIPTION "-v4.61 -Fixed missing IP Camera trap notifications -Applicable since unit version 2.11.210." REVISION "201603150500Z" DESCRIPTION "-v4.60 -Replace existing sensor .type setting with new system .group -Added Objects espcCCGroup, espcTempGroup, espcHumidGroup, espcAIGroup espcOutputGroup -Applicable since unit version 2.11.210." REVISION "201601070459Z" DESCRIPTION "-v4.59 -Added Event Sensor Alias and Class OID for event states. -Added Fuel Sensor Fuel Type. -Applicable since unit version 2.11.140." REVISION "201510290458Z" DESCRIPTION "-v4.58 -Allow read access for battery backup - percent charge and running status. -Add trap for power up/down or running on battery/main -Applicable since unit version 2.10.930." REVISION "201504030457Z" DESCRIPTION "-v4.57 -Allow read access for serial number, product name, software version -Add trap for General Sensor Unresponsive (OMX-1257) -Applicable since unit version 2.10.700." REVISION "201503200456Z" DESCRIPTION "-v4.56 -Removed non-essential Bard settings (OMX-1203). -Removed wirelessPIN and scSecret objects (OMX-1064). -Added HVAC status and settings objects. -Added ACDM wiegand point object. -Applicable since unit version 2.10.670." REVISION "201412110455Z" DESCRIPTION "-v4.55 -Changed analog-input fuel sensor objects from Integer32 to DisplayString (OMX-1177). -Added missing ipv6DefaultRouter object (OMX-1175). -Applicable since unit version 2.10.580." REVISION "201410160454Z" DESCRIPTION "-v4.54 -Added espcAIDisplayFormat object (OMX-1112). -Removed espcAIPolarity, espcAIConvHighSign, espcAIConvLowSign objects (OMX-1113). -Applicable since unit version 2.10.460." REVISION "201410030453Z" DESCRIPTION "-v4.53 -Changed analog input objects from Integer32 to DisplayString. -Applicable since unit version 2.10.460." REVISION "201409100452Z" DESCRIPTION "-v4.52 -Added dnp3 and telemetry branches (OMX-454). -Applicable since unit version 2.10.460." REVISION "201408140451Z" DESCRIPTION "-v4.51 -Fixed description for wirelessConnIP objects (OMX-1061). -Applicable since unit version 2.10.390." REVISION "201407030450Z" DESCRIPTION "-v4.50 -Fixed wirelessIdleTimeout (OMX-1037). -Fixed CPE status objects (OMX-1036). -Applicable since unit version 2.10.390." REVISION "201406240449Z" DESCRIPTION "-v4.49 -Fixed CPE status objects. -Applicable since unit version 2.10.340." REVISION "201406170448Z" DESCRIPTION "-v4.48 -Added various missing objects (OMX-751). -Added CPE objects (OMX-162). -Added ACDM objects (OMX-683). -Applicable since unit version 2.10.340." REVISION "201404110447Z" DESCRIPTION "-v4.47 -Clarified relay and power output function and documentation (OMX-926). -Applicable since unit version 2.10.300." REVISION "201401170146Z" DESCRIPTION "-v4.46 -Added IPv6 objects (OMX-705). -Added power distribution objects (powerDistributionStatus branch) (OMX-708). -Fixed ipRestrictionMask wrong type (OMX-743). -Added ftpPushPermissions (OMX-737). -Added snmpProxy objects (OMX-747). -Applicable since unit version 2.10.150." REVISION "201312160445Z" DESCRIPTION "-v4.45 -Changed evHVACStatus branch OIDs (OMX-702). -Applicable since unit version 2.10.130." REVISION "201312040444Z" DESCRIPTION "-v4.44 -Added fsGenEnable (OMX-661). -Applicable since unit version 2.10.110." REVISION "201310300443Z" DESCRIPTION "-v4.43 -Added genSetRelayTable for multiple genset ignition relays (OMX-577). -Added genSetCCDelay object (OMX-589). -Added webXMLProxy branch (OMX-629). -Applicable since unit version 2.09.625." REVISION "201310040442Z" DESCRIPTION "-v4.42 -Added objects for Emerson Vortex Power System (OMX-578). -Applicable since unit version 2.09.624." REVISION "201309260441Z" DESCRIPTION "-v4.41 -Added objects for Bard HVAC controller (OMX-563). -Applicable since unit version 2.09.623." REVISION "201308010440Z" DESCRIPTION "-v4.40 -Added missing trapEventTypeNumber available values in description (OMX-437). -Applicable since unit version 2.09.560." REVISION "201307170439Z" DESCRIPTION "-v4.39 -Corrected snmpPBufferAllPeriod object. -Applicable since unit version 2.09.560." REVISION "201307020438Z" DESCRIPTION "-v4.38 -Added snmpPoll objects (OMX-394). -Applicable since unit version 2.09.560." REVISION "201306120437Z" DESCRIPTION "-v4.37 -Renamed EX10 to Ethernet Expansion (OMX-364) -Applicable since unit version 2.09.510." REVISION "201305280436Z" DESCRIPTION "-v4.36 -Fixed incorrect SYNTAX for sysCharMask (OMX-328). -Added evGlobal branch (OMX-228). -Applicable since unit version 2.09.500." REVISION "201305100435Z" DESCRIPTION "-v4.35 -Fixed incorrect SYNTAX statements for various objects (OMX-314). -Applicable since unit version 2.09.380." REVISION "201304100434Z" DESCRIPTION "-v4.34 -Added non-weekly job scheduling objects (OMX-252). -Applicable since unit version 2.09.310." REVISION "201303150433Z" DESCRIPTION "-v4.33 -Renamed sysLocation branch to sysLoc (OMX-198). -Applicable since unit version 2.09.240." REVISION "201303140432Z" DESCRIPTION "-v4.32 -Added snmpProxy branch (OMX-190). -Applicable since unit version 2.09.280." REVISION "201302060431Z" DESCRIPTION "-v4.31 -Added ex10 branch. -Renamed telnet* objects. -Applicable since unit version 2.09.240." REVISION "201301140430Z" DESCRIPTION "-v4.30 -Added evReset branch and associated notification (OMX-83). -Applicable since unit version 2.09.220." REVISION "201211190429Z" DESCRIPTION "-v4.29 -Added sysFileTransfer and sysUpdate objects. (BN 4632) -Fixed backwards pppRoutingEnable/ethRoutingEnable comments. (BN 4620) -Applicable since unit version 2.09.120." REVISION "201208220428Z" DESCRIPTION "-v4.28 -Added additional AC power monitor items." REVISION "201208020427Z" DESCRIPTION "-v4.27 -Removed non-weekly job schedule objects." REVISION "201206120425Z" DESCRIPTION "-v4.25 -Removed user credentials objects." REVISION "201205010424Z" DESCRIPTION "-v4.24 -Added object for location. -Fixed objects for Generator Exercising Non-Start event." REVISION "201204300423Z" DESCRIPTION "-v4.23 -Added objects for fuel sensor sudden/slow change." REVISION "201204120422Z" DESCRIPTION "-v4.22 -Added objects for job scheduling and generator exercising." REVISION "201204090421Z" DESCRIPTION "-v4.21 -Added eth2WanRoutingEnable object." REVISION "201204050420Z" DESCRIPTION "-v4.20 -Added combined eventsensor status objects." REVISION "201203060419Z" DESCRIPTION "-v4.19 -Added objects and trap definitions for fuel sensor and AC power monitor." REVISION "201201160902Z" DESCRIPTION "-v4.18 -Jumped to 4.xx Asentria version series. The version 4 series officially may improve compatibility with certain NMS installations by grouping all notifications in a dedicated branch. -Added stockScriptTrap notification definition." REVISION "201109150900Z" DESCRIPTION "-v1.17 -Moved notification definitions to dedicated branch." REVISION "201108080900Z" DESCRIPTION "-v1.16 -Added s550StockOutputTrap notification definition." REVISION "201108010900Z" DESCRIPTION "-v1.15 -Added evMgmtReprocess object." REVISION "201107080900Z" DESCRIPTION "-v1.14 -Added wirelessModemStatus branch." REVISION "201101050900Z" DESCRIPTION "-v1.13 -Added espcCCNormalThreshold object." REVISION "201011030900Z" DESCRIPTION "-v1.12 -Changed deadband, threshold, and current values for temperature sensors from integer to floating-point type. This means the SNMP object type for the temperature settings (deadbands and thresholds) changed from Integer32 to DisplayString. -Fixed bug where SNMP integer range defined in the MIB for trapIncludedValue was 16-bit instead of 32-bit." REVISION "201008240900Z" DESCRIPTION "-v1.11 -Fixed bug where some stock traps had too few varbinds declared. -Removed useless trap definitions." REVISION "201003160900Z" DESCRIPTION "-v1.10 -Removed useless objects consoleInlineHsk, consoleBaud, consoleFormat, consoleHsk." REVISION "201001190900Z" DESCRIPTION "-v1.09 -Increased range for esPointValueInt" REVISION "200811210900Z" DESCRIPTION "-v1.08 -Added scripting variable objects." REVISION "200811120900Z" DESCRIPTION "-v1.07 -Corrected comments for stock trap definitions." REVISION "200806090900Z" DESCRIPTION "-v1.06 -Added sysLocation branch. -Updated phone numbers in contact info block." REVISION "200806021100Z" DESCRIPTION "-v1.05 -Added SitePath CPE routing authorization requested stock trap." REVISION "200805151500Z" DESCRIPTION "-v1.04 -Added pager settings" REVISION "200805081426Z" DESCRIPTION "-v1.03 -Fixed issue where commented OIDs used wrong module identity number" REVISION "200804221652Z" DESCRIPTION "-v1.02 -Added missing wireless objects -Removed wirelessBaud object which broke mib walk -Fixed issue where snmpNotificationTx branch was defined wrong." REVISION "200803211650Z" DESCRIPTION "-v1.01 -Added missing CPEDown/VPNGDow notification definitions" REVISION "200712070030Z" DESCRIPTION "-v1.00 -Branched new MIB off of SiteBoss 570 MIB" ::= { asentria 10 } --1.3.6.1.4.1.3052.10 --*************************************************************************************** --Concise MIB View: Top Level Branches --*************************************************************************************** -- status .1 -- eventSensorStatus .1.1 -- esPointTable .1.1.1 -- dataEventStatus .1.2 -- deStatusTable .1.2.1 -- modemStatus .1.3 -- modemCLIDLogTable .1.4 -- powerDistributionStatus .1.5 -- fuelSensorStatus .1.6 -- fsStatusTable .1.6.1 -- wirelessModemStatus .1.7 -- acPowerMonitorStatus .1.8 -- acpmStatusTable .1.8.1 -- evHVACStatus .1.11 -- evHVACStatusBard .1.11.2 -- evHVACStatusAsentria .1.11.3 -- evHVACStatusAirsys .1.11.4 -- backupBattStatus .1.12 -- liBattStatus .1.12.1 -- config .2 -- eventSensorBasics .2.1 -- esNumberEventSensors .2.1.1 -- esTable .2.1.2 -- esNewSensors .2.1.3 -- eventSensorPointConfig .2.2 -- esPointConfigTempTable .2.2.1 -- esPointConfigCCTable .2.2.2 -- esPointConfigHumidTable .2.2.3 -- esPointConfigAITable .2.2.5 -- esPointConfigOutputTable .2.2.6 -- serialPorts .2.3 -- numberPorts .2.3.1 -- portConfigTable .2.3.2 -- network .2.4 -- interface .2.4.1 -- defaultRouter .2.4.2 -- dnsTable .2.4.3 -- hostname .2.4.4 -- hostTable .2.4.5 -- ncpDuplex .2.4.6 -- ncpTimeout .2.4.7 -- snmp .2.4.8 -- ftpPush .2.4.9 -- ppp .2.4.10 -- routing .2.4.11 -- netSecurity .2.4.12 -- rts .2.4.13 -- trap .2.4.14 -- routeTest .2.4.15 -- gprs .2.4.16 -- email .2.4.17 -- netAdvanced .2.4.18 -- web .2.4.19 -- ethExpan .2.4.20 -- ipv6 .2.4.21 -- cpe .2.4.22 -- dnp3 .2.4.23 -- modem .2.5 -- time .2.8 -- clock .2.8.1 -- console .2.10 -- unitSecurity .2.11 -- secCore .2.11.1 -- secUserTable .2.11.2 -- secFactory .2.11.3 -- secSSH .2.11.4 -- secVPN .2.11.5 -- event .2.12 -- evCore .2.12.1 -- evData .2.12.2 -- evNoData1 .2.12.3 -- evNoData2 .2.12.4 -- evSched1 .2.12.5 -- evSched2 .2.12.6 -- evShskLowTable .2.12.7 -- evShskHighTable .2.12.8 -- evNoSensor .2.12.9 -- fuelSensor .2.12.11 -- fuelSensorGeneralTable .2.12.11.1 -- fuelSensorTankTable .2.12.11.2 -- fuelSensorCustomTankTable .2.12.11.3 -- fuelSensorVolumeTable .2.12.11.4 -- fuelSensorDisconnectTable .2.12.11.5 -- fuelSensorSuddenChangeTable .2.12.11.6 -- fuelSensorSlowChangeTable .2.12.11.7 -- acPowerMonitor .2.12.12 -- evReset .2.12.16 -- evGlobal .2.12.18 -- evHVAC .2.12.19 -- evHVACGeneral .2.12.19.1 -- evHVACBard .2.12.19.2 -- evHVACAsentria .2.12.19.3 -- evHVACAirsys .2.12.19.4 -- evEvps .2.12.20 -- accessControl .2.12.21 -- telemetry .2.12.22 -- siteSecurity .2.12.23 -- action .2.14 -- actionCallNumberTable .2.14.1 -- actionPagerTable .2.14.2 -- actionSched .2.14.3 -- actionAsentria .2.14.4 -- actionHostTable .2.14.6 -- actionEmailTable .2.14.7 -- actionParseError .2.14.8 -- sys .2.16 -- sysTime .2.16.1 -- sysPT .2.16.2 -- sysMTU .2.16.3 -- sysAnswerString .2.16.4 -- sysEventFileID .2.16.6 -- sysEscapeCharacter .2.16.7 -- sysTimeStamp .2.16.8 -- sysLog .2.16.9 -- sysCRDB .2.16.10 -- sysCharMask .2.16.11 -- sysPrompt .2.16.12 -- sysBootStatus .2.16.13 -- sysLoc .2.16.14 -- sysAssetMgmt .2.16.15 -- sysFileTransfer .2.16.17 -- sysUpdate .2.16.18 -- auditLog .2.17 -- scripting .2.18 -- scrGlobalEnable .2.18.1 -- scrDTRCtrlPortEnableTable .2.18.2 -- scrTable .2.18.3 -- scrVolatileStringTable .2.18.4 -- scrVolatileIntTable .2.18.5 -- scrNonVolatileStringTable .2.18.6 -- scrNonVolatileIntTable .2.18.7 -- generator .2.19 -- genSet .2.19.1 -- genSetRelay .2.19.1.2 -- genSetCc .2.19.1.3 -- genRun .2.19.2 -- genRunNonstartEvent .2.19.2.7 -- calendar .2.20 -- productIds .3 -- siteName 3.1 -- thisProduct .3.2 -- stockTrapString .3.3 -- trapEventTypeNumber .3.4 -- trapEventTypeName .3.5 -- trapIncludedValue .3.6 -- trapIncludedString .3.7 -- trapTypeString .3.8 -- trapEventClassNumber .3.9 -- trapEventClassName .3.10 -- keyInterface .4.0 --*************************************************************************************** --Complete MIB View: All Objects --*************************************************************************************** -- status .1 -- eventSensorStatus .1.1 -- esPointTable .1.1.1 -- esPointEntry .1.1.1.1 -- esIndexES .1.1.1.1.1 -- esIndexPC .1.1.1.1.2 -- esIndexPoint .1.1.1.1.3 -- esPointName .1.1.1.1.4 -- esPointInEventState .1.1.1.1.5 -- esPointValueInt .1.1.1.1.6 -- esPointValueStr .1.1.1.1.7 -- esPointTimeLastChange .1.1.1.1.8 -- esPointTimetickLastChange .1.1.1.1.9 -- esPointAliasValueStr .1.1.1.1.10 -- esPointClassValueStr .1.1.1.1.11 -- dataEventStatus .1.2 -- deStatusTable .1.2.1 -- deStatusEntry .1.2.1.1 -- deStatusIndex .1.2.1.1.1 -- deStatusName .1.2.1.1.2 -- deStatusCounter .1.2.1.1.3 -- deStatusThreshold .1.2.1.1.4 -- modemStatus .1.3 -- modemCLIDLogTable .1.4 -- modemCLIDLogEntry .1.4.1 -- modemCLIDLogIndex .1.4.1.1 -- modemCLIDLogNumber .1.4.1.2 -- powerDistributionStatus .1.5 -- pdConfig .1.5.1 -- pdNextGen .1.5.4 -- pdnTable .1.5.4.1 -- pdnEntry .1.5.4.1.1 -- pdnIndexPD .1.5.4.1.1.1 -- pdnIndexOutput .1.5.4.1.1.2 -- pdnConfig .1.5.4.1.1.3 -- pdnMainCurrentInEventState .1.5.4.1.1.4 -- pdnMainCurrentValue .1.5.4.1.1.5 -- pdnMainCurrentValueStr .1.5.4.1.1.6 -- pdnMainCurrentDeadband .1.5.4.1.1.7 -- pdnMainCurrentVHighCurrent .1.5.4.1.1.8 -- pdnMainCurrentHighCurrent .1.5.4.1.1.9 -- pdnMainCurrentLowCurrent .1.5.4.1.1.10 -- pdnMainCurrentVLowCurrent .1.5.4.1.1.11 -- pdnMainVoltageInEventState .1.5.4.1.1.12 -- pdnMainVoltageValue .1.5.4.1.1.13 -- pdnMainVoltageValueStr .1.5.4.1.1.14 -- pdnMainVoltageDeadband .1.5.4.1.1.15 -- pdnMainVoltageVHighVoltage .1.5.4.1.1.16 -- pdnMainVoltageHighVoltage .1.5.4.1.1.17 -- pdnMainVoltageLowVoltage .1.5.4.1.1.18 -- pdnMainVoltageVLowVoltage .1.5.4.1.1.19 -- pdnMainPowerValue .1.5.4.1.1.20 -- pdnMainPowerValueStr .1.5.4.1.1.21 -- pdnOutputCurrentInEventState .1.5.4.1.1.22 -- pdnOutputCurrentValue .1.5.4.1.1.23 -- pdnOutputCurrentValueStr .1.5.4.1.1.24 -- pdnOutputCurrentDeadband .1.5.4.1.1.25 -- pdnOutputCurrentVHighCurrent .1.5.4.1.1.26 -- pdnOutputCurrentHighCurrent .1.5.4.1.1.27 -- pdnOutputCurrentLowCurrent .1.5.4.1.1.28 -- pdnOutputCurrentVLowCurrent .1.5.4.1.1.29 -- pdnOutputFuseInEventState .1.5.4.1.1.30 -- pdnOutputFuseValueStr .1.5.4.1.1.31 -- pdnMainCombinedStatus .1.5.4.1.1.32 -- pdnOutputCombinedStatusBlock1 .1.5.4.1.1.33 -- pdnOutputCombinedStatusBlock2 .1.5.4.1.1.34 -- pdnDeviceCurrentValue .1.5.4.1.1.35 -- pdnDeviceCurrentValueStr .1.5.4.1.1.36 -- pdSystem .1.5.5 -- pdSystemCurrent .1.5.5.1 -- pdSystemPower .1.5.5.2 -- fuelSensorStatus .1.6 -- fsStatusTable .1.6.1 -- fsStatusEntry .1.6.1.1 -- fsStatusIndex .1.6.1.1.1 -- fsStatusName .1.6.1.1.2 -- fsStatusDeviceState .1.6.1.1.3 -- fsStatusVolumeValueString .1.6.1.1.4 -- fsStatusVolumePercentLevel .1.6.1.1.7 -- fsStatusVolumeInEventState .1.6.1.1.8 -- fsStatusCombined .1.6.1.1.9 -- wirelessModemStatus .1.7 -- wmsStatus .1.7.1 -- wmsSignal .1.7.2 -- wmsRSSI .1.7.3 -- wmsBER .1.7.4 -- wmsUpdated .1.7.5 -- wmsRegistration .1.7.6 -- wmsLAC .1.7.7 -- wmsCellID .1.7.8 -- wmsIMSI .1.7.9 -- wmsPhnum .1.7.10 -- wmsLocalIP .1.7.11 -- wmsMgfID .1.7.12 -- wmsModelID .1.7.13 -- wmsIMEI .1.7.14 -- wmsRevID .1.7.15 -- wmsNetName .1.7.16 -- wmsGPRSStatus .1.7.17 -- wmsBand .1.7.18 -- wmsChannel .1.7.19 -- wmsCountryCode .1.7.20 -- wmsNetCode .1.7.21 -- wmsPLMNColor .1.7.22 -- wmsBScolor .1.7.23 -- wmsMpRACH .1.7.24 -- wmsMinRxLevel .1.7.25 -- wmsBaseCoeff .1.7.26 -- wmsSIMStatus .1.7.27 -- wmsICCID .1.7.28 -- wmsModemType .1.7.29 -- acPowerMonitorStatus .1.8 -- acpmStatusTable .1.8.1 -- acpmStatusEntry .1.8.1.1 -- acpmsIndex .1.8.1.1.1 -- acpmsName .1.8.1.1.2 -- acpmsAvgVoltageValueStr .1.8.1.1.3 -- acpmsAvgVoltageMinStr .1.8.1.1.4 -- acpmsAvgVoltageMaxStr .1.8.1.1.5 -- acpmsAvgVoltageAvgStr .1.8.1.1.6 -- acpmsAvgVoltageInEventState .1.8.1.1.7 -- acpmsVoltagePhaseAValueStr .1.8.1.1.8 -- acpmsVoltagePhaseBValueStr .1.8.1.1.9 -- acpmsVoltagePhaseCValueStr .1.8.1.1.10 -- acpmsVoltageL1L2Value .1.8.1.1.11 -- acpmsVoltageL2L3Value .1.8.1.1.12 -- acpmsVoltageL3L1Value .1.8.1.1.13 -- acpmsAvgCurrentValueStr .1.8.1.1.14 -- acpmsAvgCurrentMinStr .1.8.1.1.15 -- acpmsAvgCurrentMaxStr .1.8.1.1.16 -- acpmsAvgCurrentAvgStr .1.8.1.1.17 -- acpmsAvgCurrentInEventState .1.8.1.1.18 -- acpmsCurrentPhaseAValueStr .1.8.1.1.19 -- acpmsCurrentPhaseBValueStr .1.8.1.1.20 -- acpmsCurrentPhaseCValueStr .1.8.1.1.21 -- acpmsFreqValueStr .1.8.1.1.22 -- acpmsFreqMinStr .1.8.1.1.23 -- acpmsFreqMaxStr .1.8.1.1.24 -- acpmsFreqAvgStr .1.8.1.1.25 -- acpmsFreqInEventState .1.8.1.1.26 -- acpmsTRPValueStr .1.8.1.1.27 -- acpmsTRPMinStr .1.8.1.1.28 -- acpmsTRPMaxStr .1.8.1.1.29 -- acpmsTRPAvgStr .1.8.1.1.30 -- acpmsTRPInEventState .1.8.1.1.31 -- acpmsRPPhaseAValueStr .1.8.1.1.32 -- acpmsRPPhaseBValueStr .1.8.1.1.33 -- acpmsRPPhaseCValueStr .1.8.1.1.34 -- acpmsCombined .1.8.1.1.35 -- acpmsTPFValueStr .1.8.1.1.36 -- acpmsTPFMinStr .1.8.1.1.37 -- acpmsTPFMaxStr .1.8.1.1.38 -- acpmsTPFAvgStr .1.8.1.1.39 -- acpmsTPFInEventState .1.8.1.1.40 -- acpmsPFPhaseAValueStr .1.8.1.1.41 -- acpmsPFPhaseBValueStr .1.8.1.1.42 -- acpmsPFPhaseCValueStr .1.8.1.1.43 -- acpmsTRcPValueStr .1.8.1.1.44 -- acpmsTRcPMinStr .1.8.1.1.45 -- acpmsTRcPMaxStr .1.8.1.1.46 -- acpmsTRcPAvgStr .1.8.1.1.47 -- acpmsRcPPhaseAValueStr .1.8.1.1.48 -- acpmsRcPPhaseBValueStr .1.8.1.1.49 -- acpmsRcPPhaseCValueStr .1.8.1.1.50 -- acpmsTAPValueStr .1.8.1.1.51 -- acpmsTAPMinStr .1.8.1.1.52 -- acpmsTAPMaxStr .1.8.1.1.53 -- acpmsTAPAvgStr .1.8.1.1.54 -- acpmsAPPhaseAValueStr .1.8.1.1.55 -- acpmsAPPhaseBValueStr .1.8.1.1.56 -- acpmsAPPhaseCValueStr .1.8.1.1.57 -- acpmsTotalEnergyWh .1.8.1.1.58 -- acpmsTotalEnergyVAR .1.8.1.1.59 -- acpmsTotalEnergyVA .1.8.1.1.60 -- acmpsAvgVoltageAlarmDatetime .1.8.1.1.61 -- acmpsAvgCurrentAlarmDatetime .1.8.1.1.62 -- acmpsFreqAlarmDatetime .1.8.1.1.63 -- acmpsRealPowerAlarmDatetime .1.8.1.1.64 -- acmpsPowerFactorAlarmDatetime .1.8.1.1.65 -- evHVACStatus .1.11 -- evHVACStatusBard .1.11.2 -- evHVACStatusBardSystem1 .1.11.2.1 -- evHVACStatusBardSystem1Stage1 .1.11.2.1.1 -- evHVACStatusBardSystem1Stage1Cooling .1.11.2.1.1.1 -- evHVACStatusBardSystem1Stage2 .1.11.2.1.2 -- evHVACStatusBardSystem1Stage2Cooling .1.11.2.1.2.1 -- evHVACStatusBardSystem1Blower .1.11.2.1.3 -- evHVACStatusBardSystem1Heating .1.11.2.1.4 -- evHVACStatusBardSystem1Economizer .1.11.2.1.5 -- evHVACStatusBardSystem2 .1.11.2.2 -- evHVACStatusBardSystem2Stage1 .1.11.2.2.1 -- evHVACStatusBardSystem2Stage1Cooling .1.11.2.2.1.1 -- evHVACStatusBardSystem2Stage2 .1.11.2.2.2 -- evHVACStatusBardSystem2Stage2Cooling .1.11.2.2.2.1 -- evHVACStatusBardSystem2Blower .1.11.2.2.3 -- evHVACStatusBardSystem2Heating .1.11.2.2.4 -- evHVACStatusBardSystem2Economizer .1.11.2.2.5 -- evHVACStatusBardTempAvg .1.11.2.3 -- evHVACStatusBardTempLocal .1.11.2.4 -- evHVACStatusBardTempRemote .1.11.2.5 -- evHVACStatusBardTempRemote1 .1.11.2.5.1 -- evHVACStatusBardTempRemote2 .1.11.2.5.2 -- evHVACStatusBardDehumidification .1.11.2.6 -- evHVACStatusBardLEDs .1.11.2.7 -- evHVACStatusBardLEDsCooling .1.11.2.7.1 -- evHVACStatusBardLEDsCooling1 .1.11.2.7.1.1 -- evHVACStatusBardLEDsCooling2 .1.11.2.7.1.2 -- evHVACStatusBardLEDsCooling3 .1.11.2.7.1.3 -- evHVACStatusBardLEDsCooling4 .1.11.2.7.1.4 -- evHVACStatusBardLEDsHeating .1.11.2.7.2 -- evHVACStatusBardLEDsHeating1 .1.11.2.7.2.1 -- evHVACStatusBardLEDsHeating2 .1.11.2.7.2.2 -- evHVACStatusBardLEDsHeating3 .1.11.2.7.2.3 -- evHVACStatusBardLEDsHeating4 .1.11.2.7.2.4 -- evHVACStatusBardLEDsDeHumid .1.11.2.7.3 -- evHVACStatusBardLEDsDeHumid1 .1.11.2.7.3.1 -- evHVACStatusBardGenerator .1.11.2.8 -- evHVACStatusBardAlarmBoardState .1.11.2.9 -- evHVACStatusBardAlarmStatus .1.11.2.10 -- evHVACStatusBardASSystem1 .1.11.2.10.1 -- evHVACStatusBardASSystem1PowerLoss .1.11.2.10.1.1 -- evHVACStatusBardASSystem1Lockout .1.11.2.10.1.2 -- evHVACStatusBardASSystem2 .1.11.2.10.2 -- evHVACStatusBardASSystem2PowerLoss .1.11.2.10.2.1 -- evHVACStatusBardASSystem2Lockout .1.11.2.10.2.2 -- evHVACStatusBardASFire .1.11.2.10.3 -- evHVACStatusBardASTemp .1.11.2.10.4 -- evHVACStatusBardASTempLowAlarm .1.11.2.10.4.1 -- evHVACStatusBardASTempHighAlarm .1.11.2.10.4.2 -- evHVACStatusBardASTempVHighAlarm .1.11.2.10.4.3 -- evHVACStatusBardASFailure .1.11.2.10.5 -- evHVACStatusBardConnState .1.11.2.11 -- evHVACStatusAsentria .1.11.3 -- evHVACStatusAsentriaSequenceTable .1.11.3.1 -- evHVACStatusAsentriaSequenceEntry .1.11.3.1.1 -- evHVACStatusAsentriaSequenceIndex .1.11.3.1.1.1 -- evHVACStatusAsentriaSeqVentTime .1.11.3.1.1.2 -- evHVACStatusAsentriaSeqCoolTime .1.11.3.1.1.3 -- evHVACStatusAsentriaSeqHeatTime .1.11.3.1.1.4 -- evHVACStatusAsentriaSeqIdleTime .1.11.3.1.1.5 -- evHVACStatusAsentriaUnitTable .1.11.3.2 -- evHVACStatusAsentriaUnitEntry .1.11.3.2.1 -- evHVACStatusAsentriaUnitIndex .1.11.3.2.1.1 -- evHVACStatusAsentriaUnitState .1.11.3.2.1.2 -- evHVACStatusAsentriaUnitVentTime .1.11.3.2.1.3 -- evHVACStatusAsentriaUnitCoolTime .1.11.3.2.1.4 -- evHVACStatusAsentriaUnitHeatTime .1.11.3.2.1.5 -- evHVACStatusAsentriaUnitIdleTime .1.11.3.2.1.6 -- evHVACStatusAsentriaBackupEvent .1.11.3.3 -- evHVACStatusAsentriaFireEvent .1.11.3.4 -- evHVACStatusAsentriaTemp .1.11.3.5 -- evHVACStatusAsentriaTempOut .1.11.3.5.1 -- evHVACStatusAsentriaTempIn .1.11.3.5.2 -- evHVACStatusAsentriaHumid .1.11.3.6 -- evHVACStatusAsentriaHumidOut .1.11.3.6.1 -- evHVACStatusAsentriaHumidIn .1.11.3.6.2 -- evHVACStatusAirsys .1.11.4 -- evHVACStatusAirsysAlarm .1.11.4.1 -- evHVACStatusAirsysAlarmUnitTable .1.11.4.1.1 -- evHVACStatusAirsysAlarmUnitEntry .1.11.4.1.1.1 -- evHVACStatusAirsysAlarmUnitIndex .1.11.4.1.1.1.1 -- evHVACStatusAirsysAlarmUnitLowPress .1.11.4.1.1.1.2 -- evHVACStatusAirsysAlarmUnitHighPress .1.11.4.1.1.1.3 -- evHVACStatusAirsysAlarmUnitEvapFan .1.11.4.1.1.1.4 -- evHVACStatusAirsysAlarmUnitDirty .1.11.4.1.1.1.5 -- evHVACStatusAirsysAlarmUnitDamper .1.11.4.1.1.1.6 -- evHVACStatusAirsysAlarmUnitSupProbe .1.11.4.1.1.1.7 -- evHVACStatusAirsysAlarmSmokeFire .1.11.4.1.2 -- evHVACStatusAirsysAlarmLowRoomTemp .1.11.4.1.3 -- evHVACStatusAirsysAlarmHighRoomTemp .1.11.4.1.4 -- evHVACStatusAirsysAlarmPower .1.11.4.1.5 -- evHVACStatusAirsysAlarmpLAN .1.11.4.1.6 -- evHVACStatusAirsysAlarmClock .1.11.4.1.7 -- evHVACStatusAirsysAlarmHumidProbe .1.11.4.1.8 -- evHVACStatusAirsysAlarmOutProbe .1.11.4.1.9 -- evHVACStatusAirsysAlarmBothCompress .1.11.4.1.10 -- evHVACStatusAirsysAlarmGenerator .1.11.4.1.11 -- evHVACStatusAirsysAlarmConnection .1.11.4.1.12 -- evHVACStatusAirsysAlarmInProbe1 .1.11.4.1.13 -- evHVACStatusAirsysAlarmInProbe2 .1.11.4.1.14 -- evHVACStatusAirsysTempOut .1.11.4.2 -- evHVACStatusAirsysTempIn .1.11.4.3 -- evHVACStatusAirsysTempInBackup .1.11.4.4 -- evHVACStatusAirsysHumidIn .1.11.4.5 -- evHVACStatusAirsysUnitTable .1.11.4.6 -- evHVACStatusAirsysUnitEntry .1.11.4.6.1 -- evHVACStatusAirsysUnitIndex .1.11.4.6.1.1 -- evHVACStatusAirsysUnitTempSupply .1.11.4.6.1.2 -- evHVACStatusAirsysUnitFanspeed .1.11.4.6.1.3 -- evHVACStatusAirsysUnitFreeOpening .1.11.4.6.1.4 -- evHVACStatusAirsysUnitStatus .1.11.4.6.1.5 -- evHVACStatusAirsysUnitLocked .1.11.4.6.1.6 -- evHVACStatusAirsysUnitCompressor .1.11.4.6.1.7 -- evHVACStatusAirsysUnitHeater .1.11.4.6.1.8 -- evHVACStatusAirsysURuntimeSupplyFan .1.11.4.6.1.9 -- evHVACStatusAirsysURuntimeCompressor .1.11.4.6.1.10 -- evHVACStatusAirsysURuntimeHeat .1.11.4.6.1.11 -- evHVACStatusAirsysURuntimeFreeCooling .1.11.4.6.1.12 -- evHVACStatusAirsysUCountSupplyFan .1.11.4.6.1.13 -- evHVACStatusAirsysUCountCompressor .1.11.4.6.1.14 -- evHVACStatusAirsysUCountHeat .1.11.4.6.1.15 -- evHVACStatusAirsysUCountFreeCooling .1.11.4.6.1.16 -- evHVACStatusAirsysDay .1.11.4.7 -- evHVACStatusAirsysDate .1.11.4.8 -- evHVACStatusAirsysTime .1.11.4.9 -- evHVACStatusAirsysVersion .1.11.4.10 -- backupBattStatus .1.12 -- liBattStatus .1.12.1 -- liBattPercentCharge .1.12.1.1 -- liBattRunning .1.12.1.2 -- config .2 -- eventSensorBasics .2.1 -- esNumberEventSensors .2.1.1 -- esTable .2.1.2 -- esEntry .2.1.2.1 -- esIndex .2.1.2.1.1 -- esName .2.1.2.1.2 -- esID .2.1.2.1.3 -- esNumberTempSensors .2.1.2.1.4 -- esTempReportingMode .2.1.2.1.5 -- esNumberCCs .2.1.2.1.6 -- esCCReportingMode .2.1.2.1.7 -- esNumberHumidSensors .2.1.2.1.8 -- esHumidReportingMode .2.1.2.1.9 -- esNumberNoiseSensors .2.1.2.1.10 -- esNoiseReportingMode .2.1.2.1.11 -- esNumberAirflowSensors .2.1.2.1.12 -- esAirflowReportingMode .2.1.2.1.13 -- esNumberAnalog .2.1.2.1.14 -- esAnalogReportingMode .2.1.2.1.15 -- esNumberOutputs .2.1.2.1.16 -- esOutputReportingMode .2.1.2.1.17 -- esTempCombinedStatus .2.1.2.1.18 -- esCCCombinedStatusBlock1 .2.1.2.1.19 -- esCCCombinedStatusBlock2 .2.1.2.1.20 -- esCCCombinedStatusBlock3 .2.1.2.1.21 -- esCCCombinedStatusBlock4 .2.1.2.1.22 -- esCCCombinedStatusBlock5 .2.1.2.1.23 -- esCCCombinedStatusBlock6 .2.1.2.1.24 -- esCCCombinedStatusBlock7 .2.1.2.1.25 -- esCCCombinedStatusBlock8 .2.1.2.1.26 -- esHumidCombinedStatus .2.1.2.1.27 -- esAnalogCombinedStatusBlock1 .2.1.2.1.28 -- esAnalogCombinedStatusBlock2 .2.1.2.1.29 -- esAnalogCombinedStatusBlock3 .2.1.2.1.30 -- esAnalogCombinedStatusBlock4 .2.1.2.1.31 -- esAnalogCombinedStatusBlock5 .2.1.2.1.32 -- esAnalogCombinedStatusBlock6 .2.1.2.1.33 -- esOutputCombinedStatusBlock1 .2.1.2.1.34 -- esOutputCombinedStatusBlock2 .2.1.2.1.35 -- esNewSensors .2.1.3 -- eventSensorPointConfig .2.2 -- esPointConfigTempTable .2.2.1 -- esPointConfigTempEntry .2.2.1.1 -- espcTempIndexES .2.2.1.1.1 -- espcTempIndexPoint .2.2.1.1.2 -- espcTempEnable .2.2.1.1.3 -- espcTempScale .2.2.1.1.4 -- espcTempDeadband .2.2.1.1.5 -- espcTempVHighTemp .2.2.1.1.6 -- espcTempVHighActions .2.2.1.1.7 -- espcTempVHighTrapnum .2.2.1.1.8 -- espcTempVHighClass .2.2.1.1.9 -- espcTempHighTemp .2.2.1.1.10 -- espcTempHighActions .2.2.1.1.11 -- espcTempHighTrapnum .2.2.1.1.12 -- espcTempHighClass .2.2.1.1.13 -- espcTempNormalActions .2.2.1.1.14 -- espcTempNormalTrapnum .2.2.1.1.15 -- espcTempNormalClass .2.2.1.1.16 -- espcTempLowTemp .2.2.1.1.17 -- espcTempLowActions .2.2.1.1.18 -- espcTempLowTrapnum .2.2.1.1.19 -- espcTempLowClass .2.2.1.1.20 -- espcTempVLowTemp .2.2.1.1.21 -- espcTempVLowActions .2.2.1.1.22 -- espcTempVLowTrapnum .2.2.1.1.23 -- espcTempVLowClass .2.2.1.1.24 -- espcTempGroup .2.2.1.1.25 -- esPointConfigCCTable .2.2.2 -- esPointConfigCCEntry .2.2.2.1 -- espcCCIndexES .2.2.2.1.1 -- espcCCIndexPoint .2.2.2.1.2 -- espcCCEnable .2.2.2.1.3 -- espcCCName .2.2.2.1.4 -- espcCCEventState .2.2.2.1.5 -- espcCCThreshold .2.2.2.1.6 -- espcCCEventActions .2.2.2.1.7 -- espcCCEventTrapnum .2.2.2.1.8 -- espcCCEventClass .2.2.2.1.9 -- espcCCNormalActions .2.2.2.1.10 -- espcCCNormalTrapnum .2.2.2.1.11 -- espcCCNormalClass .2.2.2.1.12 -- espcCCAlarmAlias .2.2.2.1.13 -- espcCCNormalAlias .2.2.2.1.14 -- espcCCNormalThreshold .2.2.2.1.15 -- espcCCOverrideGlobalReminder .2.2.2.1.16 -- espcCCReminderInterval .2.2.2.1.17 -- espcCCGroup .2.2.2.1.18 -- esPointConfigHumidTable .2.2.3 -- esPointConfigHumidEntry .2.2.3.1 -- espcHumidIndexES .2.2.3.1.1 -- espcHumidIndexPoint .2.2.3.1.2 -- espcHumidEnable .2.2.3.1.3 -- espcHumidDeadband .2.2.3.1.4 -- espcHumidVHighHumid .2.2.3.1.5 -- espcHumidVHighActions .2.2.3.1.6 -- espcHumidVHighTrapnum .2.2.3.1.7 -- espcHumidVHighClass .2.2.3.1.8 -- espcHumidHighHumid .2.2.3.1.9 -- espcHumidHighActions .2.2.3.1.10 -- espcHumidHighTrapnum .2.2.3.1.11 -- espcHumidHighClass .2.2.3.1.12 -- espcHumidNormalActions .2.2.3.1.13 -- espcHumidNormalTrapnum .2.2.3.1.14 -- espcHumidNormalClass .2.2.3.1.15 -- espcHumidLowHumid .2.2.3.1.16 -- espcHumidLowActions .2.2.3.1.17 -- espcHumidLowTrapnum .2.2.3.1.18 -- espcHumidLowClass .2.2.3.1.19 -- espcHumidVLowHumid .2.2.3.1.20 -- espcHumidVLowActions .2.2.3.1.21 -- espcHumidVLowTrapnum .2.2.3.1.22 -- espcHumidVLowClass .2.2.3.1.23 -- espcHumidGroup .2.2.3.1.24 -- esPointConfigAITable .2.2.5 -- esPointConfigAIEntry .2.2.5.1 -- espcAIIndexES .2.2.5.1.1 -- espcAIIndexPoint .2.2.5.1.2 -- espcAIEnable .2.2.5.1.3 -- espcAIDeadband .2.2.5.1.5 -- espcAIVhighValue .2.2.5.1.6 -- espcAIVhighActions .2.2.5.1.7 -- espcAIVhighTrapnum .2.2.5.1.8 -- espcAIVhighClass .2.2.5.1.9 -- espcAIHighValue .2.2.5.1.10 -- espcAIHighActions .2.2.5.1.11 -- espcAIHighTrapnum .2.2.5.1.12 -- espcAIHighClass .2.2.5.1.13 -- espcAINormalActions .2.2.5.1.14 -- espcAINormalTrapnum .2.2.5.1.15 -- espcAINormalClass .2.2.5.1.16 -- espcAILowValue .2.2.5.1.17 -- espcAILowActions .2.2.5.1.18 -- espcAILowTrapnum .2.2.5.1.19 -- espcAILowClass .2.2.5.1.20 -- espcAIVlowValue .2.2.5.1.21 -- espcAIVlowActions .2.2.5.1.22 -- espcAIVlowTrapnum .2.2.5.1.23 -- espcAIVlowClass .2.2.5.1.24 -- espcAIConvUnitName .2.2.5.1.25 -- espcAIConvHighValue .2.2.5.1.26 -- espcAIConvHighUnit .2.2.5.1.27 -- espcAIConvLowValue .2.2.5.1.29 -- espcAIConvLowUnit .2.2.5.1.30 -- espcAIDisplayFormat .2.2.5.1.32 -- espcAIGroup .2.2.5.1.33 -- esPointConfigOutputTable .2.2.6 -- esPointConfigOutputEntry .2.2.6.1 -- espcOutputIndexES .2.2.6.1.1 -- espcOutputIndexPoint .2.2.6.1.2 -- espcOutputEnable .2.2.6.1.3 -- espcOutputActiveState .2.2.6.1.4 -- espcOutputType .2.2.6.1.5 -- espcOutputAliasValue .2.2.6.1.6 -- espcOutputAliasColor .2.2.6.1.7 -- espcOutputActiveAlias .2.2.6.1.10 -- espcOutputActiveColor .2.2.6.1.11 -- espcOutputActiveActions .2.2.6.1.12 -- espcOutputActiveTrapnum .2.2.6.1.13 -- espcOutputActiveClass .2.2.6.1.14 -- espcOutputInactiveAlias .2.2.6.1.20 -- espcOutputInactiveColor .2.2.6.1.21 -- espcOutputInactiveActions .2.2.6.1.22 -- espcOutputInactiveTrapnum .2.2.6.1.23 -- espcOutputInactiveClass .2.2.6.1.24 -- espcOutputGroup .2.2.6.1.25 -- serialPorts .2.3 -- numberPorts .2.3.1 -- portConfigTable .2.3.2 -- portConfigEntry .2.3.2.1 -- portConfigIndex .2.3.2.1.1 -- portConfigBaud .2.3.2.1.2 -- portConfigDataFormat .2.3.2.1.3 -- portConfigStripPtOutputLfs .2.3.2.1.4 -- portConfigStripPtInputLfs .2.3.2.1.5 -- portConfigMaskEnable .2.3.2.1.7 -- portConfigDAEnable .2.3.2.1.8 -- portConfigStoreAlarmsDPT .2.3.2.1.9 -- portConfigRecordTimeout .2.3.2.1.10 -- portConfigDataType .2.3.2.1.11 -- portConfigEtxToCRLF .2.3.2.1.12 -- portConfigMLREnable .2.3.2.1.13 -- portConfigMLRStartField1Pos .2.3.2.1.14 -- portConfigMLRStartField1Text .2.3.2.1.15 -- portConfigMLRStartField2Pos .2.3.2.1.16 -- portConfigMLRStartField2Text .2.3.2.1.17 -- portConfigMLRNumLinesBefore .2.3.2.1.18 -- portConfigMLREndDetection .2.3.2.1.19 -- portConfigMLRLineCount .2.3.2.1.20 -- portConfigMLREndField1Pos .2.3.2.1.21 -- portConfigMLREndField1Text .2.3.2.1.22 -- portConfigMLREndField2Pos .2.3.2.1.23 -- portConfigMLREndField2Text .2.3.2.1.24 -- portConfigMLRUseComplexRules .2.3.2.1.25 -- portConfigBufferPT .2.3.2.1.26 -- portConfigId .2.3.2.1.27 -- portConfigMode .2.3.2.1.28 -- portConfigHsk .2.3.2.1.29 -- network .2.4 -- interface .2.4.1 -- ethernet .2.4.1.1 -- ethernet1 .2.4.1.1.1 -- eth1Mode .2.4.1.1.1.1 -- eth1Address .2.4.1.1.1.2 -- eth1SubnetMask .2.4.1.1.1.3 -- eth1Router .2.4.1.1.1.4 -- eth1VLAN .2.4.1.1.1.5 -- eth1VLAN1 .2.4.1.1.1.5.1 -- eth1VLAN1ID .2.4.1.1.1.5.1.1 -- eth1VLAN1Priority .2.4.1.1.1.5.1.2 -- eth1VLAN1Address .2.4.1.1.1.5.1.3 -- eth1VLAN1SubnetMask .2.4.1.1.1.5.1.4 -- eth1VLAN1Router .2.4.1.1.1.5.1.5 -- eth1VLAN2 .2.4.1.1.1.5.2 -- eth1VLAN2ID .2.4.1.1.1.5.2.1 -- eth1VLAN2Priority .2.4.1.1.1.5.2.2 -- eth1VLAN2Address .2.4.1.1.1.5.2.3 -- eth1VLAN2SubnetMask .2.4.1.1.1.5.2.4 -- eth1VLAN2Router .2.4.1.1.1.5.2.5 -- eth1VLAN3 .2.4.1.1.1.5.3 -- eth1VLAN3ID .2.4.1.1.1.5.3.1 -- eth1VLAN3Priority .2.4.1.1.1.5.3.2 -- eth1VLAN3Address .2.4.1.1.1.5.3.3 -- eth1VLAN3SubnetMask .2.4.1.1.1.5.3.4 -- eth1VLAN3Router .2.4.1.1.1.5.3.5 -- eth1VLAN4 .2.4.1.1.1.5.4 -- eth1VLAN4ID .2.4.1.1.1.5.4.1 -- eth1VLAN4Priority .2.4.1.1.1.5.4.2 -- eth1VLAN4Address .2.4.1.1.1.5.4.3 -- eth1VLAN4SubnetMask .2.4.1.1.1.5.4.4 -- eth1VLAN4Router .2.4.1.1.1.5.4.5 -- eth1VLAN5 .2.4.1.1.1.5.5 -- eth1VLAN5ID .2.4.1.1.1.5.5.1 -- eth1VLAN5Priority .2.4.1.1.1.5.5.2 -- eth1VLAN5Address .2.4.1.1.1.5.5.3 -- eth1VLAN5SubnetMask .2.4.1.1.1.5.5.4 -- eth1VLAN5Router .2.4.1.1.1.5.5.5 -- eth1VLAN6 .2.4.1.1.1.5.6 -- eth1VLAN6ID .2.4.1.1.1.5.6.1 -- eth1VLAN6Priority .2.4.1.1.1.5.6.2 -- eth1VLAN6Address .2.4.1.1.1.5.6.3 -- eth1VLAN6SubnetMask .2.4.1.1.1.5.6.4 -- eth1VLAN6Router .2.4.1.1.1.5.6.5 -- eth1MAC .2.4.1.1.1.6 -- eth1IPv6 .2.4.1.1.1.7 -- eth1IPv6Mode .2.4.1.1.1.7.1 -- eth1IPv6Static .2.4.1.1.1.7.2 -- eth1IPv6StaticAddress .2.4.1.1.1.7.2.1 -- eth1IPv6StaticRouter .2.4.1.1.1.7.2.2 -- eth1IPv6Auto .2.4.1.1.1.7.3 -- eth1IPv6AutoAddress1 .2.4.1.1.1.7.3.1 -- eth1IPv6AutoAddress2 .2.4.1.1.1.7.3.2 -- eth1IPv6AutoAddress3 .2.4.1.1.1.7.3.3 -- eth1IPv6AutoAddress4 .2.4.1.1.1.7.3.4 -- eth1IPv6LinkLocalAddress .2.4.1.1.1.7.4 -- ethernet2 .2.4.1.1.2 -- eth2Mode .2.4.1.1.2.1 -- eth2Address .2.4.1.1.2.2 -- eth2SubnetMask .2.4.1.1.2.3 -- eth2Router .2.4.1.1.2.4 -- eth2VLAN .2.4.1.1.2.5 -- eth2VLAN1 .2.4.1.1.2.5.1 -- eth2VLAN1ID .2.4.1.1.2.5.1.1 -- eth2VLAN1Priority .2.4.1.1.2.5.1.2 -- eth2VLAN1Address .2.4.1.1.2.5.1.3 -- eth2VLAN1SubnetMask .2.4.1.1.2.5.1.4 -- eth2VLAN1Router .2.4.1.1.2.5.1.5 -- eth2VLAN2 .2.4.1.1.2.5.2 -- eth2VLAN2ID .2.4.1.1.2.5.2.1 -- eth2VLAN2Priority .2.4.1.1.2.5.2.2 -- eth2VLAN2Address .2.4.1.1.2.5.2.3 -- eth2VLAN2SubnetMask .2.4.1.1.2.5.2.4 -- eth2VLAN2Router .2.4.1.1.2.5.2.5 -- eth2VLAN3 .2.4.1.1.2.5.3 -- eth2VLAN3ID .2.4.1.1.2.5.3.1 -- eth2VLAN3Priority .2.4.1.1.2.5.3.2 -- eth2VLAN3Address .2.4.1.1.2.5.3.3 -- eth2VLAN3SubnetMask .2.4.1.1.2.5.3.4 -- eth2VLAN3Router .2.4.1.1.2.5.3.5 -- eth2VLAN4 .2.4.1.1.2.5.4 -- eth2VLAN4ID .2.4.1.1.2.5.4.1 -- eth2VLAN4Priority .2.4.1.1.2.5.4.2 -- eth2VLAN4Address .2.4.1.1.2.5.4.3 -- eth2VLAN4SubnetMask .2.4.1.1.2.5.4.4 -- eth2VLAN4Router .2.4.1.1.2.5.4.5 -- eth2VLAN5 .2.4.1.1.2.5.5 -- eth2VLAN5ID .2.4.1.1.2.5.5.1 -- eth2VLAN5Priority .2.4.1.1.2.5.5.2 -- eth2VLAN5Address .2.4.1.1.2.5.5.3 -- eth2VLAN5SubnetMask .2.4.1.1.2.5.5.4 -- eth2VLAN5Router .2.4.1.1.2.5.5.5 -- eth2VLAN6 .2.4.1.1.2.5.6 -- eth2VLAN6ID .2.4.1.1.2.5.6.1 -- eth2VLAN6Priority .2.4.1.1.2.5.6.2 -- eth2VLAN6Address .2.4.1.1.2.5.6.3 -- eth2VLAN6SubnetMask .2.4.1.1.2.5.6.4 -- eth2VLAN6Router .2.4.1.1.2.5.6.5 -- eth2MAC .2.4.1.1.2.6 -- eth2IPv6 .2.4.1.1.2.7 -- eth2IPv6Mode .2.4.1.1.2.7.1 -- eth2IPv6Static .2.4.1.1.2.7.2 -- eth2IPv6StaticAddress .2.4.1.1.2.7.2.1 -- eth2IPv6StaticRouter .2.4.1.1.2.7.2.2 -- eth2IPv6Auto .2.4.1.1.2.7.3 -- eth2IPv6AutoAddress1 .2.4.1.1.2.7.3.1 -- eth2IPv6AutoAddress2 .2.4.1.1.2.7.3.2 -- eth2IPv6AutoAddress3 .2.4.1.1.2.7.3.3 -- eth2IPv6AutoAddress4 .2.4.1.1.2.7.3.4 -- eth2IPv6LinkLocalAddress .2.4.1.1.2.7.4 -- defaultRouter .2.4.2 -- dnsTable .2.4.3 -- dnsEntry .2.4.3.1 -- dnsIndex .2.4.3.1.1 -- dnsAddress .2.4.3.1.2 -- hostname .2.4.4 -- hostTable .2.4.5 -- hostEntry .2.4.5.1 -- hostIndex .2.4.5.1.1 -- hostDeclaration .2.4.5.1.2 -- ncpDuplex .2.4.6 -- ncpTimeout .2.4.7 -- snmp .2.4.8 -- snmpAgentEnable .2.4.8.1 -- snmpNotificationCaptureEnable .2.4.8.5 -- snmpNotificationCaptureFile .2.4.8.6 -- snmpNotificationTx .2.4.8.7 -- snmpNtfnAttempts .2.4.8.7.1 -- snmpNtfnTimeout .2.4.8.7.2 -- snmpNtfnCycles .2.4.8.7.3 -- snmpNtfnSnooze .2.4.8.7.4 -- snmpProxy .2.4.8.8 -- snmpProxyTable .2.4.8.8.1 -- snmpProxyEntry .2.4.8.8.1.1 -- snmpProxyIndex .2.4.8.8.1.1.1 -- snmpProxyEgressOIDBranch .2.4.8.8.1.1.2 -- snmpProxyIP .2.4.8.8.1.1.3 -- snmpProxyPort .2.4.8.8.1.1.4 -- snmpProxyIngressOIDBranch .2.4.8.8.1.1.5 -- snmpProxyName .2.4.8.8.1.1.6 -- snmpPoll .2.4.8.9 -- snmpPMode .2.4.8.9.1 -- snmpPBufferFile .2.4.8.9.2 -- snmpPBufferAllPeriod .2.4.8.9.3 -- snmpPRequestTable .2.4.8.9.4 -- snmpPRequestEntry .2.4.8.9.4.1 -- snmpPRequestIndex .2.4.8.9.4.1.1 -- snmpPRequestDescription .2.4.8.9.4.1.2 -- snmpPRequestAgent .2.4.8.9.4.1.3 -- snmpPRequestReadcom .2.4.8.9.4.1.4 -- snmpPRequestOID .2.4.8.9.4.1.5 -- snmpPRequestPeriod .2.4.8.9.4.1.6 -- snmpPRequestID .2.4.8.9.4.1.7 -- snmpPRequestThreshold .2.4.8.9.4.1.8 -- snmpPRequestResultStatus .2.4.8.9.4.1.10 -- snmpPRequestResultValue .2.4.8.9.4.1.11 -- snmpPRequestResultTime .2.4.8.9.4.1.12 -- snmpPRequestResultType .2.4.8.9.4.1.13 -- ftpPush .2.4.9 -- ftpPushEnable .2.4.9.1 -- ftpPushServer .2.4.9.2 -- ftpPushAccount .2.4.9.5 -- ftpPushDirectory .2.4.9.6 -- ftpPushperiod .2.4.9.7 -- ftpPushPushFileTable .2.4.9.8 -- ftpPushPushFileEntry .2.4.9.8.1 -- ftpPushPushFileIndex .2.4.9.8.1.1 -- ftpPushPushFile .2.4.9.8.1.2 -- ftpPushPushAudit .2.4.9.9 -- ftpPushPushAlarms .2.4.9.10 -- ftpPushRemoteFileTable .2.4.9.11 -- ftpPushRemoteFileEntry .2.4.9.11.1 -- ftpPushRemoteFileIndex .2.4.9.11.1.1 -- ftpPushRemoteFileName .2.4.9.11.1.2 -- ftpPushRemoteAlarmName .2.4.9.12 -- ftpPushPassive .2.4.9.13 -- ftpPushIncludeDate .2.4.9.14 -- ftpPushIncludeTime .2.4.9.15 -- ftpPushIncludeSeq .2.4.9.16 -- ftpPushPermissions .2.4.9.17 -- ppp .2.4.10 -- pppDial .2.4.10.1 -- pppDialEnable .2.4.10.1.1 -- pppDialNumber .2.4.10.1.2 -- pppDialIdleTimeout .2.4.10.1.5 -- pppDialRetries .2.4.10.1.6 -- pppDialCDTimeout .2.4.10.1.7 -- pppDialLoginTimeout .2.4.10.1.8 -- pppDialMdmInit .2.4.10.1.9 -- pppDialSuggestIP .2.4.10.1.10 -- pppDialPlainLogin .2.4.10.1.11 -- pppHost .2.4.10.2 -- pppHostEnable .2.4.10.2.1 -- pppHostIdleTimeout .2.4.10.2.2 -- pppHostLocalIP .2.4.10.2.3 -- pppHostRemoteIP .2.4.10.2.4 -- routing .2.4.11 -- pppRoutingEnable .2.4.11.1 -- ethRoutingEnable .2.4.11.2 -- ethRoutingNATEnable .2.4.11.3 -- routingInterface .2.4.11.4 -- eth2WanRoutingEnable .2.4.11.5 -- netSecurity .2.4.12 -- ipRestriction .2.4.12.1 -- ipRestrictionTable .2.4.12.1.1 -- ipRestrictionEntry .2.4.12.1.1.1 -- ipRestrictionIndex .2.4.12.1.1.1.1 -- ipRestrictionEnable .2.4.12.1.1.1.2 -- ipRestrictionMask .2.4.12.1.1.1.3 -- rts .2.4.13 -- rtsFileTable .2.4.13.1 -- rtsFileEntry .2.4.13.1.1 -- rtsFileIndex .2.4.13.1.1.1 -- rtsFileMode .2.4.13.1.1.2 -- rtsFileShowAnswer .2.4.13.1.1.3 -- rtsFileReqXON .2.4.13.1.1.4 -- rtsFileTimeout .2.4.13.1.1.5 -- rtsFileEmptyClose .2.4.13.1.1.6 -- rtsFilePushHost .2.4.13.1.1.7 -- rtsFilePushPort .2.4.13.1.1.8 -- rtsFilePushRetryTimer .2.4.13.1.1.9 -- rtsAlarms .2.4.13.2 -- rtsAlarmsMode .2.4.13.2.1 -- rtsAlarmsShowAnswer .2.4.13.2.2 -- rtsAlarmsReqXON .2.4.13.2.3 -- rtsAlarmsTimeout .2.4.13.2.4 -- rtsAlarmsEmptyClose .2.4.13.2.5 -- rtsAlarmsPushHost .2.4.13.2.6 -- rtsAlarmsPushPort .2.4.13.2.7 -- rtsAlarmsPushRetryTimer .2.4.13.2.8 -- trap .2.4.14 -- trapInclude .2.4.14.1 -- trapIncludeDateTime .2.4.14.1.1 -- trapIncludeSiteName .2.4.14.1.2 -- trapIncludeSensorID .2.4.14.1.3 -- trapIncludeUDName .2.4.14.1.4 -- trapIncludeUDState .2.4.14.1.5 -- trapIncludeSourceAddress .2.4.14.1.6 -- trapAuthFailEnable .2.4.14.2 -- routeTest .2.4.15 -- routeTestEnable .2.4.15.1 -- routeTestPeriod .2.4.15.2 -- routeTestAddressTable .2.4.15.3 -- routeTestAddressEntry .2.4.15.3.1 -- routeTestAddressIndex .2.4.15.3.1.1 -- routeTestAddress .2.4.15.3.1.2 -- wireless .2.4.16 -- wirelessMode .2.4.16.1 -- wirelessAPN .2.4.16.2 -- wirelessIdleTimeout .2.4.16.3 -- wirelessDRE .2.4.16.9 -- wirelessPPPUsername .2.4.16.10 -- wirelessFirewall .2.4.16.11 -- wirelessKeepaliveThreshold .2.4.16.12 -- wirelessPPPDebug .2.4.16.13 -- wirelessConnectivity .2.4.16.20 -- wirelessConnEnable .2.4.16.20.1 -- wirelessConnCheckInterval .2.4.16.20.2 -- wirelessConnFailThreshold .2.4.16.20.3 -- wirelessConnIP1 .2.4.16.20.10 -- wirelessConnIP2 .2.4.16.20.11 -- email .2.4.17 -- emailServer .2.4.17.1 -- emailDomain .2.4.17.2 -- emailAuthEnable .2.4.17.3 -- netAdvanced .2.4.18 -- arpFilter .2.4.18.1 -- web .2.4.19 -- webEnable .2.4.19.1 -- webPort .2.4.19.2 -- webTimeout .2.4.19.3 -- webXMLProxy .2.4.19.4 -- wxpEnable .2.4.19.4.1 -- wxpDeviceTable .2.4.19.4.2 -- wxpDeviceEntry .2.4.19.4.2.1 -- wxpDeviceIndex .2.4.19.4.2.1.1 -- wxpDeviceEnable .2.4.19.4.2.1.2 -- wxpDeviceIPAddress .2.4.19.4.2.1.3 -- wxpDevicePort .2.4.19.4.2.1.4 -- wxpDeviceRemoteFile .2.4.19.4.2.1.5 -- wxpDeviceLocalFile .2.4.19.4.2.1.6 -- wxpDeviceTimeout .2.4.19.4.2.1.7 -- wxpDeviceTimestamp .2.4.19.4.2.1.8 -- ethExpan .2.4.20 -- ethExpanIp .2.4.20.1 -- ethExpanMask .2.4.20.2 -- ethExpanCardTable .2.4.20.3 -- ethExpanCardEntry .2.4.20.3.1 -- ethExpanCardIndex .2.4.20.3.1.1 -- ethExpanCardMAC .2.4.20.3.1.2 -- ethExpanDHCP .2.4.20.6 -- ethExpanDHCPStartIp .2.4.20.6.1 -- ethExpanDHCPLeaseTime .2.4.20.6.2 -- ipv6 .2.4.21 -- ipv6DefaultRouter .2.4.21.1 -- cpe .2.4.22 -- cpeTable .2.4.22.1 -- cpeEntry .2.4.22.1.1 -- cpeIndex .2.4.22.1.1.1 -- cpeHost .2.4.22.1.1.2 -- cpeName .2.4.22.1.1.3 -- cpeDescription .2.4.22.1.1.4 -- cpeKeepalive .2.4.22.1.1.5 -- cpeThreshold .2.4.22.1.1.6 -- cpeEventReminderInterval .2.4.22.1.1.7 -- cpeKeepaliveTicks .2.4.22.1.1.20 -- cpePingSize .2.4.22.1.1.21 -- cpeInfoReset .2.4.22.1.1.30 -- cpeInfoNumReq .2.4.22.1.1.31 -- cpeInfoNumGoodResp .2.4.22.1.1.32 -- cpeInfoNumBadResp .2.4.22.1.1.33 -- cpeInfoNumLostResp .2.4.22.1.1.34 -- cpeInfoPercentLoss .2.4.22.1.1.35 -- cpeInfoPercentBad .2.4.22.1.1.36 -- dnp3 .2.4.23 -- dnp3General .2.4.23.1 -- dnp3Mode .2.4.23.1.1 -- dnp3SelfAddressEnable .2.4.23.1.2 -- dnp3KeepaliveTimeout .2.4.23.1.3 -- dnp3MaxRXFragmentSize .2.4.23.1.4 -- dnp3MaxTXFragmentSize .2.4.23.1.5 -- dnp3UnsolResponseEnable .2.4.23.1.6 -- dnp3UnsolResponseTimeout .2.4.23.1.7 -- dnp3UnsolResponseRetries .2.4.23.1.8 -- dnp3LogFilter .2.4.23.1.9 -- dnp3Outstation .2.4.23.2 -- dnp3OutstationTCPPort .2.4.23.2.1 -- dnp3OutstationDNP3Address .2.4.23.2.2 -- dnp3OutstationMasterIPAddress .2.4.23.2.3 -- dnp3OutstationMasterDNP3Address .2.4.23.2.4 -- dnp3OutstationUnsolResponseDNP3Address .2.4.23.2.5 -- dnp3Master .2.4.23.3 -- dnp3Error .2.4.23.4 -- dnp3DuplicateFragmentCount .2.4.23.4.1 -- dnp3CollidingFragmentCount .2.4.23.4.2 -- dnp3UnsolResponseCfmFailCount .2.4.23.4.3 -- dnp3SolCfmFailCount .2.4.23.4.4 -- dnp3ObjParseErrorCount .2.4.23.4.5 -- dnp3FrameParseErrorCount .2.4.23.4.6 -- dnp3DiscardedFrameCount .2.4.23.4.7 -- dnp3BadBlockCount .2.4.23.4.8 -- dnp3UnsolResponseRetryCount .2.4.23.4.9 -- dnp3UnsupportedFrameCount .2.4.23.4.10 -- dnp3Status .2.4.23.5 -- dnp3OutstationCount .2.4.23.5.1 -- dnp3ConnPeer .2.4.23.5.2 -- dnp3StartTime .2.4.23.5.3 -- dnp3EventAwaitingSolCfmCount .2.4.23.5.4 -- dnp3EventAwaitingUnsolCfmCount .2.4.23.5.5 -- dnp3EventCount .2.4.23.5.6 -- dnp3EventClass1Count .2.4.23.5.7 -- dnp3EventClass2Count .2.4.23.5.8 -- dnp3EventClass3Count .2.4.23.5.9 -- dnp3RxFragmentTime .2.4.23.5.10 -- dnp3TxFragmentTime .2.4.23.5.11 -- dnp3TxCachedResponseCount .2.4.23.5.12 -- dnp3TxUnsolResponseCount .2.4.23.5.13 -- dnp3TxSolResponseCount .2.4.23.5.14 -- dnp3TxFragmentReqCfmCount .2.4.23.5.15 -- dnp3RxUnsolResponseCfmCount .2.4.23.5.16 -- dnp3RxSolResponseCfmCount .2.4.23.5.17 -- dnp3RxFunctionCount .2.4.23.5.18 -- dnp3RxReadFunctionCount .2.4.23.5.19 -- dnp3RxWriteFunctionCount .2.4.23.5.20 -- dnp3RxDirOpFunctionCount .2.4.23.5.21 -- dnp3RxEnableURCount .2.4.23.5.22 -- dnp3RxDisableURCount .2.4.23.5.23 -- dnp3RxSolObjectCount .2.4.23.5.40 -- dnp3TxSolObjectCount .2.4.23.5.41 -- dnp3RxFrameTime .2.4.23.5.42 -- dnp3TxFrameTime .2.4.23.5.43 -- dnp3TxFrameCount .2.4.23.5.44 -- dnp3RxAcceptedFrameCount .2.4.23.5.45 -- dnp3RxSupportedFrameCount .2.4.23.5.46 -- modem .2.5 -- modemFormat .2.5.1 -- modemInitString .2.5.2 -- modemCallAttempts .2.5.4 -- modemCallDelay .2.5.5 -- modemCmdTimout .2.5.6 -- modemGoto .2.5.7 -- modemClid .2.5.8 -- modemCLIDEnable .2.5.8.1 -- modemCLIDNumberTable .2.5.8.2 -- modemCLIDNumberEntry .2.5.8.2.1 -- modemCLIDNumberIndex .2.5.8.2.1.1 -- modemCLIDNumber .2.5.8.2.1.2 -- modemTAPInitString .2.5.9 -- modemTAP8N1 .2.5.10 -- time .2.8 -- clock .2.8.1 -- console .2.10 -- consoleDuplex .2.10.1 -- consoleTimeout .2.10.2 -- consoleConfirm .2.10.7 -- unitSecurity .2.11 -- secCore .2.11.1 -- scShowPasswordPrompt .2.11.1.1 -- scConsoleLoginRequired .2.11.1.2 -- scModemLoginRequired .2.11.1.3 -- scTelnetLoginRequired .2.11.1.4 -- scTelnetPTLoginRequired .2.11.1.5 -- scRTSLoginRequired .2.11.1.6 -- scAuthMode .2.11.1.7 -- scRightsGroup .2.11.1.8 -- secUserTable .2.11.2 -- secUserEntry .2.11.2.1 -- secUserIndex .2.11.2.1.1 -- secUserEnable .2.11.2.1.2 -- secUserConnectVia .2.11.2.1.5 -- secUserLoginTo .2.11.2.1.6 -- secUserAccessFile .2.11.2.1.7 -- secUserPTEscapeTo .2.11.2.1.9 -- secUserPPPType .2.11.2.1.10 -- secUserRights .2.11.2.1.11 -- secUserEventsReadAccess .2.11.2.1.13 -- secUserAuditReadAccess .2.11.2.1.14 -- secUserEventsWriteAccess .2.11.2.1.16 -- secUserAuditWriteAccess .2.11.2.1.17 -- secUserExpiration .2.11.2.1.18 -- secUserCallbackNumber1 .2.11.2.1.19 -- secUserCallbackNumber2 .2.11.2.1.20 -- secUserCallbackNumber3 .2.11.2.1.21 -- secUserChallengeTelnetMode .2.11.2.1.22 -- secUserChallengeModemMode .2.11.2.1.23 -- secUserChallengeConsoleMode .2.11.2.1.24 -- secUserChallengeTelnetSendTo .2.11.2.1.25 -- secUserChallengeModemSendTo .2.11.2.1.26 -- secUserChallengeExpiration .2.11.2.1.27 -- secFactory .2.11.3 -- sfEnable .2.11.3.1 -- sfSecret .2.11.3.2 -- secSSH .2.11.4 -- secVPN .2.11.5 -- event .2.12 -- evCore .2.12.1 -- evClassNameTable .2.12.1.1 -- evClassNameEntry .2.12.1.1.1 -- evClassNameIndex .2.12.1.1.1.1 -- evClassName .2.12.1.1.1.2 -- evReminderInterval .2.12.1.2 -- evLog .2.12.1.3 -- evLogEnable .2.12.1.3.1 -- evLogStoreAlarm .2.12.1.3.2 -- evLogMaxSize .2.12.1.3.3 -- evLogStoreSensor .2.12.1.3.4 -- evLogTimeStampAlarms .2.12.1.3.5 -- evLogPrependName .2.12.1.3.6 -- evMgmt .2.12.1.4 -- evMgmtReprocess .2.12.1.4.3 -- evData .2.12.2 -- evdCore .2.12.2.1 -- evdExitOnTrue .2.12.2.1.1 -- evdFilterAction .2.12.2.1.2 -- evdWildCardChar .2.12.2.1.3 -- evdTable .2.12.2.2 -- evdEntry .2.12.2.2.1 -- evdIndex .2.12.2.2.1.1 -- evdEnable .2.12.2.2.1.2 -- evdName .2.12.2.2.1.3 -- evdEquation .2.12.2.2.1.4 -- evdThreshold .2.12.2.2.1.5 -- evdAutoclear .2.12.2.2.1.6 -- evdClearInterval .2.12.2.2.1.7 -- evdClearTime .2.12.2.2.1.8 -- evdActions .2.12.2.2.1.9 -- evdClass .2.12.2.2.1.10 -- evdTrapNum .2.12.2.2.1.11 -- evdMode .2.12.2.2.1.12 -- evdFieldTable .2.12.2.3 -- evdFieldEntry .2.12.2.3.1 -- evdFieldIndex .2.12.2.3.1.1 -- evdFieldStart .2.12.2.3.1.2 -- evdFieldLength .2.12.2.3.1.3 -- evdFieldName .2.12.2.3.1.4 -- evdFieldLine .2.12.2.3.1.5 -- evdFieldType .2.12.2.3.1.6 -- evdMacroTable .2.12.2.4 -- evdMacroEntry .2.12.2.4.1 -- evdMacroIndex .2.12.2.4.1.1 -- evdMacroName .2.12.2.4.1.2 -- evdMacroEquation .2.12.2.4.1.3 -- evNoData1 .2.12.3 -- evNoData1Enable .2.12.3.1 -- evNoData1Actions .2.12.3.2 -- evNoData1Message .2.12.3.3 -- evNoData1TrapNum .2.12.3.4 -- evNoData1Class .2.12.3.5 -- evNoData1Sched1Begin .2.12.3.6 -- evNoData1Sched1End .2.12.3.7 -- evNoData1Sched1Duration .2.12.3.8 -- evNoData1Sched2Begin .2.12.3.9 -- evNoData1Sched2End .2.12.3.10 -- evNoData1Sched2Duration .2.12.3.11 -- evNoData1PortEnableTable .2.12.3.12 -- evNoData1PortEnableEntry .2.12.3.12.1 -- evNoData1PortEnableIndex .2.12.3.12.1.1 -- evNoData1PortEnable .2.12.3.12.1.2 -- evNoData1Exclusions .2.12.3.13 -- evNoData1Days .2.12.3.14 -- evNoData2 .2.12.4 -- evNoData2Enable .2.12.4.1 -- evNoData2Actions .2.12.4.2 -- evNoData2Message .2.12.4.3 -- evNoData2TrapNum .2.12.4.4 -- evNoData2Class .2.12.4.5 -- evNoData2Sched1Begin .2.12.4.6 -- evNoData2Sched1End .2.12.4.7 -- evNoData2Sched1Duration .2.12.4.8 -- evNoData2Sched2Begin .2.12.4.9 -- evNoData2Sched2End .2.12.4.10 -- evNoData2Sched2Duration .2.12.4.11 -- evNoData2PortEnableTable .2.12.4.12 -- evNoData2PortEnableEntry .2.12.4.12.1 -- evNoData2PortEnableIndex .2.12.4.12.1.1 -- evNoData2PortEnable .2.12.4.12.1.2 -- evNoData2Exclusions .2.12.4.13 -- evNoData2Days .2.12.4.14 -- evSched1 .2.12.5 -- evSched1Enable .2.12.5.1 -- evSched1Actions .2.12.5.2 -- evSched1Message .2.12.5.3 -- evSched1TrapNum .2.12.5.4 -- evSched1Class .2.12.5.5 -- evSched1Sunday .2.12.5.6 -- evSched1Monday .2.12.5.7 -- evSched1Tuesday .2.12.5.8 -- evSched1Wednesday .2.12.5.9 -- evSched1Thursday .2.12.5.10 -- evSched1Friday .2.12.5.11 -- evSched1Saturday .2.12.5.12 -- evSched1Exclusions .2.12.5.13 -- evSched2 .2.12.6 -- evSched2Enable .2.12.6.1 -- evSched2Actions .2.12.6.2 -- evSched2Message .2.12.6.3 -- evSched2TrapNum .2.12.6.4 -- evSched2Class .2.12.6.5 -- evSched2Sunday .2.12.6.6 -- evSched2Monday .2.12.6.7 -- evSched2Tuesday .2.12.6.8 -- evSched2Wednesday .2.12.6.9 -- evSched2Thursday .2.12.6.10 -- evSched2Friday .2.12.6.11 -- evSched2Saturday .2.12.6.12 -- evSched2Exclusions .2.12.6.13 -- evShskLowTable .2.12.7 -- evShskLowEntry .2.12.7.1 -- evShskLowIndex .2.12.7.1.1 -- evShskLowEnable .2.12.7.1.2 -- evShskLowActions .2.12.7.1.3 -- evShskLowMessage .2.12.7.1.4 -- evShskLowClass .2.12.7.1.5 -- evShskLowTrapNum .2.12.7.1.6 -- evShskHighTable .2.12.8 -- evShskHighEntry .2.12.8.1 -- evShskHighIndex .2.12.8.1.1 -- evShskHighEnable .2.12.8.1.2 -- evShskHighActions .2.12.8.1.3 -- evShskHighMessage .2.12.8.1.4 -- evShskHighClass .2.12.8.1.5 -- evShskHighTrapNum .2.12.8.1.6 -- evNoSensor .2.12.9 -- evNoSensorTimeout .2.12.9.1 -- evNoSensorActions .2.12.9.2 -- evNoSensorTrapNum .2.12.9.3 -- evNoSensorClass .2.12.9.4 -- fuelSensor .2.12.11 -- fuelSensorGeneralTable .2.12.11.1 -- fsGenEntry .2.12.11.1.1 -- fsGenIndex .2.12.11.1.1.1 -- fsGenName .2.12.11.1.1.2 -- fsGenSensorType .2.12.11.1.1.3 -- fsGenDistanceUnit .2.12.11.1.1.4 -- fsGenRawValueTop .2.12.11.1.1.5 -- fsGenTopOffset .2.12.11.1.1.6 -- fsGenRawValueBottom .2.12.11.1.1.7 -- fsGenBottomOffset .2.12.11.1.1.8 -- fsGenInputES .2.12.11.1.1.9 -- fsGenInputPoint .2.12.11.1.1.10 -- fsGenFilterAveraging .2.12.11.1.1.11 -- fsGenSysrepEnable .2.12.11.1.1.12 -- fsGenSysrepThreshold .2.12.11.1.1.13 -- fsGenSysrepLimit .2.12.11.1.1.14 -- fsGenSysrepPackage .2.12.11.1.1.15 -- fsGenGroup .2.12.11.1.1.16 -- fsGenEnable .2.12.11.1.1.17 -- fsGenFuelType .2.12.11.1.1.18 -- fuelSensorTankTable .2.12.11.2 -- fsTankEntry .2.12.11.2.1 -- fsTankIndex .2.12.11.2.1.1 -- fsTankHeight .2.12.11.2.1.2 -- fsTankDimA .2.12.11.2.1.3 -- fsTankDimB .2.12.11.2.1.4 -- fsTankVolume .2.12.11.2.1.5 -- fsTankVolumeUnit .2.12.11.2.1.6 -- fsTankShape .2.12.11.2.1.7 -- fuelSensorCustomTankTable .2.12.11.3 -- fsCustomTankEntry .2.12.11.3.1 -- fsCustomTankIndexFS .2.12.11.3.1.1 -- fsCustomTankIndexDatum .2.12.11.3.1.2 -- fsCustomTankHeight .2.12.11.3.1.3 -- fsCustomTankVolume .2.12.11.3.1.4 -- fuelSensorVolumeTable .2.12.11.4 -- fsVolumeEntry .2.12.11.4.1 -- fsVolumeIndex .2.12.11.4.1.1 -- fsVolumeEnable .2.12.11.4.1.2 -- fsVolumeDeadband .2.12.11.4.1.3 -- fsVolumeVHighValue .2.12.11.4.1.4 -- fsVolumeVHighActions .2.12.11.4.1.5 -- fsVolumeVHighTrapNum .2.12.11.4.1.6 -- fsVolumeVHighClass .2.12.11.4.1.7 -- fsVolumeHighValue .2.12.11.4.1.8 -- fsVolumeHighActions .2.12.11.4.1.9 -- fsVolumeHighTrapNum .2.12.11.4.1.10 -- fsVolumeHighClass .2.12.11.4.1.11 -- fsVolumeNormalActions .2.12.11.4.1.12 -- fsVolumeNormalTrapNum .2.12.11.4.1.13 -- fsVolumeNormalClass .2.12.11.4.1.14 -- fsVolumeLowValue .2.12.11.4.1.15 -- fsVolumeLowActions .2.12.11.4.1.16 -- fsVolumeLowTrapNum .2.12.11.4.1.17 -- fsVolumeLowClass .2.12.11.4.1.18 -- fsVolumeVLowValue .2.12.11.4.1.19 -- fsVolumeVLowActions .2.12.11.4.1.20 -- fsVolumeVLowTrapNum .2.12.11.4.1.21 -- fsVolumeVLowClass .2.12.11.4.1.22 -- fuelSensorDisconnectTable .2.12.11.5 -- fsDiscEntry .2.12.11.5.1 -- fsDiscIndex .2.12.11.5.1.1 -- fsDiscEnable .2.12.11.5.1.2 -- fsDiscHighValue .2.12.11.5.1.3 -- fsDiscLowValue .2.12.11.5.1.4 -- fsDiscActions .2.12.11.5.1.5 -- fsDiscTrapNum .2.12.11.5.1.6 -- fsDiscClass .2.12.11.5.1.7 -- fsDiscNormalActions .2.12.11.5.1.8 -- fsDiscNormalTrapNum .2.12.11.5.1.9 -- fsDiscNormalClass .2.12.11.5.1.10 -- fuelSensorSuddenChangeTable .2.12.11.6 -- fsSuddenChangeEntry .2.12.11.6.1 -- fsSuddenChangeIndex .2.12.11.6.1.1 -- fsSuddenChangeEnable .2.12.11.6.1.2 -- fsSuddenChangeTime .2.12.11.6.1.3 -- fsSuddenChangeAmplitude .2.12.11.6.1.4 -- fsSuddenChangeActions .2.12.11.6.1.5 -- fsSuddenChangeTrapNum .2.12.11.6.1.6 -- fsSuddenChangeClass .2.12.11.6.1.7 -- fuelSensorSlowChangeTable .2.12.11.7 -- fuelSensorSlowChangeEntry .2.12.11.7.1 -- fsSlowChangeIndex .2.12.11.7.1.1 -- fsSlowChangeEnable .2.12.11.7.1.2 -- fsSlowChangeTime .2.12.11.7.1.3 -- fsSlowChangeAmplitude .2.12.11.7.1.4 -- fsSlowChangeActions .2.12.11.7.1.5 -- fsSlowChangeTrapNum .2.12.11.7.1.6 -- fsSlowChangeClass .2.12.11.7.1.7 -- acPowerMonitor .2.12.12 -- acpmGeneralTable .2.12.12.1 -- acpmGenEntry .2.12.12.1.1 -- acpmGenIndex .2.12.12.1.1.1 -- acpmGenDevice .2.12.12.1.1.2 -- acpmGenName .2.12.12.1.1.3 -- acpmGenAddress .2.12.12.1.1.4 -- acpmGenPtRatio .2.12.12.1.1.5 -- acpmGenCtRatio .2.12.12.1.1.6 -- acpmGenPowerType .2.12.12.1.1.7 -- acpmGenSysrepPackage .2.12.12.1.1.8 -- acpmGenGroup .2.12.12.1.1.9 -- acpmGenEnable .2.12.12.1.1.10 -- acpmAvgVoltageTable .2.12.12.2 -- acpmAvgVoltageEntry .2.12.12.2.1 -- acpmAvgVoltageIndex .2.12.12.2.1.1 -- acpmAvgVoltageEnable .2.12.12.2.1.2 -- acpmAvgVoltageDeadband .2.12.12.2.1.3 -- acpmAvgVoltageVHighValue .2.12.12.2.1.4 -- acpmAvgVoltageVHighActions .2.12.12.2.1.5 -- acpmAvgVoltageVHighTrapNum .2.12.12.2.1.6 -- acpmAvgVoltageVHighClass .2.12.12.2.1.7 -- acpmAvgVoltageHighValue .2.12.12.2.1.8 -- acpmAvgVoltageHighActions .2.12.12.2.1.9 -- acpmAvgVoltageHighTrapNum .2.12.12.2.1.10 -- acpmAvgVoltageHighClass .2.12.12.2.1.11 -- acpmAvgVoltageNormalActions .2.12.12.2.1.12 -- acpmAvgVoltageNormalTrapNum .2.12.12.2.1.13 -- acpmAvgVoltageNormalClass .2.12.12.2.1.14 -- acpmAvgVoltageLowValue .2.12.12.2.1.15 -- acpmAvgVoltageLowActions .2.12.12.2.1.16 -- acpmAvgVoltageLowTrapNum .2.12.12.2.1.17 -- acpmAvgVoltageLowClass .2.12.12.2.1.18 -- acpmAvgVoltageVLowValue .2.12.12.2.1.19 -- acpmAvgVoltageVLowActions .2.12.12.2.1.20 -- acpmAvgVoltageVLowTrapNum .2.12.12.2.1.21 -- acpmAvgVoltageVLowClass .2.12.12.2.1.22 -- acpmAvgVoltageSysrepEnable .2.12.12.2.1.23 -- acpmAvgVoltageSysrepThreshold .2.12.12.2.1.24 -- acpmAvgVoltageSysrepLimit .2.12.12.2.1.25 -- acpmAvgCurrentTable .2.12.12.3 -- acpmAvgCurrentEntry .2.12.12.3.1 -- acpmAvgCurrentIndex .2.12.12.3.1.1 -- acpmAvgCurrentEnable .2.12.12.3.1.2 -- acpmAvgCurrentDeadband .2.12.12.3.1.3 -- acpmAvgCurrentVHighValue .2.12.12.3.1.4 -- acpmAvgCurrentVHighActions .2.12.12.3.1.5 -- acpmAvgCurrentVHighTrapNum .2.12.12.3.1.6 -- acpmAvgCurrentVHighClass .2.12.12.3.1.7 -- acpmAvgCurrentHighValue .2.12.12.3.1.8 -- acpmAvgCurrentHighActions .2.12.12.3.1.9 -- acpmAvgCurrentHighTrapNum .2.12.12.3.1.10 -- acpmAvgCurrentHighClass .2.12.12.3.1.11 -- acpmAvgCurrentNormalActions .2.12.12.3.1.12 -- acpmAvgCurrentNormalTrapNum .2.12.12.3.1.13 -- acpmAvgCurrentNormalClass .2.12.12.3.1.14 -- acpmAvgCurrentLowValue .2.12.12.3.1.15 -- acpmAvgCurrentLowActions .2.12.12.3.1.16 -- acpmAvgCurrentLowTrapNum .2.12.12.3.1.17 -- acpmAvgCurrentLowClass .2.12.12.3.1.18 -- acpmAvgCurrentVLowValue .2.12.12.3.1.19 -- acpmAvgCurrentVLowActions .2.12.12.3.1.20 -- acpmAvgCurrentVLowTrapNum .2.12.12.3.1.21 -- acpmAvgCurrentVLowClass .2.12.12.3.1.22 -- acpmAvgCurrentSysrepEnable .2.12.12.3.1.23 -- acpmAvgCurrentSysrepThreshold .2.12.12.3.1.24 -- acpmAvgCurrentSysrepLimit .2.12.12.3.1.25 -- acpmFreqTable .2.12.12.4 -- acpmFreqEntry .2.12.12.4.1 -- acpmFreqIndex .2.12.12.4.1.1 -- acpmFreqEnable .2.12.12.4.1.2 -- acpmFreqDeadband .2.12.12.4.1.3 -- acpmFreqVHighValue .2.12.12.4.1.4 -- acpmFreqVHighActions .2.12.12.4.1.5 -- acpmFreqVHighTrapNum .2.12.12.4.1.6 -- acpmFreqVHighClass .2.12.12.4.1.7 -- acpmFreqHighValue .2.12.12.4.1.8 -- acpmFreqHighActions .2.12.12.4.1.9 -- acpmFreqHighTrapNum .2.12.12.4.1.10 -- acpmFreqHighClass .2.12.12.4.1.11 -- acpmFreqNormalActions .2.12.12.4.1.12 -- acpmFreqNormalTrapNum .2.12.12.4.1.13 -- acpmFreqNormalClass .2.12.12.4.1.14 -- acpmFreqLowValue .2.12.12.4.1.15 -- acpmFreqLowActions .2.12.12.4.1.16 -- acpmFreqLowTrapNum .2.12.12.4.1.17 -- acpmFreqLowClass .2.12.12.4.1.18 -- acpmFreqVLowValue .2.12.12.4.1.19 -- acpmFreqVLowActions .2.12.12.4.1.20 -- acpmFreqVLowTrapNum .2.12.12.4.1.21 -- acpmFreqVLowClass .2.12.12.4.1.22 -- acpmFreqSysrepEnable .2.12.12.4.1.23 -- acpmFreqSysrepThreshold .2.12.12.4.1.24 -- acpmFreqSysrepLimit .2.12.12.4.1.25 -- acpmTotalRealPowerTable .2.12.12.5 -- acpmTRPEntry .2.12.12.5.1 -- acpmTRPIndex .2.12.12.5.1.1 -- acpmTRPEnable .2.12.12.5.1.2 -- acpmTRPDeadband .2.12.12.5.1.3 -- acpmTRPVHighValue .2.12.12.5.1.4 -- acpmTRPVHighActions .2.12.12.5.1.5 -- acpmTRPVHighTrapNum .2.12.12.5.1.6 -- acpmTRPVHighClass .2.12.12.5.1.7 -- acpmTRPHighValue .2.12.12.5.1.8 -- acpmTRPHighActions .2.12.12.5.1.9 -- acpmTRPHighTrapNum .2.12.12.5.1.10 -- acpmTRPHighClass .2.12.12.5.1.11 -- acpmTRPNormalActions .2.12.12.5.1.12 -- acpmTRPNormalTrapNum .2.12.12.5.1.13 -- acpmTRPNormalClass .2.12.12.5.1.14 -- acpmTRPLowValue .2.12.12.5.1.15 -- acpmTRPLowActions .2.12.12.5.1.16 -- acpmTRPLowTrapNum .2.12.12.5.1.17 -- acpmTRPLowClass .2.12.12.5.1.18 -- acpmTRPVLowValue .2.12.12.5.1.19 -- acpmTRPVLowActions .2.12.12.5.1.20 -- acpmTRPVLowTrapNum .2.12.12.5.1.21 -- acpmTRPVLowClass .2.12.12.5.1.22 -- acpmTRPSysrepEnable .2.12.12.5.1.23 -- acpmTRPSysrepThreshold .2.12.12.5.1.24 -- acpmTRPSysrepLimit .2.12.12.5.1.25 -- acpmDisconnectTable .2.12.12.6 -- acpmDisconnectEntry .2.12.12.6.1 -- acpmDisconnectIndex .2.12.12.6.1.1 -- acpmDisconnectEnable .2.12.12.6.1.2 -- acpmDisconnectActions .2.12.12.6.1.3 -- acpmDisconnectTrapNum .2.12.12.6.1.4 -- acpmDisconnectClass .2.12.12.6.1.5 -- acpmDisconnectNormalActions .2.12.12.6.1.6 -- acpmDisconnectNormalTrapNum .2.12.12.6.1.7 -- acpmDisconnectNormalClass .2.12.12.6.1.8 -- acpmTotalPowerFactorTable .2.12.12.7 -- acpmTPFEntry .2.12.12.7.1 -- acpmTPFIndex .2.12.12.7.1.1 -- acpmTPFEnable .2.12.12.7.1.2 -- acpmTPFDeadband .2.12.12.7.1.3 -- acpmTPFNormalActions .2.12.12.7.1.4 -- acpmTPFNormalTrapNum .2.12.12.7.1.5 -- acpmTPFNormalClass .2.12.12.7.1.6 -- acpmTPFLowValue .2.12.12.7.1.7 -- acpmTPFLowActions .2.12.12.7.1.8 -- acpmTPFLowTrapNum .2.12.12.7.1.9 -- acpmTPFLowClass .2.12.12.7.1.10 -- acpmTPFVLowValue .2.12.12.7.1.11 -- acpmTPFVLowActions .2.12.12.7.1.12 -- acpmTPFVLowTrapNum .2.12.12.7.1.13 -- acpmTPFVLowClass .2.12.12.7.1.14 -- acpmTPFSysrepEnable .2.12.12.7.1.15 -- acpmTPFSysrepThreshold .2.12.12.7.1.16 -- acpmTPFSysrepLimit .2.12.12.7.1.17 -- evReset .2.12.16 -- evResetEnable .2.12.16.1 -- evResetDelay .2.12.16.2 -- evResetActions .2.12.16.3 -- evResetMessage .2.12.16.4 -- evResetTrapnum .2.12.16.5 -- evResetClass .2.12.16.6 -- evGlobal .2.12.18 -- evGlobalActions .2.12.18.1 -- evGlobalTrapnum .2.12.18.2 -- evHVAC .2.12.19 -- evHVACGeneral .2.12.19.1 -- evHVACBard .2.12.19.2 -- evHVACBardLocal .2.12.19.2.1 -- evHVACBardIPAddress .2.12.19.2.1.1 -- evHVACBardPort .2.12.19.2.1.2 -- evHVACBardTimeout .2.12.19.2.1.3 -- evHVACBardXMLStatus .2.12.19.2.1.4 -- evHVACBardXMLSettings .2.12.19.2.1.5 -- evHVACBardWebSettingsHTML .2.12.19.2.1.6 -- evHVACBardAlarm .2.12.19.2.1.7 -- evHVACBardAlarmEnable .2.12.19.2.1.7.1 -- evHVACBardAlarmActions .2.12.19.2.1.7.2 -- evHVACBardAlarmTrapnum .2.12.19.2.1.7.3 -- evHVACBardAlarmClass .2.12.19.2.1.7.4 -- evHVACBardAlarmNormalActions .2.12.19.2.1.7.5 -- evHVACBardAlarmNormalTrapnum .2.12.19.2.1.7.6 -- evHVACBardAlarmNormalClass .2.12.19.2.1.7.7 -- evHVACBardReset .2.12.19.2.1.8 -- evHVACBardDefault .2.12.19.2.1.9 -- evHVACBardSynchronized .2.12.19.2.2 -- evHVACBardTempScale .2.12.19.2.2.1 -- evHVACBardCoolThreshold .2.12.19.2.2.2 -- evHVACBardCoolThresholdState .2.12.19.2.2.3 -- evHVACBardHeatThreshold .2.12.19.2.2.4 -- evHVACBardHeatDiff .2.12.19.2.2.5 -- evHVACBardHeatDiffState .2.12.19.2.2.6 -- evHVACBardBlower .2.12.19.2.2.7 -- evHVACBardBlowerState .2.12.19.2.2.8 -- evHVACBardAlternate .2.12.19.2.2.9 -- evHVACBardAlternateState .2.12.19.2.2.10 -- evHVACBardChangeover .2.12.19.2.2.11 -- evHVACBardChangeoverState .2.12.19.2.2.12 -- evHVACBardBlowDiff .2.12.19.2.2.13 -- evHVACBardBlowDiffState .2.12.19.2.2.14 -- evHVACBardOffDelay .2.12.19.2.2.15 -- evHVACBardOffDelayState .2.12.19.2.2.16 -- evHVACBardRunMin .2.12.19.2.2.17 -- evHVACBardRunMinState .2.12.19.2.2.18 -- evHVACBardDiff .2.12.19.2.2.19 -- evHVACBardStage1Diff .2.12.19.2.2.19.1 -- evHVACBardStage1DiffState .2.12.19.2.2.19.2 -- evHVACBardStage2Diff .2.12.19.2.2.19.3 -- evHVACBardStage2DiffState .2.12.19.2.2.19.4 -- evHVACBardStage3Diff .2.12.19.2.2.19.5 -- evHVACBardStage3DiffState .2.12.19.2.2.19.6 -- evHVACBardCoolDisableDb .2.12.19.2.2.20 -- evHVACBardCoolDisableDbState .2.12.19.2.2.21 -- evHVACBardCoolEnableDb .2.12.19.2.2.22 -- evHVACBardCoolEnableDbState .2.12.19.2.2.23 -- evHVACBardHeatDb .2.12.19.2.2.24 -- evHVACBardHeatDbState .2.12.19.2.2.25 -- evHVACBardHeatPump .2.12.19.2.2.26 -- evHVACBardHeatPumpState .2.12.19.2.2.27 -- evHVACBardCompressors .2.12.19.2.2.28 -- evHVACBardCompressorsState .2.12.19.2.2.29 -- evHVACBardEconomizer .2.12.19.2.2.30 -- evHVACBardEconomizerState .2.12.19.2.2.31 -- evHVACBardTemp .2.12.19.2.2.32 -- evHVACBardTempLowValue .2.12.19.2.2.32.1 -- evHVACBardTempLowValueState .2.12.19.2.2.32.2 -- evHVACBardTempHighValue .2.12.19.2.2.32.3 -- evHVACBardTempHighValueState .2.12.19.2.2.32.4 -- evHVACBardTempVHighValue .2.12.19.2.2.32.5 -- evHVACBardTempVHighValueState .2.12.19.2.2.32.6 -- evHVACBardOverride .2.12.19.2.2.33 -- evHVACBardOverrideState .2.12.19.2.2.34 -- evHVACBardLock .2.12.19.2.2.35 -- evHVACBardLockState .2.12.19.2.2.36 -- evHVACBardLeadUnit .2.12.19.2.2.37 -- evHVACBardLeadUnitState .2.12.19.2.2.38 -- evHVACBardComfort .2.12.19.2.2.39 -- evHVACBardComfortState .2.12.19.2.2.40 -- evHVACAsentria .2.12.19.3 -- evHVACAsentriaSensorListTable .2.12.19.3.1 -- evHVACAsentriaSensorListEntry .2.12.19.3.1.1 -- evHVACAsentriaSensorListIndex .2.12.19.3.1.1.1 -- evHVACAsentriaSensorListES .2.12.19.3.1.1.2 -- evHVACAsentriaSensorListPT .2.12.19.3.1.1.3 -- evHVACAsentriaSensorListType .2.12.19.3.1.1.4 -- evHVACAsentriaSensorListLoc .2.12.19.3.1.1.5 -- evHVACAsentriaOverride .2.12.19.3.2 -- evHVACAsentriaSchedule .2.12.19.3.3 -- evHVACAsentriaPrimary .2.12.19.3.4 -- evHVACAsentriaMethod .2.12.19.3.5 -- evHVACAsentriaAlarm .2.12.19.3.6 -- evHVACAsentriaAlarmLagNormEnable .2.12.19.3.6.1 -- evHVACAsentriaAlarmLagNormActions .2.12.19.3.6.2 -- evHVACAsentriaAlarmLagNormTrapNum .2.12.19.3.6.3 -- evHVACAsentriaAlarmLagNormClass .2.12.19.3.6.4 -- evHVACAsentriaAlarmLagVentEnable .2.12.19.3.6.5 -- evHVACAsentriaAlarmLagVentActions .2.12.19.3.6.6 -- evHVACAsentriaAlarmLagVentTrapNum .2.12.19.3.6.7 -- evHVACAsentriaAlarmLagVentClass .2.12.19.3.6.8 -- evHVACAsentriaAlarmLagCoolEnable .2.12.19.3.6.9 -- evHVACAsentriaAlarmLagCoolActions .2.12.19.3.6.10 -- evHVACAsentriaAlarmLagCoolTrapNum .2.12.19.3.6.11 -- evHVACAsentriaAlarmLagCoolClass .2.12.19.3.6.12 -- evHVACAsentriaAlarmLagHeatEnable .2.12.19.3.6.13 -- evHVACAsentriaAlarmLagHeatActions .2.12.19.3.6.14 -- evHVACAsentriaAlarmLagHeatTrapNum .2.12.19.3.6.15 -- evHVACAsentriaAlarmLagHeatClass .2.12.19.3.6.16 -- evHVACAsentriaFire .2.12.19.3.7 -- evHVACAsentriaFireES .2.12.19.3.7.1 -- evHVACAsentriaFirePT .2.12.19.3.7.2 -- evHVACAsentriaFireActions .2.12.19.3.7.3 -- evHVACAsentriaFireTrapNum .2.12.19.3.7.4 -- evHVACAsentriaFireClass .2.12.19.3.7.5 -- evHVACAsentriaFireNormActions .2.12.19.3.7.6 -- evHVACAsentriaFireNormTrapNum .2.12.19.3.7.7 -- evHVACAsentriaFireNormClass .2.12.19.3.7.8 -- evHVACAsentriaUnitTable .2.12.19.3.8 -- evHVACAsentriaUnitEntry .2.12.19.3.8.1 -- evHVACAsentriaUnitIndex .2.12.19.3.8.1.1 -- evHVACAsentriaUnitEnable .2.12.19.3.8.1.2 -- evHVACAsentriaUnitFanRelayES .2.12.19.3.8.1.3 -- evHVACAsentriaUnitFanRelayPT .2.12.19.3.8.1.4 -- evHVACAsentriaUnitVentRelayES .2.12.19.3.8.1.5 -- evHVACAsentriaUnitVentRelayPT .2.12.19.3.8.1.6 -- evHVACAsentriaUnitTimereset .2.12.19.3.8.1.7 -- evHVACAsentriaSeqTimereset .2.12.19.3.8.1.8 -- evHVACAsentriaUnitStage1CoolES .2.12.19.3.8.1.20 -- evHVACAsentriaUnitStage1CoolPT .2.12.19.3.8.1.21 -- evHVACAsentriaUnitStage1HeatES .2.12.19.3.8.1.22 -- evHVACAsentriaUnitStage1HeatPT .2.12.19.3.8.1.23 -- evHVACAsentriaUnitStage2CoolES .2.12.19.3.8.1.30 -- evHVACAsentriaUnitStage2CoolPT .2.12.19.3.8.1.31 -- evHVACAsentriaUnitStage2HeatES .2.12.19.3.8.1.32 -- evHVACAsentriaUnitStage2HeatPT .2.12.19.3.8.1.33 -- evHVACAsentriaTemp .2.12.19.3.9 -- evHVACAsentriaTempScale .2.12.19.3.9.1 -- evHVACAsentriaTempCoolThresh .2.12.19.3.9.2 -- evHVACAsentriaTempHeatThresh .2.12.19.3.9.3 -- evHVACAsentriaTempEnable .2.12.19.3.9.4 -- evHVACAsentriaTempEventDeadband .2.12.19.3.9.5 -- evHVACAsentriaTempVLowValue .2.12.19.3.9.6 -- evHVACAsentriaTempVLowActions .2.12.19.3.9.7 -- evHVACAsentriaTempVLowTrapNum .2.12.19.3.9.8 -- evHVACAsentriaTempVLowClass .2.12.19.3.9.9 -- evHVACAsentriaTempLowValue .2.12.19.3.9.10 -- evHVACAsentriaTempLowActions .2.12.19.3.9.11 -- evHVACAsentriaTempLowTrapNum .2.12.19.3.9.12 -- evHVACAsentriaTempLowClass .2.12.19.3.9.13 -- evHVACAsentriaTempNormalActions .2.12.19.3.9.14 -- evHVACAsentriaTempNormalTrapNum .2.12.19.3.9.15 -- evHVACAsentriaTempNormalClass .2.12.19.3.9.16 -- evHVACAsentriaTempHighValue .2.12.19.3.9.17 -- evHVACAsentriaTempHighActions .2.12.19.3.9.18 -- evHVACAsentriaTempHighTrapNum .2.12.19.3.9.19 -- evHVACAsentriaTempHighClass .2.12.19.3.9.20 -- evHVACAsentriaTempVHighValue .2.12.19.3.9.21 -- evHVACAsentriaTempVHighActions .2.12.19.3.9.22 -- evHVACAsentriaTempVHighTrapNum .2.12.19.3.9.23 -- evHVACAsentriaTempVHighClass .2.12.19.3.9.24 -- evHVACAsentriaTempDeadband .2.12.19.3.9.25 -- evHVACAsentriaTempDifference .2.12.19.3.9.26 -- evHVACAsentriaHumid .2.12.19.3.10 -- evHVACAsentriaHumidInThresh .2.12.19.3.10.2 -- evHVACAsentriaHumidOutThresh .2.12.19.3.10.3 -- evHVACAsentriaHumidEnable .2.12.19.3.10.4 -- evHVACAsentriaHumidEventDeadband .2.12.19.3.10.5 -- evHVACAsentriaHumidVLowValue .2.12.19.3.10.6 -- evHVACAsentriaHumidVLowActions .2.12.19.3.10.7 -- evHVACAsentriaHumidVLowTrapNum .2.12.19.3.10.8 -- evHVACAsentriaHumidVLowClass .2.12.19.3.10.9 -- evHVACAsentriaHumidLowValue .2.12.19.3.10.10 -- evHVACAsentriaHumidLowActions .2.12.19.3.10.11 -- evHVACAsentriaHumidLowTrapNum .2.12.19.3.10.12 -- evHVACAsentriaHumidLowClass .2.12.19.3.10.13 -- evHVACAsentriaHumidNormalActions .2.12.19.3.10.14 -- evHVACAsentriaHumidNormalTrapNum .2.12.19.3.10.15 -- evHVACAsentriaHumidNormalClass .2.12.19.3.10.16 -- evHVACAsentriaHumidHighValue .2.12.19.3.10.17 -- evHVACAsentriaHumidHighActions .2.12.19.3.10.18 -- evHVACAsentriaHumidHighTrapNum .2.12.19.3.10.19 -- evHVACAsentriaHumidHighClass .2.12.19.3.10.20 -- evHVACAsentriaHumidVHighValue .2.12.19.3.10.21 -- evHVACAsentriaHumidVHighActions .2.12.19.3.10.22 -- evHVACAsentriaHumidVHighTrapNum .2.12.19.3.10.23 -- evHVACAsentriaHumidVHighClass .2.12.19.3.10.24 -- evHVACAsentriaHumidDeadband .2.12.19.3.10.25 -- evHVACAsentriaHumidDifference .2.12.19.3.10.26 -- evHVACAirsys .2.12.19.4 -- evHVACAirsysGeneral .2.12.19.4.1 -- evHVACAirsysGeneratorLogic .2.12.19.4.1.1 -- evHVACAirsysFreeMode .2.12.19.4.1.2 -- evHVACAirsysRemoteEnable .2.12.19.4.1.3 -- evHVACAirsysHVACRotation .2.12.19.4.1.4 -- evHVACAirsysRotationRuntime .2.12.19.4.1.5 -- evHVACAirsysAlarm .2.12.19.4.2 -- evHVACAirsysUnitTable .2.12.19.4.2.1 -- evHVACAirsysUnitEntry .2.12.19.4.2.1.1 -- evHVACAirsysUnitIndex .2.12.19.4.2.1.1.1 -- evHVACAirsysULowPEnable .2.12.19.4.2.1.1.2 -- evHVACAirsysULowPActions .2.12.19.4.2.1.1.3 -- evHVACAirsysULowPClass .2.12.19.4.2.1.1.4 -- evHVACAirsysULowPTrapNum .2.12.19.4.2.1.1.5 -- evHVACAirsysULowPNormActions .2.12.19.4.2.1.1.6 -- evHVACAirsysULowPNormClass .2.12.19.4.2.1.1.7 -- evHVACAirsysULowPNormTrapNum .2.12.19.4.2.1.1.8 -- evHVACAirsysUHighPEnable .2.12.19.4.2.1.1.9 -- evHVACAirsysUHighPActions .2.12.19.4.2.1.1.10 -- evHVACAirsysUHighPClass .2.12.19.4.2.1.1.11 -- evHVACAirsysUHighPTrapNum .2.12.19.4.2.1.1.12 -- evHVACAirsysUHighPNormActions .2.12.19.4.2.1.1.13 -- evHVACAirsysUHighPNormClass .2.12.19.4.2.1.1.14 -- evHVACAirsysUHighPNormTrapNum .2.12.19.4.2.1.1.15 -- evHVACAirsysUEvapFanEnable .2.12.19.4.2.1.1.16 -- evHVACAirsysUEvapFanActions .2.12.19.4.2.1.1.17 -- evHVACAirsysUEvapFanClass .2.12.19.4.2.1.1.18 -- evHVACAirsysUEvapFanTrapNum .2.12.19.4.2.1.1.19 -- evHVACAirsysUEvapFanNormActions .2.12.19.4.2.1.1.20 -- evHVACAirsysUEvapFanNormClass .2.12.19.4.2.1.1.21 -- evHVACAirsysUEvapFanNormTrapNum .2.12.19.4.2.1.1.22 -- evHVACAirsysUDirtyEnable .2.12.19.4.2.1.1.23 -- evHVACAirsysUDirtyActions .2.12.19.4.2.1.1.24 -- evHVACAirsysUDirtyClass .2.12.19.4.2.1.1.25 -- evHVACAirsysUDirtyTrapNum .2.12.19.4.2.1.1.26 -- evHVACAirsysUDirtyNormActions .2.12.19.4.2.1.1.27 -- evHVACAirsysUDirtyNormClass .2.12.19.4.2.1.1.28 -- evHVACAirsysUDirtyNormTrapNum .2.12.19.4.2.1.1.29 -- evHVACAirsysUInProbeEnable .2.12.19.4.2.1.1.30 -- evHVACAirsysUInProbeActions .2.12.19.4.2.1.1.31 -- evHVACAirsysUInProbeClass .2.12.19.4.2.1.1.32 -- evHVACAirsysUInProbeTrapNum .2.12.19.4.2.1.1.33 -- evHVACAirsysUInProbeNormActions .2.12.19.4.2.1.1.34 -- evHVACAirsysUInProbeNormClass .2.12.19.4.2.1.1.35 -- evHVACAirsysUInProbeNormTrapNum .2.12.19.4.2.1.1.36 -- evHVACAirsysUDamperEnable .2.12.19.4.2.1.1.37 -- evHVACAirsysUDamperActions .2.12.19.4.2.1.1.38 -- evHVACAirsysUDamperClass .2.12.19.4.2.1.1.39 -- evHVACAirsysUDamperTrapNum .2.12.19.4.2.1.1.40 -- evHVACAirsysUDamperNormActions .2.12.19.4.2.1.1.41 -- evHVACAirsysUDamperNormClass .2.12.19.4.2.1.1.42 -- evHVACAirsysUDamperNormTrapNum .2.12.19.4.2.1.1.43 -- evHVACAirsysUSupProbeEnable .2.12.19.4.2.1.1.44 -- evHVACAirsysUSupProbeActions .2.12.19.4.2.1.1.45 -- evHVACAirsysUSupProbeClass .2.12.19.4.2.1.1.46 -- evHVACAirsysUSupProbeTrapNum .2.12.19.4.2.1.1.47 -- evHVACAirsysUSupProbeNormActions .2.12.19.4.2.1.1.48 -- evHVACAirsysUSupProbeNormClass .2.12.19.4.2.1.1.49 -- evHVACAirsysUSupProbeNormTrapNum .2.12.19.4.2.1.1.50 -- evHVACAirsysSmokeFireEnable .2.12.19.4.2.2 -- evHVACAirsysSmokeFireAction .2.12.19.4.2.3 -- evHVACAirsysSmokeFireClass .2.12.19.4.2.4 -- evHVACAirsysSmokeFireTrapNum .2.12.19.4.2.5 -- evHVACAirsysSmokeFireNormAction .2.12.19.4.2.6 -- evHVACAirsysSmokeFireNormClass .2.12.19.4.2.7 -- evHVACAirsysSmokeFireNormTrapNum .2.12.19.4.2.8 -- evHVACAirsysLowRoomTempEnable .2.12.19.4.2.9 -- evHVACAirsysLowRoomTempAction .2.12.19.4.2.10 -- evHVACAirsysLowRoomTempClass .2.12.19.4.2.11 -- evHVACAirsysLowRoomTempTrapNum .2.12.19.4.2.12 -- evHVACAirsysLowRoomTempNormAction .2.12.19.4.2.13 -- evHVACAirsysLowRoomTempNormClass .2.12.19.4.2.14 -- evHVACAirsysLowRoomTempNormTrapNum .2.12.19.4.2.15 -- evHVACAirsysHighRoomTempEnable .2.12.19.4.2.16 -- evHVACAirsysHighRoomTempAction .2.12.19.4.2.17 -- evHVACAirsysHighRoomTempClass .2.12.19.4.2.18 -- evHVACAirsysHighRoomTempTrapNum .2.12.19.4.2.19 -- evHVACAirsysHighRoomTempNormAction .2.12.19.4.2.20 -- evHVACAirsysHighRoomTempNormClass .2.12.19.4.2.21 -- evHVACAirsysHighRoomTempNormTrapNum .2.12.19.4.2.22 -- evHVACAirsysPowerEnable .2.12.19.4.2.23 -- evHVACAirsysPowerAction .2.12.19.4.2.24 -- evHVACAirsysPowerClass .2.12.19.4.2.25 -- evHVACAirsysPowerTrapNum .2.12.19.4.2.26 -- evHVACAirsysPowerNormAction .2.12.19.4.2.27 -- evHVACAirsysPowerNormClass .2.12.19.4.2.28 -- evHVACAirsysPowerNormTrapNum .2.12.19.4.2.29 -- evHVACAirsyspLANEnable .2.12.19.4.2.30 -- evHVACAirsyspLANAction .2.12.19.4.2.31 -- evHVACAirsyspLANClass .2.12.19.4.2.32 -- evHVACAirsyspLANTrapNum .2.12.19.4.2.33 -- evHVACAirsyspLANNormAction .2.12.19.4.2.34 -- evHVACAirsyspLANNormClass .2.12.19.4.2.35 -- evHVACAirsyspLANNormTrapNum .2.12.19.4.2.36 -- evHVACAirsysClockEnable .2.12.19.4.2.37 -- evHVACAirsysClockAction .2.12.19.4.2.38 -- evHVACAirsysClockClass .2.12.19.4.2.39 -- evHVACAirsysClockTrapNum .2.12.19.4.2.40 -- evHVACAirsysClockNormAction .2.12.19.4.2.41 -- evHVACAirsysClockNormClass .2.12.19.4.2.42 -- evHVACAirsysClockNormTrapNum .2.12.19.4.2.43 -- evHVACAirsysHumidProbeEnable .2.12.19.4.2.44 -- evHVACAirsysHumidProbeAction .2.12.19.4.2.45 -- evHVACAirsysHumidProbeClass .2.12.19.4.2.46 -- evHVACAirsysHumidProbeTrapNum .2.12.19.4.2.47 -- evHVACAirsysHumidProbeNormAction .2.12.19.4.2.48 -- evHVACAirsysHumidProbeNormClass .2.12.19.4.2.49 -- evHVACAirsysHumidProbeNormTrapNum .2.12.19.4.2.50 -- evHVACAirsysOutProbeEnable .2.12.19.4.2.51 -- evHVACAirsysOutProbeAction .2.12.19.4.2.52 -- evHVACAirsysOutProbeClass .2.12.19.4.2.53 -- evHVACAirsysOutProbeTrapNum .2.12.19.4.2.54 -- evHVACAirsysOutProbeNormAction .2.12.19.4.2.55 -- evHVACAirsysOutProbeNormClass .2.12.19.4.2.56 -- evHVACAirsysOutProbeNormTrapNum .2.12.19.4.2.57 -- evHVACAirsysBothCompressEnable .2.12.19.4.2.58 -- evHVACAirsysBothCompressAction .2.12.19.4.2.59 -- evHVACAirsysBothCompressClass .2.12.19.4.2.60 -- evHVACAirsysBothCompressTrapNum .2.12.19.4.2.61 -- evHVACAirsysBothCompressNormAction .2.12.19.4.2.62 -- evHVACAirsysBothCompressNormClass .2.12.19.4.2.63 -- evHVACAirsysBothCompressNormTrapNum .2.12.19.4.2.64 -- evHVACAirsysGeneratorEnable .2.12.19.4.2.65 -- evHVACAirsysGeneratorAction .2.12.19.4.2.66 -- evHVACAirsysGeneratorClass .2.12.19.4.2.67 -- evHVACAirsysGeneratorTrapNum .2.12.19.4.2.68 -- evHVACAirsysGeneratorNormAction .2.12.19.4.2.69 -- evHVACAirsysGeneratorNormClass .2.12.19.4.2.70 -- evHVACAirsysGeneratorNormTrapNum .2.12.19.4.2.71 -- evHVACAirsysConnectionEnable .2.12.19.4.2.72 -- evHVACAirsysConnectionAction .2.12.19.4.2.73 -- evHVACAirsysConnectionClass .2.12.19.4.2.74 -- evHVACAirsysConnectionTrapNum .2.12.19.4.2.75 -- evHVACAirsysConnectionNormAction .2.12.19.4.2.76 -- evHVACAirsysConnectionNormClass .2.12.19.4.2.77 -- evHVACAirsysConnectionNormTrapNum .2.12.19.4.2.78 -- evHVACAirsysTemp .2.12.19.4.3 -- evHVACAirsysTempBaseThresh .2.12.19.4.3.1 -- evHVACAirsysTempCoolDeadband .2.12.19.4.3.2 -- evHVACAirsysTempHeatDeadband .2.12.19.4.3.3 -- evHVACAirsysTempHighValue .2.12.19.4.3.4 -- evHVACAirsysTempLowValue .2.12.19.4.3.5 -- evHVACAirsysHumid .2.12.19.4.4 -- evHVACAirsysHumidMaxFree .2.12.19.4.4.1 -- evHVACAirsysHumidDeadband .2.12.19.4.4.2 -- evEvps .2.12.20 -- evpsEnable .2.12.20.1 -- evpsIPAddress .2.12.20.2 -- evpsPort .2.12.20.3 -- evpsTimeout .2.12.20.4 -- accessControl .2.12.21 -- acActions .2.12.21.2 -- acTrapnum .2.12.21.3 -- acClass .2.12.21.4 -- accessControlDeviceTable .2.12.21.10 -- accessControlDeviceEntry .2.12.21.10.1 -- acdIndex .2.12.21.10.1.1 -- acdEnable .2.12.21.10.1.2 -- acdName .2.12.21.10.1.3 -- acdReader .2.12.21.10.1.4 -- acdWiegandES .2.12.21.10.1.5 -- acdWiegandPoint .2.12.21.10.1.6 -- acdRelayType .2.12.21.10.1.7 -- acdRelayES .2.12.21.10.1.8 -- acdRelayPoint .2.12.21.10.1.9 -- acdOpenTime .2.12.21.10.1.10 -- acdUserGroup .2.12.21.10.1.11 -- accessControlUserTable .2.12.21.11 -- accessControlUserEntry .2.12.21.11.1 -- acuIndexUserGroup .2.12.21.11.1.1 -- acuIndexUser .2.12.21.11.1.2 -- acuEnable .2.12.21.11.1.3 -- acuName .2.12.21.11.1.4 -- acuSn .2.12.21.11.1.5 -- acuSunBegin .2.12.21.11.1.6 -- acuSunEnd .2.12.21.11.1.7 -- acuMonBegin .2.12.21.11.1.8 -- acuMonEnd .2.12.21.11.1.9 -- acuTueBegin .2.12.21.11.1.10 -- acuTueEnd .2.12.21.11.1.11 -- acuWedBegin .2.12.21.11.1.12 -- acuWedEnd .2.12.21.11.1.13 -- acuThuBegin .2.12.21.11.1.14 -- acuThuEnd .2.12.21.11.1.15 -- acuFriBegin .2.12.21.11.1.16 -- acuFriEnd .2.12.21.11.1.17 -- acuSatBegin .2.12.21.11.1.18 -- acuSatEnd .2.12.21.11.1.19 -- telemetry .2.12.22 -- telemetryTable .2.12.22.1 -- telemetryTableEntry .2.12.22.1.1 -- telemetryPointIndex .2.12.22.1.1.1 -- telemetryPointName .2.12.22.1.1.2 -- telemetryPointKey .2.12.22.1.1.3 -- telemetryPointType .2.12.22.1.1.4 -- telemetryPointClass .2.12.22.1.1.5 -- telemetryPointDeadband .2.12.22.1.1.6 -- telemetryPointShortcode .2.12.22.1.1.7 -- siteSecurity .2.12.23 -- siteSecIntrusionTable .2.12.23.1 -- siteSecEnable .2.12.23.1.1 -- siteSecDisarmed .2.12.23.1.2 -- siteSecName .2.12.23.1.3 -- siteSecState .2.12.23.1.4 -- siteSecSensorES .2.12.23.1.5 -- siteSecSensorPoint .2.12.23.1.6 -- siteSecIntrusionThreshold .2.12.23.1.7 -- siteSecReader .2.12.23.1.8 -- siteSecReaderThreshold .2.12.23.1.9 -- siteSecButtonEnable .2.12.23.1.10 -- siteSecButtonES .2.12.23.1.11 -- siteSecButtonPoint .2.12.23.1.12 -- siteSecButtonType .2.12.23.1.13 -- siteSecButtonThresholdArm .2.12.23.1.14 -- siteSecButtonThresholdDisarm .2.12.23.1.15 -- siteSecSirenEnable .2.12.23.1.16 -- siteSecSirenES .2.12.23.1.17 -- siteSecSirenPoint .2.12.23.1.18 -- siteSecRearmDelay .2.12.23.1.19 -- siteSecMotionTable .2.12.23.2 -- siteSecMotionES .2.12.23.2.1 -- siteSecMotionPoint .2.12.23.2.2 -- siteSecMotionEnable .2.12.23.2.3 -- siteSecMotionName .2.12.23.2.4 -- siteSecMotionThresholdRearm .2.12.23.2.5 -- siteSecDoorAjarTable .2.12.23.3 -- siteSecDoorAjarEnable .2.12.23.3.1 -- siteSecDoorAjarName .2.12.23.3.2 -- siteSecDoorAjarES .2.12.23.3.3 -- siteSecDoorAjarPoint .2.12.23.3.4 -- siteSecDoorAjarThresholdNormal .2.12.23.3.5 -- siteSecDoorAjarThresholdExtraTime .2.12.23.3.6 -- action .2. -- actionCallNumberTable .2.14.1 -- actionCallNumberEntry .2.14.1.1 -- actionCallNumberIndex .2.14.1.1.1 -- actionCallNumber .2.14.1.1.2 -- actionPagerTable .2.14.2 -- actionPagerEntry .2.14.2.1 -- actionPagerIndex .2.14.2.1.1 -- actionPagerType .2.14.2.1.2 -- actionPagerNumber .2.14.2.1.3 -- actionPagerID .2.14.2.1.4 -- actionPagerMessage .2.14.2.1.5 -- actionPagerPostCalloutDelay .2.14.2.1.6 -- actionPagerPostIDDelay .2.14.2.1.7 -- actionSched .2.14.3 -- actionSchedEnable .2.14.3.1 -- actionSchedBegin .2.14.3.2 -- actionSchedEnd .2.14.3.3 -- actionSchedWeekdaysOnly .2.14.3.4 -- actionAsentria .2.14.4 -- actionAsentriaRequireAck .2.14.4.1 -- actionAsentriaVersion .2.14.4.2 -- actionAsentriaTCPPort .2.14.4.3 -- actionHostTable .2.14.6 -- actionHostEntry .2.14.6.1 -- actionHostIndex .2.14.6.1.1 -- actionHost .2.14.6.1.2 -- actionEmailTable .2.14.7 -- actionEmailEntry .2.14.7.1 -- actionEmailIndex .2.14.7.1.1 -- actionEmail .2.14.7.1.2 -- actionParseError .2.14.8 -- sys .2.16 -- sysTime .2.16.1 -- sysTimeAutoDST .2.16.1.1 -- sysTimeGMTOffset .2.16.1.2 -- sysTimeGMTDirection .2.16.1.3 -- sysTimeNet .2.16.1.4 -- sysTimeNetEnable .2.16.1.4.1 -- sysTimeNetHostTable .2.16.1.4.2 -- sysTimeNetHostEntry .2.16.1.4.2.1 -- sysTimeNetHostIndex .2.16.1.4.2.1.1 -- sysTimeNetHost .2.16.1.4.2.1.2 -- sysPT .2.16.2 -- sysPTTimeout .2.16.2.1 -- sysPTEndPause .2.16.2.2 -- sysPTJoinable .2.16.2.3 -- sysMTU .2.16.3 -- sysAnswerString .2.16.4 -- sysEventFileID .2.16.6 -- sysEscapeCharacter .2.16.7 -- sysTimeStamp .2.16.8 -- sysTimeStampTimeFormat .2.16.8.1 -- sysTimeStampDateFormat .2.16.8.2 -- sysTimeStampSpaceAfter .2.16.8.3 -- sysLog .2.16.9 -- sysLogMode .2.16.9.1 -- sysLoghost .2.16.9.2 -- sysLogFilter .2.16.9.3 -- sysLogFileSize .2.16.9.4 -- sysLogFileCount .2.16.9.5 -- sysLogListenPort .2.16.9.6 -- sysCRDB .2.16.10 -- sysCRDBCapacity .2.16.10.1 -- sysCRDBPercentFull .2.16.10.2 -- sysCRDBFileIDTable .2.16.10.3 -- sysCRDBFileIDEntry .2.16.10.3.1 -- sysCRDBFileIDIndex .2.16.10.3.1.1 -- sysCRDBFileID .2.16.10.3.1.2 -- sysCRDBFileEnforceMinTable .2.16.10.4 -- sysCRDBFileEnforceMinEntry .2.16.10.4.1 -- sysCRDBFileEnforceMinIndex .2.16.10.4.1.1 -- sysCRDBFileEnforceMin .2.16.10.4.1.2 -- sysCharMask .2.16.11 -- sysPrompt .2.16.12 -- sysBootStatus .2.16.13 -- sysLoc .2.16.14 -- sysLocLatitude .2.16.14.1 -- sysLocLongitude .2.16.14.2 -- sysLocXOffset .2.16.14.3 -- sysLocYOffset .2.16.14.4 -- sysLocAngle .2.16.14.5 -- sysLocAltitude .2.16.14.6 -- sysAssetMgmt .2.16.15 -- sysAMManufacturer .2.16.15.1 -- sysAMProduct .2.16.15.2 -- sysAMSerialNumber .2.16.15.3 -- sysAMHardwareOptions .2.16.15.4 -- sysAMSoftwareVersion .2.16.15.5 -- sysAMSiteName .2.16.15.6 -- sysFileTransfer .2.16.17 -- sysFileTransferStatus .2.16.17.1 -- sysFileTransferURL .2.16.17.2 -- sysFileTransferUsername .2.16.17.3 -- sysFileTransferPassword .2.16.17.4 -- sysUpdate .2.16.18 -- sysUpdateStatus .2.16.18.1 -- auditLog .2.17 -- auditLogEnable .2.17.1 -- auditLogStoreResets .2.17.2 -- auditLogStoreCommands .2.17.3 -- auditLogStoreOutputs .2.17.4 -- auditLogStoreAlarmActions .2.17.5 -- auditLogStorePwdFailures .2.17.6 -- auditLogStoreLogins .2.17.7 -- auditLogStoreSHSK .2.17.8 -- auditLogStorePassthrough .2.17.9 -- auditLogStoreInactivity .2.17.10 -- auditLogStorePolling .2.17.11 -- auditLogMaxSize .2.17.12 -- scripting .2.18 -- scrGlobalEnable .2.18.1 -- scrDTRCtrlPortEnableTable .2.18.2 -- scrDTRCtrlPortEnableEnabletry .2.18.2.1 -- scrDTRCtrlPortEnableIndex .2.18.2.1.1 -- scrDTRCtrlPortEnable .2.18.2.1.2 -- scrTable .2.18.3 -- scrEntry .2.18.3.1 -- scrIndex .2.18.3.1.1 -- scrEnable .2.18.3.1.2 -- scrName .2.18.3.1.3 -- scrFilename .2.18.3.1.4 -- scrRunAlways .2.18.3.1.5 -- scrRunAtStartup .2.18.3.1.6 -- scrRunScheduled .2.18.3.1.7 -- scrScheduleTime .2.18.3.1.8 -- scrArguments .2.18.3.1.9 -- scrRepeatInterval .2.18.3.1.10 -- scrVolatileStringTable .2.18.4 -- scrVolatileStringEntry .2.18.4.1 -- scrVolatileStringIndex .2.18.4.1.1 -- scrVolatileString .2.18.4.1.2 -- scrVolatileIntTable .2.18.5 -- scrVolatileIntEntry .2.18.5.1 -- scrVolatileIntIndex .2.18.5.1.1 -- scrVolatileInt .2.18.5.1.2 -- scrNonVolatileStringTable .2.18.6 -- scrNonVolatileStringEntry .2.18.6.1 -- scrNonVolatileStringIndex .2.18.6.1.1 -- scrNonVolatileString .2.18.6.1.2 -- scrNonVolatileIntTable .2.18.7 -- scrNonVolatileIntEntry .2.18.7.1 -- scrNonVolatileIntIndex .2.18.7.1.1 -- scrNonVolatileInt .2.18.7.1.2 -- generator .2.19 -- genSet .2.19.1 -- genSetEnable .2.19.1.1 -- genSetRelay .2.19.1.2 -- genSetRelayEs .2.19.1.2.1 -- genSetRelayPoint .2.19.1.2.2 -- genSetRelayRunningstate .2.19.1.2.3 -- genSetRelayTable .2.19.1.2.5 -- genSetRelayTableEntry .2.19.1.2.5.1 -- genSetRelayTableIndex .2.19.1.2.5.1.1 -- genSetRelayTableEnable .2.19.1.2.5.1.2 -- genSetRelayTableEs .2.19.1.2.5.1.3 -- genSetRelayTablePoint .2.19.1.2.5.1.4 -- genSetRelayTableRunningstate .2.19.1.2.5.1.5 -- genSetCc .2.19.1.3 -- genSetCcEnable .2.19.1.3.1 -- genSetCcEs .2.19.1.3.2 -- genSetCcPoint .2.19.1.3.3 -- genSetCcRunningstate .2.19.1.3.4 -- genSetCCDelay .2.19.1.3.5 -- genRun .2.19.2 -- genRunMode .2.19.2.1 -- genRunSched .2.19.2.2 -- genRunDuration .2.19.2.3 -- genRunForce .2.19.2.4 -- genRunReqasm .2.19.2.5 -- genRunStatus .2.19.2.6 -- genRunNonstartEvent .2.19.2.7 -- genRunNonstartEventEnable .2.19.2.7.1 -- genRunNonstartEventActions .2.19.2.7.2 -- genRunNonstartEventTrap .2.19.2.7.3 -- genRunNonstartEventClass .2.19.2.7.4 -- calendar .2.20 -- schedTable .2.20.1 -- schedEntry .2.20.1.1 -- schedIndex .2.20.1.1.1 -- schedEnable .2.20.1.1.2 -- schedStart .2.20.1.1.3 -- schedRepeatMode .2.20.1.1.4 -- schedRepeatFreq .2.20.1.1.5 -- schedRepeatEndMode .2.20.1.1.6 -- schedRepeatEndAfter .2.20.1.1.7 -- schedRepeatEndOn .2.20.1.1.8 -- schedRepeatWeeklySun .2.20.1.1.9 -- schedRepeatWeeklyMon .2.20.1.1.10 -- schedRepeatWeeklyTue .2.20.1.1.11 -- schedRepeatWeeklyWed .2.20.1.1.12 -- schedRepeatWeeklyThu .2.20.1.1.13 -- schedRepeatWeeklyFri .2.20.1.1.14 -- schedRepeatWeeklySat .2.20.1.1.15 -- schedRepeatMonthlyMode .2.20.1.1.16 -- schedRepeatMonthlyDates .2.20.1.1.17 -- schedRepeatMonthlyOnThe .2.20.1.1.18 -- schedRepeatMonthlyOnDay .2.20.1.1.19 -- schedRepeatYearlyJan .2.20.1.1.20 -- schedRepeatYearlyFeb .2.20.1.1.21 -- schedRepeatYearlyMar .2.20.1.1.22 -- schedRepeatYearlyApr .2.20.1.1.23 -- schedRepeatYearlyMay .2.20.1.1.24 -- schedRepeatYearlyJun .2.20.1.1.25 -- schedRepeatYearlyJul .2.20.1.1.26 -- schedRepeatYearlyAug .2.20.1.1.27 -- schedRepeatYearlySep .2.20.1.1.28 -- schedRepeatYearlyOct .2.20.1.1.29 -- schedRepeatYearlyNov .2.20.1.1.30 -- schedRepeatYearlyDec .2.20.1.1.31 -- schedRepeatYearlyOnThe .2.20.1.1.32 -- schedRepeatYearlyOnDay .2.20.1.1.33 -- schedNextTrigger .2.20.1.1.34 -- productIds .3 -- siteName 3.1 -- thisProduct .3.2 -- stockTrapString .3.3 -- trapEventTypeNumber .3.4 -- trapEventTypeName .3.5 -- trapIncludedValue .3.6 -- trapIncludedString .3.7 -- trapTypeString .3.8 -- trapEventClassNumber .3.9 -- trapEventClassName .3.10 -- keyInterface .4.0 --*************************************************************************************** --TOP-LEVEL OBJECT IDENTIFIERS --*************************************************************************************** s550notifications OBJECT IDENTIFIER ::= { s550 0 } --1.3.6.1.4.1.3052.10.0 status OBJECT IDENTIFIER ::= { s550 1 } --1.3.6.1.4.1.3052.10.1 eventSensorStatus OBJECT IDENTIFIER ::= { status 1 } --1.3.6.1.4.1.3052.10.1.1 dataEventStatus OBJECT IDENTIFIER ::= { status 2 } --1.3.6.1.4.1.3052.10.1.2 powerDistributionStatus OBJECT IDENTIFIER ::= { status 5 } --1.3.6.1.4.1.3052.10.1.5 pdNextGen OBJECT IDENTIFIER ::= { powerDistributionStatus 4 } --1.3.6.1.4.1.3052.10.1.5.4 pdSystem OBJECT IDENTIFIER ::= { powerDistributionStatus 5 } --1.3.6.1.4.1.3052.10.1.5.5 fuelSensorStatus OBJECT IDENTIFIER ::= { status 6 } --1.3.6.1.4.1.3052.10.1.6 wirelessModemStatus OBJECT IDENTIFIER ::= { status 7 } --1.3.6.1.4.1.3052.10.1.7 acPowerMonitorStatus OBJECT IDENTIFIER ::= { status 8 } --1.3.6.1.4.1.3052.10.1.8 evHVACStatus OBJECT IDENTIFIER ::= { status 11 } --1.3.6.1.4.1.3052.10.1.11 evHVACStatusBard OBJECT IDENTIFIER ::= { evHVACStatus 2 } --1.3.6.1.4.1.3052.10.1.11.2 evHVACStatusBardSystem1 OBJECT IDENTIFIER ::= { evHVACStatusBard 1 } --1.3.6.1.4.1.3052.10.1.11.2.1 evHVACStatusBardSystem1Stage1 OBJECT IDENTIFIER ::= { evHVACStatusBardSystem1 1 } --1.3.6.1.4.1.3052.10.1.11.2.1.1 evHVACStatusBardSystem1Stage2 OBJECT IDENTIFIER ::= { evHVACStatusBardSystem1 2 } --1.3.6.1.4.1.3052.10.1.11.2.1.2 evHVACStatusBardSystem2 OBJECT IDENTIFIER ::= { evHVACStatusBard 2 } --1.3.6.1.4.1.3052.10.1.11.2.2 evHVACStatusBardSystem2Stage1 OBJECT IDENTIFIER ::= { evHVACStatusBardSystem2 1 } --1.3.6.1.4.1.3052.10.1.11.2.2.1 evHVACStatusBardSystem2Stage2 OBJECT IDENTIFIER ::= { evHVACStatusBardSystem2 2 } --1.3.6.1.4.1.3052.10.1.11.2.2.2 evHVACStatusBardTempRemote OBJECT IDENTIFIER ::= { evHVACStatusBard 5 } --1.3.6.1.4.1.3052.10.1.11.2.5 evHVACStatusBardLEDs OBJECT IDENTIFIER ::= { evHVACStatusBard 7 } --1.3.6.1.4.1.3052.10.1.11.2.7.1 evHVACStatusBardLEDsCooling OBJECT IDENTIFIER ::= { evHVACStatusBardLEDs 1 } --1.3.6.1.4.1.3052.10.1.11.2.7.1 evHVACStatusBardLEDsHeating OBJECT IDENTIFIER ::= { evHVACStatusBardLEDs 2 } --1.3.6.1.4.1.3052.10.1.11.2.7.2 evHVACStatusBardLEDsDeHumid OBJECT IDENTIFIER ::= { evHVACStatusBardLEDs 3 } --1.3.6.1.4.1.3052.10.1.11.2.7.3 evHVACStatusBardAlarmStatus OBJECT IDENTIFIER ::= { evHVACStatusBard 10 } --1.3.6.1.4.1.3052.10.1.11.2.10 evHVACStatusBardASSystem1 OBJECT IDENTIFIER ::= { evHVACStatusBardAlarmStatus 1 } --1.3.6.1.4.1.3052.10.1.11.2.10.1 evHVACStatusBardASSystem2 OBJECT IDENTIFIER ::= { evHVACStatusBardAlarmStatus 2 } --1.3.6.1.4.1.3052.10.1.11.2.10.2 evHVACStatusBardASTemp OBJECT IDENTIFIER ::= { evHVACStatusBardAlarmStatus 4 } --1.3.6.1.4.1.3052.10.1.11.2.10.4 evHVACStatusAsentria OBJECT IDENTIFIER ::= { evHVACStatus 3 } --1.3.6.1.4.1.3052.10.1.11.3 evHVACStatusAsentriaTemp OBJECT IDENTIFIER ::= { evHVACStatusAsentria 5 } --1.3.6.1.4.1.3052.10.1.11.3.5 evHVACStatusAsentriaHumid OBJECT IDENTIFIER ::= { evHVACStatusAsentria 6 } --1.3.6.1.4.1.3052.10.1.11.3.6 evHVACStatusAirsys OBJECT IDENTIFIER ::= { evHVACStatus 4 } --1.3.6.1.4.1.3052.10.1.11.4 evHVACStatusAirsysAlarm OBJECT IDENTIFIER ::= { evHVACStatusAirsys 1 } --1.3.6.1.4.1.3052.10.1.11.4.1 backupBattStatus OBJECT IDENTIFIER ::= { status 12 } --1.3.6.1.4.1.3052.10.1.12 liBattStatus OBJECT IDENTIFIER ::= { backupBattStatus 1 } --1.3.6.1.4.1.3052.10.1.12.1 config OBJECT IDENTIFIER ::= { s550 2 } --1.3.6.1.4.1.3052.10.2 eventSensorBasics OBJECT IDENTIFIER ::= { config 1 } --1.3.6.1.4.1.3052.10.2.1 eventSensorPointConfig OBJECT IDENTIFIER ::= { config 2 } --1.3.6.1.4.1.3052.10.2.2 serialPorts OBJECT IDENTIFIER ::= { config 3 } --1.3.6.1.4.1.3052.10.2.3 network OBJECT IDENTIFIER ::= { config 4 } --1.3.6.1.4.1.3052.10.2.4 interface OBJECT IDENTIFIER ::= { network 1 } --1.3.6.1.4.1.3052.10.2.4 ethernet OBJECT IDENTIFIER ::= { interface 1 } --1.3.6.1.4.1.3052.10.2.4.1 ethernet1 OBJECT IDENTIFIER ::= { ethernet 1 } --1.3.6.1.4.1.3052.10.2.4.1.1 eth1VLAN OBJECT IDENTIFIER ::= { ethernet1 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.5 eth1VLAN1 OBJECT IDENTIFIER ::= { eth1VLAN 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.1 eth1VLAN2 OBJECT IDENTIFIER ::= { eth1VLAN 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.2 eth1VLAN3 OBJECT IDENTIFIER ::= { eth1VLAN 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.3 eth1VLAN4 OBJECT IDENTIFIER ::= { eth1VLAN 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.4 eth1VLAN5 OBJECT IDENTIFIER ::= { eth1VLAN 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.5 eth1VLAN6 OBJECT IDENTIFIER ::= { eth1VLAN 6 } --1.3.6.1.4.1.3052.10.2.4.1.1.5.6 eth1IPv6 OBJECT IDENTIFIER ::= { ethernet1 7 } --1.3.6.1.4.1.3052.10.2.4.1.1.7 eth1IPv6Static OBJECT IDENTIFIER ::= { eth1IPv6 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.7.2 eth1IPv6Auto OBJECT IDENTIFIER ::= { eth1IPv6 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.7.3 ethernet2 OBJECT IDENTIFIER ::= { ethernet 2 } --1.3.6.1.4.1.3052.10.2.4.1.2 eth2VLAN OBJECT IDENTIFIER ::= { ethernet2 5 } --1.3.6.1.4.1.3052.10.2.4.1.2.5 eth2VLAN1 OBJECT IDENTIFIER ::= { eth2VLAN 1 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.1 eth2VLAN2 OBJECT IDENTIFIER ::= { eth2VLAN 2 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.2 eth2VLAN3 OBJECT IDENTIFIER ::= { eth2VLAN 3 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.3 eth2VLAN4 OBJECT IDENTIFIER ::= { eth2VLAN 4 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.4 eth2VLAN5 OBJECT IDENTIFIER ::= { eth2VLAN 5 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.5 eth2VLAN6 OBJECT IDENTIFIER ::= { eth2VLAN 6 } --1.3.6.1.4.1.3052.10.2.4.1.2.5.6 eth2IPv6 OBJECT IDENTIFIER ::= { ethernet2 7 } --1.3.6.1.4.1.3052.10.2.4.1.2.7 eth2IPv6Static OBJECT IDENTIFIER ::= { eth2IPv6 2 } --1.3.6.1.4.1.3052.10.2.4.1.2.7.2 eth2IPv6Auto OBJECT IDENTIFIER ::= { eth2IPv6 3 } --1.3.6.1.4.1.3052.10.2.4.1.2.7.3 snmp OBJECT IDENTIFIER ::= { network 8 } --1.3.6.1.4.1.3052.10.2.4.8 snmpNotificationTx OBJECT IDENTIFIER ::= { snmp 7 } --1.3.6.1.4.1.3052.10.2.4.8.7 snmpProxy OBJECT IDENTIFIER ::= { snmp 8 } --1.3.6.1.4.1.3052.10.2.4.8.8 snmpPoll OBJECT IDENTIFIER ::= { snmp 9 } --1.3.6.1.4.1.3052.10.2.4.8.9 ftpPush OBJECT IDENTIFIER ::= { network 9 } --1.3.6.1.4.1.3052.10.2.4.9 ppp OBJECT IDENTIFIER ::= { network 10 } --1.3.6.1.4.1.3052.10.2.4.10 pppDial OBJECT IDENTIFIER ::= { ppp 1 } --1.3.6.1.4.1.3052.10.2.4.10.1 pppHost OBJECT IDENTIFIER ::= { ppp 2 } --1.3.6.1.4.1.3052.10.2.4.10.2 routing OBJECT IDENTIFIER ::= { network 11 } --1.3.6.1.4.1.3052.10.2.4.11 netSecurity OBJECT IDENTIFIER ::= { network 12 } --1.3.6.1.4.1.3052.10.2.4.12 ipRestriction OBJECT IDENTIFIER ::= { netSecurity 1 } --1.3.6.1.4.1.3052.10.2.4.12.1 rts OBJECT IDENTIFIER ::= { network 13 } --1.3.6.1.4.1.3052.10.2.4.13 rtsAlarms OBJECT IDENTIFIER ::= { rts 2 } --1.3.6.1.4.1.3052.10.2.4.13.2 trap OBJECT IDENTIFIER ::= { network 14 } --1.3.6.1.4.1.3052.10.2.4.14 trapInclude OBJECT IDENTIFIER ::= { trap 1} --1.3.6.1.4.1.3052.10.2.4.14.1 routeTest OBJECT IDENTIFIER ::= { network 15 } --1.3.6.1.4.1.3052.10.2.4.15 wireless OBJECT IDENTIFIER ::= { network 16 } --1.3.6.1.4.1.3052.10.2.4.16 wirelessConnectivity OBJECT IDENTIFIER ::= { wireless 20 } --1.3.6.1.4.1.3052.10.2.4.16.20 email OBJECT IDENTIFIER ::= { network 17 } --1.3.6.1.4.1.3052.10.2.4.17 netAdvanced OBJECT IDENTIFIER ::= { network 18 } --1.3.6.1.4.1.3052.10.2.4.18 web OBJECT IDENTIFIER ::= { network 19 } --1.3.6.1.4.1.3052.10.2.4.19 webXMLProxy OBJECT IDENTIFIER ::= { web 4 } --1.3.6.1.4.1.3052.10.2.4.19.4 ethExpan OBJECT IDENTIFIER ::= { network 20 } --1.3.6.1.4.1.3052.10.2.4.20 ethExpanDHCP OBJECT IDENTIFIER ::= { ethExpan 6 } --1.3.6.1.4.1.3052.10.2.4.20.6 ipv6 OBJECT IDENTIFIER ::= { network 21 } --1.3.6.1.4.1.3052.10.2.4.21 cpe OBJECT IDENTIFIER ::= { network 22 } --1.3.6.1.4.1.3052.10.2.4.22 dnp3 OBJECT IDENTIFIER ::= { network 23 } --1.3.6.1.4.1.3052.10.2.4.23 dnp3General OBJECT IDENTIFIER ::= { dnp3 1 } --1.3.6.1.4.1.3052.10.2.4.23.1 dnp3Outstation OBJECT IDENTIFIER ::= { dnp3 2 } --1.3.6.1.4.1.3052.10.2.4.23.2 dnp3Master OBJECT IDENTIFIER ::= { dnp3 3 } --1.3.6.1.4.1.3052.10.2.4.23.3 dnp3Error OBJECT IDENTIFIER ::= { dnp3 4 } --1.3.6.1.4.1.3052.10.2.4.23.4 dnp3Status OBJECT IDENTIFIER ::= { dnp3 5 } --1.3.6.1.4.1.3052.10.2.4.23.5 modem OBJECT IDENTIFIER ::= { config 5 } --1.3.6.1.4.1.3052.10.2.5 modemClid OBJECT IDENTIFIER ::= { modem 8 } --1.3.6.1.4.1.3052.10.2.5.7 time OBJECT IDENTIFIER ::= { config 8 } --1.3.6.1.4.1.3052.10.2.8 console OBJECT IDENTIFIER ::= { config 10 } --1.3.6.1.4.1.3052.10.2.10 unitSecurity OBJECT IDENTIFIER ::= { config 11 } --1.3.6.1.4.1.3052.10.2.11 secCore OBJECT IDENTIFIER ::= { unitSecurity 1 } --1.3.6.1.4.1.3052.10.2.11.1 secFactory OBJECT IDENTIFIER ::= { unitSecurity 3 } --1.3.6.1.4.1.3052.10.2.11.3 secSSH OBJECT IDENTIFIER ::= { unitSecurity 4 } --1.3.6.1.4.1.3052.10.2.11.4 secVPN OBJECT IDENTIFIER ::= { unitSecurity 5 } --1.3.6.1.4.1.3052.10.2.11.5 event OBJECT IDENTIFIER ::= { config 12 } --1.3.6.1.4.1.3052.10.2.12 evCore OBJECT IDENTIFIER ::= { event 1 } --1.3.6.1.4.1.3052.10.2.12.1 evLog OBJECT IDENTIFIER ::= { evCore 3 } --1.3.6.1.4.1.3052.10.2.12.1.3 evMgmt OBJECT IDENTIFIER ::= { evCore 4 } --1.3.6.1.4.1.3052.10.2.12.1.4 evData OBJECT IDENTIFIER ::= { event 2 } --1.3.6.1.4.1.3052.10.2.12.1 evdCore OBJECT IDENTIFIER ::= { evData 1 } --1.3.6.1.4.1.3052.10.2.12.2.1 evNoData1 OBJECT IDENTIFIER ::= { event 3 } --1.3.6.1.4.1.3052.10.2.12.3 evNoData2 OBJECT IDENTIFIER ::= { event 4 } --1.3.6.1.4.1.3052.10.2.12.4 evSched1 OBJECT IDENTIFIER ::= { event 5 } --1.3.6.1.4.1.3052.10.2.12.5 evSched2 OBJECT IDENTIFIER ::= { event 6 } --1.3.6.1.4.1.3052.10.2.12.6 evNoSensor OBJECT IDENTIFIER ::= { event 9 } --1.3.6.1.4.1.3052.10.2.12.9 fuelSensor OBJECT IDENTIFIER ::= { event 11 } --1.3.6.1.4.1.3052.10.2.12.11 acPowerMonitor OBJECT IDENTIFIER ::= { event 12 } --1.3.6.1.4.1.3052.10.2.12.12 evReset OBJECT IDENTIFIER ::= { event 16 } --1.3.6.1.4.1.3052.10.2.12.16 evGlobal OBJECT IDENTIFIER ::= { event 18 } --1.3.6.1.4.1.3052.10.2.12.18 evHVAC OBJECT IDENTIFIER ::= { event 19 } --1.3.6.1.4.1.3052.10.2.12.19 evHVACBard OBJECT IDENTIFIER ::= { evHVAC 2 } --1.3.6.1.4.1.3052.10.2.12.19.2 evHVACBardLocal OBJECT IDENTIFIER ::= { evHVACBard 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.1 evHVACBardAlarm OBJECT IDENTIFIER ::= { evHVACBardLocal 7 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7 evHVACBardSynchronized OBJECT IDENTIFIER ::= { evHVACBard 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.2 evHVACBardDiff OBJECT IDENTIFIER ::= { evHVACBardSynchronized 19 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19 evHVACBardTemp OBJECT IDENTIFIER ::= { evHVACBardSynchronized 32 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32 evHVACAsentria OBJECT IDENTIFIER ::= { evHVAC 3 } --1.3.6.1.4.1.3052.10.2.12.19.3 evHVACAsentriaAlarm OBJECT IDENTIFIER ::= { evHVACAsentria 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.6 evHVACAsentriaFire OBJECT IDENTIFIER ::= { evHVACAsentria 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.7 evHVACAsentriaTemp OBJECT IDENTIFIER ::= { evHVACAsentria 9 } --1.3.6.1.4.1.3052.10.2.12.19.3.9 evHVACAsentriaHumid OBJECT IDENTIFIER ::= { evHVACAsentria 10 } --1.3.6.1.4.1.3052.10.2.12.19.3.10 evHVACAirsys OBJECT IDENTIFIER ::= { evHVAC 4 } --1.3.6.1.4.1.3052.10.2.12.19.4 evHVACAirsysGeneral OBJECT IDENTIFIER ::= { evHVACAirsys 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.1 evHVACAirsysAlarm OBJECT IDENTIFIER ::= { evHVACAirsys 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.2 evHVACAirsysTemp OBJECT IDENTIFIER ::= { evHVACAirsys 3 } --1.3.6.1.4.1.3052.10.2.12.19.4.3 evHVACAirsysHumid OBJECT IDENTIFIER ::= { evHVACAirsys 4 } --1.3.6.1.4.1.3052.10.2.12.19.4.4 evEvps OBJECT IDENTIFIER ::= { event 20 } --1.3.6.1.4.1.3052.10.2.12.20 accessControl OBJECT IDENTIFIER ::= { event 21 } --1.3.6.1.4.1.3052.10.2.12.21 telemetry OBJECT IDENTIFIER ::= { event 22 } --1.3.6.1.4.1.3052.10.2.12.22 siteSecurity OBJECT IDENTIFIER ::= { event 23 } --1.3.6.1.4.1.3052.10.2.12.23 action OBJECT IDENTIFIER ::= { config 14 } --1.3.6.1.4.1.3052.10.2.14 actionSched OBJECT IDENTIFIER ::= { action 3 } --1.3.6.1.4.1.3052.10.2.14.3 actionAsentria OBJECT IDENTIFIER ::= { action 4 } --1.3.6.1.4.1.3052.10.2.14.4 sys OBJECT IDENTIFIER ::= { config 16 } --1.3.6.1.4.1.3052.10.2.16 sysTime OBJECT IDENTIFIER ::= { sys 1 } --1.3.6.1.4.1.3052.10.2.16.1 sysTimeNet OBJECT IDENTIFIER ::= { sysTime 4 } --1.3.6.1.4.1.3052.10.2.16.1.4 sysPT OBJECT IDENTIFIER ::= { sys 2 } --1.3.6.1.4.1.3052.10.2.16.2 sysTimeStamp OBJECT IDENTIFIER ::= { sys 8 } --1.3.6.1.4.1.3052.10.2.16.8 sysLog OBJECT IDENTIFIER ::= { sys 9 } --1.3.6.1.4.1.3052.10.2.16.9 sysCRDB OBJECT IDENTIFIER ::= { sys 10 } --1.3.6.1.4.1.3052.10.2.16.10 sysLoc OBJECT IDENTIFIER ::= { sys 14 } --1.3.6.1.4.1.3052.10.2.16.14 sysAssetMgmt OBJECT IDENTIFIER ::= { sys 15 } --1.3.6.1.4.1.3052.10.2.16.15 sysFileTransfer OBJECT IDENTIFIER ::= { sys 17 } --1.3.6.1.4.1.3052.10.2.16.17 sysUpdate OBJECT IDENTIFIER ::= { sys 18 } --1.3.6.1.4.1.3052.10.2.16.18 auditLog OBJECT IDENTIFIER ::= { config 17 } --1.3.6.1.4.1.3052.10.2.17 scripting OBJECT IDENTIFIER ::= { config 18 } --1.3.6.1.4.1.3052.10.2.18 generator OBJECT IDENTIFIER ::= { config 19 } --1.3.6.1.4.1.3052.10.2.19 genSet OBJECT IDENTIFIER ::= { generator 1 } --1.3.6.1.4.1.3052.10.2.19.1 genSetRelay OBJECT IDENTIFIER ::= { genSet 2 } --1.3.6.1.4.1.3052.10.2.19.1.2 genSetCC OBJECT IDENTIFIER ::= { genSet 3 } --1.3.6.1.4.1.3052.10.2.19.1.3 genRun OBJECT IDENTIFIER ::= { generator 2 } --1.3.6.1.4.1.3052.10.2.19.2 genRunNonstartEvent OBJECT IDENTIFIER ::= { genRun 7 } --1.3.6.1.4.1.3052.10.2.19.2.7 calendar OBJECT IDENTIFIER ::= { config 20 } --1.3.6.1.4.1.3052.10.2.20 productIds OBJECT IDENTIFIER ::= { s550 3 } --1.3.6.1.4.1.3052.10.3 --*************************************************************************************** --OBJECT DEFINITIONS --*************************************************************************************** --*************************************************************************************** --EventSensor Status Section 1.1 --*************************************************************************************** esPointTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION " This table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, output 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). " ::= { eventSensorStatus 1 } --1.3.6.1.4.1.3052.10.1.1.1 esPointEntry OBJECT-TYPE SYNTAX ESPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point table" INDEX { esIndexES, esIndexPC, esIndexPoint } ::= { esPointTable 1 } --1.3.6.1.4.1.3052.10.1.1.1.1 esIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. " ::= { esPointEntry 1 } --1.3.6.1.4.1.3052.10.1.1.1.1.1 esIndexPC OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=output (relay output or power output) " ::= { esPointEntry 2 } --1.3.6.1.4.1.3052.10.1.1.1.1.2 esIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or output) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3." ::= { esPointEntry 3 } --1.3.6.1.4.1.3052.10.1.1.1.1.3 esPointName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as ''. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as ''. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name." ::= { esPointEntry 4 } --1.3.6.1.4.1.3052.10.1.1.1.1.4 esPointInEventState OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures the values of this object are: 1=point in event state 2=point in normal state For outputs the values of this object is the numeric code for the logical state of the output: 1 or 2. The logical state of the output is either active/inactive for relay outputs or on/off for power outputs. The logical state of the output has different nomenclature depending on the type of the output (relay output or power output): 1=active (for relay output) or on (for power output) 2=inactive (for relay output) or off (for power output) This is not necessarily representative of physical state of the output. Physical state is energized/de-energized, for both relay and power outputs. For relay outputs, the active logical state corresponds to either the energized physical state or the de-energized physical state depending on how the relay output is configured. For power outputs, the on logical state always corresponds to the energized physical state. For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except output, this object is read-only. For outputs, setting this object to 1 puts the output into its active logical state. Setting this object to 2 puts the output into its inactive logical state. Setting this object to any value greater than 2 puts the output into its active logical state for that many seconds (up to 3600), after which time it puts the output into its inactive logical state. " ::= { esPointEntry 5 } --1.3.6.1.4.1.3052.10.1.1.1.1.5 esPointValueInt OBJECT-TYPE SYNTAX Integer32 (-2147483648..2147483647) MAX-ACCESS read-write STATUS current DESCRIPTION "A read-only number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. If the point class is an output, then this object is the numeric code for the physical state of the output. 0=de-energized 1=energized This object cannot be used to control the output, i.e, change its logical or physical state (instead use the esPointInEventState object). " ::= { esPointEntry 6 } --1.3.6.1.4.1.3052.10.1.1.1.1.6 esPointValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A string referring to the value of a point on an EventSensor. For contact closures this object is either 'Open' or 'Closed'. For outputs this object is a concatenation of the logical state and physical state, separated by '/'. For a relay output this object can be one of the following 4 possible values: Active/Energized Inactive/Energized Active/De-energized Inactve/De-energized For a power output this object can be one of the following 2 possible values: On/Energized Off/De-energized For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in the configured units appended with the unit name. " ::= { esPointEntry 7 } --1.3.6.1.4.1.3052.10.1.1.1.1.7 esPointTimeLastChange OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last time an event was triggerred for a point on an EventSensor in MM/DD/YY HH:MM:SS format. For contact closures, the possible events are Active and Inactive. For temperature, humidity, and analog inputs, the possible events are Normal, High, Very High, Low, and Very Low. For outputs, this object is a null string." ::= { esPointEntry 8 } --1.3.6.1.4.1.3052.10.1.1.1.1.8 esPointTimetickLastChange OBJECT-TYPE SYNTAX TimeTicks MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last time an event was triggerred for a point on an EventSensor in 100ths of seconds since reset. For contact closures, the possible events are Active and Inactive. For temperature, humidity, and analog inputs, the possible events are Normal, High, Very High, Low, and Very Low. For outputs, this object is 0." ::= { esPointEntry 9 } --1.3.6.1.4.1.3052.10.1.1.1.1.9 esPointAliasValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "For CC inputs, this is the CC active/inactive alias setting setting value that currently corresponds to the event state. So if the CC input is in the event state, then this object is the active alias setting value. If the CC input is in the normal state, then this object is the inactive alias setting value. For relay/power outputs, this is the output active/inactive alias setting value that currently corresponds to the output state. So if the output is in the active state, then this object is the active alias setting value. If the output is in hte inactive state, then this object is the inactive alias setting value. For non-CC and non-output sensors, this is the same as the esPointValueStr object." ::= { esPointEntry 10 } --1.3.6.1.4.1.3052.10.1.1.1.1.10 esPointClassValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "For CC inputs, this is the CC active/inactive class setting setting value that currently corresponds to the event state. So if the CC input is in the event state, then this object is the active class setting value. If the CC input is in the normal state, then this object is the inactive class setting value. For relay/power, analog and temp outputs, this is the output class string given the event (Very High, High, Normal, Low and Very Low). The class string is based upon the chosen string in the class table for e.g. Info, Minor, Major, Minor, Critical etc. If the given event is High, the chosen Class string for this event is what returned. " ::= { esPointEntry 11 } --1.3.6.1.4.1.3052.10.1.1.1.1.11 --*************************************************************************************** --Data Event Status Section 1.2 --*************************************************************************************** deStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF DEStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "Data Event Status Table" ::= { dataEventStatus 1 } --1.3.6.1.4.1.3052.10.1.2.1 deStatusEntry OBJECT-TYPE SYNTAX DEStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "EventSensor status entry" INDEX { deStatusIndex } ::= { deStatusTable 1 } --1.3.6.1.4.1.3052.10.1.2.1.1 deStatusIndex OBJECT-TYPE SYNTAX Integer32 (1..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Data Events" ::= { deStatusEntry 1 } --1.3.6.1.4.1.3052.10.1.2.1.1.1 deStatusName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Data Event name" ::= { deStatusEntry 2 } --1.3.6.1.4.1.3052.10.1.2.1.1.2 deStatusCounter OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of times a data record has matched this event's equation. Range: 1-999999999" ::= { deStatusEntry 3 } --1.3.6.1.4.1.3052.10.1.2.1.1.3 deStatusThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of times the equation is matched before an event is triggered. Range: 1-999999999" ::= { deStatusEntry 4 } --1.3.6.1.4.1.3052.10.1.2.1.1.4 modemStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "status of modem (idle, dialing, connected, etc.)" ::= { status 3 } --1.3.6.1.4.1.3052.10.1.3 modemCLIDLogTable OBJECT-TYPE SYNTAX SEQUENCE OF ModemCLIDLogConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of numbers of recent dialing parties" ::= { status 4 } --1.3.6.1.4.1.3052.10.1.4 modemCLIDLogEntry OBJECT-TYPE SYNTAX ModemCLIDLogConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of CLID log entries" INDEX { modemCLIDLogIndex } ::= { modemCLIDLogTable 1 } --1.3.6.1.4.1.3052.10.1.4.1 modemCLIDLogIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of CLID log entries" ::= { modemCLIDLogEntry 1 } --1.3.6.1.4.1.3052.10.1.4.1.1 modemCLIDLogNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "recently logged number of dialing party" ::= { modemCLIDLogEntry 2 } --1.3.6.1.4.1.3052.10.1.4.1.2 --*************************************************************************************** --Power Distribution Status Section 1.5 --*************************************************************************************** pdConfig OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Power Distribution output configuration" ::= { powerDistributionStatus 1 } --1.3.6.1.4.1.3052.10.1.5.1 PowerDistribNextGen ::= SEQUENCE { pdnIndexPD Integer32, pdnIndexOutput Integer32, pdnConfig DisplayString, pdnMainCurrentInEventState DisplayString, pdnMainCurrentValue Integer32, pdnMainCurrentValueStr DisplayString, pdnMainCurrentDeadband Integer32, pdnMainCurrentVHighCurrent Integer32, pdnMainCurrentHighCurrent Integer32, pdnMainCurrentLowCurrent Integer32, pdnMainCurrentVLowCurrent Integer32, pdnMainVoltageInEventState DisplayString, pdnMainVoltageValue Integer32, pdnMainVoltageValueStr DisplayString, pdnMainVoltageDeadband Integer32, pdnMainVoltageVHighVoltage Integer32, pdnMainVoltageHighVoltage Integer32, pdnMainVoltageLowVoltage Integer32, pdnMainVoltageVLowVoltage Integer32, pdnMainPowerValue Integer32, pdnMainPowerValueStr DisplayString, pdnOutputCurrentInEventState DisplayString, pdnOutputCurrentValue Integer32, pdnOutputCurrentValueStr DisplayString, pdnOutputCurrentDeadband Integer32, pdnOutputCurrentVHighCurrent Integer32, pdnOutputCurrentHighCurrent Integer32, pdnOutputCurrentLowCurrent Integer32, pdnOutputCurrentVLowCurrent Integer32, pdnOutputFuseInEventState DisplayString, pdnOutputFuseValueStr DisplayString, pdnMainCombinedStatus DisplayString, pdnOutputCombinedStatusBlock1 DisplayString, pdnOutputCombinedStatusBlock2 DisplayString, pdnDeviceCurrentValue Integer32, pdnDeviceCurrentValueStr DisplayString } pdnTable OBJECT-TYPE SYNTAX SEQUENCE OF PowerDistribNextGen MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of power distribution objects arranged according to next-generation methodology (i.e., using multiple PowerBoss power distributors in addition to the on-board power distributor)." ::= { pdNextGen 1 } --1.3.6.1.4.1.3052.10.1.5.4.1 pdnEntry OBJECT-TYPE SYNTAX PowerDistribNextGen MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of power distribution objects arranged according to next-generation methodology (i.e., using multiple PowerBoss power distributors in addition to the on-board power distributor)." INDEX { pdnIndexPD, pdnIndexOutput } ::= { pdnTable 1 } --1.3.6.1.4.1.3052.10.1.5.4.1.1 pdnIndexPD OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of power distribution objects, specifically the index that refers to which power distributor. A value of 200 means the internal power distributor. A value from 1 to 16 refers to an external power distributor (PowerBoss), and is the same value as esIndexES, which refers to the PowerBoss as an EventSensor in the eventSensorStatus object table. In other words, pdnIndexPD is the same as esIndexES: esIndexES is used to refer to the PowerBoss as an eventsensor (i.e., control outputs), while pdnIndexPD is used to refer to the PowerBoss when used for power distribution monitoring (i.e., to alarm on output current/voltage/fuse status)." ::= { pdnEntry 1 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.1 pdnIndexOutput OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of power distribution objects, specifically the index that refers to which output on the power distributor specified by pdnIndexPD. For objects where the output is irrelevant, this index should be 1." ::= { pdnEntry 2 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.2 pdnConfig OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The number of outputs on the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 3 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.3 pdnMainCurrentInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The event state of the current (i.e. Amps) event of the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'." ::= { pdnEntry 4 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.4 pdnMainCurrentValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current drawn, in mA, for the power distributor specified by pdnIndexPD. If pdnIndexPD is 1-16 then this is an external power distributor (PowerBoss) and refers to the current drawn by that PowerBoss and all equipment powered by that PowerBoss. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 5 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.5 pdnMainCurrentValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Essentially pdnMainCurrentValue formatted as a string in units of Amps, with 3 decimal places. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 6 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.6 pdnMainCurrentDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The deadband, in mA, for the main current sensor for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 7 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.7 pdnMainCurrentVHighCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for the main current sensor's Very High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 8 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.8 pdnMainCurrentHighCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for the main current sensor's High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 9 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.9 pdnMainCurrentLowCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for the main current sensor's Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 10 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.10 pdnMainCurrentVLowCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for the main current sensor's Very Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 11 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.11 pdnMainVoltageInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The event state of the voltage event of the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'." ::= { pdnEntry 12 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.12 pdnMainVoltageValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage, in mV, at the power distributor specified by pdnIndexPD. If pdnIndexPD is 1-16 then this is an external power distributor (PowerBoss) and refers to the voltage at that PowerBoss and all equipment powered by that PowerBoss. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 13 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.13 pdnMainVoltageValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Essentially pdnMainVoltageValue formatted as a string in units of Volts, with 3 decimal places. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 14 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.14 pdnMainVoltageDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The deadband, in mV, for the main voltage sensor for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 15 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.15 pdnMainVoltageVHighVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage, in mA, for the main voltage sensor's Very High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 16 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.16 pdnMainVoltageHighVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage, in mV, for the main voltage sensor's High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 17 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.17 pdnMainVoltageLowVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage, in mV, for the main voltage sensor's Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 18 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.18 pdnMainVoltageVLowVoltage OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The voltage, in mV, for the main voltage sensor's Very Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 19 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.19 pdnMainPowerValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The power, in Watts, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 20 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.20 pdnMainPowerValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The power, in Watts, for the power distributor specified by pdIndexPD, formatted as a string with the unit name 'Watts'. pdnIndexOutput should be 1 for this object." ::= { pdnEntry 21 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.21 pdnOutputCurrentInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The event state of the current (i.e. Amps) event of the power distributor output specified by pdnIndexPD and pdnIndexOutput. E.g., for pdnIndexPD=200 and pdnIndexOutput=2, this refers to power output #2 of the internal power distributor. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'." ::= { pdnEntry 22 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.22 pdnOutputCurrentValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current drawn, in mA, for the power distributor output specified by pdnIndexPD and pdIndexOutput. E.g., if pdIndexPD is 3 then this is an external power distributor (PowerBoss) identified as 'power distributor 3' and refers to the current drawn by a specific power output on that PowerBoss. The specific power output is specified by pdIndexOutput." ::= { pdnEntry 23 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.23 pdnOutputCurrentValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Essentially pdnOutputCurrentValue formatted as a string in units of Amps, with 3 decimal places." ::= { pdnEntry 24 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.24 pdnOutputCurrentDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The deadband, in mA, for the main current sensor for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput." ::= { pdnEntry 25 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.25 pdnOutputCurrentVHighCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for a specific power output's current sensor Very High event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput." ::= { pdnEntry 26 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.26 pdnOutputCurrentHighCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for a specific power output's current sensor High event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object." ::= { pdnEntry 27 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.27 pdnOutputCurrentLowCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for a specific power output's current sensor Low event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object." ::= { pdnEntry 28 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.28 pdnOutputCurrentVLowCurrent OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The current, in mA, for a specific power output's current sensor Very Low event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object." ::= { pdnEntry 29 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.29 pdnOutputFuseInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The event state of the fuse event of the power distributor output specified by pdnIndexPD and pdnIndexOutput. E.g., for pdnIndexPD=14 and pdnIndexOutput=2, this refers to power output #2 of the external power distributor (PowerBoss), identified as 'power distributor 14'. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'. This object exists only for power distributors with fuse monitoring support." ::= { pdnEntry 30 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.30 pdnOutputFuseValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The state of the fuse of the power distributor output specified by pdnIndexPD and pdnIndexOutput. Possible values for this object are: 'BLOWN' and 'OK'. This object exists only for power distributors with fuse monitoring support." ::= { pdnEntry 31 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.31 pdnMainCombinedStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: format: voltageColorCode`voltageEventState`voltageValue`mainCurrentColorCode`mainCurrentEventState`mainCurrentValue`deviceCurrentValue`mainPowerValue" ::= { pdnEntry 32 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.32 pdnOutputCombinedStatusBlock1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: format: numInBlock~outputCurrentColorCode1`outputCurrentEventState1`outputCurrentValue1`fuseColorCode1`fuseValue1~..." ::= { pdnEntry 33 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.33 pdnOutputCombinedStatusBlock2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: format: numInBlock~outputCurrentColorCode1`outputCurrentEventState1`outputCurrentValue1`fuseColorCode1`fuseValue1~..." ::= { pdnEntry 34 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.34 pdnDeviceCurrentValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current drawn by device in mA. For the internal power distributor device, this is the current drawn by the SiteBoss 571. For an external power distributor device (PowerBoss), this is the current drawn by the PowerBoss. This object exists only for power distributors with device current monitoring support." ::= { pdnEntry 35 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.35 pdnDeviceCurrentValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Current drawn by device as a string with units (Amps). For the internal power distributor device, this is the current drawn by the SiteBoss 571. For an external power distributor device (PowerBoss), this is the current drawn by the PowerBoss. This object exists only for power distributors with device current monitoring support." ::= { pdnEntry 36 } --1.3.6.1.4.1.3052.10.1.5.4.1.1.36 pdSystemCurrent OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total current drawn by all power distributors in system; that is, the sum of all pdnMainCurrentValue objects for all connected power distributors: internal and external." ::= { pdSystem 1 } --1.3.6.1.4.1.3052.10.1.5.5.1 pdSystemPower OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power used by all power distributors in system; that is, the sum of all pdnMainPowerValue objects for all connected power distributors: internal and external." ::= { pdSystem 2 } --1.3.6.1.4.1.3052.10.1.5.5.2 --*************************************************************************************** --Fuel Sensor 1.6 --*************************************************************************************** fsStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF FSStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "Fuel sensor status table" ::= { fuelSensorStatus 1 } --1.3.6.1.4.1.3052.10.1.6.1 fsStatusEntry OBJECT-TYPE SYNTAX FSStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "Fuel sensor status table entry" INDEX { fsStatusIndex } ::= { fsStatusTable 1 } --1.3.6.1.4.1.3052.10.1.6.1.1 fsStatusIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for fuel sensors" ::= { fsStatusEntry 1 } --1.3.6.1.4.1.3052.10.1.6.1.1.1 fsStatusName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Fuel sensor name" ::= { fsStatusEntry 2 } --1.3.6.1.4.1.3052.10.1.6.1.1.2 fsStatusDeviceState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Fuel sensor device state" ::= { fsStatusEntry 3 } --1.3.6.1.4.1.3052.10.1.6.1.1.3 fsStatusVolumeValueString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Fuel volume. Range is -2,147,483,648 to 2,147,483,647. This value reads -999 when the fuel sensor is disconnected" ::= { fsStatusEntry 4 } --1.3.6.1.4.1.3052.10.1.6.1.1.4 fsStatusVolumePercentLevel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Height of the fluid in the tank expressed as a percentage of the tank height, in hundredths of a percent." ::= { fsStatusEntry 7 } --1.3.6.1.4.1.3052.10.1.6.1.1.7 fsStatusVolumeInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Current event status of the fuel sensor." ::= { fsStatusEntry 8 } --1.3.6.1.4.1.3052.10.1.6.1.1.8 fsStatusCombined OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: deviceState`deviceStateColorCode`percentRounded`valueAsFloat`volumeEventState`volumeEventStateColorCode`capacity`units`name" ::= { fsStatusEntry 9 } --1.3.6.1.4.1.3052.10.1.6.1.1.9 --*************************************************************************************** --Wireless Modem Status Section 1.7 --*************************************************************************************** wmsStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem status" ::= { wirelessModemStatus 1 } --1.3.6.1.4.1.3052.10.1.7.1 wmsSignal OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Signal strength" ::= { wirelessModemStatus 2 } --1.3.6.1.4.1.3052.10.1.7.2 wmsRSSI OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Signal strength (RSSI)" ::= { wirelessModemStatus 3 } --1.3.6.1.4.1.3052.10.1.7.3 wmsBER OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Bit Error Rate" ::= { wirelessModemStatus 4 } --1.3.6.1.4.1.3052.10.1.7.4 wmsUpdated OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem info last update time" ::= { wirelessModemStatus 5 } --1.3.6.1.4.1.3052.10.1.7.5 wmsRegistration OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem registration status" ::= { wirelessModemStatus 6 } --1.3.6.1.4.1.3052.10.1.7.6 wmsLAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Location Area Code" ::= { wirelessModemStatus 7 } --1.3.6.1.4.1.3052.10.1.7.7 wmsCellID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Cell ID" ::= { wirelessModemStatus 8 } --1.3.6.1.4.1.3052.10.1.7.8 wmsIMSI OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem Internation Mobile Subscriber Identity number" ::= { wirelessModemStatus 9 } --1.3.6.1.4.1.3052.10.1.7.9 wmsPhnum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem phone number" ::= { wirelessModemStatus 10 } --1.3.6.1.4.1.3052.10.1.7.10 wmsLocalIP OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Local IP address of modem on wireless network" ::= { wirelessModemStatus 11 } --1.3.6.1.4.1.3052.10.1.7.11 wmsMgfID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem manufacturer ID" ::= { wirelessModemStatus 12 } --1.3.6.1.4.1.3052.10.1.7.12 wmsModelID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem model ID" ::= { wirelessModemStatus 13 } --1.3.6.1.4.1.3052.10.1.7.13 wmsIMEI OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem International Mobile Equipment Identity number" ::= { wirelessModemStatus 14 } --1.3.6.1.4.1.3052.10.1.7.14 wmsRevID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem revision ID" ::= { wirelessModemStatus 15 } --1.3.6.1.4.1.3052.10.1.7.15 wmsNetName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem network name" ::= { wirelessModemStatus 16 } --1.3.6.1.4.1.3052.10.1.7.16 wmsGPRSStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem (E)GPRS status" ::= { wirelessModemStatus 17 } --1.3.6.1.4.1.3052.10.1.7.17 wmsBand OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem band" ::= { wirelessModemStatus 18 } --1.3.6.1.4.1.3052.10.1.7.18 wmsChannel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem channel" ::= { wirelessModemStatus 19 } --1.3.6.1.4.1.3052.10.1.7.19 wmsCountryCode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem country code" ::= { wirelessModemStatus 20 } --1.3.6.1.4.1.3052.10.1.7.20 wmsNetCode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem network code" ::= { wirelessModemStatus 21 } --1.3.6.1.4.1.3052.10.1.7.21 wmsPLMNColor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem PLMN color" ::= { wirelessModemStatus 22 } --1.3.6.1.4.1.3052.10.1.7.22 wmsBScolor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem BS color" ::= { wirelessModemStatus 23 } --1.3.6.1.4.1.3052.10.1.7.23 wmsMpRACH OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem max power RACH" ::= { wirelessModemStatus 24 } --1.3.6.1.4.1.3052.10.1.7.24 wmsMinRxLevel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem minimum receive level" ::= { wirelessModemStatus 25 } --1.3.6.1.4.1.3052.10.1.7.25 wmsBaseCoeff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem base coefficient" ::= { wirelessModemStatus 26 } --1.3.6.1.4.1.3052.10.1.7.26 wmsSIMStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "WWireless modem SIM status" ::= { wirelessModemStatus 27 } --1.3.6.1.4.1.3052.10.1.7.27 wmsICCID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem SIM ICCID" ::= { wirelessModemStatus 28 } --1.3.6.1.4.1.3052.10.1.7.28 wmsModemType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Wireless modem type" ::= { wirelessModemStatus 29 } --1.3.6.1.4.1.3052.10.1.7.29 --*************************************************************************************** --AC Power Monitor Section 1.8 --*************************************************************************************** acpmStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "AC power monitor status table" ::= { acPowerMonitorStatus 1 } --1.3.6.1.4.1.3052.10.1.8.1 acpmStatusEntry OBJECT-TYPE SYNTAX ACPMStatus MAX-ACCESS not-accessible STATUS current DESCRIPTION "AC power monitor status table entry" INDEX { acpmsIndex } ::= { acpmStatusTable 1 } --1.3.6.1.4.1.3052.10.1.8.1.1 acpmsIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for AC power monitors" ::= { acpmStatusEntry 1 } --1.3.6.1.4.1.3052.10.1.8.1.1.1 acpmsName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Name for the AC power monitor device." ::= { acpmStatusEntry 2 } --1.3.6.1.4.1.3052.10.1.8.1.1.2 acpmsAvgVoltageValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1). This could be either the average of the phase voltages, or the sum of the phase voltages, depending on device configuration." ::= { acpmStatusEntry 3 } --1.3.6.1.4.1.3052.10.1.8.1.1.3 acpmsAvgVoltageMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum average voltage value since last reset, in volts." ::= { acpmStatusEntry 4 } --1.3.6.1.4.1.3052.10.1.8.1.1.4 acpmsAvgVoltageMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum average voltage value since last reset, in volts." ::= { acpmStatusEntry 5 } --1.3.6.1.4.1.3052.10.1.8.1.1.5 acpmsAvgVoltageAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average average voltage value since last reset, in volts. This is the unit's average of its measurements of the average voltage reported by the AC power monitor device." ::= { acpmStatusEntry 6 } --1.3.6.1.4.1.3052.10.1.8.1.1.6 acpmsAvgVoltageInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Event state of this AC power monitor voltage (Low, Normal, High, etc.)." ::= { acpmStatusEntry 7 } --1.3.6.1.4.1.3052.10.1.8.1.1.7 acpmsVoltagePhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1)." ::= { acpmStatusEntry 8 } --1.3.6.1.4.1.3052.10.1.8.1.1.8 acpmsVoltagePhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1)." ::= { acpmStatusEntry 9 } --1.3.6.1.4.1.3052.10.1.8.1.1.9 acpmsVoltagePhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1)." ::= { acpmStatusEntry 10 } --1.3.6.1.4.1.3052.10.1.8.1.1.10 acpmsVoltageL1L2Value OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Line 1 to Line 2 voltage" ::= { acpmStatusEntry 11 } --1.3.6.1.4.1.3052.10.1.8.1.1.11 acpmsVoltageL2L3Value OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Line 2 to Line 3 voltage" ::= { acpmStatusEntry 12 } --1.3.6.1.4.1.3052.10.1.8.1.1.12 acpmsVoltageL3L1Value OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Line 3 to Line 1 voltage" ::= { acpmStatusEntry 13 } --1.3.6.1.4.1.3052.10.1.8.1.1.13 acpmsAvgCurrentValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average current, in amps. This is calculated using the formula (register * CT ratio * 0.001). This could be either the average of the phase currents, or the sum of the phase currents, depending on device configuration." ::= { acpmStatusEntry 14 } --1.3.6.1.4.1.3052.10.1.8.1.1.14 acpmsAvgCurrentMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum average current value since last reset, in amps." ::= { acpmStatusEntry 15 } --1.3.6.1.4.1.3052.10.1.8.1.1.15 acpmsAvgCurrentMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum average current value since last reset, in amps." ::= { acpmStatusEntry 16 } --1.3.6.1.4.1.3052.10.1.8.1.1.16 acpmsAvgCurrentAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average average current value since last reset, in amps. This is the unit's average of its measurements of the average current reported by the AC power monitor device." ::= { acpmStatusEntry 17 } --1.3.6.1.4.1.3052.10.1.8.1.1.17 acpmsAvgCurrentInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Event state of this AC power monitor current (Low, Normal, High, etc.)." ::= { acpmStatusEntry 18 } --1.3.6.1.4.1.3052.10.1.8.1.1.18 acpmsCurrentPhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A current, in amps. This is calculated using the formula (register * CT ratio * 0.001)." ::= { acpmStatusEntry 19 } --1.3.6.1.4.1.3052.10.1.8.1.1.19 acpmsCurrentPhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B current, in amps. This is calculated using the formula (register * CT ratio * 0.001)." ::= { acpmStatusEntry 20 } --1.3.6.1.4.1.3052.10.1.8.1.1.20 acpmsCurrentPhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C current, in amps. This is calculated using the formula (register * CT ratio * 0.001)." ::= { acpmStatusEntry 21 } --1.3.6.1.4.1.3052.10.1.8.1.1.21 acpmsAvgFreqValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Frequency, in hertz. On the YD2010, this is calculated using the formula (register * 0.00106813). On the WattsOn, this is calculated using the formula (register * 0.1)." ::= { acpmStatusEntry 22 } --1.3.6.1.4.1.3052.10.1.8.1.1.22 acpmsAvgFreqMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum frequency value since last reset, in hertz." ::= { acpmStatusEntry 23 } --1.3.6.1.4.1.3052.10.1.8.1.1.23 acpmsAvgFreqMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum frequency value since last reset, in hertz." ::= { acpmStatusEntry 24 } --1.3.6.1.4.1.3052.10.1.8.1.1.24 acpmsAvgFreqAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average frequency value since last reset, in hertz. This is the unit's average of its measurements of the average frequency reported by the AC power monitor device." ::= { acpmStatusEntry 25 } --1.3.6.1.4.1.3052.10.1.8.1.1.25 acpmsAvgFreqInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Event state of this AC power monitor frequency (Low, Normal, High, etc.)." ::= { acpmStatusEntry 26 } --1.3.6.1.4.1.3052.10.1.8.1.1.26 acpmsTRPValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn models, this is calculated using the formula (register * PT * CT)." ::= { acpmStatusEntry 27 } --1.3.6.1.4.1.3052.10.1.8.1.1.27 acpmsTRPMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum total real power value since last reset, in watts." ::= { acpmStatusEntry 28 } --1.3.6.1.4.1.3052.10.1.8.1.1.28 acpmsTRPMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum total real power value since last reset, in watts." ::= { acpmStatusEntry 29 } --1.3.6.1.4.1.3052.10.1.8.1.1.29 acpmsTRPAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Average total real power value since last reset, in watts. This is the unit's average of its measurements of the average total real power reported by the AC power monitor device." ::= { acpmStatusEntry 30 } --1.3.6.1.4.1.3052.10.1.8.1.1.30 acpmsTRPInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Event state of this AC power monitor total real power (Low, Normal, High, etc.)." ::= { acpmStatusEntry 31 } --1.3.6.1.4.1.3052.10.1.8.1.1.31 acpmsRPPhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT)." ::= { acpmStatusEntry 32 } --1.3.6.1.4.1.3052.10.1.8.1.1.32 acpmsRPPhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT)." ::= { acpmStatusEntry 33 } --1.3.6.1.4.1.3052.10.1.8.1.1.33 acpmsRPPhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT)." ::= { acpmStatusEntry 34 } --1.3.6.1.4.1.3052.10.1.8.1.1.34 acpmsCombined OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: name`deviceState`deviceStateColorCode`voltage`current`frequency`power~voltageEventState`voltageColorCode`currentEventState`currentColorCode`frequencyEventState`freuencyColorCode`powerEventState`powerColorCode" ::= { acpmStatusEntry 35 } --1.3.6.1.4.1.3052.10.1.8.1.1.35 acpmsTPFValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor." ::= { acpmStatusEntry 36 } --1.3.6.1.4.1.3052.10.1.8.1.1.36 acpmsTPFMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor minimum value since last reset." ::= { acpmStatusEntry 37 } --1.3.6.1.4.1.3052.10.1.8.1.1.37 acpmsTPFMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor maximum value since last reset." ::= { acpmStatusEntry 38 } --1.3.6.1.4.1.3052.10.1.8.1.1.38 acpmsTPFAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor average value since last reset." ::= { acpmStatusEntry 39 } --1.3.6.1.4.1.3052.10.1.8.1.1.39 acpmsTPFInEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor event state." ::= { acpmStatusEntry 40 } --1.3.6.1.4.1.3052.10.1.8.1.1.40 acpmsPFPhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A power factor." ::= { acpmStatusEntry 41 } --1.3.6.1.4.1.3052.10.1.8.1.1.41 acpmsPFPhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B power factor." ::= { acpmStatusEntry 42 } --1.3.6.1.4.1.3052.10.1.8.1.1.42 acpmsPFPhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C power factor." ::= { acpmStatusEntry 43 } --1.3.6.1.4.1.3052.10.1.8.1.1.43 acpmsTRcPValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total reactive power, in VAR." ::= { acpmStatusEntry 44 } --1.3.6.1.4.1.3052.10.1.8.1.1.44 acpmsTRcPMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total reactive power minimum value since last reset, in VAR." ::= { acpmStatusEntry 45 } --1.3.6.1.4.1.3052.10.1.8.1.1.45 acpmsTRcPMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total reactive power maximum value since last reset, in VAR." ::= { acpmStatusEntry 46 } --1.3.6.1.4.1.3052.10.1.8.1.1.46 acpmsTRcPAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total reactive power average value since last reset, in VAR." ::= { acpmStatusEntry 47 } --1.3.6.1.4.1.3052.10.1.8.1.1.47 acpmsRcPPhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A reactive power, in VAR." ::= { acpmStatusEntry 48 } --1.3.6.1.4.1.3052.10.1.8.1.1.48 acpmsRcPPhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B reactive power, in VAR." ::= { acpmStatusEntry 49 } --1.3.6.1.4.1.3052.10.1.8.1.1.49 acpmsRcPPhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C reactive power, in VAR." ::= { acpmStatusEntry 50 } --1.3.6.1.4.1.3052.10.1.8.1.1.50 acpmsTAPValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total apparent power, in VA." ::= { acpmStatusEntry 51 } --1.3.6.1.4.1.3052.10.1.8.1.1.51 acpmsTAPMinStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total apparent power minimum value since last reset, in VA." ::= { acpmStatusEntry 52 } --1.3.6.1.4.1.3052.10.1.8.1.1.52 acpmsTAPMaxStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total apparent power maximum value since last reset, in VA." ::= { acpmStatusEntry 53 } --1.3.6.1.4.1.3052.10.1.8.1.1.53 acpmsTAPAvgStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Total apparent power average value since last reset, in VA." ::= { acpmStatusEntry 54 } --1.3.6.1.4.1.3052.10.1.8.1.1.54 acpmsAPPhaseAValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase A apparent power, in VA." ::= { acpmStatusEntry 55 } --1.3.6.1.4.1.3052.10.1.8.1.1.55 acpmsAPPhaseBValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase B apparent power, in VA." ::= { acpmStatusEntry 56 } --1.3.6.1.4.1.3052.10.1.8.1.1.56 acpmsAPPhaseCValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Phase C apparent power, in VA." ::= { acpmStatusEntry 57 } --1.3.6.1.4.1.3052.10.1.8.1.1.57 acpmsTotalEnergyWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total energy, in Wh." ::= { acpmStatusEntry 58 } --1.3.6.1.4.1.3052.10.1.8.1.1.58 acpmsTotalEnergyVAR OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total reactive energy, in VAR." ::= { acpmStatusEntry 59 } --1.3.6.1.4.1.3052.10.1.8.1.1.59 acpmsTotalEnergyVA OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total apparent energy, in VA." ::= { acpmStatusEntry 60 } --1.3.6.1.4.1.3052.10.1.8.1.1.60 acmpsAvgVoltageAlarmDatetime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last Average Voltage alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string." ::= { acpmStatusEntry 61 } --1.3.6.1.4.1.3052.10.1.8.1.1.61 acmpsAvgCurrentAlarmDatetime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last Average Current alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string." ::= { acpmStatusEntry 62 } --1.3.6.1.4.1.3052.10.1.8.1.1.62 acmpsFreqAlarmDatetime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last Frequency alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string." ::= { acpmStatusEntry 63 } --1.3.6.1.4.1.3052.10.1.8.1.1.63 acmpsRealPowerAlarmDatetime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last Real Power alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string." ::= { acpmStatusEntry 64 } --1.3.6.1.4.1.3052.10.1.8.1.1.64 acmpsPowerFactorAlarmDatetime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The time of the last Power Factor alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are Low, and Very Low. For outputs, this object is a null string." ::= { acpmStatusEntry 65 } --1.3.6.1.4.1.3052.10.1.8.1.1.66 --*************************************************************************************** --HVAC Status Section 1.11 --*************************************************************************************** --*************************************************************************************** --Asentria HVAC Status Section 1.11.2 --*************************************************************************************** evHVACStatusBardSystem1Stage1Cooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 1 stage 1 cooling status." ::= { evHVACStatusBardSystem1Stage1 1 } --1.3.6.1.4.1.3052.10.1.11.2.1.1.1 evHVACStatusBardSystem1Stage2Cooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 1 stage 2 cooling status." ::= { evHVACStatusBardSystem1Stage2 1 } --1.3.6.1.4.1.3052.10.1.11.2.1.2.1 evHVACStatusBardSystem1Blower OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 1 blower status." ::= { evHVACStatusBardSystem1 3 } --1.3.6.1.4.1.3052.10.1.11.2.1.3 evHVACStatusBardSystem1Heating OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 1 heating status." ::= { evHVACStatusBardSystem1 4 } --1.3.6.1.4.1.3052.10.1.11.2.1.4 evHVACStatusBardSystem1Economizer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 1 heating status." ::= { evHVACStatusBardSystem1 5 } --1.3.6.1.4.1.3052.10.1.11.2.1.5 evHVACStatusBardSystem2Stage1Cooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 2 stage 1 cooling status." ::= { evHVACStatusBardSystem2Stage1 1 } --1.3.6.1.4.1.3052.10.1.11.2.2.1.1 evHVACStatusBardSystem2Stage2Cooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 2 stage 2 cooling status." ::= { evHVACStatusBardSystem2Stage2 1 } --1.3.6.1.4.1.3052.10.1.11.2.2.2.1 evHVACStatusBardSystem2Blower OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 2 blower status." ::= { evHVACStatusBardSystem2 3 } --1.3.6.1.4.1.3052.10.1.11.2.2.3 evHVACStatusBardSystem2Heating OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 2 heating status." ::= { evHVACStatusBardSystem2 4 } --1.3.6.1.4.1.3052.10.1.11.2.2.4 evHVACStatusBardSystem2Economizer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: System 2 heating status." ::= { evHVACStatusBardSystem2 5 } --1.3.6.1.4.1.3052.10.1.11.2.2.5 evHVACStatusBardTempAvg OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Average temperature." ::= { evHVACStatusBard 3 } --1.3.6.1.4.1.3052.10.1.11.2.3 evHVACStatusBardTempLocal OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Local temperature." ::= { evHVACStatusBard 4 } --1.3.6.1.4.1.3052.10.1.11.2.4 evHVACStatusBardTempRemote1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Remote 1 temperature." ::= { evHVACStatusBardTempRemote 1 } --1.3.6.1.4.1.3052.10.1.11.2.5.1 evHVACStatusBardTempRemote2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Remote 2 temperature." ::= { evHVACStatusBardTempRemote 2 } --1.3.6.1.4.1.3052.10.1.11.2.5.2 evHVACStatusBardDehumidification OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Dehumidification status." ::= { evHVACStatusBard 6 } --1.3.6.1.4.1.3052.10.1.11.2.6 evHVACStatusBardLEDsCooling1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Cooling LED 1." ::= { evHVACStatusBardLEDsCooling 1 } --1.3.6.1.4.1.3052.10.1.11.2.7.1.1 evHVACStatusBardLEDsCooling2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Cooling LED 2." ::= { evHVACStatusBardLEDsCooling 2 } --1.3.6.1.4.1.3052.10.1.11.2.7.1.2 evHVACStatusBardLEDsCooling3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Cooling LED 3." ::= { evHVACStatusBardLEDsCooling 3 } --1.3.6.1.4.1.3052.10.1.11.2.7.1.3 evHVACStatusBardLEDsCooling4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Cooling LED 4." ::= { evHVACStatusBardLEDsCooling 4 } --1.3.6.1.4.1.3052.10.1.11.2.7.1.4 evHVACStatusBardLEDsHeating1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Heating LED 1." ::= { evHVACStatusBardLEDsHeating 1 } --1.3.6.1.4.1.3052.10.1.11.2.7.2.1 evHVACStatusBardLEDsHeating2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Heating LED 2." ::= { evHVACStatusBardLEDsHeating 2 } --1.3.6.1.4.1.3052.10.1.11.2.7.2.2 evHVACStatusBardLEDsHeating3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Heating LED 3." ::= { evHVACStatusBardLEDsHeating 3 } --1.3.6.1.4.1.3052.10.1.11.2.7.2.3 evHVACStatusBardLEDsHeating4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Heating LED 4." ::= { evHVACStatusBardLEDsHeating 4 } --1.3.6.1.4.1.3052.10.1.11.2.7.2.4 evHVACStatusBardLEDsDeHumid1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Dehumidification LED 1." ::= { evHVACStatusBardLEDsDeHumid 1 } --1.3.6.1.4.1.3052.10.1.11.2.7.3.1 evHVACStatusBardGenerator OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Backup generator status." ::= { evHVACStatusBard 7 } --1.3.6.1.4.1.3052.10.1.11.2.8 evHVACStatusBardAlarmBoardState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC: Alarm board state." ::= { evHVACStatusBard 8 } --1.3.6.1.4.1.3052.10.1.11.2.9 evHVACStatusBardASSystem1PowerLoss OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: System 1 power loss." ::= { evHVACStatusBardASSystem1 1 } --1.3.6.1.4.1.3052.10.1.11.2.10.1.1 evHVACStatusBardASSystem1Lockout OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: System 1 ref. lockout." ::= { evHVACStatusBardASSystem1 2 } --1.3.6.1.4.1.3052.10.1.11.2.10.1.2 evHVACStatusBardASSystem2PowerLoss OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: System 2 power loss." ::= { evHVACStatusBardASSystem2 1 } --1.3.6.1.4.1.3052.10.1.11.2.10.2.1 evHVACStatusBardASSystem2Lockout OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: System 2 ref. lockout." ::= { evHVACStatusBardASSystem2 2 } --1.3.6.1.4.1.3052.10.1.11.2.10.2.2 evHVACStatusBardASFire OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: Fire / smoke." ::= { evHVACStatusBardAlarmStatus 3 } --1.3.6.1.4.1.3052.10.1.11.2.10.3 evHVACStatusBardASTempLowAlarm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: Low temperature." ::= { evHVACStatusBardASTemp 1 } --1.3.6.1.4.1.3052.10.1.11.2.10.4.1 evHVACStatusBardASTempHighAlarm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: High temperature." ::= { evHVACStatusBardASTemp 2 } --1.3.6.1.4.1.3052.10.1.11.2.10.4.2 evHVACStatusBardASTempVHighAlarm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: Very high temperature." ::= { evHVACStatusBardASTemp 3 } --1.3.6.1.4.1.3052.10.1.11.2.10.4.3 evHVACStatusBardASFailure OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bard HVAC Alarm Status: Controller failure." ::= { evHVACStatusBardAlarmStatus 5 } --1.3.6.1.4.1.3052.10.1.11.2.10.5 evHVACStatusBardConnState OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Connectivity state: 1 means unit has good connectivity to the Bard HVAC controller, 0 otherwise." ::= { evHVACStatusBard 11 } --1.3.6.1.4.1.3052.10.1.11.2.11 --*************************************************************************************** --Asentria HVAC Status Section 1.11.3 --*************************************************************************************** evHVACStatusAsentriaSequenceTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACStatusAsentriaSequence MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC sequence status table" ::= { evHVACStatusAsentria 1 } --1.3.6.1.4.1.3052.10.1.11.3.1 evHVACStatusAsentriaSequenceEntry OBJECT-TYPE SYNTAX HVACStatusAsentriaSequence MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC sequence status table entry" INDEX { evHVACStatusAsentriaSequenceIndex } ::= { evHVACStatusAsentriaSequenceTable 1 } --1.3.6.1.4.1.3052.10.1.11.3.1.1 evHVACStatusAsentriaSequenceIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Asentria HVAC sequence" ::= { evHVACStatusAsentriaSequenceEntry 1 } --1.3.6.1.4.1.3052.10.1.11.3.1.1.1 evHVACStatusAsentriaSeqVentTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC sequence time spent venting" ::= { evHVACStatusAsentriaSequenceEntry 2 } --1.3.6.1.4.1.3052.10.1.11.3.1.1.2 evHVACStatusAsentriaSeqCoolTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC sequence time spent cooling" ::= { evHVACStatusAsentriaSequenceEntry 3 } --1.3.6.1.4.1.3052.10.1.11.3.1.1.3 evHVACStatusAsentriaSeqHeatTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC sequence time spent heating" ::= { evHVACStatusAsentriaSequenceEntry 4 } --1.3.6.1.4.1.3052.10.1.11.3.1.1.4 evHVACStatusAsentriaSeqIdleTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC sequence time spent idling" ::= { evHVACStatusAsentriaSequenceEntry 5 } --1.3.6.1.4.1.3052.10.1.11.3.1.1.5 evHVACStatusAsentriaUnitTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACStatusAsentriaUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC unit status table" ::= { evHVACStatusAsentria 2 } --1.3.6.1.4.1.3052.10.1.11.3.2 evHVACStatusAsentriaUnitEntry OBJECT-TYPE SYNTAX HVACStatusAsentriaUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC unit status table entry" INDEX { evHVACStatusAsentriaUnitIndex } ::= { evHVACStatusAsentriaUnitTable 1 } --1.3.6.1.4.1.3052.10.1.11.3.2.1 evHVACStatusAsentriaUnitIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Asentria HVAC unit" ::= { evHVACStatusAsentriaUnitEntry 1 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.1 evHVACStatusAsentriaUnitState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC unit status" ::= { evHVACStatusAsentriaUnitEntry 2 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.2 evHVACStatusAsentriaUnitVentTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC unit time spent venting" ::= { evHVACStatusAsentriaUnitEntry 3 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.3 evHVACStatusAsentriaUnitCoolTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC unit time spent cooling" ::= { evHVACStatusAsentriaUnitEntry 4 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.4 evHVACStatusAsentriaUnitHeatTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC unit time spent heating" ::= { evHVACStatusAsentriaUnitEntry 5 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.5 evHVACStatusAsentriaUnitIdleTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC unit time spent idling" ::= { evHVACStatusAsentriaUnitEntry 6 } --1.3.6.1.4.1.3052.10.1.11.3.2.1.6 evHVACStatusAsentriaBackupEvent OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC backup event" ::= { evHVACStatusAsentria 3 } --1.3.6.1.4.1.3052.10.1.11.3.3 evHVACStatusAsentriaFireEvent OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC smoke/fire event" ::= { evHVACStatusAsentria 4 } --1.3.6.1.4.1.3052.10.1.11.3.4 evHVACStatusAsentriaTempOut OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC temperature outside" ::= { evHVACStatusAsentriaTemp 1 } --1.3.6.1.4.1.3052.10.1.11.3.5.1 evHVACStatusAsentriaTempIn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC temperature inside" ::= { evHVACStatusAsentriaTemp 2 } --1.3.6.1.4.1.3052.10.1.11.3.5.2 evHVACStatusAsentriaHumidOut OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC humidity outside" ::= { evHVACStatusAsentriaHumid 1 } --1.3.6.1.4.1.3052.10.1.11.3.6.1 evHVACStatusAsentriaHumidIn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Asentria HVAC humidity inside" ::= { evHVACStatusAsentriaHumid 2 } --1.3.6.1.4.1.3052.10.1.11.3.6.2 --*************************************************************************************** --Airsys HVAC Status Section 1.11.4 --*************************************************************************************** evHVACStatusAirsysAlarmUnitTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACStatusAirsysAlarmUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit alarm status table" ::= { evHVACStatusAirsysAlarm 1 } --1.3.6.1.4.1.3052.10.1.11.4.1.1 evHVACStatusAirsysAlarmUnitEntry OBJECT-TYPE SYNTAX HVACStatusAirsysAlarmUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit alarm status table entry" INDEX { evHVACStatusAirsysAlarmUnitIndex } ::= { evHVACStatusAirsysAlarmUnitTable 1 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1 evHVACStatusAirsysAlarmUnitIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Airsys HVAC unit alarms" ::= { evHVACStatusAirsysAlarmUnitEntry 1 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.1 evHVACStatusAirsysAlarmUnitLowPress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit low pressure event" ::= { evHVACStatusAirsysAlarmUnitEntry 2 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.2 evHVACStatusAirsysAlarmUnitHighPress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit high pressure event" ::= { evHVACStatusAirsysAlarmUnitEntry 3 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.3 evHVACStatusAirsysAlarmUnitEvapFan OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit AC power/evaporator fan overload event" ::= { evHVACStatusAirsysAlarmUnitEntry 4 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.4 evHVACStatusAirsysAlarmUnitDirty OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit dirty filter event" ::= { evHVACStatusAirsysAlarmUnitEntry 5 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.5 evHVACStatusAirsysAlarmUnitDamper OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit damper event" ::= { evHVACStatusAirsysAlarmUnitEntry 6 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.6 evHVACStatusAirsysAlarmUnitSupProbe OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit supply probe broken event" ::= { evHVACStatusAirsysAlarmUnitEntry 7 } --1.3.6.1.4.1.3052.10.1.11.4.1.1.1.7 evHVACStatusAirsysAlarmSmokeFire OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC smoke/fire event" ::= { evHVACStatusAirsysAlarm 2 } --1.3.6.1.4.1.3052.10.1.11.4.1.2 evHVACStatusAirsysAlarmLowRoomTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC low temperature event" ::= { evHVACStatusAirsysAlarm 3 } --1.3.6.1.4.1.3052.10.1.11.4.1.3 evHVACStatusAirsysAlarmHighRoomTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC high temperature event" ::= { evHVACStatusAirsysAlarm 4 } --1.3.6.1.4.1.3052.10.1.11.4.1.4 evHVACStatusAirsysAlarmPower OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC power failure event" ::= { evHVACStatusAirsysAlarm 5 } --1.3.6.1.4.1.3052.10.1.11.4.1.5 evHVACStatusAirsysAlarmpLAN OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC pLAN event" ::= { evHVACStatusAirsysAlarm 6 } --1.3.6.1.4.1.3052.10.1.11.4.1.6 evHVACStatusAirsysAlarmClock OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC clock card event" ::= { evHVACStatusAirsysAlarm 7 } --1.3.6.1.4.1.3052.10.1.11.4.1.7 evHVACStatusAirsysAlarmHumidProbe OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC humidity probe broken event" ::= { evHVACStatusAirsysAlarm 8 } --1.3.6.1.4.1.3052.10.1.11.4.1.8 evHVACStatusAirsysAlarmOutProbe OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC outdoor probe broken event" ::= { evHVACStatusAirsysAlarm 9 } --1.3.6.1.4.1.3052.10.1.11.4.1.9 evHVACStatusAirsysAlarmBothCompress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC both compressors running event" ::= { evHVACStatusAirsysAlarm 10 } --1.3.6.1.4.1.3052.10.1.11.4.1.10 evHVACStatusAirsysAlarmGenerator OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC generator running event" ::= { evHVACStatusAirsysAlarm 11 } --1.3.6.1.4.1.3052.10.1.11.4.1.11 evHVACStatusAirsysAlarmConnection OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC controller connection event" ::= { evHVACStatusAirsysAlarm 12 } --1.3.6.1.4.1.3052.10.1.11.4.1.12 evHVACStatusAirsysAlarmInProbe1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC indoor probe broken event" ::= { evHVACStatusAirsysAlarm 13 } --1.3.6.1.4.1.3052.10.1.11.4.1.13 evHVACStatusAirsysAlarmInProbe2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC backup indoor probe broken event" ::= { evHVACStatusAirsysAlarm 14 } --1.3.6.1.4.1.3052.10.1.11.4.1.14 evHVACStatusAirsysTempOut OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC outdoor temperature" ::= { evHVACStatusAirsys 2 } --1.3.6.1.4.1.3052.10.1.11.4.2 evHVACStatusAirsysTempIn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC indoor temperature" ::= { evHVACStatusAirsys 3 } --1.3.6.1.4.1.3052.10.1.11.4.3 evHVACStatusAirsysTempInBackup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC backup indoor temperature" ::= { evHVACStatusAirsys 4 } --1.3.6.1.4.1.3052.10.1.11.4.4 evHVACStatusAirsysHumidIn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC indoor humidity" ::= { evHVACStatusAirsys 5 } --1.3.6.1.4.1.3052.10.1.11.4.5 evHVACStatusAirsysUnitTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACStatusAirsysUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit alarm status table" ::= { evHVACStatusAirsys 6 } --1.3.6.1.4.1.3052.10.1.11.4.6 evHVACStatusAirsysUnitEntry OBJECT-TYPE SYNTAX HVACStatusAirsysUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit alarm status table entry" INDEX { evHVACStatusAirsysUnitIndex } ::= { evHVACStatusAirsysUnitTable 1 } --1.3.6.1.4.1.3052.10.1.11.4.6.1 evHVACStatusAirsysUnitIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Airsys HVAC unit" ::= { evHVACStatusAirsysUnitEntry 1 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.1 evHVACStatusAirsysUnitTempSupply OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit supply temperature" ::= { evHVACStatusAirsysUnitEntry 2 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.2 evHVACStatusAirsysUnitFanspeed OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit fan speed" ::= { evHVACStatusAirsysUnitEntry 3 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.3 evHVACStatusAirsysUnitFreeOpening OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit free cooling vent opening percentage" ::= { evHVACStatusAirsysUnitEntry 4 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.4 evHVACStatusAirsysUnitStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit running status" ::= { evHVACStatusAirsysUnitEntry 5 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.5 evHVACStatusAirsysUnitLocked OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit locked status" ::= { evHVACStatusAirsysUnitEntry 6 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.6 evHVACStatusAirsysUnitCompressor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit state of compressor" ::= { evHVACStatusAirsysUnitEntry 7 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.7 evHVACStatusAirsysUnitHeater OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit state of heater" ::= { evHVACStatusAirsysUnitEntry 8 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.8 evHVACStatusAirsysURuntimeSupplyFan OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit run time of supply fan in hours" ::= { evHVACStatusAirsysUnitEntry 9 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.9 evHVACStatusAirsysURuntimeCompressor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit run time of compressor in hours" ::= { evHVACStatusAirsysUnitEntry 10 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.10 evHVACStatusAirsysURuntimeHeat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit run time of heating in hours" ::= { evHVACStatusAirsysUnitEntry 11 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.11 evHVACStatusAirsysURuntimeFreeCooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit run time of free cooling in hours" ::= { evHVACStatusAirsysUnitEntry 12 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.12 evHVACStatusAirsysUCountSupplyFan OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit number of times supply fan has started" ::= { evHVACStatusAirsysUnitEntry 13 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.13 evHVACStatusAirsysUCountCompressor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit number of times compressor has started" ::= { evHVACStatusAirsysUnitEntry 14 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.14 evHVACStatusAirsysUCountHeat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit number of times heating has started" ::= { evHVACStatusAirsysUnitEntry 15 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.15 evHVACStatusAirsysUCountFreeCooling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC unit number of times free cooling has started" ::= { evHVACStatusAirsysUnitEntry 16 } --1.3.6.1.4.1.3052.10.1.11.4.6.1.16 evHVACStatusAirsysDay OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC controller day" ::= { evHVACStatusAirsys 7 } --1.3.6.1.4.1.3052.10.1.11.4.7 evHVACStatusAirsysDate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC controller date" ::= { evHVACStatusAirsys 8 } --1.3.6.1.4.1.3052.10.1.11.4.8 evHVACStatusAirsysTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC controller time" ::= { evHVACStatusAirsys 9 } --1.3.6.1.4.1.3052.10.1.11.4.9 evHVACStatusAirsysVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Airsys HVAC controller software version" ::= { evHVACStatusAirsys 10 } --1.3.6.1.4.1.3052.10.1.11.4.10 --*************************************************************************************** --Battery Backup Status Section 1.12 --*************************************************************************************** liBattPercentCharge OBJECT-TYPE SYNTAX Integer32 (1..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Lithium Battery State Charge in Percent (0% to 100%)" ::= { liBattStatus 1 } --1.3.6.1.4.1.3052.10.1.12.1.1 liBattRunning OBJECT-TYPE SYNTAX Integer32 (0..1) MAX-ACCESS read-only STATUS current DESCRIPTION "Is the unit running on battery backup: (TRUE/FALSE) or (1/0)" ::= { liBattStatus 2 } --1.3.6.1.4.1.3052.10.1.12.1.2 --*************************************************************************************** --EventSensor Basics Section 2.1 --*************************************************************************************** esNumberEventSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of EventSensors recognized by the unit, including the internal EventSensor. Range: 1-17" ::= { eventSensorBasics 1 } --1.3.6.1.4.1.3052.10.2.1.1 esTable OBJECT-TYPE SYNTAX SEQUENCE OF ESExist MAX-ACCESS not-accessible STATUS current DESCRIPTION "The table of what EventSensors are attached to the unit, including the internal EventSensor" ::= { eventSensorBasics 2 } --1.3.6.1.4.1.3052.10.2.1.2 esEntry OBJECT-TYPE SYNTAX ESExist MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry for EventSensor table" INDEX { esIndex } ::= { esTable 1 } --1.3.6.1.4.1.3052.10.2.1.2.1 esIndex OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "This number refers to an EventSensor; it has the same meaning as the esIndexES object (see above), except that this object is used only within the esTable branch. This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndex=2 will now refer to that particular EventSensor. " ::= { esEntry 1 } --1.3.6.1.4.1.3052.10.2.1.2.1.1 esName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The name of the EventSensor" ::= { esEntry 2 } --1.3.6.1.4.1.3052.10.2.1.2.1.2 esID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The factory-assigned ID of the EventSensor" ::= { esEntry 3 } --1.3.6.1.4.1.3052.10.2.1.2.1.3 esNumberTempSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of temperature sensors on the EventSensor" ::= { esEntry 4 } --1.3.6.1.4.1.3052.10.2.1.2.1.4 esTempReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how temperature values should be interpreted." ::= { esEntry 5 } --1.3.6.1.4.1.3052.10.2.1.2.1.5 esNumberCCs OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of contact closures on the EventSensor." ::= { esEntry 6 } --1.3.6.1.4.1.3052.10.2.1.2.1.6 esCCReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how CC values should be interpreted." ::= { esEntry 7 } --1.3.6.1.4.1.3052.10.2.1.2.1.7 esNumberHumidSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of humidity sensors on the EventSensor." ::= { esEntry 8 } --1.3.6.1.4.1.3052.10.2.1.2.1.8 esHumidReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how humidity sensor values should be interpreted." ::= { esEntry 9 } --1.3.6.1.4.1.3052.10.2.1.2.1.9 esNumberNoiseSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of noise sensors on the EventSensor." ::= { esEntry 10 } --1.3.6.1.4.1.3052.10.2.1.2.1.10 esNoiseReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how noise sensor values should be interpreted." ::= { esEntry 11 } --1.3.6.1.4.1.3052.10.2.1.2.1.11 esNumberAirflowSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of airflow sensors on the EventSensor." ::= { esEntry 12 } --1.3.6.1.4.1.3052.10.2.1.2.1.12 esAirflowReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how airflow sensor values should be interpreted." ::= { esEntry 13 } --1.3.6.1.4.1.3052.10.2.1.2.1.13 esNumberAnalog OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of analog inputs on the EventSensor." ::= { esEntry 14 } --1.3.6.1.4.1.3052.10.2.1.2.1.14 esAnalogReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how analog input values should be interpreted." ::= { esEntry 15 } --1.3.6.1.4.1.3052.10.2.1.2.1.15 esNumberOutputs OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of outputs (relay or power) on the EventSensor" ::= { esEntry 16 } --1.3.6.1.4.1.3052.10.2.1.2.1.16 esOutputReportingMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of how output values should be interpreted." ::= { esEntry 17 } --1.3.6.1.4.1.3052.10.2.1.2.1.17 esTempCombinedStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: name`value`scale`eventState`eventColorCode" ::= { esEntry 18 } --1.3.6.1.4.1.3052.10.2.1.2.1.18 esCCCombinedStatusBlock1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name1`value1`eventColorCode1`alias1~name2`value2`eventColorCode2`alias2~...name8`value8`eventColorCode8`alias8" ::= { esEntry 19 } --1.3.6.1.4.1.3052.10.2.1.2.1.19 esCCCombinedStatusBlock2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name9`value9`eventColorCode9`alias9~name10`value10`eventColorCode10`alias10~...name16`value16`eventColorCode16`alias16" ::= { esEntry 20 } --1.3.6.1.4.1.3052.10.2.1.2.1.20 esCCCombinedStatusBlock3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name17`value17`eventColorCode17`alias17~name18`value18`eventColorCode18`alias18~...name24`value24`eventColorCode24`alias24" ::= { esEntry 21 } --1.3.6.1.4.1.3052.10.2.1.2.1.21 esCCCombinedStatusBlock4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name25`value25`eventColorCode25`alias25~name26`value26`eventColorCode26`alias26~...name32`value32`eventColorCode32`alias32" ::= { esEntry 22 } --1.3.6.1.4.1.3052.10.2.1.2.1.22 esCCCombinedStatusBlock5 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name33`value33`eventColorCode33`alias33~name34`value34`eventColorCode34`alias35~...name40`value40`eventColorCode40`alias40" ::= { esEntry 23 } --1.3.6.1.4.1.3052.10.2.1.2.1.23 esCCCombinedStatusBlock6 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name41`value41`eventColorCode41`alias41~name42`value42`eventColorCode42`alias43~...name48`value48`eventColorCode48`alias48" ::= { esEntry 24 } --1.3.6.1.4.1.3052.10.2.1.2.1.24 esCCCombinedStatusBlock7 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name49`value49`eventColorCode49`alias49~name50`value50`eventColorCode50`alias50~...name56`value56`eventColorCode56`alias56" ::= { esEntry 25 } --1.3.6.1.4.1.3052.10.2.1.2.1.25 esCCCombinedStatusBlock8 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name57`value57`eventColorCode57`alias57~name57`value57`eventColorCode564`alias57~...name64`value64`eventColorCode64`alias64" ::= { esEntry 26 } --1.3.6.1.4.1.3052.10.2.1.2.1.26 esHumidCombinedStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: name`value`eventState`eventColorCode" ::= { esEntry 27 } --1.3.6.1.4.1.3052.10.2.1.2.1.27 esAnalogCombinedStatusBlock1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name1`value1`units1`eventState`eventColorCode1~name2`value2`units2`eventState`eventColorCode2~..." ::= { esEntry 28 } --1.3.6.1.4.1.3052.10.2.1.2.1.28 esAnalogCombinedStatusBlock2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~name9`value9`units9`eventState9`eventColorCode9~..." ::= { esEntry 29 } --1.3.6.1.4.1.3052.10.2.1.2.1.29 esAnalogCombinedStatusBlock3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~..." ::= { esEntry 30 } --1.3.6.1.4.1.3052.10.2.1.2.1.31 esAnalogCombinedStatusBlock4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~..." ::= { esEntry 31 } --1.3.6.1.4.1.3052.10.2.1.2.1.31 esAnalogCombinedStatusBlock5 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~..." ::= { esEntry 32 } --1.3.6.1.4.1.3052.10.2.1.2.1.32 esAnalogCombinedStatusBlock6 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~..." ::= { esEntry 33 } --1.3.6.1.4.1.3052.10.2.1.2.1.33 esOutputCombinedStatusBlock1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~..." ::= { esEntry 34 } --1.3.6.1.4.1.3052.10.2.1.2.1.34 esOutputCombinedStatusBlock2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Combined status string intended to be parsed by NMS: numInBlock`namex`valuex`aliasx~namey`valuey`aliasy~...namez`valuez`aliasz" ::= { esEntry 35 } --1.3.6.1.4.1.3052.10.2.1.2.1.35 esNewSensors OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "String representing the number of new (attached but unconfigured) EventSensors" ::= { eventSensorBasics 3 } --1.3.6.1.4.1.3052.10.2.1.3 --*************************************************************************************** --EventSensor Point Config Section 2.2 --*************************************************************************************** esPointConfigTempTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigTemp MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of temperature sensor points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for temp sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor within the context of this emperature point config table ; namely, which EventSensor, and which sensor (a.k.a. point) (always 1 for temperature sensors). " ::= { eventSensorPointConfig 1 } --1.3.6.1.4.1.3052.10.2.2.1 esPointConfigTempEntry OBJECT-TYPE SYNTAX ESPointConfigTemp MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config temperature table" INDEX { espcTempIndexES, espcTempIndexPoint } ::= { esPointConfigTempTable 1 } --1.3.6.1.4.1.3052.10.2.2.1.1 espcTempIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config temperature table; namely, which EventSensor, and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. " ::= { esPointConfigTempEntry 1 } --1.3.6.1.4.1.3052.10.2.2.1.1.1 espcTempIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcTempIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of temperature point configuration." ::= { esPointConfigTempEntry 2 } --1.3.6.1.4.1.3052.10.2.2.1.1.2 espcTempEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this temperature sensor" ::= { esPointConfigTempEntry 3 } --1.3.6.1.4.1.3052.10.2.2.1.1.3 espcTempScale OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Scale (C/F) for this temperature sensor" ::= { esPointConfigTempEntry 4 } --1.3.6.1.4.1.3052.10.2.2.1.1.4 espcTempDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this temperature sensor (in floating-point format)" ::= { esPointConfigTempEntry 5 } --1.3.6.1.4.1.3052.10.2.2.1.1.5 espcTempVHighTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event threshold for this temperature sensor (in floating-point format)" ::= { esPointConfigTempEntry 6 } --1.3.6.1.4.1.3052.10.2.2.1.1.6 espcTempVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event actions for this temperature sensor" ::= { esPointConfigTempEntry 7 } --1.3.6.1.4.1.3052.10.2.2.1.1.7 espcTempVHighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event trap number for this temperature sensor" ::= { esPointConfigTempEntry 8 } --1.3.6.1.4.1.3052.10.2.2.1.1.8 espcTempVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 9 } --1.3.6.1.4.1.3052.10.2.2.1.1.9 espcTempHighTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event threshold for this temperature sensor (in floating-point format)" ::= { esPointConfigTempEntry 10 } --1.3.6.1.4.1.3052.10.2.2.1.1.10 espcTempHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event actions for this temperature sensor" ::= { esPointConfigTempEntry 11 } --1.3.6.1.4.1.3052.10.2.2.1.1.11 espcTempHighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event trap number for this temperature sensor" ::= { esPointConfigTempEntry 12 } --1.3.6.1.4.1.3052.10.2.2.1.1.12 espcTempHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 13 } --1.3.6.1.4.1.3052.10.2.2.1.1.13 espcTempNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal event actions for this temperature sensor" ::= { esPointConfigTempEntry 14 } --1.3.6.1.4.1.3052.10.2.2.1.1.14 espcTempNormalTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal event trap number for this temperature sensor" ::= { esPointConfigTempEntry 15 } --1.3.6.1.4.1.3052.10.2.2.1.1.15 espcTempNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal event class for this temperature sensor" ::= { esPointConfigTempEntry 16 } --1.3.6.1.4.1.3052.10.2.2.1.1.16 espcTempLowTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event threshold for this temperature sensor (in floating-point format)" ::= { esPointConfigTempEntry 17 } --1.3.6.1.4.1.3052.10.2.2.1.1.17 espcTempLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event actions for this temperature sensor" ::= { esPointConfigTempEntry 18 } --1.3.6.1.4.1.3052.10.2.2.1.1.18 espcTempLowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event trap number for this temperature sensor" ::= { esPointConfigTempEntry 19 } --1.3.6.1.4.1.3052.10.2.2.1.1.19 espcTempLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 20 } --1.3.6.1.4.1.3052.10.2.2.1.1.20 espcTempVLowTemp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event threshold for this temperature sensor (in floating-point format)" ::= { esPointConfigTempEntry 21 } --1.3.6.1.4.1.3052.10.2.2.1.1.21 espcTempVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event actions for this temperature sensor" ::= { esPointConfigTempEntry 22 } --1.3.6.1.4.1.3052.10.2.2.1.1.22 espcTempVLowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event trap number for this temperature sensor" ::= { esPointConfigTempEntry 23 } --1.3.6.1.4.1.3052.10.2.2.1.1.23 espcTempVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 24 } --1.3.6.1.4.1.3052.10.2.2.1.1.24 espcTempGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this temperature sensor group" ::= { esPointConfigTempEntry 25 } --1.3.6.1.4.1.3052.10.2.2.1.1.25 esPointConfigCCTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigCC MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of contact closure points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this contact closure point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 2 } --1.3.6.1.4.1.3052.10.2.2.2 esPointConfigCCEntry OBJECT-TYPE SYNTAX ESPointConfigCC MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config contact closure table" INDEX { espcCCIndexES, espcCCIndexPoint } ::= { esPointConfigCCTable 1 } --1.3.6.1.4.1.3052.10.2.2.2.1 espcCCIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigCCEntry 1 } --1.3.6.1.4.1.3052.10.2.2.2.1.1 espcCCIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcCCIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigCCEntry 2 } --1.3.6.1.4.1.3052.10.2.2.2.1.2 espcCCEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable for this contact closure" ::= { esPointConfigCCEntry 3 } --1.3.6.1.4.1.3052.10.2.2.2.1.3 espcCCName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this contact closure" ::= { esPointConfigCCEntry 4 } --1.3.6.1.4.1.3052.10.2.2.2.1.4 espcCCEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event state for this contact closure" ::= { esPointConfigCCEntry 5 } --1.3.6.1.4.1.3052.10.2.2.2.1.5 espcCCThreshold OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Event threshold (seconds) for this contact closure" ::= { esPointConfigCCEntry 6 } --1.3.6.1.4.1.3052.10.2.2.2.1.6 espcCCEventActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event actions for this contact closure" ::= { esPointConfigCCEntry 7 } --1.3.6.1.4.1.3052.10.2.2.2.1.7 espcCCEventTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Event trap number for this contact closure" ::= { esPointConfigCCEntry 8 } --1.3.6.1.4.1.3052.10.2.2.2.1.8 espcCCEventClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event class for this contact closure" ::= { esPointConfigCCEntry 9 } --1.3.6.1.4.1.3052.10.2.2.2.1.9 espcCCNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal actions for this contact closure" ::= { esPointConfigCCEntry 10 } --1.3.6.1.4.1.3052.10.2.2.2.1.10 espcCCNormalTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal trap number for this contact closure" ::= { esPointConfigCCEntry 11 } --1.3.6.1.4.1.3052.10.2.2.2.1.11 espcCCNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal class for this contact closure" ::= { esPointConfigCCEntry 12 } --1.3.6.1.4.1.3052.10.2.2.2.1.12 espcCCAlarmAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event alias for this contact closure" ::= { esPointConfigCCEntry 13 } --1.3.6.1.4.1.3052.10.2.2.2.1.13 espcCCNormalAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal alias for this contact closure" ::= { esPointConfigCCEntry 14 } --1.3.6.1.4.1.3052.10.2.2.2.1.14 espcCCNormalThreshold OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Event threshold (seconds) for this contact closure to return to normal" ::= { esPointConfigCCEntry 15 } --1.3.6.1.4.1.3052.10.2.2.2.1.15 espcCCOverrideGlobalReminder OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Override global reminder interval (evReminderInterval) for this CC." ::= { esPointConfigCCEntry 16 } --1.3.6.1.4.1.3052.10.2.2.2.1.16 espcCCReminderInterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Individual reminder interval for this CC, applicable when the global reminder is overriden." ::= { esPointConfigCCEntry 17 } --1.3.6.1.4.1.3052.10.2.2.2.1.17 espcCCGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this contact closure group" ::= { esPointConfigCCEntry 18 } --1.3.6.1.4.1.3052.10.2.2.2.1.18 esPointConfigHumidTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigHumid MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of humidity points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for humidity sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this humidity point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 3 } --1.3.6.1.4.1.3052.10.2.2.3 esPointConfigHumidEntry OBJECT-TYPE SYNTAX ESPointConfigHumid MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config humidity table" INDEX { espcHumidIndexES, espcHumidIndexPoint } ::= { esPointConfigHumidTable 1 } --1.3.6.1.4.1.3052.10.2.2.3.1 espcHumidIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigHumidEntry 1 } --1.3.6.1.4.1.3052.10.2.2.3.1.1 espcHumidIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcHumidIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigHumidEntry 2 } --1.3.6.1.4.1.3052.10.2.2.3.1.2 espcHumidEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable for this humidity sensor" ::= { esPointConfigHumidEntry 3 } --1.3.6.1.4.1.3052.10.2.2.3.1.3 espcHumidDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this humidity sensor" ::= { esPointConfigHumidEntry 4 } --1.3.6.1.4.1.3052.10.2.2.3.1.4 espcHumidVHighHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 5 } --1.3.6.1.4.1.3052.10.2.2.3.1.5 espcHumidVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions for this humidity sensor" ::= { esPointConfigHumidEntry 6 } --1.3.6.1.4.1.3052.10.2.2.3.1.6 espcHumidVHighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number for this humidity sensor" ::= { esPointConfigHumidEntry 7 } --1.3.6.1.4.1.3052.10.2.2.3.1.7 espcHumidVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class for this humidity sensor" ::= { esPointConfigHumidEntry 8 } --1.3.6.1.4.1.3052.10.2.2.3.1.8 espcHumidHighHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 9 } --1.3.6.1.4.1.3052.10.2.2.3.1.9 espcHumidHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions for this humidity sensor" ::= { esPointConfigHumidEntry 10 } --1.3.6.1.4.1.3052.10.2.2.3.1.10 espcHumidHighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number for this humidity sensor" ::= { esPointConfigHumidEntry 11 } --1.3.6.1.4.1.3052.10.2.2.3.1.11 espcHumidHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class for this humidity sensor" ::= { esPointConfigHumidEntry 12 } --1.3.6.1.4.1.3052.10.2.2.3.1.12 espcHumidNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal actions for this humidity sensor" ::= { esPointConfigHumidEntry 13 } --1.3.6.1.4.1.3052.10.2.2.3.1.13 espcHumidNormalTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal trap number for this humidity sensor" ::= { esPointConfigHumidEntry 14 } --1.3.6.1.4.1.3052.10.2.2.3.1.14 espcHumidNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal class for this humidity sensor" ::= { esPointConfigHumidEntry 15 } --1.3.6.1.4.1.3052.10.2.2.3.1.15 espcHumidLowHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 16 } --1.3.6.1.4.1.3052.10.2.2.3.1.16 espcHumidLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions for this humidity sensor" ::= { esPointConfigHumidEntry 17 } --1.3.6.1.4.1.3052.10.2.2.3.1.17 espcHumidLowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number for this humidity sensor" ::= { esPointConfigHumidEntry 18 } --1.3.6.1.4.1.3052.10.2.2.3.1.18 espcHumidLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class for this humidity sensor" ::= { esPointConfigHumidEntry 19 } --1.3.6.1.4.1.3052.10.2.2.3.1.19 espcHumidVLowHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 20 } --1.3.6.1.4.1.3052.10.2.2.3.1.20 espcHumidVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions for this humidity sensor" ::= { esPointConfigHumidEntry 21 } --1.3.6.1.4.1.3052.10.2.2.3.1.21 espcHumidVLowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event trap number for this humidity sensor" ::= { esPointConfigHumidEntry 22 } --1.3.6.1.4.1.3052.10.2.2.3.1.22 espcHumidVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class for this humidity sensor" ::= { esPointConfigHumidEntry 23 } --1.3.6.1.4.1.3052.10.2.2.3.1.23 espcHumidGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this humidity sensor group" ::= { esPointConfigHumidEntry 24 } --1.3.6.1.4.1.3052.10.2.2.3.1.24 esPointConfigAITable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigAnalogInput MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of analog input points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this analog input point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 5 } --1.3.6.1.4.1.3052.10.2.2.5 esPointConfigAIEntry OBJECT-TYPE SYNTAX ESPointConfigAnalogInput MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config analog input table" INDEX { espcHumidIndexES, espcHumidIndexPoint } ::= { esPointConfigAITable 1 } --1.3.6.1.4.1.3052.10.2.2.5.1 espcAIIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigAIEntry 1 } --1.3.6.1.4.1.3052.10.2.2.5.1.1 espcAIIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcAIIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigAIEntry 2 } --1.3.6.1.4.1.3052.10.2.2.5.1.2 espcAIEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF for this analog input sensor" ::= { esPointConfigAIEntry 3 } --1.3.6.1.4.1.3052.10.2.2.5.1.3 espcAIDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this analog input sensor" ::= { esPointConfigAIEntry 5 } --1.3.6.1.4.1.3052.10.2.2.5.1.5 espcAIVhighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 6 } --1.3.6.1.4.1.3052.10.2.2.5.1.6 espcAIVhighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions for this analog input sensor" ::= { esPointConfigAIEntry 7 } --1.3.6.1.4.1.3052.10.2.2.5.1.7 espcAIVhighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number for this analog input sensor" ::= { esPointConfigAIEntry 8 } --1.3.6.1.4.1.3052.10.2.2.5.1.8 espcAIVhighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class for this analog input sensor" ::= { esPointConfigAIEntry 9 } --1.3.6.1.4.1.3052.10.2.2.5.1.9 espcAIHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 10 } --1.3.6.1.4.1.3052.10.2.2.5.1.10 espcAIHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions for this analog input sensor" ::= { esPointConfigAIEntry 11 } --1.3.6.1.4.1.3052.10.2.2.5.1.11 espcAIHighTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number for this analog input sensor" ::= { esPointConfigAIEntry 12 } --1.3.6.1.4.1.3052.10.2.2.5.1.12 espcAIHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class for this analog input sensor" ::= { esPointConfigAIEntry 13 } --1.3.6.1.4.1.3052.10.2.2.5.1.13 espcAINormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal actions for this analog input sensor" ::= { esPointConfigAIEntry 14 } --1.3.6.1.4.1.3052.10.2.2.5.1.14 espcAINormalTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal trap number for this analog input sensor" ::= { esPointConfigAIEntry 15 } --1.3.6.1.4.1.3052.10.2.2.5.1.15 espcAINormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal class for this analog input sensor" ::= { esPointConfigAIEntry 16 } --1.3.6.1.4.1.3052.10.2.2.5.1.16 espcAILowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 17 } --1.3.6.1.4.1.3052.10.2.2.5.1.17 espcAILowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions for this analog input sensor" ::= { esPointConfigAIEntry 18 } --1.3.6.1.4.1.3052.10.2.2.5.1.18 espcAILowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number for this analog input sensor" ::= { esPointConfigAIEntry 19 } --1.3.6.1.4.1.3052.10.2.2.5.1.19 espcAILowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class for this analog input sensor" ::= { esPointConfigAIEntry 20 } --1.3.6.1.4.1.3052.10.2.2.5.1.20 espcAIVlowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 21 } --1.3.6.1.4.1.3052.10.2.2.5.1.21 espcAIVlowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions for this analog input sensor" ::= { esPointConfigAIEntry 22 } --1.3.6.1.4.1.3052.10.2.2.5.1.22 espcAIVlowTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions for this analog input sensor" ::= { esPointConfigAIEntry 23 } --1.3.6.1.4.1.3052.10.2.2.5.1.23 espcAIVlowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class for this analog input sensor" ::= { esPointConfigAIEntry 24 } --1.3.6.1.4.1.3052.10.2.2.5.1.24 espcAIConvUnitName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Converstion unit name for this analog input sensor" ::= { esPointConfigAIEntry 25 } --1.3.6.1.4.1.3052.10.2.2.5.1.25 espcAIConvHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion high value for this analog input sensor" ::= { esPointConfigAIEntry 26 } --1.3.6.1.4.1.3052.10.2.2.5.1.26 espcAIConvHighUnit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion high unit value for this analog input sensor" ::= { esPointConfigAIEntry 27 } --1.3.6.1.4.1.3052.10.2.2.5.1.27 espcAIConvLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion low value for this analog input sensor" ::= { esPointConfigAIEntry 29 } --1.3.6.1.4.1.3052.10.2.2.5.1.29 espcAIConvLowUnit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion unit low unit value for this analog input sensor" ::= { esPointConfigAIEntry 30 } --1.3.6.1.4.1.3052.10.2.2.5.1.30 espcAIDisplayFormat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Analog input display format" ::= { esPointConfigAIEntry 32 } --1.3.6.1.4.1.3052.10.2.2.5.1.32 espcAIGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this Analog input group" ::= { esPointConfigAIEntry 33 } --1.3.6.1.4.1.3052.10.2.2.5.1.33 esPointConfigOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigOutput MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes configuration items for output points. A point is a particular sensor on an EventSensor. The 3 point attributes organized in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this output config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 6 } --1.3.6.1.4.1.3052.10.2.2.6 esPointConfigOutputEntry OBJECT-TYPE SYNTAX ESPointConfigOutput MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config output table" INDEX { espcOutputIndexES, espcOutputIndexPoint } ::= { esPointConfigOutputTable 1 } --1.3.6.1.4.1.3052.10.2.2.6.1 espcOutputIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigOutputEntry 1 } --1.3.6.1.4.1.3052.10.2.2.6.1.1 espcOutputIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcOutputIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of output point configuration." ::= { esPointConfigOutputEntry 2 } --1.3.6.1.4.1.3052.10.2.2.6.1.2 espcOutputEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enables the output event for this output. This has no effect on whether the relay changes state, only on whether a state change triggers an event." ::= { esPointConfigOutputEntry 3 } --1.3.6.1.4.1.3052.10.2.2.6.1.3 espcOutputActiveState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Which state is considered the active state: energized/de-energized." ::= { esPointConfigOutputEntry 4 } --1.3.6.1.4.1.3052.10.2.2.6.1.4 espcOutputType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Output type: RELAY, POWER, SSR, TTL." ::= { esPointConfigOutputEntry 5 } --1.3.6.1.4.1.3052.10.2.2.6.1.5 espcOutputAliasValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Output alias corresponding to its event state." ::= { esPointConfigOutputEntry 6 } --1.3.6.1.4.1.3052.10.2.2.6.1.6 espcOutputAliasColor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Output color corresponding to its event state." ::= { esPointConfigOutputEntry 7 } --1.3.6.1.4.1.3052.10.2.2.6.1.7 espcOutputActiveAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Alias for the output active state." ::= { esPointConfigOutputEntry 10 } --1.3.6.1.4.1.3052.10.2.2.6.1.10 espcOutputActiveColor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Output color (as rendered in the web UI, in RGB hex format) corresponding to the output active state." ::= { esPointConfigOutputEntry 11 } --1.3.6.1.4.1.3052.10.2.2.6.1.11 espcOutputActiveActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the output active event." ::= { esPointConfigOutputEntry 12 } --1.3.6.1.4.1.3052.10.2.2.6.1.12 espcOutputActiveTrapnum OBJECT-TYPE SYNTAX Integer32 (150..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the output active event." ::= { esPointConfigOutputEntry 13 } --1.3.6.1.4.1.3052.10.2.2.6.1.13 espcOutputActiveClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for the output active event." ::= { esPointConfigOutputEntry 14 } --1.3.6.1.4.1.3052.10.2.2.6.1.14 espcOutputInactiveAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Alias for the output inactive state." ::= { esPointConfigOutputEntry 20 } --1.3.6.1.4.1.3052.10.2.2.6.1.20 espcOutputInactiveColor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Output color (as rendered in the web UI, in RGB hex format) corresponding to the output inactive state." ::= { esPointConfigOutputEntry 21 } --1.3.6.1.4.1.3052.10.2.2.6.1.21 espcOutputInactiveActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the output inactive event." ::= { esPointConfigOutputEntry 22 } --1.3.6.1.4.1.3052.10.2.2.6.1.22 espcOutputInactiveTrapnum OBJECT-TYPE SYNTAX Integer32 (150..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the output inactive event." ::= { esPointConfigOutputEntry 23 } --1.3.6.1.4.1.3052.10.2.2.6.1.23 espcOutputInactiveClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for the output inactive event." ::= { esPointConfigOutputEntry 24 } --1.3.6.1.4.1.3052.10.2.2.6.1.24 espcOutputGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this Ouput Group" ::= { esPointConfigOutputEntry 25 } --1.3.6.1.4.1.3052.10.2.2.6.1.25 --*************************************************************************************** --Serial Port Section 2.3 --*************************************************************************************** numberPorts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of RS-232 ports found. Range: 2 or 4" ::= { serialPorts 1 } --1.3.6.1.4.1.3052.10.2.3.1 portConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF PortConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Port config table" ::= { serialPorts 2 } --1.3.6.1.4.1.3052.10.2.3.2 portConfigEntry OBJECT-TYPE SYNTAX PortConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Port config entry" INDEX { portConfigIndex } ::= { portConfigTable 1 } --1.3.6.1.4.1.3052.10.2.3.2.1 portConfigIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for ports" ::= { portConfigEntry 1 } --1.3.6.1.4.1.3052.10.2.3.2.1.1 portConfigBaud OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Baud rate, 19200, 9600, etc." ::= { portConfigEntry 2 } --1.3.6.1.4.1.3052.10.2.3.2.1.2 portConfigDataFormat OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Value representing word length, parity, and stop bits: 0=8N1, 1=7E1, 2=7O1, 3=7N1, 4=8O2" ::= { portConfigEntry 3 } --1.3.6.1.4.1.3052.10.2.3.2.1.3 portConfigStripPtOutputLfs OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Strip passthrough LFs sent to device on this port: 1=yes, 0=no." ::= { portConfigEntry 4 } --1.3.6.1.4.1.3052.10.2.3.2.1.4 portConfigStripPtInputLfs OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Strip passthrough LFs received from device on this port: 1=yes, 0=no." ::= { portConfigEntry 5 } --1.3.6.1.4.1.3052.10.2.3.2.1.5 portConfigMaskEnable OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "1=Use the character mask on this port. 0=Do not use the mask. When the mask is enabled, the following ASCII characters are ignored on the port: 0, 1, 4-9, 11, 12, 14-31, 128-255. When the mask is disabled, all characters are accepted on the port." ::= { portConfigEntry 7 } --1.3.6.1.4.1.3052.10.2.3.2.1.7 portConfigDAEnable OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "1=Enable the Data Alarm Evaluator for data on this port. 0=Do not evaluate data on this port." ::= { portConfigEntry 8 } --1.3.6.1.4.1.3052.10.2.3.2.1.8 portConfigStoreAlarmsDPT OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: store alarms received during passthrough" ::= { portConfigEntry 9 } --1.3.6.1.4.1.3052.10.2.3.2.1.9 portConfigRecordTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Timeout after last unterminated data received upon which data collected so far is stored as a record." ::= { portConfigEntry 10 } --1.3.6.1.4.1.3052.10.2.3.2.1.10 portConfigDataType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "How the port interprets incoming data: ASCII/BINARY" ::= { portConfigEntry 11 } --1.3.6.1.4.1.3052.10.2.3.2.1.11 portConfigEtxToCRLF OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF whether the port translates incoming ETX to CRLF" ::= { portConfigEntry 12 } --1.3.6.1.4.1.3052.10.2.3.2.1.12 portConfigMLREnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Whether Multiline Records are collected on this port." ::= { portConfigEntry 13 } --1.3.6.1.4.1.3052.10.2.3.2.1.13 portConfigMLRStartField1Pos OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Position of MLR start field 1" ::= { portConfigEntry 14 } --1.3.6.1.4.1.3052.10.2.3.2.1.14 portConfigMLRStartField1Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text to match MLR start field 1" ::= { portConfigEntry 15 } --1.3.6.1.4.1.3052.10.2.3.2.1.15 portConfigMLRStartField2Pos OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Position of MLR start field 2" ::= { portConfigEntry 16 } --1.3.6.1.4.1.3052.10.2.3.2.1.16 portConfigMLRStartField2Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text to match MLR start field 2" ::= { portConfigEntry 17 } --1.3.6.1.4.1.3052.10.2.3.2.1.17 portConfigMLRNumLinesBefore OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of lines before the starting line which should be included in the MLR" ::= { portConfigEntry 18 } --1.3.6.1.4.1.3052.10.2.3.2.1.18 portConfigMLREndDetection OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "How the MLR parser determines what ends an MLR: by FORMULA, number of lines received so far (COUNT), or number of blank lines received so far (BLANKS)" ::= { portConfigEntry 19 } --1.3.6.1.4.1.3052.10.2.3.2.1.19 portConfigMLRLineCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of lines in the MLR (used by the end detection mode)" ::= { portConfigEntry 20 } --1.3.6.1.4.1.3052.10.2.3.2.1.20 portConfigMLREndField1Pos OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Position of MLR end field 1" ::= { portConfigEntry 21 } --1.3.6.1.4.1.3052.10.2.3.2.1.21 portConfigMLREndField1Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text to match MLR end field 1" ::= { portConfigEntry 22 } --1.3.6.1.4.1.3052.10.2.3.2.1.22 portConfigMLREndField2Pos OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Position of MLR end field 2" ::= { portConfigEntry 23 } --1.3.6.1.4.1.3052.10.2.3.2.1.23 portConfigMLREndField2Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text to match MLR end field 2" ::= { portConfigEntry 24 } --1.3.6.1.4.1.3052.10.2.3.2.1.24 portConfigMLRUseComplexRules OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF MLR parser uses complex rules (field possitions/ formulas, etc.)" ::= { portConfigEntry 25 } --1.3.6.1.4.1.3052.10.2.3.2.1.25 portConfigBufferPT OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF records received during passthrough mode are buffered/stored in the database" ::= { portConfigEntry 26 } --1.3.6.1.4.1.3052.10.2.3.2.1.26 portConfigId OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The text identifer for the port" ::= { portConfigEntry 27 } --1.3.6.1.4.1.3052.10.2.3.2.1.27 portConfigMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Mode of the serial port." ::= { portConfigEntry 28 } --1.3.6.1.4.1.3052.10.2.3.2.1.28 portConfigHsk OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Handshaking mode of the serial port." ::= { portConfigEntry 29 } --1.3.6.1.4.1.3052.10.2.3.2.1.29 --*************************************************************************************** --Network Section 2.4 --*************************************************************************************** eth1Mode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Mode of the Ethernet1 interface: STATIC,DHCP,VLAN" ::= { ethernet1 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.1 eth1Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 IP address" ::= { ethernet1 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.2 eth1SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 subnet mask" ::= { ethernet1 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.3 eth1Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 router" ::= { ethernet1 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.4 -- Ethernet1 VLAN1 eth1VLAN1ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN1 ID" ::= { eth1VLAN1 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.1.1 eth1VLAN1Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN1 priority" ::= { eth1VLAN1 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.1.2 eth1VLAN1Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN1 IP address" ::= { eth1VLAN1 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.1.3 eth1VLAN1SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN1 subnet mask" ::= { eth1VLAN1 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.1.4 eth1VLAN1Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN1 router" ::= { eth1VLAN1 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.1.5 -- Ethernet1 VLAN2 eth1VLAN2ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN2 ID" ::= { eth1VLAN2 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.2.1 eth1VLAN2Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN2 priority" ::= { eth1VLAN2 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.2.2 eth1VLAN2Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN2 IP address" ::= { eth1VLAN2 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.2.3 eth1VLAN2SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN2 subnet mask" ::= { eth1VLAN2 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.2.4 eth1VLAN2Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN2 router" ::= { eth1VLAN2 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.2.5 -- Ethernet1 VLAN3 eth1VLAN3ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN3 ID" ::= { eth1VLAN3 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.3.1 eth1VLAN3Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN3 priority" ::= { eth1VLAN3 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.3.2 eth1VLAN3Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN3 IP address" ::= { eth1VLAN3 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.3.3 eth1VLAN3SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN3 subnet mask" ::= { eth1VLAN3 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.3.4 eth1VLAN3Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN3 router" ::= { eth1VLAN3 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.3.5 -- Ethernet1 VLAN4 eth1VLAN4ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN4 ID" ::= { eth1VLAN4 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.4.1 eth1VLAN4Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN4 priority" ::= { eth1VLAN4 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.4.2 eth1VLAN4Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN4 IP address" ::= { eth1VLAN4 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.4.3 eth1VLAN4SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN4 subnet mask" ::= { eth1VLAN4 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.4.4 eth1VLAN4Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN4 router" ::= { eth1VLAN4 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.4.5 -- Ethernet1 VLAN5 eth1VLAN5ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN5 ID" ::= { eth1VLAN5 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.5.1 eth1VLAN5Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN5 priority" ::= { eth1VLAN5 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.5.2 eth1VLAN5Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN5 IP address" ::= { eth1VLAN5 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.5.3 eth1VLAN5SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN5 subnet mask" ::= { eth1VLAN5 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.5.4 eth1VLAN5Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN5 router" ::= { eth1VLAN5 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.5.5 -- Ethernet1 VLAN6 eth1VLAN6ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN6 ID" ::= { eth1VLAN6 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.6.1 eth1VLAN6Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN6 priority" ::= { eth1VLAN6 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.6.2 eth1VLAN6Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN6 IP address" ::= { eth1VLAN6 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.6.3 eth1VLAN6SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN6 subnet mask" ::= { eth1VLAN6 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.6.4 eth1VLAN6Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet1 VLAN6 router" ::= { eth1VLAN6 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.5.6.5 eth1MAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Ethernet1 MAC" ::= { ethernet1 6 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.6 eth1IPv6Mode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls IPv6 operation for this Ethernet interface." ::= { eth1IPv6 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.1 eth1IPv6StaticAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "he static IPv6 address to use for this interface when in operating in STATIC mode." ::= { eth1IPv6Static 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.2.1 eth1IPv6StaticRouter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The IPv6 router to engage as the default router when this interface operates in STATIC mode." ::= { eth1IPv6Static 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.2.1 eth1IPv6AutoAddress1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth1IPv6Auto 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.3.1 eth1IPv6AutoAddress2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth1IPv6Auto 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.3.2 eth1IPv6AutoAddress3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth1IPv6Auto 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.3.3 eth1IPv6AutoAddress4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth1IPv6Auto 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.3.4 eth1IPv6LinkLocalAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The link local IPv6 address for this interface. This is present when the IPv6 mode is not OFF." ::= { eth1IPv6 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.1.7.4 eth2Mode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Mode of the Ethernet2 interface: STATIC,DHCP,VLAN" ::= { ethernet2 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.1 eth2Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 IP address" ::= { ethernet2 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.2 eth2SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 subnet mask" ::= { ethernet2 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.3 eth2Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 router" ::= { ethernet2 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.4 -- Ethernet2 VLAN1 eth2VLAN1ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN1 ID" ::= { eth2VLAN1 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.1.1 eth2VLAN1Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN1 priority" ::= { eth2VLAN1 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.1.2 eth2VLAN1Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN1 IP address" ::= { eth2VLAN1 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.1.3 eth2VLAN1SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN1 subnet mask" ::= { eth2VLAN1 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.1.4 eth2VLAN1Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN1 router" ::= { eth2VLAN1 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.1.5 -- Ethernet2 VLAN2 eth2VLAN2ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN2 ID" ::= { eth2VLAN2 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.2.1 eth2VLAN2Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN2 priority" ::= { eth2VLAN2 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.2.2 eth2VLAN2Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN2 IP address" ::= { eth2VLAN2 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.2.3 eth2VLAN2SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN2 subnet mask" ::= { eth2VLAN2 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.2.4 eth2VLAN2Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN2 router" ::= { eth2VLAN2 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.2.5 -- Ethernet2 VLAN3 eth2VLAN3ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN3 ID" ::= { eth2VLAN3 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.3.1 eth2VLAN3Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN3 priority" ::= { eth2VLAN3 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.3.2 eth2VLAN3Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN3 IP address" ::= { eth2VLAN3 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.3.3 eth2VLAN3SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN3 subnet mask" ::= { eth2VLAN3 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.3.4 eth2VLAN3Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN3 router" ::= { eth2VLAN3 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.3.5 -- Ethernet2 VLAN4 eth2VLAN4ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN4 ID" ::= { eth2VLAN4 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.4.1 eth2VLAN4Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN4 priority" ::= { eth2VLAN4 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.4.2 eth2VLAN4Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN4 IP address" ::= { eth2VLAN4 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.4.3 eth2VLAN4SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN4 subnet mask" ::= { eth2VLAN4 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.4.4 eth2VLAN4Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN4 router" ::= { eth2VLAN4 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.4.5 -- Ethernet2 VLAN5 eth2VLAN5ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN5 ID" ::= { eth2VLAN5 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.5.1 eth2VLAN5Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN5 priority" ::= { eth2VLAN5 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.5.2 eth2VLAN5Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN5 IP address" ::= { eth2VLAN5 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.5.3 eth2VLAN5SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN5 subnet mask" ::= { eth2VLAN5 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.5.4 eth2VLAN5Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN5 router" ::= { eth2VLAN5 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.5.5 -- Ethernet2 VLAN6 eth2VLAN6ID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN6 ID" ::= { eth2VLAN6 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.6.1 eth2VLAN6Priority OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN6 priority" ::= { eth2VLAN6 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.6.2 eth2VLAN6Address OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN6 IP address" ::= { eth2VLAN6 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.6.3 eth2VLAN6SubnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN6 subnet mask" ::= { eth2VLAN6 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.6.4 eth2VLAN6Router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet2 VLAN6 router" ::= { eth2VLAN6 5 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.5.6.5 eth2MAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Ethernet2 MAC" ::= { ethernet2 6 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.6 eth2IPv6Mode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls IPv6 operation for this Ethernet interface." ::= { eth2IPv6 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.1 eth2IPv6StaticAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "he static IPv6 address to use for this interface when in operating in STATIC mode." ::= { eth2IPv6Static 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.2.1 eth2IPv6StaticRouter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The IPv6 router to engage as the default router when this interface operates in STATIC mode." ::= { eth2IPv6Static 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.2.1 eth2IPv6AutoAddress1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth2IPv6Auto 1 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.3.1 eth2IPv6AutoAddress2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth2IPv6Auto 2 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.3.2 eth2IPv6AutoAddress3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth2IPv6Auto 3 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.3.3 eth2IPv6AutoAddress4 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "One of the automatically-acquired IPv6 addresses." ::= { eth2IPv6Auto 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.3.4 eth2IPv6LinkLocalAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The link local IPv6 address for this interface. This is present when the IPv6 mode is not OFF." ::= { eth2IPv6 4 } --1.3.6.1.4.1.3052.10.2.4.1.1.2.7.4 defaultRouter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The default router/gateway" ::= { network 2 } --1.3.6.1.4.1.3052.10.2.4.2 -- DNS dnsTable OBJECT-TYPE SYNTAX SEQUENCE OF DNSConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "DNS server address table" ::= { network 3 } --1.3.6.1.4.1.3052.10.2.4.3 dnsEntry OBJECT-TYPE SYNTAX DNSConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "DNS server address entry" INDEX { dnsIndex } ::= { dnsTable 1 } --1.3.6.1.4.1.3052.10.2.4.3.1 dnsIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for DNS server address" ::= { dnsEntry 1 } --1.3.6.1.4.1.3052.10.2.4.3.1.1 dnsAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "DNS server address" ::= { dnsEntry 2 } --1.3.6.1.4.1.3052.10.2.4.3.1.2 hostname OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The hostname of the unit" ::= { network 4 } --1.3.6.1.4.1.3052.10.2.4.4 hostTable OBJECT-TYPE SYNTAX SEQUENCE OF HostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Static host table" ::= { network 5 } --1.3.6.1.4.1.3052.10.2.4.5 hostEntry OBJECT-TYPE SYNTAX HostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Static host entry" INDEX { hostIndex } ::= { hostTable 1 } --1.3.6.1.4.1.3052.10.2.4.5.1 hostIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for static host" ::= { hostEntry 1 } --1.3.6.1.4.1.3052.10.2.4.5.1.1 hostDeclaration OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Static host declaration string (i.e. 'address hostname')" ::= { hostEntry 2 } --1.3.6.1.4.1.3052.10.2.4.5.1.2 -- Network Command Processor ncpDuplex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "For network command processor: 1=Input characters are echoed; 0=no echo." ::= { network 6 } --1.3.6.1.4.1.3052.10.2.4.6 ncpTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Network command processor inactivity timeout" ::= { network 7 } --1.3.6.1.4.1.3052.10.2.4.7 -- SNMP snmpAgentEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF for snmp agent" ::= { snmp 1 } --1.3.6.1.4.1.3052.10.2.4.8.1 snmpNotificationCaptureEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF unit receives and stores SNMP traps/informs" ::= { snmp 5 } --1.3.6.1.4.1.3052.10.2.4.8.5 snmpNotificationCaptureFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "File to which unit stores received SNMP traps/informs" ::= { snmp 6 } --1.3.6.1.4.1.3052.10.2.4.8.6 snmpNtfnAttempts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum of times the unit attempts to send a notification (trap/inform) in 1 cycle" ::= { snmpNotificationTx 1 } --1.3.6.1.4.1.3052.10.2.4.8.7.1 snmpNtfnTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of seconds between retries of sending a notification" ::= { snmpNotificationTx 2 } --1.3.6.1.4.1.3052.10.2.4.8.7.2 snmpNtfnCycles OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of times the unit attempts a group of attempts to send a notification (a cycle)" ::= { snmpNotificationTx 3 } --1.3.6.1.4.1.3052.10.2.4.8.7.3 snmpNtfnSnooze OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Minutes between cycles" ::= { snmpNotificationTx 4 } --1.3.6.1.4.1.3052.10.2.4.8.7.4 -- SNMP proxy snmpProxyTable OBJECT-TYPE SYNTAX SEQUENCE OF SNMPProxyTable MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of SNMP proxy entries" ::= { snmpProxy 1 } --1.3.6.1.4.1.3052.10.2.4.8.8.1 snmpProxyEntry OBJECT-TYPE SYNTAX SNMPProxyTable MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for SNMP proxy table" INDEX { snmpProxyIndex } ::= { snmpProxyTable 1 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1 snmpProxyIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for SNMP proxy table" ::= { snmpProxyEntry 1 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.1 snmpProxyEgressOIDBranch OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The OID branch to trigger the proxy function. This should cover the device to proxy. If blank then this proxy entry is disabled." ::= { snmpProxyEntry 2 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.2 snmpProxyIP OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The IP address of the device to proxy." ::= { snmpProxyEntry 3 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.3 snmpProxyPort OBJECT-TYPE SYNTAX Integer32 (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "The UDP port on which the device to proxy listens." ::= { snmpProxyEntry 4 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.4 snmpProxyIngressOIDBranch OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The OID branch to be remapped to egress OID branch to trigger the proxy function. If blank then the egress OID branch is proxied without remapping." ::= { snmpProxyEntry 5 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.5 snmpProxyName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of this proxy entry." ::= { snmpProxyEntry 6 } --1.3.6.1.4.1.3052.10.2.4.8.8.1.1.6 -- SNMP Poll snmpPMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Mode of poll operation: OFF, POLL ONLY (just make the results available to view), or POLL BUFFER (store the results)." ::= { snmpPoll 1 } --1.3.6.1.4.1.3052.10.2.4.8.9.1 snmpPBufferFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "CRDB file in which data is stored." ::= { snmpPoll 2 } --1.3.6.1.4.1.3052.10.2.4.8.9.2 snmpPBufferAllPeriod OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Period (in seconds) that, if non-zero, all results are buffered in the CRDB regardless of the threshold." ::= { snmpPoll 3 } --1.3.6.1.4.1.3052.10.2.4.8.9.3 snmpPRequestTable OBJECT-TYPE SYNTAX SEQUENCE OF SNMPPollRequestConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of SNMP Poll requests." ::= { snmpPoll 4 } --1.3.6.1.4.1.3052.10.2.4.8.9.4 snmpPRequestEntry OBJECT-TYPE SYNTAX SNMPPollRequestConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table pf SNMP Poll requests." INDEX { snmpPRequestIndex } ::= { snmpPRequestTable 1 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1 snmpPRequestIndex OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of SNMP Poll requests." ::= { snmpPRequestEntry 1 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.1 snmpPRequestDescription OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A description for this single telemetry request; no functional effect." ::= { snmpPRequestEntry 2 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.2 snmpPRequestAgent OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP Agent IP address or hostname for this single telemetry request." ::= { snmpPRequestEntry 3 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.3 snmpPRequestReadcom OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP read community for this single telemetry request." ::= { snmpPRequestEntry 4 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.4 snmpPRequestOID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP object identifier for this single telemetry request." ::= { snmpPRequestEntry 5 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.5 snmpPRequestPeriod OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS read-write STATUS current DESCRIPTION "How many seconds between periodic SNMP polls of this single telemetry request." ::= { snmpPRequestEntry 6 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.6 snmpPRequestID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A textual field that is part of the record containing the telemetry result." ::= { snmpPRequestEntry 7 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.7 snmpPRequestThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls when new data is stored upon a successful telemetry request." ::= { snmpPRequestEntry 8 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.8 snmpPRequestResultStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the last attempt for this telemetry request." ::= { snmpPRequestEntry 10 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.10 snmpPRequestResultValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The telemetry value if the last request was successful." ::= { snmpPRequestEntry 11 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.11 snmpPRequestResultTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The timestamp of the last telemetry request." ::= { snmpPRequestEntry 12 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.12 snmpPRequestResultType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The type of the telemetry as reported by the agent." ::= { snmpPRequestEntry 13 } --1.3.6.1.4.1.3052.10.2.4.8.9.4.1.13 -- FTP ftpPushEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable FTP push for REGULAR (protocol: FTP) or SECURE (protocol: SFTP) operation, or disable it (OFF)" ::= { ftpPush 1 } --1.3.6.1.4.1.3052.10.2.4.9.1 ftpPushServer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "FTP server to which data should be pushed" ::= { ftpPush 2 } --1.3.6.1.4.1.3052.10.2.4.9.2 ftpPushAccount OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "FTP push account" ::= { ftpPush 5 } --1.3.6.1.4.1.3052.10.2.4.9.5 ftpPushDirectory OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "FTP push directory" ::= { ftpPush 6 } --1.3.6.1.4.1.3052.10.2.4.9.6 ftpPushperiod OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Minutes between pushes" ::= { ftpPush 7 } --1.3.6.1.4.1.3052.10.2.4.9.7 ftpPushPushFileTable OBJECT-TYPE SYNTAX SEQUENCE OF FTPPushPushFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of files to push" ::= { ftpPush 8 } --1.3.6.1.4.1.3052.10.2.4.9.8 ftpPushPushFileEntry OBJECT-TYPE SYNTAX FTPPushPushFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of files to push" INDEX { ftpPushPushFileIndex } ::= { ftpPushPushFileTable 1 } --1.3.6.1.4.1.3052.10.2.4.9.8.1 ftpPushPushFileIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of files to push" ::= { ftpPushPushFileEntry 1 } --1.3.6.1.4.1.3052.10.2.4.9.8.1.1 ftpPushPushFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF push this local FILEx" ::= { ftpPushPushFileEntry 2 } --1.3.6.1.4.1.3052.10.2.4.9.8.1.2 ftpPushPushAudit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF push the audit log" ::= { ftpPush 9 } --1.3.6.1.4.1.3052.10.2.4.9.9 ftpPushPushAlarms OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF push the alarms/events file" ::= { ftpPush 10 } --1.3.6.1.4.1.3052.10.2.4.9.10 ftpPushRemoteFileTable OBJECT-TYPE SYNTAX SEQUENCE OF FTPPushRemoteFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of remote names of files to push" ::= { ftpPush 11 } --1.3.6.1.4.1.3052.10.2.4.9.11 ftpPushRemoteFileEntry OBJECT-TYPE SYNTAX FTPPushRemoteFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of remote names of files to push" INDEX { ftpPushRemoteFileIndex } ::= { ftpPushRemoteFileTable 1 } --1.3.6.1.4.1.3052.10.2.4.9.11.1 ftpPushRemoteFileIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of remote names of files to push" ::= { ftpPushRemoteFileEntry 1 } --1.3.6.1.4.1.3052.10.2.4.9.11.1 ftpPushRemoteFileName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "remote name of pushed FILEx (name on server)" ::= { ftpPushRemoteFileEntry 2 } --1.3.6.1.4.1.3052.10.2.4.9.11.2 ftpPushRemoteAlarmName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Filename on server for alarms" ::= { ftpPush 12 } --1.3.6.1.4.1.3052.10.2.4.9.12 ftpPushPassive OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF use ftp passive mode" ::= { ftpPush 13 } --1.3.6.1.4.1.3052.10.2.4.9.13 ftpPushIncludeDate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include the date in the name of the pushed file" ::= { ftpPush 14 } --1.3.6.1.4.1.3052.10.2.4.9.14 ftpPushIncludeTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include the time in the name of the pushed file" ::= { ftpPush 15 } --1.3.6.1.4.1.3052.10.2.4.9.15 ftpPushIncludeSeq OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include a sequence number in the name of the pushed file" ::= { ftpPush 16 } --1.3.6.1.4.1.3052.10.2.4.9.16 ftpPushPermissions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Unix permissions to apply to pushed files (octal notation)." ::= { ftpPush 17 } --1.3.6.1.4.1.3052.10.2.4.9.17 pppDialEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF PPP dialout enabled" ::= { pppDial 1 } --1.3.6.1.4.1.3052.10.2.4.10.1.1 pppDialNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "phone number to dial" ::= { pppDial 2 } --1.3.6.1.4.1.3052.10.2.4.10.1.2 pppDialIdleTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds of inactivity after which the unit disconnects" ::= { pppDial 5 } --1.3.6.1.4.1.3052.10.2.4.10.1.5 pppDialRetries OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of dialing retries for PPP" ::= { pppDial 6 } --1.3.6.1.4.1.3052.10.2.4.10.1.6 pppDialCDTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of seconds to wait after dialing for CD before giving up" ::= { pppDial 7 } --1.3.6.1.4.1.3052.10.2.4.10.1.7 pppDialLoginTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait to negotiate PPP after connecting" ::= { pppDial 8 } --1.3.6.1.4.1.3052.10.2.4.10.1.8 pppDialMdmInit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Modem init string to use when dialing PPP" ::= { pppDial 9 } --1.3.6.1.4.1.3052.10.2.4.10.1.9 pppDialSuggestIP OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IP address to suggest as the unit's end (local end) of the PPP link" ::= { pppDial 10 } --1.3.6.1.4.1.3052.10.2.4.10.1.10 pppDialPlainLogin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF look for login/password prompt before negotiating PPP" ::= { pppDial 11 } --1.3.6.1.4.1.3052.10.2.4.10.1.11 pppHostEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Unit accepts PPP negotiation" ::= { pppHost 1 } --1.3.6.1.4.1.3052.10.2.4.10.2.1 pppHostIdleTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds of inactivity after which PPP-hosted link will terminate" ::= { pppHost 2 } --1.3.6.1.4.1.3052.10.2.4.10.2.2 pppHostLocalIP OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Local IP address to negotiate" ::= { pppHost 3 } --1.3.6.1.4.1.3052.10.2.4.10.2.3 pppHostRemoteIP OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Remote IP address to hand out to PPP peer" ::= { pppHost 4 } --1.3.6.1.4.1.3052.10.2.4.10.2.4 -- Routing pppRoutingEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF unit routes IP traffic from PPP/Wireless to Ethernet" ::= { routing 1 } --1.3.6.1.4.1.3052.10.2.4.11.1 ethRoutingEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF unit routes IP traffic from Ethernet to PPP/Wireless" ::= { routing 2 } --1.3.6.1.4.1.3052.10.2.4.11.2 ethRoutingNATEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF unit applies NAT on routed IP frames egressing the unit on its PPP interface" ::= { routing 3 } --1.3.6.1.4.1.3052.10.2.4.11.3 routingInterface OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "When Ethernet routing is enabled (routing.1), this is the Ethernet interface to which IP frames received on PPP are routed" ::= { routing 4 } --1.3.6.1.4.1.3052.10.2.4.11.4 eth2WanRoutingEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Make ETH2 operate as a WAN port to route outbound traffic arriving on ETH1." ::= { routing 5 } --1.3.6.1.4.1.3052.10.2.4.11.5 -- IP Restrictions ipRestrictionTable OBJECT-TYPE SYNTAX SEQUENCE OF IPRestrictionConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of IP restrictions" ::= { ipRestriction 1 } --1.3.6.1.4.1.3052.10.2.4.12.1.1 ipRestrictionEntry OBJECT-TYPE SYNTAX IPRestrictionConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of IP restrictions" INDEX { ipRestrictionIndex } ::= { ipRestrictionTable 1 } --1.3.6.1.4.1.3052.10.2.4.12.1.1 ipRestrictionIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of IP restrictions" ::= { ipRestrictionEntry 1 } --1.3.6.1.4.1.3052.10.2.4.12.1.1.1.1 ipRestrictionEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this IP restriction" ::= { ipRestrictionEntry 2 } --1.3.6.1.4.1.3052.10.2.4.12.1.1.1.2 ipRestrictionMask OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "IP restriction mask" ::= { ipRestrictionEntry 3 } --1.3.6.1.4.1.3052.10.2.4.12.1.1.1.3 -- RTS rtsFileTable OBJECT-TYPE SYNTAX SEQUENCE OF RTSFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of RTS files" ::= { rts 1 } --1.3.6.1.4.1.3052.10.2.4.13.1 rtsFileEntry OBJECT-TYPE SYNTAX RTSFileConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of RTS files" INDEX { rtsFileIndex } ::= { rtsFileTable 1 } --1.3.6.1.4.1.3052.10.2.4.13.1 rtsFileIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of RTS files" ::= { rtsFileEntry 1 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.1 rtsFileMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "RTS mode (OFF,LISTEN,PUSH) for FILEx" ::= { rtsFileEntry 2 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.2 rtsFileShowAnswer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Show answer string upon RTS connect for FILEx" ::= { rtsFileEntry 3 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.3 rtsFileReqXON OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF require XON to start flow for FILEx" ::= { rtsFileEntry 4 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.4 rtsFileTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Idle connection close timer (0 means no timeout) for FILEx" ::= { rtsFileEntry 5 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.5 rtsFileEmptyClose OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF close the socket when FILEx is empty" ::= { rtsFileEntry 6 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.6 rtsFilePushHost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Host to which FILEx should be pushed via RTS" ::= { rtsFileEntry 7 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.7 rtsFilePushPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port to which FILEx should be pushed via RTS" ::= { rtsFileEntry 8 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.8 rtsFilePushRetryTimer OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Retry timer (seconds) for retrying failed RTS push connect attempts" ::= { rtsFileEntry 9 } --1.3.6.1.4.1.3052.10.2.4.13.1.1.9 -- RTS Alarms rtsAlarmsMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "RTS mode (OFF,LISTEN,PUSH) for alarms file" ::= { rtsAlarms 1 } --1.3.6.1.4.1.3052.10.2.4.13.2.1 rtsAlarmsShowAnswer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Show answer string upon RTS connect for alarms file" ::= { rtsAlarms 2 } --1.3.6.1.4.1.3052.10.2.4.13.2.2 rtsAlarmsReqXON OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF require XON to start flow for alarms file" ::= { rtsAlarms 3 } --1.3.6.1.4.1.3052.10.2.4.13.2.3 rtsAlarmsTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Idle connection close timer (0 means no timeout) for alarms file" ::= { rtsAlarms 4 } --1.3.6.1.4.1.3052.10.2.4.13.2.4 rtsAlarmsEmptyClose OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF close the socket when this file is empty for alarms file" ::= { rtsAlarms 5 } --1.3.6.1.4.1.3052.10.2.4.13.2.5 rtsAlarmsPushHost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Host to which alarms file should be pushed via RTS" ::= { rtsAlarms 6 } --1.3.6.1.4.1.3052.10.2.4.13.2.6 rtsAlarmsPushPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port to which alarms file should be pushed via RTS" ::= { rtsAlarms 7 } --1.3.6.1.4.1.3052.10.2.4.13.2.7 rtsAlarmsPushRetryTimer OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Retry timer (seconds) for retrying failed RTS push connect attempts" ::= { rtsAlarms 8 } --1.3.6.1.4.1.3052.10.2.4.13.2.8 -- Traps trapIncludeDateTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include date and time in stock trap message" ::= { trapInclude 1 } --1.3.6.1.4.1.3052.10.2.4.14.1.1 trapIncludeSiteName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include site name in stock trap message" ::= { trapInclude 2 } --1.3.6.1.4.1.3052.10.2.4.14.1.2 trapIncludeSensorID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include sensor ID in stock trap message" ::= { trapInclude 3 } --1.3.6.1.4.1.3052.10.2.4.14.1.3 trapIncludeUDName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include user defined name in stock trap message" ::= { trapInclude 4 } --1.3.6.1.4.1.3052.10.2.4.14.1.4 trapIncludeUDState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include user defined state in stock trap message" ::= { trapInclude 5 } --1.3.6.1.4.1.3052.10.2.4.14.1.5 trapIncludeSourceAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF include source IP address in stock trap message" ::= { trapInclude 6 } --1.3.6.1.4.1.3052.10.2.4.14.1.6 trapAuthFailEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable trap sent upon SNMP authentication failure" ::= { trap 2 } --1.3.6.1.4.1.3052.10.2.4.14.2 -- Route testing routeTestEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable route testing" ::= { routeTest 1 } --1.3.6.1.4.1.3052.10.2.4.15.1 routeTestPeriod OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "The period which a route is considered valid" ::= { routeTest 2 } --1.3.6.1.4.1.3052.10.2.4.15.2 routeTestAddressTable OBJECT-TYPE SYNTAX SEQUENCE OF RouteTestConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of route testing addresses" ::= { routeTest 3 } --1.3.6.1.4.1.3052.10.2.4.15.3 routeTestAddressEntry OBJECT-TYPE SYNTAX RouteTestConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of RTS files" INDEX { routeTestAddressIndex } ::= { routeTestAddressTable 1 } --1.3.6.1.4.1.3052.10.2.4.15.3.1 routeTestAddressIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of RTS files" ::= { routeTestAddressEntry 1 } --1.3.6.1.4.1.3052.10.2.4.15.3.1.1 routeTestAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Address to ping to see if the route to it is valid" ::= { routeTestAddressEntry 2 } --1.3.6.1.4.1.3052.10.2.4.15.3.1.2 -- Wireless wirelessMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless mode (OFF,PERMANENT-EDGE)" ::= { wireless 1 } --1.3.6.1.4.1.3052.10.2.4.16.1 wirelessAPN OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless access point name" ::= { wireless 2 } --1.3.6.1.4.1.3052.10.2.4.16.2 wirelessIdleTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless idle timeout" ::= { wireless 3 } --1.3.6.1.4.1.3052.10.2.4.16.3 wirelessDRE OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Default route enable for wireless network interface. When this is ON, the wireless link, if up, becomes the default route, overriding the default route setting (defaultRouter object). When OFF, the default route setting controls the default route and the wireless link does not become the default route." ::= { wireless 9 } --1.3.6.1.4.1.3052.10.2.4.16.9 wirelessPPPUsername OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Username for PPP-based wireless modem connections." ::= { wireless 10 } --1.3.6.1.4.1.3052.10.2.4.16.10 wirelessFirewall OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable wireless modem firewall." ::= { wireless 11 } --1.3.6.1.4.1.3052.10.2.4.16.11 wirelessKeepaliveThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Minutes of no RX activity before sending keep-alive." ::= { wireless 12 } --1.3.6.1.4.1.3052.10.2.4.16.12 wirelessPPPDebug OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable wireless modem PPP debug." ::= { wireless 13 } --1.3.6.1.4.1.3052.10.2.4.16.13 wirelessConnEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable wireless modem connectivity check." ::= { wirelessConnectivity 1 } --1.3.6.1.4.1.3052.10.2.4.16.20.1 wirelessConnCheckInterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless connectivity check interval in minutes." ::= { wirelessConnectivity 2 } --1.3.6.1.4.1.3052.10.2.4.16.20.2 wirelessConnFailThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless connectivity fail threshold." ::= { wirelessConnectivity 3 } --1.3.6.1.4.1.3052.10.2.4.16.20.3 wirelessConnIP1 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless connectivity check IP address 1." ::= { wirelessConnectivity 10 } --1.3.6.1.4.1.3052.10.2.4.16.20.10 wirelessConnIP2 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Wireless connectivity check IP address 2." ::= { wirelessConnectivity 11 } --1.3.6.1.4.1.3052.10.2.4.16.20.11 -- Email emailServer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SMTP server to which the unit sends email" ::= { email 1 } --1.3.6.1.4.1.3052.10.2.4.17.1 emailDomain OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Domain to use in recipient address" ::= { email 2 } --1.3.6.1.4.1.3052.10.2.4.17.2 emailAuthEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable SMTP authentication" ::= { email 3 } --1.3.6.1.4.1.3052.10.2.4.17.3 -- Advanced network config arpFilter OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "ARP filter code" ::= { netAdvanced 1 } --1.3.6.1.4.1.3052.10.2.4.18.1 -- Web interface webEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF for the web interface" ::= { web 1 } --1.3.6.1.4.1.3052.10.2.4.19.1 webPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port on which web interface listens" ::= { web 2 } --1.3.6.1.4.1.3052.10.2.4.19.2 webTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Web interface session timeout (seconds)" ::= { web 3 } --1.3.6.1.4.1.3052.10.2.4.19.3 -- XML Proxy wxpEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Globally enables/disables the XML Proxy feature. This feature is not available in the STD software build." ::= { webXMLProxy 1 } --1.3.6.1.4.1.3052.10.2.4.19.4.1 wxpDeviceTable OBJECT-TYPE SYNTAX SEQUENCE OF WebXMLProxyDeviceConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of XML Proxy devices." ::= { webXMLProxy 2 } --1.3.6.1.4.1.3052.10.2.4.19.4.2 wxpDeviceEntry OBJECT-TYPE SYNTAX WebXMLProxyDeviceConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of XML Proxy devices." INDEX { wxpDeviceIndex } ::= { wxpDeviceTable 1 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1 wxpDeviceIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of XML Proxy devices." ::= { wxpDeviceEntry 1 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.1 wxpDeviceEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enables/disables this particular XML device configuration." ::= { wxpDeviceEntry 2 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.2 wxpDeviceIPAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IP address for device." ::= { wxpDeviceEntry 3 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.3 wxpDevicePort OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port on which to connect via HTTP to fetch the XML file." ::= { wxpDeviceEntry 4 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.4 wxpDeviceRemoteFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Path and name of the XML file on the remote device. E.g., 'xml/telemetry.xml' if the URL for the XML is 'http:///xml/telemetry.xml'." ::= { wxpDeviceEntry 5 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.5 wxpDeviceLocalFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of file in which the remote file content will be cached on the unit. E.g., 'alpha-telemetry.xml' if the URL for the unit-cached XML is intended to be 'http:///xmlproxy/alpha-telemetry.xml'." ::= { wxpDeviceEntry 6 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.6 wxpDeviceTimeout OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS read-write STATUS current DESCRIPTION "How long in seconds to wait for the device to serve the remote file before cancelling the fetch operation." ::= { wxpDeviceEntry 7 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.7 wxpDeviceTimestamp OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Timestamp of last successful XML file fetch/cache operation. If blank then either the device is not configured or there was a fetch error. If not blank, but not updating, then this indicates that the fetch succeeded at one point but then encountered an error." ::= { wxpDeviceEntry 8 } --1.3.6.1.4.1.3052.10.2.4.19.4.2.1.8 -- Ethernet Expansion ethExpanIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IPv4 address of the unit reachable by nodes on the network interface consisting of the Ethernet Expansion Card(s). If this is default (0.0.0.0), then each card will still convey Ethernet traffic (acting as Ethernet switch) among its nodes but those nodes will not be able to communicate with the unit." ::= { ethExpan 1 } --1.3.6.1.4.1.3052.10.2.4.20.1 ethExpanMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IPv4 subnet mask for the Ethernet Expansion network interface." ::= { ethExpan 2 } --1.3.6.1.4.1.3052.10.2.4.20.2 ethExpanCardTable OBJECT-TYPE SYNTAX SEQUENCE OF EthernetExpansionCardConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Ethernet Expansion cards" ::= { ethExpan 3 } --1.3.6.1.4.1.3052.10.2.4.20.3 ethExpanCardEntry OBJECT-TYPE SYNTAX EthernetExpansionCardConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of Ethernet Expansion cards" INDEX { ethExpanCardIndex } ::= { ethExpanCardTable 1 } --1.3.6.1.4.1.3052.10.2.4.20.3.1 ethExpanCardIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of Ethernet Expansion cards" ::= { ethExpanCardEntry 1 } --1.3.6.1.4.1.3052.10.2.4.20.3.1.1 ethExpanCardMAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "MAC address for each Ethernet Expansion Card that is bridged together to form the Ethernet Expansion network interface." ::= { ethExpanCardEntry 2 } --1.3.6.1.4.1.3052.10.2.4.20.3.1.2 ethExpanDHCPStartIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Starting IP address for serving DHCP addresses on the Ethernet Expansion network interface. If this is default (0.0.0.0) then the unit will not run DHCP to serve addresses." ::= { ethExpanDHCP 1 } --1.3.6.1.4.1.3052.10.2.4.20.6.1 ethExpanDHCPLeaseTime OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Lease time for Ethernet Expansion DHCP clients in minutes." ::= { ethExpanDHCP 2 } --1.3.6.1.4.1.3052.10.2.4.20.6.2 -- IPv6 ipv6DefaultRouter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The IPv6 default router in use." ::= { ipv6 1 } --1.3.6.1.4.1.3052.10.2.4.21.1 -- CPE table cpeTable OBJECT-TYPE SYNTAX SEQUENCE OF CPEConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of CPEs" ::= { cpe 1 } --1.3.6.1.4.1.3052.10.2.4.22.1 cpeEntry OBJECT-TYPE SYNTAX CPEConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of CPEs" INDEX { cpeIndex } ::= { cpeTable 1 } --1.3.6.1.4.1.3052.10.2.4.22.1.1 cpeIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of CPEs" ::= { cpeEntry 1 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.1 cpeHost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "CPE host (IP address or DNS name)" ::= { cpeEntry 2 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.2 cpeName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "CPE name, informational only" ::= { cpeEntry 3 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.3 cpeDescription OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "CPE description, informational only" ::= { cpeEntry 4 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.4 cpeKeepalive OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of seconds between each successful ping request." ::= { cpeEntry 5 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.5 cpeThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of unsuccessful pings that triggers the CPE event." ::= { cpeEntry 6 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.6 cpeEventReminderInterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "CPE event reminder interval (minutes)." ::= { cpeEntry 7 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.7 cpeKeepaliveTicks OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "CPE ping period in 16ths of a second (nonzero overrides keepalive)." ::= { cpeEntry 20 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.20 cpePingSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of bytes in CPE ping payload" ::= { cpeEntry 21 } --1.3.6.1.4.1.3052.10.2.4.22.1.11 cpeInfoReset OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Set any number to reset CPE ping stats." ::= { cpeEntry 30 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.30 cpeInfoNumReq OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of requests transmitted." ::= { cpeEntry 31 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.31 cpeInfoNumGoodResp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of non-corrupt responses." ::= { cpeEntry 32 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.32 cpeInfoNumBadResp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of corrupt responses." ::= { cpeEntry 33 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.33 cpeInfoNumLostResp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of requests with no response." ::= { cpeEntry 34 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.34 cpeInfoPercentLoss OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Percent loss (missing responses / total requests)." ::= { cpeEntry 35 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.35 cpeInfoPercentBad OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Percent corrupt (corrupt responses / total requests)." ::= { cpeEntry 36 } --1.3.6.1.4.1.3052.10.2.4.22.1.1.36 -- DNP3 dnp3Mode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 operating mode." ::= { dnp3General 1 } --1.3.6.1.4.1.3052.10.2.4.23.1.1 dnp3SelfAddressEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 self-address enabled." ::= { dnp3General 2 } --1.3.6.1.4.1.3052.10.2.4.23.1.2 dnp3KeepaliveTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Keepalive timeout in seconds." ::= { dnp3General 3 } --1.3.6.1.4.1.3052.10.2.4.23.1.3 dnp3MaxRXFragmentSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum size of a received fragment in bytes." ::= { dnp3General 4 } --1.3.6.1.4.1.3052.10.2.4.23.1.4 dnp3MaxTXFragmentSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum size of a transmitted fragment in bytes." ::= { dnp3General 5 } --1.3.6.1.4.1.3052.10.2.4.23.1.5 dnp3UnsolResponseEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable unsolicited responses." ::= { dnp3General 6 } --1.3.6.1.4.1.3052.10.2.4.23.1.6 dnp3UnsolResponseTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Unsolicited response confirmation timeout in seconds." ::= { dnp3General 7 } --1.3.6.1.4.1.3052.10.2.4.23.1.7 dnp3UnsolResponseRetries OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Unsolicited response confirmation timeout retries." ::= { dnp3General 8 } --1.3.6.1.4.1.3052.10.2.4.23.1.8 dnp3LogFilter OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Numeric code to describe what gets logged (for support/troubleshooting analysis only)." ::= { dnp3General 9 } --1.3.6.1.4.1.3052.10.2.4.23.1.9 dnp3OutstationTCPPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port on which to listen for connections." ::= { dnp3Outstation 1 } --1.3.6.1.4.1.3052.10.2.4.23.2.1 dnp3OutstationDNP3Address OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 address of the outstation. " ::= { dnp3Outstation 2 } --1.3.6.1.4.1.3052.10.2.4.23.2.2 dnp3OutstationMasterIPAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "IP (v4 or v6) address (non-resolved) of the intended master. Default blank. If non-blank then the outstation drops connections from TCP clients not at this address." ::= { dnp3Outstation 3 } --1.3.6.1.4.1.3052.10.2.4.23.2.3 dnp3OutstationMasterDNP3Address OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 address of the intended master upon connection. Range 0 - 65520, default 65520. If set to 0 - 65519 then the outstation discards DNP3 data link frames not from this address. 65520 is not a valid DNP3 address; if set to 65520 then it means the outstation accepts frames from any address." ::= { dnp3Outstation 4 } --1.3.6.1.4.1.3052.10.2.4.23.2.4 dnp3OutstationUnsolResponseDNP3Address OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 destination address of unsolicited responses. Range 0 - 65520, default 65520. If set to 65520 then it means the outstation addresses data link frames of unsolicited responses to the source address of the last accepted frame received from the master." ::= { dnp3Outstation 5 } --1.3.6.1.4.1.3052.10.2.4.23.2.5 dnp3DuplicateFragmentCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of duplicate fragments received." ::= { dnp3Error 1 } --1.3.6.1.4.1.3052.10.2.4.23.4.1 dnp3CollidingFragmentCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of colliding fragments received." ::= { dnp3Error 2 } --1.3.6.1.4.1.3052.10.2.4.23.4.2 dnp3UnsolResponseCfmFailCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of unsolicited response confirmation failures." ::= { dnp3Error 3 } --1.3.6.1.4.1.3052.10.2.4.23.4.3 dnp3SolCfmFailCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of solicited response confirmation failures." ::= { dnp3Error 4 } --1.3.6.1.4.1.3052.10.2.4.23.4.4 dnp3ObjParseErrorCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of received data object parse errors." ::= { dnp3Error 5 } --1.3.6.1.4.1.3052.10.2.4.23.4.5 dnp3FrameParseErrorCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of received frame parse errors." ::= { dnp3Error 6 } --1.3.6.1.4.1.3052.10.2.4.23.4.6 dnp3DiscardedFrameCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of received frames discarded." ::= { dnp3Error 7 } --1.3.6.1.4.1.3052.10.2.4.23.4.7 dnp3BadBlockCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of received frame blocks with bad CRC." ::= { dnp3Error 8 } --1.3.6.1.4.1.3052.10.2.4.23.4.8 dnp3UnsolResponseRetryCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of retried unsolicited responses." ::= { dnp3Error 9 } --1.3.6.1.4.1.3052.10.2.4.23.4.9 dnp3UnsupportedFrameCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of received frames accepted (good CRC and addressed to the outstation) with an unsupported data link function code." ::= { dnp3Error 10 } --1.3.6.1.4.1.3052.10.2.4.23.4.10 dnp3OutstationCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of running outstation instances." ::= { dnp3Status 1 } --1.3.6.1.4.1.3052.10.2.4.23.5.1 dnp3ConnPeer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Description of the connected peer (the TCP socket endpoint of the master)." ::= { dnp3Status 2 } --1.3.6.1.4.1.3052.10.2.4.23.5.2 dnp3StartTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "When the outstation instance started." ::= { dnp3Status 3 } --1.3.6.1.4.1.3052.10.2.4.23.5.3 dnp3EventAwaitingSolCfmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of events reported and awaiting solicited confirmation; usually 0." ::= { dnp3Status 4 } --1.3.6.1.4.1.3052.10.2.4.23.5.4 dnp3EventAwaitingUnsolCfmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of events reported and awaiting unsolicited confirmation; usually 0." ::= { dnp3Status 5 } --1.3.6.1.4.1.3052.10.2.4.23.5.5 dnp3EventCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of total events buffered (that is, existing, maybe reported, but not confirmed)." ::= { dnp3Status 6 } --1.3.6.1.4.1.3052.10.2.4.23.5.6 dnp3EventClass1Count OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Portion of the total events buffered that are class 1 events." ::= { dnp3Status 7 } --1.3.6.1.4.1.3052.10.2.4.23.5.7 dnp3EventClass2Count OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Portion of the total events buffered that are class 2 events." ::= { dnp3Status 8 } --1.3.6.1.4.1.3052.10.2.4.23.5.8 dnp3EventClass3Count OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Portion of the total events buffered that are class 3 events." ::= { dnp3Status 9 } --1.3.6.1.4.1.3052.10.2.4.23.5.9 dnp3RxFragmentTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Time of the last fragment received." ::= { dnp3Status 10 } --1.3.6.1.4.1.3052.10.2.4.23.5.10 dnp3TxFragmentTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Time of the last fragment transmitted." ::= { dnp3Status 11 } --1.3.6.1.4.1.3052.10.2.4.23.5.11 dnp3TxCachedResponseCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of cached responses transmitted." ::= { dnp3Status 12 } --1.3.6.1.4.1.3052.10.2.4.23.5.12 dnp3TxUnsolResponseCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of unsolicited responses transmitted." ::= { dnp3Status 13 } --1.3.6.1.4.1.3052.10.2.4.23.5.13 dnp3TxSolResponseCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of solicited responses transmitted." ::= { dnp3Status 14 } --1.3.6.1.4.1.3052.10.2.4.23.5.14 dnp3TxFragmentReqCfmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of fragments transmitted that required confirmation." ::= { dnp3Status 15 } --1.3.6.1.4.1.3052.10.2.4.23.5.15 dnp3RxUnsolResponseCfmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of unsolicited response confirmations received." ::= { dnp3Status 16 } --1.3.6.1.4.1.3052.10.2.4.23.5.16 dnp3RxSolResponseCfmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of solicited response confirmations received." ::= { dnp3Status 17 } --1.3.6.1.4.1.3052.10.2.4.23.5.17 dnp3RxFunctionCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of total application function codes received." ::= { dnp3Status 18 } --1.3.6.1.4.1.3052.10.2.4.23.5.18 dnp3RxReadFunctionCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of read application function codes received." ::= { dnp3Status 19 } --1.3.6.1.4.1.3052.10.2.4.23.5.19 dnp3RxWriteFunctionCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of write application function codes received." ::= { dnp3Status 20 } --1.3.6.1.4.1.3052.10.2.4.23.5.20 dnp3RxDirOpFunctionCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of direct operate application function codes received." ::= { dnp3Status 21 } --1.3.6.1.4.1.3052.10.2.4.23.5.21 dnp3RxEnableURCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of enable unsolicited application function codes received." ::= { dnp3Status 22 } --1.3.6.1.4.1.3052.10.2.4.23.5.22 dnp3RxDisableURCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of disabled unsolicited application function codes received." ::= { dnp3Status 23 } --1.3.6.1.4.1.3052.10.2.4.23.5.23 dnp3RxSolObjectCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of data objects received in solicited requests." ::= { dnp3Status 40 } --1.3.6.1.4.1.3052.10.2.4.23.5.40 dnp3TxSolObjectCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of data objects transmitted in solicted responses." ::= { dnp3Status 41 } --1.3.6.1.4.1.3052.10.2.4.23.5.41 dnp3RxFrameTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Time of the last frame received." ::= { dnp3Status 42 } --1.3.6.1.4.1.3052.10.2.4.23.5.42 dnp3TxFrameTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Time of the last frame transmitted." ::= { dnp3Status 43 } --1.3.6.1.4.1.3052.10.2.4.23.5.43 dnp3TxFrameCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of total frames transmitted." ::= { dnp3Status 44 } --1.3.6.1.4.1.3052.10.2.4.23.5.44 dnp3RxAcceptedFrameCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of total frames accepted." ::= { dnp3Status 45 } --1.3.6.1.4.1.3052.10.2.4.23.5.45 dnp3RxSupportedFrameCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Count of total frames accepted with a supported data link function code." ::= { dnp3Status 46 } --1.3.6.1.4.1.3052.10.2.4.23.5.46 --*************************************************************************************** --Modem Section 2.5 --*************************************************************************************** modemFormat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Modem data format (8N1,7E1,7O1,7N1)" ::= { modem 1 } --1.3.6.1.4.1.3052.10.2.5.1 modemInitString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Init string for modem" ::= { modem 2 } --1.3.6.1.4.1.3052.10.2.5.2 modemCallAttempts OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Max mumber of times the modem should try to call out until successful connect" ::= { modem 4 } --1.3.6.1.4.1.3052.10.2.5.4 modemCallDelay OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum delay (seconds) between callouts" ::= { modem 5 } --1.3.6.1.4.1.3052.10.2.5.6 modemCmdTimout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of minutes after which an idle command session via modem is terminated" ::= { modem 6 } --1.3.6.1.4.1.3052.10.2.5.6 modemGoto OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "When a user connects, where that user is routed (command session, passthrough to port 1, passthrough to port 2, etc.)" ::= { modem 7 } --1.3.6.1.4.1.3052.10.2.5.7 modemCLIDEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Calling Line Identification security" ::= { modemClid 1 } --1.3.6.1.4.1.3052.10.2.5.8.1 modemCLIDNumberTable OBJECT-TYPE SYNTAX SEQUENCE OF ModemCLIDNumberConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of authorized callers identified by phone number" ::= { modemClid 2 } --1.3.6.1.4.1.3052.10.2.5.8.2 modemCLIDNumberEntry OBJECT-TYPE SYNTAX ModemCLIDNumberConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of CLID numbers" INDEX { modemCLIDNumberIndex } ::= { modemCLIDNumberTable 1 } --1.3.6.1.4.1.3052.10.2.5.8.2.1 modemCLIDNumberIndex OBJECT-TYPE SYNTAX Integer32 (1..20) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of CLID numbers" ::= { modemCLIDNumberEntry 1 } --1.3.6.1.4.1.3052.10.2.5.8.2.1.1 modemCLIDNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "auhorized CLID number" ::= { modemCLIDNumberEntry 2 } --1.3.6.1.4.1.3052.10.2.5.8.2.1.2 modemTAPInitString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Init string to use for TAP (pager) connections" ::= { modem 9 } --1.3.6.1.4.1.3052.10.2.5.9 modemTAP8N1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: use 8N1 data/parity/stop for TAP connections" ::= { modem 10 } --1.3.6.1.4.1.3052.10.2.5.10 --*************************************************************************************** --Time Section 2.8 --*************************************************************************************** clock OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text string for date and time; e.g. 'SUN 01/02/98 12:34:27'. When setting this object, only the date and time are required; the unit will ignore a specified day of week because it is calculated from the date and time. When this object is included in a notification as a varbind, it represents the time that the triggering event occurred." ::= { time 1 } --1.3.6.1.4.1.3052.10.2.8.1 --*************************************************************************************** --Console Section 2.10 --*************************************************************************************** consoleDuplex OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF characters echoed on telnet command session" ::= { console 1 } --1.3.6.1.4.1.3052.10.2.10.1 consoleTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Minutes of inactivity after which telnet command session is terminated" ::= { console 2 } --1.3.6.1.4.1.3052.10.2.10.2 consoleConfirm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Prompt to confirm certain actions" ::= { console 7 } --1.3.6.1.4.1.3052.10.2.10.7 --*************************************************************************************** --Core Security Section 2.11.1 --*************************************************************************************** scShowPasswordPrompt OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF show password prompt upon login" ::= { secCore 1 } --1.3.6.1.4.1.3052.10.2.11.1.1 scConsoleLoginRequired OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF login required upon connecting via console" ::= { secCore 2 } --1.3.6.1.4.1.3052.10.2.11.1.2 scModemLoginRequired OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF login required upon connecting via modem" ::= { secCore 3 } --1.3.6.1.4.1.3052.10.2.11.1.3 scTelnetLoginRequired OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF login required upon connecting via Telnet" ::= { secCore 4 } --1.3.6.1.4.1.3052.10.2.11.1.4 scTelnetPTLoginRequired OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF login required upon connecting via Telnet to pass- through ports (TCP ports 210x)" ::= { secCore 5 } --1.3.6.1.4.1.3052.10.2.11.1.5 scRTSLoginRequired OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF login required upon connecting to RTS (TCP ports 220x)" ::= { secCore 6 } --1.3.6.1.4.1.3052.10.2.11.1.6 scAuthMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Authentication mode (USERNAME/PW,PW/USERNAME,PASSWORD ONLY)" ::= { secCore 7 } --1.3.6.1.4.1.3052.10.2.11.1.7 scRightsGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The set of aliases used for the 8 available rights levels" ::= { secCore 8 } --1.3.6.1.4.1.3052.10.2.11.1.8 --*************************************************************************************** --User Security Section 2.11.2 --*************************************************************************************** secUserTable OBJECT-TYPE SYNTAX SEQUENCE OF SecUserConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of users" ::= { unitSecurity 2 } --1.3.6.1.4.1.3052.10.2.11.2 secUserEntry OBJECT-TYPE SYNTAX SecUserConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of users" INDEX { secUserIndex } ::= { secUserTable 1 } --1.3.6.1.4.1.3052.10.2.11.2.1 secUserIndex OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of users" ::= { secUserEntry 1 } --1.3.6.1.4.1.3052.10.2.11.2.1.1 secUserEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable user" ::= { secUserEntry 2 } --1.3.6.1.4.1.3052.10.2.11.2.1.2 secUserConnectVia OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Methods by which user is allowed to connect: L=local (console) T=Telnet M=modem F=FTP R=RTS S=SSH " ::= { secUserEntry 5 } --1.3.6.1.4.1.3052.10.2.11.2.1.5 secUserLoginTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The function presented to the user upon login (COMMAND, PASSTHROUGH,MENU)" ::= { secUserEntry 6 } --1.3.6.1.4.1.3052.10.2.11.2.1.6 secUserAccessFile OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The default access file associated with the user" ::= { secUserEntry 7 } --1.3.6.1.4.1.3052.10.2.11.2.1.7 secUserPTEscapeTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The function presented to the user upon escaping pass- through: currently only MENU" ::= { secUserEntry 9 } --1.3.6.1.4.1.3052.10.2.11.2.1.9 secUserPPPType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The kind of PPP access allowed to this user cannot connect via PPP (NONE), can connect but only to the unit (LOCAL), or can connect and route to Ethernet (ROUTING)" ::= { secUserEntry 10 } --1.3.6.1.4.1.3052.10.2.11.2.1.10 secUserRights OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The rights level granted to this user" ::= { secUserEntry 11 } --1.3.6.1.4.1.3052.10.2.11.2.1.11 secUserEventsReadAccess OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DENY/ALLOW user to read the events/alarms file" ::= { secUserEntry 13 } --1.3.6.1.4.1.3052.10.2.11.2.1.13 secUserAuditReadAccess OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DENY/ALLOW user to read the audit log" ::= { secUserEntry 14 } --1.3.6.1.4.1.3052.10.2.11.2.1.14 secUserEventsWriteAccess OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DENY/ALLOW user to delete the events file" ::= { secUserEntry 16 } --1.3.6.1.4.1.3052.10.2.11.2.1.16 secUserAuditWriteAccess OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DENY/ALLOW user to write to the audit log" ::= { secUserEntry 17 } --1.3.6.1.4.1.3052.10.2.11.2.1.17 secUserExpiration OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Expiration date/time of this user" ::= { secUserEntry 18 } --1.3.6.1.4.1.3052.10.2.11.2.1.18 secUserCallbackNumber1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Number slot 1 the unit calls for dialback" ::= { secUserEntry 19 } --1.3.6.1.4.1.3052.10.2.11.2.1.19 secUserCallbackNumber2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Number slot 2 the unit calls for dialback" ::= { secUserEntry 20 } --1.3.6.1.4.1.3052.10.2.11.2.1.20 secUserCallbackNumber3 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Number slot 3 the unit calls for dialback" ::= { secUserEntry 21 } --1.3.6.1.4.1.3052.10.2.11.2.1.21 secUserChallengeTelnetMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Telnet challenge mode: when user logs in via telnet, unit allows access (OFF), presents a challenge (CHALLENGE), or unit sends a one-time-password (SEND PASSWORD) to a destination configured by secUserChallengeTelnetSendTo" ::= { secUserEntry 22 } --1.3.6.1.4.1.3052.10.2.11.2.1.22 secUserChallengeModemMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Modem challenge mode: when user logs in via modem, unit allows access (OFF), presents a challenge (CHALLENGE), sends a one-time-password (SEND PASSWORD) to a destination configured by secUserChallengeTelnetSendTo, or dials a number (CALLBACK) configured with secUserCallbackNumberx" ::= { secUserEntry 23 } --1.3.6.1.4.1.3052.10.2.11.2.1.23 secUserChallengeConsoleMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Console challenge mode: when user logs in via console, unit allows access (OFF), or presents a challenge (CHALLENGE)" ::= { secUserEntry 24 } --1.3.6.1.4.1.3052.10.2.11.2.1.24 secUserChallengeTelnetSendTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Email action used as the destination address for one-time- password when a user logs in with a challenge mode of SEND PASSWORD" ::= { secUserEntry 25 } --1.3.6.1.4.1.3052.10.2.11.2.1.25 secUserChallengeModemSendTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Modem action used as the destination phone number for one- time-password when a user logs in with a challenge mode of SEND PASSWORD" ::= { secUserEntry 26 } --1.3.6.1.4.1.3052.10.2.11.2.1.26 secUserChallengeExpiration OBJECT-TYPE SYNTAX Integer32 (0..180) MAX-ACCESS read-write STATUS current DESCRIPTION "Time (in minutes) after which a one-time-password is sent that it can be used to log in" ::= { secUserEntry 27 } --1.3.6.1.4.1.3052.10.2.11.2.1.27 --*************************************************************************************** --Factory Security Section 2.11.3 --*************************************************************************************** sfEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable factory access" ::= { secFactory 1 } --1.3.6.1.4.1.3052.10.2.11.3.1 sfSecret OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Secret used for factory access" ::= { secFactory 2 } --1.3.6.1.4.1.3052.10.2.11.3.2 --*************************************************************************************** --SSH Security Section 2.11.3 --*************************************************************************************** --*************************************************************************************** --Event Section 2.12 --*************************************************************************************** --*************************************************************************************** --Event Core Section 2.12.1 --*************************************************************************************** evClassNameTable OBJECT-TYPE SYNTAX SEQUENCE OF EventClassConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of classes" ::= { evCore 1 } --1.3.6.1.4.1.3052.10.2.12.1.1 evClassNameEntry OBJECT-TYPE SYNTAX EventClassConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of classes" INDEX { evClassNameIndex } ::= { evClassNameTable 1 } --1.3.6.1.4.1.3052.10.2.12.1.1.1 evClassNameIndex OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of classes" ::= { evClassNameEntry 1 } --1.3.6.1.4.1.3052.10.2.12.1.1.1.1 evClassName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class name for this slot" ::= { evClassNameEntry 2 } --1.3.6.1.4.1.3052.10.2.12.1.1.1.2 evReminderInterval OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Interval (minutes) between EventSensor reminder events" ::= { evCore 2 } --1.3.6.1.4.1.3052.10.2.12.1.2 evLogEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable event log" ::= { evLog 1 } --1.3.6.1.4.1.3052.10.2.12.1.3.1 evLogStoreAlarm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF store data alarms in event log" ::= { evLog 2 } --1.3.6.1.4.1.3052.10.2.12.1.3.2 evLogMaxSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "max size (in KB) of event log" ::= { evLog 3 } --1.3.6.1.4.1.3052.10.2.12.1.3.3 evLogStoreSensor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF store EventSensor events in event log" ::= { evLog 4 } --1.3.6.1.4.1.3052.10.2.12.1.3.4 evLogTimeStampAlarms OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF put timestamps on event log entries" ::= { evLog 5 } --1.3.6.1.4.1.3052.10.2.12.1.3.5 evLogPrependName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF prepend data event name to data alarm records in event log" ::= { evLog 6 } --1.3.6.1.4.1.3052.10.2.12.1.3.6 evMgmtReprocess OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Number of sensors that have generated events since reset. Write this to reprocess each sensor's last generated event since reset. The value to write determines what kind of events should be reprocessed: 'all': all sensor events 'cc': cc events 'temperature': temperature events 'humidity': humidity events 'analog': analog input events" ::= { evMgmt 3 } --1.3.6.1.4.1.3052.10.2.12.1.4.3 --*************************************************************************************** --Data event section 2.12.2 --*************************************************************************************** evdExitOnTrue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: Data alarm evaluator stops checking record against alarm equations when it finds an equation that matches" ::= { evdCore 1 } --1.3.6.1.4.1.3052.10.2.12.2.1.1.1 evdFilterAction OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "What happens to a record that matches an equation: REJECT/ACCEPT" ::= { evdCore 2 } --1.3.6.1.4.1.3052.10.2.12.2.1.1.2 evdWildCardChar OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Character (in decimal ASCII code format) used to indicate wildcards in data alarm equation" ::= { evdCore 3 } --1.3.6.1.4.1.3052.10.2.12.2.1.1.3 evdTable OBJECT-TYPE SYNTAX SEQUENCE OF DataEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of data events" ::= { evData 2 } --1.3.6.1.4.1.3052.10.2.12.2.2 evdEntry OBJECT-TYPE SYNTAX DataEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of data events" INDEX { evdIndex } ::= { evdTable 1 } --1.3.6.1.4.1.3052.10.2.12.2.2.1 evdIndex OBJECT-TYPE SYNTAX Integer32 (1..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of data events" ::= { evdEntry 1 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.1 evdEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this data event" ::= { evdEntry 2 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.2 evdName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this data event" ::= { evdEntry 3 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.3 evdEquation OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Equation for this data event" ::= { evdEntry 4 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.4 evdThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of equation matches that must happen to trigger this data event" ::= { evdEntry 5 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.5 evdAutoClear OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF this data alarm is automatically cleared (re-armed) upon reaching the threshold number of matches" ::= { evdEntry 6 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.6 evdClearInterval OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Interval at which this alarm is automatically cleared (no bearing with evdAutoClear)" ::= { evdEntry 7 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.7 evdClearTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Tie of day (HH:MM) at which this data alarm is cleared (no bearing with evdAutoClear)" ::= { evdEntry 8 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.8 evdActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for this data event" ::= { evdEntry 9 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.9 evdClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for this data event" ::= { evdEntry 10 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.10 evdTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for this event" ::= { evdEntry 11 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.11 evdMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ALARM/FILTER: what is happens when this data event triggers: either generate actions (mode=ALARM) )or ACCEPT/REJECT (via evdFilterAction) the record (mode=FILTER)" ::= { evdEntry 12 } --1.3.6.1.4.1.3052.10.2.12.2.2.1.12 evdFieldTable OBJECT-TYPE SYNTAX SEQUENCE OF DataEventFieldConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of data event fields" ::= { evData 3 } --1.3.6.1.4.1.3052.10.2.12.2.3 evdFieldEntry OBJECT-TYPE SYNTAX DataEventFieldConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of data event fields" INDEX { evdFieldIndex } ::= { evdFieldTable 1 } --1.3.6.1.4.1.3052.10.2.12.2.3.1 evdFieldIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of data event fields" ::= { evdFieldEntry 1 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.1 evdFieldStart OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Start position (1-based) for this data event field" ::= { evdFieldEntry 2 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.2 evdFieldLength OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of characters this data event field occupies" ::= { evdFieldEntry 3 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.3 evdFieldName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Start position (1-based) for this data event field" ::= { evdFieldEntry 4 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.4 evdFieldLine OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Line number (1-based, for multiline records) for this data event field" ::= { evdFieldEntry 5 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.5 evdFieldType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Alpha/Numeric type for this data event field" ::= { evdFieldEntry 6 } --1.3.6.1.4.1.3052.10.2.12.2.3.1.6 evdMacroTable OBJECT-TYPE SYNTAX SEQUENCE OF DataEventMacroConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of data event macros" ::= { evData 4 } --1.3.6.1.4.1.3052.10.2.12.2.4 evdMacroEntry OBJECT-TYPE SYNTAX DataEventMacroConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of data event macros" INDEX { evdMacroIndex } ::= { evdMacroTable 1 } --1.3.6.1.4.1.3052.10.2.12.2.4.1 evdMacroIndex OBJECT-TYPE SYNTAX Integer32 (1..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of data event macros" ::= { evdMacroEntry 1 } --1.3.6.1.4.1.3052.10.2.12.2.4.1.1 evdMacroName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of this macro for use in data event equations" ::= { evdMacroEntry 2 } --1.3.6.1.4.1.3052.10.2.12.2.4.1.2 evdMacroEquation OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Equation for this data event macro" ::= { evdMacroEntry 3 } --1.3.6.1.4.1.3052.10.2.12.2.4.1.3 --*************************************************************************************** --No data event 1 Section 2.12.3 --*************************************************************************************** evNoData1Enable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this no data event" ::= { evNoData1 1 } --1.3.6.1.4.1.3052.10.2.12.3.1 evNoData1Actions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for this no data event" ::= { evNoData1 2 } --1.3.6.1.4.1.3052.10.2.12.3.2 evNoData1Message OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for this no data event" ::= { evNoData1 3 } --1.3.6.1.4.1.3052.10.2.12.3.3 evNoData1TrapNum OBJECT-TYPE SYNTAX Integer32 (505..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for this no data event" ::= { evNoData1 4 } --1.3.6.1.4.1.3052.10.2.12.3.4 evNoData1Class OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for this no data event" ::= { evNoData1 5 } --1.3.6.1.4.1.3052.10.2.12.3.5 evNoData1Sched1Begin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 1 begin time (HH:MM) for this no data event" ::= { evNoData1 6 } --1.3.6.1.4.1.3052.10.2.12.3.6 evNoData1Sched1End OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 1 end time (HH:MM) for this no data event" ::= { evNoData1 7 } --1.3.6.1.4.1.3052.10.2.12.3.7 evNoData1Sched1Duration OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Duration (minutes) for schedule 1 of this no data event" ::= { evNoData1 8 } --1.3.6.1.4.1.3052.10.2.12.3.8 evNoData1Sched2Begin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 2 begin time (HH:MM) for this no data event" ::= { evNoData1 9 } --1.3.6.1.4.1.3052.10.2.12.3.9 evNoData1Sched2End OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 2 end time (HH:MM) for this no data event" ::= { evNoData1 10 } --1.3.6.1.4.1.3052.10.2.12.3.10 evNoData1Sched2Duration OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Duration (minutes) for schedule 2 of this no data event" ::= { evNoData1 11 } --1.3.6.1.4.1.3052.10.2.12.3.11 evNoData1PortEnableTable OBJECT-TYPE SYNTAX SEQUENCE OF NoDataEvent1PortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of no data event 1 port enables" ::= { evNoData1 12 } --1.3.6.1.4.1.3052.10.2.12.3.12 evNoData1PortEnableEntry OBJECT-TYPE SYNTAX NoDataEvent1PortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of no data event 1 port enables" INDEX { evNoData1PortEnableIndex } ::= { evNoData1PortEnableTable 1 } --1.3.6.1.4.1.3052.10.2.12.3.12.1 evNoData1PortEnableIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of no data event 1 port enables" ::= { evNoData1PortEnableEntry 1 } --1.3.6.1.4.1.3052.10.2.12.3.12.1.1 evNoData1PortEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: no data event 1 observes this port" ::= { evNoData1PortEnableEntry 2 } --1.3.6.1.4.1.3052.10.2.12.3.12.1.2 evNoData1Exclusions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Exclusions (space-separated MM/DD-formatted dates) for this no data event" ::= { evNoData1 13 } --1.3.6.1.4.1.3052.10.2.12.3.13 evNoData1Days OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Days of the week on which this no event is active" ::= { evNoData1 14 } --1.3.6.1.4.1.3052.10.2.12.3.14 --*************************************************************************************** --No data event 2 Section 2.12.4 --*************************************************************************************** evNoData2Enable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this no data event" ::= { evNoData2 1 } --1.3.6.1.4.1.3052.10.2.12.4.1 evNoData2Actions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for this no data event" ::= { evNoData2 2 } --1.3.6.1.4.1.3052.10.2.12.4.2 evNoData2Message OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for this no data event" ::= { evNoData2 3 } --1.3.6.1.4.1.3052.10.2.12.4.3 evNoData2TrapNum OBJECT-TYPE SYNTAX Integer32 (505..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for this no data event" ::= { evNoData2 4 } --1.3.6.1.4.1.3052.10.2.12.4.4 evNoData2Class OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for this no data event" ::= { evNoData2 5 } --1.3.6.1.4.1.3052.10.2.12.4.5 evNoData2Sched1Begin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 1 begin time (HH:MM) for this no data event" ::= { evNoData2 6 } --1.3.6.1.4.1.3052.10.2.12.4.6 evNoData2Sched1End OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 1 end time (HH:MM) for this no data event" ::= { evNoData2 7 } --1.3.6.1.4.1.3052.10.2.12.4.7 evNoData2Sched1Duration OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Duration (minutes) for schedule 1 of this no data event" ::= { evNoData2 8 } --1.3.6.1.4.1.3052.10.2.12.4.8 evNoData2Sched2Begin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 2 begin time (HH:MM) for this no data event" ::= { evNoData2 9 } --1.3.6.1.4.1.3052.10.2.12.4.9 evNoData2Sched2End OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule 2 end time (HH:MM) for this no data event" ::= { evNoData2 10 } --1.3.6.1.4.1.3052.10.2.12.4.10 evNoData2Sched2Duration OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Duration (minutes) for schedule 2 of this no data event" ::= { evNoData2 11 } --1.3.6.1.4.1.3052.10.2.12.4.11 evNoData2PortEnableTable OBJECT-TYPE SYNTAX SEQUENCE OF NoDataEvent2PortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of no data event 2 port enables" ::= { evNoData2 12 } --1.3.6.1.4.1.3052.10.2.12.4.12 evNoData2PortEnableEntry OBJECT-TYPE SYNTAX NoDataEvent2PortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of no data event 2 port enables" INDEX { evNoData2PortEnableIndex } ::= { evNoData2PortEnableTable 1 } --1.3.6.1.4.1.3052.10.2.12.4.12.1 evNoData2PortEnableIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of no data event 2 port enables" ::= { evNoData2PortEnableEntry 1 } --1.3.6.1.4.1.3052.10.2.12.4.12.1.1 evNoData2PortEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: no data event 2 observes this port" ::= { evNoData2PortEnableEntry 2 } --1.3.6.1.4.1.3052.10.2.12.4.12.1.2 evNoData2Exclusions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Exclusions (space-separated MM/DD-formatted dates) for this no data event" ::= { evNoData2 13 } --1.3.6.1.4.1.3052.10.2.12.4.13 evNoData2Days OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Days of the week on which this no event is active" ::= { evNoData2 14 } --1.3.6.1.4.1.3052.10.2.12.4.14 --*************************************************************************************** --Scheduled Event 1 Section 2.12.5 --*************************************************************************************** evSched1Enable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this scheduled event" ::= { evSched1 1 } --1.3.6.1.4.1.3052.10.2.12.5.1 evSched1Actions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for this scheduled event" ::= { evSched1 2 } --1.3.6.1.4.1.3052.10.2.12.5.2 evSched1Message OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for this scheduled event" ::= { evSched1 3 } --1.3.6.1.4.1.3052.10.2.12.5.3 evSched1TrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for this scheduled event" ::= { evSched1 4 } --1.3.6.1.4.1.3052.10.2.12.5.4 evSched1Class OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for this scheduled event" ::= { evSched1 5 } --1.3.6.1.4.1.3052.10.2.12.5.5 evSched1Sunday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Sunday (HH:MM) when this scheduled event triggers" ::= { evSched1 6 } --1.3.6.1.4.1.3052.10.2.12.5.6 evSched1Monday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Monday (HH:MM) when this scheduled event triggers" ::= { evSched1 7 } --1.3.6.1.4.1.3052.10.2.12.5.7 evSched1Tuesday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Tuesday (HH:MM) when this scheduled event triggers" ::= { evSched1 8 } --1.3.6.1.4.1.3052.10.2.12.5.8 evSched1Wednesday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Wednesday (HH:MM) when this scheduled event triggers" ::= { evSched1 9 } --1.3.6.1.4.1.3052.10.2.12.5.9 evSched1Thursday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Thursday (HH:MM) when this scheduled event triggers" ::= { evSched1 10 } --1.3.6.1.4.1.3052.10.2.12.5.10 evSched1Friday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Friday (HH:MM) when this scheduled event triggers" ::= { evSched1 11 } --1.3.6.1.4.1.3052.10.2.12.5.11 evSched1Saturday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Saturday (HH:MM) when this scheduled event triggers" ::= { evSched1 12 } --1.3.6.1.4.1.3052.10.2.12.5.12 evSched1Exclusions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Exclusions (space-separated MM/DD-formatted dates) for this scheduled event" ::= { evSched1 13 } --1.3.6.1.4.1.3052.10.2.12.5.13 --*************************************************************************************** --Scheduled Event 2 Section 2.12.6 --*************************************************************************************** evSched2Enable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this scheduled event" ::= { evSched2 1 } --1.3.6.1.4.1.3052.10.2.12.6.1 evSched2Actions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for this scheduled event" ::= { evSched2 2 } --1.3.6.1.4.1.3052.10.2.12.6.2 evSched2Message OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for this scheduled event" ::= { evSched2 3 } --1.3.6.1.4.1.3052.10.2.12.6.3 evSched2TrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for this scheduled event" ::= { evSched2 4 } --1.3.6.1.4.1.3052.10.2.12.6.4 evSched2Class OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for this scheduled event" ::= { evSched2 5 } --1.3.6.1.4.1.3052.10.2.12.6.5 evSched2Sunday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Sunday (HH:MM) when this scheduled event triggers" ::= { evSched2 6 } --1.3.6.1.4.1.3052.10.2.12.6.6 evSched2Monday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Monday (HH:MM) when this scheduled event triggers" ::= { evSched2 7 } --1.3.6.1.4.1.3052.10.2.12.6.7 evSched2Tuesday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Tuesday (HH:MM) when this scheduled event triggers" ::= { evSched2 8 } --1.3.6.1.4.1.3052.10.2.12.6.8 evSched2Wednesday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Wednesday (HH:MM) when this scheduled event triggers" ::= { evSched2 9 } --1.3.6.1.4.1.3052.10.2.12.6.9 evSched2Thursday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Thursday (HH:MM) when this scheduled event triggers" ::= { evSched2 10 } --1.3.6.1.4.1.3052.10.2.12.6.10 evSched2Friday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Friday (HH:MM) when this scheduled event triggers" ::= { evSched2 11 } --1.3.6.1.4.1.3052.10.2.12.6.11 evSched2Saturday OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time on Saturday (HH:MM) when this scheduled event triggers" ::= { evSched2 12 } --1.3.6.1.4.1.3052.10.2.12.6.12 evSched2Exclusions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Exclusions (space-separated MM/DD-formatted dates) for this scheduled event" ::= { evSched2 13 } --1.3.6.1.4.1.3052.10.2.12.6.13 --*************************************************************************************** --Serial Handshaking Low Section 2.12.7 --*************************************************************************************** evShskLowTable OBJECT-TYPE SYNTAX SEQUENCE OF SerialHandshakingLowEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of serial handshaking low events" ::= { event 7 } --1.3.6.1.4.1.3052.10.2.12.7 evShskLowEntry OBJECT-TYPE SYNTAX SerialHandshakingLowEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of serial handshaking low events" INDEX { evShskLowIndex } ::= { evShskLowTable 1 } --1.3.6.1.4.1.3052.10.2.12.7.1 evShskLowIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of serial handshaking low events" ::= { evShskLowEntry 1 } --1.3.6.1.4.1.3052.10.2.12.7.1.1 evShskLowEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: enable the serial handshaking low event for this port" ::= { evShskLowEntry 2 } --1.3.6.1.4.1.3052.10.2.12.7.1.2 evShskLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the serial handshaking low event for this port" ::= { evShskLowEntry 3 } --1.3.6.1.4.1.3052.10.2.12.7.1.3 evShskLowMessage OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for the serial handshaking low event for this port" ::= { evShskLowEntry 4 } --1.3.6.1.4.1.3052.10.2.12.7.1.4 evShskLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for the serial handshaking low event for this port" ::= { evShskLowEntry 5 } --1.3.6.1.4.1.3052.10.2.12.7.1.5 evShskLowTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for the serial handshaking low event for this port" ::= { evShskLowEntry 6 } --1.3.6.1.4.1.3052.10.2.12.7.1.6 --*************************************************************************************** --Serial Handshaking High Section 2.12.8 --*************************************************************************************** evShskHighTable OBJECT-TYPE SYNTAX SEQUENCE OF SerialHandshakingHighEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of serial handshaking high events" ::= { event 8 } --1.3.6.1.4.1.3052.10.2.12.8 evShskHighEntry OBJECT-TYPE SYNTAX SerialHandshakingHighEventConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of serial handshaking high events" INDEX { evShskHighIndex } ::= { evShskHighTable 1 } --1.3.6.1.4.1.3052.10.2.12.8.1 evShskHighIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of serial handshaking high events" ::= { evShskHighEntry 1 } --1.3.6.1.4.1.3052.10.2.12.8.1.1 evShskHighEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: enable the serial handshaking high event for this port" ::= { evShskHighEntry 2 } --1.3.6.1.4.1.3052.10.2.12.8.1.2 evShskHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the serial handshaking high event for this port" ::= { evShskHighEntry 3 } --1.3.6.1.4.1.3052.10.2.12.8.1.3 evShskHighMessage OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for the serial handshaking high event for this port" ::= { evShskHighEntry 4 } --1.3.6.1.4.1.3052.10.2.12.8.1.4 evShskHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for the serial handshaking high event for this port" ::= { evShskHighEntry 5 } --1.3.6.1.4.1.3052.10.2.12.8.1.5 evShskHighTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for the serial handshaking high event for this port" ::= { evShskHighEntry 6 } --1.3.6.1.4.1.3052.10.2.12.8.1.6 --*************************************************************************************** --No Sensor Event Section 2.12.9 --*************************************************************************************** evNoSensorTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Timeout (seconds) after which an EventSensor becomes unresponsive that this event is triggered" ::= { evNoSensor 1 } --1.3.6.1.4.1.3052.10.2.12.9.1 evNoSensorActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for no sensor event" ::= { evNoSensor 2 } --1.3.6.1.4.1.3052.10.2.12.9.2 evNoSensorTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for no sensor event" ::= { evNoSensor 3 } --1.3.6.1.4.1.3052.10.2.12.9.3 evNoSensorClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for no sensor event" ::= { evNoSensor 4 } --1.3.6.1.4.1.3052.10.2.12.9.4 --*************************************************************************************** --Fuel Sensor Config Section 2.12.11 --*************************************************************************************** fuelSensorGeneralTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigGeneral MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes general fuel sensor attributes." ::= { fuelSensor 1 } --1.3.6.1.4.1.3052.10.2.12.11.1 fsGenEntry OBJECT-TYPE SYNTAX FuelSensorConfigGeneral MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor general config table." INDEX { fsGenIndex } ::= { fuelSensorGeneralTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.1.1 fsGenIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor general config table." ::= { fsGenEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.1 fsGenName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor name." ::= { fsGenEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.2 fsGenSensorType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Type of fuel sensor in use; NONE disables the fuel sensor." ::= { fsGenEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.3 fsGenDistanceUnit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Distance units in use when setting and indicating tank dimensions." ::= { fsGenEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.4 fsGenRawValueTop OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Analog input reading corresponding to the SENSOR FULL point." ::= { fsGenEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.5 fsGenTopOffset OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Distance, in the specified distance unit, between the SENSOR FULL point and the TANK FULL point. The value is positive if the SENSOR FULL point is above the TANK FULL point, and negative if it is below." ::= { fsGenEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.6 fsGenRawValueBottom OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Analog input reading corresponding to the minimum fluid height measurable by the fuel sensor." ::= { fsGenEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.7 fsGenBottomOffset OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Distance, in the specified distance unit, between the SENSOR EMPTY point and the TANK EMPTY point. The value is positive if the SENSOR EMPTY point is above the TANK EMPTY point, and negative if it is below." ::= { fsGenEntry 8 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.8 fsGenInputES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-write STATUS current DESCRIPTION "Which eventsensor contains the analog input associated with this fuel sensor. Allowed values are 200 (for internal ES), or 1-16." ::= { fsGenEntry 9 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.9 fsGenInputPoint OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Which analog input point, on the specified eventsensor, that is associated with the fuel sensor." ::= { fsGenEntry 10 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.10 fsGenFilterAveraging OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor filter averaging factor." ::= { fsGenEntry 11 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.11 fsGenSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor System Reporting enable." ::= { fsGenEntry 12 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.12 fsGenSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor System Reporting threshold (floating point value)." ::= { fsGenEntry 13 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.13 fsGenSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor System Reporting limit." ::= { fsGenEntry 14 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.14 fsGenSysrepPackage OBJECT-TYPE SYNTAX Integer32 (0..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor System Reporting package number." ::= { fsGenEntry 15 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.15 fsGenGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor ASM profile type." ::= { fsGenEntry 16 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.16 fsGenEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor enable." ::= { fsGenEntry 17 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.17 fsGenFuelType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Type of fuel being measured: DIESEL, PROPANE, NATURAL GAS, HYDROGEN, GASOLINE, OTHER." ::= { fsGenEntry 18 } --1.3.6.1.4.1.3052.10.2.12.11.1.1.18 fuelSensorTankTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigTank MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes tank-specific fuel sensor attributes." ::= { fuelSensor 2 } --1.3.6.1.4.1.3052.10.2.12.11.2 fsTankEntry OBJECT-TYPE SYNTAX FuelSensorConfigTank MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor tank config table." INDEX { fsTankIndex } ::= { fuelSensorTankTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.2.1 fsTankIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor tank config table." ::= { fsTankEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.1 fsTankHeight OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Height of the tank, from the TANK EMPTY point to the TANK FULL point, in the specified distance unit (i.e. TANK HEIGHT). This is a floating point value." ::= { fsTankEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.2 fsTankDimA OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Tank dimension measurement A for certain tank profiles. For HORIZ OVAL, this is the length of the straight section. This is a floating point value." ::= { fsTankEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.3 fsTankDimB OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Tank dimension measurement B for certain tank profiles. For HORIZ OVAL, this is the radius of the curved section. This is a floating point value." ::= { fsTankEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.4 fsTankVolume OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "How many volume units the tank contains, when full. This is a floating point value." ::= { fsTankEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.5 fsTankVolumeUnit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of the unit representing fluid volume in the tank. This is only used for display purposes; it does not affect the volume calculation." ::= { fsTankEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.6 fsTankShape OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The shape of the fuel tank. A value of LINEAR produces a fluid volume reading that is directly proportional to fluid height. The HORIZ CYL and HORIZ OVAL settings use a hard-coded formula to calculate the volume. The CUSTOM setting uses a strapping table that must be configured as well (see fuelSensorCustomTankTable)." ::= { fsTankEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.2.1.7 fuelSensorCustomTankTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigCustomTankStrapping MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes the custom tank strapping table. Each fuel sensor has a table of height/volume pairs in service only when the tank shape (fsTankShape) in CUSTOM. This allows the unit to calculate volumes for nonstandard tank shapes, to the degree that accurate height/volume measurements can be configured. This SNMP table has two indexes: the first for which fuel sensor and the second for which height/volume pair." ::= { fuelSensor 3 } --1.3.6.1.4.1.3052.10.2.12.11.3 fsCustomTankEntry OBJECT-TYPE SYNTAX FuelSensorConfigCustomTankStrapping MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor custom tank config table." INDEX { fsCustomTankIndexFS, fsCustomTankIndexDatum } ::= { fuelSensorCustomTankTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.3.1 fsCustomTankIndexFS OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor tank config table. This is the first of two indexes for this SNMP table." ::= { fsCustomTankEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.3.1.1 fsCustomTankIndexDatum OBJECT-TYPE SYNTAX Integer32 (1..32) MAX-ACCESS read-only STATUS current DESCRIPTION "Which hight/volume pair: there are 32 pairs per fuel sensor. This is the second of two indexes for this SNMP table." ::= { fsCustomTankEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.3.1.2 fsCustomTankHeight OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Height of custom tank height/volume pair. This is a floating point value." ::= { fsCustomTankEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.3.1.3 fsCustomTankVolume OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Volume of custom tank height/volume pair. This is a floating point value." ::= { fsCustomTankEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.3.1.4 fuelSensorVolumeTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigVolume MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes volume-event-specific fuel sensor attributes." ::= { fuelSensor 4 } --1.3.6.1.4.1.3052.10.2.12.11.4 fsVolumeEntry OBJECT-TYPE SYNTAX FuelSensorConfigVolume MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor volume event config table." INDEX { fsVolumeIndex } ::= { fuelSensorVolumeTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.4.1 fsVolumeIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor volume event config table." ::= { fsVolumeEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.1 fsVolumeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable fuel sensor volume events." ::= { fsVolumeEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.2 fsVolumeDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor deadband (hysteresis). This is a floating point value." ::= { fsVolumeEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.3 fsVolumeVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very high event threshold value. This is a floating point value." ::= { fsVolumeEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.4 fsVolumeVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very high event threshold actions." ::= { fsVolumeEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.5 fsVolumeVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (519..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very high event threshold trap number." ::= { fsVolumeEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.6 fsVolumeVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very high event threshold class (severity)." ::= { fsVolumeEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.7 fsVolumeHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume high event threshold value. This is a floating point value." ::= { fsVolumeEntry 8 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.8 fsVolumeHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume high event threshold actions." ::= { fsVolumeEntry 9 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.9 fsVolumeHighTrapNum OBJECT-TYPE SYNTAX Integer32 (519..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume high event threshold trap number." ::= { fsVolumeEntry 10 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.10 fsVolumeHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume high event threshold class (severity)." ::= { fsVolumeEntry 11 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.11 fsVolumeNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume return to normal actions." ::= { fsVolumeEntry 12 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.12 fsVolumeNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (519..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume return to normal trap number." ::= { fsVolumeEntry 13 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.13 fsVolumeNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume return to normal class (severity)." ::= { fsVolumeEntry 14 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.14 fsVolumeLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume low event threshold value. This is a floating point value." ::= { fsVolumeEntry 15 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.15 fsVolumeLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume low event threshold actions." ::= { fsVolumeEntry 16 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.16 fsVolumeLowTrapNum OBJECT-TYPE SYNTAX Integer32 (519..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume low event threshold trap number." ::= { fsVolumeEntry 17 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.17 fsVolumeLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume low event threshold class (severity)." ::= { fsVolumeEntry 18 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.18 fsVolumeVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very low event threshold value. This is a floating point value." ::= { fsVolumeEntry 19 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.19 fsVolumeVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very low event threshold actions." ::= { fsVolumeEntry 20 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.20 fsVolumeVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (519..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very low event threshold trap number." ::= { fsVolumeEntry 21 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.21 fsVolumeVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor volume very low event threshold class (severity)." ::= { fsVolumeEntry 22 } --1.3.6.1.4.1.3052.10.2.12.11.4.1.22 fuelSensorDisconnectTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigDisconnect MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes disconnect-event-specific fuel sensor attributes." ::= { fuelSensor 5 } --1.3.6.1.4.1.3052.10.2.12.11.5 fsDiscEntry OBJECT-TYPE SYNTAX FuelSensorConfigDisconnect MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor disconnect event config table." INDEX { fsDiscIndex } ::= { fuelSensorDisconnectTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.5.1 fsDiscIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor disconnect event config table." ::= { fsDiscEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.1 fsDiscEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect event enable." ::= { fsDiscEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.2 fsDiscHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High end of input value range when fuel sensor is disconnected. This is in the units of the analog input value." ::= { fsDiscEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.3 fsDiscLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low end of input value range when fuel sensor is disconnected. This is in the units of the analog input value." ::= { fsDiscEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.4 fsDiscActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect event actions." ::= { fsDiscEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.5 fsDiscTrapNum OBJECT-TYPE SYNTAX Integer32 (515..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect event trap number." ::= { fsDiscEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.6 fsDiscClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect event class (severity)." ::= { fsDiscEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.7 fsDiscNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect return to normal actions." ::= { fsDiscEntry 8 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.8 fsDiscNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (515..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect return to normal trap number." ::= { fsDiscEntry 9 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.9 fsDiscNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel sensor disconnect return to normal class (severity)." ::= { fsDiscEntry 10 } --1.3.6.1.4.1.3052.10.2.12.11.5.1.10 fuelSensorSuddenChangeTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigSuddenChange MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes sudden-change-event-specific fuel sensor attributes." ::= { fuelSensor 6 } --1.3.6.1.4.1.3052.10.2.12.11.6 fsSuddenChangeEntry OBJECT-TYPE SYNTAX FuelSensorConfigSuddenChange MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor sudden change event config table." INDEX { fsSuddenChangeIndex } ::= { fuelSensorSuddenChangeTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.6.1 fsSuddenChangeIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor sudden change event config table." ::= { fsSuddenChangeEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.1 fsSuddenChangeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event enable." ::= { fsSuddenChangeEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.2 fsSuddenChangeTime OBJECT-TYPE SYNTAX Integer32 (5..360) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event time (minutes): what duration defines 'sudden'." ::= { fsSuddenChangeEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.3 fsSuddenChangeAmplitude OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event amplitude: what amount (in fuel volume units) over the duration (fsSuddenChangeTime) defines enough change." ::= { fsSuddenChangeEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.4 fsSuddenChangeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event actions." ::= { fsSuddenChangeEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.5 fsSuddenChangeTrapNum OBJECT-TYPE SYNTAX Integer32 (527..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event trap number." ::= { fsSuddenChangeEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.6 fsSuddenChangeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume sudden change event class (severity)." ::= { fsSuddenChangeEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.6.1.7 fuelSensorSlowChangeTable OBJECT-TYPE SYNTAX SEQUENCE OF FuelSensorConfigSlowChange MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes slow-change-event-specific fuel sensor attributes." ::= { fuelSensor 7 } --1.3.6.1.4.1.3052.10.2.12.11.7 fsSlowChangeEntry OBJECT-TYPE SYNTAX FuelSensorConfigSlowChange MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for fuel sensor slow change event config table." INDEX { fsSlowChangeIndex } ::= { fuelSensorSlowChangeTable 1 } --1.3.6.1.4.1.3052.10.2.12.11.7.1 fsSlowChangeIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Which fuel sensor in the fuel sensor slow change event config table." ::= { fsSlowChangeEntry 1 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.1 fsSlowChangeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event enable." ::= { fsSlowChangeEntry 2 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.2 fsSlowChangeTime OBJECT-TYPE SYNTAX Integer32 (1..168) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event time (minutes): what duration defines 'slow'." ::= { fsSlowChangeEntry 3 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.3 fsSlowChangeAmplitude OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event amplitude: what amount (in fuel volume units) over the duration (fsSlowChangeTime) defines enough change." ::= { fsSlowChangeEntry 4 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.4 fsSlowChangeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event actions." ::= { fsSlowChangeEntry 5 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.5 fsSlowChangeTrapNum OBJECT-TYPE SYNTAX Integer32 (528..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event trap number." ::= { fsSlowChangeEntry 6 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.6 fsSlowChangeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Fuel volume slow change event class (severity)." ::= { fsSlowChangeEntry 7 } --1.3.6.1.4.1.3052.10.2.12.11.7.1.7 --*************************************************************************************** --AC Power Monitor Config Section 2.12.12 --*************************************************************************************** acpmGeneralTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigGeneral MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes general AC power monitor attributes." ::= { acPowerMonitor 1 } --1.3.6.1.4.1.3052.10.2.12.12.1 acpmGenEntry OBJECT-TYPE SYNTAX ACPMConfigGeneral MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor general config table." INDEX { acpmGenIndex } ::= { acpmGeneralTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.1.1 acpmGenIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor general config table." ::= { acpmGenEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.1 acpmGenDevice OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Model of the AC power monitor device. The unit needs this setting to know which registers to poll for the various data items, among other things." ::= { acpmGenEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.2 acpmGenName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for the AC power monitor device." ::= { acpmGenEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.3 acpmGenAddress OBJECT-TYPE SYNTAX Integer32 (1..247) MAX-ACCESS read-write STATUS current DESCRIPTION "Modbus address of the AC power monitor device." ::= { acpmGenEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.4 acpmGenPtRatio OBJECT-TYPE SYNTAX Integer32 (1..10000) MAX-ACCESS read-write STATUS current DESCRIPTION "Ratio of secondary turns to primary turns on potential transformers (PT)." ::= { acpmGenEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.5 acpmGenCtRatio OBJECT-TYPE SYNTAX Integer32 (1..10000) MAX-ACCESS read-write STATUS current DESCRIPTION "Ratio of secondary turns to primary turns on current transformers (CT)." ::= { acpmGenEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.6 acpmGenPowerType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Type of power being monitored." ::= { acpmGenEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.7 acpmGenSysrepPackage OBJECT-TYPE SYNTAX Integer32 (0..10) MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting package number." ::= { acpmGenEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.8 acpmGenGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ASM profile group." ::= { acpmGenEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.9 acpmGenEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "AC power monitor enable." ::= { acpmGenEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.1.1.10 acpmAvgVoltageTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigAvgVoltage MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor average voltage attributes." ::= { acPowerMonitor 2 } --1.3.6.1.4.1.3052.10.2.12.12.2 acpmAvgVoltageEntry OBJECT-TYPE SYNTAX ACPMConfigAvgVoltage MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor average voltage config table." INDEX { acpmAvgVoltageIndex } ::= { acpmAvgVoltageTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.2.1 acpmAvgVoltageIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor average voltage config table." ::= { acpmAvgVoltageEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.1 acpmAvgVoltageEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor average voltage events." ::= { acpmAvgVoltageEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.2 acpmAvgVoltageDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband (hysteresis) for average voltage event. This is a floating point value." ::= { acpmAvgVoltageEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.3 acpmAvgVoltageVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold. This is a floating point value." ::= { acpmAvgVoltageEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.4 acpmAvgVoltageVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions." ::= { acpmAvgVoltageEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.5 acpmAvgVoltageVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (520..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number." ::= { acpmAvgVoltageEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.6 acpmAvgVoltageVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class." ::= { acpmAvgVoltageEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.7 acpmAvgVoltageHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold. This is a floating point value." ::= { acpmAvgVoltageEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.8 acpmAvgVoltageHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions." ::= { acpmAvgVoltageEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.9 acpmAvgVoltageHighTrapNum OBJECT-TYPE SYNTAX Integer32 (520..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number." ::= { acpmAvgVoltageEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.10 acpmAvgVoltageHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class." ::= { acpmAvgVoltageEntry 11 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.11 acpmAvgVoltageNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal actions." ::= { acpmAvgVoltageEntry 12 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.12 acpmAvgVoltageNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (520..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal trap number." ::= { acpmAvgVoltageEntry 13 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.13 acpmAvgVoltageNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal class." ::= { acpmAvgVoltageEntry 14 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.14 acpmAvgVoltageLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold. This is a floating point value." ::= { acpmAvgVoltageEntry 15 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.15 acpmAvgVoltageLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions." ::= { acpmAvgVoltageEntry 16 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.16 acpmAvgVoltageLowTrapNum OBJECT-TYPE SYNTAX Integer32 (520..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number." ::= { acpmAvgVoltageEntry 17 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.17 acpmAvgVoltageLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class." ::= { acpmAvgVoltageEntry 18 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.18 acpmAvgVoltageVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold. This is a floating point value." ::= { acpmAvgVoltageEntry 19 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.19 acpmAvgVoltageVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions." ::= { acpmAvgVoltageEntry 20 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.20 acpmAvgVoltageVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (520..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event trap number." ::= { acpmAvgVoltageEntry 21 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.21 acpmAvgVoltageVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class." ::= { acpmAvgVoltageEntry 22 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.22 acpmAvgVoltageSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting enable for average voltage telemetry." ::= { acpmAvgVoltageEntry 23 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.23 acpmAvgVoltageSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting threshold for average voltage telemetry. This is a floating point value." ::= { acpmAvgVoltageEntry 24 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.24 acpmAvgVoltageSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting limit for average voltage telemetry." ::= { acpmAvgVoltageEntry 25 } --1.3.6.1.4.1.3052.10.2.12.12.2.1.25 acpmAvgCurrentTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigAvgCurrent MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor average current attributes." ::= { acPowerMonitor 3 } --1.3.6.1.4.1.3052.10.2.12.12.3 acpmAvgCurrentEntry OBJECT-TYPE SYNTAX ACPMConfigAvgCurrent MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor average current config table." INDEX { acpmAvgCurrentIndex } ::= { acpmAvgCurrentTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.3.1 acpmAvgCurrentIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor average current config table." ::= { acpmAvgCurrentEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.1 acpmAvgCurrentEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor average current events." ::= { acpmAvgCurrentEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.2 acpmAvgCurrentDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband (hysteresis) for average current event. This is a floating point value." ::= { acpmAvgCurrentEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.3 acpmAvgCurrentVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold. This is a floating point value." ::= { acpmAvgCurrentEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.4 acpmAvgCurrentVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions." ::= { acpmAvgCurrentEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.5 acpmAvgCurrentVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (521..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number." ::= { acpmAvgCurrentEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.6 acpmAvgCurrentVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class." ::= { acpmAvgCurrentEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.7 acpmAvgCurrentHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold. This is a floating point value." ::= { acpmAvgCurrentEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.8 acpmAvgCurrentHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions." ::= { acpmAvgCurrentEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.9 acpmAvgCurrentHighTrapNum OBJECT-TYPE SYNTAX Integer32 (521..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number." ::= { acpmAvgCurrentEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.10 acpmAvgCurrentHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class." ::= { acpmAvgCurrentEntry 11 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.11 acpmAvgCurrentNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal actions." ::= { acpmAvgCurrentEntry 12 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.12 acpmAvgCurrentNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (521..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal trap number." ::= { acpmAvgCurrentEntry 13 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.13 acpmAvgCurrentNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal class." ::= { acpmAvgCurrentEntry 14 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.14 acpmAvgCurrentLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold. This is a floating point value." ::= { acpmAvgCurrentEntry 15 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.15 acpmAvgCurrentLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions." ::= { acpmAvgCurrentEntry 16 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.16 acpmAvgCurrentLowTrapNum OBJECT-TYPE SYNTAX Integer32 (521..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number." ::= { acpmAvgCurrentEntry 17 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.17 acpmAvgCurrentLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class." ::= { acpmAvgCurrentEntry 18 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.18 acpmAvgCurrentVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold. This is a floating point value." ::= { acpmAvgCurrentEntry 19 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.19 acpmAvgCurrentVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions." ::= { acpmAvgCurrentEntry 20 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.20 acpmAvgCurrentVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (521..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event trap number." ::= { acpmAvgCurrentEntry 21 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.21 acpmAvgCurrentVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class." ::= { acpmAvgCurrentEntry 22 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.22 acpmAvgCurrentSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting enable for average current telemetry." ::= { acpmAvgCurrentEntry 23 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.23 acpmAvgCurrentSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting threshold for average current telemetry. This is a floating point value." ::= { acpmAvgCurrentEntry 24 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.24 acpmAvgCurrentSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting limit for average current telemetry." ::= { acpmAvgCurrentEntry 25 } --1.3.6.1.4.1.3052.10.2.12.12.3.1.25 acpmFreqTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigFreq MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor frequency attributes." ::= { acPowerMonitor 4 } --1.3.6.1.4.1.3052.10.2.12.12.4 acpmFreqEntry OBJECT-TYPE SYNTAX ACPMConfigFreq MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor frequency config table." INDEX { acpmFreqIndex } ::= { acpmFreqTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.4.1 acpmFreqIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor frequency config table." ::= { acpmFreqEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.1 acpmFreqEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor frequency events." ::= { acpmFreqEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.2 acpmFreqDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband (hysteresis) for frequency event. This is a floating point value." ::= { acpmFreqEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.3 acpmFreqVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold. This is a floating point value." ::= { acpmFreqEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.4 acpmFreqVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions." ::= { acpmFreqEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.5 acpmFreqVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (522..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number." ::= { acpmFreqEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.6 acpmFreqVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class." ::= { acpmFreqEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.7 acpmFreqHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold. This is a floating point value." ::= { acpmFreqEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.8 acpmFreqHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions." ::= { acpmFreqEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.9 acpmFreqHighTrapNum OBJECT-TYPE SYNTAX Integer32 (522..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number." ::= { acpmFreqEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.10 acpmFreqHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class." ::= { acpmFreqEntry 11 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.11 acpmFreqNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal actions." ::= { acpmFreqEntry 12 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.12 acpmFreqNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (522..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal trap number." ::= { acpmFreqEntry 13 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.13 acpmFreqNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal class." ::= { acpmFreqEntry 14 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.14 acpmFreqLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold. This is a floating point value." ::= { acpmFreqEntry 15 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.15 acpmFreqLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions." ::= { acpmFreqEntry 16 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.16 acpmFreqLowTrapNum OBJECT-TYPE SYNTAX Integer32 (522..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number." ::= { acpmFreqEntry 17 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.17 acpmFreqLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class." ::= { acpmFreqEntry 18 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.18 acpmFreqVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold. This is a floating point value." ::= { acpmFreqEntry 19 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.19 acpmFreqVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions." ::= { acpmFreqEntry 20 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.20 acpmFreqVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (522..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event trap number." ::= { acpmFreqEntry 21 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.21 acpmFreqVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class." ::= { acpmFreqEntry 22 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.22 acpmFreqSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting enable for frequency telemetry." ::= { acpmFreqEntry 23 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.23 acpmFreqSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting threshold for frequency telemetry. This is a floating point value." ::= { acpmFreqEntry 24 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.24 acpmFreqSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting limit for frequency telemetry." ::= { acpmFreqEntry 25 } --1.3.6.1.4.1.3052.10.2.12.12.4.1.25 acpmTotalRealPowerTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigTRP MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor total real power attributes." ::= { acPowerMonitor 5 } --1.3.6.1.4.1.3052.10.2.12.12.5 acpmTRPEntry OBJECT-TYPE SYNTAX ACPMConfigTRP MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor total real power config table." INDEX { acpmTRPIndex } ::= { acpmTotalRealPowerTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.5.1 acpmTRPIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor total real power config table." ::= { acpmTRPEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.1 acpmTRPEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor total real power events." ::= { acpmTRPEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.2 acpmTRPDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband (hysteresis) for total real power event. This is a floating point value." ::= { acpmTRPEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.3 acpmTRPVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold. This is a floating point value." ::= { acpmTRPEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.4 acpmTRPVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event actions." ::= { acpmTRPEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.5 acpmTRPVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (523..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event trap number." ::= { acpmTRPEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.6 acpmTRPVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class." ::= { acpmTRPEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.7 acpmTRPHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold. This is a floating point value." ::= { acpmTRPEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.8 acpmTRPHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event actions." ::= { acpmTRPEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.9 acpmTRPHighTrapNum OBJECT-TYPE SYNTAX Integer32 (523..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "High event trap number." ::= { acpmTRPEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.10 acpmTRPHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class." ::= { acpmTRPEntry 11 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.11 acpmTRPNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal actions." ::= { acpmTRPEntry 12 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.12 acpmTRPNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (523..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal trap number." ::= { acpmTRPEntry 13 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.13 acpmTRPNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to normal class." ::= { acpmTRPEntry 14 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.14 acpmTRPLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold. This is a floating point value." ::= { acpmTRPEntry 15 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.15 acpmTRPLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event actions." ::= { acpmTRPEntry 16 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.16 acpmTRPLowTrapNum OBJECT-TYPE SYNTAX Integer32 (523..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Low event trap number." ::= { acpmTRPEntry 17 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.17 acpmTRPLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class." ::= { acpmTRPEntry 18 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.18 acpmTRPVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold. This is a floating point value." ::= { acpmTRPEntry 19 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.19 acpmTRPVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event actions." ::= { acpmTRPEntry 20 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.20 acpmTRPVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (523..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event trap number." ::= { acpmTRPEntry 21 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.21 acpmTRPVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class." ::= { acpmTRPEntry 22 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.22 acpmTRPSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting enable for total real power telemetry." ::= { acpmTRPEntry 23 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.23 acpmTRPSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting threshold for total real power telemetry. This is a floating point value." ::= { acpmTRPEntry 24 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.24 acpmTRPSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting limit for total real power telemetry." ::= { acpmTRPEntry 25 } --1.3.6.1.4.1.3052.10.2.12.12.5.1.25 acpmDisconnectTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigDisconnect MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor device disconnect event attributes." ::= { acPowerMonitor 6 } --1.3.6.1.4.1.3052.10.2.12.12.6 acpmDisconnectEntry OBJECT-TYPE SYNTAX ACPMConfigDisconnect MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor device disconnect event config table." INDEX { acpmDisconnectIndex } ::= { acpmDisconnectTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.6.1 acpmDisconnectIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor device disconnect event config table." ::= { acpmDisconnectEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.1 acpmDisconnectEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor device disconnect event." ::= { acpmDisconnectEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.2 acpmDisconnectActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for disconnect event." ::= { acpmDisconnectEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.3 acpmDisconnectTrapNum OBJECT-TYPE SYNTAX Integer32 (524..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for disconnect event." ::= { acpmDisconnectEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.4 acpmDisconnectClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for disconnect event." ::= { acpmDisconnectEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.5 acpmDisconnectNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for disconnect return to normal event." ::= { acpmDisconnectEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.6 acpmDisconnectNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (524..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for disconnect return to normal event." ::= { acpmDisconnectEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.7 acpmDisconnectNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class for disconnect return to normal event." ::= { acpmDisconnectEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.6.1.8 acpmTotalPowerFactorTable OBJECT-TYPE SYNTAX SEQUENCE OF ACPMConfigTotalPowerFactor MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes AC power monitor device total power factor event attributes." ::= { acPowerMonitor 7 } --1.3.6.1.4.1.3052.10.2.12.12.7 acpmTPFEntry OBJECT-TYPE SYNTAX ACPMConfigTotalPowerFactor MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for AC power monitor device total power factor event config table." INDEX { acpmTPFIndex } ::= { acpmTotalPowerFactorTable 1 } --1.3.6.1.4.1.3052.10.2.12.12.7.1 acpmTPFIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Which AC power monitor in the AC power monitor device disconnect event config table." ::= { acpmTPFEntry 1 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.1 acpmTPFEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable AC power monitor device disconnect event." ::= { acpmTPFEntry 2 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.2 acpmTPFDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband (hysteresis)." ::= { acpmTPFEntry 3 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.3 acpmTPFNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Normal actions." ::= { acpmTPFEntry 4 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.4 acpmTPFNormalTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Normal trap number." ::= { acpmTPFEntry 5 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.5 acpmTPFNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Normal class." ::= { acpmTPFEntry 6 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.6 acpmTPFLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low threshold." ::= { acpmTPFEntry 7 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.7 acpmTPFLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low actions." ::= { acpmTPFEntry 8 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.8 acpmTPFLowTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low trap number." ::= { acpmTPFEntry 9 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.9 acpmTPFLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low class." ::= { acpmTPFEntry 10 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.10 acpmTPFVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low threshold." ::= { acpmTPFEntry 11 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.11 acpmTPFVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low actions." ::= { acpmTPFEntry 12 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.12 acpmTPFVLowTrapNum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low trap number." ::= { acpmTPFEntry 13 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.13 acpmTPFVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low class." ::= { acpmTPFEntry 14 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.14 acpmTPFSysrepEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting enable." ::= { acpmTPFEntry 15 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.15 acpmTPFSysrepThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting threshold." ::= { acpmTPFEntry 16 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.16 acpmTPFSysrepLimit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "System reporting limit." ::= { acpmTPFEntry 17 } --1.3.6.1.4.1.3052.10.2.12.12.7.1.17 --*************************************************************************************** --Reset Event Section 2.12.16 --*************************************************************************************** evResetEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable reset event. This event is triggered when the unit finishes booting." ::= { evReset 1 } --1.3.6.1.4.1.3052.10.2.12.16.1 evResetDelay OBJECT-TYPE SYNTAX Integer32 (0..3600) MAX-ACCESS read-write STATUS current DESCRIPTION "Number of seconds to wait after unit finishes booting before triggering the reset event." ::= { evReset 2 } --1.3.6.1.4.1.3052.10.2.12.16.2 evResetActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for reset event." ::= { evReset 3 } --1.3.6.1.4.1.3052.10.2.12.16.3 evResetMessage OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Message for reset event." ::= { evReset 4 } --1.3.6.1.4.1.3052.10.2.12.16.4 evResetTrapnum OBJECT-TYPE SYNTAX Integer32 (543..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for reset event." ::= { evReset 5 } --1.3.6.1.4.1.3052.10.2.12.16.5 evResetClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for reset event." ::= { evReset 6 } --1.3.6.1.4.1.3052.10.2.12.16.6 --*************************************************************************************** --Global Event Section 2.12.18 --*************************************************************************************** evGlobalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Global event actions." ::= { evGlobal 2 } --1.3.6.1.4.1.3052.10.2.12.18.2 evGlobalTrapnum OBJECT-TYPE SYNTAX Integer32 (0..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Global trap number." ::= { evGlobal 3 } --1.3.6.1.4.1.3052.10.2.12.18.3 --*************************************************************************************** --HVAC Configuration Section 2.12.19 --*************************************************************************************** --*************************************************************************************** --BARD HVAC Configuration Section 2.12.19.2 --*************************************************************************************** evHVACBardIPAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IP address of the Bard HVAC controller." ::= { evHVACBardLocal 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.1 evHVACBardPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port of the Bard HVAC controller interface." ::= { evHVACBardLocal 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.2 evHVACBardTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait for a response from the Bard HVAC controller." ::= { evHVACBardLocal 3 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.3 evHVACBardXMLStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "XML status page of the Bard HVAC controller." ::= { evHVACBardLocal 4 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.4 evHVACBardXMLSettings OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "XML settings page of the Bard HVAC controller." ::= { evHVACBardLocal 5 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.5 evHVACBardWebSettingsHTML OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Web settings page of the Bard HVAC controller." ::= { evHVACBardLocal 6 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.6 evHVACBardAlarmEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable the Bard HVAC Alarm event." ::= { evHVACBardAlarm 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.1 evHVACBardAlarmActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the Bard HVAC Alarm event." ::= { evHVACBardAlarm 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.2 evHVACBardAlarmTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for the Bard HVAC Alarm event." ::= { evHVACBardAlarm 3 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.3 evHVACBardAlarmClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for the Bard HVAC Alarm event." ::= { evHVACBardAlarm 4 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.4 evHVACBardAlarmNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the Bard HVAC Alarm Return to Normal event." ::= { evHVACBardAlarm 5 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.5 evHVACBardAlarmNormalTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for the Bard HVAC Alarm Return to Normal event." ::= { evHVACBardAlarm 6 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.6 evHVACBardAlarmNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for the Bard HVAC Alarm Return to Normal event." ::= { evHVACBardAlarm 7 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.7.7 evHVACBardReset OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Set to any value to reset the Bard HVAC controller. Always reads zero." ::= { evHVACBardLocal 8 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.8 evHVACBardDefault OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Set to any value to restore default settings on the Bard HVAC controller. Always reads zero." ::= { evHVACBardLocal 9 } --1.3.6.1.4.1.3052.10.2.12.19.2.1.9 evHVACBardTempScale OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Scale used, Celsius or Fahrenheit (C or F)." ::= { evHVACBardSynchronized 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.1 evHVACBardCoolThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling threshold to turn on HVAC cooling elements (economizer/compressor)." ::= { evHVACBardSynchronized 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.2 evHVACBardCoolThresholdState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 3 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.3 evHVACBardHeatThreshold OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Heating threshold to turn on HVAC heating elements (economizer/compressor)." ::= { evHVACBardSynchronized 4 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.4 evHVACBardHeatDiff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Heating differential to turn on HVAC heating elements. The heating threshold is calculated by subtracting this number from the current cool threshold." ::= { evHVACBardSynchronized 5 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.5 evHVACBardHeatDiffState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 6 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.6 evHVACBardBlower OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Continuous blower operation enable." ::= { evHVACBardSynchronized 7 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.7 evHVACBardBlowerState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 8 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.8 evHVACBardAlternate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Alternate lead-lag sequence for the economizer." ::= { evHVACBardSynchronized 9 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.9 evHVACBardAlternateState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 10 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.10 evHVACBardChangeover OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Lead-lag changeover time in days." ::= { evHVACBardSynchronized 11 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.11 evHVACBardChangeoverState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 12 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.12 evHVACBardBlowDiff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable to run blowers if two sensors have a difference of 5 F or greater." ::= { evHVACBardSynchronized 13 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.13 evHVACBardBlowDiffState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 14 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.14 evHVACBardOffDelay OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "3 minute lead/4 minute lag unit off delay enable." ::= { evHVACBardSynchronized 15 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.15 evHVACBardOffDelayState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 16 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.16 evHVACBardRunMin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run the compressor for at least 3 minutes before shutting off enable." ::= { evHVACBardSynchronized 17 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.17 evHVACBardRunMinState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 18 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.18 evHVACBardStage1Diff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature differential between stages 1 and 2." ::= { evHVACBardDiff 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.1 evHVACBardStage1DiffState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardDiff 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.2 evHVACBardStage2Diff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature differential between stages 2 and 3." ::= { evHVACBardDiff 3 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.3 evHVACBardStage2DiffState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardDiff 4 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.4 evHVACBardStage3Diff OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature differential between stages 3 and 4." ::= { evHVACBardDiff 5 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.5 evHVACBardStage3DiffState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardDiff 6 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.19.6 evHVACBardCoolDisableDb OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling disable deadband." ::= { evHVACBardSynchronized 20 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.20 evHVACBardCoolDisableDbState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 21 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.21 evHVACBardCoolEnableDb OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Cooling enable deadband." ::= { evHVACBardSynchronized 22 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.22 evHVACBardCoolEnableDbState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 23 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.23 evHVACBardHeatDb OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Heating deadband." ::= { evHVACBardSynchronized 24 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.24 evHVACBardHeatDbState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 25 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.25 evHVACBardHeatPump OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Heat pump logic enable." ::= { evHVACBardSynchronized 26 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.26 evHVACBardHeatPumpState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 27 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.27 evHVACBardCompressors OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 28 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.28 evHVACBardCompressorsState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 29 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.29 evHVACBardEconomizer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 30 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.30 evHVACBardEconomizerState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 31 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.31 evHVACBardTempLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low alarm for temperature." ::= { evHVACBardTemp 1 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.1 evHVACBardTempLowValueState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardTemp 2 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.2 evHVACBardTempHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High alarm for temperature." ::= { evHVACBardTemp 3 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.3 evHVACBardTempHighValueState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardTemp 4 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.4 evHVACBardTempVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high alarm for temperature." ::= { evHVACBardTemp 5 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.5 evHVACBardTempVHighValueState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardTemp 6 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.32.6 evHVACBardOverride OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The HVAC controller override." ::= { evHVACBardSynchronized 33 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.33 evHVACBardOverrideState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 34 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.34 evHVACBardLock OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable the external controller lock." ::= { evHVACBardSynchronized 35 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.35 evHVACBardLockState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 36 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.36 evHVACBardLeadUnit OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Which HVAC unit is currently the lead unit." ::= { evHVACBardSynchronized 37 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.37 evHVACBardLeadUnitState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 38 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.38 evHVACBardComfort OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable comfort mode." ::= { evHVACBardSynchronized 39 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.39 evHVACBardComfortState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Synchronization status of previous object: ERROR (with possible description), PENDING, or OK." ::= { evHVACBardSynchronized 40 } --1.3.6.1.4.1.3052.10.2.12.19.2.2.40 --*************************************************************************************** --Asentria HVAC Configuration Section 2.12.19.3 --*************************************************************************************** evHVACAsentriaSensorListTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACAsentriaSensorList MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor list table" ::= { evHVACAsentria 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.1 evHVACAsentriaSensorListEntry OBJECT-TYPE SYNTAX HVACAsentriaSensorList MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor list table entry" INDEX { evHVACAsentriaSensorListIndex } ::= { evHVACAsentriaSensorListTable 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1 evHVACAsentriaSensorListIndex OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Asentria HVAC temperature/humidity sensor" ::= { evHVACAsentriaSensorListEntry 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1.1 evHVACAsentriaSensorListES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor EventSensor number" ::= { evHVACAsentriaSensorListEntry 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1.2 evHVACAsentriaSensorListPT OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor point" ::= { evHVACAsentriaSensorListEntry 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1.3 evHVACAsentriaSensorListType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor type" ::= { evHVACAsentriaSensorListEntry 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1.4 evHVACAsentriaSensorListLoc OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature/humidity sensor location" ::= { evHVACAsentriaSensorListEntry 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.1.1.5 evHVACAsentriaOverride OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC controller override" ::= { evHVACAsentria 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.2 evHVACAsentriaSchedule OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC unit primary/lead swap schedule" ::= { evHVACAsentria 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.3 evHVACAsentriaPrimary OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC primary/lead unit to operate" ::= { evHVACAsentria 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.4 evHVACAsentriaMethod OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC controller temperature/humidity calculation method" ::= { evHVACAsentria 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.5 evHVACAsentriaAlarmLagNormEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC enable for normal/idle alarm notification on lag unit" ::= { evHVACAsentriaAlarm 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.1 evHVACAsentriaAlarmLagNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC actions to perform for normal/idle alarm notification on lag unit" ::= { evHVACAsentriaAlarm 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.2 evHVACAsentriaAlarmLagNormTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC trap number for normal/idle alarm notification on lag unit" ::= { evHVACAsentriaAlarm 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.3 evHVACAsentriaAlarmLagNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC alarm class for normal/idle alarm notification on lag unit" ::= { evHVACAsentriaAlarm 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.4 evHVACAsentriaAlarmLagVentEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC enable for venting alarm notification on lag unit" ::= { evHVACAsentriaAlarm 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.5 evHVACAsentriaAlarmLagVentActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC actions to perform for venting alarm notification on lag unit" ::= { evHVACAsentriaAlarm 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.6 evHVACAsentriaAlarmLagVentTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC trap number for venting alarm notification on lag unit" ::= { evHVACAsentriaAlarm 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.7 evHVACAsentriaAlarmLagVentClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC alarm class for venting alarm notification on lag unit" ::= { evHVACAsentriaAlarm 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.8 evHVACAsentriaAlarmLagCoolEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC enable for cooling alarm notification on lag unit" ::= { evHVACAsentriaAlarm 9 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.9 evHVACAsentriaAlarmLagCoolActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC actions to perform for cooling alarm notification on lag unit" ::= { evHVACAsentriaAlarm 10 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.10 evHVACAsentriaAlarmLagCoolTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC trap number for cooling alarm notification on lag unit" ::= { evHVACAsentriaAlarm 11 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.11 evHVACAsentriaAlarmLagCoolClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC alarm class for cooling alarm notification on lag unit" ::= { evHVACAsentriaAlarm 12 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.12 evHVACAsentriaAlarmLagHeatEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC enable for heating alarm notification on lag unit" ::= { evHVACAsentriaAlarm 13 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.13 evHVACAsentriaAlarmLagHeatActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC actions to perform for heating alarm notification on lag unit" ::= { evHVACAsentriaAlarm 14 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.14 evHVACAsentriaAlarmLagHeatTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC trap number for heating alarm notification on lag unit" ::= { evHVACAsentriaAlarm 15 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.15 evHVACAsentriaAlarmLagHeatClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC alarm class for heating alarm notification on lag unit" ::= { evHVACAsentriaAlarm 16 } --1.3.6.1.4.1.3052.10.2.12.19.3.6.16 evHVACAsentriaFireES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC fire/smoke alarm EventSensor number" ::= { evHVACAsentriaFire 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.1 evHVACAsentriaFirePT OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC fire/smoke alarm point number" ::= { evHVACAsentriaFire 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.2 evHVACAsentriaFireActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC actions to perform for fire/smoke alarm notification" ::= { evHVACAsentriaFire 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.3 evHVACAsentriaFireTrapnum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC trap number for fire/smoke alarm notification" ::= { evHVACAsentriaFire 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.4 evHVACAsentriaFireClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC alarm class for fire/smoke alarm notification" ::= { evHVACAsentriaFire 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.5 evHVACAsentriaFireNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC return to normal actions to perform for fire/smoke alarm notification" ::= { evHVACAsentriaFire 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.6 evHVACAsentriaFireNormTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC return to normal trap number for fire/smoke alarm notification" ::= { evHVACAsentriaFire 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.7 evHVACAsentriaFireNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC return to normal class for fire/smoke alarm notification" ::= { evHVACAsentriaFire 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.7.8 evHVACAsentriaUnitTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACAsentriaUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC unit table" ::= { evHVACAsentria 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.8 evHVACAsentriaUnitEntry OBJECT-TYPE SYNTAX HVACAsentriaUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Asentria HVAC unit table entry" INDEX { evHVACAsentriaUnitIndex } ::= { evHVACAsentriaUnitTable 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1 evHVACAsentriaUnitIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Asentria HVAC unit" ::= { evHVACAsentriaUnitEntry 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.1 evHVACAsentriaUnitEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC unit enable" ::= { evHVACAsentriaUnitEntry 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.2 evHVACAsentriaUnitFanRelayES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control the fan on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.3 evHVACAsentriaUnitFanRelayPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control the fan on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.4 evHVACAsentriaUnitVentRelayES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control the vent on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.5 evHVACAsentriaUnitVentRelayPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control the vent on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.6 evHVACAsentriaUnitTimereset OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Resets the time counter for Asentria HVAC unit" ::= { evHVACAsentriaUnitEntry 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.7 evHVACAsentriaSeqTimereset OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Resets the time counter for Asentria HVAC sequence number" ::= { evHVACAsentriaUnitEntry 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.8 evHVACAsentriaUnitStage1CoolES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control compressor stage 1 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 20 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.20 evHVACAsentriaUnitStage1CoolPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control compressor stage 1 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 21 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.21 evHVACAsentriaUnitStage1HeatES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control heater stage 1 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 22 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.22 evHVACAsentriaUnitStage1HeatPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control heater stage 1 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 23 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.23 evHVACAsentriaUnitStage2CoolES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control compressor stage 2 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 30 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.30 evHVACAsentriaUnitStage2CoolPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control compressor stage 2 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 31 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.31 evHVACAsentriaUnitStage2HeatES OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EventSensor number of relay to control heater stage 2 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 32 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.32 evHVACAsentriaUnitStage2HeatPT OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Point number of relay to control heater stage 2 on Asentria HVAC controller" ::= { evHVACAsentriaUnitEntry 33 } --1.3.6.1.4.1.3052.10.2.12.19.3.8.1.33 evHVACAsentriaTempScale OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC controller temperature scale" ::= { evHVACAsentriaTemp 1 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.1 evHVACAsentriaTempCoolThresh OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature above this threshold before cooling via Asentria HVAC controller" ::= { evHVACAsentriaTemp 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.2 evHVACAsentriaTempHeatThresh OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature below this threshold before heating via Asentria HVAC controller" ::= { evHVACAsentriaTemp 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.3 evHVACAsentriaTempEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm enable" ::= { evHVACAsentriaTemp 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.4 evHVACAsentriaTempEventDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event deadband" ::= { evHVACAsentriaTemp 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.5 evHVACAsentriaTempVLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very low value" ::= { evHVACAsentriaTemp 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.6 evHVACAsentriaTempVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very low actions" ::= { evHVACAsentriaTemp 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.7 evHVACAsentriaTempVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very low trap number" ::= { evHVACAsentriaTemp 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.8 evHVACAsentriaTempVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very low class" ::= { evHVACAsentriaTemp 9 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.9 evHVACAsentriaTempLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event low value" ::= { evHVACAsentriaTemp 10 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.10 evHVACAsentriaTempLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event low actions" ::= { evHVACAsentriaTemp 11 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.11 evHVACAsentriaTempLowTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event low trap number" ::= { evHVACAsentriaTemp 12 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.12 evHVACAsentriaTempLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event low class" ::= { evHVACAsentriaTemp 13 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.13 evHVACAsentriaTempNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event return to normal actions" ::= { evHVACAsentriaTemp 14 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.14 evHVACAsentriaTempNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event return to normal trap number" ::= { evHVACAsentriaTemp 15 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.15 evHVACAsentriaTempNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event return to normal class" ::= { evHVACAsentriaTemp 16 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.16 evHVACAsentriaTempHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event high value" ::= { evHVACAsentriaTemp 17 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.17 evHVACAsentriaTempHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event high actions" ::= { evHVACAsentriaTemp 18 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.18 evHVACAsentriaTempHighTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event high trap number" ::= { evHVACAsentriaTemp 19 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.19 evHVACAsentriaTempHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event high class" ::= { evHVACAsentriaTemp 20 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.20 evHVACAsentriaTempVHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very high value" ::= { evHVACAsentriaTemp 21 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.21 evHVACAsentriaTempVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very high actions" ::= { evHVACAsentriaTemp 22 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.22 evHVACAsentriaTempVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very high trap number" ::= { evHVACAsentriaTemp 23 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.23 evHVACAsentriaTempVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature alarm event very high class" ::= { evHVACAsentriaTemp 24 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.24 evHVACAsentriaTempDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature deadband before stopping current state" ::= { evHVACAsentriaTemp 25 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.25 evHVACAsentriaTempDifference OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC temperature step before changing states" ::= { evHVACAsentriaTemp 26 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.26 evHVACAsentriaHumidInThresh OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Humidity above this threshold before cooling via Asentria HVAC controller" ::= { evHVACAsentriaHumid 2 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.2 evHVACAsentriaHumidOutThresh OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Humidity above this threshold before not allowing venting via Asentria HVAC controller" ::= { evHVACAsentriaHumid 3 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.3 evHVACAsentriaHumidEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm enable" ::= { evHVACAsentriaHumid 4 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.4 evHVACAsentriaHumidEventDeadband OBJECT-TYPE SYNTAX Integer32 (1..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event deadband" ::= { evHVACAsentriaHumid 5 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.5 evHVACAsentriaHumidVLowValue OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very low value" ::= { evHVACAsentriaHumid 6 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.6 evHVACAsentriaHumidVLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very low actions" ::= { evHVACAsentriaHumid 7 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.7 evHVACAsentriaHumidVLowTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very low trap number" ::= { evHVACAsentriaHumid 8 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.8 evHVACAsentriaHumidVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very low class" ::= { evHVACAsentriaHumid 9 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.9 evHVACAsentriaHumidLowValue OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event low value" ::= { evHVACAsentriaHumid 10 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.10 evHVACAsentriaHumidLowActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event low actions" ::= { evHVACAsentriaHumid 11 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.11 evHVACAsentriaHumidLowTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event low trap number" ::= { evHVACAsentriaHumid 12 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.12 evHVACAsentriaHumidLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event low class" ::= { evHVACAsentriaHumid 13 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.13 evHVACAsentriaHumidNormalActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event return to normal actions" ::= { evHVACAsentriaHumid 14 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.14 evHVACAsentriaHumidNormalTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event return to normal trap number" ::= { evHVACAsentriaHumid 15 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.15 evHVACAsentriaHumidNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event return to normal class" ::= { evHVACAsentriaHumid 16 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.16 evHVACAsentriaHumidHighValue OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event high value" ::= { evHVACAsentriaHumid 17 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.17 evHVACAsentriaHumidHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event high actions" ::= { evHVACAsentriaHumid 18 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.18 evHVACAsentriaHumidHighTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event high trap number" ::= { evHVACAsentriaHumid 19 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.19 evHVACAsentriaHumidHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event high class" ::= { evHVACAsentriaHumid 20 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.20 evHVACAsentriaHumidVHighValue OBJECT-TYPE SYNTAX Integer32 (0..100) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very high value" ::= { evHVACAsentriaHumid 21 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.21 evHVACAsentriaHumidVHighActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very high actions" ::= { evHVACAsentriaHumid 22 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.22 evHVACAsentriaHumidVHighTrapNum OBJECT-TYPE SYNTAX Integer32 (545..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very high trap number" ::= { evHVACAsentriaHumid 23 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.23 evHVACAsentriaHumidVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity alarm event very high class" ::= { evHVACAsentriaHumid 24 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.24 evHVACAsentriaHumidDeadband OBJECT-TYPE SYNTAX Integer32 (1..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity deadband before stopping current state" ::= { evHVACAsentriaHumid 25 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.25 evHVACAsentriaHumidDifference OBJECT-TYPE SYNTAX Integer32 (1..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Asentria HVAC humidity step before changing states" ::= { evHVACAsentriaHumid 26 } --1.3.6.1.4.1.3052.10.2.12.19.3.9.26 --*************************************************************************************** --Airsys HVAC Configuration Section 2.12.19.4 --*************************************************************************************** evHVACAirsysGeneratorLogic OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC generator logic" ::= { evHVACAirsysGeneral 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.1.1 evHVACAirsysFreeMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC free mode" ::= { evHVACAirsysGeneral 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.1.2 evHVACAirsysRemoteEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC remote control enable" ::= { evHVACAirsysGeneral 3 } --1.3.6.1.4.1.3052.10.2.12.19.4.1.3 evHVACAirsysHVACRotation OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC rotate unit lead/lag" ::= { evHVACAirsysGeneral 4 } --1.3.6.1.4.1.3052.10.2.12.19.4.1.4 evHVACAirsysRotationRuntime OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC rotation runtime period" ::= { evHVACAirsysGeneral 5 } --1.3.6.1.4.1.3052.10.2.12.19.4.1.5 evHVACAirsysUnitTable OBJECT-TYPE SYNTAX SEQUENCE OF HVACAirsysUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit table" ::= { evHVACAirsysAlarm 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1 evHVACAirsysUnitEntry OBJECT-TYPE SYNTAX HVACAirsysUnit MAX-ACCESS not-accessible STATUS current DESCRIPTION "Airsys HVAC unit table entry" INDEX { evHVACAirsysUnitIndex } ::= { evHVACAirsysUnitTable 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1 evHVACAirsysUnitIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for Airsys HVAC unit" ::= { evHVACAirsysUnitEntry 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.1 evHVACAirsysULowPEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit low pressure alarm enable" ::= { evHVACAirsysUnitEntry 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.2 evHVACAirsysULowPActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 3 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.3 evHVACAirsysULowPTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 4 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.4 evHVACAirsysULowPClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 5 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.5 evHVACAirsysULowPNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 6 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.6 evHVACAirsysULowPNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 7 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.7 evHVACAirsysULowPNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for low pressure alarm notification" ::= { evHVACAirsysUnitEntry 8 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.8 evHVACAirsysUHighPEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit high pressure alarm enable" ::= { evHVACAirsysUnitEntry 9 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.9 evHVACAirsysUHighPActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 10 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.10 evHVACAirsysUHighPTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 11 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.11 evHVACAirsysUHighPClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 12 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.12 evHVACAirsysUHighPNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 13 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.13 evHVACAirsysUHighPNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 14 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.14 evHVACAirsysUHighPNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 15 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.15 evHVACAirsysUEvapFanEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit evaporator fan alarm enable" ::= { evHVACAirsysUnitEntry 16 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.16 evHVACAirsysUEvapFanActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 17 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.17 evHVACAirsysUEvapFanTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 18 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.18 evHVACAirsysUEvapFanClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 19 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.19 evHVACAirsysUEvapFanNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 20 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.20 evHVACAirsysUEvapFanNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 21 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.21 evHVACAirsysUEvapFanNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for evaporator fan alarm notification" ::= { evHVACAirsysUnitEntry 22 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.22 evHVACAirsysUDirtyEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit dirty filter alarm enable" ::= { evHVACAirsysUnitEntry 23 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.23 evHVACAirsysUDirtyActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 24 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.24 evHVACAirsysUDirtyTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 25 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.25 evHVACAirsysUDirtyClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 26 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.26 evHVACAirsysUDirtyNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 27 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.27 evHVACAirsysUDirtyNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 28 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.28 evHVACAirsysUDirtyNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for dirty filter alarm notification" ::= { evHVACAirsysUnitEntry 29 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.29 evHVACAirsysUInProbeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit indoor probe broken alarm enable" ::= { evHVACAirsysUnitEntry 30 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.30 evHVACAirsysUInProbeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 31 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.31 evHVACAirsysUInProbeTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 32 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.32 evHVACAirsysUInProbeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 33 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.33 evHVACAirsysUInProbeNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 34 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.34 evHVACAirsysUInProbeNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 35 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.35 evHVACAirsysUInProbeNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for indoor probe broken alarm notification" ::= { evHVACAirsysUnitEntry 36 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.36 evHVACAirsysUDamperEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit high pressure alarm enable" ::= { evHVACAirsysUnitEntry 37 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.37 evHVACAirsysUDamperActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 38 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.38 evHVACAirsysUDamperTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 39 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.39 evHVACAirsysUDamperClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 40 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.40 evHVACAirsysUDamperNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 41 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.41 evHVACAirsysUDamperNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 42 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.42 evHVACAirsysUDamperNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for high pressure alarm notification" ::= { evHVACAirsysUnitEntry 43 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.43 evHVACAirsysUSupProbeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit supply probe broken alarm enable" ::= { evHVACAirsysUnitEntry 44 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.44 evHVACAirsysUSupProbeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 45 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.45 evHVACAirsysUSupProbeTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 46 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.46 evHVACAirsysUSupProbeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 47 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.47 evHVACAirsysUSupProbeNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 48 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.48 evHVACAirsysUSupProbeNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 49 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.49 evHVACAirsysUSupProbeNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for supply probe broken alarm notification" ::= { evHVACAirsysUnitEntry 50 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.1.1.50 evHVACAirsysSmokeFireEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit smoke/fire alarm enable" ::= { evHVACAirsysAlarm 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.2 evHVACAirsysSmokeFireActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 3 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.3 evHVACAirsysSmokeFireTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 4 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.4 evHVACAirsysSmokeFireClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 5 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.5 evHVACAirsysSmokeFireNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 6 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.6 evHVACAirsysSmokeFireNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 7 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.7 evHVACAirsysSmokeFireNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for smoke/fire alarm notification" ::= { evHVACAirsysAlarm 8 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.8 evHVACAirsysLowRoomTempEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit low room temperature alarm enable" ::= { evHVACAirsysAlarm 9 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.9 evHVACAirsysLowRoomTempActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for low room temperature alarm notification" ::= { evHVACAirsysAlarm 10 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.10 evHVACAirsysLowRoomTempTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for low room temperature alarm notification" ::= { evHVACAirsysAlarm 11 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.11 evHVACAirsysLowRoomTempClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for low room temperature alarm notification" ::= { evHVACAirsysAlarm 12 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.12 evHVACAirsysLowRoomTempNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for low room temperature alarm notification" ::= { evHVACAirsysAlarm 13 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.13 evHVACAirsysLowRoomTempNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for low room temperature alarm notification" ::= { evHVACAirsysAlarm 14 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.14 evHVACAirsysLowRoomTempNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for low room temperature alarm notification" ::= { evHVACAirsysAlarm 15 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.15 evHVACAirsysHighRoomTempEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit high room temperature alarm enable" ::= { evHVACAirsysAlarm 16 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.16 evHVACAirsysHighRoomTempActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for high room temperature alarm notification" ::= { evHVACAirsysAlarm 17 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.17 evHVACAirsysHighRoomTempTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for high room temperature alarm notification" ::= { evHVACAirsysAlarm 18 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.18 evHVACAirsysHighRoomTempClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for high room temperature alarm notification" ::= { evHVACAirsysAlarm 19 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.19 evHVACAirsysHighRoomTempNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for high room temperature alarm notification" ::= { evHVACAirsysAlarm 20 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.20 evHVACAirsysHighRoomTempNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for high room temperature alarm notification" ::= { evHVACAirsysAlarm 21 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.21 evHVACAirsysHighRoomTempNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for high room temperature alarm notification" ::= { evHVACAirsysAlarm 22 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.22 evHVACAirsysPowerEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit power failure alarm enable" ::= { evHVACAirsysAlarm 23 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.23 evHVACAirsysPowerActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for power failure alarm notification" ::= { evHVACAirsysAlarm 24 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.24 evHVACAirsysPowerTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for power failure alarm notification" ::= { evHVACAirsysAlarm 25 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.25 evHVACAirsysPowerClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for power failure alarm notification" ::= { evHVACAirsysAlarm 26 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.26 evHVACAirsysPowerNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for power failure alarm notification" ::= { evHVACAirsysAlarm 27 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.27 evHVACAirsysPowerNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for power failure alarm notification" ::= { evHVACAirsysAlarm 28 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.28 evHVACAirsysPowerNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for power failure alarm notification" ::= { evHVACAirsysAlarm 29 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.29 evHVACAirsyspLANEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit pLAN alarm enable" ::= { evHVACAirsysAlarm 30 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.30 evHVACAirsyspLANActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for pLAN alarm notification" ::= { evHVACAirsysAlarm 31 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.31 evHVACAirsyspLANTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for pLAN alarm notification" ::= { evHVACAirsysAlarm 32 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.32 evHVACAirsyspLANClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for pLAN alarm notification" ::= { evHVACAirsysAlarm 33 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.33 evHVACAirsyspLANNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for pLAN alarm notification" ::= { evHVACAirsysAlarm 34 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.34 evHVACAirsyspLANNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for pLAN alarm notification" ::= { evHVACAirsysAlarm 35 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.35 evHVACAirsyspLANNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for pLAN alarm notification" ::= { evHVACAirsysAlarm 36 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.36 evHVACAirsysClockEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit clock alarm enable" ::= { evHVACAirsysAlarm 37 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.37 evHVACAirsysClockActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for clock alarm notification" ::= { evHVACAirsysAlarm 38 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.38 evHVACAirsysClockTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for clock alarm notification" ::= { evHVACAirsysAlarm 39 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.39 evHVACAirsysClockClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for clock alarm notification" ::= { evHVACAirsysAlarm 40 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.40 evHVACAirsysClockNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for clock alarm notification" ::= { evHVACAirsysAlarm 41 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.41 evHVACAirsysClockNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for clock alarm notification" ::= { evHVACAirsysAlarm 42 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.42 evHVACAirsysClockNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for clock alarm notification" ::= { evHVACAirsysAlarm 43 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.43 evHVACAirsysHumidProbeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit humidity probe broken alarm enable" ::= { evHVACAirsysAlarm 44 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.44 evHVACAirsysHumidProbeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 45 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.45 evHVACAirsysHumidProbeTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 46 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.46 evHVACAirsysHumidProbeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 47 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.47 evHVACAirsysHumidProbeNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 48 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.48 evHVACAirsysHumidProbeNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 49 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.49 evHVACAirsysHumidProbeNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for humidity probe broken alarm notification" ::= { evHVACAirsysAlarm 50 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.50 evHVACAirsysOutProbeEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit outdoor probe broken alarm enable" ::= { evHVACAirsysAlarm 51 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.51 evHVACAirsysOutProbeActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 52 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.52 evHVACAirsysOutProbeTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 53 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.53 evHVACAirsysOutProbeClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 54 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.54 evHVACAirsysOutProbeNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 55 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.55 evHVACAirsysOutProbeNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 56 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.56 evHVACAirsysOutProbeNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for outdoor probe broken alarm notification" ::= { evHVACAirsysAlarm 57 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.57 evHVACAirsysBothCompressEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit both compressors on alarm enable" ::= { evHVACAirsysAlarm 58 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.58 evHVACAirsysBothCompressActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for both compressors on alarm notification" ::= { evHVACAirsysAlarm 59 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.59 evHVACAirsysBothCompressTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for both compressors on alarm notification" ::= { evHVACAirsysAlarm 60 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.60 evHVACAirsysBothCompressClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for both compressors on alarm notification" ::= { evHVACAirsysAlarm 61 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.61 evHVACAirsysBothCompressNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for both compressors on alarm notification" ::= { evHVACAirsysAlarm 62 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.62 evHVACAirsysBothCompressNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for both compressors on alarm notification" ::= { evHVACAirsysAlarm 63 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.63 evHVACAirsysBothCompressNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for both compressors on alarm notification" ::= { evHVACAirsysAlarm 64 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.64 evHVACAirsysGeneratorEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit generator running alarm enable" ::= { evHVACAirsysAlarm 65 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.65 evHVACAirsysGeneratorActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for generator running alarm notification" ::= { evHVACAirsysAlarm 66 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.66 evHVACAirsysGeneratorTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for generator running alarm notification" ::= { evHVACAirsysAlarm 67 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.67 evHVACAirsysGeneratorClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for generator running alarm notification" ::= { evHVACAirsysAlarm 68 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.68 evHVACAirsysGeneratorNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for generator running alarm notification" ::= { evHVACAirsysAlarm 69 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.69 evHVACAirsysGeneratorNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for generator running alarm notification" ::= { evHVACAirsysAlarm 70 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.70 evHVACAirsysGeneratorNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for generator running alarm notification" ::= { evHVACAirsysAlarm 71 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.71 evHVACAirsysConnectionEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC unit lost connection alarm enable" ::= { evHVACAirsysAlarm 72 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.72 evHVACAirsysConnectionActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC actions to perform for lost connection alarm notification" ::= { evHVACAirsysAlarm 73 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.73 evHVACAirsysConnectionTrapnum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC trap number for lost connection alarm notification" ::= { evHVACAirsysAlarm 74 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.74 evHVACAirsysConnectionClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC alarm class for lost connection alarm notification" ::= { evHVACAirsysAlarm 75 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.75 evHVACAirsysConnectionNormActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal actions to perform for lost connection alarm notification" ::= { evHVACAirsysAlarm 76 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.76 evHVACAirsysConnectionNormTrapNum OBJECT-TYPE SYNTAX Integer32 (548..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal trap number for lost connection alarm notification" ::= { evHVACAirsysAlarm 77 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.77 evHVACAirsysConnectionNormClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for lost connection alarm notification" ::= { evHVACAirsysAlarm 78 } --1.3.6.1.4.1.3052.10.2.12.19.4.2.78 evHVACAirsysTempBaseThresh OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC temperature base threshold" ::= { evHVACAirsysTemp 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.3.1 evHVACAirsysTempCoolDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC temperature cool deadband" ::= { evHVACAirsysTemp 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.3.2 evHVACAirsysTempHeatDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC temperature heat deadband" ::= { evHVACAirsysTemp 3 } --1.3.6.1.4.1.3052.10.2.12.19.4.3.3 evHVACAirsysTempHighValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC high temperature alarm value" ::= { evHVACAirsysTemp 4 } --1.3.6.1.4.1.3052.10.2.12.19.4.3.4 evHVACAirsysTempLowValue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC low temperature alarm value" ::= { evHVACAirsysTemp 5 } --1.3.6.1.4.1.3052.10.2.12.19.4.3.5 evHVACAirsysHumidMaxFree OBJECT-TYPE SYNTAX Integer32 (0..99) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for lost connection alarm notification" ::= { evHVACAirsysHumid 1 } --1.3.6.1.4.1.3052.10.2.12.19.4.4.1 evHVACAirsysHumidDeadband OBJECT-TYPE SYNTAX Integer32 (0..99) MAX-ACCESS read-write STATUS current DESCRIPTION "Airsys HVAC return to normal class for lost connection alarm notification" ::= { evHVACAirsysHumid 2 } --1.3.6.1.4.1.3052.10.2.12.19.4.4.2 --*************************************************************************************** --EVPS Section 2.12.20 --*************************************************************************************** evpsEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EVPS (Emerson Vortex Power System) enable." ::= { evEvps 1 } --1.3.6.1.4.1.3052.10.2.12.20.1 evpsIPAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "EVPS IP address." ::= { evEvps 2 } --1.3.6.1.4.1.3052.10.2.12.20.2 evpsPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "EVPS IP web port." ::= { evEvps 3 } --1.3.6.1.4.1.3052.10.2.12.20.3 evpsTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "EVPS IP timeout." ::= { evEvps 4 } --1.3.6.1.4.1.3052.10.2.12.20.4 --*************************************************************************************** --Access Control Device Management Section 2.12.21 --*************************************************************************************** acActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for the access control event." ::= { accessControl 2 } --1.3.6.1.4.1.3052.10.2.12.21.2 acTrapnum OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for the access control event." ::= { accessControl 3 } --1.3.6.1.4.1.3052.10.2.12.21.3 acClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for the access control event." ::= { accessControl 4 } --1.3.6.1.4.1.3052.10.2.12.21.4 accessControlDeviceTable OBJECT-TYPE SYNTAX SEQUENCE OF AccessControlDevice MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of access control devices for Access Control Device Management." ::= { accessControl 10 } --1.3.6.1.4.1.3052.10.2.12.21.10 accessControlDeviceEntry OBJECT-TYPE SYNTAX AccessControlDevice MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of access control devices for Access Control Device Management." INDEX { acdIndex } ::= { accessControlDeviceTable 1 } --1.3.6.1.4.1.3052.10.2.12.21.10.1 acdIndex OBJECT-TYPE SYNTAX Integer32 (1..3) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of access control devices for Access Control Device Management." ::= { accessControlDeviceEntry 1 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.1 acdEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable management for this access control device." ::= { accessControlDeviceEntry 2 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.2 acdName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of the access control device for informational purpose only." ::= { accessControlDeviceEntry 3 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.3 acdReader OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The kind of access control device." ::= { accessControlDeviceEntry 4 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.4 acdWiegandES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Index of the Wiegand interface hardware instance allocated as the access control device." ::= { accessControlDeviceEntry 5 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.5 acdWiegandPoint OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-write STATUS current DESCRIPTION "Which wiegand on the wiegand EventSensor to use for as the access control device." ::= { accessControlDeviceEntry 6 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.6 acdRelayType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Type of relay which activates the door strike." ::= { accessControlDeviceEntry 7 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.7 acdRelayES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay EventSensor is connected to the door strike." ::= { accessControlDeviceEntry 8 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.8 acdRelayPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay on the relay EventSensor is connected to the door strike." ::= { accessControlDeviceEntry 9 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.9 acdOpenTime OBJECT-TYPE SYNTAX Integer32 (1..25) MAX-ACCESS read-write STATUS current DESCRIPTION "" ::= { accessControlDeviceEntry 10 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.10 acdUserGroup OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-write STATUS current DESCRIPTION "User group to which this access control device applies." ::= { accessControlDeviceEntry 11 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.11 accessControlUserTable OBJECT-TYPE SYNTAX SEQUENCE OF AccessControlUser MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of access control users for Access Control Device Management." ::= { accessControl 11 } --1.3.6.1.4.1.3052.10.2.12.21.11 accessControlUserEntry OBJECT-TYPE SYNTAX AccessControlUser MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of access control users for Access Control Device Management." INDEX { acuIndexUserGroup, acuIndexUser } ::= { accessControlUserTable 1 } --1.3.6.1.4.1.3052.10.2.12.21.11.1 acuIndexUserGroup OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of access control devices for Access Control Device Management which corresponds to the user group containing the user." ::= { accessControlUserEntry 1 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.1 acuIndexUser OBJECT-TYPE SYNTAX Integer32 (1..50) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of access control devices for Access Control Device Management which corresponds to the user within the user group." ::= { accessControlUserEntry 2 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.2 acuEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable this access control user." ::= { accessControlUserEntry 3 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.3 acuName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this access control user." ::= { accessControlUserEntry 4 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.4 acuSn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial number of the card associated with the user." ::= { accessControlUserEntry 5 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.5 acuSunBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Sundays when this user should be granted access." ::= { accessControlUserEntry 6 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.6 acuSunEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Sundays when this user should be forbidden access." ::= { accessControlUserEntry 7 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.7 acuMonBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Mondays when this user should be granted access." ::= { accessControlUserEntry 8 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.8 acuMonEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Mondays when this user should be forbidden access." ::= { accessControlUserEntry 9 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.9 acuTueBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Tuesdays when this user should be granted access." ::= { accessControlUserEntry 10 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.10 acuTueEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Tuesdays when this user should be forbidden access." ::= { accessControlUserEntry 11 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.11 acuWedBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Wednesdays when this user should be granted access." ::= { accessControlUserEntry 12 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.12 acuWedEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Wednesdays when this user should be forbidden access." ::= { accessControlUserEntry 13 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.13 acuThuBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Thursdays when this user should be granted access." ::= { accessControlUserEntry 14 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.14 acuThuEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Thursdays when this user should be forbidden access." ::= { accessControlUserEntry 15 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.15 acuFriBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Fridays when this user should be granted access." ::= { accessControlUserEntry 16 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.16 acuFriEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Fridays when this user should be forbidden access." ::= { accessControlUserEntry 17 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.17 acuSatBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Saturdays when this user should be granted access." ::= { accessControlUserEntry 18 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.18 acuSatEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) on Saturdays when this user should be forbidden access." ::= { accessControlUserEntry 19 } --1.3.6.1.4.1.3052.10.2.12.21.10.1.19 --*************************************************************************************** --Telemetry Section 2.12.22 --*************************************************************************************** telemetryTable OBJECT-TYPE SYNTAX SEQUENCE OF TelemetryPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { telemetry 1 } --1.3.6.1.4.1.3052.10.2.12.22.1 telemetryEntry OBJECT-TYPE SYNTAX TelemetryPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of telemetry points" INDEX { telemetryPointIndex } ::= { telemetryTable 1 } --1.3.6.1.4.1.3052.10.2.12.22.1.1 telemetryPointIndex OBJECT-TYPE SYNTAX Integer32 (1..256) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of telemetry points." ::= { telemetryEntry 1 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.1 telemetryPointName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of telemetry point for information purpose only." ::= { telemetryEntry 2 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.2 telemetryPointKey OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Key for telemetry point that specifies the telemetry data source." ::= { telemetryEntry 3 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.3 telemetryPointType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 type for telemetry point" ::= { telemetryEntry 4 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.4 telemetryPointClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "DNP3 class for telemetry point" ::= { telemetryEntry 5 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.5 telemetryPointDeadband OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for telemetry point" ::= { telemetryEntry 6 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.6 telemetryPointShortcode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Shortcode for telemetry point" ::= { telemetryEntry 7 } --1.3.6.1.4.1.3052.10.2.12.22.1.1.7 --*************************************************************************************** --Site Security Section 2.12.23 --*************************************************************************************** siteSecIntrusionTable OBJECT-TYPE SYNTAX SEQUENCE OF SiteSecIntrusion MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of for Site Security" ::= { siteSecurity 1 } --1.3.6.1.4.1.3052.10.2.12.23.1 siteSecEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Security zone 1 to 10 is ON or OFF stating that a zone is configured properly" ::= { siteSecIntrusionTable 1 } --1.3.6.1.4.1.3052.10.2.12.23.1.1 siteSecDisarmed OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON or OFF if ON the zone will not detect intrusion because it is disarmed, OFF arms the zone to detect intrusion" ::= { siteSecIntrusionTable 2 } --1.3.6.1.4.1.3052.10.2.12.23.1.2 siteSecName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name given to the zone" ::= { siteSecIntrusionTable 3 } --1.3.6.1.4.1.3052.10.2.12.23.1.3 siteSecState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ALARM/DISARMED/DISABLED/INTRUDER/REARMING one of five states the zone is in" ::= { siteSecIntrusionTable 4 } --1.3.6.1.4.1.3052.10.2.12.23.1.4 siteSecSensorES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "The Event Sensors related to a particular zone" ::= { siteSecIntrusionTable 5 } --1.3.6.1.4.1.3052.10.2.12.23.1.5 siteSecSensorPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "The point in conjunction with event-sensor and zone" ::= { siteSecIntrusionTable 6 } --1.3.6.1.4.1.3052.10.2.12.23.1.6 siteSecIntrusionThreshold OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait for a disarm event" ::= { siteSecIntrusionTable 7 } --1.3.6.1.4.1.3052.10.2.12.23.1.7 siteSecReader OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Comma separated string of readers that disarms a zone" ::= { siteSecIntrusionTable 8 } --1.3.6.1.4.1.3052.10.2.12.23.1.8 siteSecReaderThreshold OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "The number of seconds a user has to disable a detected intrusion via the reader configured for the zone" ::= { siteSecIntrusionTable 9 } --1.3.6.1.4.1.3052.10.2.12.23.1.9 siteSecButtonEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Button to disable an alarm is PRESENT/NOT PRESENT" ::= { siteSecIntrusionTable 10 } --1.3.6.1.4.1.3052.10.2.12.23.1.10 siteSecButtonES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Configured event-sensor for the Site-Security button" ::= { siteSecIntrusionTable 11 } --1.3.6.1.4.1.3052.10.2.12.23.1.11 siteSecButtonPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Configured pont for the Site-Security button" ::= { siteSecIntrusionTable 12 } --1.3.6.1.4.1.3052.10.2.12.23.1.12 siteSecButtonType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Button type configured : MOMENTARY/TOGGLE" ::= { siteSecIntrusionTable 13 } --1.3.6.1.4.1.3052.10.2.12.23.1.13 siteSecButtonThresholdArm OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to hold button to arm a zone" ::= { siteSecIntrusionTable 14 } --1.3.6.1.4.1.3052.10.2.12.23.1.14 siteSecButtonThresholdDisarm OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to hold button to disarm a zone" ::= { siteSecIntrusionTable 15 } --1.3.6.1.4.1.3052.10.2.12.23.1.15 siteSecSirenEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable realy output for siren" ::= { siteSecIntrusionTable 16 } --1.3.6.1.4.1.3052.10.2.12.23.1.16 siteSecSirenES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Event-sensor relay location of siren for the zone" ::= { siteSecIntrusionTable 17 } --1.3.6.1.4.1.3052.10.2.12.23.1.17 siteSecSirenPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Event-sensor point location of siren for the zone" ::= { siteSecIntrusionTable 18 } --1.3.6.1.4.1.3052.10.2.12.23.1.18 siteSecRearmDelay OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "A delay in seconds after a rearm event before the site is actually rearmed" ::= { siteSecIntrusionTable 19 } --1.3.6.1.4.1.3052.10.2.12.23.1.19 siteSecMotionTable OBJECT-TYPE SYNTAX SEQUENCE OF SiteSecMotion MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of for Site Security motion sensors" ::= { siteSecurity 2 } --1.3.6.1.4.1.3052.10.2.12.23.2 siteSecMotionES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Event-sensor for motion detection device" ::= { siteSecMotionTable 1 } --1.3.6.1.4.1.3052.10.2.12.23.2.1 siteSecMotionPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Point for event-sensor motion detection device" ::= { siteSecMotionTable 2 } --1.3.6.1.4.1.3052.10.2.12.23.2.2 siteSecMotionEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable or disable motion alarm" ::= { siteSecMotionTable 3 } --1.3.6.1.4.1.3052.10.2.12.23.2.3 siteSecMotionName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of the motion sensor" ::= { siteSecMotionTable 4 } --1.3.6.1.4.1.3052.10.2.12.23.2.4 siteSecMotionThresholdRearm OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "A threshold to wait for no motion before rearming" ::= { siteSecMotionTable 5 } --1.3.6.1.4.1.3052.10.2.12.23.2.5 siteSecDoorAjarTable OBJECT-TYPE SYNTAX SEQUENCE OF SiteSecDoorAjar MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of for Site Security Door Ajar sensors" ::= { siteSecurity 3 } --1.3.6.1.4.1.3052.10.2.12.23.3 siteSecDoorAjarEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable or disable door ajar sensor" ::= { siteSecDoorAjarTable 1 } --1.3.6.1.4.1.3052.10.2.12.23.3.1 siteSecDoorAjarName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for the door ajar sensor" ::= { siteSecDoorAjarTable 2 } --1.3.6.1.4.1.3052.10.2.12.23.3.2 siteSecDoorAjarES OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Event-sensor for door ajar detection device" ::= { siteSecDoorAjarTable 3 } --1.3.6.1.4.1.3052.10.2.12.23.3.3 siteSecDoorAjarPoint OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Point for event-sensor door ajar detection device" ::= { siteSecDoorAjarTable 4 } --1.3.6.1.4.1.3052.10.2.12.23.3.4 siteSecDoorAjarThresholdNormal OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold to wait in seconds before tripping the door ajar alarm " ::= { siteSecDoorAjarTable 5 } --1.3.6.1.4.1.3052.10.2.12.23.3.5 siteSecDoorAjarThresholdExtraTime OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Extra seconds added to the door ajar threshold for disabled person before door ajar alarm is set" ::= { siteSecDoorAjarTable 6 } --1.3.6.1.4.1.3052.10.2.12.23.3.6 --*************************************************************************************** --Action Section 2.14 --*************************************************************************************** actionCallNumberTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionCallNumberConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of phone numbers to dial for modem actions" ::= { action 1 } --1.3.6.1.4.1.3052.10.2.14.1 actionCallNumberEntry OBJECT-TYPE SYNTAX ActionCallNumberConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of phone numbers to dial for modem actions" INDEX { actionCallNumberIndex } ::= { actionCallNumberTable 1 } --1.3.6.1.4.1.3052.10.2.14.1.1 actionCallNumberIndex OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of phone numbers to dial for modem actions" ::= { actionCallNumberEntry 1 } --1.3.6.1.4.1.3052.10.2.14.1.1.1 actionCallNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The number to dial for this action slot" ::= { actionCallNumberEntry 2 } --1.3.6.1.4.1.3052.10.2.14.1.1.2 actionPagerTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionPagerConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of pager configurations" ::= { action 2 } --1.3.6.1.4.1.3052.10.2.14.2 actionPagerEntry OBJECT-TYPE SYNTAX ActionPagerConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of pager configurations" INDEX { actionPagerIndex } ::= { actionPagerTable 1 } --1.3.6.1.4.1.3052.10.2.14.2.1 actionPagerIndex OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "index for table of pager configurations" ::= { actionPagerEntry 1 } --1.3.6.1.4.1.3052.10.2.14.2.1.1 actionPagerType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "type of this pager configuration" ::= { actionPagerEntry 2 } --1.3.6.1.4.1.3052.10.2.14.2.1.2 actionPagerNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "phone number to dial for this pager configuration" ::= { actionPagerEntry 3 } --1.3.6.1.4.1.3052.10.2.14.2.1.3 actionPagerID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ID to use for this pager configuration" ::= { actionPagerEntry 4 } --1.3.6.1.4.1.3052.10.2.14.2.1.4 actionPagerMessage OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "message to use for this pager configuration" ::= { actionPagerEntry 5 } --1.3.6.1.4.1.3052.10.2.14.2.1.5 actionPagerPostCalloutDelay OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait after dialing before sending ID" ::= { actionPagerEntry 6 } --1.3.6.1.4.1.3052.10.2.14.2.1.6 actionPagerPostIDDelay OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait after sending ID to send message" ::= { actionPagerEntry 7 } --1.3.6.1.4.1.3052.10.2.14.2.1.7 actionSchedEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable action schedule" ::= { actionSched 1 } --1.3.6.1.4.1.3052.10.2.14.3.1 actionSchedBegin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "action schedule begin time (HH:MM)" ::= { actionSched 2 } --1.3.6.1.4.1.3052.10.2.14.3.2 actionSchedEnd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "action schedule end time (HH:MM)" ::= { actionSched 3 } --1.3.6.1.4.1.3052.10.2.14.3.3 actionSchedWeekdaysOnly OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF whether the action schedule applies to weekdays only (ON) or all days (OFF)" ::= { actionSched 4 } --1.3.6.1.4.1.3052.10.2.14.3.4 actionAsentriaRequireAck OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Asentria action requires an ack from the receiver" ::= { actionAsentria 1 } --1.3.6.1.4.1.3052.10.2.14.4.1 actionAsentriaVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "version 1.0 or 1.1" ::= { actionAsentria 2 } --1.3.6.1.4.1.3052.10.2.14.4.2 actionAsentriaTCPPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port used for TCP-based Asentria alarms" ::= { actionAsentria 3 } --1.3.6.1.4.1.3052.10.2.14.4.3 actionHostTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionHostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of network hosts to use for network-based actions" ::= { action 6 } --1.3.6.1.4.1.3052.10.2.14.6 actionHostEntry OBJECT-TYPE SYNTAX ActionHostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of network hosts to use for network-based actions" INDEX { actionHostIndex } ::= { actionHostTable 1 } --1.3.6.1.4.1.3052.10.2.14.6.1 actionHostIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of network hosts to use for network-based actions" ::= { actionHostEntry 1 } --1.3.6.1.4.1.3052.10.2.14.6.1.1 actionHost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Hostname/IP address used as destination for network-based action (e.g., trap)" ::= { actionHostEntry 2 } --1.3.6.1.4.1.3052.10.2.14.6.1.2 actionEmailTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionEmailConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of email addresses to use for email actions" ::= { action 7 } --1.3.6.1.4.1.3052.10.2.14.7 actionEmailEntry OBJECT-TYPE SYNTAX ActionEmailConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of email addresses to use for email actions" INDEX { actionEmailIndex } ::= { actionEmailTable 1 } --1.3.6.1.4.1.3052.10.2.14.7.1 actionEmailIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of email addresses to use for email actions" ::= { actionEmailEntry 1 } --1.3.6.1.4.1.3052.10.2.14.7.1.1 actionEmail OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "email address" ::= { actionEmailEntry 2 } --1.3.6.1.4.1.3052.10.2.14.7.1.2 actionParseError OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "When a user attempts to configure an invalid action setting/ object, this object says why it was invalid." ::= { action 8 } --1.3.6.1.4.1.3052.10.2.14.8 --*************************************************************************************** --System Section 2.16 --*************************************************************************************** sysTimeAutoDST OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF automatically adjust for Daylight Savings Time" ::= { sysTime 1 } --1.3.6.1.4.1.3052.10.2.16.1.1 sysTimeGMTOffset OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Absolute value of offset (hours) from GMT of the timezone" ::= { sysTime 2 } --1.3.6.1.4.1.3052.10.2.16.1.2 sysTimeGMTDirection OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Direction (AHEAD/BEHIND) of timezone relative to GMT" ::= { sysTime 3 } --1.3.6.1.4.1.3052.10.2.16.1.3 sysTimeNetEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Network time mode" ::= { sysTimeNet 1 } --1.3.6.1.4.1.3052.10.2.16.1.4.1 sysTimeNetHostTable OBJECT-TYPE SYNTAX SEQUENCE OF NetworkTimeHostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of hosts to use for network time services" ::= { sysTimeNet 2 } --1.3.6.1.4.1.3052.10.2.16.1.4.2 sysTimeNetHostEntry OBJECT-TYPE SYNTAX NetworkTimeHostConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of hosts to use for network time services" INDEX { sysTimeNetHostIndex } ::= { sysTimeNetHostTable 1 } --1.3.6.1.4.1.3052.10.2.16.1.4.2.1 sysTimeNetHostIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of hosts to use for network time services" ::= { sysTimeNetHostEntry 1 } --1.3.6.1.4.1.3052.10.2.16.1.4.2.1.1 sysTimeNetHost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "host to use for network time services" ::= { sysTimeNetHostEntry 2 } --1.3.6.1.4.1.3052.10.2.16.1.4.2.1.2 sysPTTimeout OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Timeout (minutes) of inactivity after which a pass-through session is terminated (0 means it never terminates)" ::= { sysPT 1 } --1.3.6.1.4.1.3052.10.2.16.2.1 sysPTEndPause OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "number of 16ths of a second between escape characters received on pass-through origin IO handle that are reuired for the escape characters to register as pass-through escape characters in the pass-through escape sequence. Set to 0 to make the escape character register as part of the pass- through escape sequence without requiring a pause." ::= { sysPT 2 } --1.3.6.1.4.1.3052.10.2.16.2.2 sysPTJoinable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable joinable pass-through sessions." ::= { sysPT 3 } --1.3.6.1.4.1.3052.10.2.16.2.3 sysMTU OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum transfer unit for ethernet interfaces" ::= { sys 3 } --1.3.6.1.4.1.3052.10.2.16.3 sysAnswerString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "String displayed upon login" ::= { sys 4 } --1.3.6.1.4.1.3052.10.2.16.4 sysEventFileID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ID string for events file" ::= { sys 6 } --1.3.6.1.4.1.3052.10.2.16.6 sysEscapeCharacter OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Decimal ASCII code of the system escape character" ::= { sys 7 } --1.3.6.1.4.1.3052.10.2.16.7 sysTimeStampTimeFormat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Format of time stamp: HH:MM,HH:MM:SS,BLANK" ::= { sysTimeStamp 1 } --1.3.6.1.4.1.3052.10.2.16.8.1 sysTimeStampDateFormat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Format of date stamp: MM/DD,MM/DD/YY,MM/DD/YYYY,BLANK" ::= { sysTimeStamp 2 } --1.3.6.1.4.1.3052.10.2.16.8.2 sysTimeStampSpaceAfter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF Inlude a space after timestamp" ::= { sysTimeStamp 3 } --1.3.6.1.4.1.3052.10.2.16.8.3 sysLogMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Syslog mode: disabled, emit UDP (REMOTE), save in a rotating file set (FILE), or emit on a listening socket (SERVER)" ::= { sysLog 1 } --1.3.6.1.4.1.3052.10.2.16.9.1 sysLoghost OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Syslog host: destination machine when syslog mode is REMOTE" ::= { sysLog 2 } --1.3.6.1.4.1.3052.10.2.16.9.2 sysLogFilter OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "String describing what functions place data in the syslog" ::= { sysLog 3 } --1.3.6.1.4.1.3052.10.2.16.9.3 sysLogFileSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Size (in KB) of syslog files (when syslog mode is SERVER or FILE)" ::= { sysLog 4 } --1.3.6.1.4.1.3052.10.2.16.9.4 sysLogFileCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Number of files in syslog file set (when syslog mode is SERVER or FILE)" ::= { sysLog 5 } --1.3.6.1.4.1.3052.10.2.16.9.5 sysLogListenPort OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "TCP port on which the unit listens for a connection on which syslog data is dumped (when syslog mode is SERVER)" ::= { sysLog 6 } --1.3.6.1.4.1.3052.10.2.16.9.6 sysCRDBCapacity OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Capacity of Call Record Database (in KB)" ::= { sysCRDB 1 } --1.3.6.1.4.1.3052.10.2.16.10.1 sysCRDBPercentFull OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Percent of the CRDB used" ::= { sysCRDB 2 } --1.3.6.1.4.1.3052.10.2.16.10.2 sysCRDBFileIDTable OBJECT-TYPE SYNTAX SEQUENCE OF CRDBFileIDConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of CRDB file IDs" ::= { sysCRDB 3 } --1.3.6.1.4.1.3052.10.2.16.10.3 sysCRDBFileIDEntry OBJECT-TYPE SYNTAX CRDBFileIDConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of CRDB file IDs" INDEX { sysCRDBFileIDIndex } ::= { sysCRDBFileIDTable 1 } --1.3.6.1.4.1.3052.10.2.16.10.3.1 sysCRDBFileIDIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of CRDB file IDs" ::= { sysCRDBFileIDEntry 1 } --1.3.6.1.4.1.3052.10.2.16.10.3.1.1 sysCRDBFileID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ID of CRDB file for this port-associated file x" ::= { sysCRDBFileIDEntry 2 } --1.3.6.1.4.1.3052.10.2.16.10.3.1.2 sysCRDBFileEnforceMinTable OBJECT-TYPE SYNTAX SEQUENCE OF CRDBFileEnforceMinConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of CRDB file minimum size enforcement settings" ::= { sysCRDB 4 } --1.3.6.1.4.1.3052.10.2.16.10.4 sysCRDBFileEnforceMinEntry OBJECT-TYPE SYNTAX CRDBFileEnforceMinConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of CRDB file minimum size enforcement settings" INDEX { sysCRDBFileEnforceMinIndex } ::= { sysCRDBFileEnforceMinTable 1 } --1.3.6.1.4.1.3052.10.2.16.10.4.1 sysCRDBFileEnforceMinIndex OBJECT-TYPE SYNTAX Integer32 (1..24) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of CRDB file minimum size enforcement settings" ::= { sysCRDBFileEnforceMinEntry 1 } --1.3.6.1.4.1.3052.10.2.16.10.4.1.1 sysCRDBFileEnforceMin OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: enforce minimum size for this CRDB file x" ::= { sysCRDBFileEnforceMinEntry 2 } --1.3.6.1.4.1.3052.10.2.16.10.4.1.2 sysCharMask OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-write STATUS current DESCRIPTION "Character mask used for ignoring certain characters on serial ports when assembling data records (when port mode is ASCII)" ::= { sys 11 } --1.3.6.1.4.1.3052.10.2.16.11 sysPrompt OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Prompt to use in a commnand session" ::= { sys 12 } --1.3.6.1.4.1.3052.10.2.16.12 sysBootStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "String describing the boot status of the unit (Booted OK/ still booting" ::= { sys 13 } --1.3.6.1.4.1.3052.10.2.16.13 --*************************************************************************************** --Sys Location Section 2.16.14 --*************************************************************************************** sysLocLatitude OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Latitude portion of geographic coordinates as string" ::= { sysLoc 1 } --1.3.6.1.4.1.3052.10.2.16.14.1 sysLocLongitude OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Longitude portion of geographic coordinates as string" ::= { sysLoc 2 } --1.3.6.1.4.1.3052.10.2.16.14.2 sysLocXOffset OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "X-offset portion of geographic coordinates as string" ::= { sysLoc 3 } --1.3.6.1.4.1.3052.10.2.16.14.3 sysLocYOffset OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Y offset portion of geographic coordinates as string" ::= { sysLoc 4 } --1.3.6.1.4.1.3052.10.2.16.14.4 sysLocAngle OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Angle portion of geographic coordinates as string" ::= { sysLoc 5 } --1.3.6.1.4.1.3052.10.2.16.14.5 sysLocAltitude OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Altitude as string" ::= { sysLoc 6 } --1.3.6.1.4.1.3052.10.2.16.14.6 --*************************************************************************************** --Sys Asset Managment 2.16.15 --*************************************************************************************** sysAMManufacturer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Device manufacturer" ::= { sysAssetMgmt 1 } --1.3.6.1.4.1.3052.10.2.16.15.1 sysAMProduct OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Device product description (i.e., model or model number)" ::= { sysAssetMgmt 2 } --1.3.6.1.4.1.3052.10.2.16.15.2 sysAMSerialNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Manufacturer serial number for device" ::= { sysAssetMgmt 3 } --1.3.6.1.4.1.3052.10.2.16.15.3 sysAMHardwareOptions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Hardware options currently installed on device" ::= { sysAssetMgmt 4 } --1.3.6.1.4.1.3052.10.2.16.15.4 sysAMSoftwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Currently-running software version on device" ::= { sysAssetMgmt 5 } --1.3.6.1.4.1.3052.10.2.16.15.5 sysAMSiteName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Site Name of device (user definable, also known as the siteName object under the productIds branch." ::= { sysAssetMgmt 6 } --1.3.6.1.4.1.3052.10.2.16.15.6 --*************************************************************************************** --Sys File Transfer Section 2.16.17 --*************************************************************************************** sysFileTransferStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Start/cancel file transfer, or check transfer status. To start, set this object to 'start'. To cancel, set this object to 'cancel'. To check status, get the object" ::= { sysFileTransfer 1 } --1.3.6.1.4.1.3052.10.2.16.17.1 sysFileTransferURL OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "URL (describing protocol, host, directory, and file) on which file transfer function operates." ::= { sysFileTransfer 2 } --1.3.6.1.4.1.3052.10.2.16.17.2 sysFileTransferUsername OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Username for user account at the resource specified by sysFileTransferURL." ::= { sysFileTransfer 3 } --1.3.6.1.4.1.3052.10.2.16.17.3 sysFileTransferPassword OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Password for user account at the resource specified by sysFileTransferURL." ::= { sysFileTransfer 4 } --1.3.6.1.4.1.3052.10.2.16.17.4 --*************************************************************************************** --Sys Update Section 2.16.18 --*************************************************************************************** sysUpdateStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Check time/result of last update attempt." ::= { sysUpdate 1 } --1.3.6.1.4.1.3052.10.2.16.18.1 --*************************************************************************************** --Audit Log Section 2.17 --*************************************************************************************** auditLogEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable audit log" ::= { auditLog 1 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreResets OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores when the unit resets" ::= { auditLog 2 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreCommands OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores commands entered in a command session" ::= { auditLog 3 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreOutputs OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores output (relay output and power output) activity" ::= { auditLog 4 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreAlarmActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores action delivery activity" ::= { auditLog 5 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStorePwdFailures OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores when user was denied login" ::= { auditLog 6 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreLogins OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores when a user was allowed login" ::= { auditLog 7 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreSHSK OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores serial handshaking status (regardless of serial handshaking event)" ::= { auditLog 8 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStorePassthrough OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores pass-through activity" ::= { auditLog 9 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStoreInactivity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores when sessions expire due to inactivity" ::= { auditLog 10 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogStorePolling OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF audit log stores CRDB polling activity" ::= { auditLog 11 } --1.3.6.1.4.1.3052.10.2.17.1 auditLogMaxSize OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum size (in KB) of audit log" ::= { auditLog 12 } --1.3.6.1.4.1.3052.10.2.17.1 --*************************************************************************************** --Scripting Section 2.17 --*************************************************************************************** scrGlobalEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable scripting" ::= { scripting 1 } --1.3.6.1.4.1.3052.10.2.18.1 scrDTRCtrlPortEnableTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingDTRCtrlPortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of DTR control port enables" ::= { scripting 2 } --1.3.6.1.4.1.3052.10.2.18.2 scrDTRCtrlPortEnableEntry OBJECT-TYPE SYNTAX ScriptingDTRCtrlPortEnableConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of DTR control port enables" INDEX { scrDTRCtrlPortEnableIndex } ::= { scrDTRCtrlPortEnableTable 1 } --1.3.6.1.4.1.3052.10.2.18.2.1 scrDTRCtrlPortEnableIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of DTR control port enables" ::= { scrDTRCtrlPortEnableEntry 1 } --1.3.6.1.4.1.3052.10.2.18.2.1.1 scrDTRCtrlPortEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable DTR control of scripting for this port" ::= { scrDTRCtrlPortEnableEntry 2 } --1.3.6.1.4.1.3052.10.2.18.2.1.2 scrTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of scripts" ::= { scripting 3 } --1.3.6.1.4.1.3052.10.2.18.3 scrEntry OBJECT-TYPE SYNTAX ScriptingConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of scripts" INDEX { scrIndex } ::= { scrTable 1 } --1.3.6.1.4.1.3052.10.2.18.3.1 scrIndex OBJECT-TYPE SYNTAX Integer32 (1..20) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of scripts" ::= { scrEntry 1 } --1.3.6.1.4.1.3052.10.2.18.3.1.1 scrEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this script" ::= { scrEntry 2 } --1.3.6.1.4.1.3052.10.2.18.3.1.2 scrName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name of this script" ::= { scrEntry 3 } --1.3.6.1.4.1.3052.10.2.18.3.1.3 scrFilename OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Filename for this script" ::= { scrEntry 4 } --1.3.6.1.4.1.3052.10.2.18.3.1.4 scrRunAlways OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: this script always runs" ::= { scrEntry 5 } --1.3.6.1.4.1.3052.10.2.18.3.1.5 scrRunAtStartup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: this script runs at startup" ::= { scrEntry 6 } --1.3.6.1.4.1.3052.10.2.18.3.1.6 scrRunScheduled OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF: this script runs at a certain time of day" ::= { scrEntry 7 } --1.3.6.1.4.1.3052.10.2.18.3.1.7 scrScheduleTime OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Time of day (HH:MM) this script is scheduled to run" ::= { scrEntry 8 } --1.3.6.1.4.1.3052.10.2.18.3.1.8 scrArguments OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Arguments for this script" ::= { scrEntry 9 } --1.3.6.1.4.1.3052.10.2.18.3.1.9 scrRepeatInterval OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "How often this script runs (minutes)" ::= { scrEntry 10 } --1.3.6.1.4.1.3052.10.2.18.3.1.10 scrVolatileStringTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingVolatileString MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of volatile string settings for use in scripts." ::= { scripting 4 } --1.3.6.1.4.1.3052.10.2.18.4 scrVolatileStringEntry OBJECT-TYPE SYNTAX ScriptingVolatileString MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of volatile script string settings" INDEX { scrVolatileStringIndex } ::= { scrVolatileStringTable 1 } --1.3.6.1.4.1.3052.10.2.18.4.1 scrVolatileStringIndex OBJECT-TYPE SYNTAX Integer32 (1..50) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of volatile script string settings" ::= { scrVolatileStringEntry 1 } --1.3.6.1.4.1.3052.10.2.18.4.1.1 scrVolatileString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Volatile string for use in scripts. Use this object to cache frequently-changing string values or string values that do not need to persist through reset. This object corresponds to the scripting.vstring[] setting key branch; use those keys in scripts and you can view or change their values with this object." ::= { scrVolatileStringEntry 2 } --1.3.6.1.4.1.3052.10.2.18.4.1.2 scrVolatileIntTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingVolatileInt MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of volatile integer settings for use in scripts." ::= { scripting 5 } --1.3.6.1.4.1.3052.10.2.18.5 scrVolatileIntEntry OBJECT-TYPE SYNTAX ScriptingVolatileInt MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of volatile script integer settings" INDEX { scrVolatileIntIndex } ::= { scrVolatileIntTable 1 } --1.3.6.1.4.1.3052.10.2.18.5.1 scrVolatileIntIndex OBJECT-TYPE SYNTAX Integer32 (1..50) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of volatile script integer settings" ::= { scrVolatileIntEntry 1 } --1.3.6.1.4.1.3052.10.2.18.5.1.1 scrVolatileInt OBJECT-TYPE SYNTAX Integer32 (0..2147483647) MAX-ACCESS read-write STATUS current DESCRIPTION "Volatile integer for use in scripts. Use this object to cache frequently-changing integer values or integer values that do not need to persist through reset. This object corresponds to the scripting.vint[] setting key branch; use those keys in scripts and you can view or change their values with this object." ::= { scrVolatileIntEntry 2 } --1.3.6.1.4.1.3052.10.2.18.5.1.2 scrNonVolatileStringTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingNonVolatileString MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of non-volatile string settings for use in scripts." ::= { scripting 6 } --1.3.6.1.4.1.3052.10.2.18.6 scrNonVolatileStringEntry OBJECT-TYPE SYNTAX ScriptingNonVolatileString MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of non-volatile script string settings" INDEX { scrNonVolatileStringIndex } ::= { scrNonVolatileStringTable 1 } --1.3.6.1.4.1.3052.10.2.18.6.1 scrNonVolatileStringIndex OBJECT-TYPE SYNTAX Integer32 (1..50) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of non-volatile script string settings" ::= { scrNonVolatileStringEntry 1 } --1.3.6.1.4.1.3052.10.2.18.6.1.1 scrNonVolatileString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Non-volatile string for use in scripts. Use this object to store values that need to persist through reset. This object corresponds to the scripting.nvstring[] setting key branch; use those keys in scripts and you can view or change their values with this object. Note: to store frequently- changing integers, use the scrVolatileString object, otherwise your scripts may cause unnecessary wear of the non-volatile storage medium on the unit." ::= { scrNonVolatileStringEntry 2 } --1.3.6.1.4.1.3052.10.2.18.6.1.2 scrNonVolatileIntTable OBJECT-TYPE SYNTAX SEQUENCE OF ScriptingNonVolatileInt MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of non-volatile integer settings for use in scripts." ::= { scripting 7 } --1.3.6.1.4.1.3052.10.2.18.7 scrNonVolatileIntEntry OBJECT-TYPE SYNTAX ScriptingNonVolatileInt MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of non-volatile script integer settings" INDEX { scrNonVolatileIntIndex } ::= { scrNonVolatileIntTable 1 } --1.3.6.1.4.1.3052.10.2.18.7.1 scrNonVolatileIntIndex OBJECT-TYPE SYNTAX Integer32 (1..50) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of non-volatile script integer settings" ::= { scrNonVolatileIntEntry 1 } --1.3.6.1.4.1.3052.10.2.18.7.1.1 scrNonVolatileInt OBJECT-TYPE SYNTAX Integer32 (0..2147483647) MAX-ACCESS read-write STATUS current DESCRIPTION "Non-volatile integer for use in scripts. Use this object to store integer values that need to persist through reset. This object corresponds to the scripting.nvint[] setting key branch; use those keys in scripts and you can view or change their values with this object. Note: to store frequently- changing integers, use the scrVolatileInt object, otherwise your scripts may cause unnecessary wear of the non-volatile storage medium on the unit." ::= { scrNonVolatileIntEntry 2 } --1.3.6.1.4.1.3052.10.2.18.7.1.2 --*************************************************************************************** --Generator Section 2.19 --*************************************************************************************** genSetEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable genset functionality; that is, a generator is in use." ::= { genSet 1 } --1.3.6.1.4.1.3052.10.2.19.1.1 genSetRelayEs OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-write STATUS current DESCRIPTION "Which EventSensor has the relay which starts the generator, for genset relay configuration 1 only. This object maps to the same setting as genSetRelayTableEs.1." ::= { genSetRelay 1 } --1.3.6.1.4.1.3052.10.2.19.1.2.1 genSetRelayPoint OBJECT-TYPE SYNTAX Integer32 (1..13) MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay starts the generator, for genset relay configuration 1 only. This object maps to the same setting as genSetRelayTablePoint.1." ::= { genSetRelay 2 } --1.3.6.1.4.1.3052.10.2.19.1.2.2 genSetRelayRunningstate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay state corresponds with the generator starting/running. This object maps to the same setting as genSetRelayTableRunningstate.1." ::= { genSetRelay 3 } --1.3.6.1.4.1.3052.10.2.19.1.2.3 genSetRelayTable OBJECT-TYPE SYNTAX SEQUENCE OF GenSetRelaySequence MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of relays for genset ignition." ::= { genSetRelay 5 } --1.3.6.1.4.1.3052.10.2.19.1.2.5 genSetRelayTableEntry OBJECT-TYPE SYNTAX GenSetRelaySequence MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of relays for genset ignition." INDEX { genSetRelayTableIndex } ::= { genSetRelayTable 1 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1 genSetRelayTableIndex OBJECT-TYPE SYNTAX Integer32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of relays for genset ignition." ::= { genSetRelayTableEntry 1 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1.1 genSetRelayTableEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable this relay for starting the generator." ::= { genSetRelayTableEntry 2 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1.2 genSetRelayTableEs OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-write STATUS current DESCRIPTION "Which EventSensor has the relay which starts the generator, for this genset relay configuration specified by the table index." ::= { genSetRelayTableEntry 3 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1.3 genSetRelayTablePoint OBJECT-TYPE SYNTAX Integer32 (1..13) MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay point on the EventSensor used for starting the generator, for this genset relay configuration specified by the table index." ::= { genSetRelayTableEntry 4 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1.4 genSetRelayTableRunningstate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Which relay state corresponds with the generator starting/running, for this genset relay configuration specified by the table index." ::= { genSetRelayTableEntry 5 } --1.3.6.1.4.1.3052.10.2.19.1.2.5.1.5 genSetCCEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable generator running detection functionality; that is, the associated CC is valid for determining if generator is running." ::= { genSetCC 1 } --1.3.6.1.4.1.3052.10.2.19.1.3.1 genSetCCEs OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-write STATUS current DESCRIPTION "Which CC EventSensor has the CC which is connected to the genertor running detection monitor." ::= { genSetCC 2 } --1.3.6.1.4.1.3052.10.2.19.1.3.2 genSetCCPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-write STATUS current DESCRIPTION "Which CC is connected to the genertor running detection monitor." ::= { genSetCC 3 } --1.3.6.1.4.1.3052.10.2.19.1.3.3 genSetCCRunningState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Which CC physical state corresponds with the generator running." ::= { genSetCC 4 } --1.3.6.1.4.1.3052.10.2.19.1.3.4 genSetCCDelay OBJECT-TYPE SYNTAX Integer32 (0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "How long (in seconds) to wait for the generator to indicate itself as running after engaging the generator-starting mechanism." ::= { genSetCC 5 } --1.3.6.1.4.1.3052.10.2.19.1.3.5 genRunMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Generator Exercising function main operating mode; set to INHIBIT to inhibit exercising the generator." ::= { genRun 1 } --1.3.6.1.4.1.3052.10.2.19.2.1 genRunSched OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Schedule number(s) which govern(s) when Generator Exercising function runs." ::= { genRun 2 } --1.3.6.1.4.1.3052.10.2.19.2.2 genRunDuration OBJECT-TYPE SYNTAX Integer32 (600..3600) MAX-ACCESS read-write STATUS current DESCRIPTION "Number of seconds that generator should run, started when the generator needs to start by SCHEDULE or by being forced to start." ::= { genRun 3 } --1.3.6.1.4.1.3052.10.2.19.2.3 genRunForce OBJECT-TYPE SYNTAX Integer32 (0..1) MAX-ACCESS read-write STATUS current DESCRIPTION "Write 1 to this to force the generator exercising to start. Always reads as 0." ::= { genRun 4 } --1.3.6.1.4.1.3052.10.2.19.2.4 genRunReqasm OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Require ASM connectivity before starting the generator from a schedule." ::= { genRun 5 } --1.3.6.1.4.1.3052.10.2.19.2.5 genRunStatus OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Status of Generator Exercising function." ::= { genRun 6 } --1.3.6.1.4.1.3052.10.2.19.2.6 genRunNonstartEventEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable generator non-start event." ::= { genRunNonstartEvent 1 } --1.3.6.1.4.1.3052.10.2.19.2.7.1 genRunNonstartEventActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Actions for generator non-start event." ::= { genRunNonstartEvent 2 } --1.3.6.1.4.1.3052.10.2.19.2.7.2 genRunNonstartEventTrap OBJECT-TYPE SYNTAX Integer32 (536..1199) MAX-ACCESS read-write STATUS current DESCRIPTION "Trap number for generator non-start event." ::= { genRunNonstartEvent 3 } --1.3.6.1.4.1.3052.10.2.19.2.7.3 genRunNonstartEventClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Class (severity) for generator non-start event." ::= { genRunNonstartEvent 4 } --1.3.6.1.4.1.3052.10.2.19.2.7.4 --*************************************************************************************** --Calendar Section 2.20 --*************************************************************************************** schedTable OBJECT-TYPE SYNTAX SEQUENCE OF ScheduleConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of schedules" ::= { calendar 1 } --1.3.6.1.4.1.3052.10.2.20.1 schedEntry OBJECT-TYPE SYNTAX ScheduleConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of schedules." INDEX { schedIndex } ::= { schedTable 1 } --1.3.6.1.4.1.3052.10.2.20.1.1 schedIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of schedules." ::= { schedEntry 1 } --1.3.6.1.4.1.3052.10.2.20.1.1.1 schedEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Enable this schedule." ::= { schedEntry 2 } --1.3.6.1.4.1.3052.10.2.20.1.1.2 schedStart OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is of the form 'mm/dd/yy hh:mm:ss'. This controls on which date/time the schedule starts." ::= { schedEntry 3 } --1.3.6.1.4.1.3052.10.2.20.1.1.3 schedRepeatMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls in which way the schedule should repeat." ::= { schedEntry 4 } --1.3.6.1.4.1.3052.10.2.20.1.1.4 schedRepeatFreq OBJECT-TYPE SYNTAX Integer32 (1..400) MAX-ACCESS read-write STATUS current DESCRIPTION "Controls how often the schedule should repeat: every nth day, week, month, or year." ::= { schedEntry 5 } --1.3.6.1.4.1.3052.10.2.20.1.1.5 schedRepeatEndMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls how the repeating schedule should end." ::= { schedEntry 6 } --1.3.6.1.4.1.3052.10.2.20.1.1.6 schedRepeatEndAfter OBJECT-TYPE SYNTAX Integer32 (1..1000) MAX-ACCESS read-write STATUS current DESCRIPTION "Number of times this schedule should be repeated; relevant when the repeat end mode is AFTER." ::= { schedEntry 7 } --1.3.6.1.4.1.3052.10.2.20.1.1.7 schedRepeatEndOn OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Date/time (in the form 'mm/yy/dd hh:mm:ss' or blank string) after which repeating should end, relevant when repeat end mode is ON DATE." ::= { schedEntry 8 } --1.3.6.1.4.1.3052.10.2.20.1.1.8 schedRepeatWeeklySun OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Sunday(s); relevant when repeat mode is weekly." ::= { schedEntry 9 } --1.3.6.1.4.1.3052.10.2.20.1.1.9 schedRepeatWeeklyMon OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Monday(s); relevant when repeat mode is weekly." ::= { schedEntry 10 } --1.3.6.1.4.1.3052.10.2.20.1.1.10 schedRepeatWeeklyTue OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Tuesday(s); relevant when repeat mode is weekly." ::= { schedEntry 11 } --1.3.6.1.4.1.3052.10.2.20.1.1.11 schedRepeatWeeklyWed OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Wednesday(s); relevant when repeat mode is weekly." ::= { schedEntry 12 } --1.3.6.1.4.1.3052.10.2.20.1.1.12 schedRepeatWeeklyThu OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Thursday(s); relevant when repeat mode is weekly." ::= { schedEntry 13 } --1.3.6.1.4.1.3052.10.2.20.1.1.13 schedRepeatWeeklyFri OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Friday(s); relevant when repeat mode is weekly." ::= { schedEntry 14 } --1.3.6.1.4.1.3052.10.2.20.1.1.14 schedRepeatWeeklySat OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule on Saturday(s); relevant when repeat mode is weekly." ::= { schedEntry 15 } --1.3.6.1.4.1.3052.10.2.20.1.1.15 schedRepeatMonthlyMode OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "EACH means the schedule runs on specific dates of the month. ON THE means the schedule runs on calculated dates of the month according to which day that month starts." ::= { schedEntry 16 } --1.3.6.1.4.1.3052.10.2.20.1.1.16 schedRepeatMonthlyDates OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Comma-separated list of dates of a month on which this schedule should run, relevant when repeat monthly mode is EACH." ::= { schedEntry 17 } --1.3.6.1.4.1.3052.10.2.20.1.1.17 schedRepeatMonthlyOnThe OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls on which day of the month this schedule should run, relevant when repeat monthly mode is ON THE." ::= { schedEntry 18 } --1.3.6.1.4.1.3052.10.2.20.1.1.18 schedRepeatMonthlyOnDay OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls the day of week on which this schedule is run, relevant when repeat monthly mode is ON THE" ::= { schedEntry 19 } --1.3.6.1.4.1.3052.10.2.20.1.1.19 schedRepeatYearlyJan OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in January, relevant when repeat mode is YEARLY." ::= { schedEntry 20 } --1.3.6.1.4.1.3052.10.2.20.1.1.20 schedRepeatYearlyFeb OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in February, relevant when repeat mode is YEARLY." ::= { schedEntry 21 } --1.3.6.1.4.1.3052.10.2.20.1.1.21 schedRepeatYearlyMar OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in March, relevant when repeat mode is YEARLY." ::= { schedEntry 22 } --1.3.6.1.4.1.3052.10.2.20.1.1.22 schedRepeatYearlyApr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in April, relevant when repeat mode is YEARLY." ::= { schedEntry 23 } --1.3.6.1.4.1.3052.10.2.20.1.1.23 schedRepeatYearlyMay OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in May, relevant when repeat mode is YEARLY." ::= { schedEntry 24 } --1.3.6.1.4.1.3052.10.2.20.1.1.24 schedRepeatYearlyJun OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in June, relevant when repeat mode is YEARLY." ::= { schedEntry 25 } --1.3.6.1.4.1.3052.10.2.20.1.1.25 schedRepeatYearlyJul OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in July, relevant when repeat mode is YEARLY." ::= { schedEntry 26 } --1.3.6.1.4.1.3052.10.2.20.1.1.26 schedRepeatYearlyAug OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in August, relevant when repeat mode is YEARLY." ::= { schedEntry 27 } --1.3.6.1.4.1.3052.10.2.20.1.1.27 schedRepeatYearlySep OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in September, relevant when repeat mode is YEARLY." ::= { schedEntry 28 } --1.3.6.1.4.1.3052.10.2.20.1.1.28 schedRepeatYearlyOct OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in October, relevant when repeat mode is YEARLY." ::= { schedEntry 29 } --1.3.6.1.4.1.3052.10.2.20.1.1.29 schedRepeatYearlyNov OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in November, relevant when repeat mode is YEARLY." ::= { schedEntry 30 } --1.3.6.1.4.1.3052.10.2.20.1.1.30 schedRepeatYearlyDec OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Run this schedule in December, relevant when repeat mode is YEARLY." ::= { schedEntry 31 } --1.3.6.1.4.1.3052.10.2.20.1.1.31 schedRepeatYearlyOnThe OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls on which day of the month this schedule should run, relevant when repeat mode is YEARLY." ::= { schedEntry 32 } --1.3.6.1.4.1.3052.10.2.20.1.1.32 schedRepeatYearlyOnDay OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Controls the day of week on which this schedule is run, relevant when repeat mode is YEARLY." ::= { schedEntry 33 } --1.3.6.1.4.1.3052.10.2.20.1.1.33 schedNextTrigger OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "When this schedule will next trigger." ::= { schedEntry 34 } --1.3.6.1.4.1.3052.10.2.20.1.1.34 --*************************************************************************************** --Product IDs Section 3 --*************************************************************************************** siteName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Site Name string; Max 40 characters." ::= { productIds 1 } --1.3.6.1.4.1.3052.10.3.1 thisProduct OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is a factory configured string for the product name." ::= { productIds 2 } --1.3.6.1.4.1.3052.10.3.2 stockTrapString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The message defined for the event that triggers a trap." ::= { productIds 3 } --1.3.6.1.4.1.3052.10.3.3 trapEventTypeNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 17 Humidity High 18 Humidity Very High 19 Humidity Low 20 Humidity Very Low 21 Humidity Return to Normal 26 Analog High 27 Analog Very High 28 Analog Low 29 Analog Very Low 30 Analog Normal 40 EventSensor Unresponsive 41 Custom 42 CPE Down 44 CPE Normal 49 Fuel Sensor Disconnect 50 Fuel Sensor Disconnect Return to Normal 56 Fuel Sensor 57 AC Power Monitor Average Voltage Very Low 58 AC Power Monitor Average Voltage Low 59 AC Power Monitor Average Voltage Return to Normal 60 AC Power Monitor Average Voltage High 61 AC Power Monitor Average Voltage Very High 62 AC Power Monitor Average Current Very Low 63 AC Power Monitor Average Current Low 64 AC Power Monitor Average Current Return to Normal 65 AC Power Monitor Average Current High 66 AC Power Monitor Average Current Very High 67 AC Power Monitor Frequency Very Low 68 AC Power Monitor Frequency Low 69 AC Power Monitor Frequency Return to Normal 70 AC Power Monitor Frequency High 71 AC Power Monitor Frequency Very High 72 AC Power Monitor Total Real Power Very Low 73 AC Power Monitor Total Real Power Low 74 AC Power Monitor Total Real Power Return to Normal 75 AC Power Monitor Total Real Power High 76 AC Power Monitor Total Real Power Very High 77 AC Power Monitor Disconnect 78 AC Power Monitor Disconnect Return to Normal 81 Fuel Sensor Volume Sudden Change 82 Fuel Sensor Volume Slow Change 83 CPE Down Reminder 84 AC Power Monitor Total Power Factor Very Low 85 AC Power Monitor Total Power Factor Low 86 AC Power Monitor Total Power Factor Return to Normal 100 Contact Closure Active Reminder 101 Temperature High Reminder 102 Temperature High Very Reminder 103 Temperature Low Reminder 104 Temperature Very Low Reminder 105 Humidity High Reminder 106 Humidity Very High Reminder 107 Humidity Low Reminder 108 Humidity Very Low Reminder 109 Analog High Reminder 110 Analog Very High Reminder 111 Analog Low Reminder 112 Analog Very Low Reminder 130 Relay Output Active 131 Relay Output Inactive 132 Power Output On 133 Power Output Off 161 Camera 164 Reset 166 Fuel Sensor Levels Auto Adjust " ::= { productIds 4 } --1.3.6.1.4.1.3052.10.3.4 trapEventTypeName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the string corresponding to the event type." ::= { productIds 5 } --1.3.6.1.4.1.3052.10.3.5 trapIncludedValue OBJECT-TYPE SYNTAX Integer32 (-2147483648..2147483647) MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the generic included value." ::= { productIds 6 } --1.3.6.1.4.1.3052.10.3.6 trapIncludedString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the generic included string." ::= { productIds 7 } --1.3.6.1.4.1.3052.10.3.7 trapTypeString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The cause of the trap, added for DL880 compatibility." ::= { productIds 8 } --1.3.6.1.4.1.3052.10.3.8 trapEventClassNumber OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the configurable class number associated with the triggering event." ::= { productIds 9 } --1.3.6.1.4.1.3052.10.3.9 trapEventClassName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The user-defined trap variable for the configurable class name associated with the class number." ::= { productIds 10 } --1.3.6.1.4.1.3052.10.3.10 --*************************************************************************************** --Key Interface Section 4 --*************************************************************************************** keyInterface OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This object represents a setting key interface. When setting this object, the value to set is the 'sk' command you would enter on the command line (without the 'sk'). To get the result of the operation, read this object after you write it. For example, to configure EventSensor 1 contact closure 34 event actions to be an SNMP InformRequest to host foo, set this object to: 'event.sensor[1].cc[34].eventactions=inform(foo)'. The SNMP response is the result of the operation: if setting that key to that value was a success then the SNMP response will be a success and the response value will be what you had set. If you subsequently read this object then you will see a message 'OK: ...'. If setting that key to that value failed then the SNMP response will be a failure (a badValue response). If you subsequently read this object then the value returned is the reason that setting that key to that value failed. For another example, to read user 3's pass-through access for port 7, set this object to: 'sec.user[3].port[7].ptaccess'. The SNMP response is the result of the operation: if reading that key is a success then the SNMP response will be a success and the response value will be what you had SET (i.e., the opertion of reading a key, which is just the key itself with no '=' operator, and this is not the key value you want to read). If you subsequently read this object then the value returned is the value of the key you want to read. If reading that key failed (e.g., if the key is invalid) then the SNMP response to your SNMP set operation (the value you set being the invalid key to read) will be a failure (a badValue response). If you subsequently read this object then the value returned is the reason that reading that key failed (i.e., 'invalid key')." ::= { s550 4 } --1.3.6.1.4.1.3052.10.4 --*************************************************************************************** --TABLE DEFINITIONS --*************************************************************************************** ESPointConfigTemp ::= SEQUENCE { espcTempIndexES Integer32, espcTempIndexPoint Integer32, espcTempEnable DisplayString, espcTempScale DisplayString, espcTempDeadband DisplayString, espcTempVHighTemp DisplayString, espcTempVHighActions DisplayString, espcTempVHighTrapnum Integer32, espcTempVHighClass DisplayString, espcTempHighTemp DisplayString, espcTempHighActions DisplayString, espcTempHighTrapnum Integer32, espcTempHighClass DisplayString, espcTempNormalActions DisplayString, espcTempNormalTrapnum Integer32, espcTempNormalClass DisplayString, espcTempLowTemp DisplayString, espcTempLowActions DisplayString, espcTempLowTrapnum Integer32, espcTempLowClass DisplayString, espcTempVLowTemp DisplayString, espcTempVLowActions DisplayString, espcTempVLowTrapnum Integer32, espcTempVLowClass DisplayString, espcTempGroup DisplayString } ESPointConfigCC ::= SEQUENCE { espcCCIndexES Integer32, espcCCIndexPoint Integer32, espcCCEnable DisplayString, espcCCName DisplayString, espcCCEventState DisplayString, espcCCThreshold Integer32, espcCCEventActions DisplayString, espcCCEventTrapnum Integer32, espcCCEventClass DisplayString, espcCCNormalActions DisplayString, espcCCNormalTrapnum Integer32, espcCCNormalClass DisplayString, espcCCAlarmAlias DisplayString, espcCCNormalAlias DisplayString, espcCCNormalThreshold Integer32, espcCCOverrideGlobalReminder DisplayString, espcCCReminderInterval Integer32, espcCCGroup DisplayString } ESPointConfigHumid ::= SEQUENCE { espcHumidIndexES Integer32, espcHumidIndexPoint Integer32, espcHumidEnable DisplayString, espcHumidDeadband Integer32, espcHumidVHighHumid Integer32, espcHumidVHighActions DisplayString, espcHumidVHighTrapnum Integer32, espcHumidVHighClass DisplayString, espcHumidHighHumid Integer32, espcHumidHighActions DisplayString, espcHumidHighTrapnum Integer32, espcHumidHighClass DisplayString, espcHumidNormalActions DisplayString, espcHumidNormalTrapnum Integer32, espcHumidNormalClass DisplayString, espcHumidLowHumid Integer32, espcHumidLowActions DisplayString, espcHumidLowTrapnum Integer32, espcHumidLowClass DisplayString, espcHumidVLowHumid Integer32, espcHumidVLowActions DisplayString, espcHumidVLowTrapnum Integer32, espcHumidVLowClass DisplayString, espcHumidGroup DisplayString } ESPointConfigAnalogInput ::= SEQUENCE { espcAIIndexES Integer32, espcAIIndexPoint Integer32, espcAIEnable DisplayString, espcAIDeadband DisplayString, espcAIVhighValue DisplayString, espcAIVhighActions DisplayString, espcAIVhighTrapnum Integer32, espcAIVhighClass DisplayString, espcAIHighValue DisplayString, espcAIHighActions DisplayString, espcAIHighTrapnum Integer32, espcAIHighClass DisplayString, espcAINormalActions DisplayString, espcAINormalTrapnum Integer32, espcAINormalClass DisplayString, espcAILowValue DisplayString, espcAILowActions DisplayString, espcAILowTrapnum Integer32, espcAILowClass DisplayString, espcAIVlowValue DisplayString, espcAIVlowActions DisplayString, espcAIVlowTrapnum Integer32, espcAIVlowClass DisplayString, espcAIConvUnitName DisplayString, espcAIConvHighValue DisplayString, espcAIConvHighUnit DisplayString, espcAIConvLowValue DisplayString, espcAIConvLowUnit DisplayString, espcAIDisplayFormat DisplayString, espcAIGroup DisplayString } ActionCallNumberConfig ::= SEQUENCE { actionCallNumberIndex Integer32, actionCallNumber DisplayString } ActionPagerConfig ::= SEQUENCE { actionPagerIndex Integer32, actionPagerType DisplayString, actionPagerNumber DisplayString, actionPagerID DisplayString, actionPagerMessage DisplayString, actionPagerPostCalloutDelay Integer32, actionPagerPostIDDelay Integer32 } ESPointConfigOutput ::= SEQUENCE { espcOutputIndexES Integer32, espcOutputIndexPoint Integer32, espcOutputEnable DisplayString, espcOutputActiveState DisplayString, espcOutputType DisplayString, espcOutputAliasValue DisplayString, espcOutputAliasColor DisplayString, espcOutputActiveAlias DisplayString, espcOutputActiveColor DisplayString, espcOutputActiveActions DisplayString, espcOutputActiveTrapnum Integer32, espcOutputActiveClass DisplayString, espcOutputInactiveAlias DisplayString, espcOutputInactiveColor DisplayString, espcOutputInactiveActions DisplayString, espcOutputInactiveTrapnum Integer32, espcOutputInactiveClass DisplayString, espcOutputGroup DisplayString } EventClassConfig ::= SEQUENCE { evClassNameIndex Integer32, evClassName DisplayString } RTSFileConfig ::= SEQUENCE { rtsFileIndex Integer32, rtsFileMode DisplayString, rtsFileShowAnswer DisplayString, rtsFileReqXON DisplayString, rtsFileTimeout Integer32, rtsFileEmptyClose DisplayString, rtsFilePushHost DisplayString, rtsFilePushPort Integer32, rtsFilePushRetryTimer Integer32 } ModemCLIDLogConfig ::= SEQUENCE { modemCLIDLogIndex Integer32, modemCLIDLogNumber DisplayString } CPEConfig ::= SEQUENCE { cpeIndex Integer32, cpeHost DisplayString, cpeName DisplayString, cpeDescription DisplayString, cpeKeepalive Integer32, cpeThreshold Integer32, cpeEventReminderInterval Integer32, cpeKeepaliveTicks Integer32, cpePingSize Integer32, cpeInfoReset Integer32, cpeInfoNumReq Integer32, cpeInfoNumGoodResp Integer32, cpeInfoNumBadResp Integer32, cpeInfoNumLostResp Integer32, cpeInfoPercentLoss DisplayString, cpeInfoPercentBad DisplayString } ScriptingConfig ::= SEQUENCE { scrIndex Integer32, scrEnable DisplayString, scrName DisplayString, scrFilename DisplayString, scrRunAlways DisplayString, scrRunAtStartup DisplayString, scrRunScheduled DisplayString, scrScheduleTime DisplayString, scrArguments DisplayString, scrRepeatInterval Integer32 } ScriptingDTRCtrlPortEnableConfig ::= SEQUENCE { scrDTRCtrlPortEnableIndex Integer32, scrDTRCtrlPortEnable DisplayString } ScriptingVolatileString ::= SEQUENCE { scrVolatileStringIndex Integer32, scrVolatileString DisplayString } ScriptingVolatileInt ::= SEQUENCE { scrVolatileIntIndex Integer32, scrVolatileInt Integer32 } ScriptingNonVolatileString ::= SEQUENCE { scrNonVolatileStringIndex Integer32, scrNonVolatileString DisplayString } ScriptingNonVolatileInt ::= SEQUENCE { scrNonVolatileIntIndex Integer32, scrNonVolatileInt Integer32 } GenSetRelaySequence ::= SEQUENCE { genSetRelayTableIndex Integer32, genSetRelayTableEnable DisplayString, genSetRelayTableEs Integer32, genSetRelayTablePoint Integer32, genSetRelayTableRunningstate DisplayString } CRDBFileEnforceMinConfig ::= SEQUENCE { sysCRDBFileEnforceMinIndex Integer32, sysCRDBFileEnforceMin DisplayString } CRDBFileIDConfig ::= SEQUENCE { sysCRDBFileIDIndex Integer32, sysCRDBFileID DisplayString } NetworkTimeHostConfig ::= SEQUENCE { sysTimeNetHostIndex Integer32, sysTimeNetHost DisplayString } ActionHostConfig ::= SEQUENCE { actionHostIndex Integer32, actionHost DisplayString } ActionEmailConfig ::= SEQUENCE { actionEmailIndex Integer32, actionEmail DisplayString } FileEnforceMinimumConfig ::= SEQUENCE { sysCRDBFileEnforceMinIndex Integer32, sysCRDBFileEnforceMin DisplayString } SerialHandshakingLowEventConfig ::= SEQUENCE { evShskLowIndex Integer32, evShskLowEnable DisplayString, evShskLowActions DisplayString, evShskLowMessage DisplayString, evShskLowClass DisplayString, evShskLowTrapNum Integer32 } SerialHandshakingHighEventConfig ::= SEQUENCE { evShskHighIndex Integer32, evShskHighEnable DisplayString, evShskHighActions DisplayString, evShskHighMessage DisplayString, evShskHighClass DisplayString, evShskHighTrapNum Integer32 } NoDataEvent1PortEnableConfig ::= SEQUENCE { evNoData1PortEnableIndex Integer32, evNoData1PortEnable DisplayString } NoDataEvent2PortEnableConfig ::= SEQUENCE { evNoData2PortEnableIndex Integer32, evNoData2PortEnable DisplayString } DataEventMacroConfig ::= SEQUENCE { evdMacroIndex Integer32, evdMacroName DisplayString, evdMacroEquation DisplayString } DataEventFieldConfig ::= SEQUENCE { evdFieldIndex Integer32, evdFieldStart Integer32, evdFieldLength Integer32, evdFieldName DisplayString, evdFieldLine Integer32, evdFieldType DisplayString } DataEventConfig ::= SEQUENCE { evdIndex Integer32, evdEnable DisplayString, evdName DisplayString, evdEquation DisplayString, evdThreshold Integer32, evdAutoClear DisplayString, evdClearInterval DisplayString, evdClearTime DisplayString, evdActions DisplayString, evdClass DisplayString, evdTrapNum Integer32, evdMode DisplayString } SecUserConfig ::= SEQUENCE { secUserIndex Integer32, secUserEnable DisplayString, secUserConnectVia DisplayString, secUserLoginTo DisplayString, secUserAccessFile DisplayString, secUserPTEscapeTo DisplayString, secUserPPPType DisplayString, secUserRights DisplayString, secUserEventsReadAccess DisplayString, secUserAuditReadAccess DisplayString, secUserEventsWriteAccess DisplayString, secUserAuditWriteAccess DisplayString, secUserExpiration DisplayString, secUserCallbackNumber1 DisplayString, secUserCallbackNumber2 DisplayString, secUserCallbackNumber3 DisplayString, secUserChallengeTelnetMode DisplayString, secUserChallengeModemMode DisplayString, secUserChallengeConsoleMode DisplayString, secUserChallengeTelnetSendTo DisplayString, secUserChallengeModemSendTo DisplayString, secUserChallengeExpiration Integer32 } ModemCLIDNumberConfig ::= SEQUENCE { modemCLIDNumberIndex Integer32, modemCLIDNumber DisplayString } RouteTestConfig ::= SEQUENCE { routeTestAddressIndex Integer32, routeTestAddress DisplayString } IPRestrictionConfig ::= SEQUENCE { ipRestrictionIndex Integer32, ipRestrictionEnable DisplayString, ipRestrictionMask DisplayString } DNSConfig ::= SEQUENCE { dnsIndex Integer32, dnsAddress IpAddress } HostConfig ::= SEQUENCE { hostIndex Integer32, hostDeclaration DisplayString } SNMPProxyTable ::= SEQUENCE { snmpProxyIndex Integer32, snmpProxyEgressOIDBranch DisplayString, snmpProxyIP DisplayString, snmpProxyPort Integer32, snmpProxyIngressOIDBranch DisplayString, snmpProxyName DisplayString } SNMPPollRequestConfig ::= SEQUENCE { snmpPRequestIndex Integer32, snmpPRequestDescription DisplayString, snmpPRequestAgent DisplayString, snmpPRequestReadcom DisplayString, snmpPRequestOID DisplayString, snmpPRequestPeriod Integer32, snmpPRequestID DisplayString, snmpPRequestThreshold DisplayString, snmpPRequestResultStatus DisplayString, snmpPRequestResultValue DisplayString, snmpPRequestResultTime DisplayString, snmpPRequestResultType DisplayString } FTPPushPushFileConfig ::= SEQUENCE { ftpPushPushFileIndex Integer32, ftpPushPushFile DisplayString } FTPPushRemoteFileConfig ::= SEQUENCE { ftpPushRemoteFileIndex Integer32, ftpPushRemoteFileName DisplayString } PortConfig ::= SEQUENCE { portConfigIndex Integer32, portConfigBaud Integer32, portConfigDataFormat Integer32, portConfigStripPtOutputLfs Integer32, portConfigStripPtInputLfs Integer32, portConfigMaskEnable Integer32, portConfigDAEnable Integer32, portConfigStoreAlarmsDPT DisplayString, portConfigRecordTimeout Integer32, portConfigDataType DisplayString, portConfigEtxToCRLF DisplayString, portConfigMLREnable DisplayString, portConfigMLRStartField1Pos Integer32, portConfigMLRStartField1Text DisplayString, portConfigMLRStartField2Pos Integer32, portConfigMLRStartField2Text DisplayString, portConfigMLRNumLinesBefore Integer32, portConfigMLREndDetection DisplayString, portConfigMLRLineCount Integer32, portConfigMLREndField1Pos Integer32, portConfigMLREndField1Text DisplayString, portConfigMLREndField2Pos Integer32, portConfigMLREndField2Text DisplayString, portConfigMLRUseComplexRules DisplayString, portConfigBufferPT DisplayString, portConfigId DisplayString, portConfigMode DisplayString, portConfigHsk DisplayString } ESPoint ::= SEQUENCE { esIndexES Integer32, esIndexPC Integer32, esIndexPoint Integer32, esPointName DisplayString, esPointInEventState Integer32, esPointValueInt Integer32, esPointValueStr DisplayString, esPointTimeLastChange DisplayString, esPointTimetickLastChange TimeTicks, esPointAliasValueStr DisplayString, esPointClassValueStr DisplayString } ESExist ::= SEQUENCE { esIndex Integer32, esName DisplayString, esID DisplayString, esNumberTempSensors Integer32, esTempReportingMode DisplayString, esNumberCCs Integer32, esCCReportingMode DisplayString, esNumberHumidSensors Integer32, esHumidReportingMode DisplayString, esNumberNoiseSensors Integer32, esNoiseReportingMode DisplayString, esNumberAirflowSensors Integer32, esAirflowReportingMode DisplayString, esNumberAnalog Integer32, esAnalogReportingMode DisplayString, esNumberOutputs Integer32, esOutputReportingMode DisplayString, esTempCombinedStatus DisplayString, esCCCombinedStatusBlock1 DisplayString, esCCCombinedStatusBlock2 DisplayString, esCCCombinedStatusBlock3 DisplayString, esCCCombinedStatusBlock4 DisplayString, esCCCombinedStatusBlock5 DisplayString, esCCCombinedStatusBlock6 DisplayString, esCCCombinedStatusBlock7 DisplayString, esCCCombinedStatusBlock8 DisplayString, esHumidCombinedStatus DisplayString, esAnalogCombinedStatusBlock1 DisplayString, esAnalogCombinedStatusBlock2 DisplayString, esAnalogCombinedStatusBlock3 DisplayString, esAnalogCombinedStatusBlock4 DisplayString, esAnalogCombinedStatusBlock5 DisplayString, esAnalogCombinedStatusBlock6 DisplayString, esOutputCombinedStatusBlock1 DisplayString, esOutputCombinedStatusBlock2 DisplayString } DEStatus ::= SEQUENCE { deStatusIndex Integer32, deStatusName DisplayString, deStatusCounter Integer32, deStatusThreshold Integer32 } FSStatus ::= SEQUENCE { fsStatusIndex Integer32, fsStatusName DisplayString, fsStatusDeviceState DisplayString, fsStatusVolumeValueString DisplayString, fsStatusVolumePercentLevel DisplayString, fsStatusVolumeInEventState DisplayString, fsStatusCombined DisplayString } ACPMStatus ::= SEQUENCE { acpmsIndex Integer32, acpmsName DisplayString, acpmsAvgVoltageValueStr DisplayString, acpmsAvgVoltageMinStr DisplayString, acpmsAvgVoltageMaxStr DisplayString, acpmsAvgVoltageAvgStr DisplayString, acpmsAvgVoltageInEventState DisplayString, acpmsVoltagePhaseAValueStr DisplayString, acpmsVoltagePhaseBValueStr DisplayString, acpmsVoltagePhaseCValueStr DisplayString, acpmsAvgCurrentValueStr DisplayString, acpmsAvgCurrentMinStr DisplayString, acpmsAvgCurrentMaxStr DisplayString, acpmsAvgCurrentAvgStr DisplayString, acpmsAvgCurrentInEventState DisplayString, acpmsCurrentPhaseAValueStr DisplayString, acpmsCurrentPhaseBValueStr DisplayString, acpmsCurrentPhaseCValueStr DisplayString, acpmsVoltageL1L2Value DisplayString, acpmsVoltageL2L3Value DisplayString, acpmsVoltageL3L1Value DisplayString, acpmsAvgFreqValueStr DisplayString, acpmsAvgFreqMinStr DisplayString, acpmsAvgFreqMaxStr DisplayString, acpmsAvgFreqAvgStr DisplayString, acpmsAvgFreqInEventState DisplayString, acpmsTRPValueStr DisplayString, acpmsTRPMinStr DisplayString, acpmsTRPMaxStr DisplayString, acpmsTRPAvgStr DisplayString, acpmsTRPInEventState DisplayString, acpmsRPPhaseAValueStr DisplayString, acpmsRPPhaseBValueStr DisplayString, acpmsRPPhaseCValueStr DisplayString, acpmsCombined DisplayString, acpmsTPFValueStr DisplayString, acpmsTPFMinStr DisplayString, acpmsTPFMaxStr DisplayString, acpmsTPFAvgStr DisplayString, acpmsTPFInEventState DisplayString, acpmsPFPhaseAValueStr DisplayString, acpmsPFPhaseBValueStr DisplayString, acpmsPFPhaseCValueStr DisplayString, acpmsTRcPValueStr DisplayString, acpmsTRcPMinStr DisplayString, acpmsTRcPMaxStr DisplayString, acpmsTRcPAvgStr DisplayString, acpmsRcPPhaseAValueStr DisplayString, acpmsRcPPhaseBValueStr DisplayString, acpmsRcPPhaseCValueStr DisplayString, acpmsTAPValueStr DisplayString, acpmsTAPMinStr DisplayString, acpmsTAPMaxStr DisplayString, acpmsTAPAvgStr DisplayString, acpmsAPPhaseAValueStr DisplayString, acpmsAPPhaseBValueStr DisplayString, acpmsAPPhaseCValueStr DisplayString, acpmsTotalEnergyWh Integer32, acpmsTotalEnergyVAR Integer32, acpmsTotalEnergyVA Integer32, acmpsAvgVoltageAlarmDatetime DisplayString, acmpsAvgCurrentAlarmDatetime DisplayString, acmpsFreqAlarmDatetime DisplayString, acmpsRealPowerAlarmDatetime DisplayString, acmpsPowerFactorAlarmDatetime DisplayString } HVACStatusAsentriaSequence ::= SEQUENCE { evHVACStatusAsentriaSequenceIndex Integer32, evHVACStatusAsentriaSeqVentTime DisplayString, evHVACStatusAsentriaSeqCoolTime DisplayString, evHVACStatusAsentriaSeqHeatTime DisplayString, evHVACStatusAsentriaSeqIdleTime DisplayString } HVACStatusAsentriaUnit ::= SEQUENCE { evHVACStatusAsentriaUnitIndex Integer32, evHVACStatusAsentriaUnitState DisplayString, evHVACStatusAsentriaUnitVentTime DisplayString, evHVACStatusAsentriaUnitCoolTime DisplayString, evHVACStatusAsentriaUnitHeatTime DisplayString, evHVACStatusAsentriaUnitIdleTime DisplayString } HVACStatusAirsysAlarmUnit ::= SEQUENCE { evHVACStatusAirsysAlarmUnitIndex Integer32, evHVACStatusAirsysAlarmUnitLowPress DisplayString, evHVACStatusAirsysAlarmUnitHighPress DisplayString, evHVACStatusAirsysAlarmUnitEvapFan DisplayString, evHVACStatusAirsysAlarmUnitDirty DisplayString, evHVACStatusAirsysAlarmUnitDamper DisplayString, evHVACStatusAirsysAlarmUnitSupProbe DisplayString } HVACStatusAirsysUnit ::= SEQUENCE { evHVACStatusAirsysUnitIndex Integer32, evHVACStatusAirsysUnitTempSupply DisplayString, evHVACStatusAirsysUnitFanspeed DisplayString, evHVACStatusAirsysUnitFreeOpening DisplayString, evHVACStatusAirsysUnitStatus DisplayString, evHVACStatusAirsysUnitLocked DisplayString, evHVACStatusAirsysUnitCompressor DisplayString, evHVACStatusAirsysUnitHeater DisplayString, evHVACStatusAirsysURuntimeSupplyFan DisplayString, evHVACStatusAirsysURuntimeCompressor DisplayString, evHVACStatusAirsysURuntimeHeat DisplayString, evHVACStatusAirsysURuntimeFreeCooling DisplayString, evHVACStatusAirsysUCountSupplyFan DisplayString, evHVACStatusAirsysUCountCompressor DisplayString, evHVACStatusAirsysUCountHeat DisplayString, evHVACStatusAirsysUCountFreeCooling DisplayString } HVACAsentriaSensorList ::= SEQUENCE { evHVACAsentriaSensorListIndex Integer32, evHVACAsentriaSensorListES DisplayString, evHVACAsentriaSensorListPT Integer32, evHVACAsentriaSensorListType DisplayString, evHVACAsentriaSensorListLoc DisplayString } HVACAsentriaUnit ::= SEQUENCE { evHVACAsentriaUnitIndex Integer32, evHVACAsentriaUnitEnable DisplayString, evHVACAsentriaUnitFanRelayES DisplayString, evHVACAsentriaUnitFanRelayPT Integer32, evHVACAsentriaUnitVentRelayES DisplayString, evHVACAsentriaUnitVentRelayPT Integer32, evHVACAsentriaUnitTimereset Integer32, evHVACAsentriaSeqTimereset Integer32, evHVACAsentriaUnitStage1CoolES DisplayString, evHVACAsentriaUnitStage1CoolPT Integer32, evHVACAsentriaUnitStage1HeatES DisplayString, evHVACAsentriaUnitStage1HeatPT Integer32, evHVACAsentriaUnitStage2CoolES DisplayString, evHVACAsentriaUnitStage2CoolPT Integer32, evHVACAsentriaUnitStage2HeatES DisplayString, evHVACAsentriaUnitStage2HeatPT Integer32 } HVACAirsysUnit::= SEQUENCE { evHVACAirsysUnitIndex Integer32, evHVACAirsysULowPEnable DisplayString, evHVACAirsysULowPActions DisplayString, evHVACAirsysULowPTrapnum Integer32, evHVACAirsysULowPClass DisplayString, evHVACAirsysULowPNormActions DisplayString, evHVACAirsysULowPNormTrapNum Integer32, evHVACAirsysULowPNormClass DisplayString, evHVACAirsysUHighPEnable DisplayString, evHVACAirsysUHighPActions DisplayString, evHVACAirsysUHighPTrapnum Integer32, evHVACAirsysUHighPClass DisplayString, evHVACAirsysUHighPNormActions DisplayString, evHVACAirsysUHighPNormTrapNum Integer32, evHVACAirsysUHighPNormClass DisplayString, evHVACAirsysUEvapFanEnable DisplayString, evHVACAirsysUEvapFanActions DisplayString, evHVACAirsysUEvapFanTrapnum Integer32, evHVACAirsysUEvapFanClass DisplayString, evHVACAirsysUEvapFanNormActions DisplayString, evHVACAirsysUEvapFanNormTrapNum Integer32, evHVACAirsysUEvapFanNormClass DisplayString, evHVACAirsysUDirtyEnable DisplayString, evHVACAirsysUDirtyActions DisplayString, evHVACAirsysUDirtyTrapnum Integer32, evHVACAirsysUDirtyClass DisplayString, evHVACAirsysUDirtyNormActions DisplayString, evHVACAirsysUDirtyNormTrapNum Integer32, evHVACAirsysUDirtyNormClass DisplayString, evHVACAirsysUInProbeEnable DisplayString, evHVACAirsysUInProbeActions DisplayString, evHVACAirsysUInProbeTrapnum Integer32, evHVACAirsysUInProbeClass DisplayString, evHVACAirsysUInProbeNormActions DisplayString, evHVACAirsysUInProbeNormTrapNum Integer32, evHVACAirsysUInProbeNormClass DisplayString, evHVACAirsysUDamperEnable DisplayString, evHVACAirsysUDamperActions DisplayString, evHVACAirsysUDamperTrapnum Integer32, evHVACAirsysUDamperClass DisplayString, evHVACAirsysUDamperNormActions DisplayString, evHVACAirsysUDamperNormTrapNum Integer32, evHVACAirsysUDamperNormClass DisplayString, evHVACAirsysUSupProbeEnable DisplayString, evHVACAirsysUSupProbeActions DisplayString, evHVACAirsysUSupProbeTrapnum Integer32, evHVACAirsysUSupProbeClass DisplayString, evHVACAirsysUSupProbeNormActions DisplayString, evHVACAirsysUSupProbeNormTrapNum Integer32, evHVACAirsysUSupProbeNormClass DisplayString } ScheduleConfig ::= SEQUENCE { schedIndex Integer32, schedEnable DisplayString, schedStart DisplayString, schedRepeatMode DisplayString, schedRepeatFreq Integer32, schedRepeatEndMode DisplayString, schedRepeatEndAfter Integer32, schedRepeatEndOn DisplayString, schedRepeatWeeklySun DisplayString, schedRepeatWeeklyMon DisplayString, schedRepeatWeeklyTue DisplayString, schedRepeatWeeklyWed DisplayString, schedRepeatWeeklyThu DisplayString, schedRepeatWeeklyFri DisplayString, schedRepeatWeeklySat DisplayString, schedRepeatMonthlyMode DisplayString, schedRepeatMonthlyDates DisplayString, schedRepeatMonthlyOnThe DisplayString, schedRepeatMonthlyOnDay DisplayString, schedRepeatYearlyJan DisplayString, schedRepeatYearlyFeb DisplayString, schedRepeatYearlyMar DisplayString, schedRepeatYearlyApr DisplayString, schedRepeatYearlyMay DisplayString, schedRepeatYearlyJun DisplayString, schedRepeatYearlyJul DisplayString, schedRepeatYearlyAug DisplayString, schedRepeatYearlySep DisplayString, schedRepeatYearlyOct DisplayString, schedRepeatYearlyNov DisplayString, schedRepeatYearlyDec DisplayString, schedRepeatYearlyOnThe DisplayString, schedRepeatYearlyOnDay DisplayString, schedNextTrigger DisplayString } FuelSensorConfigGeneral ::= SEQUENCE { fsGenIndex Integer32, fsGenName DisplayString, fsGenSensorType DisplayString, fsGenDistanceUnit DisplayString, fsGenRawValueTop DisplayString, fsGenTopOffset DisplayString, fsGenRawValueBottom DisplayString, fsGenBottomOffset DisplayString, fsGenInputES Integer32, fsGenInputPoint Integer32, fsGenFilterAveraging Integer32, fsGenSysrepEnable DisplayString, fsGenSysrepThreshold DisplayString, fsGenSysrepLimit Integer32, fsGenSysrepPackage Integer32, fsGenGroup DisplayString, fsGenEnable DisplayString, fsGenFuelType DisplayString } FuelSensorConfigTank ::= SEQUENCE { fsTankIndex Integer32, fsTankHeight DisplayString, fsTankDimA DisplayString, fsTankDimB DisplayString, fsTankVolume DisplayString, fsTankVolumeUnit DisplayString, fsTankShape DisplayString } FuelSensorConfigCustomTankStrapping ::= SEQUENCE { fsCustomTankIndexFS Integer32, fsCustomTankIndexDatum Integer32, fsCustomTankHeight DisplayString, fsCustomTankVolume DisplayString } FuelSensorConfigVolume ::= SEQUENCE { fsVolumeIndex Integer32, fsVolumeEnable DisplayString, fsVolumeDeadband DisplayString, fsVolumeVHighValue DisplayString, fsVolumeVHighActions DisplayString, fsVolumeVHighTrapNum Integer32, fsVolumeVHighClass DisplayString, fsVolumeHighValue DisplayString, fsVolumeHighActions DisplayString, fsVolumeHighTrapNum Integer32, fsVolumeHighClass DisplayString, fsVolumeNormalActions DisplayString, fsVolumeNormalTrapNum Integer32, fsVolumeNormalClass DisplayString, fsVolumeLowValue DisplayString, fsVolumeLowActions DisplayString, fsVolumeLowTrapNum Integer32, fsVolumeLowClass DisplayString, fsVolumeVLowValue DisplayString, fsVolumeVLowActions DisplayString, fsVolumeVLowTrapNum Integer32, fsVolumeVLowClass DisplayString } FuelSensorConfigDisconnect ::= SEQUENCE { fsDiscIndex Integer32, fsDiscEnable DisplayString, fsDiscHighValue DisplayString, fsDiscLowValue DisplayString, fsDiscActions DisplayString, fsDiscTrapNum Integer32, fsDiscClass DisplayString, fsDiscNormalActions DisplayString, fsDiscNormalTrapNum Integer32, fsDiscNormalClass DisplayString } FuelSensorConfigSuddenChange ::= SEQUENCE { fsSuddenChangeIndex Integer32, fsSuddenChangeEnable DisplayString, fsSuddenChangeTime Integer32, fsSuddenChangeAmplitude DisplayString, fsSuddenChangeActions DisplayString, fsSuddenChangeTrapNum Integer32, fsSuddenChangeClass DisplayString } FuelSensorConfigSlowChange ::= SEQUENCE { fsSlowChangeIndex Integer32, fsSlowChangeEnable DisplayString, fsSlowChangeTime Integer32, fsSlowChangeAmplitude DisplayString, fsSlowChangeActions DisplayString, fsSlowChangeTrapNum Integer32, fsSlowChangeClass DisplayString } ACPMConfigGeneral ::= SEQUENCE { acpmGenIndex Integer32, acpmGenDevice DisplayString, acpmGenName DisplayString, acpmGenAddress Integer32, acpmGenPtRatio Integer32, acpmGenCtRatio Integer32, acpmGenPowerType DisplayString, acpmGenSysrepPackage Integer32, acpmGenGroup DisplayString, acpmGenEnable DisplayString } ACPMConfigAvgVoltage ::= SEQUENCE { acpmAvgVoltageIndex Integer32, acpmAvgVoltageEnable DisplayString, acpmAvgVoltageDeadband DisplayString, acpmAvgVoltageVHighValue DisplayString, acpmAvgVoltageVHighActions DisplayString, acpmAvgVoltageVHighTrapNum Integer32, acpmAvgVoltageVHighClass DisplayString, acpmAvgVoltageHighValue DisplayString, acpmAvgVoltageHighActions DisplayString, acpmAvgVoltageHighTrapNum Integer32, acpmAvgVoltageHighClass DisplayString, acpmAvgVoltageNormalActions DisplayString, acpmAvgVoltageNormalTrapNum Integer32, acpmAvgVoltageNormalClass DisplayString, acpmAvgVoltageLowValue DisplayString, acpmAvgVoltageLowActions DisplayString, acpmAvgVoltageLowTrapNum Integer32, acpmAvgVoltageLowClass DisplayString, acpmAvgVoltageVLowValue DisplayString, acpmAvgVoltageVLowActions DisplayString, acpmAvgVoltageVLowTrapNum Integer32, acpmAvgVoltageVLowClass DisplayString, acpmAvgVoltageSysrepEnable DisplayString, acpmAvgVoltageSysrepThreshold DisplayString, acpmAvgVoltageSysrepLimit Integer32 } ACPMConfigAvgCurrent ::= SEQUENCE { acpmAvgCurrentIndex Integer32, acpmAvgCurrentEnable DisplayString, acpmAvgCurrentDeadband DisplayString, acpmAvgCurrentVHighValue DisplayString, acpmAvgCurrentVHighActions DisplayString, acpmAvgCurrentVHighTrapNum Integer32, acpmAvgCurrentVHighClass DisplayString, acpmAvgCurrentHighValue DisplayString, acpmAvgCurrentHighActions DisplayString, acpmAvgCurrentHighTrapNum Integer32, acpmAvgCurrentHighClass DisplayString, acpmAvgCurrentNormalActions DisplayString, acpmAvgCurrentNormalTrapNum Integer32, acpmAvgCurrentNormalClass DisplayString, acpmAvgCurrentLowValue DisplayString, acpmAvgCurrentLowActions DisplayString, acpmAvgCurrentLowTrapNum Integer32, acpmAvgCurrentLowClass DisplayString, acpmAvgCurrentVLowValue DisplayString, acpmAvgCurrentVLowActions DisplayString, acpmAvgCurrentVLowTrapNum Integer32, acpmAvgCurrentVLowClass DisplayString, acpmAvgCurrentSysrepEnable DisplayString, acpmAvgCurrentSysrepThreshold DisplayString, acpmAvgCurrentSysrepLimit Integer32 } ACPMConfigFreq ::= SEQUENCE { acpmFreqIndex Integer32, acpmFreqEnable DisplayString, acpmFreqDeadband DisplayString, acpmFreqVHighValue DisplayString, acpmFreqVHighActions DisplayString, acpmFreqVHighTrapNum Integer32, acpmFreqVHighClass DisplayString, acpmFreqHighValue DisplayString, acpmFreqHighActions DisplayString, acpmFreqHighTrapNum Integer32, acpmFreqHighClass DisplayString, acpmFreqNormalActions DisplayString, acpmFreqNormalTrapNum Integer32, acpmFreqNormalClass DisplayString, acpmFreqLowValue DisplayString, acpmFreqLowActions DisplayString, acpmFreqLowTrapNum Integer32, acpmFreqLowClass DisplayString, acpmFreqVLowValue DisplayString, acpmFreqVLowActions DisplayString, acpmFreqVLowTrapNum Integer32, acpmFreqVLowClass DisplayString, acpmFreqSysrepEnable DisplayString, acpmFreqSysrepThreshold DisplayString, acpmFreqSysrepLimit Integer32 } ACPMConfigTRP ::= SEQUENCE { acpmTRPIndex Integer32, acpmTRPEnable DisplayString, acpmTRPDeadband DisplayString, acpmTRPVHighValue DisplayString, acpmTRPVHighActions DisplayString, acpmTRPVHighTrapNum Integer32, acpmTRPVHighClass DisplayString, acpmTRPHighValue DisplayString, acpmTRPHighActions DisplayString, acpmTRPHighTrapNum Integer32, acpmTRPHighClass DisplayString, acpmTRPNormalActions DisplayString, acpmTRPNormalTrapNum Integer32, acpmTRPNormalClass DisplayString, acpmTRPLowValue DisplayString, acpmTRPLowActions DisplayString, acpmTRPLowTrapNum Integer32, acpmTRPLowClass DisplayString, acpmTRPVLowValue DisplayString, acpmTRPVLowActions DisplayString, acpmTRPVLowTrapNum Integer32, acpmTRPVLowClass DisplayString, acpmTRPSysrepEnable DisplayString, acpmTRPSysrepThreshold DisplayString, acpmTRPSysrepLimit Integer32 } ACPMConfigDisconnect ::= SEQUENCE { acpmDisconnectIndex Integer32, acpmDisconnectEnable DisplayString, acpmDisconnectActions DisplayString, acpmDisconnectTrapNum Integer32, acpmDisconnectClass DisplayString, acpmDisconnectNormalActions DisplayString, acpmDisconnectNormalTrapNum Integer32, acpmDisconnectNormalClass DisplayString } ACPMConfigTotalPowerFactor ::= SEQUENCE { acpmTPFIndex Integer32, acpmTPFEnable DisplayString, acpmTPFDeadband DisplayString, acpmTPFNormalActions DisplayString, acpmTPFNormalTrapNum Integer32, acpmTPFNormalClass DisplayString, acpmTPFLowValue DisplayString, acpmTPFLowActions DisplayString, acpmTPFLowTrapNum Integer32, acpmTPFLowClass DisplayString, acpmTPFVLowValue DisplayString, acpmTPFVLowActions DisplayString, acpmTPFVLowTrapNum Integer32, acpmTPFVLowClass DisplayString, acpmTPFSysrepEnable DisplayString, acpmTPFSysrepThreshold DisplayString, acpmTPFSysrepLimit Integer32 } WebXMLProxyDeviceConfig ::= SEQUENCE { wxpDeviceIndex Integer32, wxpDeviceEnable DisplayString, wxpDeviceIPAddress IpAddress, wxpDevicePort Integer32, wxpDeviceRemoteFile DisplayString, wxpDeviceLocalFile DisplayString, wxpDeviceTimeout Integer32, wxpDeviceTimestamp DisplayString } EthernetExpansionCardConfig ::= SEQUENCE { ethExpanCardIndex Integer32, ethExpanCardMAC DisplayString } AccessControlDevice ::= SEQUENCE { acdIndex Integer32, acdEnable DisplayString, acdName DisplayString, acdReader DisplayString, acdWiegandES Integer32, acdWiegandPoint Integer32, acdRelayType DisplayString, acdRelayES Integer32, acdRelayPoint Integer32, acdOpenTime Integer32, acdUserGroup Integer32 } AccessControlUser ::= SEQUENCE { acuIndexUserGroup Integer32, acuIndexUser Integer32, acuEnable DisplayString, acuName DisplayString, acuSn DisplayString, acuSunBegin DisplayString, acuSunEnd DisplayString, acuMonBegin DisplayString, acuMonEnd DisplayString, acuTueBegin DisplayString, acuTueEnd DisplayString, acuWedBegin DisplayString, acuWedEnd DisplayString, acuThuBegin DisplayString, acuThuEnd DisplayString, acuFriBegin DisplayString, acuFriEnd DisplayString, acuSatBegin DisplayString, acuSatEnd DisplayString } TelemetryPoint ::= SEQUENCE { telemetryPointIndex Integer32, telemetryPointName DisplayString, telemetryPointKey DisplayString, telemetryPointType DisplayString, telemetryPointClass DisplayString, telemetryPointDeadband DisplayString, telemetryPointShortcode DisplayString } SiteSecIntrusion ::= SEQUENCE { siteSecEnable DisplayString, siteSecDisarmed DisplayString, siteSecName DisplayString, siteSecState DisplayString, siteSecSensorES Integer32, siteSecSensorPoint Integer32, siteSecIntrusionThreshold Integer32, siteSecReader DisplayString, siteSecReaderThreshold Integer32, siteSecButtonEnable DisplayString, siteSecButtonES Integer32, siteSecButtonPoint Integer32, siteSecButtonType DisplayString, siteSecButtonThresholdArm Integer32, siteSecButtonThresholdDisarm Integer32, siteSecSirenEnable DisplayString, siteSecSirenES Integer32, siteSecSirenPoint Integer32, siteSecRearmDelay Integer32 } SiteSecMotion ::= SEQUENCE { siteSecMotionES Integer32, siteSecMotionPoint Integer32, siteSecMotionEnable DisplayString, siteSecMotionName DisplayString, siteSecMotionThresholdRearm Integer32 } SiteSecDoorAjar ::= SEQUENCE { siteSecDoorAjarEnable DisplayString, siteSecDoorAjarName DisplayString, siteSecDoorAjarES Integer32, siteSecDoorAjarPoint Integer32, siteSecDoorAjarThresholdNormal Integer32, siteSecDoorAjarThresholdExtraTime Integer32 } --*************************************************************************************** --TRAP DEFINITIONS --*************************************************************************************** s550StockSensorUnresponsiveTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock unresponsive trap is issued when a sensor is unresponsive." ::= { s550notifications 50 } s550notificationsStockContactClosureTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock contact closure trap is issued when a contact closure event happens." ::= { s550notifications 110 } s550notificationsStockTempTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock temperature trap is issued when a temperature event happens." ::= { s550notifications 120 } s550notificationsStockHumidityTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock humidity trap is issued when a humidity event happens." ::= { s550notifications 130 } s550notificationsStockAnalogTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock analog trap is issued when an analog sensor event happens." ::= { s550notifications 140 } s550notificationsStockOutputTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock output trap is issued when an output event happens. That is, depending on the configuration, when an output changes state for any reason, this trap will be sent." ::= { s550notifications 150 } s550StockPDCurrentTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock analog trap is issued when a power distribution current event happens." ::= { s550notifications 180 } s550StockPDVoltageTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock analog trap is issued when a power distribution voltage event happens." ::= { s550notifications 190 } s550StockPDFuseTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock analog trap is issued when a power distribution fuse event happens." ::= { s550notifications 210 } s550notificationsStockDbasePfullTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "The stock database percent full trap is issued when the database size surpasses the threshold." ::= { s550notifications 501 } s550notificationsStockDataAlarmTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "The stock data alarm trap is issued when a data alarm happens." ::= { s550notifications 503 } s550notificationsStockNoDataAlarmTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "The stock no-data alarm trap is issued when the unit has received no data for a configured interval within a configured schedule." ::= { s550notifications 505 } s550notificationsStockSchedTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "The stock scheduled alarm trap is issued when the current time reaches the scheduled alarm time." ::= { s550notifications 506 } s550notificationsStockImmediateTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "The stock immediate alarm trap is issued when the user enters the DOTRAP command." ::= { s550notifications 507 } s550StockBattRunningTrap NOTIFICATION-TYPE OBJECTS { siteName, liBattPercentCharge, liBattRunning } STATUS current DESCRIPTION "The stock trap issued when the battery power state change. Gives the unit name, percentage charge of the battery and if unit is running on battery backup (0 is False and 1 is True)" ::= { s550notifications 508 } s550notificationsStockCTSTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock CTS trap is issued when an RS-232 CTS event happens." ::= { s550notifications 510 } s550notificationsCPEDownTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock CPE Down trap is issued when a CPE Down event happens." ::= { s550notifications 511 } s550notificationsFuelSensorDisconnectTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock Fuel Sensor Disconnect trap is issued when a Fuel Sensor Disconnect or Connect (Return to Normal) event happens." ::= { s550notifications 515 } s550notificationsFuelSensorVolumeTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock Fuel Sensor Volume trap is issued when a Fuel Sensor Volume event happens" ::= { s550notifications 519 } s550notificationsACPowerMonitorAvgVoltageTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor average voltage trap is issued when an AC power monitor average voltage event happens." ::= { s550notifications 520 } s550notificationsACPowerMonitorAvgCurrentTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor average current trap is issued when an AC power monitor average current event happens." ::= { s550notifications 521 } s550notificationsACPowerMonitorFrequencyTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor frequency trap is issued when an AC power monitor frequency event happens." ::= { s550notifications 522 } s550notificationsACPowerMonitorTRPTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor TRP (total real power) trap is issued when an AC power monitor TRP event happens." ::= { s550notifications 523 } s550notificationsACPowerMonitorDisconnectTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor disconnect trap is issued when an AC power monitor disconnect event happens." ::= { s550notifications 524 } s550notificationsStockScriptTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock script trap is issued when a script triggers an event via a_lib.PostEvent() called with no trap number (or this trap number) specified." ::= { s550notifications 526 } s550notificationsFuelSensorVolumeSuddenChangeTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock Fuel Sensor Volume Sudden Change trap is issued when a Fuel Sensor Volume Sudden Change event happens" ::= { s550notifications 527 } s550notificationsFuelSensorVolumeSlowChangeTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock Fuel Sensor Volume Slow Change trap is issued when a Fuel Sensor Volume Slow Change event happens" ::= { s550notifications 528 } s550notificationsCameraTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock camera trap is issued when a camera event happens." ::= { s550notifications 539 } s550notificationsGeneratorNonStartTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock Generator Non-start trap is issued when the unit commands the generator to start as part of the generator exercising feature, and the generator fails to register as started after 30 seconds (as detected by CC generator running detection)." ::= { s550notifications 536 } s550notificationsACTotalPowerFactorTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock AC power monitor total power factor trap is issued when an AC power monitor total power factor event happens." ::= { s550notifications 540 } s550notificationsResetTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock reset trap is issued when a reset event happens." ::= { s550notifications 543 } s550notificationHVACAsentriaControlTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock HVAC Asentria Control trap is issued when an issue with temperature, humidity, fire detection and other HVAC related event happens." ::= { s550notifications 545 } s550notificationAccessControlTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock access control trap is issued when an access control device management event happens." ::= { s550notifications 547 } s550notificationHVACAirsysControlTrap NOTIFICATION-TYPE OBJECTS { siteName, stockTrapString, trapTypeString } STATUS current DESCRIPTION "A stock HVAC Airsys Control trap is issued when an issue related to alarm conditions for the Airsys HVAC system event happens." ::= { s550notifications 548 } s550notificationsUserTrap1000 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1000." ::= { s550notifications 1000 } s550notificationsUserTrap1001 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1001." ::= { s550notifications 1001 } s550notificationsUserTrap1002 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1002." ::= { s550notifications 1002 } s550notificationsUserTrap1003 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1003." ::= { s550notifications 1003 } s550notificationsUserTrap1004 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1004." ::= { s550notifications 1004 } s550notificationsUserTrap1005 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1005." ::= { s550notifications 1005 } s550notificationsUserTrap1006 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1006." ::= { s550notifications 1006 } s550notificationsUserTrap1007 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1007." ::= { s550notifications 1007 } s550notificationsUserTrap1008 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1008." ::= { s550notifications 1008 } s550notificationsUserTrap1009 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1009." ::= { s550notifications 1009 } s550notificationsUserTrap1010 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1010." ::= { s550notifications 1010 } s550notificationsUserTrap1011 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1011." ::= { s550notifications 1011 } s550notificationsUserTrap1012 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1012." ::= { s550notifications 1012 } s550notificationsUserTrap1013 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1013." ::= { s550notifications 1013 } s550notificationsUserTrap1014 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1014." ::= { s550notifications 1014 } s550notificationsUserTrap1015 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1015." ::= { s550notifications 1015 } s550notificationsUserTrap1016 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1016." ::= { s550notifications 1016 } s550notificationsUserTrap1017 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1017." ::= { s550notifications 1017 } s550notificationsUserTrap1018 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1018." ::= { s550notifications 1018 } s550notificationsUserTrap1019 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1019." ::= { s550notifications 1019 } s550notificationsUserTrap1020 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1020." ::= { s550notifications 1020 } s550notificationsUserTrap1021 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1021." ::= { s550notifications 1021 } s550notificationsUserTrap1022 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1022." ::= { s550notifications 1022 } s550notificationsUserTrap1023 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1023." ::= { s550notifications 1023 } s550notificationsUserTrap1024 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1024." ::= { s550notifications 1024 } s550notificationsUserTrap1025 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1025." ::= { s550notifications 1025 } s550notificationsUserTrap1026 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1026." ::= { s550notifications 1026 } s550notificationsUserTrap1027 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1027." ::= { s550notifications 1027 } s550notificationsUserTrap1028 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1028." ::= { s550notifications 1028 } s550notificationsUserTrap1029 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1029." ::= { s550notifications 1029 } s550notificationsUserTrap1030 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1030." ::= { s550notifications 1030 } s550notificationsUserTrap1031 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1031." ::= { s550notifications 1031 } s550notificationsUserTrap1032 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1032." ::= { s550notifications 1032 } s550notificationsUserTrap1033 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1033." ::= { s550notifications 1033 } s550notificationsUserTrap1034 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1034." ::= { s550notifications 1034 } s550notificationsUserTrap1035 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1035." ::= { s550notifications 1035 } s550notificationsUserTrap1036 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1036." ::= { s550notifications 1036 } s550notificationsUserTrap1037 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1037." ::= { s550notifications 1037 } s550notificationsUserTrap1038 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1038." ::= { s550notifications 1038 } s550notificationsUserTrap1039 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1039." ::= { s550notifications 1039 } s550notificationsUserTrap1040 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1040." ::= { s550notifications 1040 } s550notificationsUserTrap1041 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1041." ::= { s550notifications 1041 } s550notificationsUserTrap1042 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1042." ::= { s550notifications 1042 } s550notificationsUserTrap1043 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1043." ::= { s550notifications 1043 } s550notificationsUserTrap1044 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1044." ::= { s550notifications 1044 } s550notificationsUserTrap1045 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1045." ::= { s550notifications 1045 } s550notificationsUserTrap1046 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1046." ::= { s550notifications 1046 } s550notificationsUserTrap1047 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1047." ::= { s550notifications 1047 } s550notificationsUserTrap1048 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1048." ::= { s550notifications 1048 } s550notificationsUserTrap1049 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1049." ::= { s550notifications 1049 } s550notificationsUserTrap1050 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1050." ::= { s550notifications 1050 } s550notificationsUserTrap1051 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1051." ::= { s550notifications 1051 } s550notificationsUserTrap1052 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1052." ::= { s550notifications 1052 } s550notificationsUserTrap1053 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1053." ::= { s550notifications 1053 } s550notificationsUserTrap1054 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1054." ::= { s550notifications 1054 } s550notificationsUserTrap1055 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1055." ::= { s550notifications 1055 } s550notificationsUserTrap1056 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1056." ::= { s550notifications 1056 } s550notificationsUserTrap1057 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1057." ::= { s550notifications 1057 } s550notificationsUserTrap1058 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1058." ::= { s550notifications 1058 } s550notificationsUserTrap1059 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1059." ::= { s550notifications 1059 } s550notificationsUserTrap1060 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1060." ::= { s550notifications 1060 } s550notificationsUserTrap1061 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1061." ::= { s550notifications 1061 } s550notificationsUserTrap1062 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1062." ::= { s550notifications 1062 } s550notificationsUserTrap1063 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1063." ::= { s550notifications 1063 } s550notificationsUserTrap1064 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1064." ::= { s550notifications 1064 } s550notificationsUserTrap1065 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1065." ::= { s550notifications 1065 } s550notificationsUserTrap1066 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1066." ::= { s550notifications 1066 } s550notificationsUserTrap1067 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1067." ::= { s550notifications 1067 } s550notificationsUserTrap1068 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1068." ::= { s550notifications 1068 } s550notificationsUserTrap1069 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1069." ::= { s550notifications 1069 } s550notificationsUserTrap1070 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1070." ::= { s550notifications 1070 } s550notificationsUserTrap1071 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1071." ::= { s550notifications 1071 } s550notificationsUserTrap1072 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1072." ::= { s550notifications 1072 } s550notificationsUserTrap1073 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1073." ::= { s550notifications 1073 } s550notificationsUserTrap1074 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1074." ::= { s550notifications 1074 } s550notificationsUserTrap1075 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1075." ::= { s550notifications 1075 } s550notificationsUserTrap1076 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1076." ::= { s550notifications 1076 } s550notificationsUserTrap1077 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1077." ::= { s550notifications 1077 } s550notificationsUserTrap1078 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1078." ::= { s550notifications 1078 } s550notificationsUserTrap1079 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1079." ::= { s550notifications 1079 } s550notificationsUserTrap1080 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1080." ::= { s550notifications 1080 } s550notificationsUserTrap1081 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1081." ::= { s550notifications 1081 } s550notificationsUserTrap1082 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1082." ::= { s550notifications 1082 } s550notificationsUserTrap1083 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1083." ::= { s550notifications 1083 } s550notificationsUserTrap1084 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1084." ::= { s550notifications 1084 } s550notificationsUserTrap1085 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1085." ::= { s550notifications 1085 } s550notificationsUserTrap1086 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1086." ::= { s550notifications 1086 } s550notificationsUserTrap1087 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1087." ::= { s550notifications 1087 } s550notificationsUserTrap1088 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1088." ::= { s550notifications 1088 } s550notificationsUserTrap1089 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1089." ::= { s550notifications 1089 } s550notificationsUserTrap1090 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1090." ::= { s550notifications 1090 } s550notificationsUserTrap1091 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1091." ::= { s550notifications 1091 } s550notificationsUserTrap1092 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1092." ::= { s550notifications 1092 } s550notificationsUserTrap1093 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1093." ::= { s550notifications 1093 } s550notificationsUserTrap1094 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1094." ::= { s550notifications 1094 } s550notificationsUserTrap1095 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1095." ::= { s550notifications 1095 } s550notificationsUserTrap1096 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1096." ::= { s550notifications 1096 } s550notificationsUserTrap1097 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1097." ::= { s550notifications 1097 } s550notificationsUserTrap1098 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1098." ::= { s550notifications 1098 } s550notificationsUserTrap1099 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1099." ::= { s550notifications 1099 } s550notificationsUserTrap1100 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1100." ::= { s550notifications 1100 } s550notificationsUserTrap1101 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1101." ::= { s550notifications 1101 } s550notificationsUserTrap1102 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1102." ::= { s550notifications 1102 } s550notificationsUserTrap1103 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1103." ::= { s550notifications 1103 } s550notificationsUserTrap1104 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1104." ::= { s550notifications 1104 } s550notificationsUserTrap1105 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1105." ::= { s550notifications 1105 } s550notificationsUserTrap1106 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1106." ::= { s550notifications 1106 } s550notificationsUserTrap1107 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1107." ::= { s550notifications 1107 } s550notificationsUserTrap1108 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1108." ::= { s550notifications 1108 } s550notificationsUserTrap1109 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1109." ::= { s550notifications 1109 } s550notificationsUserTrap1110 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1110." ::= { s550notifications 1110 } s550notificationsUserTrap1111 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1111." ::= { s550notifications 1111 } s550notificationsUserTrap1112 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1112." ::= { s550notifications 1112 } s550notificationsUserTrap1113 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1113." ::= { s550notifications 1113 } s550notificationsUserTrap1114 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1114." ::= { s550notifications 1114 } s550notificationsUserTrap1115 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1115." ::= { s550notifications 1115 } s550notificationsUserTrap1116 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1116." ::= { s550notifications 1116 } s550notificationsUserTrap1117 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1117." ::= { s550notifications 1117 } s550notificationsUserTrap1118 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1118." ::= { s550notifications 1118 } s550notificationsUserTrap1119 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1119." ::= { s550notifications 1119 } s550notificationsUserTrap1120 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1120." ::= { s550notifications 1120 } s550notificationsUserTrap1121 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1121." ::= { s550notifications 1121 } s550notificationsUserTrap1122 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1122." ::= { s550notifications 1122 } s550notificationsUserTrap1123 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1123." ::= { s550notifications 1123 } s550notificationsUserTrap1124 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1124." ::= { s550notifications 1124 } s550notificationsUserTrap1125 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1125." ::= { s550notifications 1125 } s550notificationsUserTrap1126 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1126." ::= { s550notifications 1126 } s550notificationsUserTrap1127 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1127." ::= { s550notifications 1127 } s550notificationsUserTrap1128 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1128." ::= { s550notifications 1128 } s550notificationsUserTrap1129 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1129." ::= { s550notifications 1129 } s550notificationsUserTrap1130 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1130." ::= { s550notifications 1130 } s550notificationsUserTrap1131 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1131." ::= { s550notifications 1131 } s550notificationsUserTrap1132 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1132." ::= { s550notifications 1132 } s550notificationsUserTrap1133 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1133." ::= { s550notifications 1133 } s550notificationsUserTrap1134 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1134." ::= { s550notifications 1134 } s550notificationsUserTrap1135 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1135." ::= { s550notifications 1135 } s550notificationsUserTrap1136 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1136." ::= { s550notifications 1136 } s550notificationsUserTrap1137 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1137." ::= { s550notifications 1137 } s550notificationsUserTrap1138 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1138." ::= { s550notifications 1138 } s550notificationsUserTrap1139 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1139." ::= { s550notifications 1139 } s550notificationsUserTrap1140 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1140." ::= { s550notifications 1140 } s550notificationsUserTrap1141 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1141." ::= { s550notifications 1141 } s550notificationsUserTrap1142 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1142." ::= { s550notifications 1142 } s550notificationsUserTrap1143 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1143." ::= { s550notifications 1143 } s550notificationsUserTrap1144 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1144." ::= { s550notifications 1144 } s550notificationsUserTrap1145 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1145." ::= { s550notifications 1145 } s550notificationsUserTrap1146 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1146." ::= { s550notifications 1146 } s550notificationsUserTrap1147 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1147." ::= { s550notifications 1147 } s550notificationsUserTrap1148 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1148." ::= { s550notifications 1148 } s550notificationsUserTrap1149 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1149." ::= { s550notifications 1149 } s550notificationsUserTrap1150 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1150." ::= { s550notifications 1150 } s550notificationsUserTrap1151 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1151." ::= { s550notifications 1151 } s550notificationsUserTrap1152 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1152." ::= { s550notifications 1152 } s550notificationsUserTrap1153 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1153." ::= { s550notifications 1153 } s550notificationsUserTrap1154 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1154." ::= { s550notifications 1154 } s550notificationsUserTrap1155 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1155." ::= { s550notifications 1155 } s550notificationsUserTrap1156 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1156." ::= { s550notifications 1156 } s550notificationsUserTrap1157 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1157." ::= { s550notifications 1157 } s550notificationsUserTrap1158 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1158." ::= { s550notifications 1158 } s550notificationsUserTrap1159 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1159." ::= { s550notifications 1159 } s550notificationsUserTrap1160 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1160." ::= { s550notifications 1160 } s550notificationsUserTrap1161 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1161." ::= { s550notifications 1161 } s550notificationsUserTrap1162 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1162." ::= { s550notifications 1162 } s550notificationsUserTrap1163 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1163." ::= { s550notifications 1163 } s550notificationsUserTrap1164 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1164." ::= { s550notifications 1164 } s550notificationsUserTrap1165 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1165." ::= { s550notifications 1165 } s550notificationsUserTrap1166 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1166." ::= { s550notifications 1166 } s550notificationsUserTrap1167 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1167." ::= { s550notifications 1167 } s550notificationsUserTrap1168 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1168." ::= { s550notifications 1168 } s550notificationsUserTrap1169 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1169." ::= { s550notifications 1169 } s550notificationsUserTrap1170 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1170." ::= { s550notifications 1170 } s550notificationsUserTrap1171 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1171." ::= { s550notifications 1171 } s550notificationsUserTrap1172 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1172." ::= { s550notifications 1172 } s550notificationsUserTrap1173 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1173." ::= { s550notifications 1173 } s550notificationsUserTrap1174 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1174." ::= { s550notifications 1174 } s550notificationsUserTrap1175 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1175." ::= { s550notifications 1175 } s550notificationsUserTrap1176 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1176." ::= { s550notifications 1176 } s550notificationsUserTrap1177 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1177." ::= { s550notifications 1177 } s550notificationsUserTrap1178 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1178." ::= { s550notifications 1178 } s550notificationsUserTrap1179 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1179." ::= { s550notifications 1179 } s550notificationsUserTrap1180 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1180." ::= { s550notifications 1180 } s550notificationsUserTrap1181 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1181." ::= { s550notifications 1181 } s550notificationsUserTrap1182 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1182." ::= { s550notifications 1182 } s550notificationsUserTrap1183 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1183." ::= { s550notifications 1183 } s550notificationsUserTrap1184 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1184." ::= { s550notifications 1184 } s550notificationsUserTrap1185 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1185." ::= { s550notifications 1185 } s550notificationsUserTrap1186 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1186." ::= { s550notifications 1186 } s550notificationsUserTrap1187 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1187." ::= { s550notifications 1187 } s550notificationsUserTrap1188 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1188." ::= { s550notifications 1188 } s550notificationsUserTrap1189 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1189." ::= { s550notifications 1189 } s550notificationsUserTrap1190 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1190." ::= { s550notifications 1190 } s550notificationsUserTrap1191 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1191." ::= { s550notifications 1191 } s550notificationsUserTrap1192 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1192." ::= { s550notifications 1192 } s550notificationsUserTrap1193 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1193." ::= { s550notifications 1193 } s550notificationsUserTrap1194 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1194." ::= { s550notifications 1194 } s550notificationsUserTrap1195 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1195." ::= { s550notifications 1195 } s550notificationsUserTrap1196 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1196." ::= { s550notifications 1196 } s550notificationsUserTrap1197 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1197." ::= { s550notifications 1197 } s550notificationsUserTrap1198 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1198." ::= { s550notifications 1198 } s550notificationsUserTrap1199 NOTIFICATION-TYPE OBJECTS { siteName, esIndex, esName, trapEventTypeNumber, trapEventTypeName, esIndexPoint, esPointName, esID, clock, trapIncludedValue, trapIncludedString, trapEventClassNumber, trapEventClassName } STATUS current DESCRIPTION "This user-defined trap is issued when an event happens that causes a trap with specific trap type 1199." ::= { s550notifications 1199 } END