-- Toshiba MIB -- MIB for Toshiba G9000 Uninterruptible Power Supply -- --{iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) -- toshiba(186) equ(1) equups(19) ticups(2) rmti4 (5) upsG9000-G2020(1)} --============================================================================= TIC-RMTI4-G9000-G2020-MIB DEFINITIONS ::= BEGIN --============================================================================= -- Update : September 28, 2016 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: renamed MIB file from upsG9000 to upsG9000-G2020 --============================================================================= -- Update : May 28, 2015 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: Added in description warning for upsTrapBatteryLow, upsTrapBatteryLowClear and upsAlarmBatteryLow. -- : Added in description warning for upsTrapBatteryDepleted, upsTrapBatteryDepletedClear and upsAlarmBatteryDepleted. -- : Added in description warning for upsTrapAsyncOperation, upsTrapAsyncOperationClear and upsAlarmAsyncOperation. -- : Added in description warning for upsTrapRemotEyeCommError, upsTrapRemotEyeCommErrorClear and upsAlarmRemotEyeCommError. -- : Added in description warning for upsTrapOnBypass, upsTrapOnBypassClear and upsAlarmOnBypass. -- : Added in description info for upsTrapPowerFailure, upsTrapPowerFailureClear, and upsAlarmPowerFailure --============================================================================= -- Update : March 19, 2015 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: renamed upsConfigInputRatedFrequency to upsConfigRatedInputFrequency -- : Added upsAlarmUserDefinedOverload -- : Added upsConfigUserDefinedOverloadSetPoint -- : Added upsTrapUserDefinedOverload -- : Added upsTrapUserDefinedOverloadClear --============================================================================= -- Update : February 3, 2015 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: renamed upsConfigInputRatedFrequency to upsConfigRatedInputFrequency --============================================================================= -- Update : January 30, 2015 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: Changed Access Level for upsConfigBatteryInstallationDate to R/W -- : Changed Access Level for upsConfigPassword to R/W --============================================================================= -- Update: November 13, 2014 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: Changed upsOutputCurrentPhaseA units to "RMS Amps" -- : Changed upsOutputCurrentPhaseB units to "RMS Amps" -- : Changed upsOutputCurrentPhaseC units to "RMS Amps" --============================================================================= -- Update : October 29, 2014 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: Changed upsInputCurrentPhaseA units to "0.1 RMS Amps" -- : Changed upsInputCurrentPhaseB units to "0.1 RMS Amps" -- : Changed upsInputCurrentPhaseC units to "0.1 RMS Amps" -- : Changed upsOutputCurrentPhaseA units to "0.1 RMS Amps" -- : Changed upsOutputCurrentPhaseB units to "0.1 RMS Amps" -- : Changed upsOutputCurrentPhaseC units to "0.1 RMS Amps" --============================================================================= -- Update : June 18, 2014 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: Changed upsInputCurrentPhaseA units to "RMS Amps" -- : Changed upsInputCurrentPhaseB units to "RMS Amps" -- : Changed upsInputCurrentPhaseC units to "RMS Amps" -- : Changed upsOutputCurrentPhaseA units to "RMS Amps" -- : Changed upsOutputCurrentPhaseB units to "RMS Amps" -- : Changed upsOutputCurrentPhaseC units to "RMS Amps" --============================================================================= -- Update : January 13, 2014 -- By : Edwin Rubio, Toshiba International Corp. -- Revised: -- : upsBattery 14: upsBatteryInstalledDate SYNTAX DisplayString from size 8 to 10 -- : upsIdent 4: upsIdentName changed to upsIdentSysName -- : upsInput 1: upsInputNumLines changed to upsInputNumOfPhases -- : upsInput 5: upsInputLLVoltagePercentAB added to MIB -- : upsInput 6: upsInputLLVoltagePercentBC added to MIB -- : upsInput 7: upsInputLLVoltagePercentCA added to MIB -- : upsInput 16: upsInputRatedLLVoltage added to MIB -- : upsOutput 2: upsOutputNumLines changed to upsOutputNumOfPhases -- : upsOutput 6: upsOutputPhaseCurrentA changed to upsOutputCurrentPhaseA -- : upsOutput 7: upsOutputPhaseCurrentB changed to upsOutputCurrentPhaseB -- : upsOutput 8: upsOutputPhaseCurrentC changed to upsOutputCurrentPhaseC -- : upsOutput 13: upsOutputActivePower changed to upsOutputTotalAcitvePower -- : upsOutput 14: upsOutputActivePowerPercent changed to upsOutputTotalActivePowerPercent -- : upsOutput 16: upsOutputRatedActivePower added to MIB -- : upsOutput 17: upsOutputApparentPower changed to upsOutputRatedApparentPower -- : upsOutput 18: upsOutputRatedLLVoltage added to MIB -- : upsBypass 1: upsBypassNumLines changed to upsBypassNumOfPhases -- : upsBattery 2: upsSecondsOnBattery changed to upsElapsedTimeOnBatteryPower -- : upsBattery 3: upsEstimatedMinutesRemaining changed to upsEstimatedBatteryRuntime -- : upsBattery 6: upsBatteryEstimatedChargeRemaining changed to upsBatteryEstimatedCharge -- : upsBattery 10: upsBatteryInSeries added to MIB -- : upsBattery 11: upsBatteryNumStrings added to MIB -- : upsBattery 12: upsBatteryRatedAmpereHour added to MIB -- : upsBattery 14: upsBatteryInstalledDate changed to upsBatteryInstallationDate -- : upsWellKnownAlarms 1/upsTrap 1 & 2: upsAlarmFaultStatus changed to upsAlarmFault -- : upsWellKnownAlarms 3/upsTrap 5 & 6: upsAlarmLowBattery changed to upsAlarmBatteryLow -- : upsWellKnownAlarms 4/upsTrap 7 7 & 8: upsAlarmDepletedBattery changed to upsAlarmBatteryDepleted -- : upsAlarmInputVoltageAbnormal removed from MIB -- : upsAlarmOutputBad removed from MIB -- : upsWellKnownAlarms 8/upsTrap 15 & 16: upsAlarmPowerFailure added to MIB -- : upsWellKnownAlarms 11/upsTrap 21 & 22: upsAlarmUpsOutputOff changed to upsAlarmOutputOff -- : upsAlarmRE4UPSCommError removed from MIB -- : upsAlarmInverterSynchronous removed from MIB -- : upsWellKnownAlarms 12/upsTrap 23 & 24: upsAlarmAsyncOperation added to MIB -- : upsWellKnownAlarms 13/upsTrap 25 & 26: upsAlarmDCOverCurrent changed to upsAlarmDCBusOverCurrent -- : upsWellKnownAlarms 14/upsTrap 27 & 28: upsAlarmDCOverVoltage changed to upsAlarmDCBusOverVoltage -- : upsWellKnownAlarms 15/upsTrap 29 & 30: upsAlarmDCUnderVoltage changed to upsAlarmDCBusUnderVoltage -- : upsWellKnownAlarms 16/upsTrap 31 & 32: upsAlarmDCUnbalanced changed to upsAlarmDCBusImbalance -- : upsWellKnownAlarms 20/upsTrap 39 & 40: upsAlarmOutputOverCurrent changed to upsAlarmInverterOvercurrent -- : upsWellKnownAlarms 21/upsTrap 41 & 42: upsAlarmRemotEyeCommError added to MIB -- : upsConfig 2: upsConfigUPSSoftwareVersion changed to upsConfigUPSFirmwareVersion -- : upsConfig 3: upsConfigInputNumLines changed to upsConfigInputNumOfPhases -- : upsConfig 4: upsConfigInputFreq changed to upsConfigRatedInputFrequency -- : upsConfig 5: upsConfigInputVoltage changed to upsConfigRatedInputLLVoltage -- : upsConfig 6: upsConfigInputPF changed to upsConfigRatedInputPowerFactor -- : upsConfig 7: upsConfigOutputNumLines changed to upsConfigOutputNumOfPhases -- : upsConfig 8: upsConfigOutputFreq changed to upsConfigRatedOutputFrequency -- : upsConfig 9: upsConfigOutputVoltage changed to upsConfigRatedOutputLLVoltage -- : upsConfig 10: upsConfigOutputVA changed to upsConfigRatedOutputApperentPower -- : upsConfig 11: upsConfigOutputActivePower changed to upsConfigRatedOuputActivePower -- : upsConfig 12: upsConfigOutputPF changed to upsConfigRatedOutputPowerFactor -- : upsConfig 13: upsConfigBypassNumOfPhases added to MIB -- : upsConfig 16: upsConfigNumBattSeries changed to upsConfigBatteryInSeries -- : upsConfig 17: upsConfigNumBattStrings changed to upsConfigBatterNumStrings -- : upsConfig 18: upsConfig1BattVoltage changed to upsConfigRatedBatteryVoltage -- : upsConfig 19: upsConfigBatteryRatedAmpereHour changed to upsConfigRatedBatteryAmpereHour -- : upsConfig 20: upsConfigBattModel changed to upsConfigBatteryModel -- : upsConfig 21: upsConfigBattRatedHoldingTime changed to upsConfigBatteryRatedBackupTime -- : upsConfig 22: upsConfigBatteryInstalledDate changed to upsConfigBatteryInstallationDate -- : upsConfig 23: upsConfigSysName added to MIB -- : upsConfig 24: upsConfigAttachedDevices added to MIB -- : upsConfig 25: upsConfigPassword added to MIB -- : upsTrap 1 & 2: upsTrapFaultStatus changed to upsTrapFault -- : upsTrap 5 & 6: upsTrapBatteryLowVoltage changed to upsTrapBatteryLow -- : upsTrap 7 & 8: upsTrapDepletedBattery changed to upsTrapBatteryDepleted -- : upsTrap 15 & 16: upsTrapPowerFailure added to MIB -- : upsTrap 19 & 20: upsTrapOnBypass added to MIB -- : upsTrap 21 & 22: upsTrapUpsOutputOff changed to upsTrapOutputOff -- : upsTrapInverterSynchronous removed from MIB -- : upsTrap 23 & 24: upsTrapAsyncOperation added to MIB -- : upsTrap 25 & 26: upsTrapDCOvercurrent changed to upsTrapsDCBusOverCurrent -- : upsTrap 27 & 28: upsTrapDCOvervoltage changed to upsTrapDCBusOverVoltage -- : upsTrap 29 & 30: upsTrapDCUndervoltage changed to upsTrapDCBusUnderVoltage -- : upsTrap 31 & 32: upsTrapDCUnbalance changed to upsTrapDCBusImbalance -- : upsTrap 33 & 34: upsTrapOutputUndervoltage changed to upsTrapOutputUnderVoltage -- : upsTrap 35 & 36: upsTrapOutputOvervoltage changed to upsTrapOutputOverVoltage -- : upsTrap 41 & 42: upsTrapRemotEyeCommError added to MIB -- : upsTrapOutputBad removed from MIB -- : upsTrapBypassSourceSupply removed from MIB -- : upsTrapInputVoltageAbnormal removed from MIB --============================================================================= -- Update : December 22, 2013 -- By : Tiffany Tye, Toshiba International Corp. -- Revised:upsOutputCurrentPercentA, B & C syntax change from nonnegativeinteger to Integer (1..200) -- : upsBatteryInstalledDate SYNTAX DisplayString from size 8 to 10 -- : Remove EMD Alarm and Traps -- : upsConfigBatteryInstalledDate SYNTAX DisplayString from size 8 to 10 upsConfigBatteryInstalledDate Add unit -- : Remove TrapRE4UPSComm & TrapLoginError -- : Change upsBatteryRatedHoldingTime to upsBatteryRatedBackupTime --============================================================================= -- Update: July 30, 2013 -- By : Edwin Rubio, Toshiba International Corp. -- For : G9000 First Draft MIB for RemotEye 4 --============================================================================== IMPORTS DisplayString, TimeStamp, TimeInterval, TestAndIncr, AutonomousType FROM SNMPv2-TC enterprises FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; PositiveInteger ::= INTEGER (0..2147483647) NonNegativeInteger ::= INTEGER (0..2147483647) toshiba OBJECT IDENTIFIER ::= { enterprises 186 } equ OBJECT IDENTIFIER ::= { toshiba 1 } equUPS OBJECT IDENTIFIER ::= { equ 19 } ticUPS OBJECT IDENTIFIER ::= { equUPS 2 } rmti4 OBJECT IDENTIFIER ::= { ticUPS 5 } upsG9000-G2020 OBJECT IDENTIFIER ::= { rmti4 1 } upsIdent OBJECT IDENTIFIER ::= { upsG9000-G2020 1 } upsInput OBJECT IDENTIFIER ::= { upsG9000-G2020 2 } upsOutput OBJECT IDENTIFIER ::= { upsG9000-G2020 3 } upsBypass OBJECT IDENTIFIER ::= { upsG9000-G2020 4 } upsBattery OBJECT IDENTIFIER ::= { upsG9000-G2020 5 } upsAlarm OBJECT IDENTIFIER ::= { upsG9000-G2020 6 } upsConfig OBJECT IDENTIFIER ::= { upsG9000-G2020 7 } upsTime OBJECT IDENTIFIER ::= { upsG9000-G2020 8 } upsTrap OBJECT IDENTIFIER ::= { upsG9000-G2020 9 } -- =========================================================================== -- upsIdentification – Group 1 -- Device Identification group -- All objects in this group are set at device initialization and remain static. --=========================================================================== upsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "The name of the UPS manufacturer." ::= { upsIdent 1 } upsIdentTypeform OBJECT-TYPE SYNTAX DisplayString (SIZE (0..127)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Model designation." ::= { upsIdent 2 } upsIdentUPSFirmwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS firmware version." ::= { upsIdent 3 } upsIdentSysName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the UPS. This object is set by the administrator." ::= { upsIdent 4 } upsIdentAttachedDevices OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator." ::= { upsIdent 5 } --=========================================================================== -- upsInput – Group 2 -- -- Input group. -- =========================================================================== upsInputNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "Number of input lines. This data is used by upsInputNumLines." ::= { upsInput 1 } upsInputLLVoltageAB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage for AB in RMS volts." ::= { upsInput 2 } upsInputLLVoltageBC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage for BC in RMS volts." ::= { upsInput 3 } upsInputLLVoltageCA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage for CA in RMS volts." ::= { upsInput 4 } upsInputLLVoltagePercentAB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage percent for AB." ::= { upsInput 5 } upsInputLLVoltagePercentBC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage percent for BC." ::= { upsInput 6 } upsInputLLVoltagePercentCA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line voltage percent for CA." ::= { upsInput 7 } upsInputCurrentPhaseA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The input phase current for Phase A." ::= { upsInput 8 } upsInputCurrentPhaseB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The input phase current unit for Phase B." ::= { upsInput 9 } upsInputCurrentPhaseC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The input phase current unit for Phase C." ::= { upsInput 10 } upsInputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS mandatory DESCRIPTION "The input frequency unit 0.1 Hertz." ::= { upsInput 11 } upsInputActivePowerA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Watts" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input true power for phase A." ::= { upsInput 12 } upsInputActivePowerB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Watts" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input true power for phase B." ::= { upsInput 13 } upsInputActivePowerC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Watts" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input true power for phase C." ::= { upsInput 14 } upsInputTotalActivePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Watts" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the total input true power." ::= { upsInput 15 } upsInputRatedLLVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The input line to line rated voltage in RMS volts." ::= { upsInput 16 } -- =========================================================================== -- upsOutput – Group 3 -- -- Output group -- =========================================================================== upsOutputSource OBJECT-TYPE SYNTAX INTEGER { other(1), none(2), normal(3), bypass(4), battery(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker." ::= { upsOutput 1 } upsOutputNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of output lines utilized in this device." ::= { upsOutput 2 } upsOutputLLVoltageAB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The output line to line voltage for AB in RMS volts." ::= { upsOutput 3 } upsOutputLLVoltageBC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The output line to line voltage for BC in RMS volts." ::= { upsOutput 4 } upsOutputLLVoltageCA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The output line to line voltage for CA in RMS volts." ::= { upsOutput 5 } upsOutputCurrentPhaseA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The Output phase current for phase A in amps." ::= { upsOutput 6 } upsOutputCurrentPhaseB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The Output phase current for phase B in amps." ::= { upsOutput 7 } upsOutputCurrentPhaseC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The Output phase current for phase C in amps." ::= { upsOutput 8 } upsOutputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS mandatory DESCRIPTION "The Output Frequency for phase A in 1/10 of HZ." ::= { upsOutput 9 } upsOutputCurrentPercentA OBJECT-TYPE SYNTAX INTEGER UNITS "PERCENT" ACCESS read-only STATUS mandatory DESCRIPTION "The output current for phase A in percent." ::= { upsOutput 10 } upsOutputCurrentPercentB OBJECT-TYPE SYNTAX INTEGER UNITS "PERCENT" ACCESS read-only STATUS mandatory DESCRIPTION "The output current for phase B in percent." ::= { upsOutput 11 } upsOutputCurrentPercentC OBJECT-TYPE SYNTAX INTEGER UNITS "PERCENT" ACCESS read-only STATUS mandatory DESCRIPTION "The output current for phase C in percent." ::= { upsOutput 12 } upsOutputTotalActivePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "kWatts" ACCESS read-only STATUS mandatory DESCRIPTION "The output active power." ::= { upsOutput 13 } upsOutputTotalActivePowerPercent OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The output active power in percent." ::= { upsOutput 14 } upsOutputPowerFactor OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.01" ACCESS read-only STATUS mandatory DESCRIPTION "The UPS output power factor." ::= { upsOutput 15 } upsOutputRatedActivePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Watts" ACCESS read-only STATUS mandatory DESCRIPTION "The output rated active power for the UPS." ::= { upsOutput 16 } upsOutputRatedApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "VA" ACCESS read-only STATUS mandatory DESCRIPTION "The output rated apparent power for the UPS." ::= { upsOutput 17 } upsOutputRatedLLVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The output rated line to line voltage for the UPS." ::= { upsOutput 18 } -- =========================================================================== -- upsBypass – Group 4 -- =========================================================================== upsBypassNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of bypass lines utilized." ::= { upsBypass 1 } upsBypassLLVoltageAB OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass line to line voltage for AB in RMS volts." ::= { upsBypass 2 } upsBypassLLVoltageBC OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass line to line voltage for BC in RMS volts." ::= { upsBypass 3 } upsBypassLLVoltageCA OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass line to line voltage for CA in RMS volts." ::= { upsBypass 4 } upsBypassFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass frequency in 0.1 Hertz." ::= { upsBypass 5 } --=========================================================================== -- upsBattery – Group 5 -- -- The Battery group. -- =========================================================================== upsBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6) } ACCESS read-only STATUS mandatory DESCRIPTION "The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power. " ::= { upsBattery 1 } upsElapsedTimeOnBatteryPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "seconds" ACCESS read-only STATUS mandatory DESCRIPTION "If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power." ::= { upsBattery 2 } upsEstimatedBatteryRuntime OBJECT-TYPE SYNTAX PositiveInteger UNITS "minutes" ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off." ::= { upsBattery 3 } upsBatteryVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Volt DC" ACCESS read-only STATUS mandatory DESCRIPTION "The battery voltage DC." ::= { upsBattery 4 } upsBatteryVoltagePercent OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "percentage" ACCESS read-only STATUS mandatory DESCRIPTION "Battery voltage in percent." ::= { upsBattery 5 } upsBatteryEstimatedCharge OBJECT-TYPE SYNTAX INTEGER(0..100) UNITS "percentage" ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off." ::= { upsBattery 6 } upsBatteryDischargeCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The present battery discharge Current in percent." ::= { upsBattery 7 } upsBatteryChargeCurrent OBJECT-TYPE SYNTAX Integer32 UNITS "percentage" ACCESS read-only STATUS mandatory DESCRIPTION "The present battery charge Current in percent." ::= { upsBattery 8 } upsBatteryModel OBJECT-TYPE SYNTAX DisplayString (SIZE(0..15)) ACCESS read-write STATUS mandatory DESCRIPTION "The Battery manufacturer." ::= { upsBattery 9 } upsBatteryInSeries OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-write STATUS mandatory DESCRIPTION "The Battery rated holding time in minutes." ::= { upsBattery 10 } upsBatteryNumStrings OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-write STATUS mandatory DESCRIPTION "The Battery rated holding time in minutes." ::= { upsBattery 11 } upsBatteryRatedAmpereHour OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Ampere Hour" ACCESS read-write STATUS mandatory DESCRIPTION "The Battery rated holding time in minutes." ::= { upsBattery 12 } upsBatteryRatedBackupTime OBJECT-TYPE SYNTAX DisplayString (SIZE(0..8)) UNITS "minutes" ACCESS read-write STATUS mandatory DESCRIPTION "The Battery rated holding time in minutes." ::= { upsBattery 13 } upsBatteryInstallationDate OBJECT-TYPE SYNTAX DisplayString (SIZE(10)) ACCESS read-only STATUS mandatory DESCRIPTION "The battery install date." ::= { upsBattery 14 } -- =========================================================================== -- upsAlarm – Group 6 -- =========================================================================== upsAlarmsPresent OBJECT-TYPE SYNTAX Gauge32 ACCESS read-only STATUS mandatory DESCRIPTION "The present number of active alarm conditions." ::= { upsAlarm 1 } upsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent." ::= { upsAlarm 2 } upsAlarmEntry OBJECT-TYPE SYNTAX UpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular alarm." INDEX { upsAlarmId } ::= { upsAlarmTable 1 } UpsAlarmEntry ::= SEQUENCE { upsAlarmId PositiveInteger, upsAlarmDescr AutonomousType, upsAlarmTime TimeStamp } -- =========================================================================== -- upsAlarmTable/upsAlarmEntry/upsAlarmId -- =========================================================================== upsAlarmId OBJECT-TYPE SYNTAX PositiveInteger ACCESS not-accessible STATUS mandatory DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant." ::= { upsAlarmEntry 1 } upsAlarmDescr OBJECT-TYPE SYNTAX AutonomousType ACCESS read-only STATUS mandatory DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { upsAlarmEntry 2 } -- =========================================================================== -- .../upsAlarmTime -- =========================================================================== upsAlarmTime OBJECT-TYPE SYNTAX TimeStamp ACCESS read-only STATUS mandatory DESCRIPTION "The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0." ::= { upsAlarmEntry 3 } upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 } upsAlarmFault OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: A UPS fault/Alarm condition exists." ::= { upsWellKnownAlarms 1 } upsAlarmOnBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Info: The UPS is on Battery mode; it is supplying output power from its batteries." ::= { upsWellKnownAlarms 2 } upsAlarmBatteryLow OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime." ::= { upsWellKnownAlarms 3 } upsAlarmBatteryDepleted OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load." ::= { upsWellKnownAlarms 4 } upsAlarmBatteryOverheat OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: Detection of over temperature at the batteries." ::= { upsWellKnownAlarms 5 } upsAlarmBatteryVoltageAbnormal OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: Battery voltage is abnormality." ::= { upsWellKnownAlarms 6 } upsAlarmUPSOverheat OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center." ::= { upsWellKnownAlarms 7 } upsAlarmPowerFailure OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Info: Power Failure." ::= { upsWellKnownAlarms 8 } upsAlarmUPSOverload OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load." ::= { upsWellKnownAlarms 9 } upsAlarmUserDefinedOverloadWarning OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: The inverter output load % is greater than the user defined overload set point (default: 110%)." ::= { upsWellKnownAlarms 10 } upsAlarmOnBypass OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: The UPS is in Stop (Bypass) mode." ::= { upsWellKnownAlarms 11 } upsAlarmOutputOff OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Info: The UPS output is off." ::= { upsWellKnownAlarms 12 } upsAlarmAsyncOperation OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: Async Operation" ::= { upsWellKnownAlarms 13 } upsAlarmDCBusOverCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault." ::= { upsWellKnownAlarms 14 } upsAlarmDCBusOverVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault." ::= { upsWellKnownAlarms 15 } upsAlarmDCBusUnderVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault." ::= { upsWellKnownAlarms 16 } upsAlarmDCBusImbalanced OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: The DC imbalanced alarm detection." ::= { upsWellKnownAlarms 17 } upsAlarmOutputUnderVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault." ::= { upsWellKnownAlarms 18 } upsAlarmOutputOverVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault." ::= { upsWellKnownAlarms 19 } upsAlarmInverterOverload OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: Short time over-current has been detected." ::= { upsWellKnownAlarms 20 } upsAlarmInverterOvercurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Fault: Detection of inverter overcurrent." ::= { upsWellKnownAlarms 21 } upsAlarmRemotEyeCommError OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Warning: Communication error between the RemotEye 4 and the UPS." ::= { upsWellKnownAlarms 22 } -- =========================================================================== -- upsConfig – Group 7 -- Config data -- 1) All 'upsConfig' data is to be stored in NV-RAM inside the agent device. -- 2) All 'upsConfig' data is to be checked at each agent startup -- 3) If initial values present at startup, replace with default values -- unless specified otherwise. -- =========================================================================== upsConfigModelIDString OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option." ::= { upsConfig 1 } upsConfigUPSFirmwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The G9000 software version." ::= { upsConfig 2 } upsConfigInputNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "Number of input lines. This data is used by upsInputNumLines." ::= { upsConfig 3 } upsConfigRatedInputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS mandatory DESCRIPTION "The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 4 } upsConfigRatedInputLLVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-write STATUS mandatory DESCRIPTION "The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 5 } upsConfigRatedInputPowerFactor OBJECT-TYPE SYNTAX PositiveInteger UNITS "0.01" ACCESS read-only STATUS mandatory DESCRIPTION "UNITS are in hundredths. For 0.95 = 95." ::= { upsConfig 6 } upsConfigOutputNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "Number of output lines. This data is used by upsOutputNumLines." ::= { upsConfig 7 } upsConfigRatedOutputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS mandatory DESCRIPTION "The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2." ::= { upsConfig 8 } upsConfigRatedOutputLLVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "RMS Volts" ACCESS read-write STATUS mandatory DESCRIPTION "The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2." ::= { upsConfig 9 } upsConfigRatedOutputApperentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Volt-Amps" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the nominal Volt-Amp rating." ::= { upsConfig 10 } upsConfigRatedOutputActivePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "KWatts" ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the nominal true power rating." ::= { upsConfig 11 } upsConfigRatedOutputPowerFactor OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.01" ACCESS read-only STATUS mandatory DESCRIPTION "UNITS are in hundredths. For 0.70 = 70." ::= { upsConfig 12 } upsConfigBypassNumOfPhases OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of bypass lines utilized." ::= { upsConfig 13 } upsConfigLowVoltageTransferPoint OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "percentage" ACCESS read-write STATUS mandatory DESCRIPTION "The minimum input line voltage allowed before the UPS system transfers to battery backup." ::= { upsConfig 14 } upsConfigHighVoltageTransferPoint OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "percentage" ACCESS read-write STATUS mandatory DESCRIPTION "The maximum line voltage allowed before the UPS system transfers to battery backup." ::= { upsConfig 15 } upsConfigBatteryInSeries OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-write STATUS mandatory DESCRIPTION "The number of batteries in each string connected in series." ::= { upsConfig 16 } upsConfigBatteryNumStrings OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-write STATUS mandatory DESCRIPTION "The number of parallel battery strings." ::= { upsConfig 17 } upsConfigRatedBatteryVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "Volts DC" ACCESS read-write STATUS mandatory DESCRIPTION "Rated voltage of a single battery." ::= { upsConfig 18 } upsConfigRatedBatteryAmpereHour OBJECT-TYPE SYNTAX INTEGER UNITS "Ahr" ACCESS read-write STATUS mandatory DESCRIPTION "The rated battery in ampere hour." ::= { upsConfig 19 } upsConfigBatteryModel OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The manufacturer of the battery." ::= { upsConfig 20 } upsConfigBatteryRatedBackupTime OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "minutes" ACCESS read-write STATUS mandatory DESCRIPTION "The rated duration batteries can hold when unit is in backup mode with full load." ::= { upsConfig 21 } upsConfigUserDefinedOverloadSetPoint OBJECT-TYPE SYNTAX INTEGER UNITS "%" ACCESS read-write STATUS mandatory DESCRIPTION "The maximum output load % defined by the user." ::= { upsConfig 22 } upsConfigBatteryInstallationDate OBJECT-TYPE SYNTAX DisplayString (SIZE(10)) UNITS "mm/dd/yyyy" ACCESS read-write STATUS mandatory DESCRIPTION "The battery install date." ::= { upsConfig 23 } upsConfigSysName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the UPS. This object is set by the administrator." ::= { upsConfig 24 } upsConfigAttachedDevices OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator." ::= { upsConfig 25 } upsConfigPassword OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "Password." ::= { upsConfig 26 } -- =========================================================================== -- upsTime – Group 8 -- -- Time group -- =========================================================================== upsTimeRealDate OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "Present date: year-month-date-day of the week." ::= { upsTime 1 } upsTimeRealTime OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00." ::= { upsTime 2 } -- --======================================================================= -- upsTraps – Group 9 -- -- Traps group -- --======================================================================= upsTrapFault TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Alarm: One or more fault/status alarm(s) reported." ::= 1 upsTrapFaultClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Alarm Clear: One or more fault/status reported." ::= 2 upsTrapOnBattery TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info: The UPS is on Battery Mode." ::= 3 upsTrapOnBatteryClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info Clear: The UPS is on Battery Mode." ::= 4 upsTrapBatteryLow TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning: Battery Low Voltage." ::= 5 upsTrapBatteryLowClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear: Battery Low Voltage." ::= 6 upsTrapBatteryDepleted TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load." ::= 7 upsTrapBatteryDepletedClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.." ::= 8 upsTrapBatteryOverheat TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: Battery Overheat." ::= 9 upsTrapBatteryOverheatClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: Battery Overheat." ::= 10 upsTrapBatteryVoltageAbnormal TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination." ::= 11 upsTrapBatteryVoltageAbnormalClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination." ::= 12 upsTrapUPSOverheat TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination." ::= 13 upsTrapUPSOverheatClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination." ::= 14 upsTrapPowerFailure TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info: Power Failure." ::= 15 upsTrapPowerFailureClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info Clear: PowerFailure." ::= 16 upsTrapUPSOverload TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load." ::= 17 upsTrapUPSOverloadClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load." ::= 18 upsTrapUserDefinedOverloadWarning TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning: The inverter output load % is greater than the user defined overload set point (default: 110%)." ::= 19 upsTrapUserDefinedOverloadWarningClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%)." ::= 20 upsTrapOnBypass TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning:On Bypass." ::= 21 upsTrapOnBypassClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear: On Bypass." ::= 22 upsTrapOutputOff TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info: The UPS output is off." ::= 23 upsTrapOutputOffClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Info Clear: The UPS output is off." ::= 24 upsTrapAsyncOperation TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning: Inverter Synchronous." ::= 25 upsTrapAsyncOperationClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear: Inverter Synchronous." ::= 26 upsTrapDCBusOverCurrent TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination." ::= 27 upsTrapDCBusOverCurrentClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination." ::= 28 upsTrapDCBusOverVoltage TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination." ::= 29 upsTrapDCBusOverVoltageClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination." ::= 30 upsTrapDCBusUnderVoltage TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination." ::= 31 upsTrapDCBusUnderVoltageClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination." ::= 32 upsTrapDCBusImbalance TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: DC Unbalance. Contact your Toshiba authorized service center for examination." ::= 33 upsTrapDCBusImbalanceClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination." ::= 34 upsTrapOutputUnderVoltage TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination." ::= 35 upsTrapOutputUnderVoltageClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination." ::= 36 upsTrapOutputOverVoltage TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination." ::= 37 upsTrapOutputOverVoltageClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination." ::= 38 upsTrapInverterOverload TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load." ::= 39 upsTrapInverterOverloadClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load." ::= 40 upsTrapInverterOvercurrent TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination." ::= 41 upsTrapInverterOvercurrentClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination." ::= 42 upsTrapRemotEyeCommError TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning: RemotEye UPS communication error." ::= 43 upsTrapRemotEyeCommErrorClear TRAP-TYPE ENTERPRISE upsG9000-G2020 DESCRIPTION "Warning Clear:RemotEye UPS communication error." ::= 44 END