-- MIB version: 1.1.115 -- MIB release note -- | date | MIB version | author | note -- -------------------------------------------------------------------------------------------------------------------------- -- | 02/11/2015 | 1.1.116 | Zack Huang | Syntax modification of POP modes -- -------------------------------------------------------------------------------------------------------------------------- -- | 12/02/2014 | 1.1.115 | Zack Huang | Wording modification -- -------------------------------------------------------------------------------------------------------------------------- -- | 10/22/2014 | 1.1.114 | HC Sun | Add get/set function for new POP feature -- -------------------------------------------------------------------------------------------------------------------------- -- | 07/28/2014 | 1.1.113 | Zack Huang | Modify and unify responses of empty and not-support measurement values -- -------------------------------------------------------------------------------------------------------------------------- -- | 10/31/2013 | 1.1.112 | Zack Huang | updated mib to pass smilint level 3 -- -------------------------------------------------------------------------------------------------------------------------- -- | 10/03/2013 | 1.1.111 | Jenny Teng | updated mib to pass smilint level 3 -- -------------------------------------------------------------------------------------------------------------------------- -- | 08/09/2013 | 1.1.110 | Jenny Teng | Add outlet init mode -- -------------------------------------------------------------------------------------------------------------------------- -- | 07/17/2013 | 1.1.109 | Zack Huang | Add CAP Priority Settings -- -------------------------------------------------------------------------------------------------------------------------- -- | 07/05/2013 | 1.1.108 | Jenny Teng | Add Description and change some Syntax of oids -- -------------------------------------------------------------------------------------------------------------------------- -- | 05/23/2013 | 1.1.107 | Carter Wu | Change "usrEnable" order from 40 to 47 in "UsrListEntry" -- -------------------------------------------------------------------------------------------------------------------------- -- | 05/21/2013 | 1.1.106 | Carter Wu | Hide CAP function -- -------------------------------------------------------------------------------------------------------------------------- -- | 05/14/2013 | 1.1.105 | Carter Wu | Modify Power Threshold Description -- -------------------------------------------------------------------------------------------------------------------------- -- | 05/07/2013 | 1.1.104 | Carter Wu | Add CAP Function OID -- -------------------------------------------------------------------------------------------------------------------------- -- | 04/26/2013 | 1.1.103 | Zack Huang | Add Door Sensor Type OID -- -------------------------------------------------------------------------------------------------------------------------- -- | 04/24/2013 | 1.1.102 | Zack Huang | Modify Status Description of Door Sensor -- -------------------------------------------------------------------------------------------------------------------------- -- | 02/20/2013 | 1.1.101 | Zack Huang | -- -------------------------------------------------------------------------------------------------------------------------- -- | 02/17/2012 | | Jenny Teng | -- -------------------------------------------------------------------------------------------------------------------------- -- | 03/29/2010 | | Zack Yang | Initiative Version -- -------------------------------------------------------------------------------------------------------------------------- -- ATEN International Co., Ltd. -- This file defines the mib struct of Management in PE series -- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe subtree ATEN-PE-CFG DEFINITIONS ::= BEGIN IMPORTS enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI enterprises FROM RFC1155-SMI DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 MODULE-IDENTITY, NOTIFICATION-TYPE FROM SNMPv2-SMI KeyChange FROM SNMP-USER-BASED-SM-MIB TEXTUAL-CONVENTION FROM SNMPv2-TC; aten MODULE-IDENTITY LAST-UPDATED "201310311110Z" ORGANIZATION "ATEN" CONTACT-INFO "Aten, Inc." DESCRIPTION "ATEN PE MIB" REVISION "201310311110Z" DESCRIPTION "updated mib to pass smilint level 3" ::= { enterprises 21317 } atenProducts OBJECT IDENTIFIER ::= { aten 1 } overip OBJECT IDENTIFIER ::= { atenProducts 3 } poweroverip OBJECT IDENTIFIER ::= { overip 2} pe OBJECT IDENTIFIER ::= {poweroverip 2} userManagement OBJECT IDENTIFIER ::= { pe 1 } control OBJECT IDENTIFIER ::= { pe 2 } device OBJECT IDENTIFIER ::= { control 1 } doorSensor OBJECT IDENTIFIER ::= { device 16 } pop OBJECT IDENTIFIER ::= { device 17 } cap OBJECT IDENTIFIER ::= { device 18 } outlet OBJECT IDENTIFIER ::= { control 2 } bank OBJECT IDENTIFIER ::= { control 3 } deviceManagement OBJECT IDENTIFIER ::= { pe 3 } config OBJECT IDENTIFIER ::= { deviceManagement 4 } dashBoard OBJECT IDENTIFIER ::= { config 4 } servicePorts OBJECT IDENTIFIER ::= { config 5 } ipv4config OBJECT IDENTIFIER ::= { config 6 } eventNotification OBJECT IDENTIFIER ::= { config 7 } devicesnmp OBJECT IDENTIFIER ::= { eventNotification 1 } syslog OBJECT IDENTIFIER ::= { eventNotification 2 } smtp OBJECT IDENTIFIER ::= { eventNotification 3 } configurationNotification OBJECT IDENTIFIER ::= { eventNotification 9 } dateTime OBJECT IDENTIFIER ::= { config 8 } timeZone OBJECT IDENTIFIER ::= { dateTime 1 } manualInput OBJECT IDENTIFIER ::= { dateTime 2 } networkTime OBJECT IDENTIFIER ::= { dateTime 3 } devicesecurity OBJECT IDENTIFIER ::= { deviceManagement 5 } loginFailures OBJECT IDENTIFIER ::= { devicesecurity 1 } workingMode OBJECT IDENTIFIER ::= { devicesecurity 2 } accountPolicy OBJECT IDENTIFIER ::= { devicesecurity 3 } loginRestriction OBJECT IDENTIFIER ::= { devicesecurity 4 } ipFilter OBJECT IDENTIFIER ::= { loginRestriction 2 } macFilter OBJECT IDENTIFIER ::= { loginRestriction 3 } authentication OBJECT IDENTIFIER ::= { devicesecurity 5 } radius OBJECT IDENTIFIER ::= { authentication 1 } --CPM OBJECT IDENTIFIER ::= { pe 7 } -- CPMDevice OBJECT IDENTIFIER ::= { CPM 9 } -- Sensor OBJECT IDENTIFIER ::= { CPM 10 } -- EnergySensor OBJECT IDENTIFIER ::= { CPM 11 } --SNMPv3UsmAuthPrivProtocol ::= TEXTUAL-CONVENTION -- STATUS current -- DESCRIPTION -- "This textual convention enumerates the authentication and privledge -- protocol for USM configuration. -- " -- SYNTAX INTEGER -- { -- hmacMD5Auth(2), -- hmacSHAAuth(3) -- desPrivProtocol(5), -- aesPrivProtocol(6) -- } -- Device Control modelName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Indicate PE device model name." ::= { device 1 } deviceName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of PE device. string length: 1~39 NOTE: Input string as /empty to set this object to NULL. " ::= { device 2 } deviceValueTable OBJECT-TYPE SYNTAX SEQUENCE OF DeviceValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device value table. This table displays device's current, voltage, power and power dissipation. " ::= { device 3 } deviceValueEntry OBJECT-TYPE SYNTAX DeviceValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single deviceValue entry containing device info." INDEX { deviceValueIndex } ::= { deviceValueTable 1 } DeviceValueEntry ::= SEQUENCE { deviceValueIndex INTEGER, --deviceCurrent -- DisplayString, --deviceVoltage -- DisplayString, -- devicePower -- DisplayString, -- devicePowerDissipation -- DisplayString, inputMaxVoltage INTEGER, inputMaxCurrent INTEGER, powerCapacity INTEGER, devicePowerFactor DisplayString } deviceValueIndex OBJECT-TYPE SYNTAX INTEGER (1) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of deviceValue." ::= { deviceValueEntry 1 } --deviceCurrent OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device electric current value. -- " -- ::= { deviceValueEntry 2 } --deviceVoltage OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device voltage value." -- ::= { deviceValueEntry 3 } --devicePower OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power value." -- ::= { deviceValueEntry 4 } --devicePowerDissipation OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power dissipation value." -- ::= { deviceValueEntry 5 } inputMaxVoltage OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device input Voltage value. unit:(V) If the device does not support this OID, we show value 0. " ::= { deviceValueEntry 6 } inputMaxCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device input Current value. unit:(A) If the device does not support this OID, we show value 0." ::= { deviceValueEntry 7 } powerCapacity OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power Capacity value.unit:(VA) If the device does not support this OID, we show value 0." ::= { deviceValueEntry 8 } devicePowerFactor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Device power Factor value. If the device does not support this OID, it returns: not-support." ::= { deviceValueEntry 9 } --sensorValueTable OBJECT-TYPE -- SYNTAX SEQUENCE OF SensorValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Device's sensor value table. This table displays sensor's temperature, humidity and -- pressure. -- " -- ::= { device 4 } --sensorValueEntry OBJECT-TYPE -- SYNTAX SensorValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Single device's sensor value entry containing device info." -- INDEX { sensorValueIndex } -- ::= { sensorValueTable 1 } --SensorValueEntry ::= -- SEQUENCE { -- sensorValueIndex -- INTEGER, -- sensorTemperature -- DisplayString, -- sensorHumidity -- DisplayString, -- sensorPressure -- DisplayString, -- sensorProperty -- INTEGER -- } --sensorValueIndex OBJECT-TYPE -- SYNTAX INTEGER (1..6) -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Index of sensor number." -- ::= { sensorValueEntry 1 } --sensorTemperature OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Sensor's Temperature value." -- ::= { sensorValueEntry 2 } --sensorHumidity OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Sensor's Humidity value." -- ::= { sensorValueEntry 3 } --sensorPressure OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Sensor's Pressure value." -- ::= { sensorValueEntry 4 } --sensorProperty OBJECT-TYPE -- SYNTAX INTEGER { intake(1), exhaust(2), floor(3) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Sensor's Property." -- ::= { sensorValueEntry 5 } deviceOutletStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF DeviceOutletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device outlet status value table." ::= { device 5 } deviceOutletStatusEntry OBJECT-TYPE SYNTAX DeviceOutletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single deviceOutletStatus entry containing device info." INDEX { deviceOutletStatusIndex } ::= { deviceOutletStatusTable 1 } DeviceOutletStatusEntry ::= SEQUENCE { deviceOutletStatusIndex INTEGER, displayOutletStatus INTEGER --deviceOutletControl --INTEGER, --deviceOutletReboot -- INTEGER } deviceOutletStatusIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of deviceOutletStatus" ::= { deviceOutletStatusEntry 1 } displayOutletStatus OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), fault(4), noauth(5), not-support(6), pop(7) } MAX-ACCESS read-only STATUS current DESCRIPTION "Display outlet status." ::= { deviceOutletStatusEntry 2 } deviceConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF DeviceConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device configuration table" ::= { device 6 } deviceConfigEntry OBJECT-TYPE SYNTAX DeviceConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single deviceConfig entry containing device info." INDEX { deviceConfigIndex } ::= { deviceConfigTable 1 } DeviceConfigEntry ::= SEQUENCE { deviceConfigIndex INTEGER, deviceMinCurMT INTEGER, deviceMaxCurMT INTEGER, deviceMinVolMT INTEGER, deviceMaxVolMT INTEGER, deviceMinPMT INTEGER, deviceMaxPMT INTEGER, --deviceMinPDMT --INTEGER, deviceMaxPDMT INTEGER --deviceCurFlu -- INTEGER, --deviceVolFlu -- INTEGER, --devicePFlu -- INTEGER --devicePDFlu --INTEGER } deviceConfigIndex OBJECT-TYPE SYNTAX INTEGER (1) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of deviceConfig" ::= { deviceConfigEntry 1 } deviceMinCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 2 } deviceMaxCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 3 } deviceMinVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum voltage measurement threshold. Exapmple: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 4 } deviceMaxVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 5 } deviceMinPMT OBJECT-TYPE SYNTAX INTEGER (0..99999 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 6 } deviceMaxPMT OBJECT-TYPE SYNTAX INTEGER (0..99999 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 7 } --deviceCurFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display device electric current fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceConfigEntry 9 } --deviceVolFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display device voltage fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceConfigEntry 10 } --devicePFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display device power fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceConfigEntry 11 } --deviceMinPDMT OBJECT-TYPE --SYNTAX INTEGER (0..2000) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set device minimum power dissipation measurement threshold." --::= { deviceConfigEntry 8 } deviceMaxPDMT OBJECT-TYPE SYNTAX INTEGER (0..999990 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceConfigEntry 8 } --devicePDFlu OBJECT-TYPE --SYNTAX INTEGER (0..2000) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display device power dissipation fluctuation threshold." --::= { deviceConfigEntry 13 } deviceSensorTresholdTable OBJECT-TYPE SYNTAX SEQUENCE OF DeviceSensorTresholdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device environment value table" ::= { device 7 } deviceSensorTresholdEntry OBJECT-TYPE SYNTAX DeviceSensorTresholdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device's sensor Environment entry containing sensor info." INDEX { deviceSensorTresholdIndex } ::= { deviceSensorTresholdTable 1 } DeviceSensorTresholdEntry ::= SEQUENCE { deviceSensorTresholdIndex INTEGER, sensorMinTempMT INTEGER, sensorMaxTempMT INTEGER, sensorMinHumMT INTEGER, sensorMaxHumMT INTEGER, sensorMinPressMT INTEGER, sensorMaxPressMT INTEGER --sensorTempFlu --INTEGER, --sensorHumFlu --INTEGER, --sensorPressFlu --INTEGER } deviceSensorTresholdIndex OBJECT-TYPE SYNTAX INTEGER (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of sensor number" ::= { deviceSensorTresholdEntry 1 } sensorMinTempMT OBJECT-TYPE SYNTAX INTEGER (-200..600 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 2 } sensorMaxTempMT OBJECT-TYPE SYNTAX INTEGER (-200..600 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 3 } sensorMinHumMT OBJECT-TYPE SYNTAX INTEGER (150..950 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 4 } sensorMaxHumMT OBJECT-TYPE SYNTAX INTEGER (150..950 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 5 } sensorMinPressMT OBJECT-TYPE SYNTAX INTEGER (-2500..2500 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 6 } sensorMaxPressMT OBJECT-TYPE SYNTAX INTEGER (-2500..2500 | -3000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { deviceSensorTresholdEntry 7 } --sensorTempFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display sensor temperature fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceEnvironmentEntry 8 } --sensorHumFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display sensor humidity fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceEnvironmentEntry 9 } --sensorPressFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display sensor pressure fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { deviceEnvironmentEntry 10 } deviceOutletControl OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), nostatus(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION " This function is used for all outlet ports control. Set off(1) to turn off for all outlet ports. Set on(2) to turn on for all outlet ports. Get this object always return nostatus(3), because there is no device status. " ::= { device 8 } deviceOutletReboot OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION " This function is used for all outlet ports to reboot. Only when outlet status is ON can do outlet reboot action to all ports. Set yes(2) to reboot all outlet ports. Get this object always return no(1). " ::= { device 9 } switchable OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2), mix(3)} MAX-ACCESS read-only STATUS current DESCRIPTION " Outlet is switchable or not." ::= { device 10 } perportreading OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-only STATUS current DESCRIPTION " Outlet is per-port reading or not." ::= { device 11 } sensornumber OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION " Sensor number." ::= { device 12 } outletnumber OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION " Outlet number." ::= { device 13 } banknumber OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION " Bank number." ::= { device 14 } --chainnumber OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-only --STATUS current --DESCRIPTION -- " The slave device number." --::= { device 15 } doorSensorStatus OBJECT-TYPE SYNTAX INTEGER { close(0), open(1), not-attached(2), not-support(4) } MAX-ACCESS read-only STATUS current DESCRIPTION " Display door sensor status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device." ::= { doorSensor 1 } doorSensorType OBJECT-TYPE SYNTAX INTEGER { notinstalled(0), photo(1), inductiveproximity(2), reed(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Door Sensor Type Selection" ::= { doorSensor 2 } -- -- pop enablePOPmode OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2)} MAX-ACCESS read-write STATUS current DESCRIPTION " Enable/Disable POP mode." ::= { pop 1 } popThreshold OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION " (-1)means default value same as Bank Max Current 16 A. Example: range 0.0~32.0 represents 0~320 You can define the POP threshold or set as default(-1) value." ::= { pop 2 } enableOutletPOPmode OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2), not-support(3)} MAX-ACCESS read-write STATUS current DESCRIPTION " Enable/Disable Outlet POP mode." ::= { pop 3 } enableLIFOPOPmode OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2), not-support(3)} MAX-ACCESS read-write STATUS current DESCRIPTION " Enable/Disable LIFO POP mode." ::= { pop 4 } enablePriorityPOPmode OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2), not-support(3)} MAX-ACCESS read-write STATUS current DESCRIPTION " Enable/Disable Priority POP mode." ::= { pop 5 } -- CAP enableCAPmode OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2)} MAX-ACCESS read-write STATUS current DESCRIPTION " Enable/Disable CAP mode." ::= { cap 1 } outletCAPTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletCAPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet CAP table" ::= { cap 2 } outletCAPEntry OBJECT-TYPE SYNTAX OutletCAPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet CAP entry containing CAP info." INDEX { outletCAPIndex } ::= { outletCAPTable 1 } OutletCAPEntry ::= SEQUENCE { outletCAPIndex INTEGER, outletCAPPriority INTEGER } outletCAPIndex OBJECT-TYPE SYNTAX INTEGER (1..40) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of outlet's CAP configuration" ::= { outletCAPEntry 1 } outletCAPPriority OBJECT-TYPE SYNTAX INTEGER (0..99) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID." ::= { outletCAPEntry 2 } -- ontlet control init mode outletInitMode OBJECT-TYPE SYNTAX INTEGER {no-delaytime(1), delaytime(2), not-support(3)} MAX-ACCESS read-write STATUS current DESCRIPTION "choose outlet init mode you want." ::= { device 19 } -- integer value deviceIntegerValueTable OBJECT-TYPE SYNTAX SEQUENCE OF DeviceIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device value table. This table displays device's current, voltage, power and power dissipation. " ::= { device 99 } deviceIntegerValueEntry OBJECT-TYPE SYNTAX DeviceIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single deviceValue entry containing device info." INDEX { deviceIntegerValueIndex } ::= { deviceIntegerValueTable 1 } DeviceIntegerValueEntry ::= SEQUENCE { deviceIntegerValueIndex INTEGER, deviceIntegerCurrent INTEGER, deviceIntegerVoltage INTEGER, deviceIntegerPower INTEGER, deviceIntegerPowerDissipation INTEGER --inputMaxVoltage -- INTEGER, --inputMaxCurrent -- INTEGER, --powerCapacity -- INTEGER --devicePowerFactor -- INTEGER } deviceIntegerValueIndex OBJECT-TYPE SYNTAX INTEGER (1) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of deviceValue." ::= { deviceIntegerValueEntry 1 } deviceIntegerCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { deviceIntegerValueEntry 2 } deviceIntegerVoltage OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { deviceIntegerValueEntry 3 } deviceIntegerPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { deviceIntegerValueEntry 4 } deviceIntegerPowerDissipation OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { deviceIntegerValueEntry 5 } --inputMaxVoltage OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device input Voltage value. unit:(V)" -- ::= { deviceValueEntry 6 } --inputMaxCurrent OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device input Current value. unit:(A)" -- ::= { deviceValueEntry 7 } --powerCapacity OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power Capacity value.unit:(VA)" -- ::= { deviceValueEntry 8 } --devicePowerFactor OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power Factor value." -- ::= { deviceValueEntry 9 } sensorIntegerValueTable OBJECT-TYPE SYNTAX SEQUENCE OF SensorIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device's sensor value table. This table displays sensor's temperature, humidity and pressure. " ::= { device 100 } sensorIntegerValueEntry OBJECT-TYPE SYNTAX SensorIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single device's sensor value entry containing device info." INDEX { sensorIntegerValueIndex } ::= { sensorIntegerValueTable 1 } SensorIntegerValueEntry ::= SEQUENCE { sensorIntegerValueIndex INTEGER, sensorIntegerTemperature INTEGER, sensorIntegerHumidity INTEGER, sensorIntegerPressure INTEGER --sensorIntegerProperty -- INTEGER } sensorIntegerValueIndex OBJECT-TYPE SYNTAX INTEGER (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of sensor number." ::= { sensorIntegerValueEntry 1 } sensorIntegerTemperature OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { sensorIntegerValueEntry 2 } sensorIntegerHumidity OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { sensorIntegerValueEntry 3 } sensorIntegerPressure OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { sensorIntegerValueEntry 4 } --sensorIntegerProperty OBJECT-TYPE -- SYNTAX INTEGER { intake(1), exhaust(2), floor(3) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Sensor's Property." -- ::= { sensorIntegerValueEntry 5 } -- Device Control End -- Outlet Control outletValueTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Display total outlet value table" ::= { outlet 1 } outletValueEntry OBJECT-TYPE SYNTAX OutletValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single outletValue entry containing outlet info." INDEX { outletValueIndex } ::= { outletValueTable 1 } OutletValueEntry ::= SEQUENCE { outletValueIndex INTEGER, -- outletCurrent -- DisplayString, -- outletVoltage -- DisplayString, -- outletPower -- DisplayString, -- outletPowerDissipation -- DisplayString, outletMaxCurrent INTEGER, outletPowerFactor DisplayString } outletValueIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of outlet number" ::= { outletValueEntry 1 } --outletCurrent OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Outlet electric current value" -- ::= { outletValueEntry 2 } --outletVoltage OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Outlet voltage value" -- ::= { outletValueEntry 3 } --outletPower OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Outlet power value" -- ::= { outletValueEntry 4 } --outletPowerDissipation OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Outlet power dissipation value" -- ::= { outletValueEntry 5 } outletMaxCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet Max Current value. unit: (A). If the device does not support this OID, we show value 0. " ::= { outletValueEntry 6 } outletPowerFactor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet Power Factor value. If the device does not support this OID, it returns: not-support." ::= { outletValueEntry 7 } outlet1Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 1 status. Can't set pending status." ::= { outlet 2 } outlet2Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 2 status. Can't set pending status." ::= { outlet 3 } outlet3Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 3 status. Can't set pending status." ::= { outlet 4 } outlet4Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 4 status. Can't set pending status." ::= { outlet 5 } outlet5Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 5 status. Can't set pending status." ::= { outlet 6 } outlet6Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 6 status. Can't set pending status." ::= { outlet 7 } outlet7Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 7 status. Can't set pending status." ::= { outlet 8 } outlet8Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 8 status. Can't set pending status." ::= { outlet 9 } outlet9Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 9 status. Can't set pending status." ::= { outlet 11 } outlet10Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 10 status. Can't set pending status." ::= { outlet 12 } outlet11Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 11 status. Can't set pending status." ::= { outlet 13 } outlet12Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 12 status. Can't set pending status." ::= { outlet 14 } outlet13Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 13 status. Can't set pending status." ::= { outlet 15 } outlet14Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 14 status. Can't set pending status." ::= { outlet 16 } outlet15Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 15 status. Can't set pending status." ::= { outlet 17 } outlet16Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 16 status. Can't set pending status." ::= { outlet 18 } outlet17Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 17 status. Can't set pending status." ::= { outlet 19 } outlet18Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 18 status. Can't set pending status." ::= { outlet 20 } outlet19Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 19 status. Can't set pending status." ::= { outlet 21 } outlet20Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 20 status. Can't set pending status." ::= { outlet 22 } outlet21Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 21 status. Can't set pending status." ::= { outlet 23 } outlet22Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 22 status. Can't set pending status." ::= { outlet 24 } outlet23Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 23 status. Can't set pending status." ::= { outlet 25 } outlet24Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 24 status. Can't set pending status." ::= { outlet 26 } outlet25Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 25 status. Can't set pending status." ::= { outlet 27 } outlet26Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 26 status. Can't set pending status." ::= { outlet 28 } outlet27Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 27 status. Can't set pending status." ::= { outlet 29 } outlet28Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 28 status. Can't set pending status." ::= { outlet 30 } outlet29Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 29 status. Can't set pending status." ::= { outlet 31 } outlet30Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 30 status. Can't set pending status." ::= { outlet 32 } outlet31Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 31 status. Can't set pending status." ::= { outlet 33 } outlet32Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 32 status. Can't set pending status." ::= { outlet 34 } outlet33Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 33 status. Can't set pending status." ::= { outlet 35 } outlet34Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 34 status. Can't set pending status." ::= { outlet 36 } outlet35Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 35 status. Can't set pending status." ::= { outlet 37 } outlet36Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 36 status. Can't set pending status." ::= { outlet 38 } outlet37Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 37 status. Can't set pending status." ::= { outlet 39 } outlet38Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 38 status. Can't set pending status." ::= { outlet 40 } outlet39Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 39 status. Can't set pending status." ::= { outlet 41 } outlet40Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 40 status. Can't set pending status." ::= { outlet 42 } outlet41Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 41 status. Can't set pending status." ::= { outlet 43 } outlet42Status OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display and control outlet 42 status. Can't set pending status." ::= { outlet 44 } -- outletSwitchableTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletSwitchableEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION " " ::= { outlet 70 } outletSwitchableEntry OBJECT-TYPE SYNTAX OutletSwitchableEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" INDEX { outletSwitchableIndex } ::= { outletSwitchableTable 1 } OutletSwitchableEntry ::= SEQUENCE { outletSwitchableIndex INTEGER, outletSwitchable INTEGER } outletSwitchableIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of outlet number. " ::= { outletSwitchableEntry 1 } outletSwitchable OBJECT-TYPE SYNTAX INTEGER {no(1), yes(2) } MAX-ACCESS read-only STATUS current DESCRIPTION " " ::= { outletSwitchableEntry 2 } --outlet integer value outletIntegerValueTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Display total outlet value table" ::= { outlet 99 } outletIntegerValueEntry OBJECT-TYPE SYNTAX OutletIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single outletValue entry containing outlet info." INDEX { outletIntegerValueIndex } ::= { outletIntegerValueTable 1 } OutletIntegerValueEntry ::= SEQUENCE { outletIntegerValueIndex INTEGER, outletIntegerCurrent INTEGER, outletIntegerVoltage INTEGER, outletIntegerPower INTEGER, outletIntegerPowerDissipation INTEGER } outletIntegerValueIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of outlet number. " ::= { outletIntegerValueEntry 1 } outletIntegerCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { outletIntegerValueEntry 2 } outletIntegerVoltage OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { outletIntegerValueEntry 3 } outletIntegerPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { outletIntegerValueEntry 4 } outletIntegerPowerDissipation OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000." ::= { outletIntegerValueEntry 5 } outletConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet configuration table" ::= { outlet 10 } outletConfigEntry OBJECT-TYPE SYNTAX OutletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet Config entry containing outlet info." INDEX { outletConfigIndex } ::= { outletConfigTable 1 } OutletConfigEntry ::= SEQUENCE { outletConfigIndex INTEGER, outletName DisplayString, outletConfirmation INTEGER, outletOnDelayTime INTEGER, outletOffDelayTime INTEGER, outletShutdownMethod INTEGER, outletMAC DisplayString, outletMinCurMT INTEGER, outletMaxCurMT INTEGER, outletMinVolMT INTEGER, outletMaxVolMT INTEGER, outletMinPMT INTEGER, outletMaxPMT INTEGER, --outletMinPDMT --INTEGER, outletMaxPDMT INTEGER --outletCurFlu --INTEGER, --outletVolFlu --INTEGER, --outletPFlu --INTEGER --outletPDFlu --INTEGER } outletConfigIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of outlet number" ::= { outletConfigEntry 1 } outletName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the name of outlet. If the device does not support this OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL. " ::= { outletConfigEntry 2 } outletConfirmation OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) , noauth(3), not-support(4)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the confirmation of outlet." ::= { outletConfigEntry 3 } outletOnDelayTime OBJECT-TYPE SYNTAX INTEGER (0..999 | -1) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the ON delay time of outlet. When this model does not support the OID, we show value -1. " ::= { outletConfigEntry 4 } outletOffDelayTime OBJECT-TYPE SYNTAX INTEGER (0..999 | -1) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the OFF delay time of outlet. When this model does not support the OID, we show value -1. " ::= { outletConfigEntry 5 } outletShutdownMethod OBJECT-TYPE SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4)} MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the shutdown mehtod of outlet." ::= { outletConfigEntry 6 } outletMAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the MAC address of ShutdownMethod. If the device does not support this OID, we show n/a. string length: 12 " ::= { outletConfigEntry 7 } outletMinCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 8 } outletMaxCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 9 } outletMinVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 10 } outletMaxVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 11 } outletMinPMT OBJECT-TYPE SYNTAX INTEGER (0..99999 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 12 } outletMaxPMT OBJECT-TYPE SYNTAX INTEGER (0..99999 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 13 } --outletMinPDMT OBJECT-TYPE --SYNTAX INTEGER (0..100) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the outlet minimum power dissipation measurment threshold ." --::= { outletConfigEntry 14 } outletMaxPDMT OBJECT-TYPE SYNTAX INTEGER (0..999990 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { outletConfigEntry 14 } --outletCurFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display the outlet electric current fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { outletConfigEntry 15 } --outletVolFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display the outlet voltage fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { outletConfigEntry 16 } --outletPFlu OBJECT-TYPE --SYNTAX INTEGER --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display the outlet power fluctuation threshold. -- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { outletConfigEntry 17 } --outletPDFlu OBJECT-TYPE --SYNTAX INTEGER (0..100) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display the outlet power dissipation fluctuation threshold ." --::= { outletConfigEntry 19 } -- Outlet Control End -- Bank control breakerStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF BreakerStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Display total bank value table" ::= { bank 1 } breakerStatusEntry OBJECT-TYPE SYNTAX BreakerStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single bankValue entry containing bank info." INDEX { breakerStatusIndex } ::= { breakerStatusTable 1 } BreakerStatusEntry ::= SEQUENCE { breakerStatusIndex INTEGER, breakerStatus INTEGER } breakerStatusIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of breaker number." ::= { breakerStatusEntry 1 } breakerStatus OBJECT-TYPE SYNTAX INTEGER { off(1), on(2), not-support(3)} MAX-ACCESS read-only STATUS current DESCRIPTION "Breaker status." ::= { breakerStatusEntry 2 } bankValueTable OBJECT-TYPE SYNTAX SEQUENCE OF BankValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Display total bank value table" ::= { bank 2 } bankValueEntry OBJECT-TYPE SYNTAX BankValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single bankValue entry containing bank info." INDEX { bankValueIndex } ::= { bankValueTable 1 } BankValueEntry ::= SEQUENCE { bankValueIndex INTEGER, -- bankCurrent -- DisplayString, -- bankVoltage -- DisplayString, -- bankPower -- DisplayString, -- bankPowerDissipation -- DisplayString, bankMaxCurrent INTEGER, bankAttachStatus INTEGER, bankPowerFactor DisplayString } bankValueIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of bank number" ::= { bankValueEntry 1 } --bankCurrent OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Bank electric current value" -- ::= { bankValueEntry 2 } --bankVoltage OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Bank voltage value" -- ::= { bankValueEntry 3 } --bankPower OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Bank power value" -- ::= { bankValueEntry 4 } --bankPowerDissipation OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Bank power dissipation value" -- ::= { bankValueEntry 5 } bankMaxCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "The Bank Max Current value. unit: (A) EC1000:0A~320A " ::= { bankValueEntry 6 } bankAttachStatus OBJECT-TYPE SYNTAX INTEGER { noattached(1), attached(2), error(3), noexisted(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The status of Energy sensor Bank attached status." ::= { bankValueEntry 7 } bankPowerFactor OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Bank Power Factor value. If the device does not support this OID, it returns: not-support." ::= { bankValueEntry 8 } bankConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF BankConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank configuration table" ::= { bank 3 } bankConfigEntry OBJECT-TYPE SYNTAX BankConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank Config entry containing Bank info." INDEX { bankConfigIndex } ::= { bankConfigTable 1 } BankConfigEntry ::= SEQUENCE { bankConfigIndex INTEGER, bankName DisplayString, bankMinCurMT INTEGER, bankMaxCurMT INTEGER, bankMinVolMT INTEGER, bankMaxVolMT INTEGER, bankMinPMT INTEGER, bankMaxPMT INTEGER, --outletMinPDMT --INTEGER, bankMaxPDMT INTEGER --outletCurFlu --INTEGER, --outletVolFlu --INTEGER, --outletPFlu --INTEGER --outletPDFlu --INTEGER } bankConfigIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of bank number" ::= { bankConfigEntry 1 } bankName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the name of bank. When this model does not support the OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL. " ::= { bankConfigEntry 2 } bankMinCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 3 } bankMaxCurMT OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 4} bankMinVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 5 } bankMaxVolMT OBJECT-TYPE SYNTAX INTEGER (900..2600 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 6 } bankMinPMT OBJECT-TYPE SYNTAX INTEGER (0..99999| -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 7 } bankMaxPMT OBJECT-TYPE SYNTAX INTEGER (0..99999 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 8 } --outletMinPDMT OBJECT-TYPE --SYNTAX INTEGER (0..100) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the outlet minimum power dissipation measurment threshold ." --::= { outletConfigEntry 14 } bankMaxPDMT OBJECT-TYPE SYNTAX INTEGER (0..999990 | -3000 | -2000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000." ::= { bankConfigEntry 9 } bankControlTable OBJECT-TYPE SYNTAX SEQUENCE OF BankControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank Control table" ::= { bank 4 } bankControlEntry OBJECT-TYPE SYNTAX BankControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank control entry." INDEX { bankControlIndex } ::= { bankControlTable 1 } BankControlEntry ::= SEQUENCE { bankControlIndex INTEGER, bankControlStatus INTEGER } bankControlIndex OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of bank number" ::= { bankControlEntry 1 } bankControlStatus OBJECT-TYPE SYNTAX INTEGER {off(1), on(2), reboot(3), nostatus(4), not-support(5)} MAX-ACCESS read-write STATUS current DESCRIPTION " This function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to turn on for outlet control of bank. Get this object always return nostatus(3), because there is no bank status. " ::= { bankControlEntry 2 } -- Bank control End bankIntegerValueTable OBJECT-TYPE SYNTAX SEQUENCE OF BankIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Display total bank value table" ::= { bank 99 } bankIntegerValueEntry OBJECT-TYPE SYNTAX BankIntegerValueEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single bankValue entry containing bank info." INDEX { bankIntegerValueIndex } ::= { bankIntegerValueTable 1 } BankIntegerValueEntry ::= SEQUENCE { bankIntegerValueIndex INTEGER, bankIntegerCurrent INTEGER, bankIntegerVoltage INTEGER, bankIntegerPower INTEGER, bankIntegerPowerDissipation INTEGER --bankIntegerMaxCurrent -- INTEGER, --bankIntegerAttachStatus -- INTEGER, --bankIntegerPowerFactor --INTEGER } bankIntegerValueIndex OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of bank number. " ::= { bankIntegerValueEntry 1 } bankIntegerCurrent OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank electric current value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { bankIntegerValueEntry 2 } bankIntegerVoltage OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank voltage value. This value indicates that 1,000 times. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { bankIntegerValueEntry 3 } bankIntegerPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank power value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { bankIntegerValueEntry 4 } bankIntegerPowerDissipation OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank power dissipation value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000." ::= { bankIntegerValueEntry 5 } --bankMaxCurrent OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The Bank Max Current value. unit: (A) -- EC1000:0A~320A -- " -- ::= { bankValueEntry 6 } --bankAttachStatus OBJECT-TYPE -- SYNTAX INTEGER { noattached(1), attached(2), error(3) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The status of Energy sensor Bank attached status." -- ::= { bankValueEntry 7 } --bankPowerFactor OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Bank Power Factor value" -- ::= { bankValueEntry 8 } -- Device Management deviceMAC OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Display device MAC address." ::= { config 1 } deviceIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-only STATUS current DESCRIPTION "Display device IP address." ::= { config 2 } deviceFWversion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Display device FW version." ::= { config 3 } -- dashboard settings dashboardRow OBJECT-TYPE SYNTAX INTEGER (1..26) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device's dashboard row number." ::= { dashBoard 1 } dashboardColumn OBJECT-TYPE SYNTAX INTEGER (1..26) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device's dashboard column number." ::= { dashBoard 2 } dashboardRackName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device's dashboard rack name. string length: 1~32 NOTE: Input string as /empty to set this object to NULL. " ::= { dashBoard 3 } httpPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the HTTP port of PE device." ::= { servicePorts 1 } httpsPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the HTTPs port of PE device." ::= { servicePorts 2 } httpsOnlyEnable OBJECT-TYPE SYNTAX INTEGER {yes(1), no(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs" ::= { servicePorts 3 } staticIPEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set IPv4 address automatically or not" ::= { ipv4config 1 } fixedIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set fixed IPv4 address" ::= { ipv4config 2 } subnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set subnet mask address" ::= { ipv4config 3 } gateway OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set gateway address" ::= { ipv4config 4 } staticDNSEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set DNS address automatically or not" ::= { ipv4config 5 } dnsPreferIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer DNS address" ::= { ipv4config 6 } dnsAlternateIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternate DNS address" ::= { ipv4config 7 } trapEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Indicates if this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c." ::= { devicesnmp 1 } trapVersion OBJECT-TYPE SYNTAX INTEGER { v1(1), v2c(2), v3(3)} MAX-ACCESS read-write STATUS current DESCRIPTION " Choose SNMP Trap version to send trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c." ::= { devicesnmp 2 } snmpTrapTable OBJECT-TYPE SYNTAX SEQUENCE OF SnmpTrapEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "PE SNMP agent trap setup table. If users want to use trap, they must set enable trap, ip and community first." ::= { devicesnmp 3 } snmpTrapEntry OBJECT-TYPE SYNTAX SnmpTrapEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single trap entry containing trap receiver info." INDEX { trapReceiverNumber } ::= { snmpTrapTable 1 } SnmpTrapEntry ::= SEQUENCE { trapReceiverNumber INTEGER, --trapEnabled --INTEGER, trapReceiverIPAddress IpAddress, --trapCommunity --DisplayString, trapPort INTEGER, trapCommunity DisplayString, trapUsername DisplayString, trapAuthpassword DisplayString, trapPrivpassword DisplayString } trapReceiverNumber OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Index of trap receiver" ::= { snmpTrapEntry 1 } trapReceiverIPAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Trap receiver IP address" ::= { snmpTrapEntry 2 } trapPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "NMS trap port to be used by agent to send trap" ::= { snmpTrapEntry 3 } trapCommunity OBJECT-TYPE SYNTAX DisplayString (SIZE (0..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv1/v2c to receive trap should set this Community string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. " ::= { snmpTrapEntry 4 } trapUsername OBJECT-TYPE SYNTAX DisplayString (SIZE (0..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this string. NOTE: Input string as /empty to set this object to NULL. MAX string length: 20 " ::= { snmpTrapEntry 5 } trapAuthpassword OBJECT-TYPE SYNTAX DisplayString (SIZE (8..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. " ::= { snmpTrapEntry 6 } trapPrivpassword OBJECT-TYPE SYNTAX DisplayString (SIZE (8..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. " ::= { snmpTrapEntry 7 } --privacypassword OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "SNMPv3 privacy password to be used by agent to send trap -- string length: 8~20 -- " -- ::= { devicesnmp 4 } --engineID OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "EngineID" -- ::= { devicesnmp 5 } --engineBoot OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "EngineBoot" -- ::= { devicesnmp 6 } --engineTime OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "EngineTime" -- ::= { devicesnmp 7 } --engineMaxMSG OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "EngineMaxMSG" -- ::= { devicesnmp 8 } sysLogServerEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set syslog server address automatically or not" ::= { syslog 1 } sysLogServerIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set syslog server address" ::= { syslog 2 } sysLogServerPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set syslog server port" ::= { syslog 3 } smtpServerEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set SMTP server enable status." ::= { smtp 1 } smtpServerName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a SMTP server name. NOTE: Input string as /empty to set this object to NULL. " ::= { smtp 2 } smtpAuthEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set authentication of SMTP server." ::= { smtp 3 } smtpAccountName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a user's name of SMTP server. NOTE: Input string as /empty to set this object to NULL. " ::= { smtp 4 } smtpAccountPwd OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a user's password of SMTP server. NOTE: Input string as /empty to set this object to NULL. " ::= { smtp 5 } smtpMailFrom OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL. " ::= { smtp 6 } smtpMailTo OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL. " ::= { smtp 7 } -- configurationNotifyEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION " " ::= { configurationNotification 1 } configurationNotifyTrapMSG NOTIFICATION-TYPE STATUS current --OBJECTS { customTrapMSG } DESCRIPTION " " ::= { configurationNotification 2 } -- timeZoneSetting OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the time zone of PE device. (0) [GMT-12:00] Eniwetok Kwajalein (1) [GMT-11:00] Midway Island Samoa (2) [GMT-10:00] Hawaii (3) [GMT-09:00] Alaska (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana (5) [GMT-07:00] Mountain Time (US & Canada) (6) [GMT-07:00] Arizona (7) [GMT-06:00] Central Time (US & Canada) (8) [GMT-06:00] Mexico City (9) [GMT-06:00] Saskatchewan (10)[GMT-06:00] Central America (11)[GMT-05:00] Eastern Time (US & Canada) (12)[GMT-05:00] Indiana (East) (13)[GMT-05:00] Bogota Lima Quito (14)[GMT-04:00] Atlantic Time (Canada) (15)[GMT-04:00] Caracas La Paz (16)[GMT-04:00] Santiago (17)[GMT-03:30] Newfoundland (18)[GMT-03:00] Buenos Aires Georgetown (19)[GMT-03:00] Brasilia (20)[GMT-03:00] Greenland (21)[GMT-02:00] Mid-Atlantic (22)[GMT-01:00] Azores (23)[GMT-01:00] Cape Verde Is (24)[GMT] Casablanca Monrovia (25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius (27)[GMT+01:00] West Central Africa (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna (31)[GMT+02:00] Cairo (32)[GMT+02:00] Harare Pretoria (33)[GMT+02:00] Jerusalem (34)[GMT+02:00] Bucharest (35)[GMT+02:00] Helsinki Riga Tallinn (36)[GMT+02:00] Athens Istanbul Minsk (37)[GMT+03:00] Kuwait Riyadh (38)[GMT+03:00] Nairobi (39)[GMT+03:00] Baghdad (40)[GMT+03:00] Moscow St. Petersburg Volgograd (41)[GMT+03:30] Tehran (42)[GMT+04:00] Abu Dhabi Muscat (43)[GMT+04:00] Baku Tbilisi Yerevan (44)[GMT+04:30] Kabul (45)[GMT+05:00] Islamabad Karachi Tashkent (46)[GMT+05:00] Ekaterinburg (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi (48)[GMT+05:45] Kathmandu (49)[GMT+06:00] Astana Dhaka (50)[GMT+06:00] Sri Jayawardenepura (51)[GMT+06:00] Almaty Novosibirsk (52)[GMT+06:30] Rangoon (53)[GMT+07:00] Bangkok Hanoi Jakarta (54)[GMT+07:00] Krasnoyarsk (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi (56)[GMT+08:00] Perth (57)[GMT+08:00] Kuala Lumpur Singapore (58)[GMT+08:00] Taipei (59)[GMT+08:00] Irkutsk Ulaan Bataar (60)[GMT+09:00] Osaka Sapporo Tokyo (61)[GMT+09:00] Seoul (62)[GMT+09:00] Yakutsk (63)[GMT+09:30] Darwin (64)[GMT+09:30] Adelaide (65)[GMT+10:00] Canberra Melbourne Sydney (66)[GMT+10:00] Brisbane (67)[GMT+10:00] Guam Port Moresby (68)[GMT+10:00] Hobart (69)[GMT+10:00] Vladivostok (70)[GMT+11:00] Magadan Solomon Is New Caledonia (71)[GMT+12:00] Fiji Kamchatka Marshall Is. (72)[GMT+12:00] Auckland Wellington (73)[GMT+13:00] Nuku'alofa " ::= { timeZone 1 } dstEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set daylight savings time ." ::= { timeZone 2 } dateSetting OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set date in a manual way.(This is Greenwich Mean Time, GMT) string length: 10 This value format must match the following form: YYYY-MM-DD ex. 2011-01-01 Note: range of year: 2000-2099 range of month: 01-12 range of day: 01-31 " ::= { manualInput 1 } timeSetting OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set time in a manual way.(This is Greenwich Mean Time, GMT) string length: 8 This value format must match the following form: HH:MM:SS ex. 02:02:02 Note: range of hour: 00-24 range of minute: 00-60 range of second: 00-60 " ::= { manualInput 2 } --syncWithPC OBJECT-TYPE -- SYNTAX INTEGER { no(1), yes(2) } -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set date time useing sync PC way." -- ::= { manualInput 3 } autoAdjustEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set date time useing auto adjustment way." ::= { networkTime 1 } preferNTP OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79) " ::= { networkTime 2 } preferServerIPenable OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable or disable prefer custom server IP." ::= { networkTime 3 } preferNTPIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer NTP server IP." ::= { networkTime 4 } alternateNtpEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set date time using alternate NTP server." ::= { networkTime 5 } alternateNtp OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternative NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79) " ::= { networkTime 6 } alternateServerIPenable OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable or disable alternate custom server IP." ::= { networkTime 7 } alternateNtpIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternative NTP server IP." ::= { networkTime 8 } adjustTimeEveryDays OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set frequency of adjustment in days." ::= { networkTime 9 } --adjustTimeNow OBJECT-TYPE --SYNTAX INTEGER { no(1), yes(2) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Adjust time using NTP server." --::= { networkTime 8 } loginAllowTimes OBJECT-TYPE SYNTAX INTEGER (1..99) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set time of login faliure." ::= { loginFailures 1 } loginTimeOut OBJECT-TYPE SYNTAX INTEGER (1..240) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set login time out." ::= { loginFailures 2 } icmpEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of ICMP." ::= { workingMode 1 } --multiUserEnabled OBJECT-TYPE --SYNTAX INTEGER { no(1), yes(2) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set status of multi-user operation." --::= { workingMode 2 } --browserEnabled OBJECT-TYPE --SYNTAX INTEGER { no(1), yes(2) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set status of browser." --::= { workingMode 3 } minUserNameLen OBJECT-TYPE SYNTAX INTEGER (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set minimum length of user name." ::= { accountPolicy 1 } minUserPwdLen OBJECT-TYPE SYNTAX INTEGER (1..16) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set minimum length of user password. " ::= { accountPolicy 2 } upperCaseEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set one upper case rule in user password." ::= { accountPolicy 3 } lowerCaseEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set one lower case rule in user password." ::= { accountPolicy 4 } numberEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set one number rule in user password." ::= { accountPolicy 5 } disableDuplicateLogin OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of disabled duplicate login rule." ::= { accountPolicy 6 } loginString OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set a login string. string length: 0~32 NOTE: Input string as /empty to set this object to NULL. " ::= { loginRestriction 1 } ipFilterEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of ip filter." ::= { ipFilter 1 } ipFilterRule OBJECT-TYPE SYNTAX INTEGER { include(1), exclude(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of ip filter rule." ::= { ipFilter 2 } ipFilterTable OBJECT-TYPE SYNTAX SEQUENCE OF IpFilterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of restricted ip." ::= { ipFilter 3 } ipFilterEntry OBJECT-TYPE SYNTAX IpFilterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Status and parameter values for a PE's restricted IP." INDEX { ipFilterIndex } ::= { ipFilterTable 1 } IpFilterEntry ::= SEQUENCE { ipFilterIndex INTEGER, ipFilterFrom IpAddress, ipFilterTo IpAddress } ipFilterIndex OBJECT-TYPE SYNTAX INTEGER (1..5) MAX-ACCESS read-only STATUS current DESCRIPTION "The value of index for the ip filter. " ::= { ipFilterEntry 1 } ipFilterFrom OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "A set of restricted ip. ex. 192.168.0.1 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0 " ::= { ipFilterEntry 2 } ipFilterTo OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "A set of restricted ip. ex. 192.168.0.255 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0 " ::= { ipFilterEntry 3 } macFilterEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of mac filter." ::= { macFilter 1 } macFilterRule OBJECT-TYPE SYNTAX INTEGER { include(1), exclude(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of mac filter rule." ::= { macFilter 2 } macFilterTable OBJECT-TYPE SYNTAX SEQUENCE OF MacFilterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of restricted mac." ::= { macFilter 3 } macFilterEntry OBJECT-TYPE SYNTAX MacFilterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Status and parameter values for a PE's restricted MAC." INDEX { macFilterIndex } ::= { macFilterTable 1 } MacFilterEntry ::= SEQUENCE { macFilterIndex INTEGER, macFilterSet DisplayString } macFilterIndex OBJECT-TYPE SYNTAX INTEGER (1..5) MAX-ACCESS read-only STATUS current DESCRIPTION "The value of index for the mac filter. " ::= { macFilterEntry 1 } macFilterSet OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A set of restricted mac. string length: 12 ex. 004854655511 Note: Users must follow in order to set the MAC address. Note: To clear the settings to set the MAC 000000000000 " ::= { macFilterEntry 2 } --LocalAuth OBJECT-TYPE --SYNTAX INTEGER { no(1), yes(2) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set status of disable local authentication." --::= { authentication 1 } radiusEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set status of RADIUS server." ::= { radius 1 } preferRadiusIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer RADIUS server IP." ::= { radius 2 } preferRadiusPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer RADIUS server port." ::= { radius 3 } alternateRadiusIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternative RADIUS server IP." ::= { radius 4 } alternateRadiusPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternative RADIUS server port." ::= { radius 5 } radiusTimeOut OBJECT-TYPE SYNTAX INTEGER (1..60) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set time out of authentication using RADIUS server. The unit is sec. " ::= { radius 6 } radiusRetry OBJECT-TYPE SYNTAX INTEGER (0..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set retry times of authentication using RADIUS server." ::= { radius 7 } radiusSecret OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set shared secret of RADIUS server. string length: 6~15 At least 6 characters. NOTE: Input string as /empty to set this object to NULL. " ::= { radius 8 } -- Device Management End -- User Management usrListTable OBJECT-TYPE SYNTAX SEQUENCE OF UsrListEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of user. The number of user is given by the value of usrcfgNumber." ::= { userManagement 1 } usrListEntry OBJECT-TYPE SYNTAX UsrListEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Status and parameter values for a pe8208 user." INDEX { usrIndex } ::= { usrListTable 1 } UsrListEntry ::= SEQUENCE { usrIndex INTEGER, usrType INTEGER, usrName DisplayString, usrPassword DisplayString, usrPort1Auth INTEGER, usrPort2Auth INTEGER, usrPort3Auth INTEGER, usrPort4Auth INTEGER, usrPort5Auth INTEGER, usrPort6Auth INTEGER, usrPort7Auth INTEGER, usrPort8Auth INTEGER, usrPort9Auth INTEGER, usrPort10Auth INTEGER, usrPort11Auth INTEGER, usrPort12Auth INTEGER, usrPort13Auth INTEGER, usrPort14Auth INTEGER, usrPort15Auth INTEGER, usrPort16Auth INTEGER, usrPort17Auth INTEGER, usrPort18Auth INTEGER, usrPort19Auth INTEGER, usrPort20Auth INTEGER, usrPort21Auth INTEGER, usrPort22Auth INTEGER, usrPort23Auth INTEGER, usrPort24Auth INTEGER, usrPort25Auth INTEGER, usrPort26Auth INTEGER, usrPort27Auth INTEGER, usrPort28Auth INTEGER, usrPort29Auth INTEGER, usrPort30Auth INTEGER, usrPort31Auth INTEGER, usrPort32Auth INTEGER, usrPort33Auth INTEGER, usrPort34Auth INTEGER, usrPort35Auth INTEGER, usrPort36Auth INTEGER, usrPort37Auth INTEGER, usrPort38Auth INTEGER, usrPort39Auth INTEGER, usrPort40Auth INTEGER, usrPort41Auth INTEGER, usrPort42Auth INTEGER, usrEnable INTEGER } usrIndex OBJECT-TYPE SYNTAX INTEGER (1..9) MAX-ACCESS read-only STATUS current DESCRIPTION "The value of usrIndex for the user. We have 1 administrator and 8 users. The index 9 will be the administrator. " ::= { usrListEntry 1 } usrType OBJECT-TYPE SYNTAX INTEGER { administrator(1), user(2)} MAX-ACCESS read-only STATUS current DESCRIPTION "The user's type." ::= { usrListEntry 2 } usrName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "A textual string containing name of the user. string length: 1~16 " ::= { usrListEntry 3 } usrPassword OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "A textual string containing password of the user. string length: 1~16 " ::= { usrListEntry 4 } usrPort1Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 1 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 5 } usrPort2Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 2 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 6 } usrPort3Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 3 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 7 } usrPort4Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 4 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 8 } usrPort5Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 5 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 9 } usrPort6Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Dispaly or set this user's outlet 6 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 10 } usrPort7Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 7 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 11 } usrPort8Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 8 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 12 } usrEnable OBJECT-TYPE SYNTAX INTEGER { disable(1), enable(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user is enable or not" ::= { usrListEntry 47 } usrPort9Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 9 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 13 } usrPort10Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 10 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 14 } usrPort11Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 11 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 15 } usrPort12Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 12 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 16 } usrPort13Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 13 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 17 } usrPort14Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 14 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 18 } usrPort15Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 15 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 19 } usrPort16Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 16 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 20 } usrPort17Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 17 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 21 } usrPort18Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 18 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 22 } usrPort19Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 19 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 23 } usrPort20Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 20 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 24 } usrPort21Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 21 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 25 } usrPort22Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 22 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 26 } usrPort23Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 23 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 27 } usrPort24Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 24 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 28 } usrPort25Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 25 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 29 } usrPort26Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 26 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 30 } usrPort27Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 27 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 31 } usrPort28Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 28 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 32 } usrPort29Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 29 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 33 } usrPort30Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 30 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 34 } usrPort31Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 31 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 35 } usrPort32Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 32 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 36 } usrPort33Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 33 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 37 } usrPort34Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 34 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 38 } usrPort35Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 35 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 39 } usrPort36Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 36 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 40 } usrPort37Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 37 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 41 } usrPort38Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 38 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 42 } usrPort39Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 39 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 43 } usrPort40Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 40 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 44 } usrPort41Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 41 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 45 } usrPort42Auth OBJECT-TYPE SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set this user's outlet 42 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu." ::= { usrListEntry 46 } -- User Management End -- SNMPv3 USM Settings --snmpv3UsmUserTable OBJECT-TYPE -- SYNTAX SEQUENCE OF Snmpv3UsmUserEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION "This table is used to configure PE SNMPv3 USM. -- To get the SNMPv3 access, One need to configure security -- name,authentication,auth password,priv protocol and priv -- password. -- " -- ::= { snmp 2 } --snmpv3UsmUserEntry OBJECT-TYPE -- SYNTAX Snmpv3UsmUserEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION "A user configured for the User-based -- Security Model. -- " -- INDEX { usmIndex } -- ::= { snmpv3UsmUserTable 1 } --Snmpv3UsmUserEntry ::= SEQUENCE { -- usmIndex INTEGER, -- usmSecurityName SnmpAdminString, -- smAuthProtocol SNMPv3UsmAuthPrivProtocol, -- usmPrivPassword SnmpAdminString -- } --usmIndex OBJECT-TYPE -- SYNTAX INTEGER (1) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION "Usm configuration index. " -- ::= { snmpv3UsmUserEntry 1 } --usmSecurityName OBJECT-TYPE -- SYNTAX SnmpAdminString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION "A human readable string representing the user in -- Security Model independent format. -- The default transformation of the User-based Security -- Model dependent security ID to the securityName and -- vice versa is the identity function so that the -- securityName is the same as the userName. -- " -- ::= { snmpv3UsmUserEntry 2 } --usmKeyAlgorithm OBJECT-TYPE -- SYNTAX SNMPv3UsmAuthPrivProtocol -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION " -- If usmAuthProtocol == HMACMD5Auth , supports MD5 AuthKey and PrivKey -- If usmAuthProtocol == HMACSHAAuth, supports SHA AuthKey and PrivKey -- " -- ::= { snmpv3UsmUserEntry 3 } --usmPrivProtocol OBJECT-TYPE -- SYNTAX SNMPv3UsmAuthPrivProtocol -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION " A privacy protocol to provide encryption and decryption -- SNMPv3 pdu. -- " -- ::= { snmpv3UsmUserEntry 4 } --usmPrivPassword OBJECT-TYPE -- SYNTAX SnmpAdminString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION "An user's privacy password, Associated protocol -- and a secret key is used to establish a connection -- for the snmp agent and manager commnucation. -- " -- ::= { snmpv3UsmUserEntry 4 } -- SNMPv3 Target MIB --snmpv3TargetTable OBJECT-TYPE -- SYNTAX SEQUENCE OF Snmpv3TargetEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "A table of SNMP target information to be used -- in the generation of SNMP trap messages." -- ::= { snmp 3 } --snmpv3TargetEntry OBJECT-TYPE -- SYNTAX Snmpv3TargetEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "A set of SNMP target information. -- " -- INDEX { snmpv3TargetIndex } -- ::= { snmpv3TargetTable 1 } --Snmpv3TargetEntry ::= SEQUENCE { -- snmpv3TargetIndex INTEGER, -- snmpv3TargetMPModel SnmpMessageProcessingModel, -- snmpv3TargetSecurityModel SnmpSecurityModel, -- snmpv3TargetSecurityName SnmpAdminString --} --snmpv3TargetIndex OBJECT-TYPE -- SYNTAX INTEGER(1) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "The locally arbitrary, but unique identifier associated -- with this snmpv3TargetEntry." -- ::= { snmpv3TargetEntry 1 } --snmpv3TargetMPModel OBJECT-TYPE -- SYNTAX SnmpMessageProcessingModel -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The Message Processing Model to be used when generating -- SNMP messages using this entry." -- ::= { snmpv3TargetEntry 2 } --snmpv3TargetSecurityModel OBJECT-TYPE -- SYNTAX SnmpSecurityModel (1..2147483647) -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The Security Model to be used when generating SNMP -- messages using this entry. An implementation may -- choose to return an inconsistentValue error if an -- attempt is made to set this variable to a value -- for a security model which the implementation does -- not support." -- ::= { snmpv3TargetEntry 3 } --snmpv3TargetSecurityName OBJECT-TYPE -- SYNTAX SnmpAdminString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The securityName which identifies the Principal on -- whose behalf SNMP messages will be generated using -- this entry." -- ::= { snmpv3TargetEntry 4 } --snmpv3TargetSecurityLevel OBJECT-TYPE -- SYNTAX SnmpSecurityLevel -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The Level of Security to be used when generating -- SNMP messages using this entry." -- ::= { snmpv3TargetEntry 5 } -- Custom Trap Message customTrapMSG NOTIFICATION-TYPE STATUS current --OBJECTS { customTrapMSG } DESCRIPTION "Display custom trap message." ::= { pe 5 } rebootDevice OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reboot PE Device" ::= { pe 6 } -- CPM --modelName OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Indicate CPM device model name." -- ::= { CPM 1 } --cpmName OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "The name of CPM device. -- string length: 1~39 -- NOTE: Input string as /empty to set this object to NULL. -- " -- ::= { CPM 2 } --cpmswitchable OBJECT-TYPE -- SYNTAX INTEGER { no(1), yes(2) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- " Switchable or not. " -- ::= { CPM 3 } --cpmPDUreading OBJECT-TYPE -- SYNTAX INTEGER { no(1), yes(2) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- " CPM is per-PDU reading or not." -- ::= { CPM 4 } --cpmSensornumber OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- " CPM's Sensor number." -- ::= { CPM 5 } --cpmOutletnumber OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- " CPM's Outlet number." -- ::= { CPM 6 } --cpmbreaker OBJECT-TYPE --SYNTAX INTEGER { off(1), on(2) } --MAX-ACCESS read-only --STATUS current --DESCRIPTION -- "CPM's breaker status." --::= { CPM 7 } -- Device --cpmdeviceValueTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmDeviceValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Device value table. This table displays device's current. -- " -- ::= { CPMDevice 1 } --cpmdeviceValueEntry OBJECT-TYPE -- SYNTAX cpmDeviceValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Single deviceValue entry containing device info." -- INDEX { cpmdeviceValueIndex } -- ::= { cpmdeviceValueTable 1 } --cpmDeviceValueEntry ::= -- SEQUENCE { -- cpmdeviceValueIndex -- INTEGER, -- cpmdeviceCurrent -- DisplayString, --cpmdeviceVoltage -- DisplayString, --cpmdevicePower -- DisplayString, --cpmdevicePowerDissipation -- DisplayString, --cpminputMaxVoltage -- INTEGER, -- cpminputMaxCurrent -- INTEGER --cpmpowerCapacity -- INTEGER -- } --cpmdeviceValueIndex OBJECT-TYPE -- SYNTAX INTEGER (1) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of device Value." -- ::= { cpmdeviceValueEntry 1 } --cpmdeviceCurrent OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device electric current value. -- " -- ::= { cpmdeviceValueEntry 2 } --cpmdeviceVoltage OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device voltage value." -- ::= { cpmdeviceValueEntry 3 } --cpmdevicePower OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power value." -- ::= { cpmdeviceValueEntry 4 } --cpmdevicePowerDissipation OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power dissipation value." -- ::= { cpmdeviceValueEntry 5 } --cpminputMaxVoltage OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device input Voltage value. unit:(V)" -- ::= { cpmdeviceValueEntry 6 } --cpminputMaxCurrent OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device input Current value. unit:(A)" -- ::= { cpmdeviceValueEntry 7 } --cpmpowerCapacity OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "Device power Capacity value.unit:(VA)" -- ::= { cpmdeviceValueEntry 8 } --cpmdeviceConfigTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmDeviceConfigEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Device configuration table" -- ::= { CPMDevice 2 } --cpmdeviceConfigEntry OBJECT-TYPE -- SYNTAX cpmDeviceConfigEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Single deviceConfig entry containing device info." -- INDEX { cpmdeviceConfigIndex } -- ::= { cpmdeviceConfigTable 1 } --cpmDeviceConfigEntry ::= -- SEQUENCE { -- cpmdeviceConfigIndex -- INTEGER, --cpmdeviceMinCurMT -- INTEGER, -- cpmdeviceMaxCurMT -- INTEGER --cpmdeviceMinVolMT -- INTEGER, --cpmdeviceMaxVolMT -- INTEGER, -- } --cpmdeviceConfigIndex OBJECT-TYPE -- SYNTAX INTEGER (1) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of deviceConfig" -- ::= { cpmdeviceConfigEntry 1 } --cpmdeviceMinCurMT OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set device minimum electric current measurement threshold. -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- range:0.0~32.0 represents:0~320 -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmdeviceConfigEntry 2 } --cpmdeviceMaxCurMT OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set device maximum electric current measurement threshold. -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- Example: range 0.0~32.0 represents: 0~320 -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmdeviceConfigEntry 3 } --cpmdeviceMinVolMT OBJECT-TYPE -- SYNTAX INTEGER (900..2600 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set device minimum voltage measurement threshold. -- range:90.0~260.0 represents:900~2600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmdeviceConfigEntry 4 } --cpmdeviceMaxVolMT OBJECT-TYPE -- SYNTAX INTEGER (900..2600 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set device maximum voltage measurement threshold. -- range:90.0~260.0 represents:900~2600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmdeviceConfigEntry 5 } -- Sensor --cpmSensorValueTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmSensorValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's sensor value table. This table displays sensor's temperature, humidity and -- pressure. -- " -- ::= { Sensor 1 } --cpmSensorValueEntry OBJECT-TYPE -- SYNTAX cpmSensorValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's sensor value entry containing Sensor info." -- INDEX { cpmSensorValueIndex } -- ::= { cpmSensorValueTable 1 } --cpmSensorValueEntry ::= -- SEQUENCE { -- cpmSensorValueIndex -- INTEGER, -- cpmSensorTemperature -- DisplayString, -- cpmSensorHumidity -- DisplayString, -- cpmSensorPressure -- DisplayString, -- cpmSensorProperty -- INTEGER -- } --cpmSensorValueIndex OBJECT-TYPE -- SYNTAX INTEGER (1..4) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of CPM's Sensor number." -- ::= { cpmSensorValueEntry 1 } --cpmSensorTemperature OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's Sensor Temperature value." -- ::= { cpmSensorValueEntry 2 } --cpmSensorHumidity OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's Sensor Humidity value." -- ::= { cpmSensorValueEntry 3 } --cpmSensorPressure OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's Sensor Pressure value." -- ::= { cpmSensorValueEntry 4 } --cpmSensorProperty OBJECT-TYPE -- SYNTAX INTEGER { intake(1), exhaust(2) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's Sensor Property." -- ::= { cpmSensorValueEntry 5 } --cpmSensorThresholdTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmSensorThresholdEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's Sensor value table" -- ::= { Sensor 2 } --cpmSensorThresholdEntry OBJECT-TYPE -- SYNTAX cpmSensorThresholdEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's sensor threshold entry containing sensor info." -- INDEX { cpmSensorThresholdIndex } -- ::= { cpmSensorThresholdTable 1 } --cpmSensorThresholdEntry ::= -- SEQUENCE { -- cpmSensorThresholdIndex -- INTEGER, -- cpmsensorMinTempMT -- INTEGER, -- cpmsensorMaxTempMT -- INTEGER, -- cpmsensorMinHumMT -- INTEGER, -- cpmsensorMaxHumMT -- INTEGER, -- cpmsensorMinPressMT -- INTEGER, -- cpmsensorMaxPressMT -- INTEGER --sensorTempFlu --INTEGER, --sensorHumFlu --INTEGER, --sensorPressFlu --INTEGER -- } --cpmSensorThresholdIndex OBJECT-TYPE -- SYNTAX INTEGER (1..4) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of CPM's sensor number" -- ::= { cpmSensorThresholdEntry 1 } --cpmsensorMinTempMT OBJECT-TYPE -- SYNTAX INTEGER (-200..600 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor minimum temperature measurement threshold. -- Example: range 0.0 ~ 60.0 represents 0~600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold. -- " -- ::= { cpmSensorThresholdEntry 2 } --cpmsensorMaxTempMT OBJECT-TYPE -- SYNTAX INTEGER (-200..600 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor maximum temperature measurement threshold. -- Example: range 0.0 ~ 60.0 represents 0~600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmSensorThresholdEntry 3 } --cpmsensorMinHumMT OBJECT-TYPE -- SYNTAX INTEGER (150..950 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor minimum humidity measurement threshold. -- Example: range 15.0 ~ 95.0 represents 150~950 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmSensorThresholdEntry 4 } --cpmsensorMaxHumMT OBJECT-TYPE -- SYNTAX INTEGER (150..950 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor maximum humidity measurement threshold. -- Example: range 15.0 ~ 95.0 represents 150~950 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmSensorThresholdEntry 5 } --cpmsensorMinPressMT OBJECT-TYPE -- SYNTAX INTEGER (-2500..2500 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor minimum pressure measurement threshold. -- Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmSensorThresholdEntry 6 } --cpmsensorMaxPressMT OBJECT-TYPE -- SYNTAX INTEGER (-2500..2500 | -3000) -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set sensor maximum pressure measurement threshold. -- Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmSensorThresholdEntry 7 } -- pdu --cpmPDUValueTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmPDUValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Display the PDU's current value of CPM" -- ::= { EnergySensor 1 } --cpmPDUValueEntry OBJECT-TYPE -- SYNTAX cpmPDUValueEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's monitor pdu Value entry containing outlet info." -- INDEX { cpmPDUValueIndex } -- ::= { cpmPDUValueTable 1 } --cpmPDUValueEntry ::= -- SEQUENCE { -- cpmPDUValueIndex -- INTEGER, -- cpmPDUCurrent -- DisplayString, --cpmPDUVoltage -- DisplayString, --cpmPDUPower -- DisplayString, --cpmPDUPowerDissipation -- DisplayString, -- cpmPDUMaxCurrent -- INTEGER -- } --cpmPDUValueIndex OBJECT-TYPE -- SYNTAX INTEGER (1..4) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of PDU number" -- ::= { cpmPDUValueEntry 1 } --cpmPDUCurrent OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's monitor PDU electric current value" -- ::= { cpmPDUValueEntry 2 } --cpmPDUVoltage OBJECT-TYPE --SYNTAX DisplayString --MAX-ACCESS read-only --STATUS current --DESCRIPTION -- "CPM's monitor PDU voltage value" --::= { cpmPDUValueEntry 3 } --cpmPDUPower OBJECT-TYPE --SYNTAX DisplayString --MAX-ACCESS read-only --STATUS current --DESCRIPTION -- "CPM's monitor PDU power value" --::= { cpmPDUValueEntry 4 } --cpmPDUPowerDissipation OBJECT-TYPE --SYNTAX DisplayString --MAX-ACCESS read-only --STATUS current --DESCRIPTION -- "CPM's monitor PDU power dissipation value" --::= { cpmPDUValueEntry 5 } --cpmPDUMaxCurrent OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "CPM's monitor PDU Max Current value. unit: (A)" -- ::= { cpmPDUValueEntry 6 } --cpmBankStatus OBJECT-TYPE -- SYNTAX INTEGER { noattached(1), attached(2) } -- MAX-ACCESS read-only -- STATUS current -- DESCRIPTION -- "The status CPM device Bank status." -- ::= { cpmPDUValueEntry 7 } --cpmPDUConfigTable OBJECT-TYPE -- SYNTAX SEQUENCE OF cpmPDUConfigEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's monitor PDU configuration table" -- ::= { EnergySensor 2 } --cpmPDUConfigEntry OBJECT-TYPE -- SYNTAX cpmPDUConfigEntry -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "CPM's monitor PDU config entry containing PDU info." -- INDEX { cpmPDUConfigIndex } -- ::= { cpmPDUConfigTable 1 } --cpmPDUConfigEntry ::= -- SEQUENCE { -- cpmPDUConfigIndex -- INTEGER, -- cpmPDUName -- DisplayString, --cpmPDUConfirmation -- INTEGER, --cpmPDUOnDelayTime -- INTEGER, --cpmPDUOffDelayTime -- INTEGER, --cpmPDUShutdownMethod -- INTEGER, --cpmPDUMAC -- DisplayString, --cpmPDUMinCurMT -- INTEGER, -- cpmPDUMaxCurMT -- INTEGER --cpmPDUMinVolMT -- INTEGER, --cpmPDUMaxVolMT -- INTEGER, -- } --cpmPDUConfigIndex OBJECT-TYPE -- SYNTAX INTEGER (1..4) -- MAX-ACCESS not-accessible -- STATUS current -- DESCRIPTION -- "Index of PDU number" -- ::= { cpmPDUConfigEntry 1 } --cpmPDUName OBJECT-TYPE -- SYNTAX DisplayString -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set the name of pdu. -- string length: 0~15 -- NOTE: Input string as /empty to set this object to NULL. -- " -- ::= { cpmPDUConfigEntry 2 } --cpmPDUConfirmation OBJECT-TYPE --SYNTAX INTEGER { no(1), yes(2) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the confirmation of outlet." --::= { cpmPDUConfigEntry 3 } --cpmPDUOnDelayTime OBJECT-TYPE --SYNTAX INTEGER (0..999) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the ON delay time of outlet." --::= { cpmPDUConfigEntry 4 } --cpmPDUOffDelayTime OBJECT-TYPE --SYNTAX INTEGER (0..999) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the OFF delay time of outlet." --::= { cpmPDUConfigEntry 5 } --cpmPDUShutdownMethod OBJECT-TYPE --SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3) } --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the shutdown mehtod of outlet." --::= { cpmPDUConfigEntry 6 } --cpmPDUMAC OBJECT-TYPE --SYNTAX DisplayString --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the MAC address of ShutdownMethod. -- string length: 12 -- " --::= { cpmPDUConfigEntry 7 } --cpmPDUMinCurMT OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set the PDU minimum electric current measurment threshold. -- Range:0.0 ~16.0 rerpresnts 0~160 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmPDUConfigEntry 3 } --cpmPDUMaxCurMT OBJECT-TYPE -- SYNTAX INTEGER -- MAX-ACCESS read-write -- STATUS current -- DESCRIPTION -- "Display or set the PDU maximum electric current measurment threshold. -- Example: range 0.0 ~16.0 represents 0~160 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " -- ::= { cpmPDUConfigEntry 4 } --cpmPDUMinVolMT OBJECT-TYPE --SYNTAX INTEGER (900..2600) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the outlet minimum voltage measurment threshold. -- Range:90.0 ~260.0 represents 900~2600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { cpmPDUConfigEntry 10 } --cpmPDUMaxVolMT OBJECT-TYPE --SYNTAX INTEGER (900..2600) --MAX-ACCESS read-write --STATUS current --DESCRIPTION -- "Display or set the outlet maximum voltage measurment threshold. -- Range:90.0 ~260.0 represents 900~2600 -- When this value is -3000,it indicate this is NULL. -- When set this value to -3000, indicate set this object as NULL. -- NOTICE:Minimum threshold should be setted smaller than Maxima threshold -- " --::= { cpmPDUConfigEntry 11 } END