-- ***************************************************************** -- CAREL-RITTAL-LCP-3311-MIB -- MIB for rittal 3311 lcp chillers using a carel pcoweb card (SK 3311.320) -- -- June, 2021 Gregory Bers, Limburg, Belgium -- -- System OID found under .1.3.6.1.2.1.1.2.0 -- -- Documentation: https://github.com/epiecs/carel-pco-mibs -- -- PCO settings -- System OID: 1.3.6.1.4.1.9839.2606.1 -- Enterprise OID: 9839.2606 -- ***************************************************************** CAREL-RITTAL-LCP-3311-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, enterprises, OBJECT-TYPE, Integer32 FROM SNMPv2-SMI OBJECT-GROUP FROM SNMPv2-CONF TEXTUAL-CONVENTION FROM SNMPv2-TC ; carel MODULE-IDENTITY LAST-UPDATED "202106290000Z" ORGANIZATION "Epiecs" CONTACT-INFO "EPIECS epiecs.be Email: gregorybers@epiecs.be" DESCRIPTION "Custom MIB for Rittal LCP 3311 chillers connected to a pco web card" REVISION "202106290000Z" DESCRIPTION "First draft containing the values outlined in the 3311.320 docs https://www.rittal.com/imf/none/3_4342/3311320_Instructions_spec__EN" ::= { enterprises 9839 } -- tree under 9839 rittal OBJECT IDENTIFIER ::= { carel 2606 } rittalLCP3311 OBJECT IDENTIFIER ::= { rittal 2 } sensors OBJECT IDENTIFIER ::= { rittalLCP3311 1 } digital OBJECT IDENTIFIER ::= { sensors 1 } analog OBJECT IDENTIFIER ::= { sensors 2 } integer OBJECT IDENTIFIER ::= { sensors 3 } -- -- object groups -- -- integerSensors OBJECT-GROUP -- OBJECTS { fanSpeedPercent, fanSpeedRpm } -- STATUS current -- DESCRIPTION -- "A collection of all sensors providing integer values" -- ::= { integer 1 } -- -- conversions -- DivBy10 ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-1" STATUS current DESCRIPTION "Fixed point, one decimal" SYNTAX Integer32 -- -- digital objects -- -- .1.3.6.1.4.1.9839.2606.2.1.1.2 compressorOverloadAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor overload alarm ok (0), alarm (1)" ::= { digital 2 } -- .1.3.6.1.4.1.9839.2606.2.1.1.3 highPressureAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure alarm ok (0), alarm (1)" ::= { digital 3 } -- .1.3.6.1.4.1.9839.2606.2.1.1.8 remoteOnOff OBJECT-TYPE SYNTAX INTEGER { off (0), on (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Remote On/Off off (0), on (1)" ::= { digital 8 } -- .1.3.6.1.4.1.9839.2606.2.1.1.11 inverterAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Inverter alarm ok (0), alarm (1)" ::= { digital 11 } -- .1.3.6.1.4.1.9839.2606.2.1.1.12 driveAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Power+ drive off-line alarm ok (0), alarm (1)" ::= { digital 12 } -- .1.3.6.1.4.1.9839.2606.2.1.1.17 inverterOnOff OBJECT-TYPE SYNTAX INTEGER { off (0), on (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Inverter On/Off off (0), on (1)" ::= { digital 17 } -- .1.3.6.1.4.1.9839.2606.2.1.1.23 generalAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "General alarm alarm (0), ok (1)" ::= { digital 23 } -- .1.3.6.1.4.1.9839.2606.2.1.1.29 resetAllAlarms OBJECT-TYPE SYNTAX INTEGER { no (0), yes (1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset all alarms no (0), yes (1)" ::= { digital 29 } -- .1.3.6.1.4.1.9839.2606.2.1.1.30 compressorEnvelopeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor forced off working out envelope ok (0), alarm (1)" ::= { digital 30 } -- .1.3.6.1.4.1.9839.2606.2.1.1.31 compressorStartupFailureAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor startup failure alarm, reached max retries ok (0), alarm (1)" ::= { digital 31 } -- .1.3.6.1.4.1.9839.2606.2.1.1.33 maxDischargeTemperatureAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum discharge temperature has been reached ok (0), alarm (1)" ::= { digital 33 } -- .1.3.6.1.4.1.9839.2606.2.1.1.35 compressorDeltaPressureAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Delta pressure too big to startup compressor ok (0), alarm (1)" ::= { digital 35 } -- .1.3.6.1.4.1.9839.2606.2.1.1.36 oilReturnAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Oil return alarm for when the compressor is running. Lubrication issue. ok (0), alarm (1)" ::= { digital 36 } -- .1.3.6.1.4.1.9839.2606.2.1.1.38 outputTemperatureTopProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Top output temperature probe broken ok (0), alarm (1)" ::= { digital 38 } -- .1.3.6.1.4.1.9839.2606.2.1.1.39 outputTemperatureMidProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Mid output temperature probe broken ok (0), alarm (1)" ::= { digital 39 } -- .1.3.6.1.4.1.9839.2606.2.1.1.40 outputTemperatureBottomProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom output temperature probe broken ok (0), alarm (1)" ::= { digital 40 } -- .1.3.6.1.4.1.9839.2606.2.1.1.42 inputTemperatureTopProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Top input temperature probe broken ok (0), alarm (1)" ::= { digital 42 } -- .1.3.6.1.4.1.9839.2606.2.1.1.43 inputTemperatureMidProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Mid input temperature probe broken ok (0), alarm (1)" ::= { digital 43 } -- .1.3.6.1.4.1.9839.2606.2.1.1.44 inputTemperatureBottomProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom input temperature probe broken ok (0), alarm (1)" ::= { digital 44 } -- .1.3.6.1.4.1.9839.2606.2.1.1.45 compressorDischargeTemperatureProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor discharge temperature probe broken ok (0), alarm (1)" ::= { digital 45 } -- .1.3.6.1.4.1.9839.2606.2.1.1.46 compressorSuctionTemperatureProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor suction temperature probe broken ok (0), alarm (1)" ::= { digital 46 } -- .1.3.6.1.4.1.9839.2606.2.1.1.47 compressorDischargePressureProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor discharge pressure probe broken ok (0), alarm (1)" ::= { digital 47 } -- .1.3.6.1.4.1.9839.2606.2.1.1.48 compressorSuctionPressureProbeAlarm OBJECT-TYPE SYNTAX INTEGER { ok (0), alarm (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor suction pressure probe broken ok (0), alarm (1)" ::= { digital 48 } -- .1.3.6.1.4.1.9839.2606.2.1.1.100 reboot OBJECT-TYPE SYNTAX INTEGER { no (0), yes (1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reboot the system no (0), yes (1)" ::= { digital 100 } -- -- integer objects -- -- .1.3.6.1.4.1.9839.2606.2.1.3.1 compressorRotorSpeedHz OBJECT-TYPE SYNTAX INTEGER (0..9999) UNITS "Hz" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor rotor speed in Hz" ::= { integer 1 } -- .1.3.6.1.4.1.9839.2606.2.1.3.2 driverPowerStatus OBJECT-TYPE SYNTAX INTEGER { stop (1), run (2), alarm (3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Driver power status stop (1), run (2), alarm (3)" ::= { integer 2 } -- .1.3.6.1.4.1.9839.2606.2.1.3.3 currentErrorCode OBJECT-TYPE SYNTAX INTEGER { OK (0), ALA02 (2), ALA03 (3), ALA04 (4), ALA05 (5), ALA06 (6), ALA07 (7), ALA08 (8), ALA09 (9), ALA10 (10), ALA11 (11), ALA12 (12), ALB01 (13), ALB02 (14), ALB03 (15), ALC01 (16), ALC03 (17), ALC04 (18), ALC05 (19), ALC06 (20), ALF01 (21), ALD02 (22), ALD03 (23), ALD04 (24), ALD05 (25), ALD06 (26), ALD07 (27), ALD08 (28), ALD09 (29), ALL01 (30), ALL02 (31), ALL99 (32), ALW04 (33) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current error code" ::= { integer 3 } -- .1.3.6.1.4.1.9839.2606.2.1.3.4 driverTemperature OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Driver Power+ Temperature" ::= { integer 4 } -- .1.3.6.1.4.1.9839.2606.2.1.3.5 dcBusVoltage OBJECT-TYPE SYNTAX DivBy10 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "Power+ DC Voltage" ::= { integer 5 } -- .1.3.6.1.4.1.9839.2606.2.1.3.6 motorVoltage OBJECT-TYPE SYNTAX DivBy10 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "Motor Voltage" ::= { integer 6 } -- .1.3.6.1.4.1.9839.2606.2.1.3.7 powerRequest OBJECT-TYPE SYNTAX DivBy10 UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Request of power for inverter after envelop" ::= { integer 7 } -- .1.3.6.1.4.1.9839.2606.2.1.3.13 unitOnOff OBJECT-TYPE SYNTAX INTEGER { off (0), on (1), energy-save (2), auto (3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Unit on/off state off (0), on (1), energy-save (2), auto (3) " ::= { integer 13 } -- .1.3.6.1.4.1.9839.2606.2.1.3.14 envelopeZone OBJECT-TYPE SYNTAX INTEGER { ok (0), maximum-compression-ratio (1), maximum-discharge-power (2), current-limit (3), maximum-suction-power(4), minimum-compression-ratio (5), minimum-delta-power (6), minimum-discharge-power(7), minimum-suction-power (8) } MAX-ACCESS read-only STATUS current DESCRIPTION "envelope zone ok (0), maximum compression ratio (1), maximum discharge power (2), current limit (3), maximum suction power(4), minimum compression ratio (5), minimum delta power (6), minimum discharge power(7), minimum suction power (8) " ::= { integer 14 } -- .1.3.6.1.4.1.9839.2606.2.1.3.16 coolingCapacity OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual EVD valve cooling capacity" ::= { integer 16 } -- .1.3.6.1.4.1.9839.2606.2.1.3.17 evdValveSteps OBJECT-TYPE SYNTAX INTEGER (0..540) UNITS "steps" MAX-ACCESS read-only STATUS current DESCRIPTION "EVD valve steps position" ::= { integer 17 } -- .1.3.6.1.4.1.9839.2606.2.1.3.28 fanSpeedPercent OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "The fan speed percentage" ::= { integer 28 } -- .1.3.6.1.4.1.9839.2606.2.1.3.29 fanSpeedRpm OBJECT-TYPE SYNTAX INTEGER (0..3700) UNITS "rpm" MAX-ACCESS read-only STATUS current DESCRIPTION "The fan speed rpm" ::= { integer 29 } -- .1.3.6.1.4.1.9839.2606.2.1.3.30 evdValveOpening OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual EVD valve opening" ::= { integer 30 } -- -- analog objects -- -- .1.3.6.1.4.1.9839.2606.2.1.2.2 outputTemperatureTopSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Top sensor output temperature in Celcius" ::= { analog 2 } -- .1.3.6.1.4.1.9839.2606.2.1.2.3 outputTemperatureMidSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Mid sensor output temperature in Celcius" ::= { analog 3 } -- .1.3.6.1.4.1.9839.2606.2.1.2.4 outputTemperatureBottomSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom sensor output temperature in Celcius" ::= { analog 4 } -- .1.3.6.1.4.1.9839.2606.2.1.2.6 inputTemperatureTopSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Top sensor input temperature in Celcius" ::= { analog 6 } -- .1.3.6.1.4.1.9839.2606.2.1.2.7 inputTemperatureMidSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Mid sensor input temperature in Celcius" ::= { analog 7 } -- .1.3.6.1.4.1.9839.2606.2.1.2.8 inputTemperatureBottomSensor OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Bottom sensor input temperature in Celcius" ::= { analog 8 } -- .1.3.6.1.4.1.9839.2606.2.1.2.9 compressorDischargeTemperature OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor discharge temperature" ::= { analog 9 } -- .1.3.6.1.4.1.9839.2606.2.1.2.10 compressorSuctionTemperature OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor suction temperature" ::= { analog 10 } -- .1.3.6.1.4.1.9839.2606.2.1.2.11 compressorDischargePressure OBJECT-TYPE SYNTAX DivBy10 UNITS "bar" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor discharge pressure" ::= { analog 11 } -- .1.3.6.1.4.1.9839.2606.2.1.2.12 compressorSuctionPressure OBJECT-TYPE SYNTAX DivBy10 UNITS "bar" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor suction pressure" ::= { analog 12 } -- .1.3.6.1.4.1.9839.2606.2.1.2.13 evaporatorTemperature OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Evaporator temperature from Low pressure conversion" ::= { analog 13 } -- .1.3.6.1.4.1.9839.2606.2.1.2.14 condensingTemperature OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Condensing temperature from High pressure conversion" ::= { analog 14 } -- .1.3.6.1.4.1.9839.2606.2.1.2.21 inputTemperatureAverage OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Average input temperature in Celcius" ::= { analog 21 } -- .1.3.6.1.4.1.9839.2606.2.1.2.22 outputTemperatureAverage OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-only STATUS current DESCRIPTION "Average output temperature in Celcius" ::= { analog 22 } -- .1.3.6.1.4.1.9839.2606.2.1.2.45 compressorRotorSpeed OBJECT-TYPE SYNTAX DivBy10 UNITS "rps" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor rotor speed" ::= { analog 45 } -- .1.3.6.1.4.1.9839.2606.2.1.2.46 compressorMotorCurrent OBJECT-TYPE SYNTAX DivBy10 UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor motor current" ::= { analog 46 } -- .1.3.6.1.4.1.9839.2606.2.1.2.48 lcpSetpoint OBJECT-TYPE SYNTAX DivBy10 UNITS "C" MAX-ACCESS read-write STATUS current DESCRIPTION "Main LCP setpoint" ::= { analog 48 } END