-- ============================================================================= LIEBERT-GP-SYSTEM-MIB DEFINITIONS ::= BEGIN IMPORTS OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, NOTIFICATION-TYPE, Integer32, Unsigned32 FROM SNMPv2-SMI DisplayString FROM SNMPv2-TC lgpSystem, liebertSystemModuleReg FROM LIEBERT-GP-REGISTRATION-MIB sysUpTime FROM RFC1213-MIB lgpAgentConnectedDeviceCount, lgpAgentDeviceIndex FROM LIEBERT-GP-AGENT-MIB ; -- ============================================================================= -- Module Identification and Registration -- ============================================================================= -- liebertSystemModule MODULE-IDENTITY LAST-UPDATED "200811170000Z" ORGANIZATION "Liebert Corporation" CONTACT-INFO "Contact: Technical Support Postal: Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH, 43229 US Tel: +1 (800) 222-5877 E-mail: liebert.monitoring@vertivco.com Web: www.vertivco.com Author: Gregory M. Hoge" DESCRIPTION "The MIB module used to specify Liebert Controller OIDs Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification." REVISION "200811170000Z" DESCRIPTION "Added support for NXL unit." REVISION "200807020000Z" DESCRIPTION "Added missing items to the IMPORT statement" REVISION "200801100000Z" DESCRIPTION "Add system notifications sub-tree and modified contact email address." REVISION "200705290000Z" DESCRIPTION "Added support for XDF Unit." REVISION "200602220000Z" DESCRIPTION "Added support for Liebert DS Unit." ::= { liebertSystemModuleReg 1 } -- ============================================================================= -- lgpSystem - Liebert System Groups -- ============================================================================= lgpSysStatistics OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Statistics object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Statistics Group." ::= { lgpSystem 1 } lgpSysStatus OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Status object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Status Group." ::= { lgpSystem 2 } lgpSysSettings OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Settings object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Settings Group." ::= { lgpSystem 3 } lgpSysControl OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Control object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Control Group." ::= { lgpSystem 4 } lgpSysTime OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Time object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Time Group." ::= { lgpSystem 5 } lgpSysMaintenance OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Maintenance object identifiers." REFERENCE "The registrations for the objects in this sub-tree are defined below in the sub-section titled Liebert System Maintenance Group." ::= { lgpSystem 6 } lgpSysEventDescription OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) MAX-ACCESS read-only STATUS current DESCRIPTION "An ASCII textual description for the event. This object is primarily used in the varbind of some notifications to provide a simple human-readable description." ::= { lgpSystem 7 } lgpSysEventNotifications OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register Liebert System Notification object identifiers." ::= { lgpSystem 8 } -- ----------------------------------------------------------------------------- -- Device Component Group -- ----------------------------------------------------------------------------- lgpSysDeviceComponentGroup OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree registers well known device components." REFERENCE "These well known components are referenced in the 'lgpSysDeviceComponentDescr' column in the 'lgpSysDeviceComponentTable'." ::= { lgpSystem 9 } -- ----------------------------------------------------------------------------- -- Device Component Table -- ----------------------------------------------------------------------------- lgpSysDeviceComponentTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpSysDeviceComponentEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of components of devices identified by their serial number and or model number. This table contains zero, one, or many rows. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpSysDeviceComponentGroup 1 } lgpSysDeviceComponentEntry OBJECT-TYPE SYNTAX LgpSysDeviceComponentEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This entry defines the contents of the columns for the table 'lgpSysDeviceComponentTable'." INDEX { lgpAgentDeviceIndex, lgpSysDeviceComponentIndex } ::= { lgpSysDeviceComponentTable 1 } LgpSysDeviceComponentEntry ::= SEQUENCE { lgpSysDeviceComponentIndex Unsigned32, lgpSysDeviceComponentDescr OBJECT IDENTIFIER, lgpSysDeviceComponentSerialNum DisplayString (SIZE (255)), lgpSysDeviceComponentModelNum DisplayString (SIZE (255)) } lgpSysDeviceComponentIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index indicating the row in the table 'lgpSysDeviceComponentTable' for a component entry." ::= { lgpSysDeviceComponentEntry 1 } lgpSysDeviceComponentDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER MAX-ACCESS read-only STATUS current DESCRIPTION "An OID representing a component of the device indicated by the index lgpAgentDeviceIndex." REFERENCE "The object identifiers in this column can be found in the sub-tree 'lgpSysDeviceComponentWellknown'." ::= { lgpSysDeviceComponentEntry 2 } lgpSysDeviceComponentSerialNum OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) MAX-ACCESS read-only STATUS current DESCRIPTION "This is the serial number of the component described by the OID 'lgpSysDeviceComponentDescr'. This data is intended for display / human consumption. Do not use this field for determining programmatic behavior." ::= { lgpSysDeviceComponentEntry 3 } lgpSysDeviceComponentModelNum OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) MAX-ACCESS read-only STATUS current DESCRIPTION "This is the model identifier of the component described by the OID 'lgpSysDeviceComponentDescr'. This data is intended for display / human consumption. Do not use this field for determining programmatic behavior." ::= { lgpSysDeviceComponentEntry 4 } lgpSysDeviceComponentWellknown OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree registers well known Liebert System Components." REFERENCE "These well known measurement identifiers are referenced in the 'lgpSysDeviceComponentDescr' column in the 'lgpSysDeviceComponentTable'." ::= { lgpSysDeviceComponentGroup 5 } lgpSysDeviceBatCabinet OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register a battery cabinet component. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS (Single-Module System) the first index is always 1. Example: lgpSysDeviceComponentCabinet.2.4 'lgpSysDeviceCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4 in second module" ::= { lgpSysDeviceComponentWellknown 5 } lgpSysDeviceParallelCabinet OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register a parallel cabinet." ::= { lgpSysDeviceComponentWellknown 6 } lgpSysDeviceMaintBypass OBJECT-IDENTITY STATUS current DESCRIPTION "This sub-tree is used to register the maintenance bypass." ::= { lgpSysDeviceComponentWellknown 7 } -- ============================================================================= -- lgpSysNotifications - Liebert System Notifications Group -- ============================================================================= lgpSysNotification NOTIFICATION-TYPE OBJECTS { sysUpTime, lgpSysEventDescription } STATUS current DESCRIPTION "This notification is a generic notification intended for direct user visibility. The user event description identifies the system condition that has occurred. This text will be prefixed with either 'Active:', 'Cleared:', or 'Message:' depending on the state of the event. Note: That a prefix of 'Message:' identifies a stateless event and as such there will be no corresponding 'Cleared:' trap sent." ::= { lgpSysEventNotifications 1 } lgpSysNormal NOTIFICATION-TYPE OBJECTS { sysUpTime, lgpAgentConnectedDeviceCount } STATUS current DESCRIPTION "The system has returned to a normal operating state. This implies prior to the generation of this event the system was operating in a state where one or more alarm or warning conditions were present. All of those alarms or conditions have now cleared. NOTE: This notification may be generated after a short delay during a cold boot of the system -- if no alarms or conditions are present in the monitored device(s) at that time." ::= { lgpSysEventNotifications 2 } -- ============================================================================= -- lgpSysStatistics - Liebert System Statistics Group -- ============================================================================= lgpSysStatisticsRunHrs OBJECT-TYPE SYNTAX Unsigned32 UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated run hours of the system." ::= { lgpSysStatistics 1 } -- ============================================================================= -- lgpSysStatus - Liebert System Status Group -- ============================================================================= lgpSysSelfTestResult OBJECT-TYPE SYNTAX INTEGER { unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), inhibited(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "The outcome of the previous self-test." ::= { lgpSysStatus 1 } lgpSysState OBJECT-TYPE SYNTAX INTEGER { normalOperation(1), startUp(2), normalWithWarning(3), normalWithAlarm(4), abnormalOperation(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "The operating status for the system. The intent of this data is to provide a high level status of the system. The possible states are: normalOperation(1) The system is operating normally with no active warnings or alarms. startUp(2) The system is in a startup state (initializing). Monitoring operations and information may not be fully supported at this time. This state will clear automatically when the system is fully initialized and ready to accept monitoring commands. normalWithWarning(3) The system is operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(4) The system is operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(5) They system is operating abnormally. There is a failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited." ::= { lgpSysStatus 2 } -- ============================================================================= -- lgpSysSettings - Liebert System Settings Group -- ============================================================================= lgpSysAudibleAlarm OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The state of the audible alarm of the device." ::= { lgpSysSettings 1 } -- ============================================================================= -- lgpSysControl - Liebert System Control Group -- ============================================================================= lgpSysSelfTest OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Self-Test Command. This command will initiate a system self-test of the system. If already initiated, this command will abort the self-test. This command should be sent with a parameter of 1. This variable doesn't return a value when read." ::= { lgpSysControl 1 } lgpSysControlOperationOnOff OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "This object allows control of the system functionality. This will not affect the communications or control of the system, so that once turned off, the system operation can be restored by setting this value to 'on'." ::= { lgpSysControl 2 } -- ============================================================================= -- lgpSysTime - Liebert System Time Group -- ============================================================================= lgpSysTimeEpoch OBJECT-TYPE SYNTAX Unsigned32 UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "The present time of the system. This time is represented as the number of seconds since the epoch of 1970-01-01 00:00:00 GMT." ::= { lgpSysTime 1 } -- ============================================================================= -- lgpSysMaintenance - Liebert System Maintenance Group -- ============================================================================= lgpSysMaintenanceCapacity OBJECT-TYPE SYNTAX Unsigned32 UNITS "percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The relative percentage of time that has elapsed since the last scheduled maintenance was performed. When this value reaches 100%, the device is due for another scheduled maintenance procedure." ::= { lgpSysMaintenance 1 } lgpSysMaintenanceYear OBJECT-TYPE SYNTAX Unsigned32 UNITS "year" MAX-ACCESS read-only STATUS current DESCRIPTION "The year in which the next scheduled service is due" ::= { lgpSysMaintenance 2 } lgpSysMaintenanceMonth OBJECT-TYPE SYNTAX Unsigned32 UNITS "month" MAX-ACCESS read-only STATUS current DESCRIPTION "The month in which the next scheduled service is due" ::= { lgpSysMaintenance 3 } END