PDU-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI enterprises, Integer32, IpAddress, Opaque FROM SNMPv2-SMI MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF TEXTUAL-CONVENTION, DisplayString, MacAddress FROM SNMPv2-TC; eaton MODULE-IDENTITY LAST-UPDATED "200803140000Z" -- March 14, 2008 ORGANIZATION "Eaton Corporation" CONTACT-INFO " Author: Eaton Corporation postal: Eaton Corporation Eaton Center 1111 Superior Avenue Cleveland, OH 44114-2584 phone: +1 (216) 523-5000 " DESCRIPTION "This mib describes the SNMP functions of the Power Distribution Unit by Eaton Corporation." REVISION "200803140000z" DESCRIPTION "Modified MIB in effort to better support HP Openview and other SNMP managers." REVISION "200702140000Z" DESCRIPTION "Updated version for remote access to pdu." ::= { enterprises 534 } product OBJECT IDENTIFIER ::= { eaton 6 } pduagent OBJECT IDENTIFIER ::= { product 6 } pdu OBJECT IDENTIFIER ::= { pduagent 6 } traps OBJECT IDENTIFIER ::= { pdu 0 } board OBJECT IDENTIFIER ::= { pdu 1 } environmental OBJECT IDENTIFIER ::= { pdu 2 } conformance OBJECT IDENTIFIER ::= { pdu 9 } info OBJECT IDENTIFIER ::= { board 1 } outlets OBJECT IDENTIFIER ::= { board 2 } unit OBJECT IDENTIFIER ::= { board 3 } unitReadings OBJECT IDENTIFIER ::= { unit 1 } compliances OBJECT IDENTIFIER ::= { conformance 1 } groups OBJECT IDENTIFIER ::= { conformance 2 } -- Conformance Information compliance MODULE-COMPLIANCE STATUS current DESCRIPTION "The requirements for conformance to the PDU-MIB." MODULE -- this module GROUP infoGroup DESCRIPTION "The info group." GROUP outletsGroup DESCRIPTION "The outlets group." GROUP unitSensorsGroup DESCRIPTION "The unit sensor readings association group." GROUP externalTemperatureGroup DESCRIPTION "The external temperature sensor association group." GROUP externalHumidityGroup DESCRIPTION "The external humidity sensor association group." GROUP trapsGroup DESCRIPTION "The traps group." ::= { compliances 1 } infoGroup OBJECT-GROUP OBJECTS { firmwareVersion, serialNumber, ipAddress, netmask, gateway, mac, hardwareRev, userName, objectName, objectInstance, targetUser, groupName, imageVersion, sensorDescr, thresholdDescr, thresholdSeverity, thresholdEventType, status, slaveIpAddress } STATUS current DESCRIPTION "A collection of objects providing basic information about the pdu." ::= { groups 1 } outletsGroup OBJECT-GROUP OBJECTS { outletCount, outletLabel, outletOperationalState, outletCurrent, outletMaxCurrent, outletVoltage, outletActivePower, outletApparentPower, outletPowerFactor, outletCurrentUpperWarning, outletCurrentUpperCritical } STATUS current DESCRIPTION "A collection of objects providing basic information about the outlets, including sensor readings." ::= { groups 2 } unitSensorsGroup OBJECT-GROUP OBJECTS { unitCurrent, unitVoltage, unitActivePower, unitApparentPower, unitCpuTemp, unitCircuitBreak0State, unitCircuitBreak1State, unitCircuitBreak2State, unitCircuitBreak0Current, unitCircuitBreak1Current, unitCircuitBreak2Current, unitVoltageLowerWarning, unitVoltageUpperWarning, unitVoltageLowerCritical, unitVoltageUpperCritical, unitCurrentUpperWarning, unitCurrentUpperCritical, unitTempLowerWarning, unitTempUpperWarning, unitTempLowerCritical, unitTempUpperCritical } STATUS current DESCRIPTION "A collection of objects providing unit level sensor readings." ::= { groups 4 } externalTemperatureGroup OBJECT-GROUP OBJECTS { tempSensorCount, tempSensorLabel, temperature, tempLowerWarning, tempUpperWarning, tempLowerCritical, tempUpperCritical, tempLowerWarningReset, tempUpperWarningReset, tempLowerCriticalReset, tempUpperCriticalReset } STATUS current DESCRIPTION "A collection of objects providing external temperature sensor readings and threshold settings." ::= { groups 6 } externalHumidityGroup OBJECT-GROUP OBJECTS { humiditySensorCount, humiditySensorLabel, humidity, humidityLowerWarning, humidityUpperWarning, humidityLowerCritical, humidityUpperCritical, humidityLowerWarningReset, humidityUpperWarningReset, humidityLowerCriticalReset, humidityUpperCriticalReset } STATUS current DESCRIPTION "A collection of objects providing external humidity sensor readings and threshold settings." ::= { groups 7 } trapsGroup NOTIFICATION-GROUP NOTIFICATIONS { rebootStarted, rebootCompleted, userLogin, userLogout, userAuthenticationFailure, userSessionTimeout, userAdded, userModified, userDeleted, groupAdded, groupModified, groupDeleted, deviceUpdateStarted, userBlocked, powerControl, userPasswordChanged, passwordSettingsChanged, firmwareFileDiscarded, firmwareValidationFailed, securityViolation, logFileCleared, thresholdAlarm, outletGroupingConnectivityLost } STATUS current DESCRIPTION "A collection of traps." ::= { groups 9 } -- Textual Conventions MilliAmps ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with current sensors. If the underlying hardware sensor indicates 1 amp, then the SNMP agent will report a value of 1000 milliamps. The value is scaled in this manner as a way to deal with floating point types that SNMP does not currently support." SYNTAX Unsigned32 MilliVolts ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 1 volts, then the SNMP agent will report a value of 1000 millivolts. The value is scaled in this manner as a way to deal with floating point types that SNMP does not currently support." SYNTAX Unsigned32 Watts ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with active power sensors. If the underlying hardware sensor indicates 1 watt, then the SNMP agent will report a value of 1 watt. No scaling is performed for this type." SYNTAX Unsigned32 VoltAmps ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with apparent power sensors. If the underlying hardware sensor indicates 1 volt-amp, then the SNMP agent will report a value of 1 volt-amp. No scaling is performed for this type." SYNTAX Unsigned32 DegreesCelsius ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with temperature sensors. If the underlying hardware sensor indicates 1 degree Celsius, then the SNMP agent will report a value of 1 degree Celsius. No scaling is performed for this type." SYNTAX Unsigned32 Hertz ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with frequency sensors. If the underlying hardware sensor indicates 1 Hertz, then the SNMP agent will report a value of 1 Hertz. No scaling is performed for this type." SYNTAX Unsigned32 RelativeHumidity ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with humidity sensors. Relative humidity is expressed as percentage and is defined as the ratio of the partial pressure of water vapor in a gaseous mixture of air and water vapor to the saturated vapor pressure of water at a given temperature." SYNTAX Unsigned32 (0..100) PowerFactorPercentage ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "Data type for reporting sensor readings and thresholds associated with power factor sensors. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. A PowerFactorPercentage value is calculated by taking this ratio and multiplying by 100. The power factor is used to indicate how efficiently a particular load is utilizing energy." SYNTAX Unsigned32 (0..100) SensorTypeEnumeration ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "The types a sensor can be." SYNTAX INTEGER { outletCurrent(0), outletMaxCurrent(1), outletVoltage(2), outletActivePower(3), outletApparentPower(4), outletMaxActivePower(5), outletAverageActivePower(6), outletPowerFactor(7), powerBranchVoltage(200), powerBranchFrequency(201), powerBranchTemperature(202), powerBranchCurrent(203), environmentalTemp1(300), environmentalTemp2(301), environmentalTemp3(302), environmentalTemp4(303), environmentalTemp5(304), environmentalTemp6(305), environmentalTemp7(306), environmentalTemp8(307), environmentalHumidity1(400), environmentalHumidity2(401), environmentalHumidity3(402), environmentalHumidity4(403), environmentalHumidity5(404), environmentalHumidity6(405), environmentalHumidity7(406), environmentalHumidity8(407), unitRmsCurrent(500), unitMaxRmsCurrent(501), unitVoltage(502), unitCpuTemp(503), unitActivePower(504), unitApparentPower(505), unitCircuitBreak0State(550), unitCircuitBreak1State(551), unitCircuitBreak2State(552), unitCircuitBreak0Current(600), unitCircuitBreak1Current(601), unitCircuitBreak2Current(602) } SensorStateEnumeration ::= TEXTUAL-CONVENTION STATUS current DESCRIPTION "The states a sensor can be in." SYNTAX INTEGER { unavailable(-1), ok(0), belowLowerWarning(1), aboveUpperWarning(2), belowLowerCritical(3), aboveUpperCritical(4) } -- the info group firmwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The current firmware version" ::= { info 1 } serialNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The serial number." ::= { info 2 } ipAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-only STATUS current DESCRIPTION "The current IP address. A value of 0.0.0.0 indicates an error or an unset option." ::= { info 3 } netmask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-only STATUS current DESCRIPTION "The current Netmask. A value of 0.0.0.0 indicates an error or an unset option." ::= { info 4 } gateway OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-only STATUS current DESCRIPTION "The current Gateway. A value of 0.0.0.0 indicates an error or an unset option." ::= { info 5 } mac OBJECT-TYPE SYNTAX MacAddress MAX-ACCESS read-only STATUS current DESCRIPTION "The current MAC address." ::= { info 6 } hardwareRev OBJECT-TYPE SYNTAX Integer32(0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "The hardware revision number." ::= { info 7 } userName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The login of a user." ::= { info 10 } objectName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The model type of the device" ::= { info 12 } objectInstance OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The device name" ::= { info 13} targetUser OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The user record being operated on" ::= { info 14} groupName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The group record being operated on" ::= { info 15 } imageVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The version of the Upgrade image" ::= { info 18 } sensorDescr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Sensor description indicating which sensor experienced a threshold exceeded event. When applicable the description will indicate the sensor number." ::= { info 19 } thresholdDescr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Threshold description indicating which configured threshold has been triggered (or cleared)." ::= { info 20 } thresholdSeverity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared)." ::= { info 21 } thresholdEventType OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "String (triggered, cleared) indicating if the threshold event indicates that a configured threshold has been triggered or cleared." ::= { info 22 } status OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The success status of an operation" ::= { info 23 } slaveIpAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-only STATUS current DESCRIPTION "In a shepherding configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error or an unset option." ::= { info 24} -- the outlets group -- Implementation for managing the outlets outletCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of outlets (regardless of their current state) present on this pdu." ::= { outlets 1 } -- the outlets table -- The outlets table contains information on the pdu's outlets. -- It further provides functions for managing them. outletTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of outlet entries. The number of entries is given by the value of outletCount." ::= { outlets 2 } outletEntry OBJECT-TYPE SYNTAX OutletEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "An outlet entry containing objects at the for a particular outlet." INDEX { outletIndex } ::= { outletTable 1 } OutletEntryStruct ::= SEQUENCE { outletIndex Integer32, outletLabel DisplayString, outletOperationalState INTEGER, outletCurrent MilliAmps, outletMaxCurrent MilliAmps, outletVoltage MilliVolts, outletActivePower Watts, outletApparentPower VoltAmps, outletPowerFactor PowerFactorPercentage, outletCurrentUpperWarning MilliAmps, outletCurrentUpperCritical MilliAmps } outletIndex OBJECT-TYPE SYNTAX Integer32(0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for each outlet. Its value ranges between 1 and the value of outletCount." ::= { outletEntry 1 } outletLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A textual string containing information about the outlet." ::= { outletEntry 2 } outletOperationalState OBJECT-TYPE SYNTAX INTEGER { error(-1), off(0), on(1), cycling(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "A value for each outlet which describes the operational state of the outlet. It is also used to set the operational state of the outlet" ::= { outletEntry 3 } outletCurrent OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)" ::= { outletEntry 4 } outletMaxCurrent OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the max. current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp)" ::= { outletEntry 5 } outletVoltage OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt)" ::= { outletEntry 6 } outletActivePower OBJECT-TYPE SYNTAX Watts MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the active power sensor attached to the outlet. This value is reported in Watts." ::= { outletEntry 7 } outletApparentPower OBJECT-TYPE SYNTAX VoltAmps MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the apparent power sensor attached to the outlet. This value is reported in Volt-Amps" ::= { outletEntry 8 } outletPowerFactor OBJECT-TYPE SYNTAX PowerFactorPercentage MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100%." ::= { outletEntry 9 } outletCurrentUpperWarning OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)" ::= { outletEntry 21 } outletCurrentUpperCritical OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)" ::= { outletEntry 23 } -- the unitReadings group -- The unitReadings group contains sensor reading values -- for the PDU unit as a whole unitCurrent OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's current sensor in millamps." ::= { unitReadings 1 } unitVoltage OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's voltage sensor in millivolts." ::= { unitReadings 2 } unitActivePower OBJECT-TYPE SYNTAX Watts MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's voltage sensor in volt-amps." ::= { unitReadings 3 } unitApparentPower OBJECT-TYPE SYNTAX Watts MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's voltage sensor in volt-amps." ::= { unitReadings 4 } unitCpuTemp OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's CPU temperature sensor in degrees Celsius." ::= { unitReadings 5 } unitCircuitBreak0State OBJECT-TYPE SYNTAX INTEGER { unavailable(-1), ok(0), tripped(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker state sensor 0." ::= { unitReadings 20 } unitCircuitBreak1State OBJECT-TYPE SYNTAX INTEGER { unavailable(-1), ok(0), tripped(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker state sensor 1." ::= { unitReadings 21 } unitCircuitBreak2State OBJECT-TYPE SYNTAX INTEGER { unavailable(-1), ok(0), tripped(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker state sensor 2." ::= { unitReadings 22 } unitCircuitBreak0Current OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker current sensor 0." ::= { unitReadings 40 } unitCircuitBreak1Current OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker current sensor 1." ::= { unitReadings 41 } unitCircuitBreak2Current OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value for the unit's circuit breaker current sensor 2." ::= { unitReadings 42 } unitVoltageLowerWarning OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) unit level voltage threshold." ::= { unitReadings 60 } unitVoltageLowerCritical OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical unit level voltage threshold." ::= { unitReadings 61 } unitVoltageUpperWarning OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) unit level voltage threshold." ::= { unitReadings 62 } unitVoltageUpperCritical OBJECT-TYPE SYNTAX MilliVolts MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical unit level voltage threshold." ::= { unitReadings 63 } unitCurrentUpperWarning OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) unit level current threshold." ::= { unitReadings 70 } unitCurrentUpperCritical OBJECT-TYPE SYNTAX MilliAmps MAX-ACCESS read-only STATUS current DESCRIPTION "The value of the upper critical unit level current threshold. NOTE: This particular threshold is NOT settable " ::= { unitReadings 71 } unitTempLowerWarning OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) unit level temperature threshold." ::= { unitReadings 80 } unitTempLowerCritical OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical unit level temperature threshold." ::= { unitReadings 81 } unitTempUpperWarning OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) unit level temperature threshold." ::= { unitReadings 82 } unitTempUpperCritical OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical unit level temperature threshold." ::= { unitReadings 83 } -- the externalTemperature group -- Implementation for managing external temperature sensors tempSensorCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of external temperature sensors (regardless of their current state) present on this pdu." ::= { environmental 1 } -- the temperature sensors table -- The tempSensorTable table contains information on the pdu's external temperature sensors. tempSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF TempSensorEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of temperature sensor entries. The number of entries is given by the value of tempSensorCount." ::= { environmental 2 } tempSensorEntry OBJECT-TYPE SYNTAX TempSensorEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "An entry containing sensor reading and threshold settings for a particular temperature sensor." INDEX { tempSensorIndex } ::= { tempSensorTable 1 } TempSensorEntryStruct ::= SEQUENCE { tempSensorIndex Integer32, tempSensorLabel DisplayString, temperature DegreesCelsius, tempLowerWarning DegreesCelsius, tempUpperWarning DegreesCelsius, tempLowerCritical DegreesCelsius, tempUpperCritical DegreesCelsius, tempLowerWarningReset DegreesCelsius, tempUpperWarningReset DegreesCelsius, tempLowerCriticalReset DegreesCelsius, tempUpperCriticalReset DegreesCelsius } tempSensorIndex OBJECT-TYPE SYNTAX Integer32(0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for each temperature sensor. Its value ranges between 1 and tempSensorCount." ::= { tempSensorEntry 1 } tempSensorLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A settable human-readable label for the external temperature sensor. One possible use for this label is to convey sensor location." ::= { tempSensorEntry 2 } temperature OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-only STATUS current DESCRIPTION "The value of the external temperature sensor reported in degrees celsius." ::= { tempSensorEntry 3 } tempLowerWarning OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) threshold." ::= { tempSensorEntry 4 } tempUpperWarning OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) threshold." ::= { tempSensorEntry 5 } tempLowerCritical OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical threshold." ::= { tempSensorEntry 6 } tempUpperCritical OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical threshold." ::= { tempSensorEntry 7 } tempLowerWarningReset OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) reset/hysteresis value." ::= { tempSensorEntry 8 } tempUpperWarningReset OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) reset/hysteresis value." ::= { tempSensorEntry 9 } tempLowerCriticalReset OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical reset/hysteresis value." ::= { tempSensorEntry 10 } tempUpperCriticalReset OBJECT-TYPE SYNTAX DegreesCelsius MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical reset/hysteresis value." ::= { tempSensorEntry 11 } -- the externalHumidity group -- Implementation for managing external humidity sensors humiditySensorCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number of external humidity sensors (regardless of their current state) present on this pdu." ::= { environmental 3 } -- the humidity sensors table -- The humiditySensorTable table contains information on the pdu's external humidity sensors. humiditySensorTable OBJECT-TYPE SYNTAX SEQUENCE OF HumiditySensorEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of humidity sensor entries. The number of entries is given by the value of humiditySensorCount." ::= { environmental 4 } humiditySensorEntry OBJECT-TYPE SYNTAX HumiditySensorEntryStruct MAX-ACCESS not-accessible STATUS current DESCRIPTION "An entry containing sensor reading and threshold settings for a particular humidity sensor." INDEX { humiditySensorIndex } ::= { humiditySensorTable 1 } HumiditySensorEntryStruct ::= SEQUENCE { humiditySensorIndex Integer32, humiditySensorLabel DisplayString, humidity RelativeHumidity, humidityLowerWarning RelativeHumidity, humidityUpperWarning RelativeHumidity, humidityLowerCritical RelativeHumidity, humidityUpperCritical RelativeHumidity, humidityLowerWarningReset RelativeHumidity, humidityUpperWarningReset RelativeHumidity, humidityLowerCriticalReset RelativeHumidity, humidityUpperCriticalReset RelativeHumidity } humiditySensorIndex OBJECT-TYPE SYNTAX Integer32(0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for each humidity sensor. Its value ranges between 1 and humiditySensorCount." ::= { humiditySensorEntry 1 } humiditySensorLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A settable human-readable label for the external humidity sensor. One possible use for this label is to convey sensor location." ::= { humiditySensorEntry 2 } humidity OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-only STATUS current DESCRIPTION "The value of the external humidity sensor reported as relative humidity (a percentage)." ::= { humiditySensorEntry 3 } humidityLowerWarning OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) threshold." ::= { humiditySensorEntry 4 } humidityUpperWarning OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) threshold." ::= { humiditySensorEntry 5 } humidityLowerCritical OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical threshold." ::= { humiditySensorEntry 6 } humidityUpperCritical OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical threshold." ::= { humiditySensorEntry 7 } humidityLowerWarningReset OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower warning (non-critical) reset/hysteresis value." ::= { humiditySensorEntry 8 } humidityUpperWarningReset OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper warning (non-critical) reset/hysteresis value." ::= { humiditySensorEntry 9 } humidityLowerCriticalReset OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the lower critical reset/hysteresis value." ::= { humiditySensorEntry 10 } humidityUpperCriticalReset OBJECT-TYPE SYNTAX RelativeHumidity MAX-ACCESS read-write STATUS current DESCRIPTION "The value of the upper critical reset/hysteresis value." ::= { humiditySensorEntry 11 } -- Start the traps rebootStarted NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName } STATUS current DESCRIPTION "The reboot process has started" ::= { traps 1 } rebootCompleted NOTIFICATION-TYPE OBJECTS { objectName, objectInstance } STATUS current DESCRIPTION "The reboot process is complete" ::= { traps 2 } userLogin NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "A user logged in" ::= { traps 3 } userLogout NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "A user logged out" ::= { traps 4 } userAuthenticationFailure NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "A user authentication attempt failed" ::= { traps 5 } userSessionTimeout NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "A user timed out from the device" ::= { traps 8 } userAdded NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, targetUser } STATUS current DESCRIPTION "A user was added to the system" ::= { traps 11 } userModified NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, targetUser } STATUS current DESCRIPTION "A user account was modified" ::= { traps 12 } userDeleted NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, targetUser } STATUS current DESCRIPTION "A user was deleted from the system" ::= { traps 13 } groupAdded NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, groupName } STATUS current DESCRIPTION "A group was added to the system" ::= { traps 14 } groupModified NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, groupName } STATUS current DESCRIPTION "A group was modified" ::= { traps 15 } groupDeleted NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, groupName } STATUS current DESCRIPTION "A group was deleted from the system" ::= { traps 16 } deviceUpdateStarted NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress, imageVersion } STATUS current DESCRIPTION "The device update has started" ::= { traps 20 } userBlocked NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "A blocked user tried to log in" ::= { traps 22 } powerControl NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress, outletLabel, outletOperationalState } STATUS current DESCRIPTION "An outlet has been switched" ::= { traps 23 } userPasswordChanged NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, targetUser, ipAddress } STATUS current DESCRIPTION "A user password was changed" ::= { traps 24 } passwordSettingsChanged NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, status } STATUS current DESCRIPTION "Strong password settings changed " ::= { traps 28 } -- Start new event to support RP products firmwareFileDiscarded NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName } STATUS current DESCRIPTION "A firmware file discarded " ::= { traps 36 } firmwareValidationFailed NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName } STATUS current DESCRIPTION "A firmware validation failed " ::= { traps 38 } securityViolation NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName, ipAddress } STATUS current DESCRIPTION "Security violation." ::= { traps 39 } logFileCleared NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, userName } STATUS current DESCRIPTION "The log file has been cleared." ::= { traps 41 } --sensor threshold exceeded traps thresholdAlarm NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, ipAddress, sensorDescr, thresholdDescr, thresholdSeverity, thresholdEventType } STATUS current DESCRIPTION "Configured sensor theshold event. The 'thresholdType' variable will indicate whether or not the threshold triggered or cleared" ::= { traps 45 } -- Shepherd Application traps outletGroupingConnectivityLost NOTIFICATION-TYPE OBJECTS { objectName, objectInstance, ipAddress, slaveIpAddress } STATUS current DESCRIPTION "Master PDU lost contact with the slave PDU in an outlet grouping configuration." ::= { traps 50 } END