LIEBERT-GP-PDU-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM SNMPv2-TC MODULE-IDENTITY, OBJECT-IDENTITY, OBJECT-TYPE, Integer32, Unsigned32 FROM SNMPv2-SMI lgpPdu, liebertPduModuleReg FROM LIEBERT-GP-REGISTRATION-MIB ; -- ============================================================================= -- Module Identification and Registration -- ============================================================================= liebertGlobalProductsPduModule MODULE-IDENTITY LAST-UPDATED "200807020000Z" ORGANIZATION "Liebert Corporation" CONTACT-INFO "Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Keith Sarbaugh" DESCRIPTION "The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification." REVISION "200807020000Z" DESCRIPTION "Initial Version" ::= { liebertPduModuleReg 1 } -- ============================================================================= -- lgpPdu - Liebert Power Distribution Registrations -- ============================================================================= -- ----------------------------------------------------------------------------- -- PDU Global Data and Control Information -- ----------------------------------------------------------------------------- lgpPduGlobalData OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains data and control associated with PDU's controlled by this agent. Data in this sub-tree will affect the behavior of all PDU's controlled by this agent." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 5 } lgpPduEntrySWOverTemperatureProtectionConfig OBJECT-TYPE SYNTAX INTEGER { local(0), array(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "This configures the scope of behavior for the PDU Software Over Temperature Protection feature. See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed. local (0) Only receptacles on the PDU with the alarming temperature sensor will be affected. array (1) All receptacles in the PDU array will be affected, regardless of which PDU the alarming temperature sensor is connected to. " ::= { lgpPduGlobalData 5 } lgpPduEntrySWOverTemperatureProtectionDelay OBJECT-TYPE SYNTAX Unsigned32 UNITS "Seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "This sets the delay for the PDU Software Over Temperature Protection feature. This value determines the amount of time to delay, after the high temperature alarm becomes active, before taking action on the enabled receptacles. If the high temperature alarm becomes inactive before the expiration of the delay time, no action will be taken on the enabled receptacles. See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed. " ::= { lgpPduGlobalData 10 } -- ----------------------------------------------------------------------------- -- PDU Group Information -- ----------------------------------------------------------------------------- lgpPduCluster OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about PDU clusters. Clusters are groups of PDU's under a single monitoring or control domain." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 10 } lgpPduGrpSysStatus OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This value represents a bit-field of the various operational states of the PDUs that are part of the cluster of PDUs being monitored by this agent. This value is the bit-wise logical OR of all of the 'lgpPduEntrySysStatus' columns in the 'lgpPduTable' which represents the combined statuses of all PDUs for this agent. Note the bit-position is given parenthetically next to the operational state in the description below. The bit position is big-endian (least significant digit is the right-most digit). The state is present in the PDU when the bit is on (value = 1). The value is a logical OR of all of the following potential states of each PDU in the cluster. normalOperation(1) One or more PDUs in the cluster are operating normally with no active warnings or alarms. startUp(2) One or more PDUs are in the startup state (initializing). Control and monitoring operations may be inhibited or unavailable while the PDU is in this state. This state will clear automatically when the PDU(s) are fully initialized and ready to accept control and monitoring commands. unknownNoSupport(4) The state of one or more PDUs are not known at this time or there is no support for this piece of information from 1 or more PDUs in the cluster/group. normalWithWarning(8) One or more PDUs are operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(16) One or more PDUs are operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(32) One ore more PDUs are operating abnormally. There is a failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited. unknownCommFailure(64) The state of one or more PDUs are not known due to a communications failure between the PDU hardware and the communications module. This state is usually indicative of a hardware problem. " ::= { lgpPduCluster 5 } -- ----------------------------------------------------------------------------- -- Power Distribution (PDU) Table. -- ----------------------------------------------------------------------------- lgpPduTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of PDUs being monitored by this agent. This is the number of entries in the lgpPduTable." ::= { lgpPdu 19 } lgpPduTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of PDU entries. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored. The Network Management System (NMS) cannot create or delete rows in the table. The rows are created by the agent based upon the number of PDUs being managed. Each row in the table represents a PDU in the system." ::= { lgpPdu 20 } lgpPduEntry OBJECT-TYPE SYNTAX LgpPduEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the columns to be populated in the 'lgpPduTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU identifier that is unique within the agent. " INDEX { lgpPduEntryIndex } ::= { lgpPduTable 1 } LgpPduEntry ::= SEQUENCE { lgpPduEntryIndex Unsigned32, lgpPduEntryId Unsigned32, lgpPduEntryUsrLabel DisplayString, lgpPduEntrySysAssignLabel DisplayString, lgpPduEntryPositionRelative Unsigned32, lgpPduEntrySysStatus Unsigned32, lgpPduEntryUsrTag1 DisplayString, lgpPduEntryUsrTag2 DisplayString, lgpPduEntrySerialNumber DisplayString, lgpPduEntryRbCount Unsigned32, lgpPduEntrySWOverCurrentProtection INTEGER } lgpPduEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index that indicates the row of the 'lgpPduTable'." ::= { lgpPduEntry 1 } lgpPduEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is an internal index representing a unique identifier for each PDU represented by this agent. The value is assigned by the agent." ::= { lgpPduEntry 5 } lgpPduEntryUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is a user assigned label representing the PDU." ::= { lgpPduEntry 10 } lgpPduEntrySysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "System assigned identifier representing the PDU. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use." ::= { lgpPduEntry 15 } lgpPduEntryPositionRelative OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "This is a one-based value that indicates the PDU's relative position within a rack or other enclosing entity." ::= { lgpPduEntry 20 } lgpPduEntrySysStatus OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This value represents a bit-field of the various operational states of the PDU. The value is a logical OR of all of the following potential states of the PDU. Note the bit-position is given parenthetically next to the operational state in the description below. The bit position is assumed to be a big-endian format (least significant digit is the right-most digit). The state is present in the PDU when the bit is on (value = 1). normalOperation(1) The PDU is operating normally with no active warnings or alarms. startUp(2) The PDU is in the startup state (initializing). Control and monitoring operations maybe inhibited or unavailable while the PDU is in this state. This state will clear automatically when the PDU(s) are fully initialized and ready to accept control and monitoring commands. normalWithWarning(8) The PDU is operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(16) The PDU is operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(32) The PDU is operating abnormally. That is there is some failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited. " ::= { lgpPduEntry 25 } lgpPduEntryUsrTag1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units." ::= { lgpPduEntry 35 } lgpPduEntryUsrTag2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units." ::= { lgpPduEntry 40 } lgpPduEntrySerialNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "System assigned serial number for this PDU. This number is assigned at time of manufacture, is globally unique with respect to all PDU units." ::= { lgpPduEntry 45 } lgpPduEntryRbCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of receptacle branches (Rb) within this PDU." ::= { lgpPduEntry 50 } lgpPduEntrySWOverCurrentProtection OBJECT-TYPE SYNTAX INTEGER { disabled(0), enable(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "This is the PDU Software Over Current Protection feature which will prevent unused receptacles from turning on when the 'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold is violated. Such receptacles shall get locked to prevent any user from switching them ON. Only device-admin shall have the authorization to unlock such receptacles. If the feature is enabled, in case of PDU Over Current Warning or Alarm condition, following action will be taken on the receptacles: a. Locked & OFF – No change b. Locked & ON - No change c. UnLocked & OFF – Receptacle shall be locked d. Unlocked & ON – If the receptacle is being used (current>0), no change. If that outlet is being unused(current=0), turn it off and lock it in that position. No action will be taken if the feature is disabled. Note: Only applicable to PDU models where receptacle measurement and control is supported. Not applicable for PDU models that support only branch monitoring. disabled This function is disabled. enable This function is enabled." ::= { lgpPduEntry 55 } -- ----------------------------------------------------------------------------- -- PDU Power Source. -- ----------------------------------------------------------------------------- lgpPduPowerSource OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about PDU power sources." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 30 } lgpPduPsTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of power sources in the lgpPduPsTable." ::= { lgpPduPowerSource 19 } lgpPduPsTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduPsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the PDU's power source(s). The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of power sources installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents a PDU's Power Source." ::= { lgpPduPowerSource 20 } lgpPduPsEntry OBJECT-TYPE SYNTAX LgpPduPsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduPsTable' (Power Source Table). This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex' which is a unique identifier for the Power Source within a given PDU. Taken together these two indexes uniquely identify a Power Source within this agent. " INDEX { lgpPduEntryIndex, lgpPduPsEntryIndex } ::= { lgpPduPsTable 1 } LgpPduPsEntry ::= SEQUENCE { lgpPduPsEntryIndex Unsigned32, lgpPduPsEntryId Unsigned32, lgpPduPsEntrySysAssignLabel DisplayString, lgpPduPsEntryModel DisplayString, lgpPduPsEntryWiringType INTEGER, lgpPduPsEntryEpInputRated Unsigned32, lgpPduPsEntryEcInputRated Unsigned32, lgpPduPsEntryFreqRated Unsigned32, lgpPduPsEntryEnergyAccum Unsigned32, lgpPduPsEntrySerialNum DisplayString, lgpPduPsEntryFirmwareVersion DisplayString, lgpPduPsEntryPwrTotal Unsigned32, lgpPduPsEntryEcNeutral Unsigned32, lgpPduPsEntryEcNeutralThrshldOvrWarn Unsigned32, lgpPduPsEntryEcNeutralThrshldOvrAlarm Unsigned32, lgpPduPsEntryUnbalancedLoadThrshldAlarm Unsigned32, lgpPduPsEntryApTotal Unsigned32, lgpPduPsEntryPfTotal Integer32, lgpPduPsEntryEcResidual Unsigned32, lgpPduPsEntryEcResidualThrshldOvrAlarm Unsigned32 } lgpPduPsEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is a unique identifier for the Power Source within a given PDU. This is one of two indexes used to indicate the row of the 'lgpPduTable'." ::= { lgpPduPsEntry 5 } lgpPduPsEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "This is a unique entry id representing a given PDU power source for the PDU." ::= { lgpPduPsEntry 10 } lgpPduPsEntrySysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "System assigned identifier for this power source. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use." ::= { lgpPduPsEntry 15 } lgpPduPsEntryModel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is the model name (identifier) of the power supply." ::= { lgpPduPsEntry 20 } lgpPduPsEntryWiringType OBJECT-TYPE SYNTAX INTEGER { not-specified(0), single-phase-3-wire-L1-N-PE(1), two-phase-3-wire-L1-L2-PE(2), three-phase-4-wire-L1-L2-L3-PE(3), three-phase-5-wire-L1-L2-L3-N-PE(4), two-phase-4-wire-L1-L2-N-PE(5) } MAX-ACCESS read-write STATUS current DESCRIPTION "The PDU's power supply physical wiring type. not-specified The type has not been specified/configured. The end_user must configure this object to specify the physical wiring type. single-phase-3-wire-L1-N-PE Single Phase input with 3 wires (Line 1, Neutral and Protective Earth). two-phase-3-wire-L1-L2-PE Two Phase input with 3 wires (Line 1, Line 2, and Protective Earth). three-phase-4-wire-L1-L2-L3-PE Three Phase input with 4 wires (Line 1, Line 2, Line 3, and Protective Earth). three-phase-5-wire-L1-L2-L3-N-PE Three Phase input with 5 wires (Line 1, Line 2, Line 3, Neutral and Protective Earth). two-phase-4-wire-L1-L2-N-PE Two Phase input with 4 wires (Line 1, Line 2, Neutral, and Protective Earth)." ::= { lgpPduPsEntry 25 } lgpPduPsEntryEpInputRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltRMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Rated Input Line Voltage for the power source (i.e. this is the nominal line input voltage; it is NOT a measured voltage). The value is defined to be the rated line voltage (either line-to-neutral or line-to-line depending upon the power source's type)." ::= { lgpPduPsEntry 30 } lgpPduPsEntryEcInputRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "This is the rated input line current for the module (it is NOT the measured current)." ::= { lgpPduPsEntry 35 } lgpPduPsEntryFreqRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "Hertz" MAX-ACCESS read-only STATUS current DESCRIPTION "Rated input line frequency for this power source (i.e. This is the expected line frequency; it is NOT a measured frequency; it is typically 50 Hz or 60 Hz)." ::= { lgpPduPsEntry 40 } lgpPduPsEntryEnergyAccum OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Kilowatt-Hour" MAX-ACCESS read-write STATUS current DESCRIPTION "Total accumulated energy, measured at the power source input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events." ::= { lgpPduPsEntry 50 } lgpPduPsEntrySerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is a unique serial number of the power supply. This number is assigned to the power supply at the time of manufacture." ::= { lgpPduPsEntry 55 } lgpPduPsEntryFirmwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is the version of the firmware installed on the PDU's power supply." ::= { lgpPduPsEntry 60 } lgpPduPsEntryPwrTotal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS current DESCRIPTION "Total input power for this power supply. This is the sum of the power for all phases" ::= { lgpPduPsEntry 65 } lgpPduPsEntryEcNeutral OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The neutral current measured at the PDU's power source." ::= { lgpPduPsEntry 70 } lgpPduPsEntryEcNeutralThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current warning is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current warning (lgpConditionSource1NeutralOverCurrent) is activated." ::= { lgpPduPsEntry 75 } lgpPduPsEntryEcNeutralThrshldOvrAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current alarm is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current alarm (lgpConditionSource1NeutralOverCurrent) is activated." ::= { lgpPduPsEntry 80 } lgpPduPsEntryUnbalancedLoadThrshldAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The parameter is for setting the maximum acceptable percentage of 'Unbalanced Load' between any two phases. This setting shall trigger an alarm when the % load between any two phases varies by a percentage higher than this configurable value. If this value is 0% then the alarm would be deactivated." ::= { lgpPduPsEntry 85 } lgpPduPsEntryApTotal OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltAmp" MAX-ACCESS read-only STATUS current DESCRIPTION "Total Apparent power for this power supply. This is the sum of the apparent power for all phases" ::= { lgpPduPsEntry 90 } lgpPduPsEntryPfTotal OBJECT-TYPE SYNTAX Integer32 UNITS "0.01 Power Factor" MAX-ACCESS read-only STATUS current DESCRIPTION "Total power factor, which is real power/apparent power for all phases combined. This is the sum of the real power for all phases divided by the sum of the apparent power for all phases." ::= { lgpPduPsEntry 95 } lgpPduPsEntryEcResidual OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.001 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured residual current." ::= { lgpPduPsEntry 100 } lgpPduPsEntryEcResidualThrshldOvrAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.001 Amp-AC-RMS" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current alarm is activated. If the measured residual current (lgpPduPsEntryEcResidual) is above this value, an over current alarm is activated. Setting this to 0mA disables the alarm." ::= { lgpPduPsEntry 105 } -- ----------------------------------------------------------------------------- -- PDU - Power Source Line/Phase Table. -- ----------------------------------------------------------------------------- lgpPduPsLineTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduPsLineEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of PDU's power source line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDU's Power Sources being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU's power supply(s). Each row in the table represents a particular phase/line measurement of a power supply for a given PDU." ::= { lgpPduPowerSource 40 } lgpPduPsLineEntry OBJECT-TYPE SYNTAX LgpPduPsLineEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduPsLineTable'. The table is index by three indexes which taken together uniquely identify line/phase information for a given power source within a PDU. The 'lgpPduEntryIndex' is an index into the 'lgpPduTable'. This identifies the PDU that the power source is on. The 'lgpPduPsEntryIndex' is an index that together with the 'lgpPduEntryIndex' uniquely identifies the power source within the PDU that the row in this table represents. The final index 'lgpPduPsLineEntryIndex' identifies the particular line/phase that the measurement applies to within the identified power source." INDEX { lgpPduEntryIndex, lgpPduPsEntryIndex, lgpPduPsLineEntryIndex } ::= { lgpPduPsLineTable 1 } LgpPduPsLineEntry ::= SEQUENCE { lgpPduPsLineEntryIndex Unsigned32, lgpPduPsLineEntryId Unsigned32, lgpPduPsLineEntryLine INTEGER, lgpPduPsLineEntryEpLNTenths Unsigned32, lgpPduPsLineEntryEpLN Unsigned32, lgpPduPsLineEntryEc Unsigned32, lgpPduPsLineEntryEcHundredths Unsigned32, lgpPduPsLineEntryEcThrshldUndrAlarm Unsigned32, lgpPduPsLineEntryEcThrshldOvrWarn Unsigned32, lgpPduPsLineEntryEcThrshldOvrAlarm Unsigned32, lgpPduPsLineEntryEcAvailBeforeAlarm Unsigned32, lgpPduPsLineEntryEcUsedBeforeAlarm Unsigned32, lgpPduPsLineEntryEpLL Unsigned32, lgpPduPsLineEntryEpLLTenths Unsigned32, lgpPduPsLineEntryEcAvailBeforeAlarmHundredths Unsigned32, lgpPduPsLineEntryPwrLN Unsigned32, lgpPduPsLineEntryPwrLL Unsigned32, lgpPduPsLineEntryApLN Unsigned32, lgpPduPsLineEntryApLL Unsigned32, lgpPduPsLineEntryPfLN Integer32, lgpPduPsLineEntryPfLL Integer32 } lgpPduPsLineEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index that indicates the line/phase of the measurements in the given row of the 'lgpPduPsLineTable'." ::= { lgpPduPsLineEntry 5 } lgpPduPsLineEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unique identifier (within a PDU) for the PDU's power source. The object may not be available in non-modular systems." ::= { lgpPduPsLineEntry 10 } lgpPduPsLineEntryLine OBJECT-TYPE SYNTAX INTEGER { phase1(1), phase2(2), phase3(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "The line number (phase) that the measurement represents for all measurements in a given row of the table. Note that this always matches the lgpPduPsLineEntryIndex of the same row in the table. The line/phases are as follows: Line# Description ----- --------------------------------------------------- 1 Line 1-N (A) for Line-to-Neutral measurements 2 Line 2-N (B) for Line-to-Neutral measurements 3 Line 3-N (C) for Line-to-Neutral measurements 1 Line 1-2 (A-B) for Line-to-Line measurements 2 Line 2-3 (B-C) for Line-to-Line measurements 3 Line 3-1 (C-A) for Line-to-Line measurements " ::= { lgpPduPsLineEntry 15 } lgpPduPsLineEntryEpLNTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 19 } lgpPduPsLineEntryEpLN OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 20 } lgpPduPsLineEntryEc OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 21 } lgpPduPsLineEntryEcHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 22 } lgpPduPsLineEntryEcThrshldUndrAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an under current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an under current alarm is activated." ::= { lgpPduPsLineEntry 35 } lgpPduPsLineEntryEcThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current warning is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current warning is activated." ::= { lgpPduPsLineEntry 36 } lgpPduPsLineEntryEcThrshldOvrAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current alarm is activated." ::= { lgpPduPsLineEntry 37 } lgpPduPsLineEntryEcAvailBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduPsLineEntry 38 } lgpPduPsLineEntryEcUsedBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percent of current utilization relative to the over current alarm threshold." ::= { lgpPduPsLineEntry 39 } lgpPduPsLineEntryEpLL OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 60 } lgpPduPsLineEntryEpLLTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 61 } lgpPduPsLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduPsLineEntry 62 } lgpPduPsLineEntryPwrLN OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 63 } lgpPduPsLineEntryPwrLL OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-line measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 64 } lgpPduPsLineEntryApLN OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltAmp" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 65 } lgpPduPsLineEntryApLL OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltAmp" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-line measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 66 } lgpPduPsLineEntryPfLN OBJECT-TYPE SYNTAX Integer32 UNITS "0.01 Power Factor" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 67 } lgpPduPsLineEntryPfLL OBJECT-TYPE SYNTAX Integer32 UNITS "0.01 Power Factor" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-line measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table." ::= { lgpPduPsLineEntry 68 } -- ----------------------------------------------------------------------------- -- PDU Receptacle Branch -- ----------------------------------------------------------------------------- lgpPduReceptacleBranch OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about PDU receptacle branches." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 40 } lgpPduRbTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of receptacle branches in the lgpPduRbTable." ::= { lgpPduReceptacleBranch 19 } lgpPduRbTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduRbEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of PDU Receptacle branches. The table contains zero, one, or many rows, depending upon the number of PDUs being managed and how many receptacle branches each PDU has installed. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being managed. Each row in the table represents a receptacle branch for a given PDU. The PDU that a branch is installed on is indicated by the column lgpPduEntryIndex. The branch within the lgpPduEntryIndex PDU is indicated by the column lgpPduRbEntryIndex." ::= { lgpPduReceptacleBranch 20 } lgpPduRbEntry OBJECT-TYPE SYNTAX LgpPduRbEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduRbTable'. The table is indexed by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable that the branch is on. The lgpPduRbEntryIndex uniquely identifies the branch within that PDU. Taken together the two indexes uniquely identify a branch being monitored by this agent. " INDEX { lgpPduEntryIndex, lgpPduRbEntryIndex } ::= { lgpPduRbTable 1 } LgpPduRbEntry ::= SEQUENCE { lgpPduRbEntryIndex Unsigned32, lgpPduRbEntryId Unsigned32, lgpPduRbEntryUsrLabel DisplayString, lgpPduRbEntrySysAssignLabel DisplayString, lgpPduRbEntryPositionRelative Unsigned32, lgpPduRbEntrySerialNum DisplayString, lgpPduRbEntryModel DisplayString, lgpPduRbEntryFirmwareVersion DisplayString, lgpPduRbEntryUsrTag1 DisplayString, lgpPduRbEntryUsrTag2 DisplayString, lgpPduRbEntryReceptacleType INTEGER, lgpPduRbEntryCapabilities INTEGER, lgpPduRbEntryLineSource INTEGER, lgpPduRbEntryRcpCount Unsigned32, lgpPduRbEntryEpRated Unsigned32, lgpPduRbEntryEcRated Unsigned32, lgpPduRbEntryFreqRated Unsigned32, lgpPduRbEntryEnergyAccum Unsigned32, lgpPduRbEntryEpLNTenths Unsigned32, lgpPduRbEntryPwr Unsigned32, lgpPduRbEntryAp Unsigned32, lgpPduRbEntryPf Integer32, lgpPduRbEntryEcHundredths Unsigned32, lgpPduRbEntryEcThrshldUndrAlm Unsigned32, lgpPduRbEntryEcThrshldOvrWarn Unsigned32, lgpPduRbEntryEcThrshldOvrAlm Unsigned32, lgpPduRbEntryEcAvailBeforeAlarmHundredths Unsigned32, lgpPduRbEntryEcUsedBeforeAlarm Unsigned32, lgpPduRbEntryEpLLTenths Unsigned32, lgpPduRbEntrySwOverCurrentProtection INTEGER } lgpPduRbEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index that indicates the row of the 'lgpPduRbTable'" ::= { lgpPduRbEntry 1 } lgpPduRbEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "A unique id representing the receptacle branch within the collection of branches being monitored by this agent. The uniqueness of this id is within the PDUs being managed by a single agent." ::= { lgpPduRbEntry 5 } lgpPduRbEntryUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A user assigned label representing the receptacle branch." ::= { lgpPduRbEntry 8 } lgpPduRbEntrySysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "System assigned identifier for this receptacle branch. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use." ::= { lgpPduRbEntry 20 } lgpPduRbEntryPositionRelative OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "This is a one-based value that indicates the relative position of the branch within the PDU." ::= { lgpPduRbEntry 25 } lgpPduRbEntrySerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A globally unique serial number for this branch. This number is assigned to the branch at the time of manufacture and can not be modified. NOTE: Generally only PDUs with replaceable receptacle branches will have serial numbers." ::= { lgpPduRbEntry 30 } lgpPduRbEntryModel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is the model designation for this receptacle branch." ::= { lgpPduRbEntry 35 } lgpPduRbEntryFirmwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This is the firmware version number of the control software running on the receptacle branch. Only PDUs with replaceable receptacle branches will typically support this object." ::= { lgpPduRbEntry 40 } lgpPduRbEntryUsrTag1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units." ::= { lgpPduRbEntry 41 } lgpPduRbEntryUsrTag2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units." ::= { lgpPduRbEntry 42 } lgpPduRbEntryReceptacleType OBJECT-TYPE SYNTAX INTEGER { not-specified(0), nema-5-20R-20-Amp(1), iec-C13-sheet-F-10-Amp(2), iec-C19-sheet-J-16-Amp(3), iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp(4), nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp(5), nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp(6), cee-7-type-E-schuko(7), nema-L6-30R-30-Amp(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "This enumeration represents the type of receptacles installed on this receptacle branch. All receptacles on this branch are of this type/style. not-specified If this value is returned, either the receptacle type has not been specified/configured or the agent monitoring this PDU does not have a SNMP enumeration defined to the type. " ::= { lgpPduRbEntry 45 } lgpPduRbEntryCapabilities OBJECT-TYPE SYNTAX INTEGER { not-specified(0), no-optional-capabilities(1), measurement-only(2), measurement-and-control(3), control-only(4), current-measurement-only(5), current-measurement-and-control(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Receptacle branch capabilities describes what an individual branch is capable of. no-optional-capabilities The branch is unable to report measurements and lacks control capabilities. measurement-only The branch is capable of reporting multiple measurements. measurement-and-control The branch is capable of reporting multiple measurements and controlling the state. control-only The branch is capable of controlling the state. current-measurement-only The branch is capable of reporting the current/amperage only. current-measurement-and-control The branch is capable of reporting the current/amperage and has the ability to control the state." ::= { lgpPduRbEntry 50 } lgpPduRbEntryLineSource OBJECT-TYPE SYNTAX INTEGER { not-specified(0), line-1-neutral(1), line-2-neutral(2), line-3-neutral(3), line-1-line-2(4), line-2-line-3(5), line-3-line-1(6), line-1-line-2-and-line-1-neutral(7), line-2-line-3-and-line-2-neutral(8), line-3-line-1-and-line-3-neutral(9), unknown-line-neutral(10), unknown-line-line(11) } MAX-ACCESS read-only STATUS current DESCRIPTION "This represents the line source that is supplying power to this receptacle branch. not-specified The line source supplying power to the load for this receptacle branch has not been specified/configured. line-1-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 1 to neutral). line-2-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 2 to neutral). line-3-N The load for this receptacle branch is supplied by a line-to-neutral configuration. (line 3 to neutral). line-1-line-2 The load for this receptacle branch is supplied by a line-to-line configuration (line 1 to line 2). line-2-line-3 The load for this receptacle branch is supplied by a line-to-line configuration (line 2 to line 3). line-3-line-1 The load for this receptacle branch is supplied by a line-to-line configuration (line 3 to line 1). line-1-line-2-and-line-1-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 1 to line 2 and line 1 to neutral). line-2-line-3-and-line-2-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 2 to line 3 and line 2 to neutral). line-3-line-1-and-line-3-neutral The load for this mixed receptacle branch is supplied by a line-to-line and line-to-neutral configuration (line 3 to line 1 and line 3 to neutral). unknown-line-neutral The load for this branch is supplied by a line-to-neutral configuration. The system is unable to determine which lines are supporting the load. unknown-line-line The load for this branch is supplied by a line-to-line configuration. The system is unable to determine which lines are supporting the load. " ::= { lgpPduRbEntry 55 } lgpPduRbEntryRcpCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "The number of receptacles on this receptacle branch." ::= { lgpPduRbEntry 60 } lgpPduRbEntryEpRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltRMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Rated Line Voltage for the receptacle branch and its associated receptacles (i.e. This is the nominal line voltage that is available to the connected load; it is NOT a measured voltage.)" ::= { lgpPduRbEntry 70 } lgpPduRbEntryEcRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "This is the rated input line current for the module (it is NOT the measured current)." ::= { lgpPduRbEntry 75 } lgpPduRbEntryFreqRated OBJECT-TYPE SYNTAX Unsigned32 UNITS "Hertz" MAX-ACCESS read-only STATUS current DESCRIPTION "This is the rated electrical frequency for the receptacle branch and its associated receptacles" ::= { lgpPduRbEntry 80 } lgpPduRbEntryEnergyAccum OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Kilowatt-Hour" MAX-ACCESS read-write STATUS current DESCRIPTION "Total accumulated energy, measured at the receptacle branch input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events. NOTE: Resetting this value does not reset the values for the individual receptacles." ::= { lgpPduRbEntry 85 } lgpPduRbEntryEpLNTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 VoltRMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbEntry 100 } lgpPduRbEntryPwr OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Real Power (Wattage)" ::= { lgpPduRbEntry 115 } lgpPduRbEntryAp OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltAmp" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Apparent Power (VA)" ::= { lgpPduRbEntry 120 } lgpPduRbEntryPf OBJECT-TYPE SYNTAX Integer32 UNITS "0.01 Power Factor" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Power Factor of the receptacle branches' input." ::= { lgpPduRbEntry 125 } lgpPduRbEntryEcHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared)." ::= { lgpPduRbEntry 130 } lgpPduRbEntryEcThrshldUndrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an under current alarm is activated. If the measured current (lgpPduRbEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated" ::= { lgpPduRbEntry 135 } lgpPduRbEntryEcThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current warning is activated. If the measured current (lgpPduRbEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated" ::= { lgpPduRbEntry 140 } lgpPduRbEntryEcThrshldOvrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current alarm is activated. If the measured current (lgpPduRbEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated" ::= { lgpPduRbEntry 145 } lgpPduRbEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduRbEntry 150 } lgpPduRbEntryEcUsedBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percent of current utilization relative to the over current alarm threshold." ::= { lgpPduRbEntry 160 } lgpPduRbEntryEpLLTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 VoltRMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbEntry 170 } lgpPduRbEntrySwOverCurrentProtection OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "The configuration parameter to enable or disable the Branch SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the receptacles: Locked & On - No Change Locked & Off - No Change Unlocked & Off - Turn it Off and Lock it Unlocked & On - If load present, No Change. If no load, turn it Off and Lock it. No action will be taken if the feature is disabled. Note: Only applicable to PDU models where receptacle measurement and control is possible. Not applicable to branch monoitoring models disabled This function is disabled. enable This function is enabled." ::= { lgpPduRbEntry 175 } -- ----------------------------------------------------------------------------- -- PDU Receptacle Branch - Line/Phase Measurements. -- ----------------------------------------------------------------------------- lgpPduRbLineTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduRbLineEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This table contains a list of PDU receptacle branch line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDUs and the number of receptacle branches on each PDU that are being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDU(s) being monitored. Each row in the table represents a particular phase/line measurement of a PDU Receptacle Branch. Rows in the table are uniquely identified by three indexes representing respectively the PDU (lgpPduEntryIndex), the receptacle branch (lgpPduRbEntryIndex) and the line/phase being measured (lgpPduRbLineEntryIndex). " ::= { lgpPduReceptacleBranch 40 } lgpPduRbLineEntry OBJECT-TYPE SYNTAX LgpPduRbLineEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduRbLineTable'. The table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' to which this receptacle branch line/phase measurement belongs. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' references the receptacle branch in the 'lgpPduRbTable'. The 'lgpPduRbLineEntryIndex' represents the line/phase of the measurements in the row of this table. Together these three indexes uniquely identify a phase/line measurement on a receptacle branch within a PDU being monitored by this agent. " INDEX { lgpPduEntryIndex, lgpPduRbEntryIndex, lgpPduRbLineEntryIndex } ::= { lgpPduRbLineTable 1 } LgpPduRbLineEntry ::= SEQUENCE { lgpPduRbLineEntryIndex Unsigned32, lgpPduRbLineEntryId Unsigned32, lgpPduRbLineEntryLine INTEGER, lgpPduRbLineEntryEpLNTenths Unsigned32, lgpPduRbLineEntryEpLN Unsigned32, lgpPduRbLineEntryEc Unsigned32, lgpPduRbLineEntryPwr Unsigned32, lgpPduRbLineEntryAp Unsigned32, lgpPduRbLineEntryPf Integer32, lgpPduRbLineEntryEcHundredths Unsigned32, lgpPduRbLineEntryEcThrshldUndrAlm Unsigned32, lgpPduRbLineEntryEcThrshldOvrWarn Unsigned32, lgpPduRbLineEntryEcThrshldOvrAlm Unsigned32, lgpPduRbLineEntryEcAvailBeforeAlarmHundredths Unsigned32, lgpPduRbLineEntryEcAvailBeforeAlarm Unsigned32, lgpPduRbLineEntryEcUsedBeforeAlarm Unsigned32, lgpPduRbLineEntryEpLL Unsigned32, lgpPduRbLineEntryEpLLTenths Unsigned32 } lgpPduRbLineEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This is the index that indicates the row of the 'lgpPduRbLineTable'" ::= { lgpPduRbLineEntry 1 } lgpPduRbLineEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Runtime assigned branch identifier." ::= { lgpPduRbLineEntry 5 } lgpPduRbLineEntryLine OBJECT-TYPE SYNTAX INTEGER { phase1(1), phase2(2), phase3(3) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line number or phase that the measurement for this receptacle branch represents for each measurement in this row of the table. The phases are as follows: Line# Description ----- --------------------------------------------------- 1 Line 1-N (A) for Line-to-Neutral measurements 2 Line 2-N (B) for Line-to-Neutral measurements 3 Line 3-N (C) for Line-to-Neutral measurements 1 Line 1-2 (A-B) for Line-to-Line measurements 2 Line 2-3 (B-C) for Line-to-Line measurements 3 Line 3-1 (C-A) for Line-to-Line measurements " ::= { lgpPduRbLineEntry 10 } lgpPduRbLineEntryEpLNTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 VoltRMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 19 } lgpPduRbLineEntryEpLN OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltRMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 20 } lgpPduRbLineEntryEc OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amp-AC-RMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 21 } lgpPduRbLineEntryPwr OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Real Power (Wattage)" ::= { lgpPduRbLineEntry 22 } lgpPduRbLineEntryAp OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltAmp" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Apparent Power (VA)" ::= { lgpPduRbLineEntry 23 } lgpPduRbLineEntryPf OBJECT-TYPE SYNTAX Integer32 UNITS "0.01 Power Factor" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Power Factor of the receptacle branches' input." ::= { lgpPduRbLineEntry 24 } lgpPduRbLineEntryEcHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amp-AC-RMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 25 } lgpPduRbLineEntryEcThrshldUndrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated" ::= { lgpPduRbLineEntry 35 } lgpPduRbLineEntryEcThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated" ::= { lgpPduRbLineEntry 36 } lgpPduRbLineEntryEcThrshldOvrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated" ::= { lgpPduRbLineEntry 37 } lgpPduRbLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amps-AC-RMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduRbLineEntry 39 } lgpPduRbLineEntryEcAvailBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amps-AC-RMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduRbLineEntry 40 } lgpPduRbLineEntryEcUsedBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Percent" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The percent of current utilization relative to the over current alarm threshold." ::= { lgpPduRbLineEntry 41 } lgpPduRbLineEntryEpLL OBJECT-TYPE SYNTAX Unsigned32 UNITS "VoltRMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 60 } lgpPduRbLineEntryEpLLTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 VoltRMS" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared)." ::= { lgpPduRbLineEntry 61 } -- ----------------------------------------------------------------------------- -- PDU Receptacle (RCP) - Table -- ----------------------------------------------------------------------------- lgpPduReceptacle OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about PDU receptacles." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 50 } lgpPduRcpTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of receptacles in the lgpPduRcpTable." ::= { lgpPduReceptacle 19 } lgpPduRcpTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduRcpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of PDU receptacle entries. The table contains numerous rows representing an individual receptacle, depending upon the number and configuration of the PDU(s) being monitored by the agent. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU(s). Each row in the table represents a receptacle in the system. " ::= { lgpPduReceptacle 20 } lgpPduRcpEntry OBJECT-TYPE SYNTAX LgpPduRcpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpTable'. This table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' that a given row in this table represents. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' specifies a row in the 'lgpPduRbTable' that the receptacle belongs. The 'lgpPduRcpEntryIndex' identifies the particular receptacle within the branch. " INDEX { lgpPduEntryIndex, lgpPduRbEntryIndex, lgpPduRcpEntryIndex } ::= { lgpPduRcpTable 1 } LgpPduRcpEntry ::= SEQUENCE { lgpPduRcpEntryIndex Unsigned32, lgpPduRcpEntryId Unsigned32, lgpPduRcpEntryUsrLabel DisplayString, lgpPduRcpEntryUsrTag1 DisplayString, lgpPduRcpEntryUsrTag2 DisplayString, lgpPduRcpEntrySysAssignLabel DisplayString, lgpPduRcpEntryPosition Unsigned32, lgpPduRcpEntryType INTEGER, lgpPduRcpEntryLineSource INTEGER, lgpPduRcpEntryCapabilities INTEGER, lgpPduRcpEntryEp Unsigned32, lgpPduRcpEntryEpTenths Unsigned32, lgpPduRcpEntryEc Unsigned32, lgpPduRcpEntryEcHundredths Unsigned32, lgpPduRcpEntryPwrOut Unsigned32, lgpPduRcpEntryApOut Unsigned32, lgpPduRcpEntryPf Unsigned32, lgpPduRcpEntryFreq Unsigned32, lgpPduRcpEntryEnergyAccum Unsigned32, lgpPduRcpEntryPwrOnDelay Unsigned32, lgpPduRcpEntryPwrState INTEGER, lgpPduRcpEntryPwrUpState INTEGER, lgpPduRcpEntryControl INTEGER, lgpPduRcpEntryControlLock INTEGER, lgpPduRcpEntryEcThrshldUnderAlarm Unsigned32, lgpPduRcpEntryEcThrshldOverWarn Unsigned32, lgpPduRcpEntryEcThrshldOverAlarm Unsigned32, lgpPduRcpEntryEcAvailBeforeAlarmHundredths Unsigned32, lgpPduRcpEntryEcAvailBeforeAlarm Unsigned32, lgpPduRcpEntryEcUsedBeforeAlarm Unsigned32, lgpPduRcpEntryEcCrestFactor Unsigned32, lgpPduRcpEntryBlinkLED INTEGER, lgpPduRcpEntrySwOverTemperatureProtection INTEGER, lgpPduRcpEntryOperationCondition INTEGER, lgpPduRcpEntryCriticality INTEGER, lgpPduRcpEntryPostOnDelay Unsigned32, lgpPduRcpEntryPostOffDelay Unsigned32, lgpPduRcpEntryAddReceptacleToGroup OBJECT IDENTIFIER, lgpPduRcpEntryRemoveReceptacleFromGroup OBJECT IDENTIFIER } lgpPduRcpEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index that indicates the receptacle position on the receptacle branch. This along with the other two indexes on the lgpPduRcpTable uniquely identify the receptacle in this table." ::= { lgpPduRcpEntry 1 } lgpPduRcpEntryId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "A runtime assigned receptacle identification number." ::= { lgpPduRcpEntry 5 } lgpPduRcpEntryUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned label for this receptacle." ::= { lgpPduRcpEntry 10 } lgpPduRcpEntryUsrTag1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain." ::= { lgpPduRcpEntry 15 } lgpPduRcpEntryUsrTag2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain." ::= { lgpPduRcpEntry 20 } lgpPduRcpEntrySysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "System assigned identifier representing the receptacle. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use." ::= { lgpPduRcpEntry 25 } lgpPduRcpEntryPosition OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "A number representing the position of the receptacle within the receptacle branch." ::= { lgpPduRcpEntry 30 } lgpPduRcpEntryType OBJECT-TYPE SYNTAX INTEGER { not-specified(0), nema-5-20R-20-Amp(1), iec-C13-sheet-F-10-Amp(2), iec-C19-sheet-J-16-Amp(3), cee-7-type-E-schuko(7), nema-L6-30R-30-Amp(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "The type or form of receptacle. The enumerations are specified in well-known industry standard terms and abbreviations." ::= { lgpPduRcpEntry 40 } lgpPduRcpEntryLineSource OBJECT-TYPE SYNTAX INTEGER { not-specified(0), line-1-N(1), line-2-N(2), line-3-N(3), line-1-line-2(4), line-2-line-3(5), line-3-line-1(6), unknown-line-neutral(7), unknown-line-line(8) } MAX-ACCESS read-only STATUS current DESCRIPTION "This represents the line source that is supplying power to this receptacle. not-specified The line source supplying power to the load for this receptacle has not been specified/configured. line-1-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 1 to neutral). line-2-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 2 to neutral). line-3-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 3 to neutral). line-1-line-2 The load for this receptacle is supplied by a line-to-line configuration (line 1 to line 2). line-2-line-3 The load for this receptacle is supplied by a line-to-line configuration (line 2 to line 3). line-3-line-1 The load for this receptacle is supplied by a line-to-line configuration (line 3 to line 1). unknown-line-neutral The load for this receptacle is supplied by a line-to-neutral configuration. The system is unable to determine which lines are supporting the load. unknown-line-line The load for this receptacle is supplied by a line-to-line configuration. The system is unable to determine which lines are supporting the load. " ::= { lgpPduRcpEntry 45 } lgpPduRcpEntryCapabilities OBJECT-TYPE SYNTAX INTEGER { not-specified(0), no-optional-capabilities(1), measurement-only(2), measurement-and-control(3), control-only(4), current-measurement-only(5), current-measurement-and-control(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Receptacle capabilities describes what an individual receptacle is capable of. no-optional-capabilities The receptacle is unable to report measurements and lacks control capabilities. measurement-only The receptacle is capable of reporting multiple measurements. measurement-and-control The receptacle is capable of reporting multiple measurements and controlling the state. control-only The receptacle is capable of controlling the state. current-measurement-only The receptacle is capable of reporting the current/amperage only. current-measurement-and-control The receptacle is capable of reporting the current/amperage and has the ability to control the state." ::= { lgpPduRcpEntry 50 } lgpPduRcpEntryEp OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement." ::= { lgpPduRcpEntry 55 } lgpPduRcpEntryEpTenths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Volts-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement." ::= { lgpPduRcpEntry 56 } lgpPduRcpEntryEc OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared)." ::= { lgpPduRcpEntry 60 } lgpPduRcpEntryEcHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amp-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared)." ::= { lgpPduRcpEntry 61 } lgpPduRcpEntryPwrOut OBJECT-TYPE SYNTAX Unsigned32 UNITS "Watt" MAX-ACCESS read-only STATUS current DESCRIPTION "Real Power (watts) being delivered to the load attached to the receptacle." ::= { lgpPduRcpEntry 65 } lgpPduRcpEntryApOut OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volt-Amp-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "Apparent Power (volt-amps) being delivered to the load attached to the receptacle." ::= { lgpPduRcpEntry 70 } lgpPduRcpEntryPf OBJECT-TYPE SYNTAX Unsigned32 UNITS ".01 Power Factor" MAX-ACCESS read-only STATUS current DESCRIPTION "Receptacle Power Factor, which is the ratio of real power to apparent power (i.e. ratio of watts to volts-amps)." ::= { lgpPduRcpEntry 75 } lgpPduRcpEntryFreq OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Hertz" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured line frequency being delivered to the load attached to the receptacle." ::= { lgpPduRcpEntry 80 } lgpPduRcpEntryEnergyAccum OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Kilowatt-Hour" MAX-ACCESS read-write STATUS current DESCRIPTION "Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events." ::= { lgpPduRcpEntry 85 } lgpPduRcpEntryPwrOnDelay OBJECT-TYPE SYNTAX Unsigned32 UNITS "Seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "The amount of time to wait before power is applied to the receptacle after a power strip is turned on or rebooted. This can be used to stagger the powering of multiple receptacles in order to prevent a large initial current draw." ::= { lgpPduRcpEntry 90 } lgpPduRcpEntryPwrState OBJECT-TYPE SYNTAX INTEGER { unknown(0), off(1), on(2), off-pending-on-delay(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "unknown The current power state is unknown. off The current power state of the receptacle is OFF. on The current power state of the receptacle is ON. off-pending-on-delay The current power state of the receptacle is OFF. The power will be ON at the expiration of the ON delay of this receptacle." ::= { lgpPduRcpEntry 95 } lgpPduRcpEntryPwrUpState OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), last-state(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The 'Power Up State' defines the state to which the receptacle shall return after a power cycle of the PDU. on The receptacle shall be switched to the ON state after the power on delay timer (lgpPduRcpEntryPwrOnDelay). off The receptacle shall be in the OFF state upon power cycle. last-state The receptacle shall be put to the previous state. Again, on state will be effective only after the power on delay (lgpPduRcpEntryPwrOnDelay)." ::= { lgpPduRcpEntry 96 } lgpPduRcpEntryControl OBJECT-TYPE SYNTAX INTEGER { off(0), on(1), cycle-power(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "This object represents the current and persistent (configured) power state of the receptacle. The receptacle can also be controlled by writing to this object. off The current and persisted (configured) power state of the receptacle is 'off'. When writing 'off' to this object the receptacle, if ON, will be turned OFF and its persistent (configured) power state will be set to 'off'. on The current and persisted (configured) power state of the receptacle is 'on'. When writing 'on' to this object the receptacle, if 'off', will be turned 'on' and its persistent (configured) power state will be set to 'on'. cycle-power The receptacle is currently in a power-cycle state. The power to the receptacle is being turned off momentarily and will then revert to being 'on'. When writing 'cycle-power' to this OBJECT if the receptacle is 'on' it will be momentarily turned 'off' and then revert to the 'on' state. The receptacle's persistent (configured) power state will be left unchanged ('on'). If the receptacle is OFF writing cycle-power has no affect on the receptacle. " ::= { lgpPduRcpEntry 100 } lgpPduRcpEntryControlLock OBJECT-TYPE SYNTAX INTEGER { unknown(0), unlocked(1), locked(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "This object represents the locked state of the receptacle. unknown The lock state of the receptacle is not known at this time. locked If the receptacle is 'locked' then its current persisted (configured) state can not be changed. unlocked If the receptacle is 'unlocked', then a user with proper permissions may change the receptacles state." ::= { lgpPduRcpEntry 105 } lgpPduRcpEntryEcThrshldUnderAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated" ::= { lgpPduRcpEntry 150 } lgpPduRcpEntryEcThrshldOverWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated" ::= { lgpPduRcpEntry 151 } lgpPduRcpEntryEcThrshldOverAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-write STATUS current DESCRIPTION "The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated" ::= { lgpPduRcpEntry 152 } lgpPduRcpEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduRcpEntry 159 } lgpPduRcpEntryEcAvailBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Amps-AC-RMS" MAX-ACCESS read-only STATUS current DESCRIPTION "The amount that the current/amperage may increase from its present value before an over current alarm occurs." ::= { lgpPduRcpEntry 160 } lgpPduRcpEntryEcUsedBeforeAlarm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 Percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The percent of current utilization relative to the over current alarm threshold." ::= { lgpPduRcpEntry 161 } lgpPduRcpEntryEcCrestFactor OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.01" MAX-ACCESS read-only STATUS current DESCRIPTION "Receptacle current crest factor, which is the peak amplitude of the current waveform divided by the RMS value of the waveform." ::= { lgpPduRcpEntry 162 } lgpPduRcpEntryBlinkLED OBJECT-TYPE SYNTAX INTEGER { noAction(1), blinkLED(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Blink the receptacle LED. Writing blinkLED(2) will cause the LED to blink for a predefined duration of time. Reading this object will always return noAction(1)." ::= { lgpPduRcpEntry 200 } lgpPduRcpEntrySwOverTemperatureProtection OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "The configuration parameter to enable or disable the Receptacle SW Over Temperature Protection feature If the feature is enabled, in case of Over Temperature Alarm condition, following action will be taken on the receptacles: Locked & Off - No Change Unlocked & Off - No Change Unlocked & On - Turn it Off. Locked & On - Turn it Off and keep it Locked. No action will be taken if the feature is disabled." ::= { lgpPduRcpEntry 205 } lgpPduRcpEntryOperationCondition OBJECT-TYPE SYNTAX INTEGER { normalOperation(1), normalWithWarning(2), normalWithAlarm(3), abnormal(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "Receptacle Operating Condition - indicates the condition of the receptacle. The operating condition has the following: Normal Normal operation without any alarm or warning. Alarm An Alarm condition due to over/under current. Warning A Warning condition due to over/under current Abnormal A condition in which the outlet is in 'Power Off State' but still drawing current." ::= { lgpPduRcpEntry 210 } lgpPduRcpEntryCriticality OBJECT-TYPE SYNTAX INTEGER { critical(0), notCritical(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "The configuration parameter can be used by the user to mark a receptacle as critical or non-critical." ::= { lgpPduRcpEntry 215 } lgpPduRcpEntryPostOnDelay OBJECT-TYPE SYNTAX Unsigned32 UNITS "Seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "The 'Post On Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch ON a receptacle before applying power to the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned on immediately on command issue)." ::= { lgpPduRcpEntry 220 } lgpPduRcpEntryPostOffDelay OBJECT-TYPE SYNTAX Unsigned32 UNITS "Seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch OFF a receptacle before removing power from the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned off immediately on command issue)." ::= { lgpPduRcpEntry 225 } lgpPduRcpEntryAddReceptacleToGroup OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-write STATUS current DESCRIPTION "This receptacle can be added to a group by writing a corresponding OID to this column. The OID must be a pointer to the lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to add this receptacle to group 1, the oid .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to this column." ::= { lgpPduRcpEntry 230 } lgpPduRcpEntryRemoveReceptacleFromGroup OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-write STATUS current DESCRIPTION "This receptacle can be removed from a group by writing a corresponding OID to this column. The OID must be a pointer to the lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to remove this receptacle from group 1, the oid .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to this column." ::= { lgpPduRcpEntry 235 } -- ----------------------------------------------------------------------------- -- PDU Receptacle Group Table -- ----------------------------------------------------------------------------- lgpPduRcpGroup OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about receptacle groups. Receptacle groups are supported by some PDU's and allow control of multiple receptacles at a time by issuing commands to an associated receptacle group." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPduReceptacle 30 } lgpPduRcpGroupTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of receptacle groups (rows) in the lgpPduRcpGroupTable." ::= { lgpPduRcpGroup 9 } lgpPduRcpGroupTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduRcpGroupEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the possible receptacle groups that can be created. The table contains a fixed number of rows, which is the maximum number of receptacle groups that can be used." ::= { lgpPduRcpGroup 10 } lgpPduRcpGroupEntry OBJECT-TYPE SYNTAX LgpPduRcpGroupEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupTable'. This table is indexed by lgpPduRcpGroupIndex. " INDEX { lgpPduRcpGroupIndex } ::= { lgpPduRcpGroupTable 1 } LgpPduRcpGroupEntry ::= SEQUENCE { lgpPduRcpGroupIndex Unsigned32, lgpPduRcpGroupUsrLabel DisplayString, lgpPduRcpGroupDeleteGroup INTEGER, lgpPduRcpGroupControlPower INTEGER, lgpPduRcpGroupControlLock INTEGER, lgpPduRcpGroupBlinkLED INTEGER } lgpPduRcpGroupIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is an index into the table. There will always be 64 rows, each representing a separate receptacle group. " ::= { lgpPduRcpGroupEntry 1 } lgpPduRcpGroupUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned identifier for this receptacle group." ::= { lgpPduRcpGroupEntry 10 } lgpPduRcpGroupDeleteGroup OBJECT-TYPE SYNTAX INTEGER { no-action(0), delete-receptacle-group(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "This column will delete the receptacles from the group when written to." ::= { lgpPduRcpGroupEntry 20 } lgpPduRcpGroupControlPower OBJECT-TYPE SYNTAX INTEGER { no-action(0), off(1), on(2), cycle-power(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "This column controls the power to the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group. " ::= { lgpPduRcpGroupEntry 30 } lgpPduRcpGroupControlLock OBJECT-TYPE SYNTAX INTEGER { no-action(0), unlock(1), lock(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "This column controls the locking of the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group. " ::= { lgpPduRcpGroupEntry 40 } lgpPduRcpGroupBlinkLED OBJECT-TYPE SYNTAX INTEGER { no-action(0), blinkLED(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "This column will blink the LED's associated with all receptacles that are part of the group. " ::= { lgpPduRcpGroupEntry 50 } -- ----------------------------------------------------------------------------- -- PDU Receptacle Group Display Table -- ----------------------------------------------------------------------------- lgpPduRcpGroupDisplayTableCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of rows currently in the lgpPduRcpGroupDisplayTable." ::= { lgpPduRcpGroup 19 } lgpPduRcpGroupDisplayTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduRcpGroupDisplayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table is used to display which receptacle groups are currently defined and which receptacles are associated with each group. The table will have 0 rows when no receptacles have been added to any receptacle groups. If a single receptacle has been added to 2 different groups, there will be 2 rows in the table. " ::= { lgpPduRcpGroup 20 } lgpPduRcpGroupDisplayEntry OBJECT-TYPE SYNTAX LgpPduRcpGroupDisplayEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupDisplayTable'. This table is indexed by two indexes. The 'lgpPduRcpGroupIndex' references a receptacle group in the 'lgpPduRcpGroupTable' that a given row in this table represents. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' that identifies the particular PDU receptacle list within the receptacle group. " INDEX { lgpPduRcpGroupIndex, lgpPduEntryIndex } ::= { lgpPduRcpGroupDisplayTable 1 } LgpPduRcpGroupDisplayEntry ::= SEQUENCE { lgpPduRcpGroupDisplayIndex Unsigned32, lgpPduRcpGroupDisplayGroup DisplayString } lgpPduRcpGroupDisplayIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is an index into the table. There can be zero or more rows in this table." ::= { lgpPduRcpGroupDisplayEntry 10 } lgpPduRcpGroupDisplayGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "This column displays the PDU receptacle list of the specified receptacle group. The value in this column is a comma delimted string that decribes the list of receptacles of a PDU that are members of the receptacle group. For example, if receptacles 1 and 3 of branch A and receptacles 2 and 4 of branch B are members of the receptacle group, this column would show: A-1,A-3,B-2,B-4" ::= { lgpPduRcpGroupDisplayEntry 20 } -- ----------------------------------------------------------------------------- -- PDU Auxiliary Sensors -- ----------------------------------------------------------------------------- lgpPduAuxiliarySensors OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree contains information about PDU Auxiliary Sensors." REFERENCE "The registrations for the objects in this sub-tree are defined below." ::= { lgpPdu 60 } lgpPduAuxSensorCount OBJECT-TYPE SYNTAX Unsigned32 UNITS "Count" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of auxiliary sensors in the lgpPduAuxSensorTable." ::= { lgpPduAuxiliarySensors 5 } lgpPduAuxSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduAuxSensorEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This table contains a list of the PDU's Auxiliary Sensors. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of auxiliary sensors installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor in a PDU." ::= { lgpPduAuxiliarySensors 10 } lgpPduAuxSensorEntry OBJECT-TYPE SYNTAX LgpPduAuxSensorEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxSensorTable'. This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduAuxSensorIndex'which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify an Auxiliary Sensor within this agent." INDEX { lgpPduEntryIndex, lgpPduAuxSensorIndex } ::= { lgpPduAuxSensorTable 1 } LgpPduAuxSensorEntry ::= SEQUENCE { lgpPduAuxSensorIndex Unsigned32, lgpPduAuxSensorMeasType INTEGER, lgpPduAuxSensorId Unsigned32, lgpPduAuxSensorSysAssignLabel DisplayString, lgpPduAuxSensorPositionRelative Unsigned32, lgpPduAuxSensorUsrLabel DisplayString, lgpPduAuxSensorUsrTag1 DisplayString, lgpPduAuxSensorUsrTag2 DisplayString, lgpPduAuxSensorTempSerialNum DisplayString, lgpPduAuxSensorHumSerialNum DisplayString, lgpPduAuxSensorTempMeasurementDegF Integer32, lgpPduAuxSensorTempThrshldUndrAlmDegF Integer32, lgpPduAuxSensorTempThrshldOvrAlmDegF Integer32, lgpPduAuxSensorTempThrshldUndrWarnDegF Integer32, lgpPduAuxSensorTempThrshldOvrWarnDegF Integer32, lgpPduAuxSensorTempMeasurementDegC Integer32, lgpPduAuxSensorTempThrshldUndrAlmDegC Integer32, lgpPduAuxSensorTempThrshldOvrAlmDegC Integer32, lgpPduAuxSensorTempThrshldUndrWarnDegC Integer32, lgpPduAuxSensorTempThrshldOvrWarnDegC Integer32, lgpPduAuxSensorHumMeasurement Unsigned32, lgpPduAuxSensorHumThrshldUndrAlm Unsigned32, lgpPduAuxSensorHumThrshldOvrAlm Unsigned32, lgpPduAuxSensorHumThrshldUndrWarn Unsigned32, lgpPduAuxSensorHumThrshldOvrWarn Unsigned32 } lgpPduAuxSensorIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "This is the index indicating the nth element of the table." ::= { lgpPduAuxSensorEntry 1 } lgpPduAuxSensorMeasType OBJECT-TYPE SYNTAX INTEGER { not-specified(0), temperature(1), humidity(2), temperature-and-humidity(3) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "not-specified The type of sensor is unknown. temperature The sensor in this row of the table measures temperature. humidity The sensor in this row of the table measures relative humidity. temperature-and-humidity The sensor in this row of the table measures both temperature and relative humidity." ::= { lgpPduAuxSensorEntry 5 } lgpPduAuxSensorId OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "System assigned auxiliary sensor identification number. The value assigned is product specific." ::= { lgpPduAuxSensorEntry 10 } lgpPduAuxSensorSysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag." ::= { lgpPduAuxSensorEntry 15 } lgpPduAuxSensorPositionRelative OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Auxiliary sensor relative position. This is a one-based value that indicates the sensor's position relative to the sensor string connector." ::= { lgpPduAuxSensorEntry 20 } lgpPduAuxSensorUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User assigned auxiliary sensor label." ::= { lgpPduAuxSensorEntry 25 } lgpPduAuxSensorUsrTag1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain." ::= { lgpPduAuxSensorEntry 30 } lgpPduAuxSensorUsrTag2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain." ::= { lgpPduAuxSensorEntry 35 } lgpPduAuxSensorTempSerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The temperature sensor's globally unique serial number assigned at the time of manufacture." ::= { lgpPduAuxSensorEntry 40 } lgpPduAuxSensorHumSerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "The humidity sensor's globally unique serial number assigned at the time of manufacture." ::= { lgpPduAuxSensorEntry 45 } lgpPduAuxSensorTempMeasurementDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Fahrenheit." ::= { lgpPduAuxSensorEntry 50 } lgpPduAuxSensorTempThrshldUndrAlmDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value." ::= { lgpPduAuxSensorEntry 55 } lgpPduAuxSensorTempThrshldOvrAlmDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value." ::= { lgpPduAuxSensorEntry 60 } lgpPduAuxSensorTempThrshldUndrWarnDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value." ::= { lgpPduAuxSensorEntry 65 } lgpPduAuxSensorTempThrshldOvrWarnDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value." ::= { lgpPduAuxSensorEntry 70 } lgpPduAuxSensorTempMeasurementDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Celsius." ::= { lgpPduAuxSensorEntry 75 } lgpPduAuxSensorTempThrshldUndrAlmDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value." ::= { lgpPduAuxSensorEntry 80 } lgpPduAuxSensorTempThrshldOvrAlmDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value." ::= { lgpPduAuxSensorEntry 85 } lgpPduAuxSensorTempThrshldUndrWarnDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value." ::= { lgpPduAuxSensorEntry 90 } lgpPduAuxSensorTempThrshldOvrWarnDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value." ::= { lgpPduAuxSensorEntry 95 } lgpPduAuxSensorHumMeasurement OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Relative Humidity measured at the humidity sensor." ::= { lgpPduAuxSensorEntry 100 } lgpPduAuxSensorHumThrshldUndrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value." ::= { lgpPduAuxSensorEntry 105 } lgpPduAuxSensorHumThrshldOvrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value." ::= { lgpPduAuxSensorEntry 110 } lgpPduAuxSensorHumThrshldUndrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value." ::= { lgpPduAuxSensorEntry 115 } lgpPduAuxSensorHumThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value." ::= { lgpPduAuxSensorEntry 120 } lgpPduAuxMeasTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduAuxMeasEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the PDU's Auxiliary Sensor Measurements. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored, the number of auxiliary sensors installed for each PDU, and the number of measurements within each sensor. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor measurement in a PDU." ::= { lgpPduAuxiliarySensors 15 } lgpPduAuxMeasEntry OBJECT-TYPE SYNTAX LgpPduAuxMeasEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the measurement's index identified on the sensor. Taken together these three indexes uniquely identify an Auxiliary Sensor Measurement within this agent." INDEX { lgpPduEntryIndex, lgpPduAuxMeasSensorIndex, lgpPduAuxMeasSensorMeasurementIndex } ::= { lgpPduAuxMeasTable 1 } LgpPduAuxMeasEntry ::= SEQUENCE { lgpPduAuxMeasSensorIndex Unsigned32, lgpPduAuxMeasSensorMeasurementIndex Unsigned32, lgpPduAuxMeasType INTEGER, lgpPduAuxMeasSensorSysAssignLabel DisplayString, lgpPduAuxMeasUsrLabel DisplayString, lgpPduAuxMeasUsrTag1 DisplayString, lgpPduAuxMeasUsrTag2 DisplayString, lgpPduAuxMeasSensorSerialNum DisplayString, lgpPduAuxMeasTempDegF Integer32, lgpPduAuxMeasTempThrshldUndrAlmDegF Integer32, lgpPduAuxMeasTempThrshldOvrAlmDegF Integer32, lgpPduAuxMeasTempThrshldUndrWarnDegF Integer32, lgpPduAuxMeasTempThrshldOvrWarnDegF Integer32, lgpPduAuxMeasTempDegC Integer32, lgpPduAuxMeasTempThrshldUndrAlmDegC Integer32, lgpPduAuxMeasTempThrshldOvrAlmDegC Integer32, lgpPduAuxMeasTempThrshldUndrWarnDegC Integer32, lgpPduAuxMeasTempThrshldOvrWarnDegC Integer32, lgpPduAuxMeasHum Unsigned32, lgpPduAuxMeasHumThrshldUndrAlm Unsigned32, lgpPduAuxMeasHumThrshldOvrAlm Unsigned32, lgpPduAuxMeasHumThrshldUndrWarn Unsigned32, lgpPduAuxMeasHumThrshldOvrWarn Unsigned32, lgpPduAuxMeasDrClosureState INTEGER, lgpPduAuxMeasDrClosureConfig INTEGER, lgpPduAuxMeasCntctClosureState INTEGER, lgpPduAuxMeasCntctClosureConfig INTEGER, lgpPduAuxMeasDiffPressure Integer32, lgpPduAuxMeasDiffPressureThrshldUndrAlm Integer32, lgpPduAuxMeasDiffPressureThrshldOvrAlm Integer32, lgpPduAuxMeasDiffPressureThrshldUndrWarn Integer32, lgpPduAuxMeasDiffPressureThrshldOvrWarn Integer32, lgpPduAuxMeasLeakDetectState INTEGER } lgpPduAuxMeasSensorIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the sensor the measurement is accessed from." ::= { lgpPduAuxMeasEntry 1 } lgpPduAuxMeasSensorMeasurementIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the measurement's index identified on the sensor." ::= { lgpPduAuxMeasEntry 5 } lgpPduAuxMeasType OBJECT-TYPE SYNTAX INTEGER { not-specified(0), temperature(1), humidity(2), door-closure(3), contact-closure(4), differential-pressure(5), leak-detection(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "not-specified The type of measurement is unknown. temperature The measurement in this row of the table measures temperature. humidity The measurement in this row of the table measures relative humidity. door-closure The measurement in this row of the table measures the state of a door. contact-closure The measurement in this row of the table measures the state of a contact closure. differential-pressure The measurement in this row of the table measures differential pressure. leak-detection The measurement in this row of the table measures the state of a leak detection sensor." ::= { lgpPduAuxMeasEntry 10 } lgpPduAuxMeasSensorSysAssignLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag." ::= { lgpPduAuxMeasEntry 15 } lgpPduAuxMeasUsrLabel OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned auxiliary sensor measurement label." ::= { lgpPduAuxMeasEntry 20 } lgpPduAuxMeasUsrTag1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain." ::= { lgpPduAuxMeasEntry 25 } lgpPduAuxMeasUsrTag2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain." ::= { lgpPduAuxMeasEntry 30 } lgpPduAuxMeasSensorSerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "The sensor's globally unique serial number assigned at the time of manufacture." ::= { lgpPduAuxMeasEntry 35 } lgpPduAuxMeasTempDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Fahrenheit." ::= { lgpPduAuxMeasEntry 40 } lgpPduAuxMeasTempThrshldUndrAlmDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value." ::= { lgpPduAuxMeasEntry 50 } lgpPduAuxMeasTempThrshldOvrAlmDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value." ::= { lgpPduAuxMeasEntry 55 } lgpPduAuxMeasTempThrshldUndrWarnDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value." ::= { lgpPduAuxMeasEntry 60 } lgpPduAuxMeasTempThrshldOvrWarnDegF OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Fahrenheit" MAX-ACCESS read-write STATUS current DESCRIPTION "Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value." ::= { lgpPduAuxMeasEntry 65 } lgpPduAuxMeasTempDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature measured at the temperature sensor reported in degrees Celsius." ::= { lgpPduAuxMeasEntry 70 } lgpPduAuxMeasTempThrshldUndrAlmDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value." ::= { lgpPduAuxMeasEntry 75 } lgpPduAuxMeasTempThrshldOvrAlmDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value." ::= { lgpPduAuxMeasEntry 80 } lgpPduAuxMeasTempThrshldUndrWarnDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value." ::= { lgpPduAuxMeasEntry 85 } lgpPduAuxMeasTempThrshldOvrWarnDegC OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value." ::= { lgpPduAuxMeasEntry 90 } lgpPduAuxMeasHum OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "Relative Humidity measured at the humidity sensor." ::= { lgpPduAuxMeasEntry 95 } lgpPduAuxMeasHumThrshldUndrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value." ::= { lgpPduAuxMeasEntry 100 } lgpPduAuxMeasHumThrshldOvrAlm OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value." ::= { lgpPduAuxMeasEntry 105 } lgpPduAuxMeasHumThrshldUndrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value." ::= { lgpPduAuxMeasEntry 110 } lgpPduAuxMeasHumThrshldOvrWarn OBJECT-TYPE SYNTAX Unsigned32 UNITS "0.1 percent Relative Humidity" MAX-ACCESS read-write STATUS current DESCRIPTION "Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value." ::= { lgpPduAuxMeasEntry 115 } lgpPduAuxMeasDrClosureState OBJECT-TYPE SYNTAX INTEGER { not-specified(0), open(1), closed(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The state of a door sensor measurement. not-specified The door state is unknown. open The door is in the open state. closed The door is in the closed state." ::= { lgpPduAuxMeasEntry 120 } lgpPduAuxMeasDrClosureConfig OBJECT-TYPE SYNTAX INTEGER { disabled(0), alarm-when-open(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Configure door state alarms. This object provides the ability to select when a door closure measurement should cause an alarm. disabled The door state will never result in alarm. alarm-when-open Activate an alarm when the door state becomes open." ::= { lgpPduAuxMeasEntry 125 } lgpPduAuxMeasCntctClosureState OBJECT-TYPE SYNTAX INTEGER { not-specified(0), open(1), closed(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The state of a contact closure sensor measurement. not-specified The contact closure state is unknown. open The contact closure is in the open state. closed The contact closure is in the closed state." ::= { lgpPduAuxMeasEntry 130 } lgpPduAuxMeasCntctClosureConfig OBJECT-TYPE SYNTAX INTEGER { disabled(0), alarm-when-open(1), alarm-when-closed(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Configure contact closure state alarms. This object provides the ability to select when a contact closure measurement should activate an alarm. disabled The contact closure state will never result in alarm. alarm-when-open Activate an alarm when the contact closure state becomes open. alarm-when-closed Activate an alarm when the contact closure state becomes closed." ::= { lgpPduAuxMeasEntry 135 } lgpPduAuxMeasDiffPressure OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 Pascal" MAX-ACCESS read-only STATUS current DESCRIPTION "Pressure difference measured at the differential pressure sensor." ::= { lgpPduAuxMeasEntry 140 } lgpPduAuxMeasDiffPressureThrshldUndrAlm OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 Pascal" MAX-ACCESS read-write STATUS current DESCRIPTION "Under differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or below this value." ::= { lgpPduAuxMeasEntry 145 } lgpPduAuxMeasDiffPressureThrshldOvrAlm OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 Pascal" MAX-ACCESS read-write STATUS current DESCRIPTION "Over differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or above this value." ::= { lgpPduAuxMeasEntry 150 } lgpPduAuxMeasDiffPressureThrshldUndrWarn OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 Pascal" MAX-ACCESS read-write STATUS current DESCRIPTION "Under differential pressure warning threshold. A warning is activated if the differential pressure is equal to or below this value." ::= { lgpPduAuxMeasEntry 155 } lgpPduAuxMeasDiffPressureThrshldOvrWarn OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 Pascal" MAX-ACCESS read-write STATUS current DESCRIPTION "Over differential pressure warning threshold. A warning is activated if the differential pressure is equal to or above this value." ::= { lgpPduAuxMeasEntry 160 } lgpPduAuxMeasLeakDetectState OBJECT-TYPE SYNTAX INTEGER { not-specified(0), no-leak-detected(1), leak-detected(2), leak-detection-pending(3), cable-fault(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "not-specified The leak detection state is unknown. no-leak-detected No leak has been detected. leak-detected A leak has been detected. leak-detection-pending Characterization of possible leak is pending further analysis based on new data received from the sensor. This state may not occur at all, but if it does, it should occur only for a small amount of time before transitioning to no-leak-detected or leak-detected. cable-fault A fault in the cable has been detected (for example, a disconnected cable). The sensor will not be able to detect a leak. " ::= { lgpPduAuxMeasEntry 165 } lgpPduAuxMeasOrderTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpPduAuxMeasOrderEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains a list of the PDU's Auxiliary Sensors and their respective 'location' in the lgpPduAuxMeasTable table. This table contains 1 row, for potential sensor for each PDU. The rows in this table are created by the agent based on the maximum number of sensor's supported for each PDU. Each row in the table represents an auxiliary sensor, identified by its factory assigned serial number and its placement in the lgpPduAuxMeasTable. If all serial numbers in this table are empty strings then the location of the sensors in the lgpPduAuxMeasTable will default to the agent's default placement algorithm. If sensors in the lgpPduAuxMeasTable and are not represented by an entry in this table then the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable, and other display mediums, will be determined by the agent, but in no case will an unrepresented sensor occupy a position reserved for a sensor present in this table. Those unrepresented sensor's display location is not guaranteed to be consistent across reboots or rediscovery actions on the sensor bus. Only sensors represented in this table are guarantted consistent placement as specified by their index entries (position) in this table. Note that it is possible to have entries in this table representing sensors that may not exist on the given PDU at runtime. These allocated by not present sensors will reduce the total number of sensors that can be displayed for the given PDU." ::= { lgpPduAuxiliarySensors 20 } lgpPduAuxMeasOrderEntry OBJECT-TYPE SYNTAX LgpPduAuxMeasOrderEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasOrderTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify a Auxiliary Sensor within this agent." INDEX { lgpPduEntryIndex, lgpPduAuxSensorOrderIndex } ::= { lgpPduAuxMeasOrderTable 1 } LgpPduAuxMeasOrderEntry ::= SEQUENCE { lgpPduEntryIndex Unsigned32, lgpPduAuxSensorOrderIndex Unsigned32, lgpPduAuxMeasOrderSensorSerialNum DisplayString } lgpPduAuxSensorOrderIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "Index representing the position within the sensor string on the given PDU" ::= { lgpPduAuxMeasOrderEntry 5 } lgpPduAuxMeasOrderSensorSerialNum OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The sensor's globally unique serial number assigned at the time of manufacture. The sensor represented by this serial number will be, if discovered, by the agent placed in the lgpPduAuxMeasTable at the location specified by the index entries herein. A empty string in this object indicates an open display position that can be occupied by any sensor not given a specific display position in this table." ::= { lgpPduAuxMeasOrderEntry 15 } END