---------------------------------------------------------------------- -- MIB table for T3610 -- -- v3.0 for firmware 1-5-7-2, 2016-04-11 ----------------------------------------------------------------------- T3610-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; DisplayString ::= OCTET STRING comet OBJECT IDENTIFIER ::= { enterprises 22626 } products OBJECT IDENTIFIER ::= { comet 1 } t3610 OBJECT IDENTIFIER ::= { products 2 } values OBJECT IDENTIFIER ::= { t3610 1 } global OBJECT IDENTIFIER ::= { t3610 2 } valuesInt OBJECT IDENTIFIER ::= { t3610 3 } settings OBJECT IDENTIFIER ::= { t3610 4 } traps OBJECT IDENTIFIER ::= { t3610 5 } tables OBJECT IDENTIFIER ::= { t3610 6 } ----------------------------------------------------------------------- -- Measured values - String ----------------------------------------------------------------------- temp OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature" ::= { values 1 } hum OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Relative humidity" ::= { values 2 } compVal OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value" ::= { values 3 } tempAlarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Temperature; none, high, low" ::= { values 5 } humAlarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Relative humidity; none, high, low" ::= { values 6 } compValAlarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Computed value; none, high, low" ::= { values 7 } tempUnit OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Unit" ::= { values 9 } humUnit OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Relative humidity Unit" ::= { values 10 } compValUnit OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value Unit" ::= { values 11 } tempMin OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Minimal temperature" ::= { values 13 } humMin OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Minimal relative humidity" ::= { values 14 } compValMin OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Minimal computed value" ::= { values 15 } tempMax OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Maximal temperature" ::= { values 17 } humMax OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Maximal relative humidity" ::= { values 18 } compValMax OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Maximal computed value" ::= { values 19 } ----------------------------------------------------------------------- -- Device informations ----------------------------------------------------------------------- sensorName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..68)) ACCESS read-only STATUS mandatory DESCRIPTION "Device name" ::= { global 1 } serialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-only STATUS mandatory DESCRIPTION "Serial number" ::= { global 2 } deviceType OBJECT-TYPE SYNTAX INTEGER (0..65534) ACCESS read-only STATUS mandatory DESCRIPTION "Device type" ::= { global 3 } ----------------------------------------------------------------------- -- Measured values - Integer ----------------------------------------------------------------------- tempInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature (value*10)" ::= { valuesInt 1 } humInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Relative humidity (value*10)" ::= { valuesInt 2 } compValInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value (value*10)" ::= { valuesInt 3 } tempAlarmInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low" ::= { valuesInt 5 } humAlarmInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Relative humidity; 0 - No, 1 - High, 2 - Low" ::= { valuesInt 6 } compValAlarmInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on Computed value; 0 - No, 1 - High, 2 - Low" ::= { valuesInt 7 } ----------------------------------------------------------------------- -- Alarm settings ----------------------------------------------------------------------- tempLowInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Limit Low (value*10)" ::= { settings 1 } tempHighInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Limit High (value*10)" ::= { settings 2 } humLowInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Humidity Limit Low (value*10)" ::= { settings 3 } humHighInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Humidity Limit High (value*10)" ::= { settings 4 } compValLowInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value Limit Low (value*10)" ::= { settings 5 } compValHighInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value Limit High (value*10)" ::= { settings 6 } tempDelayInt OBJECT-TYPE SYNTAX INTEGER (0..4500) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature alaram delay [sec]" ::= { settings 7 } humDelayInt OBJECT-TYPE SYNTAX INTEGER (0..4500) ACCESS read-only STATUS mandatory DESCRIPTION "Humidity alaram delay [sec]" ::= { settings 8 } compValDelayInt OBJECT-TYPE SYNTAX INTEGER (0..4500) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value alaram delay [sec]" ::= { settings 9 } tempHystInt OBJECT-TYPE SYNTAX INTEGER (0..10000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature hysteresis (value*10)" ::= { settings 10 } humHystInt OBJECT-TYPE SYNTAX INTEGER (0..10000) ACCESS read-only STATUS mandatory DESCRIPTION "Humidity hysteresis (value*10)" ::= { settings 11 } compValHystInt OBJECT-TYPE SYNTAX INTEGER (0..10000) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value hysteresis (value*10)" ::= { settings 12 } ----------------------------------------------------------------------- -- Trap message ----------------------------------------------------------------------- messageString OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "Message giving more detailed information on alarms" ::= { traps 1 } ----------------------------------------------------------------------- -- Tables ----------------------------------------------------------------------- historyTable OBJECT-TYPE SYNTAX SEQUENCE OF HistoryEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Table of the history values" ::= { tables 1 } historyEntry OBJECT-TYPE SYNTAX HistoryEntry ACCESS not-accessible STATUS optional DESCRIPTION "History values entries" INDEX { histTemp } ::= { historyTable 1 } HistoryEntry ::= SEQUENCE { histTemp INTEGER, histHum INTEGER, histCompVal INTEGER } histTemp OBJECT-TYPE SYNTAX INTEGER(-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature reading" ::= { historyEntry 1 } histHum OBJECT-TYPE SYNTAX INTEGER(-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Humidity reading" ::= { historyEntry 2 } histCompVal OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Computed value reading" ::= { historyEntry 3 } ----------------------------------------------------------------------- -- Traps definition ----------------------------------------------------------------------- trapTest TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Testing trap, testing trap by TSensor software" ::= 0 trapNTPError TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Error on time synchronisation via NTP" ::= 1 trapEmailErrLogin TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - unknown server" ::= 2 trapEmailErrAuth TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - authentication error" ::= 3 trapEmailErrSome TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - error during communication with server, unexpected return code" ::= 4 trapEmailErrSocket TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - socket error, server is not available" ::= 5 trapEmailErrDNS TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - DNS error" ::= 6 trapSOAPErrFile TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - file SOAP not found" ::= 7 trapSOAPErrDNS TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - DNS error" ::= 8 trapSOAPErrSocket TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - socket error, server is not available" ::= 9 trapSOAPErrDelivery TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - delivery error, wrong return code from server" ::= 10 trapTempHighAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarmInt } DESCRIPTION "Trap for high alarm on temperature" ::= 11 trapHumHighAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, hum, humAlarmInt } DESCRIPTION "Trap for high alarm on relative humidity" ::= 12 trapCompValHighAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, compVal, compValAlarmInt } DESCRIPTION "Trap for high alarm on computed value" ::= 13 trapTempLowAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarmInt } DESCRIPTION "Trap for low alarm on temperature" ::= 21 trapHumLowAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, hum, humAlarmInt } DESCRIPTION "Trap for low alarm on relative humidity" ::= 22 trapCompValLowAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, compVal, compValAlarmInt } DESCRIPTION "Trap for low alarm on computed value" ::= 23 trapTempClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarmInt } DESCRIPTION "Trap for clearing alarm on temperature" ::= 31 trapHumClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, hum, humAlarmInt } DESCRIPTION "Trap for clearing alarm on relative humidity" ::= 32 trapCompValClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, compVal, compValAlarmInt } DESCRIPTION "Trap for clearing alarm on computed value" ::= 33 trapTempError TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarmInt } DESCRIPTION "Trap for error on temperature" ::= 41 trapHumError TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, hum, humAlarmInt } DESCRIPTION "Trap for error on relative humidity" ::= 42 trapCompValError TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, compVal, compValAlarmInt } DESCRIPTION "Trap for error on computed value" ::= 43 END