LIEBERT-GP-ENVIRONMENTAL-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, Integer32 FROM SNMPv2-SMI DisplayString FROM SNMPv2-TC lgpEnvironmental, liebertEnvironmentalModuleReg FROM LIEBERT-GP-REGISTRATION-MIB ; -- ============================================================================= -- Module Identification and Registration -- ============================================================================= liebertGlobalProductsEnvironmentalModule MODULE-IDENTITY LAST-UPDATED "201507210000Z" ORGANIZATION "Liebert Corporation" CONTACT-INFO "Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge" DESCRIPTION "The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification." REVISION "200811170000Z" DESCRIPTION "Added support for NXL unit." REVISION "200807020000Z" DESCRIPTION "SMIv2 changes (INTEGER to Integer32. Corrected spelling errors." REVISION "200801100000Z" DESCRIPTION "Modified contact email address." REVISION "200705290000Z" DESCRIPTION "Added support for XDF Unit." REVISION "200608150000Z" DESCRIPTION "Added support for HP release." REVISION "200602220000Z" DESCRIPTION "Added support for Liebert DS Unit." ::= { liebertEnvironmentalModuleReg 1 } -- ============================================================================= -- lgpEnvironmental - Liebert Environmental Registrations -- ============================================================================= lgpEnvTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert temperature object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Temperature Group." ::= { lgpEnvironmental 1 } lgpEnvHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert humidity object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Humidity Group." ::= { lgpEnvironmental 2 } lgpEnvState OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental state object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental State Group." ::= { lgpEnvironmental 3 } lgpEnvConfig OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental configuration object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Configuration Group." ::= { lgpEnvironmental 4 } lgpEnvControl OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental control object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Control Group." ::= { lgpEnvironmental 5 } lgpEnvStatistics OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental statistic object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Statistics Group." ::= { lgpEnvironmental 6 } lgpEnvPoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental point object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental point Group." ::= { lgpEnvironmental 7 } lgpEnvUnits OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental unit object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental units Group." ::= { lgpEnvironmental 8 } lgpEnvRemoteSensors OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert environmental remote sensor object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Remote Sensor Group." ::= { lgpEnvironmental 9 } -- ============================================================================= -- lgpEnvTemperature - Liebert Environmental Temperature Group -- ============================================================================= lgpEnvTemperatureWellKnown OBJECT-IDENTITY STATUS current DESCRIPTION "Liebert well known temperature objects are identified by OIDs that reside in this sub-tree." ::= { lgpEnvTemperature 1 } lgpEnvTemperatureFahrenheit OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Fahrenheit Temperature Group." ::= { lgpEnvTemperature 2 } lgpEnvTemperatureCelsius OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Celsius Temperature Group." ::= { lgpEnvTemperature 3 } lgpEnvTemperatureControlMode OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control." ::= { lgpEnvTemperature 4 } -- ============================================================================= -- lgpEnvHumidity - Liebert Environmental Humidity Group -- ============================================================================= lgpEnvHumidityWellKnown OBJECT-IDENTITY STATUS current DESCRIPTION "Liebert well known humidity objects are defined by OIDs that reside in this sub-tree." ::= { lgpEnvHumidity 1 } lgpEnvHumidityRelative OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains OIDs that are used to control and monitor relative humidity." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert Environmental Relative Humidity Group." ::= { lgpEnvHumidity 2 } -- ============================================================================= -- lgpEnvState - Liebert Environmental State Group -- ============================================================================= lgpEnvStateSystem OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), standby(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the system." ::= { lgpEnvState 1 } lgpEnvStateCooling OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the cooling subsystem." ::= { lgpEnvState 2 } lgpEnvStateHeating OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the heating subsystem." ::= { lgpEnvState 3 } lgpEnvStateHumidifying OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the humidifier subsystem." ::= { lgpEnvState 4 } lgpEnvStateDehumidifying OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the dehumidifier subsystem" ::= { lgpEnvState 5 } lgpEnvStateEconoCycle OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the Econ-o-cycle subsystem." ::= { lgpEnvState 6 } lgpEnvStateFan OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the system fan." ::= { lgpEnvState 7 } lgpEnvStateGeneralAlarmOutput OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the general alarm output. This indicates if an alarm is active in the system." ::= { lgpEnvState 8 } lgpEnvStateCoolingCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the cooling capacity presently in use." ::= { lgpEnvState 9 } lgpEnvStateHeatingCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the heating capacity presently in use." ::= { lgpEnvState 10 } lgpEnvStateAudibleAlarm OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the audible alarm output." ::= { lgpEnvState 11 } lgpEnvStateCoolingUnits OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains OIDs that are used to indicate the status of cooling units." ::= { lgpEnvState 12 } lgpEnvStateCoolingUnit1 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of cooling unit 1." ::= { lgpEnvStateCoolingUnits 2 } lgpEnvStateCoolingUnit2 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of cooling unit 2." ::= { lgpEnvStateCoolingUnits 3 } lgpEnvStateCoolingUnit3 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of cooling unit 3." ::= { lgpEnvStateCoolingUnits 4 } lgpEnvStateCoolingUnit4 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of cooling unit 4." ::= { lgpEnvStateCoolingUnits 5 } lgpEnvStateHeatingUnits OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains OIDs that are used to indicate the status of heating units." ::= { lgpEnvState 13 } lgpEnvStateHeatingUnit1 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of heating unit 1." ::= { lgpEnvStateHeatingUnits 2 } lgpEnvStateHeatingUnit2 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of heating unit 2." ::= { lgpEnvStateHeatingUnits 3 } lgpEnvStateHeatingUnit3 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of heating unit 3." ::= { lgpEnvStateHeatingUnits 4 } lgpEnvStateHeatingUnit4 OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of heating unit 4." ::= { lgpEnvStateHeatingUnits 5 } lgpEnvStateOperatingReason OBJECT-TYPE SYNTAX INTEGER { none(1), localUser(2), alarm(3), schedule(4), remoteUser(5), externalDevice(6), localDisplay(7) } MAX-ACCESS read-only STATUS current DESCRIPTION "The reason for the current operating state of the system." ::= { lgpEnvState 14 } lgpEnvStateOperatingMode OBJECT-TYPE SYNTAX INTEGER { auto(1), manual(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present operating mode of the system." ::= { lgpEnvState 15 } lgpEnvStateFanCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the fan capacity presently in use." ::= { lgpEnvState 16 } lgpEnvStateFreeCoolingCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the free cooling capacity presently in use." ::= { lgpEnvState 17 } lgpEnvStateDehumidifyingCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the dehumidifying capacity presently in use." ::= { lgpEnvState 18 } lgpEnvStateHumidifyingCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percentage of the humidifying capacity presently in use." ::= { lgpEnvState 19 } lgpEnvStateFreeCooling OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), start(3), unavailable(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable." ::= { lgpEnvState 20 } lgpEnvStateElectricHeater OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of the electric heaters." ::= { lgpEnvState 21 } lgpEnvStateHotWater OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The present state of hot water system." ::= { lgpEnvState 22 } lgpEnvStateOperatingEfficiency OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The ratio of cooling energy provided to the amount of total energy being used." ::= { lgpEnvState 23 } lgpEnvComponentStateTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvComponentStateEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored." ::= { lgpEnvState 50 } lgpEnvComponentStateEntry OBJECT-TYPE SYNTAX LgpEnvComponentStateEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'." INDEX { lgpEnvComponentStateIndex } ::= { lgpEnvComponentStateTable 1 } LgpEnvComponentStateEntry ::= SEQUENCE { lgpEnvComponentStateIndex Unsigned32, lgpEnvComponentStateDescr OBJECT IDENTIFIER, lgpEnvComponentState INTEGER } lgpEnvComponentStateIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the nth element of the table." ::= { lgpEnvComponentStateEntry 1 } lgpEnvComponentStateDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table." ::= { lgpEnvComponentStateEntry 2 } lgpEnvComponentState OBJECT-TYPE SYNTAX INTEGER { not-specified(0), on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "not-specified The state of the component is unknown. on The component is on. off The component is off." ::= { lgpEnvComponentStateEntry 3 } lgpEnvValveTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvValveEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored." ::= { lgpEnvState 70 } lgpEnvValveEntry OBJECT-TYPE SYNTAX LgpEnvValveEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'." INDEX { lgpEnvValveIndex } ::= { lgpEnvValveTable 1 } LgpEnvValveEntry ::= SEQUENCE { lgpEnvValveIndex Unsigned32, lgpEnvValveDescr OBJECT IDENTIFIER, lgpEnvValveState INTEGER, lgpEnvValvePositionTenths Unsigned32 } lgpEnvValveIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the nth element of the table." ::= { lgpEnvValveEntry 1 } lgpEnvValveDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table." ::= { lgpEnvValveEntry 2 } lgpEnvValveState OBJECT-TYPE SYNTAX INTEGER { not-specified(0), open(1), closed(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "not-specified The state of the component is unknown. open The valve is open. off The valve is closed." ::= { lgpEnvValveEntry 3 } lgpEnvValvePositionTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS ".1 percent" MAX-ACCESS read-only STATUS current DESCRIPTION "This gives a value describing the position of the valve." ::= { lgpEnvValveEntry 20 } -- ============================================================================= -- lgpEnvConfig - Liebert Environmental Configuration Group -- ============================================================================= lgpEnvConfigReheatLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If locked-out the reheats will not operate even if controller calls for its operation." ::= { lgpEnvConfig 1 } lgpEnvConfigHumLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If locked-out the humidifier will not operate even if controller calls for its operation." ::= { lgpEnvConfig 2 } lgpEnvConfigRestartDelay OBJECT-TYPE SYNTAX Unsigned32 UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart." ::= { lgpEnvConfig 4 } lgpEnvConfigRemoteShutdown OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing." ::= { lgpEnvConfig 7 } lgpEnvConfigCoolingServiceInterval OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0." ::= { lgpEnvConfig 8 } lgpEnvConfigHumidifierServiceInterval OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0." ::= { lgpEnvConfig 9 } lgpEnvConfigFilterServiceInterval OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0." ::= { lgpEnvConfig 10 } lgpEnvConfigSleepModeDeadbandRangeDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation." ::= { lgpEnvConfig 11 } lgpEnvConfigSleepModeDeadbandRangeDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation." ::= { lgpEnvConfig 12 } lgpEnvConfigSupplyTempLowLimitDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The minimum allowable supply temperature." ::= { lgpEnvConfig 13 } lgpEnvConfigSupplyTempLowLimitDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The minimum allowable supply temperature." ::= { lgpEnvConfig 14 } lgpEnvConfigTemperatureIntegTime OBJECT-TYPE SYNTAX Integer32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "The value used as the integration factor in the proportional integral derivative (PID) temperature calculation." ::= { lgpEnvConfig 15 } lgpEnvConfigLocalTemperatureUnit OBJECT-TYPE SYNTAX INTEGER { degC(1), degF(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The local temperature unit of the system." ::= { lgpEnvConfig 16 } lgpEnvConfigSleepMode OBJECT-TYPE SYNTAX INTEGER { enabled(1), disabled(2), auto(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges." ::= { lgpEnvConfig 17 } lgpEnvConfigHumidityIntegTime OBJECT-TYPE SYNTAX Integer32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "The value used as the integration factor in the proportional integral derivative (PID) humidity calculation." ::= { lgpEnvConfig 18 } lgpEnvConfigFreecoolingDeltaDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling." ::= { lgpEnvConfig 19 } lgpEnvConfigFreecoolingDeltaDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling." ::= { lgpEnvConfig 20 } lgpEnvConfigSupplyTempLowLimit OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable the supply air low temperature limit." ::= { lgpEnvConfig 21 } lgpEnvConfigSensorEventsStandard OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable the standard sensor events." ::= { lgpEnvConfig 22 } lgpEnvConfigSensorEvents1 OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable sensor 1 events." ::= { lgpEnvConfig 23 } lgpEnvConfigSleepModeDeadbandRange OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm." ::= { lgpEnvConfig 24 } lgpEnvConfigAutoConfiguration OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters." ::= { lgpEnvConfig 25 } lgpEnvConfigDeltaGlycolType OBJECT-TYPE SYNTAX INTEGER { disabled(1), contact(2), value(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated." ::= { lgpEnvConfig 26 } lgpEnvConfigChillWaterControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system configuration parameter to enable or disable the minimum chill water temperature control." ::= { lgpEnvConfig 27 } lgpEnvConfigInfaredFlushRate OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation." ::= { lgpEnvConfig 28 } lgpEnvConfigHumidityControl OBJECT-TYPE SYNTAX INTEGER { relative(1), compensated(2), predictive(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The present configured state of the automatic humidity compensation algorithm." ::= { lgpEnvConfig 29 } lgpEnvConfigCompressorLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation." ::= { lgpEnvConfig 30 } lgpEnvConfigReheatAndHumidifierLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation." ::= { lgpEnvConfig 31 } -- ----------------------------------------------------------------------------- -- Operational Time Table -- ----------------------------------------------------------------------------- lgpEnvOperationalTimeTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvOperationalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvConfig 32 } lgpEnvOperationalTimeEntry OBJECT-TYPE SYNTAX LgpEnvOperationalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'." REFERENCE "The 'lgpEnvOperationTimePoint' in this table corresponds to what the operation time applies to." INDEX { lgpEnvOperationTimeIndex } ::= { lgpEnvOperationalTimeTable 1 } LgpEnvOperationalTimeEntry ::= SEQUENCE { lgpEnvOperationTimeIndex Unsigned32, lgpEnvOperationTimePoint OBJECT IDENTIFIER, lgpEnvOperationTimeSubID Integer32, lgpEnvOperationTimeUnit OBJECT IDENTIFIER, lgpEnvOperationTimeValue Integer32, lgpEnvOperationTimeHighWarning Integer32 } lgpEnvOperationTimeIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the nth element of the table." ::= { lgpEnvOperationalTimeEntry 1 } lgpEnvOperationTimePoint OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "An OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc." REFERENCE "The object identifiers in this column can be found in the sub-tree 'lgpEnvWellKnownPoints' and correspond to the entry in the table 'lgpEnvOperationalTimeTable'." ::= { lgpEnvOperationalTimeEntry 2 } lgpEnvOperationTimeSubID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2." ::= { lgpEnvOperationalTimeEntry 3 } lgpEnvOperationTimeUnit OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "An OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc." REFERENCE "The object identifiers in this column can be found in the sub-tree 'lgpEnvWellKnownUnits' and correspond to the entry in the table lgpEnvOperationalTimeTable." ::= { lgpEnvOperationalTimeEntry 4 } lgpEnvOperationTimeValue OBJECT-TYPE SYNTAX Integer32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "The actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them." ::= { lgpEnvOperationalTimeEntry 5 } lgpEnvOperationTimeHighWarning OBJECT-TYPE SYNTAX Integer32 UNITS "hours" MAX-ACCESS read-write STATUS current DESCRIPTION "The high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them." ::= { lgpEnvOperationalTimeEntry 6 } lgpEnvConfigTempControlAlgorithm OBJECT-TYPE SYNTAX INTEGER { pi(1), pid(2), intelligent(3), proportional(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Selects the algorithm for controlling temperature." ::= { lgpEnvConfig 33 } lgpEnvConfigFanSpeedMode OBJECT-TYPE SYNTAX INTEGER { manual(1), auto(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Changes the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity." ::= { lgpEnvConfig 34 } lgpEnvConfigFanSpeedCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-write STATUS current DESCRIPTION "Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit)." ::= { lgpEnvConfig 35 } lgpEnvConfigBmsResetTimer OBJECT-TYPE SYNTAX Unsigned32 UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit)." ::= { lgpEnvConfig 36 } lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used." ::= { lgpEnvConfig 37 } lgpEnvConfigDisableSensorOffsetDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used." ::= { lgpEnvConfig 38 } lgpEnvConfigCabinetSensorAlarms OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable or Disable Cabinet Sensor Alarms." ::= { lgpEnvConfig 39 } lgpEnvConfigAirTemperatureControlSensor OBJECT-TYPE SYNTAX INTEGER { supply(1), remote(2), return(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Sensor from which air temperature measurements will be used for cooling and heating control." ::= { lgpEnvConfig 42 } lgpEnvConfigFanSpeedControlSensor OBJECT-TYPE SYNTAX INTEGER { supply(1), remote(2), return(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Sensor from which air temperature measurements will be used for fan speed control." ::= { lgpEnvConfig 43 } lgpEnvConfigMinFanSpeed OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-write STATUS current DESCRIPTION "Sets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'." ::= { lgpEnvConfig 44 } lgpEnvConfigMaxFanSpeed OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-write STATUS current DESCRIPTION "Sets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'." ::= { lgpEnvConfig 45 } lgpEnvConfigFanSpeedPropBandDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled." ::= { lgpEnvConfig 46 } lgpEnvConfigFanSpeedPropBandDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled." ::= { lgpEnvConfig 47 } -- ============================================================================= -- lgpEnvControl - Liebert Environmental Control Group -- ============================================================================= lgpEnvControlShutdownAfterDelay OBJECT-TYPE SYNTAX Integer32 (-1..2147483647) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Setting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect." ::= { lgpEnvControl 1 } lgpEnvControlStartupAfterDelay OBJECT-TYPE SYNTAX Integer32 (-1..2147483647) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Setting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted." ::= { lgpEnvControl 2 } lgpEnvSleepIntervalTimeTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvSleepIntervalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvControl 3 } lgpEnvSleepIntervalTimeEntry OBJECT-TYPE SYNTAX LgpEnvSleepIntervalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'." INDEX { lgpEnvSleepTimeIndex } ::= { lgpEnvSleepIntervalTimeTable 1 } LgpEnvSleepIntervalTimeEntry ::= SEQUENCE { lgpEnvSleepTimeIndex Unsigned32, lgpEnvSleepTimeSubID Integer32, lgpEnvSleepTimeStartHour Integer32, lgpEnvSleepTimeStartMinute Integer32, lgpEnvSleepTimeStopHour Integer32, lgpEnvSleepTimeStopMinute Integer32 } lgpEnvSleepTimeIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'." ::= { lgpEnvSleepIntervalTimeEntry 1 } lgpEnvSleepTimeSubID OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2." ::= { lgpEnvSleepIntervalTimeEntry 2 } lgpEnvSleepTimeStartHour OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hour" MAX-ACCESS read-write STATUS current DESCRIPTION "This is the hours digit of the time when the system will be put online." ::= { lgpEnvSleepIntervalTimeEntry 3 } lgpEnvSleepTimeStartMinute OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minute" MAX-ACCESS read-write STATUS current DESCRIPTION "This is the minutes digit of the time when the system will be put online." ::= { lgpEnvSleepIntervalTimeEntry 4 } lgpEnvSleepTimeStopHour OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hour" MAX-ACCESS read-write STATUS current DESCRIPTION "This is the hours digit containing the time when the system will be taken offline." ::= { lgpEnvSleepIntervalTimeEntry 5 } lgpEnvSleepTimeStopMinute OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minute" MAX-ACCESS read-write STATUS current DESCRIPTION "This is the minutes digit containing the time when the system will be taken offline." ::= { lgpEnvSleepIntervalTimeEntry 6 } lgpEnvSleepDayTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvSleepDayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvControl 4 } lgpEnvSleepDayEntry OBJECT-TYPE SYNTAX LgpEnvSleepDayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'." INDEX { lgpEnvSleepDayIndex } ::= { lgpEnvSleepDayTable 1 } LgpEnvSleepDayEntry ::= SEQUENCE { lgpEnvSleepDayIndex Unsigned32, lgpEnvSleepDay INTEGER, lgpEnvSleepAllDayEnabled INTEGER } lgpEnvSleepDayIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the row of the table 'lgpEnvSleepDayTable'." ::= { lgpEnvSleepDayEntry 1 } lgpEnvSleepDay OBJECT-TYPE SYNTAX INTEGER { sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saturday(7) } MAX-ACCESS read-only STATUS current DESCRIPTION "This is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'." ::= { lgpEnvSleepDayEntry 2 } lgpEnvSleepAllDayEnabled OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'." ::= { lgpEnvSleepDayEntry 3 } -- ============================================================================= -- lgpEnvStatistics - Liebert Environmental Statistics Group -- ============================================================================= lgpEnvStatisticsComp1RunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 1 } lgpEnvStatisticsComp2RunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 2 } lgpEnvStatisticsFanRunHr OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION " Accumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 3 } lgpEnvStatisticsHumRunHr OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION " Accumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 4 } lgpEnvStatisticsReheat1RunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 7 } lgpEnvStatisticsReheat2RunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 8 } lgpEnvStatisticsReheat3RunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 9 } lgpEnvStatisticsCoolingModeHrs OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 10 } lgpEnvStatisticsHeatingModeHrs OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 11 } lgpEnvStatisticsHumidifyModeHrs OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 12 } lgpEnvStatisticsDehumidifyModeHrs OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 13 } lgpEnvStatisticsHotGasRunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 14 } lgpEnvStatisticsHotWaterRunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 15 } lgpEnvStatisticsFreeCoolRunHr OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'." ::= { lgpEnvStatistics 16 } lgpEnvStatisticsComp3RunHr OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION " Accumulated run hours of compressor 3." ::= { lgpEnvStatistics 17 } lgpEnvStatisticsComp4RunHr OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION " Accumulated run hours of compressor 4." ::= { lgpEnvStatistics 18 } -- ============================================================================= -- lgpEnvWellKnownPoints - Liebert "well-known" points -- ============================================================================= lgpEnvWellKnownPoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied." ::= { lgpEnvPoints 1 } lgpEnvFanPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known fan measurement point." ::= { lgpEnvWellKnownPoints 1 } lgpEnvCompressorPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known compressor measurement point." ::= { lgpEnvWellKnownPoints 2 } lgpEnvElectricHeaterPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known electric heater measurement point." ::= { lgpEnvWellKnownPoints 3 } lgpEnvChilledWaterPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known chilled water measurement point." ::= { lgpEnvWellKnownPoints 4 } lgpEnvHumidifierPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known humidifier measurement point." ::= { lgpEnvWellKnownPoints 5 } lgpEnvDehumidifierPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known dehumidifier measurement point." ::= { lgpEnvWellKnownPoints 6 } lgpEnvFreeCoolingPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known free-cooling measurement process." ::= { lgpEnvWellKnownPoints 7 } lgpEnvHotWaterPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known hot water measurement point." ::= { lgpEnvWellKnownPoints 8 } lgpEnvHotGasPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known hot gas measurement point." ::= { lgpEnvWellKnownPoints 9 } lgpEnvBatteryCabinetPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4" ::= { lgpEnvWellKnownPoints 10 } lgpEnvPumpPoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree identifies well-known pumps in the system." ::= { lgpEnvWellKnownPoints 11 } lgpEnvPump1Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents pump 1." ::= { lgpEnvPumpPoints 1 } lgpEnvPump2Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents pump 2." ::= { lgpEnvPumpPoints 2 } lgpEnvCompressorPoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree identifies well-known compressors in the system." ::= { lgpEnvWellKnownPoints 12 } lgpEnvCompressor1Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 1." ::= { lgpEnvCompressorPoints 1 } lgpEnvCompressor1APoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 1A." ::= { lgpEnvCompressor1Point 1 } lgpEnvCompressor1BPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 1B." ::= { lgpEnvCompressor1Point 2 } lgpEnvCompressor2Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 2." ::= { lgpEnvCompressorPoints 2 } lgpEnvCompressor2APoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 2A." ::= { lgpEnvCompressor2Point 1 } lgpEnvCompressor2BPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents compressor 2B." ::= { lgpEnvCompressor2Point 2 } lgpEnvValvePoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree identifies well-known valves in the system." ::= { lgpEnvWellKnownPoints 13 } lgpEnvHotGasValve1Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents hot gas valve 1." ::= { lgpEnvValvePoints 1 } lgpEnvHotGasValve2Point OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents hot gas valve 2." ::= { lgpEnvValvePoints 2 } lgpEnvRemoteSensorStatisticPoints OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree identifies well-known remote sensor statistics in the system." ::= { lgpEnvWellKnownPoints 14 } lgpEnvRemoteSensorMinimumPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents the minimum value for remote sensor readings." ::= { lgpEnvRemoteSensorStatisticPoints 1 } lgpEnvRemoteSensorMaximumPoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents the maximum value for remote sensor readings." ::= { lgpEnvRemoteSensorStatisticPoints 2 } lgpEnvRemoteSensorAveragePoint OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents the average value for remote sensor readings." ::= { lgpEnvRemoteSensorStatisticPoints 3 } -- ============================================================================= -- lgpEnvWellKnownUnits - Liebert "well-known" units -- ============================================================================= lgpEnvWellKnownUnits OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied." ::= { lgpEnvUnits 1 } lgpEnvHours OBJECT-IDENTITY STATUS current DESCRIPTION "This identifier represents well known time unit of hours." ::= { lgpEnvWellKnownUnits 1 } -- ============================================================================= -- lgpEnvTemperatureMeasurements - Liebert "well-known" temperature objects -- ============================================================================= lgpEnvControlTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement used as control feedback." ::= { lgpEnvTemperatureWellKnown 1 } lgpEnvReturnAirTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of return air." ::= { lgpEnvTemperatureWellKnown 2 } lgpEnvSupplyAirTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of supply air." ::= { lgpEnvTemperatureWellKnown 3 } lgpAmbientTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Ambient temperature measurement." ::= { lgpEnvTemperatureWellKnown 4 } lgpInverterTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of the inverter." ::= { lgpEnvTemperatureWellKnown 5 } lgpBatteryTempterature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of the battery." ::= { lgpEnvTemperatureWellKnown 6 } lgpAcDcConverterTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of the AC-to-DC Converter." ::= { lgpEnvTemperatureWellKnown 7 } lgpPfcTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of the power factor correction circuitry." ::= { lgpEnvTemperatureWellKnown 8 } lgpTransformerTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of the transformer." ::= { lgpEnvTemperatureWellKnown 9 } lgpLocalTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurement of local temperature sensor." ::= { lgpEnvTemperatureWellKnown 10 } lgpLocal1Temperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of Local Sensor 1." ::= { lgpLocalTemperature 1 } lgpLocal2Temperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of Local Sensor 2." ::= { lgpLocalTemperature 2 } lgpLocal3Temperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of Local Sensor 3." ::= { lgpLocalTemperature 3 } lgpDigitalScrollCompressorTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of a digital Scroll Compressor." ::= { lgpEnvTemperatureWellKnown 11 } lgpDigitalScrollCompressor1Temperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of a digital Scroll Compressor 1." ::= { lgpDigitalScrollCompressorTemperature 1 } lgpDigitalScrollCompressor2Temperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements of a digital Scroll Compressor 2." ::= { lgpDigitalScrollCompressorTemperature 2 } lgpChillWaterTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurements of a chill water system." ::= { lgpEnvTemperatureWellKnown 12 } lgpCoolantTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature measurements of an environmental system's coolant." ::= { lgpEnvTemperatureWellKnown 13 } lgpEnvEnclosureTemperatureSensors OBJECT-IDENTITY STATUS current DESCRIPTION "Enclosure temperature sensors" ::= { lgpEnvTemperatureWellKnown 14 } lgpEnvEnclosureTemperatureSensor1 OBJECT-IDENTITY STATUS current DESCRIPTION "Enclosure temperature sensor 1" ::= { lgpEnvEnclosureTemperatureSensors 1 } lgpEnvEnclosureTemperatureSensor2 OBJECT-IDENTITY STATUS current DESCRIPTION "Enclosure temperature sensor 2" ::= { lgpEnvEnclosureTemperatureSensors 2 } lgpEnvEnclosureTemperatureSensor3 OBJECT-IDENTITY STATUS current DESCRIPTION "Enclosure temperature sensor 3" ::= { lgpEnvEnclosureTemperatureSensors 3 } lgpEnvEnclosureTemperatureSensor4 OBJECT-IDENTITY STATUS current DESCRIPTION "Enclosure temperature sensor 4" ::= { lgpEnvEnclosureTemperatureSensors 4 } lgpEnvValueAmbientRoomTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature outside enclosure." ::= { lgpEnvTemperatureWellKnown 15 } lgpEnvDewPointTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The calculated temperature outside of the enclosure at which condensation is likely to occur." ::= { lgpEnvTemperatureWellKnown 16 } lgpEnvEnclosureTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature inside of enclosure." ::= { lgpEnvTemperatureWellKnown 17 } lgpEnvAdjustedTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors." ::= { lgpEnvTemperatureWellKnown 18 } lgpEnvExternalSensors OBJECT-IDENTITY STATUS current DESCRIPTION "External sensors to monitor environmental variables such as temperature and humidity" ::= { lgpEnvTemperatureWellKnown 19 } lgpEnvExternalAirSensorA OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements from external air sensor A." ::= { lgpEnvExternalSensors 1 } lgpEnvExternalAirSensorADewPoint OBJECT-IDENTITY STATUS current DESCRIPTION "Dewpoint temperature for External Air Sensor A." ::= { lgpEnvExternalSensors 2 } lgpEnvExternalAirSensorB OBJECT-IDENTITY STATUS current DESCRIPTION "Temperature and humidity measurements from external air sensor B." ::= { lgpEnvExternalSensors 3 } lgpEnvExternalAirSensorBDewPoint OBJECT-IDENTITY STATUS current DESCRIPTION "Dewpoint temperature for External Air Sensor B." ::= { lgpEnvExternalSensors 4 } lgpEnvSupplyFluidTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The current temperature of the fluid being supplied." ::= { lgpEnvTemperatureWellKnown 20 } lgpEnvSupplyRefrigerantTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The current temperature of the refrigerant being supplied." ::= { lgpEnvTemperatureWellKnown 21 } lgpEnvMinDesiredRoomAirTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "The minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling." ::= { lgpEnvTemperatureWellKnown 22 } lgpEnvDewPointTemperatures OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree identifies well-known dew point temperatures in the system." ::= { lgpEnvTemperatureWellKnown 23 } lgpEnvInletDewPointTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Dew point temperature measured at the inlet of the unit." ::= { lgpEnvDewPointTemperatures 1 } -- ============================================================================= -- lgpEnvTemperatureFahrenheit - Liebert Environmental Fahrenheit -- Temperature Group -- ============================================================================= lgpEnvTemperatureSettingDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius." ::= { lgpEnvTemperatureFahrenheit 1 } lgpEnvTemperatureToleranceDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius." ::= { lgpEnvTemperatureFahrenheit 2 } lgpEnvTemperatureTableDegF OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegF MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius." ::= { lgpEnvTemperatureFahrenheit 3 } lgpEnvTemperatureDeadbandRangeDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled." ::= { lgpEnvTemperatureFahrenheit 4 } lgpEnvTemperatureEntryDegF OBJECT-TYPE SYNTAX LgpEnvTemperatureEntryDegF MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'." INDEX { lgpEnvTemperatureIdDegF } ::= { lgpEnvTemperatureTableDegF 1 } LgpEnvTemperatureEntryDegF ::= SEQUENCE { lgpEnvTemperatureIdDegF Unsigned32, lgpEnvTemperatureDescrDegF OBJECT IDENTIFIER, lgpEnvTemperatureMeasurementDegF Integer32, lgpEnvTemperatureHighThresholdDegF Integer32, lgpEnvTemperatureLowThresholdDegF Integer32, lgpEnvTemperatureSetPointDegF Integer32, lgpEnvTemperatureDailyHighDegF Integer32, lgpEnvTemperatureDailyLowDegF Integer32, lgpEnvTempDailyHighTimeHourDegF Integer32, lgpEnvTempDailyHighTimeMinuteDegF Integer32, lgpEnvTempDailyHighTimeSecondDegF Integer32, lgpEnvTempDailyLowTimeHourDegF Integer32, lgpEnvTempDailyLowTimeMinuteDegF Integer32, lgpEnvTempDailyLowTimeSecondDegF Integer32, lgpEnvTemperatureMeasurementTenthsDegF Integer32, lgpEnvTemperatureHighThresholdTenthsDegF Integer32, lgpEnvTemperatureLowThresholdTenthsDegF Integer32, lgpEnvTemperatureSetPointTenthsDegF Integer32, lgpEnvTemperatureDeadBandTenthsDegF Integer32, lgpEnvTempHeatingPropBandTenthsDegF Integer32, lgpEnvTempCoolingPropBandTenthsDegF Integer32 } lgpEnvTemperatureIdDegF OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'." ::= { lgpEnvTemperatureEntryDegF 1 } lgpEnvTemperatureDescrDegF OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature." ::= { lgpEnvTemperatureEntryDegF 2 } lgpEnvTemperatureMeasurementDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured temperature value." ::= { lgpEnvTemperatureEntryDegF 3 } lgpEnvTemperatureHighThresholdDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegF 4 } lgpEnvTemperatureLowThresholdDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegF 5 } lgpEnvTemperatureSetPointDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration." ::= { lgpEnvTemperatureEntryDegF 6 } lgpEnvTemperatureDailyHighDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegF 7 } lgpEnvTemperatureDailyLowDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegF 8 } lgpEnvTempDailyHighTimeHourDegF OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegF 9 } lgpEnvTempDailyHighTimeMinuteDegF OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegF 10 } lgpEnvTempDailyHighTimeSecondDegF OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegF 11 } lgpEnvTempDailyLowTimeHourDegF OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegF 12 } lgpEnvTempDailyLowTimeMinuteDegF OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegF 13 } lgpEnvTempDailyLowTimeSecondDegF OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegF 14 } lgpEnvTemperatureMeasurementTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured temperature value." ::= { lgpEnvTemperatureEntryDegF 50 } lgpEnvTemperatureHighThresholdTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegF 51 } lgpEnvTemperatureLowThresholdTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegF 52 } lgpEnvTemperatureSetPointTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration." ::= { lgpEnvTemperatureEntryDegF 53 } lgpEnvTemperatureDeadBandTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur." ::= { lgpEnvTemperatureEntryDegF 60 } lgpEnvTempHeatingPropBandTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled." ::= { lgpEnvTemperatureEntryDegF 61 } lgpEnvTempCoolingPropBandTenthsDegF OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled." ::= { lgpEnvTemperatureEntryDegF 62 } -- ============================================================================= -- lgpEnvTemperatureCelsius - Liebert Environmental Celsius -- Temperature Group -- ============================================================================= lgpEnvTemperatureSettingDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit." ::= { lgpEnvTemperatureCelsius 1 } lgpEnvTemperatureToleranceDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit." ::= { lgpEnvTemperatureCelsius 2 } lgpEnvTemperatureTableDegC OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvTemperatureEntryDegC MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit." ::= { lgpEnvTemperatureCelsius 3 } lgpEnvTemperatureDeadbandRangeDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled." ::= { lgpEnvTemperatureCelsius 4 } lgpEnvTemperatureEntryDegC OBJECT-TYPE SYNTAX LgpEnvTemperatureEntryDegC MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'." INDEX { lgpEnvTemperatureIdDegC } ::= { lgpEnvTemperatureTableDegC 1 } LgpEnvTemperatureEntryDegC ::= SEQUENCE { lgpEnvTemperatureIdDegC Unsigned32, lgpEnvTemperatureDescrDegC OBJECT IDENTIFIER, lgpEnvTemperatureMeasurementDegC Integer32, lgpEnvTemperatureHighThresholdDegC Integer32, lgpEnvTemperatureLowThresholdDegC Integer32, lgpEnvTemperatureSetPointDegC Integer32, lgpEnvTemperatureDailyHighDegC Integer32, lgpEnvTemperatureDailyLowDegC Integer32, lgpEnvTempDailyHighTimeHourDegC Integer32, lgpEnvTempDailyHighTimeMinuteDegC Integer32, lgpEnvTempDailyHighTimeSecondDegC Integer32, lgpEnvTempDailyLowTimeHourDegC Integer32, lgpEnvTempDailyLowTimeMinuteDegC Integer32, lgpEnvTempDailyLowTimeSecondDegC Integer32, lgpEnvTemperatureMeasurementTenthsDegC Integer32, lgpEnvTemperatureHighThresholdTenthsDegC Integer32, lgpEnvTemperatureLowThresholdTenthsDegC Integer32, lgpEnvTemperatureSetPointTenthsDegC Integer32, lgpEnvTemperatureDeadBandTenthsDegC Integer32, lgpEnvTempHeatingPropBandTenthsDegC Integer32, lgpEnvTempCoolingPropBandTenthsDegC Integer32 } lgpEnvTemperatureIdDegC OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'." ::= { lgpEnvTemperatureEntryDegC 1 } lgpEnvTemperatureDescrDegC OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature." ::= { lgpEnvTemperatureEntryDegC 2 } lgpEnvTemperatureMeasurementDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured temperature value." ::= { lgpEnvTemperatureEntryDegC 3 } lgpEnvTemperatureHighThresholdDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegC 4 } lgpEnvTemperatureLowThresholdDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegC 5 } lgpEnvTemperatureSetPointDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration." ::= { lgpEnvTemperatureEntryDegC 6 } lgpEnvTemperatureDailyHighDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegC 7 } lgpEnvTemperatureDailyLowDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegC 8 } lgpEnvTempDailyHighTimeHourDegC OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegC 9 } lgpEnvTempDailyHighTimeMinuteDegC OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegC 10 } lgpEnvTempDailyHighTimeSecondDegC OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily high temperature measurement." ::= { lgpEnvTemperatureEntryDegC 11 } lgpEnvTempDailyLowTimeHourDegC OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegC 12 } lgpEnvTempDailyLowTimeMinuteDegC OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegC 13 } lgpEnvTempDailyLowTimeSecondDegC OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily low temperature measurement." ::= { lgpEnvTemperatureEntryDegC 14 } lgpEnvTemperatureMeasurementTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured temperature value." ::= { lgpEnvTemperatureEntryDegC 50 } lgpEnvTemperatureHighThresholdTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegC 51 } lgpEnvTemperatureLowThresholdTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification." ::= { lgpEnvTemperatureEntryDegC 52 } lgpEnvTemperatureSetPointTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration." ::= { lgpEnvTemperatureEntryDegC 53 } lgpEnvTemperatureDeadBandTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur." ::= { lgpEnvTemperatureEntryDegC 60 } lgpEnvTempHeatingPropBandTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled." ::= { lgpEnvTemperatureEntryDegC 61 } lgpEnvTempCoolingPropBandTenthsDegC OBJECT-TYPE SYNTAX Integer32 UNITS ".1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled." ::= { lgpEnvTemperatureEntryDegC 62 } -- ============================================================================= -- lgpEnvHumidityMeasurements - Liebert "well-known" Humidity objects -- ============================================================================= lgpEnvControlHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Humidity measurement used as control feedback." ::= { lgpEnvHumidityWellKnown 1 } lgpEnvReturnAirHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Humidity measurement of return air." ::= { lgpEnvHumidityWellKnown 2 } lgpEnvSupplyAirHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Humidity measurement of supply air." ::= { lgpEnvHumidityWellKnown 3 } lgpEnvValueAmbientHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Humidity outside enclosure." ::= { lgpEnvHumidityWellKnown 4 } -- ============================================================================= -- lgpEnvRelativeHumidity - Liebert Environmental Relative Humidity Group -- ============================================================================= lgpEnvHumiditySettingRel OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The humidity setting used to control the well known humidity point." ::= { lgpEnvHumidityRelative 1 } lgpEnvHumidityToleranceRel OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "Acceptable variance from lgpEnvHumiditySettingRel, without initiating a control action." ::= { lgpEnvHumidityRelative 2 } lgpEnvHumidityTableRel OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvHumidityEntryRel MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvHumidityRelative 3 } lgpEnvHumidityDeadbandRange OBJECT-TYPE SYNTAX Integer32 UNITS ".1 percent RH" MAX-ACCESS read-write STATUS current DESCRIPTION "The allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled." ::= { lgpEnvHumidityRelative 4 } lgpEnvHumidityEntryRel OBJECT-TYPE SYNTAX LgpEnvHumidityEntryRel MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'." INDEX { lgpEnvHumidityIdRel } ::= { lgpEnvHumidityTableRel 1 } LgpEnvHumidityEntryRel ::= SEQUENCE { lgpEnvHumidityIdRel Unsigned32, lgpEnvHumidityDescrRel OBJECT IDENTIFIER, lgpEnvHumidityMeasurementRel Integer32, lgpEnvHumidityHighThresholdRel Integer32, lgpEnvHumidityLowThresholdRel Integer32, lgpEnvHumiditySetPoint Integer32, lgpEnvHumidityDailyHigh Integer32, lgpEnvHumidityDailyLow Integer32, lgpEnvHumidityDailyHighTimeHour Integer32, lgpEnvHumidityDailyHighTimeMinute Integer32, lgpEnvHumidityDailyHighTimeSecond Integer32, lgpEnvHumidityDailyLowTimeHour Integer32, lgpEnvHumidityDailyLowTimeMinute Integer32, lgpEnvHumidityDailyLowTimeSecond Integer32, lgpEnvHumidityDeadBand Integer32, lgpEnvHumidifyPropBand Integer32, lgpEnvDehumidifyPropBand Integer32, lgpEnvHumidityMeasurementRelTenths Integer32, lgpEnvHumidityHighThresholdRelTenths Integer32, lgpEnvHumidityLowThresholdRelTenths Integer32 } lgpEnvHumidityIdRel OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'." ::= { lgpEnvHumidityEntryRel 1 } lgpEnvHumidityDescrRel OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "A reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity." ::= { lgpEnvHumidityEntryRel 2 } lgpEnvHumidityMeasurementRel OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured humidity value." ::= { lgpEnvHumidityEntryRel 3 } lgpEnvHumidityHighThresholdRel OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification." ::= { lgpEnvHumidityEntryRel 4 } lgpEnvHumidityLowThresholdRel OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification." ::= { lgpEnvHumidityEntryRel 5 } lgpEnvHumiditySetPoint OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration." ::= { lgpEnvHumidityEntryRel 6 } lgpEnvHumidityDailyHigh OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily high relative humidity measurement." ::= { lgpEnvHumidityEntryRel 7 } lgpEnvHumidityDailyLow OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "The daily low relative humidity measurement." ::= { lgpEnvHumidityEntryRel 8 } lgpEnvHumidityDailyHighTimeHour OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily high humidity measurement." ::= { lgpEnvHumidityEntryRel 9 } lgpEnvHumidityDailyHighTimeMinute OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily high humidity measurement." ::= { lgpEnvHumidityEntryRel 10 } lgpEnvHumidityDailyHighTimeSecond OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily high humidity measurement." ::= { lgpEnvHumidityEntryRel 11 } lgpEnvHumidityDailyLowTimeHour OBJECT-TYPE SYNTAX Integer32(0..23) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "The hours digit of the time corresponding to the daily low humidity measurement." ::= { lgpEnvHumidityEntryRel 12 } lgpEnvHumidityDailyLowTimeMinute OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "minutes" MAX-ACCESS read-only STATUS current DESCRIPTION "The minutes digit of the time corresponding to the daily low humidity measurement." ::= { lgpEnvHumidityEntryRel 13 } lgpEnvHumidityDailyLowTimeSecond OBJECT-TYPE SYNTAX Integer32(0..59) UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The seconds digit of the time corresponding to the daily low humidity measurement." ::= { lgpEnvHumidityEntryRel 14 } lgpEnvHumidityDeadBand OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur." ::= { lgpEnvHumidityEntryRel 15 } lgpEnvHumidifyPropBand OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled." ::= { lgpEnvHumidityEntryRel 16 } lgpEnvDehumidifyPropBand OBJECT-TYPE SYNTAX Integer32 UNITS "percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled." ::= { lgpEnvHumidityEntryRel 17 } lgpEnvHumidityMeasurementRelTenths OBJECT-TYPE SYNTAX Integer32 UNITS ".1 percent Relative Humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured humidity value." ::= { lgpEnvHumidityEntryRel 50 } lgpEnvHumidityHighThresholdRelTenths OBJECT-TYPE SYNTAX Integer32 UNITS ".1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification." ::= { lgpEnvHumidityEntryRel 51 } lgpEnvHumidityLowThresholdRelTenths OBJECT-TYPE SYNTAX Integer32 UNITS ".1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "The low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification." ::= { lgpEnvHumidityEntryRel 52 } -- ============================================================================= -- lgpEnvRemoteSensors - Liebert Environmental Remote Sensor Group -- ============================================================================= lgpEnvRemoteSensorCalc OBJECT-TYPE SYNTAX INTEGER { average(1), maximum(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control." ::= { lgpEnvRemoteSensors 1 } lgpEnvRemoteSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvRemoteSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit." ::= { lgpEnvRemoteSensors 10 } lgpEnvRemoteSensorEntry OBJECT-TYPE SYNTAX LgpEnvRemoteSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'." INDEX { lgpEnvRemoteSensorIndex } ::= { lgpEnvRemoteSensorTable 1 } LgpEnvRemoteSensorEntry ::= SEQUENCE { lgpEnvRemoteSensorIndex Unsigned32, lgpEnvRemoteSensorId Unsigned32, lgpEnvRemoteSensorMode Integer32, lgpEnvRemoteSensorUsrLabel DisplayString, lgpEnvRemoteSensorTempMeasurementDegF Integer32, lgpEnvRemoteSensorTempMeasurementDegC Integer32 } lgpEnvRemoteSensorIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the nth element of the table." ::= { lgpEnvRemoteSensorEntry 1 } lgpEnvRemoteSensorId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is the sensor number identifying the sensor." ::= { lgpEnvRemoteSensorEntry 2 } lgpEnvRemoteSensorMode OBJECT-TYPE SYNTAX INTEGER { disable(0), reference(1), control(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Function assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control." ::= { lgpEnvRemoteSensorEntry 3 } lgpEnvRemoteSensorUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned remote sensor label." ::= { lgpEnvRemoteSensorEntry 4 } lgpEnvRemoteSensorTempMeasurementDegF OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Fahrenheit." ::= { lgpEnvRemoteSensorEntry 5 } lgpEnvRemoteSensorTempMeasurementDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Celsius." ::= { lgpEnvRemoteSensorEntry 6 } END