-- file: ORION-BASE-MIB.mib ORION-BASE-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM SNMPv2-TC OBJECT-GROUP, NOTIFICATION-GROUP, MODULE-COMPLIANCE FROM SNMPv2-CONF modules, orion FROM GLOBAL-REG enterprises, MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Gauge32, Integer32, IpAddress FROM SNMPv2-SMI; orionBaseMibModule MODULE-IDENTITY LAST-UPDATED "200802211439Z" ORGANIZATION "Delta Energy Systems (Switzerland) AG" CONTACT-INFO "postal: Delta Energy Systems (Switzerland) AG Freiburgstrasse 251, CH-3018 Bern-Buempliz web: www.deltapowersolutions.com email: patrick.camina@delta-es.com" DESCRIPTION "MIB for managing a DC power system with PSC 3." REVISION "201204271200Z" DESCRIPTION "Rev V5.0 - ORION V5.10 - Add Multi-Stage temperature compensation - Add dcBoD and dcEnableUsTempComp" REVISION "201201261415Z" DESCRIPTION "Rev V2.1 - ORION V5.0 - changed product name from PSC3 to Orion" REVISION "201106200734Z" DESCRIPTION "Rev V2.0 - PSC 3 V3.20 - hour meter functionality added" REVISION "201102100901Z" DESCRIPTION "Rev V1.9 - PSC 3 V3.10 - dcPowerSystem can be negativ now - added limits for DefaultLog and EventProcessing table - added dcResendActiveAlarmTraps in deschMiscGroup" REVISION "201006161027Z" DESCRIPTION "Rev V1.8 - PSC 3 V2.70 - new rectifier types added - resend active alarm traps feature added - measurement table added - battery test result enum extended" REVISION "201002241046Z" DESCRIPTION "Rev V1.7 - PSC 3 V2.60 - Critical alarm trap added - Float Charge, Battery Test, Equalize, Boost Charge, ,System Voltage Supervision and Event Control Charge parameter added - Rectifier Group table added - Rectifier power limitation and efficiency cycling parameter added - LVD table added - Default Log event configuration table added - Event Processing event configuration table added - Loss of Backup time parameter added" REVISION "200909040952Z" DESCRIPTION "Rev V1.6 - PSC 3 V2.50 - Generic Alarm table added - Trap Destination table added" REVISION "200802211439Z" DESCRIPTION "Rev V1.5 - PSC V2.20 - support of write access - added battery parameters" REVISION "200801180835Z" DESCRIPTION "Rev V1.4 - PSC 3 V2.10 - added event controlled charge state" REVISION "200607271026Z" DESCRIPTION "Rev V1.3 - PSC 3 V1.70 - corrected Oid comment for dcStartTemp, dcStopTemp and dcTotalBatteryCapacity" REVISION "200603020855Z" DESCRIPTION "Rev V1.2 - added various parameters. - added additional TRAP parameter." REVISION "200602230932Z" DESCRIPTION "Rev V1.1 - PSC 3 V1.60 - extended dcChargeState with new sepCharge state." REVISION "200506031107Z" DESCRIPTION "Rev V1.0 - PSC 3 V1.5 and older - added dcCurrentLimit parameter. - renamed module. - increased dcSoftwareVersion string size. - added recharge state to dcChargeState parameter. - added max. number of entries in comment for event history." -- 1.3.6.1.4.1.20246.2.1.1.2 -- ::= { modules 2 } -- root for items in the controller MIB module orionBaseMib OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1 -- ::= { orion 1 } -- conformance area, containing groups and compliance specifications controllerConfs OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.1 -- ::= { orionBaseMib 1 } controllerGroups OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1 -- ::= { controllerConfs 1 } controllerCompl OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2 -- ::= { controllerConfs 2 } -- sub-tree for objects, and for each functional area controllerObjects OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2 -- ::= { orionBaseMib 2 } dcSystemInfo OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1 -- ::= { controllerObjects 1 } dcSystemAlarms OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2 -- ::= { controllerObjects 2 } dcSystemMonitor OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3 -- ::= { controllerObjects 3 } dcRectifier OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4 -- ::= { controllerObjects 4 } dcRectifierFunctions OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6 -- ::= { dcRectifier 6 } dcEfficiencyCycling OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1 -- ::= { dcRectifierFunctions 1 } dcPowerLimitation OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 -- ::= { dcRectifierFunctions 2 } dcBattery OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 -- ::= { controllerObjects 5 } dcFloatCharge OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1 -- ::= { dcBattery 1 } dcBatteryTest OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 -- ::= { dcBattery 2 } dcBatteryTestParameter OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 -- ::= { dcBatteryTest 1 } dcBatteryTestResults OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2 -- ::= { dcBatteryTest 2 } dcBatteryParameter OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3 -- ::= { dcBattery 3 } dcLossOfBackupTime OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3 -- ::= { dcBatteryParameter 3 } dcEqualize OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4 -- ::= { dcBattery 4 } dcEqualizeParameter OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4 -- ::= { dcEqualize 4 } dcBoostCharge OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5 -- ::= { dcBattery 5 } dcBoostChargeParameter OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4 -- ::= { dcBoostCharge 4 } dcSystemVoltageSupervision OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6 -- ::= { dcBattery 6 } dcEvtCtrlCharge OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7 -- ::= { dcBattery 7 } dcEvtCtrlChargeParameter OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3 -- ::= { dcEvtCtrlCharge 3 } dcTempComp OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8 -- ::= { dcBattery 8 } dcTempSupervision OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9 -- ::= { dcBattery 9 } dcInputOutput OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6 -- ::= { controllerObjects 6 } dcMisc OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7 -- ::= { controllerObjects 7 } dcConfig OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8 -- ::= { controllerObjects 8 } dcMeasurement OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9 -- ::= { controllerObjects 9 } dcMeterPanel OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10 -- ::= { controllerObjects 10 } -- sub-tree for notifications controllerEvents OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.3 -- ::= { orionBaseMib 3 } controllerEventObjects OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1 -- ::= { controllerEvents 1 } -- The following OBJECT IDENTIFIER is used to define SNMPv2 notifications -- that are backward compatible with SNMPv1 traps controllerEventsV2 OBJECT IDENTIFIER -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0 -- ::= { controllerEventObjects 0 } -- ================================ -- Scalar objects -- ================================ dcSiteName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "An administratively-assigned site name for this DC-power system." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 -- ::= { dcSystemInfo 1 } dcSystemName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "An administratively-assigned system name for this DC-power system." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 -- ::= { dcSystemInfo 2 } dcSystemDateTime OBJECT-TYPE SYNTAX DisplayString (SIZE (19)) MAX-ACCESS read-write STATUS current DESCRIPTION "ISO 8601 representation of controllerīs local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 -- ::= { dcSystemInfo 3 } dcSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (10..12)) MAX-ACCESS read-only STATUS current DESCRIPTION "The controllerīs software version e.g V2.50Build1." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 -- ::= { dcSystemInfo 4 } dcNumberUrgentAlarms OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 -- ::= { dcSystemAlarms 3 } dcNumberNonUrgentAlarms OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 -- ::= { dcSystemAlarms 4 } dcMainsFailureAlarm OBJECT-TYPE SYNTAX INTEGER { inactive(1), active(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Mains failure alarm." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 -- ::= { dcSystemAlarms 5 } dcUrgentAlarmIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 -- ::= { dcSystemAlarms 6 } dcUrgentAlarmValue OBJECT-TYPE SYNTAX INTEGER { false(1), indeterminate(2), -- deprecated, not used anymore true(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 -- ::= { dcSystemAlarms 7 } dcNonUrgentAlarmIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 -- ::= { dcSystemAlarms 8 } dcNonUrgentAlarmValue OBJECT-TYPE SYNTAX INTEGER { false(1), indeterminate(2), -- deprecated, not used anymore true(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 -- ::= { dcSystemAlarms 9 } dcUrgentAlarmName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Current alarm name for urgent alarm that corresponds to urgent alarm identifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 -- ::= { dcSystemAlarms 10 } dcNonUrgentAlarmName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 -- ::= { dcSystemAlarms 11 } dcNumberCriticalAlarms OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of currently active critical alarm sources. A zero value indicates that critical alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 -- ::= { dcSystemAlarms 13 } dcCriticalAlarmIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Current unique critical alarm event identifier. A zero value indicates that critical alarm is not active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 -- ::= { dcSystemAlarms 14 } dcCriticalAlarmValue OBJECT-TYPE SYNTAX INTEGER { false(1), indeterminate(2), -- deprecated, not used anymore true(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current critical alarm event status that corresponds to the critical alarm identifier. If the critical alarm identifier is zero then the alarm value is false." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 -- ::= { dcSystemAlarms 15 } dcCriticalAlarmName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Current alarm name for active critical alarm that corresponds to critical alarm identifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 -- ::= { dcSystemAlarms 16 } dcSystemVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured system voltage. The max. value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 -- ::= { dcSystemMonitor 1 } dcLoadCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured load current. The max. value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 -- ::= { dcSystemMonitor 2 } dcBatteryCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured battery current. The max. value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 -- ::= { dcSystemMonitor 3 } dcBatteryTemperature OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 -- ::= { dcSystemMonitor 4 } dcChargeState OBJECT-TYPE SYNTAX INTEGER { float(1), discharge(2), equalize(3), boost(4), battTest(5), recharge(6), sepCharge(7), evCtrlCharge(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "Battery charge state." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 -- ::= { dcSystemMonitor 5 } dcCurrentLimit OBJECT-TYPE SYNTAX INTEGER { inactive(1), active(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Battery current limit." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 -- ::= { dcSystemMonitor 6 } dcRectifierCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-only STATUS current DESCRIPTION "Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 -- ::= { dcSystemMonitor 7 } dcSystemPower OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated system power. The maximum value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 -- ::= { dcSystemMonitor 8 } -- Rectifier dcNumberRectifiers OBJECT-TYPE SYNTAX Gauge32 (0..128) MAX-ACCESS read-only STATUS current DESCRIPTION "The configured number of rectifiers plugged into the system. The maximum number of rectifiersi is 128." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 -- ::= { dcRectifier 1 } dcNumberRectifiersFailure OBJECT-TYPE SYNTAX Gauge32 (0..128) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of rectifiers that are not properly working." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 -- ::= { dcRectifier 2 } dcNumberRectifiersOkay OBJECT-TYPE SYNTAX Gauge32 (0..128) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of rectifiers that are properly working." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 -- ::= { dcRectifier 3 } -- Rectifier - RectifierFunctions - EfficiencyCycling dcEfficiencyCyclingEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable efficiency cycling." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 -- ::= { dcEfficiencyCycling 1 } dcLimitSwitchingTimes OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable limit switching times." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 -- ::= { dcEfficiencyCycling 2 } dcForceSwitchingOncePerMonth OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable force switching once per month." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 -- ::= { dcEfficiencyCycling 3 } dcMaximumLoadStep OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum load setup." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 -- ::= { dcEfficiencyCycling 4 } dcMinimumLoadStep OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum load setup." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 -- ::= { dcEfficiencyCycling 5 } -- Battery - FloatCharge dcUsys20 OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Voltage to regulate to at 20°C. If temperature compensation is used, this voltage will vary." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 -- ::= { dcFloatCharge 1 } -- Battery - BatteryTest - BatteryTestParameter dcBatteryTestUsupport OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Support charge voltage for the battery." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 -- ::= { dcBatteryTestParameter 1 } dcBatteryTestDuration OBJECT-TYPE SYNTAX Gauge32 UNITS "minute" MAX-ACCESS read-write STATUS current DESCRIPTION "Battery test duration." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 -- ::= { dcBatteryTestParameter 2 } dcBatteryTestInterval OBJECT-TYPE SYNTAX Gauge32 UNITS "days" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimal time between programmed battery tests as start condition." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 -- ::= { dcBatteryTestParameter 3 } dcBatteryTestDischargeCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 -- ::= { dcBatteryTestParameter 4 } dcBatteryTestMinDuration OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 -- ::= { dcBatteryTestParameter 5 } dcBatteryTestVoltageWithinUfloat OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestVoltageWithinUfloatPeriod) in order to start a battery test." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 -- ::= { dcBatteryTestParameter 6 } dcBatteryTestVoltageWithinUfloatPeriod OBJECT-TYPE SYNTAX Gauge32 UNITS "days" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcBatteryTestVoltageWithinUfloat parameter." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 -- ::= { dcBatteryTestParameter 7 } dcBatteryTestTempFrom OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "Battery temperature must be within temperature range given by dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery test can be started." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 -- ::= { dcBatteryTestParameter 8 } dcBatteryTestTempTo OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcBatteryTestTempFrom parameter." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 -- ::= { dcBatteryTestParameter 9 } dcBatteryTestIntervalEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable interval. For more details see dcBatteryTestInterval." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.10 -- ::= { dcBatteryTestParameter 10 } dcBatteryTestStartTimeFrom OBJECT-TYPE SYNTAX DisplayString (SIZE (8)) MAX-ACCESS read-write STATUS current DESCRIPTION "Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestStartTimeFrom and dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 -- ::= { dcBatteryTestParameter 11 } dcBatteryTestStartTimeTo OBJECT-TYPE SYNTAX DisplayString (SIZE (8)) MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcBatteryTestStartTimeFrom." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 -- ::= { dcBatteryTestParameter 12 } -- Battery - BatteryTest - BatteryTestResults dcBatteryTestDateTime OBJECT-TYPE SYNTAX DisplayString (SIZE (19)) MAX-ACCESS read-only STATUS current DESCRIPTION "ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 -- ::= { dcBatteryTestResults 1 } dcBatteryTestResult OBJECT-TYPE SYNTAX INTEGER { none(1), failed(2), aborted(3), loadFailure(4), okay(5), abortedManual(6), abortedEvCtrlCharge(7), abortedInhibitEv(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "Result of last performed battery test." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 -- ::= { dcBatteryTestResults 2 } dcBatteryTestEndVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-only STATUS current DESCRIPTION "System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 -- ::= { dcBatteryTestResults 3 } dcBatteryTestControl OBJECT-TYPE SYNTAX INTEGER { start(1), stop(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please note that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 -- ::= { dcBatteryTest 3 } dcBatteryTestStatus OBJECT-TYPE SYNTAX INTEGER { inactive(1), starting(2), stopping(3), constantCurrent(4), timeBased(5), energyBased(6), recovery(7), realLoad(8), stop(9) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of battery test." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 -- ::= { dcBatteryTest 4 } dcBatteryTestFailureEvent OBJECT-TYPE SYNTAX INTEGER { reset(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset battery test failure event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 -- ::= { dcBatteryTest 5 } dcBatteryTestType OBJECT-TYPE SYNTAX INTEGER { none(1), constantCurrent(2), --timeBased(3), deprecated -- --energyBased(4), deprecated -- realLoad(5) } MAX-ACCESS read-write STATUS current DESCRIPTION "Battery test type used." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 -- ::= { dcBatteryTest 6 } -- Battery - BatteryParameter dcTotalBatteryCapacity OBJECT-TYPE SYNTAX Gauge32 UNITS "100 mAh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total battery capacity for all available batteries." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 -- ::= { dcBatteryParameter 1 } -- Battery - BatteryParameter - LossOfBackupTime dcLossOfBackupTimeEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable loss of backup time functionality." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 -- ::= { dcLossOfBackupTime 1 } dcLossOfBackupTimeStatus OBJECT-TYPE SYNTAX INTEGER { inactive(1), ok(2), occured(3), fail(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of loss of backup time functionality." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 -- ::= { dcLossOfBackupTime 2 } dcExpectedBackupTime OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Expected backup time value. Based on the given value for the parameter expected backup time, the corresponding maximum discharge current is calculated." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 -- ::= { dcLossOfBackupTime 3 } -- Battery - Equalize dcEqualizeControl OBJECT-TYPE SYNTAX INTEGER { start(1), stop(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 -- ::= { dcEqualize 1 } dcEqualizeStatus OBJECT-TYPE SYNTAX INTEGER { inactive(1), starting(2), stopping(3), preparing(4), cooking(5), recovering(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current status of battery equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 -- ::= { dcEqualize 2 } dcEqualizeEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 -- ::= { dcEqualize 3 } -- Equalize - EqualizeParameter dcEqualizeVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Voltage used for equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 -- ::= { dcEqualizeParameter 1 } dcEqualizeDuration OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Duration of equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 -- ::= { dcEqualizeParameter 2 } dcEqualizeUseBattRoomFanEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable battery room fan during equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 -- ::= { dcEqualizeParameter 3 } dcEqualizeLeadTime OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Lead time for equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 -- ::= { dcEqualizeParameter 4 } dcEqualizeTimeLag OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Time lag for equalize." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 -- ::= { dcEqualizeParameter 5 } dcEqualizeInterval OBJECT-TYPE SYNTAX Gauge32 UNITS "days" MAX-ACCESS read-write STATUS current DESCRIPTION "Interval for equalize as start condition." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 -- ::= { dcEqualizeParameter 6 } dcEqualizeStartTimeIntervalFrom OBJECT-TYPE SYNTAX DisplayString (SIZE (8)) MAX-ACCESS read-write STATUS current DESCRIPTION "Defines start time window for equqlize. The possible time window is defined as the range between dcEqualizeStartTimeIntervalFrom and dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 -- ::= { dcEqualizeParameter 7 } dcEqualizeStartTimeIntervalTo OBJECT-TYPE SYNTAX DisplayString (SIZE (8)) MAX-ACCESS read-write STATUS current DESCRIPTION "For detail see dcEqualizeStartTimeIntervalFrom." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 -- ::= { dcEqualizeParameter 8 } dcEqualizeInhibitAfterBoost OBJECT-TYPE SYNTAX Gauge32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "Inhibit after boost as start condition." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 -- ::= { dcEqualizeParameter 9 } -- Battery - BoostCharge dcBoostChargeControl OBJECT-TYPE SYNTAX INTEGER { start(1), stop(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 -- ::= { dcBoostCharge 1 } dcBoostChargeStatus OBJECT-TYPE SYNTAX INTEGER { inactive(1), starting(2), stopping(3), cooking(4), recovering(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current status of boost charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 -- ::= { dcBoostCharge 2 } dcBoostChargeType OBJECT-TYPE SYNTAX INTEGER { none(1), currentBased(2), timeBased(3), energyBased(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Boost charge type." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 -- ::= { dcBoostCharge 3 } -- Battery - BoostCharge - BoostChargeParameter dcBoostChargeVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Voltage used for boost charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.1 -- ::= { dcBoostChargeParameter 1 } dcBoostChargeMaxDuration OBJECT-TYPE SYNTAX Gauge32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "Defines the maximum allowed time for boost charge to prevent that the battery is charged forever." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.2 -- ::= { dcBoostChargeParameter 2 } dcBoostChargeUseBattRoomFanEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable battery room fan during boost charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.3 -- ::= { dcBoostChargeParameter 3 } dcBoostChargeTimeLag OBJECT-TYPE SYNTAX Gauge32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Time lag used for boost charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.4 -- ::= { dcBoostChargeParameter 4 } dcBoostChargeIstart OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "For current based boost charge, the parameters Istart and Istop are the battery current values at which boost charge starts or stops." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.5 -- ::= { dcBoostChargeParameter 5 } dcBoostChargeIstop OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcBoostChargeIstart." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.6 -- ::= { dcBoostChargeParameter 6 } dcBoostChargeInhibitTime OBJECT-TYPE SYNTAX Gauge32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "A start condition for all types of boost charge. It defines the time from last boost charge stop to the next acceptable boost charge start." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.7 -- ::= { dcBoostChargeParameter 7 } -- Battery - SystemVoltageSupervision dcUaMax OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "If the system voltage is outside the range specified by the values UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the system event 'S Ua low'/'S Ua high' is activated. The values for the parameters UaMin and UaMax are not temperature compensated." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 -- ::= { dcSystemVoltageSupervision 1 } dcUaMin OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcUaMax." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 -- ::= { dcSystemVoltageSupervision 2 } dcUsMax OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "If the voltage is outside the range defined by the parameters UsMin (lower safety voltage)/UsMax (upper safety voltage), the system event 'S Us low'/'S Us high' is activated. If temperature compensation is enabled, the levels for Us min and / Us max are automatically temperature compensated to correspond to the required system voltage. The parameters are defined at 20°C." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 -- ::= { dcSystemVoltageSupervision 3 } dcUsMin OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcUsMax." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 -- ::= { dcSystemVoltageSupervision 4 } dcBoD OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Voltage threshold for Battery on Discharge alarm." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 -- ::= { dcSystemVoltageSupervision 5 } dcHysteresis OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Hysteresis used for Ua and Us." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 -- ::= { dcSystemVoltageSupervision 6 } dcSuppressUaLowEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Suppress Ua Low alarm during mains failure." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 -- ::= { dcSystemVoltageSupervision 7 } dcSuppressUsLowEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Suppress Us Low alarm during mains failure." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 -- ::= { dcSystemVoltageSupervision 8 } dcEnableUsTempComp OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max)." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 -- ::= { dcSystemVoltageSupervision 9 } -- Battery - EvtCtrlCharge dcEvtCtrlChargeStatus OBJECT-TYPE SYNTAX INTEGER { inactive(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Event control charge status." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 -- ::= { dcEvtCtrlCharge 1 } dcEvtCtrlChargeType OBJECT-TYPE SYNTAX INTEGER { none(1), voltageControlled(2), noBatteryCharge(3), currentLimitation(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Selected event control charge type." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 -- ::= { dcEvtCtrlCharge 2 } dcEvtCtrlChargeVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Voltage used for event control charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.1 -- ::= { dcEvtCtrlChargeParameter 1} dcEvtCtrlChargeTempCompEnabled OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable temperature compensation during event control charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.2 -- ::= { dcEvtCtrlChargeParameter 2 } dcEvtCtrlChargeMaxIBatt OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "Max. IBatt used for event control charge." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.3 -- ::= { dcEvtCtrlChargeParameter 3} dcTempCompType OBJECT-TYPE SYNTAX INTEGER { no(1), linear(2), multi-stage(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable battery temperature compensation." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 -- ::= { dcTempComp 1 } dcSlope OBJECT-TYPE SYNTAX Integer32 UNITS "-1 mV/°C" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature compensation coefficient for system voltage." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 -- ::= { dcTempComp 2 } dcStartTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "Lower limit for the area in which the temperature compensation is active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 -- ::= { dcTempComp 3 } dcStopTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "Upper limit for the area in which the temperature compensation is active." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 -- ::= { dcTempComp 4 } dcMaxVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Upper limit for the area in which the temperature compensation is not controlling the system voltage." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 -- ::= { dcTempComp 5 } dcLowStopVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature compensation will not control the charging voltage above this parameter at low temperatures." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 -- ::= { dcTempComp 6 } dcLowStartTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature limit of the lower range." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 -- ::= { dcTempComp 7 } dcLowTempSlope OBJECT-TYPE SYNTAX Integer32 UNITS "-1 mV/°C" MAX-ACCESS read-write STATUS current DESCRIPTION "Compensation factor applied inside the low range." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 -- ::= { dcTempComp 8 } dcHighStartTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "The low temperature limit of the higher range." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 -- ::= { dcTempComp 9 } dcHighTempSlope OBJECT-TYPE SYNTAX Integer32 UNITS "-1 mV/°C" MAX-ACCESS read-write STATUS current DESCRIPTION "Compensation factor applied inside the high range." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 -- ::= { dcTempComp 10 } dcHighStopVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature compensation will not control the charging voltage below this parameter at high temperatures." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 -- ::= { dcTempComp 11 } dcRunawayTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "A threshold for detecting thermal runaway of the battery." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 -- ::= { dcTempComp 12 } dcRunawayVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Charging voltage while Runaway Temp has been exceeded." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 -- ::= { dcTempComp 13 } dcHighTemp OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature threshold for high battery temperature alarm 10°C ... 70°C" -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 -- ::= { dcTempSupervision 1 } dcHighTempHyst OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 °C" MAX-ACCESS read-write STATUS current DESCRIPTION "Hysteresis for the High Temp 1°C ... 70°C" -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 -- ::= { dcTempSupervision 2 } -- Misc dcFileProcessingStatus OBJECT-TYPE SYNTAX INTEGER { idle(1), inProgress(2), successful(3), error(4), unknown(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "File processing status for software and setup up/downloads." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 -- ::= { dcMisc 2 } dcResendActiveAlarmTraps OBJECT-TYPE SYNTAX INTEGER { resend(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Resend all active Urgent, Non Urgent, and Critical Alarm Traps." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 -- ::= { dcMisc 4 } -- Event Processing Table dcEventProcessingEventSelected OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-write STATUS current DESCRIPTION "Reference to dcEventProcessingEventIndex in order to select a specific event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 -- ::= { dcConfig 3 } -- ==================================================================== -- Event History table -- ==================================================================== dcEventHistoryTable OBJECT-TYPE SYNTAX SEQUENCE OF DcEventHistoryEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Controllerīs event history table that shows the content of the default log file." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 -- ::= { dcSystemAlarms 1 } dcEventHistoryEntry OBJECT-TYPE SYNTAX DcEventHistoryEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular Event History entry." INDEX { dcEventHistoryIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 -- ::= { dcEventHistoryTable 1 } DcEventHistoryEntry ::= SEQUENCE { dcEventHistoryIndex Integer32, dcEventHistoryTimestamp DisplayString, dcEventHistoryMessage DisplayString } dcEventHistoryIndex OBJECT-TYPE SYNTAX Integer32 (1..10000) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 -- ::= { dcEventHistoryEntry 1 } dcEventHistoryTimestamp OBJECT-TYPE SYNTAX DisplayString (SIZE (19)) MAX-ACCESS read-only STATUS current DESCRIPTION "ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 -- ::= { dcEventHistoryEntry 2 } dcEventHistoryMessage OBJECT-TYPE SYNTAX DisplayString (SIZE (1..255)) MAX-ACCESS read-only STATUS current DESCRIPTION "Event message of a particular entry." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 -- ::= { dcEventHistoryEntry 3 } -- ==================================================================== -- Active Alarm table -- ==================================================================== dcAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF DcAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s)." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 -- ::= { dcSystemAlarms 2 } dcAlarmEntry OBJECT-TYPE SYNTAX DcAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular active alarm source entry." INDEX { dcAlarmIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 -- ::= { dcAlarmTable 1 } DcAlarmEntry ::= SEQUENCE { dcAlarmIndex Integer32, dcAlarmEventCategory INTEGER, dcAlarmEventName DisplayString, dcAlarmEventIdentifier Gauge32, dcAlarmEventValue INTEGER } dcAlarmIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 -- ::= { dcAlarmEntry 1 } dcAlarmEventCategory OBJECT-TYPE SYNTAX INTEGER { unknown(1), urgent(2), nonUrgent(3), critical(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Specifies the type of alarm source." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 -- ::= { dcAlarmEntry 2 } dcAlarmEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of a particular alarm source entry." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 -- ::= { dcAlarmEntry 3 } dcAlarmEventIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unique alarm event identifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 -- ::= { dcAlarmEntry 4 } dcAlarmEventValue OBJECT-TYPE SYNTAX INTEGER { false(1), -- indeterminate(2), deprecated -- true(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Event status that corresponds to alarm event identifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 -- ::= { dcAlarmEntry 5 } -- ==================================================================== -- Generic Alarm table -- ==================================================================== dcGenericAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF DcGenericAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows ten alarm event assignments that can be configured via WEB interface." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 -- ::= { dcSystemAlarms 12 } dcGenericAlarmEntry OBJECT-TYPE SYNTAX DcGenericAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular generic alarm entry." INDEX { dcGenericAlarmIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 -- ::= { dcGenericAlarmTable 1 } DcGenericAlarmEntry ::= SEQUENCE { dcGenericAlarmIndex Integer32, dcGenericAlarmEventName DisplayString, dcGenericAlarmEventIdentifier Gauge32, dcGenericAlarmEventValue INTEGER } dcGenericAlarmIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 -- ::= { dcGenericAlarmEntry 1 } dcGenericAlarmEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Plain text name of the assigned alarm event. Empty if not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 -- ::= { dcGenericAlarmEntry 2 } dcGenericAlarmEventIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unique numeric identifier of the assigned alarm event. Zero if not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 -- ::= { dcGenericAlarmEntry 3 } dcGenericAlarmEventValue OBJECT-TYPE SYNTAX INTEGER { false(1), true(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current value of the assigned alarm event. Value is false if not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 -- ::= { dcGenericAlarmEntry 4 } -- ==================================================================== -- Rectifier table -- ==================================================================== dcRectifierTable OBJECT-TYPE SYNTAX SEQUENCE OF DcRectifierEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows all currently active rectifier modules." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 -- ::= { dcRectifier 4 } dcRectifierEntry OBJECT-TYPE SYNTAX DcRectifierEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular rectifier entry." INDEX { dcRectifierIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 -- ::= { dcRectifierTable 1 } DcRectifierEntry ::= SEQUENCE { dcRectifierIndex Integer32, dcRectifierIdentifier DisplayString, dcRectifierStatus INTEGER } dcRectifierIndex OBJECT-TYPE SYNTAX Integer32 (1..128) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 -- ::= { dcRectifierEntry 1 } dcRectifierIdentifier OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 -- ::= { dcRectifierEntry 2 } dcRectifierStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), off(2), on(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Specifies status of rectifiers." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 -- ::= { dcRectifierEntry 3 } -- ==================================================================== -- Rectifier Group table -- ==================================================================== dcRectifierGroupTable OBJECT-TYPE SYNTAX SEQUENCE OF DcRectifierGroupEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows all available rectifier groups." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 -- ::= { dcRectifier 5 } dcRectifierGroupEntry OBJECT-TYPE SYNTAX DcRectifierGroupEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular rectifier group entry." INDEX { dcRectifierGroupIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 -- ::= { dcRectifierGroupTable 1 } DcRectifierGroupEntry ::= SEQUENCE { dcRectifierGroupIndex Integer32, dcRectifierGroupName DisplayString, dcRectifierGroupRectifierType INTEGER, dcRectifierGroupDefaultVoltage Integer32, dcRectifierGroupDefaultCurrentLimit Integer32, dcRectifierGroupDefaultPowerLimit Integer32, dcRectifierGroupInputLowOff Integer32, dcRectifierGroupInputLowOn Integer32, dcRectifierGroupStartupVoltage Integer32, dcRectifierGroupStartupCurrentLimit Integer32, dcRectifierGroupStartupPowerLimit Integer32, dcRectifierGroupStartupTimeLimit Gauge32, dcRectifierGroupPowerupDelay Gauge32, dcRectifierGroupPowerupTime Gauge32, dcRectifierGroupUmaxOff Integer32 } dcRectifierGroupIndex OBJECT-TYPE SYNTAX Integer32 (1..1) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 -- ::= { dcRectifierGroupEntry 1 } dcRectifierGroupName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Rectifier group name to identify an individual device parameter set." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 -- ::= { dcRectifierGroupEntry 2 } dcRectifierGroupRectifierType OBJECT-TYPE SYNTAX INTEGER { unknown48V(1), fR48V2000W(2), dPR1200B48(3), dPR1500B48(4), dPR600B48(5), dPR7200B48(6), fR48to60V2000W(7), unknown24V(8), unknown60V(9), dPR600B60(10), dPR3500B48(11), dPR3500B24(12), dPR300B48(13), dPR1600B48(14), dPR2700B48(15), dPR2400B48(16), dPR4000B48(17), dPR2900B48(18), dPR4000B48to60(19), dPR850B48(20), dPR2000B48(21) } MAX-ACCESS read-only STATUS current DESCRIPTION "Rectifier type defined for this group." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 -- ::= { dcRectifierGroupEntry 3 } dcRectifierGroupDefaultVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "This default voltage is used by rectifiers when there is no connection to PSC 3." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 -- ::= { dcRectifierGroupEntry 4 } dcRectifierGroupDefaultCurrentLimit OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "This default current limit is used by rectifiers when there is no connection to PSC 3." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 -- ::= { dcRectifierGroupEntry 5 } dcRectifierGroupDefaultPowerLimit OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-write STATUS current DESCRIPTION "This default power limit is used by rectifiers when there is no connection to PSC 3." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 -- ::= { dcRectifierGroupEntry 6 } dcRectifierGroupInputLowOff OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold for low AC input voltage. It can is used to adjust the behaviour of the power system to the available AC network limitation." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 -- ::= { dcRectifierGroupEntry 7 } dcRectifierGroupInputLowOn OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcRectifierGroupInputLowOff." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 -- ::= { dcRectifierGroupEntry 8 } dcRectifierGroupStartupVoltage OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Startup parameters are the values that rectifiers use during the start-up phase. These parameters allow starting the system smoothly after a mains failure even on a discharged battery and even without PSC 3." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 -- ::= { dcRectifierGroupEntry 9 } dcRectifierGroupStartupCurrentLimit OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcRectifierGroupStartupVoltage." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 -- ::= { dcRectifierGroupEntry 10 } dcRectifierGroupStartupPowerLimit OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcRectifierGroupStartupVoltage." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 -- ::= { dcRectifierGroupEntry 11 } dcRectifierGroupStartupTimeLimit OBJECT-TYPE SYNTAX Gauge32 UNITS "10 ms" MAX-ACCESS read-write STATUS current DESCRIPTION "For details see dcRectifierGroupStartupVoltage." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 -- ::= { dcRectifierGroupEntry 12 } dcRectifierGroupPowerupDelay OBJECT-TYPE SYNTAX Gauge32 UNITS "10 ms" MAX-ACCESS read-write STATUS current DESCRIPTION "This parameter is used after a mains failure to delay the start-up of all rectifiers." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 -- ::= { dcRectifierGroupEntry 13 } dcRectifierGroupPowerupTime OBJECT-TYPE SYNTAX Gauge32 UNITS "10 ms" MAX-ACCESS read-write STATUS current DESCRIPTION "This parameter used after a mains failure and allows defining a time within all rectifiers needs to start-up one after another." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 -- ::= { dcRectifierGroupEntry 14 } dcRectifierGroupUmaxOff OBJECT-TYPE SYNTAX Integer32 UNITS "10 mV" MAX-ACCESS read-write STATUS current DESCRIPTION "Overvoltage protection value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 -- ::= { dcRectifierGroupEntry 15 } -- ==================================================================== -- Rectifier Power Limitation table -- ==================================================================== dcPowerLimitationTable OBJECT-TYPE SYNTAX SEQUENCE OF DcPowerLimitationEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows parameters of the available power limitation functions." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 -- ::= { dcPowerLimitation 1 } dcPowerLimitationEntry OBJECT-TYPE SYNTAX DcPowerLimitationEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular power limitation entry." INDEX { dcPowerLimitationIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 -- ::= { dcPowerLimitationTable 1 } DcPowerLimitationEntry ::= SEQUENCE { dcPowerLimitationIndex Integer32, dcPowerLimitationEventName DisplayString, dcPowerLimitationStatus INTEGER, dcPowerLimitationType INTEGER, dcPowerLimitationLimit Integer32, dcPowerLimitationNoBatteryDischarge INTEGER } dcPowerLimitationIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 -- ::= { dcPowerLimitationEntry 1 } dcPowerLimitationEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of the power limitation event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.2 -- ::= { dcPowerLimitationEntry 2 } dcPowerLimitationStatus OBJECT-TYPE SYNTAX INTEGER { disabled(1), inactive(2), powerLimit(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of power limitation." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.3 -- ::= { dcPowerLimitationEntry 3 } dcPowerLimitationType OBJECT-TYPE SYNTAX INTEGER { dynamic(1), fixedLimit(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Power limitation type." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.4 -- ::= { dcPowerLimitationEntry 4 } dcPowerLimitationLimit OBJECT-TYPE SYNTAX Integer32 UNITS "1 W" MAX-ACCESS read-write STATUS current DESCRIPTION "Limit used for power limitation." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.5 -- ::= { dcPowerLimitationEntry 5 } dcPowerLimitationNoBatteryDischarge OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable/disable no battery discharge during power limitation." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.6 -- ::= { dcPowerLimitationEntry 6 } -- ==================================================================== -- BatteryString table -- ==================================================================== dcBatteryStringTable OBJECT-TYPE SYNTAX SEQUENCE OF DcBatteryStringEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows parameters of the available battery strings." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 -- ::= { dcBatteryParameter 2 } dcBatteryStringEntry OBJECT-TYPE SYNTAX DcBatteryStringEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular battery string entry." INDEX { dcBatteryStringIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 -- ::= { dcBatteryStringTable 1 } DcBatteryStringEntry ::= SEQUENCE { dcBatteryStringIndex Integer32, dcBatteryStringName DisplayString, dcBatteryStringMaxIBatt Integer32, dcBatteryStringCapacity Gauge32 } dcBatteryStringIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 -- ::= { dcBatteryStringEntry 1 } dcBatteryStringName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of the battery string." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 -- ::= { dcBatteryStringEntry 2 } dcBatteryStringMaxIBatt OBJECT-TYPE SYNTAX Integer32 UNITS "100 mA" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum battery charging current for this string. This parameter can be set individually for each battery. PSC 3 then regulates the system voltage such that the maximum battery charging current of each battery is respected." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 -- ::= { dcBatteryStringEntry 3 } dcBatteryStringCapacity OBJECT-TYPE SYNTAX Gauge32 UNITS "100 mAh" MAX-ACCESS read-write STATUS current DESCRIPTION "Capacity of battery can be defined individually. It is used to calculate the expected backup time of the system." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 -- ::= { dcBatteryStringEntry 4 } -- ==================================================================== -- Control Event table -- ==================================================================== dcControlEventTable OBJECT-TYPE SYNTAX SEQUENCE OF DcControlEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that shows ten output event assignments that can be configured via WEB interface." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 -- ::= { dcInputOutput 1 } dcControlEventEntry OBJECT-TYPE SYNTAX DcControlEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular generic output entry." INDEX { dcControlEventIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 -- ::= { dcControlEventTable 1 } DcControlEventEntry ::= SEQUENCE { dcControlEventIndex Integer32, dcControlEventName DisplayString, dcControlEventIdentifier Gauge32, dcControlEventValue INTEGER } dcControlEventIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 -- ::= { dcControlEventEntry 1 } dcControlEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Plain text name of the assigned control event. Empty if not configure." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 -- ::= { dcControlEventEntry 2 } dcControlEventIdentifier OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unique numeric identifier of the assigned control event. Zero if not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 -- ::= { dcControlEventEntry 3 } dcControlEventValue OBJECT-TYPE SYNTAX INTEGER { false(1), true(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Current value of the assigned control event. Value is false if not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 -- ::= { dcControlEventEntry 4 } -- ==================================================================== -- Trap Destinations table -- ==================================================================== dcTrapDestinationTable OBJECT-TYPE SYNTAX SEQUENCE OF DcTrapDestinationEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap table that shows all configured trap destinations." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 -- ::= { dcMisc 1 } dcTrapDestinationEntry OBJECT-TYPE SYNTAX DcTrapDestinationEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular trap destination entry." INDEX { dcTrapDestinationIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 -- ::= { dcTrapDestinationTable 1 } DcTrapDestinationEntry ::= SEQUENCE { dcTrapDestinationIndex Integer32, dcTrapDestinationIp IpAddress, dcTrapDestinationPort Gauge32 } dcTrapDestinationIndex OBJECT-TYPE SYNTAX Integer32 (1..10) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 -- ::= { dcTrapDestinationEntry 1 } dcTrapDestinationIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 -- ::= { dcTrapDestinationEntry 2 } dcTrapDestinationPort OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-write STATUS current DESCRIPTION "Port number of the trap destination. By default port 162 is used." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 -- ::= { dcTrapDestinationEntry 3 } -- ==================================================================== -- Default Log Config table -- ==================================================================== dcDefaultLogEventTable OBJECT-TYPE SYNTAX SEQUENCE OF DcDefaultLogEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Event config table for default log." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 -- ::= { dcConfig 1 } dcDefaultLogEventEntry OBJECT-TYPE SYNTAX DcDefaultLogEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular event entry." INDEX { dcDefaultLogEventIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 -- ::= { dcDefaultLogEventTable 1 } DcDefaultLogEventEntry ::= SEQUENCE { dcDefaultLogEventIndex Integer32, dcDefaultLogEventName DisplayString, dcDefaultLogEventLogged INTEGER } dcDefaultLogEventIndex OBJECT-TYPE SYNTAX Integer32 (0..1000) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 -- ::= { dcDefaultLogEventEntry 1 } dcDefaultLogEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Plain text name of the event that can be logged." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 -- ::= { dcDefaultLogEventEntry 2 } dcDefaultLogEventLogged OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If yes then this event is logged otherwise not." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 -- ::= { dcDefaultLogEventEntry 3 } -- ==================================================================== -- Event Processing Config table -- ==================================================================== dcEventProcessingEventTable OBJECT-TYPE SYNTAX SEQUENCE OF DcEventProcessingEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Event config table for event ORs." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 -- ::= { dcConfig 2 } dcEventProcessingEventEntry OBJECT-TYPE SYNTAX DcEventProcessingEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular event entry." INDEX { dcEventProcessingEventIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 -- ::= { dcEventProcessingEventTable 1 } DcEventProcessingEventEntry ::= SEQUENCE { dcEventProcessingEventIndex Integer32, dcEventProcessingEventName DisplayString, dcEventProcessingEventAssigned INTEGER, dcEventProcessingEventType INTEGER } dcEventProcessingEventIndex OBJECT-TYPE SYNTAX Integer32 (0..1000) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 -- ::= { dcEventProcessingEventEntry 1 } dcEventProcessingEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..35)) MAX-ACCESS read-only STATUS current DESCRIPTION "Plain text name of the input event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 -- ::= { dcEventProcessingEventEntry 2 } dcEventProcessingEventAssigned OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If yes then the input event is assigned to the selected event. Please note, that it is only possible to change assignment of event ORs." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 -- ::= { dcEventProcessingEventEntry 3 } dcEventProcessingEventType OBJECT-TYPE SYNTAX INTEGER { unknown(1), eventOR(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the input event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 -- ::= { dcEventProcessingEventEntry 4 } -- ==================================================================== -- LVD Config table -- ==================================================================== dcLvdTable OBJECT-TYPE SYNTAX SEQUENCE OF DcLvdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table lists all available LVDs." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 -- ::= { dcConfig 4 } dcLvdEntry OBJECT-TYPE SYNTAX DcLvdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular LVD entry." INDEX { dcLvdIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 -- ::= { dcLvdTable 1 } DcLvdEntry ::= SEQUENCE { dcLvdIndex Integer32, dcLvdName DisplayString, dcLvdDisconnectDelay DisplayString } dcLvdIndex OBJECT-TYPE SYNTAX Integer32 (1..96) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 -- ::= { dcLvdEntry 1 } dcLvdName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of the LVD." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 -- ::= { dcLvdEntry 2 } dcLvdDisconnectDelay OBJECT-TYPE SYNTAX DisplayString (SIZE (8)) MAX-ACCESS read-write STATUS current DESCRIPTION "Time delay from the activation of the source event, after which the LVD event is switched. The value is in the format 'hh:mm:ss'." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 -- ::= { dcLvdEntry 3 } -- ==================================================================== -- Measurement table -- ==================================================================== dcMeasurementTable OBJECT-TYPE SYNTAX SEQUENCE OF DcMeasurementEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table lists all available measurements." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 -- ::= { dcMeasurement 1 } dcMeasurementEntry OBJECT-TYPE SYNTAX DcMeasurementEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular measurement entry." INDEX { dcMeasurementIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 -- ::= { dcMeasurementTable 1 } DcMeasurementEntry ::= SEQUENCE { dcMeasurementIndex Integer32, dcMeasurementName DisplayString, dcMeasurementValue Integer32, dcMeasurementScaleFactor Integer32, dcMeasurementUnit INTEGER } dcMeasurementIndex OBJECT-TYPE SYNTAX Integer32 (1..500) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 -- ::= { dcMeasurementEntry 1 } dcMeasurementName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of the measurement." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 -- ::= { dcMeasurementEntry 2 } dcMeasurementValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unscaled calibrated value of the measurement." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 -- ::= { dcMeasurementEntry 3 } dcMeasurementScaleFactor OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Scale factor as power of 10 to be multiplied with measurement value." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 -- ::= { dcMeasurementEntry 4 } dcMeasurementUnit OBJECT-TYPE SYNTAX INTEGER { unknown(1), none(2), voltDC(3), voltAC(4), ampere(5), ampereHour(6), degreeCelsius(7), temperatureCoefficient(8), watt(9), wattHour(10), seconds(11), percent(12), hertz(13), voltAmpere(14), voltAmpereReactive(15), voltAmpereReactiveHour(16) } MAX-ACCESS read-only STATUS current DESCRIPTION "Unit of the measurement." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 -- ::= { dcMeasurementEntry 5 } -- ==================================================================== -- Meter Panel Event table -- ==================================================================== dcMeterPanelEventTable OBJECT-TYPE SYNTAX SEQUENCE OF DcMeterPanelEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table lists all available meter panel events." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 -- ::= { dcMeterPanel 1 } dcMeterPanelEventEntry OBJECT-TYPE SYNTAX DcMeterPanelEventEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A particular meter panel event entry." INDEX { dcMeterPanelEventIndex } -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 -- ::= { dcMeterPanelEventTable 1 } DcMeterPanelEventEntry ::= SEQUENCE { dcMeterPanelEventIndex Integer32, dcMeterPanelEventName DisplayString, dcMeterPanelEventValue INTEGER, dcMeterPanelEventHourMeterValue Gauge32 } dcMeterPanelEventIndex OBJECT-TYPE SYNTAX Integer32 (1..128) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table index." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 -- ::= { dcMeterPanelEventEntry 1 } dcMeterPanelEventName OBJECT-TYPE SYNTAX DisplayString (SIZE (1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "Name of the event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 -- ::= { dcMeterPanelEventEntry 2 } dcMeterPanelEventValue OBJECT-TYPE SYNTAX INTEGER { false(1), indeterminate(2), true(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Value of the event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 -- ::= { dcMeterPanelEventEntry 3 } dcMeterPanelEventHourMeterValue OBJECT-TYPE SYNTAX Gauge32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Value of the hour meter event." -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 -- ::= { dcMeterPanelEventEntry 4 } -- ==================================================================== -- Notifications -- ==================================================================== systemNonUrgentAlarm NOTIFICATION-TYPE OBJECTS { dcSystemDateTime, dcNumberNonUrgentAlarms, dcNonUrgentAlarmIdentifier, dcNonUrgentAlarmValue, dcNonUrgentAlarmName } STATUS current DESCRIPTION "The controller reports that one or more elements have changed into none urgent alarm state." -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1 -- ::= { controllerEventsV2 1 } systemUrgentAlarm NOTIFICATION-TYPE OBJECTS { dcSystemDateTime, dcNumberUrgentAlarms, dcUrgentAlarmIdentifier, dcUrgentAlarmValue, dcUrgentAlarmName } STATUS current DESCRIPTION "The controller reports that one or more elements have changed into urgent alarm state." -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2 -- ::= { controllerEventsV2 2 } systemCriticalAlarm NOTIFICATION-TYPE OBJECTS { dcSystemDateTime, dcNumberCriticalAlarms, dcCriticalAlarmIdentifier, dcCriticalAlarmValue, dcCriticalAlarmName } STATUS current DESCRIPTION "The controller reports that one or more elements have changed into critical alarm state." -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3 -- ::= { controllerEventsV2 3 } -- ==================================================================== -- Conformance area, containing groups and compliance specifications -- ==================================================================== systemInfoGroup OBJECT-GROUP OBJECTS { dcSiteName, dcSystemName, dcSystemDateTime, dcSoftwareVersion } STATUS current DESCRIPTION "The collection of system info scalar objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1 -- ::= { controllerGroups 1 } systemAlarmGroup OBJECT-GROUP OBJECTS { dcNumberUrgentAlarms, dcNumberNonUrgentAlarms, dcMainsFailureAlarm, dcUrgentAlarmIdentifier, dcUrgentAlarmValue, dcNonUrgentAlarmIdentifier, dcNonUrgentAlarmValue, dcUrgentAlarmName, dcNonUrgentAlarmName, dcNumberCriticalAlarms, dcCriticalAlarmIdentifier, dcCriticalAlarmValue, dcCriticalAlarmName } STATUS current DESCRIPTION "The collection of system alarm scalar objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2 -- ::= { controllerGroups 2 } systemMonitorGroup OBJECT-GROUP OBJECTS { dcSystemVoltage, dcLoadCurrent, dcBatteryCurrent, dcBatteryTemperature, dcChargeState, dcCurrentLimit, dcRectifierCurrent, dcSystemPower } STATUS current DESCRIPTION "The collection of system monitor scalar objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3 -- ::= { controllerGroups 3 } rectifierGroup OBJECT-GROUP OBJECTS { dcNumberRectifiers, dcNumberRectifiersFailure, dcNumberRectifiersOkay, dcEfficiencyCyclingEnabled, dcLimitSwitchingTimes, dcForceSwitchingOncePerMonth, dcMaximumLoadStep, dcMinimumLoadStep } STATUS current DESCRIPTION "The collection of rectifier scalar objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4 -- ::= { controllerGroups 4 } eventHistoryTableGroup OBJECT-GROUP OBJECTS { dcEventHistoryTimestamp, dcEventHistoryMessage } STATUS current DESCRIPTION "The collection of event history table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5 -- ::= { controllerGroups 5 } alarmTableGroup OBJECT-GROUP OBJECTS { dcAlarmEventCategory, dcAlarmEventName, dcAlarmEventIdentifier, dcAlarmEventValue } STATUS current DESCRIPTION "The collection of alarm table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6 -- ::= { controllerGroups 6 } rectifierTableGroup OBJECT-GROUP OBJECTS { dcRectifierIdentifier, dcRectifierStatus } STATUS current DESCRIPTION "The collection of rectifier table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7 -- ::= { controllerGroups 7 } notificationsGroup NOTIFICATION-GROUP NOTIFICATIONS { systemNonUrgentAlarm, systemUrgentAlarm, systemCriticalAlarm } STATUS current DESCRIPTION "The group of all controller notifications." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8 -- ::= { controllerGroups 8 } genericAlarmTableGroup OBJECT-GROUP OBJECTS { dcGenericAlarmEventIdentifier, dcGenericAlarmEventName, dcGenericAlarmEventValue } STATUS current DESCRIPTION "Assignment of events to alarm table entries." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9 -- ::= { controllerGroups 9 } batteryGroup OBJECT-GROUP OBJECTS { dcUsys20, dcTempCompType, dcSlope, dcStartTemp, dcStopTemp, dcMaxVoltage, dcLowStopVoltage, dcLowStartTemp, dcLowTempSlope, dcHighStartTemp, dcHighTempSlope, dcHighStopVoltage, dcRunawayTemp, dcRunawayVoltage, dcBatteryTestUsupport, dcBatteryTestDuration, dcBatteryTestInterval, dcBatteryTestDischargeCurrent, dcBatteryTestMinDuration, dcBatteryTestVoltageWithinUfloat, dcBatteryTestVoltageWithinUfloatPeriod, dcBatteryTestTempFrom, dcBatteryTestTempTo, dcBatteryTestIntervalEnabled, dcBatteryTestStartTimeFrom, dcBatteryTestStartTimeTo, dcBatteryTestDateTime, dcBatteryTestResult, dcBatteryTestEndVoltage, dcBatteryTestControl, dcBatteryTestStatus, dcBatteryTestFailureEvent, dcBatteryTestType, dcTotalBatteryCapacity, dcLossOfBackupTimeEnabled, dcLossOfBackupTimeStatus, dcExpectedBackupTime, dcEqualizeControl, dcEqualizeStatus, dcEqualizeEnabled, dcEqualizeVoltage, dcEqualizeDuration, dcEqualizeUseBattRoomFanEnabled, dcEqualizeLeadTime, dcEqualizeTimeLag, dcEqualizeInterval, dcEqualizeStartTimeIntervalFrom, dcEqualizeStartTimeIntervalTo, dcEqualizeInhibitAfterBoost, dcBoostChargeControl, dcBoostChargeStatus, dcBoostChargeType, dcBoostChargeVoltage, dcBoostChargeMaxDuration, dcBoostChargeUseBattRoomFanEnabled, dcBoostChargeTimeLag, dcBoostChargeIstart, dcBoostChargeIstop, dcBoostChargeInhibitTime, dcUaMax, dcUaMin, dcUsMax, dcUsMin, dcBoD, dcHysteresis, dcSuppressUaLowEnabled, dcSuppressUsLowEnabled, dcEnableUsTempComp, dcEvtCtrlChargeStatus, dcEvtCtrlChargeType, dcEvtCtrlChargeVoltage, dcEvtCtrlChargeTempCompEnabled, dcEvtCtrlChargeMaxIBatt, dcHighTemp, dcHighTempHyst } STATUS current DESCRIPTION "The collection of battery scalar objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10 -- ::= { controllerGroups 10 } controlEventTableGroup OBJECT-GROUP OBJECTS { dcControlEventName, dcControlEventIdentifier, dcControlEventValue } STATUS current DESCRIPTION "Assignment of control events to table entries." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11 -- ::= { controllerGroups 11 } trapDestinationTableGroup OBJECT-GROUP OBJECTS { dcTrapDestinationIp, dcTrapDestinationPort } STATUS current DESCRIPTION "Trap destionation table." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12 -- ::= { controllerGroups 12 } miscGroup OBJECT-GROUP OBJECTS { dcFileProcessingStatus, dcResendActiveAlarmTraps } STATUS current DESCRIPTION "The collection of miscellaneous objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13 -- ::= { controllerGroups 13 } rectifierGroupTableGroup OBJECT-GROUP OBJECTS { dcRectifierGroupName, dcRectifierGroupRectifierType, dcRectifierGroupDefaultVoltage, dcRectifierGroupDefaultCurrentLimit, dcRectifierGroupDefaultPowerLimit, dcRectifierGroupInputLowOff, dcRectifierGroupInputLowOn, dcRectifierGroupStartupVoltage, dcRectifierGroupStartupCurrentLimit, dcRectifierGroupStartupPowerLimit, dcRectifierGroupStartupTimeLimit, dcRectifierGroupPowerupDelay, dcRectifierGroupPowerupTime, dcRectifierGroupUmaxOff } STATUS current DESCRIPTION "The collection of rectifier group table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14 -- ::= { controllerGroups 14 } batteryStringTableGroup OBJECT-GROUP OBJECTS { dcBatteryStringName, dcBatteryStringMaxIBatt, dcBatteryStringCapacity } STATUS current DESCRIPTION "The collection of battery string table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15 -- ::= { controllerGroups 15 } defaultLogEventTableGroup OBJECT-GROUP OBJECTS { dcDefaultLogEventName, dcDefaultLogEventLogged } STATUS current DESCRIPTION "The collection of default log event table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16 -- ::= { controllerGroups 16 } eventProcessingEventTableGroup OBJECT-GROUP OBJECTS { dcEventProcessingEventName, dcEventProcessingEventAssigned, dcEventProcessingEventType, dcEventProcessingEventSelected } STATUS current DESCRIPTION "The collection of event processing event table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17 -- ::= { controllerGroups 17 } lvdTableGroup OBJECT-GROUP OBJECTS { dcLvdName, dcLvdDisconnectDelay } STATUS current DESCRIPTION "The collection of LVD table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18 -- ::= { controllerGroups 18 } powerLimitationTableGroup OBJECT-GROUP OBJECTS { dcPowerLimitationEventName, dcPowerLimitationStatus, dcPowerLimitationType, dcPowerLimitationLimit, dcPowerLimitationNoBatteryDischarge } STATUS current DESCRIPTION "The collection of power limitation table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19 -- ::= { controllerGroups 19 } measurementTableGroup OBJECT-GROUP OBJECTS { dcMeasurementName, dcMeasurementValue, dcMeasurementScaleFactor, dcMeasurementUnit } STATUS current DESCRIPTION "The collection of measurement table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20 -- ::= { controllerGroups 20 } meterPanelEventTableGroup OBJECT-GROUP OBJECTS { dcMeterPanelEventName, dcMeterPanelEventValue, dcMeterPanelEventHourMeterValue } STATUS current DESCRIPTION "The collection of meter panel event table objects." -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21 -- ::= { controllerGroups 21 } controllerBasicCompl MODULE-COMPLIANCE STATUS current DESCRIPTION "The basic implementation requirements for the controller MIB." MODULE MANDATORY-GROUPS { systemInfoGroup, systemAlarmGroup, systemMonitorGroup, alarmTableGroup, notificationsGroup } -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1 -- ::= { controllerCompl 1 } END