-- RPS S.p.A enterprise MIB definition -- Copyright (c) RPS S.p.A. -- Version: 1.0.3 by Michele Marcon -- Date: 29.05.2017 -- Title: RIELLOUPS-MIB -- RielloUPS-MIB { iso org(3) dod(6) internet(1) private(4) -- enterprises(1) riello(5491) } -- ************************************************************************ -- ************************************************************************ RIELLOUPS-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, Counter32, Gauge32, Integer32 FROM SNMPv2-SMI DisplayString, TimeStamp, TimeInterval, TestAndIncr, AutonomousType, TEXTUAL-CONVENTION FROM SNMPv2-TC MODULE-COMPLIANCE, OBJECT-GROUP FROM SNMPv2-CONF Gauge, Counter FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 rielloMIB FROM RIELLO-MIB; rupsMIB OBJECT IDENTIFIER ::= { rielloMIB 10 } PositiveInteger ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "This data type is a non-zero and non-negative value." SYNTAX INTEGER (1..2147483647) NonNegativeInteger ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "This data type is a non-negative value." SYNTAX INTEGER (0..2147483647) rupsObjects OBJECT IDENTIFIER ::= { rupsMIB 1 } rupsIdent OBJECT IDENTIFIER ::= { rupsObjects 1 } rupsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the UPS manufacturer." ::= { rupsIdent 1 } rupsIdentModel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Model designation." ::= { rupsIdent 2 } rupsIdentUPSSoftwareVersion OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations." ::= { rupsIdent 3 } rupsIdentAgentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations." ::= { rupsIdent 4 } rupsIdentName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the UPS. This object should be set by the administrator." ::= { rupsIdent 5 } rupsIdentAttachedDevices OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator." ::= { rupsIdent 6 } rupsIdentIOConfiguration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS IO configuration." ::= { rupsIdent 7 } rupsIdentUpsType OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS type." ::= { rupsIdent 8 } rupsIdentNominalPowerVA OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal power VA." ::= { rupsIdent 9 } rupsIdentNominalPowerW OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal power W." ::= { rupsIdent 10 } rupsIdentBatteryVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal battery voltage." ::= { rupsIdent 11 } rupsIdentBatteryCapacity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal battery capacity." ::= { rupsIdent 12 } rupsIdentOutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal output voltage." ::= { rupsIdent 13 } rupsIdentOutputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS nominal output frequency." ::= { rupsIdent 14 } rupsBattery OBJECT IDENTIFIER ::= { rupsObjects 2 } rupsBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than rupsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to rupsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output)." ::= { rupsBattery 1 } rupsSecondsOnBattery OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS seconds ACCESS read-only STATUS mandatory DESCRIPTION "If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power." ::= { rupsBattery 2 } rupsEstimatedMinutesRemaining OBJECT-TYPE SYNTAX PositiveInteger -- UNITS minutes ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off." ::= { rupsBattery 3 } rupsEstimatedChargeRemaining OBJECT-TYPE SYNTAX INTEGER -- UNITS percent ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the battery charge remaining expressed as a percent of full charge." ::= { rupsBattery 4 } rupsBatteryVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present battery voltage." ::= { rupsBattery 5 } rupsBatteryCurrent OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 Amp DC ACCESS read-only STATUS mandatory DESCRIPTION "The present battery current." ::= { rupsBattery 6 } rupsBatteryTemperature OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS degrees Centigrade ACCESS read-only STATUS mandatory DESCRIPTION "The ambient temperature at or near the UPS Battery casing." ::= { rupsBattery 7 } rupsBatteryPositiveVoltage OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS V ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery positive voltage." ::= { rupsBattery 8 } rupsBatteryNegativeVoltage OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS V ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery negative voltage." ::= { rupsBattery 9 } rupsBatteryPositiveCurrent OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 A ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery positive current." ::= { rupsBattery 10 } rupsBatteryNegativeCurrent OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 A ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery positive current." ::= { rupsBattery 11 } rupsIsCharging OBJECT-TYPE SYNTAX INTEGER { discharging(0), charging(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The charging/discharging status of the battery" ::= { rupsBattery 12 } rupsInput OBJECT IDENTIFIER ::= { rupsObjects 3 } rupsInputLineBads OBJECT-TYPE SYNTAX Counter ACCESS read-only STATUS mandatory DESCRIPTION "A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance." ::= { rupsInput 1 } rupsInputNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of input lines utilized in this device. This variable indicates the number of rows in the input table." ::= { rupsInput 2 } rupsInputTable OBJECT-TYPE SYNTAX SEQUENCE OF RUpsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the value of upsInputNumLines." ::= { rupsInput 3 } rupsInputEntry OBJECT-TYPE SYNTAX RUpsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input line." INDEX { rupsInputLineIndex } ::= { rupsInputTable 1 } RUpsInputEntry ::= SEQUENCE { rupsInputLineIndex PositiveInteger, rupsInputFrequency NonNegativeInteger, rupsInputVoltage NonNegativeInteger, rupsInputCurrent NonNegativeInteger, rupsInputTruePower NonNegativeInteger } rupsInputLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS not-accessible STATUS mandatory DESCRIPTION "The input line identifier." ::= { rupsInputEntry 1 } rupsInputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present input frequency." ::= { rupsInputEntry 2 } rupsInputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input voltage." ::= { rupsInputEntry 3 } rupsInputCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input current." ::= { rupsInputEntry 4 } rupsInputTruePower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input true power." ::= { rupsInputEntry 5 } rupsOutput OBJECT IDENTIFIER ::= { rupsObjects 4 } rupsOutputSource OBJECT-TYPE SYNTAX INTEGER { other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7) } ACCESS read-only STATUS mandatory DESCRIPTION "The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker." ::= { rupsOutput 1 } rupsOutputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present output frequency." ::= { rupsOutput 2 } rupsOutputNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of output lines utilized in this device. This variable indicates the number of rows in the output table." ::= { rupsOutput 3 } rupsOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF RUpsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the value of rupsOutputNumLines." ::= { rupsOutput 4 } rupsOutputEntry OBJECT-TYPE SYNTAX RUpsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output line." INDEX { rupsOutputLineIndex } ::= { rupsOutputTable 1 } RUpsOutputEntry ::= SEQUENCE { rupsOutputLineIndex PositiveInteger, rupsOutputVoltage NonNegativeInteger, rupsOutputCurrent NonNegativeInteger, rupsOutputPower NonNegativeInteger, rupsOutputPercentLoad INTEGER, rupsOutputPeakCurrent NonNegativeInteger } rupsOutputLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS not-accessible STATUS mandatory DESCRIPTION "The output line identifier." ::= { rupsOutputEntry 1 } rupsOutputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The present output voltage." ::= { rupsOutputEntry 2 } rupsOutputCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The present output current." ::= { rupsOutputEntry 3 } rupsOutputPower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The present output true power." ::= { rupsOutputEntry 4 } rupsOutputPercentLoad OBJECT-TYPE SYNTAX INTEGER -- UNITS percent ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA." ::= { rupsOutputEntry 5 } rupsOutputPeakCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The present output peak current." ::= { rupsOutputEntry 6 } rupsBypass OBJECT IDENTIFIER ::= { rupsObjects 5 } rupsBypassFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass frequency." ::= { rupsBypass 1 } rupsBypassNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table." ::= { rupsBypass 2 } rupsBypassTable OBJECT-TYPE SYNTAX SEQUENCE OF RUpsBypassEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of bypass table entries. The number of entries is given by the value of rupsBypassNumLines." ::= { rupsBypass 3 } rupsBypassEntry OBJECT-TYPE SYNTAX RUpsBypassEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular bypass input." INDEX { rupsBypassLineIndex } ::= { rupsBypassTable 1 } RUpsBypassEntry ::= SEQUENCE { rupsBypassLineIndex PositiveInteger, rupsBypassVoltage NonNegativeInteger, rupsBypassCurrent NonNegativeInteger, rupsBypassPower NonNegativeInteger } rupsBypassLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS not-accessible STATUS mandatory DESCRIPTION "The bypass line identifier." ::= { rupsBypassEntry 1 } rupsBypassVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass voltage." ::= { rupsBypassEntry 2 } rupsBypassCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass current." ::= { rupsBypassEntry 3 } rupsBypassPower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The present true power conveyed by the bypass." ::= { rupsBypassEntry 4 } rupsAlarm OBJECT IDENTIFIER ::= { rupsObjects 6 } rupsAlarmsPresent OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The present number of active alarm conditions." ::= { rupsAlarm 1 } rupsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF RUpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with rupsAlarmId equal to 1, and increments the value of rupsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of rupsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because rupsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), rupsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of rupsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of rupsAlarmsPresent." ::= { rupsAlarm 2 } rupsAlarmEntry OBJECT-TYPE SYNTAX RUpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular alarm." INDEX { rupsAlarmId } ::= { rupsAlarmTable 1 } RUpsAlarmEntry ::= SEQUENCE { rupsAlarmId PositiveInteger, rupsAlarmDescr OBJECT IDENTIFIER, rupsAlarmTime PositiveInteger } rupsAlarmId OBJECT-TYPE SYNTAX PositiveInteger ACCESS not-accessible STATUS mandatory DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant." ::= { rupsAlarmEntry 1 } rupsAlarmDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS mandatory DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { rupsAlarmEntry 2 } rupsAlarmTime OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS mandatory DESCRIPTION "The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of rupsAlarmTime shall equal 0." ::= { rupsAlarmEntry 3 } rupsWellKnownAlarms OBJECT IDENTIFIER ::= { rupsAlarm 3 } rupsAlarmBatteryBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 1 } rupsAlarmOnBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 2 } rupsAlarmLowBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 3 } rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 4 } rupsAlarmTempBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 5 } rupsAlarmFault OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 6 } rupsAlarmInternal OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 7 } rupsAlarmOutputOverload OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 8 } rupsAlarmOnBypass OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 9 } rupsAlarmBypassBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 10 } rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 11 } -- -- The Test Group -- rupsTest OBJECT IDENTIFIER ::= { rupsObjects 7 } rupsTestId OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-write STATUS optional DESCRIPTION "The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the rupsTestId variable to rupsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned." ::= { rupsTest 1 } -- see [6] for more information on the semantics of objects with -- syntax of TestAndIncr rupsTestSpinLock OBJECT-TYPE SYNTAX TestAndIncr ACCESS read-write STATUS optional DESCRIPTION "A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1." ::= { rupsTest 2 } rupsTestResultsSummary OBJECT-TYPE SYNTAX INTEGER { donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6) } ACCESS read-only STATUS optional DESCRIPTION "The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results." ::= { rupsTest 3 } rupsTestResultsDetail OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS optional DESCRIPTION "Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned." ::= { rupsTest 4 } rupsTestStartTime OBJECT-TYPE SYNTAX TimeStamp ACCESS read-only STATUS optional DESCRIPTION "The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0." ::= { rupsTest 5 } rupsTestElapsedTime OBJECT-TYPE SYNTAX TimeInterval ACCESS read-only STATUS optional DESCRIPTION "The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0." ::= { rupsTest 6 } -- -- Well known tests. -- rupsWellKnownTests OBJECT IDENTIFIER ::= { rupsTest 7 } rupsTestNoTestsInitiated OBJECT IDENTIFIER -- "No tests have been initiated and no test is in -- progress." ::= { rupsWellKnownTests 1 } rupsTestAbortTestInProgress OBJECT IDENTIFIER -- "The test in progress is to be aborted / the test in -- progress was aborted." ::= { rupsWellKnownTests 2 } rupsTestGeneralSystemsTest OBJECT IDENTIFIER -- "The manufacturer's standard test of UPS device -- systems." ::= { rupsWellKnownTests 3 } rupsTestQuickBatteryTest OBJECT IDENTIFIER -- "A test that is sufficient to determine if the battery -- needs replacement." ::= { rupsWellKnownTests 4 } rupsTestDeepBatteryCalibration OBJECT IDENTIFIER -- "The system is placed on battery to a discharge level, -- set by the manufacturer, sufficient to determine -- battery replacement and battery run-time with a high -- degree of confidence. WARNING: this test will leave -- the battery in a low charge state and will require -- time for recharging to a level sufficient to provide -- normal battery duration for the protected load." ::= { rupsWellKnownTests 5 } rupsControl OBJECT IDENTIFIER ::= { rupsObjects 8 } rupsShutdownType OBJECT-TYPE SYNTAX INTEGER { output(1), system(2) } ACCESS read-write STATUS mandatory DESCRIPTION "This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off." ::= { rupsControl 1 } rupsShutdownAfterDelay OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect." ::= { rupsControl 2 } rupsStartupAfterDelay OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted." ::= { rupsControl 3 } rupsRebootWithDuration OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored." ::= { rupsControl 4 } rupsAutoRestart OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied." ::= { rupsControl 5 } rupsTemperature OBJECT IDENTIFIER ::= { rupsObjects 10 } rupsSystemTemperature OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 1 } rupsPowerTemperature1 OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 2 } rupsPowerTemperature2 OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 3 } rupsPowerTemperature3 OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 4 } rupsChargerTemperature OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 5 } rupsBatteryPositiveTemperature OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 6 } rupsBatteryNegativeTemperature OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 7 } rupsBatteryExternalTemperature OBJECT-TYPE SYNTAX INTEGER -- UNITS degree Celsius ACCESS read-only STATUS mandatory DESCRIPTION "The present temperature." ::= { rupsTemperature 8 } rupsMPS OBJECT IDENTIFIER ::= { rupsObjects 20 } mpsAlarmGroupS OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group s." ::= { rupsMPS 1 } mpsAlarmGroupC OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group c." ::= { rupsMPS 2 } mpsAlarmGroupB OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group b." ::= { rupsMPS 3 } mpsAlarmGroupR OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group r." ::= { rupsMPS 4 } mpsAlarmGroupRI OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group RI." ::= { rupsMPS 5 } mpsAlarmGroupI OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group I." ::= { rupsMPS 6 } mpsAlarmGroupA0 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A0." ::= { rupsMPS 7 } mpsAlarmGroupA1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A1." ::= { rupsMPS 8 } mpsAlarmGroupA2 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A2." ::= { rupsMPS 9 } mpsAlarmGroupA3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A3." ::= { rupsMPS 10 } mpsAlarmGroupA4 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A4." ::= { rupsMPS 11 } mpsAlarmGroupA5 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The alarm group A5." ::= { rupsMPS 12 } rupsMST OBJECT IDENTIFIER ::= { rupsObjects 21 } mstWarningGroupW0W1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The anomaly group W0W1." ::= { rupsMST 1 } mstAnomalyGroupA0A1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The anomaly group A0A1." ::= { rupsMST 2 } mstAnomalyGroupA2A3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The anomaly group A2A3." ::= { rupsMST 3 } mstAnomalyGroupA4A5 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The anomaly group A4A5." ::= { rupsMST 4 } mstFaultGroupF0F1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The fault group F0F1." ::= { rupsMST 5 } mstFaultGroupF2F3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The fault group F2F3." ::= { rupsMST 6 } mstFaultGroupF4F5 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The fault group F4F5." ::= { rupsMST 7 } mstLockGroupL0L1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The lock group L0L1." ::= { rupsMST 8 } mstLockGroupL2L3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The lock group L2L3." ::= { rupsMST 9 } mstLockGroupL4L5 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The lock group L4L5." ::= { rupsMST 10 } mstEventGroupE0E1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The event group E0E1." ::= { rupsMST 11 } rupsMPW OBJECT IDENTIFIER ::= { rupsObjects 22 } mpwSystemStatusGroup1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The system status group 1." ::= { rupsMPW 1 } mpwSystemStatusGroup2 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The system status group 2." ::= { rupsMPW 2 } mpwSystemStatusGroup3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The system status group 3." ::= { rupsMPW 3 } mpwBypassModuleAlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bypass module alarm group." ::= { rupsMPW 4 } mpwPowerModule1AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 1 alarm group." ::= { rupsMPW 5 } mpwPowerModule2AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 2 alarm group." ::= { rupsMPW 6 } mpwPowerModule3AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 3 alarm group." ::= { rupsMPW 7 } mpwPowerModule4AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 4 alarm group." ::= { rupsMPW 8 } mpwPowerModule5AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 5 alarm group." ::= { rupsMPW 9 } mpwPowerModule6AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 6 alarm group." ::= { rupsMPW 10 } mpwPowerModule7AlarmGroup OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power module 7 alarm group." ::= { rupsMPW 11 } mpwBypassModuleStatus OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The bypass module status." ::= { rupsMPW 12 } mpwPowerModule1Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 1." ::= { rupsMPW 13 } mpwPowerModule2Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 2." ::= { rupsMPW 14 } mpwPowerModule3Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 3." ::= { rupsMPW 15 } mpwPowerModule4Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 4." ::= { rupsMPW 16 } mpwPowerModule5Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 5." ::= { rupsMPW 17 } mpwPowerModule6Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 6." ::= { rupsMPW 18 } mpwPowerModule7Status OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The status of power module 7." ::= { rupsMPW 19 } mpwControl OBJECT IDENTIFIER ::= { rupsMPW 20 } mpwCommandCode OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Command code." ::= { mpwControl 1 } mpwShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Shutdown delay." ::= { mpwControl 2 } mpwRestoreDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Restore delay." ::= { mpwControl 3 } mpwModuleApplyCommand OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Module apply command" ::= { mpwControl 4 } mpwCommandResult OBJECT-TYPE SYNTAX INTEGER -- UNITS RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "Result of command." ::= { mpwControl 5 } rupsTraps OBJECT IDENTIFIER ::= { rupsMIB 2 } rupsTrapOnBattery TRAP-TYPE ENTERPRISE rupsTraps VARIABLES { rupsEstimatedMinutesRemaining, rupsSecondsOnBattery, rupsConfigLowBattTime } DESCRIPTION "The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery." ::= 1 rupsTrapTestCompleted TRAP-TYPE ENTERPRISE rupsTraps DESCRIPTION "This trap is sent upon completion of a UPS diagnostic test." ::= 2 rupsTrapAlarmEntryAdded TRAP-TYPE ENTERPRISE rupsTraps DESCRIPTION "This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for rupsAlarmOnBattery and rupsAlarmTestInProgress." ::= 3 rupsTrapAlarmEntryRemoved TRAP-TYPE ENTERPRISE rupsTraps DESCRIPTION "This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for rupsAlarmTestInProgress." ::= 4 END