VERTIV-V5-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString, TruthValue, MacAddress FROM SNMPv2-TC SnmpAdminString FROM SNMP-FRAMEWORK-MIB MODULE-IDENTITY, OBJECT-TYPE, enterprises, Integer32, Gauge32, NOTIFICATION-TYPE, OBJECT-IDENTITY FROM SNMPv2-SMI sysName FROM SNMPv2-MIB; vertiv MODULE-IDENTITY LAST-UPDATED "202001070000Z" ORGANIZATION "Vertiv" CONTACT-INFO "support@geistglobal.com" DESCRIPTION "The MIB for Vertiv products" REVISION "202001070000Z" DESCRIPTION "Updates for VRC spec change" REVISION "201909300000Z" DESCRIPTION "Added hostname, alarm/warning count, and manufacturer to deviceInfo" REVISION "201909120000Z" DESCRIPTION "Added SN-2D door switch sensor" REVISION "201908300000Z" DESCRIPTION "Removed current min, max, and peak fields from pdu phase, line, breaker, and outlet tables Removed voltage min, max, and peak fields from pdu phase, line, breaker, and outlet tables Removed minmax reset value from pduOutletMeterReset Added balance field to pdu phase table" REVISION "201906060000Z" DESCRIPTION "Updated pduOutletSwitchControl description" REVISION "201905070000Z" DESCRIPTION "Changed productMacAddress type to MacAddress" REVISION "201904300000Z" DESCRIPTION "Added remote humidity-only sensor" REVISION "201903070000Z" DESCRIPTION "Added VRC support" REVISION "201801190000Z" DESCRIPTION "Modified pduOutletSwitchTable to support outlet actions with delays" REVISION "201709190000Z" DESCRIPTION "Changed SYNTAX of objects, with a UTF-8 encoded string value, to SnmpAdminString" REVISION "201708100000Z" DESCRIPTION "Added pduBreakerCurrentPeak, pduLineCurrentPeak, pduOutletMeterCurrentPeak, pduPhaseVoltagePeak, and pduPhaseCurrentPeak Updated object descriptions, indicating which fields are not supported on all platforms" REVISION "201705100000Z" DESCRIPTION "Added trapObj group with trap payload objects Added additional payload objects to trap definitions" REVISION "201704050000Z" DESCRIPTION "Added productPlatform to deviceInfo group Added product identity entries" REVISION "201606300000Z" DESCRIPTION "Raven version" REVISION "201209110000Z" DESCRIPTION "Original version" ::= { enterprises 21239 } v5 OBJECT IDENTIFIER ::= { vertiv 5 } imd OBJECT IDENTIFIER ::= { v5 2 } --###########################################################################################-- --deviceInfo-- --###########################################################################################-- deviceInfo OBJECT IDENTIFIER ::= { imd 1 } productTitle OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product name" ::= { deviceInfo 1 } productVersion OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product version" ::= { deviceInfo 2 } productFriendlyName OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "User-assigned name" ::= { deviceInfo 3 } productMacAddress OBJECT-TYPE SYNTAX MacAddress MAX-ACCESS read-only STATUS current DESCRIPTION "Product's unique MAC address" ::= { deviceInfo 4 } deviceCount OBJECT-TYPE SYNTAX Integer32(0..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of devices on unit" ::= { deviceInfo 6 } temperatureUnits OBJECT-TYPE SYNTAX INTEGER { fahrenheit(0), celsius(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Current units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsius" ::= { deviceInfo 7 } productModelNumber OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product model number (factory-assigned)" ::= { deviceInfo 8 } productPartNumber OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product part number (factory-assigned)" ::= { deviceInfo 9 } productSerialNumber OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product serial number (factory-assigned)" ::= { deviceInfo 10 } productPlatform OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product platform" ::= { deviceInfo 11 } productHostname OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product hostname" ::= { deviceInfo 12 } productAlarmCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of alarms currently tripped" ::= { deviceInfo 13 } productWarnCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of warnings currently tripped" ::= { deviceInfo 14 } productManufacturer OBJECT-TYPE SYNTAX SnmpAdminString MAX-ACCESS read-only STATUS current DESCRIPTION "Product manufacturer" ::= { deviceInfo 15 } --###########################################################################################-- --pdu-- --###########################################################################################-- pdu OBJECT IDENTIFIER ::= { imd 3 } --###########################################################################################-- --pduMainTable-- --###########################################################################################-- pduMainTable OBJECT-TYPE SYNTAX SEQUENCE OF PduMainEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "PDU general information" ::= { pdu 1 } pduMainEntry OBJECT-TYPE SYNTAX PduMainEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduMainTable table: each entry contains an index and other sensor details" INDEX { pduMainIndex } ::= { pduMainTable 1 } PduMainEntry ::= SEQUENCE { pduMainIndex Integer32, pduMainSerial DisplayString, pduMainName SnmpAdminString, pduMainLabel SnmpAdminString, pduMainAvail Gauge32, pduMeterType INTEGER, pduTotalName SnmpAdminString, pduTotalLabel SnmpAdminString, pduTotalRealPower Gauge32, pduTotalApparentPower Gauge32, pduTotalPowerFactor Gauge32, pduTotalEnergy Gauge32 } pduMainIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduMainEntry 1 } pduMainSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { pduMainEntry 2 } pduMainName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU name (factory-assigned)" ::= { pduMainEntry 3 } pduMainLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU label (user-defined)" ::= { pduMainEntry 4 } pduMainAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { pduMainEntry 5 } pduMeterType OBJECT-TYPE SYNTAX INTEGER { wye(0), delta(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Current meter type: 0 = Wye 1 = Delta" ::= { pduMainEntry 6 } pduTotalName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Total name (factory-assigned)" ::= { pduMainEntry 7 } pduTotalLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Total label (user-defined)" ::= { pduMainEntry 8 } pduTotalRealPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "watts" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU total real power" ::= { pduMainEntry 9 } pduTotalApparentPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "volt-amps" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU total apparent power" ::= { pduMainEntry 10 } pduTotalPowerFactor OBJECT-TYPE SYNTAX Gauge32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU total power factor" ::= { pduMainEntry 11 } pduTotalEnergy OBJECT-TYPE SYNTAX Gauge32(0..9999000) UNITS "watt-hours" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU total accumulated energy in watt-hours" ::= { pduMainEntry 12 } --###########################################################################################-- --pduPhaseTable-- --###########################################################################################-- pduPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF PduPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "PDU phases information" ::= { pdu 2 } pduPhaseEntry OBJECT-TYPE SYNTAX PduPhaseEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduPhaseTable table: each entry contains an index and other sensor details" INDEX { pduPhaseIndex } ::= { pduPhaseTable 1 } PduPhaseEntry ::= SEQUENCE { pduPhaseIndex Integer32, pduPhaseName SnmpAdminString, pduPhaseLabel SnmpAdminString, pduPhaseVoltage Gauge32, pduPhaseCurrent Gauge32, pduPhaseRealPower Gauge32, pduPhaseApparentPower Gauge32, pduPhasePowerFactor Gauge32, pduPhaseEnergy Gauge32, pduPhaseBalance Gauge32, pduPhaseCurrentCrestFactor Gauge32 } pduPhaseIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduPhaseEntry 1 } pduPhaseName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU phase name (factory-assigned)" ::= { pduPhaseEntry 2 } pduPhaseLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU phase label (user-defined)" ::= { pduPhaseEntry 3 } pduPhaseVoltage OBJECT-TYPE SYNTAX Gauge32(0..3100) UNITS "decivolts (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU phase voltage in tenths of a volt" ::= { pduPhaseEntry 4 } pduPhaseCurrent OBJECT-TYPE SYNTAX Gauge32(0..9900) UNITS "centiamps (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU phase current reading in hundredths of an amp" ::= { pduPhaseEntry 8 } pduPhaseRealPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "watts" MAX-ACCESS read-only STATUS current DESCRIPTION "Real power for phase in watts" ::= { pduPhaseEntry 12 } pduPhaseApparentPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "volt-amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Apparent power for phase in volt-amps" ::= { pduPhaseEntry 13 } pduPhasePowerFactor OBJECT-TYPE SYNTAX Gauge32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor for phase" ::= { pduPhaseEntry 14 } pduPhaseEnergy OBJECT-TYPE SYNTAX Gauge32(0..9999000) UNITS "watt-hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated energy for phase in watt-hours" ::= { pduPhaseEntry 15 } pduPhaseBalance OBJECT-TYPE SYNTAX Gauge32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase balance as percent" ::= { pduPhaseEntry 17 } pduPhaseCurrentCrestFactor OBJECT-TYPE SYNTAX Gauge32(0..9999) MAX-ACCESS read-only STATUS current DESCRIPTION "Current crest factor for phase, in hundredths" ::= { pduPhaseEntry 19 } --###########################################################################################-- --pduBreakerTable-- --###########################################################################################-- pduBreakerTable OBJECT-TYPE SYNTAX SEQUENCE OF PduBreakerEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "PDU breaker information" ::= { pdu 3 } pduBreakerEntry OBJECT-TYPE SYNTAX PduBreakerEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduBreakerTable table: each entry contains an index and other sensor details" INDEX { pduBreakerIndex } ::= { pduBreakerTable 1 } PduBreakerEntry ::= SEQUENCE { pduBreakerIndex Integer32, pduBreakerName SnmpAdminString, pduBreakerLabel SnmpAdminString, pduBreakerCurrent Gauge32, pduBreakerVoltage Gauge32, pduBreakerRealPower Gauge32, pduBreakerApparentPower Gauge32, pduBreakerPowerFactor Gauge32, pduBreakerEnergy Gauge32 } pduBreakerIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduBreakerEntry 1 } pduBreakerName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU breaker name (factory-assigned)" ::= { pduBreakerEntry 2 } pduBreakerLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU breaker label (user-defined)" ::= { pduBreakerEntry 3 } pduBreakerCurrent OBJECT-TYPE SYNTAX Gauge32(0..9900) UNITS "centiamps (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU breaker current reading in hundredths of an amp" ::= { pduBreakerEntry 4 } pduBreakerVoltage OBJECT-TYPE SYNTAX Gauge32(0..3100) UNITS "decivolts (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences." ::= { pduBreakerEntry 8 } pduBreakerRealPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "watts" MAX-ACCESS read-only STATUS current DESCRIPTION "Real power for breaker in watts. This object may not exist on all platforms, due to hardware differences." ::= { pduBreakerEntry 12 } pduBreakerApparentPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "volt-amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Apparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences." ::= { pduBreakerEntry 13 } pduBreakerPowerFactor OBJECT-TYPE SYNTAX Gauge32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor for breaker. This object may not exist on all platforms, due to hardware differences." ::= { pduBreakerEntry 14 } pduBreakerEnergy OBJECT-TYPE SYNTAX Gauge32(0..9999000) UNITS "watt-hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences." ::= { pduBreakerEntry 15 } --###########################################################################################-- --pduLineTable-- --###########################################################################################-- pduLineTable OBJECT-TYPE SYNTAX SEQUENCE OF PduLineEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "PDU line current information" ::= { pdu 4 } pduLineEntry OBJECT-TYPE SYNTAX PduLineEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduLineTable table: each entry contains an index and other sensor details" INDEX { pduLineIndex } ::= { pduLineTable 1 } PduLineEntry ::= SEQUENCE { pduLineIndex Integer32, pduLineName SnmpAdminString, pduLineLabel SnmpAdminString, pduLineCurrent Gauge32 } pduLineIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduLineEntry 1 } pduLineName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU line name (factory-assigned)" ::= { pduLineEntry 2 } pduLineLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU line label (user-defined)" ::= { pduLineEntry 3 } pduLineCurrent OBJECT-TYPE SYNTAX Gauge32(0..9900) UNITS "centiamps (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU line current reading in hundredths of an amp" ::= { pduLineEntry 4 } --###########################################################################################-- --pduOutletSwitchTable-- --###########################################################################################-- pduOutletSwitchTable OBJECT-TYPE SYNTAX SEQUENCE OF PduOutletSwitchEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Data, config and control for outlets with switching" ::= { pdu 5 } pduOutletSwitchEntry OBJECT-TYPE SYNTAX PduOutletSwitchEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduOutletSwitchTable table: each entry contains an index and other sensor details" INDEX { pduOutletSwitchIndex } ::= { pduOutletSwitchTable 1 } PduOutletSwitchEntry ::= SEQUENCE { pduOutletSwitchIndex Integer32, pduOutletSwitchName SnmpAdminString, pduOutletSwitchLabel SnmpAdminString, pduOutletSwitchState INTEGER, pduOutletSwitchRelayFailure TruthValue, pduOutletSwitchControl INTEGER, pduOutletSwitchTimeToAction Integer32, pduOutletSwitchOnDelay Integer32, pduOutletSwitchOffDelay Integer32, pduOutletSwitchRebootDelay Integer32, pduOutletSwitchRebootHoldDelay Integer32, pduOutletSwitchPoaAction INTEGER, pduOutletSwitchPoaDelay Integer32 } pduOutletSwitchIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduOutletSwitchEntry 1 } pduOutletSwitchName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU outlet name (factory-assigned)" ::= { pduOutletSwitchEntry 2 } pduOutletSwitchLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU outlet label (user-defined)" ::= { pduOutletSwitchEntry 3 } pduOutletSwitchState OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), on2off(3), off2on(4), rebootOn(5), rebootOff(6), unavailable(7) } MAX-ACCESS read-only STATUS current DESCRIPTION "Switch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet state" ::= { pduOutletSwitchEntry 4 } pduOutletSwitchRelayFailure OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Tells if the outlet relay has failed. In normal operation, the value will be false(2)." ::= { pduOutletSwitchEntry 5 } pduOutletSwitchControl OBJECT-TYPE SYNTAX INTEGER { cancel(1), on(2), onAfterDelay(3), off(4), offAfterDelay(5), reboot(6), rebootAfterDelay(7), none(8) } MAX-ACCESS read-write STATUS current DESCRIPTION "Used for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests." ::= { pduOutletSwitchEntry 6 } pduOutletSwitchTimeToAction OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-only STATUS current DESCRIPTION "Seconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay." ::= { pduOutletSwitchEntry 7 } pduOutletSwitchOnDelay OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions." ::= { pduOutletSwitchEntry 8 } pduOutletSwitchOffDelay OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions." ::= { pduOutletSwitchEntry 9 } pduOutletSwitchRebootDelay OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info." ::= { pduOutletSwitchEntry 10 } pduOutletSwitchRebootHoldDelay OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info." ::= { pduOutletSwitchEntry 11 } pduOutletSwitchPoaAction OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), last(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known state" ::= { pduOutletSwitchEntry 12 } pduOutletSwitchPoaDelay OBJECT-TYPE SYNTAX Integer32(0..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Seconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up." ::= { pduOutletSwitchEntry 13 } --###########################################################################################-- --pduOutletMeterTable-- --###########################################################################################-- pduOutletMeterTable OBJECT-TYPE SYNTAX SEQUENCE OF PduOutletMeterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Metering data for outlets that support this feature" ::= { pdu 6 } pduOutletMeterEntry OBJECT-TYPE SYNTAX PduOutletMeterEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the pduOutletMeterTable table: each entry contains an index and other sensor details" INDEX { pduOutletMeterIndex } ::= { pduOutletMeterTable 1 } PduOutletMeterEntry ::= SEQUENCE { pduOutletMeterIndex Integer32, pduOutletMeterName SnmpAdminString, pduOutletMeterLabel SnmpAdminString, pduOutletMeterVoltage Gauge32, pduOutletMeterCurrent Gauge32, pduOutletMeterRealPower Gauge32, pduOutletMeterApparentPower Gauge32, pduOutletMeterPowerFactor Gauge32, pduOutletMeterEnergy Gauge32, pduOutletMeterReset INTEGER, pduOutletCurrentCrestFactor Gauge32 } pduOutletMeterIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { pduOutletMeterEntry 1 } pduOutletMeterName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU outlet name (factory-assigned)" ::= { pduOutletMeterEntry 2 } pduOutletMeterLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "PDU outlet label (user-defined)" ::= { pduOutletMeterEntry 3 } pduOutletMeterVoltage OBJECT-TYPE SYNTAX Gauge32(0..3100) UNITS "decivolts (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU outlet voltage in tenths of a volt" ::= { pduOutletMeterEntry 4 } pduOutletMeterCurrent OBJECT-TYPE SYNTAX Gauge32(0..9900) UNITS "centiamps (rms)" MAX-ACCESS read-only STATUS current DESCRIPTION "PDU outlet current reading in hundredths of an amp" ::= { pduOutletMeterEntry 8 } pduOutletMeterRealPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "watts" MAX-ACCESS read-only STATUS current DESCRIPTION "Real power for outlet in watts" ::= { pduOutletMeterEntry 12 } pduOutletMeterApparentPower OBJECT-TYPE SYNTAX Gauge32(0..9999) UNITS "volt-amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Apparent power for outlet in volt-amps" ::= { pduOutletMeterEntry 13 } pduOutletMeterPowerFactor OBJECT-TYPE SYNTAX Gauge32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor for outlet" ::= { pduOutletMeterEntry 14 } pduOutletMeterEnergy OBJECT-TYPE SYNTAX Gauge32(0..9999000) UNITS "watt-hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Accumulated energy for outlet in watt-hours" ::= { pduOutletMeterEntry 15 } pduOutletMeterReset OBJECT-TYPE SYNTAX INTEGER { resetEnergy(1), none(8) } MAX-ACCESS read-write STATUS current DESCRIPTION "Used to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0" ::= { pduOutletMeterEntry 16 } pduOutletCurrentCrestFactor OBJECT-TYPE SYNTAX Gauge32(0..9999) MAX-ACCESS read-only STATUS current DESCRIPTION "Current crest factor for outlet, in hundredths" ::= { pduOutletMeterEntry 19 } --###########################################################################################-- --tempSensorTable-- --###########################################################################################-- tempSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF TempSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Remote Temperature (RT) sensor" ::= { imd 4 } tempSensorEntry OBJECT-TYPE SYNTAX TempSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the tempSensorTable table: each entry contains an index and other sensor details" INDEX { tempSensorIndex } ::= { tempSensorTable 1 } TempSensorEntry ::= SEQUENCE { tempSensorIndex Integer32, tempSensorSerial DisplayString, tempSensorLabel SnmpAdminString, tempSensorAvail Gauge32, tempSensorTemp Integer32 } tempSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { tempSensorEntry 1 } tempSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { tempSensorEntry 2 } tempSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { tempSensorEntry 3 } tempSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { tempSensorEntry 4 } tempSensorTemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { tempSensorEntry 5 } --###########################################################################################-- --airFlowSensorTable-- --###########################################################################################-- airFlowSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF AirFlowSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor" ::= { imd 5 } airFlowSensorEntry OBJECT-TYPE SYNTAX AirFlowSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the airFlowSensorTable table: each entry contains an index and other sensor details" INDEX { airFlowSensorIndex } ::= { airFlowSensorTable 1 } AirFlowSensorEntry ::= SEQUENCE { airFlowSensorIndex Integer32, airFlowSensorSerial DisplayString, airFlowSensorLabel SnmpAdminString, airFlowSensorAvail Gauge32, airFlowSensorTemp Integer32, airFlowSensorFlow Integer32, airFlowSensorHumidity Integer32, airFlowSensorDewPoint Integer32 } airFlowSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { airFlowSensorEntry 1 } airFlowSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { airFlowSensorEntry 2 } airFlowSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { airFlowSensorEntry 3 } airFlowSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { airFlowSensorEntry 4 } airFlowSensorTemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { airFlowSensorEntry 5 } airFlowSensorFlow OBJECT-TYPE SYNTAX Integer32(0..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Airflow reading. Still air will be less than 20, while rushing air will be around 100." ::= { airFlowSensorEntry 6 } airFlowSensorHumidity OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Humidity reading" ::= { airFlowSensorEntry 7 } airFlowSensorDewPoint OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { airFlowSensorEntry 8 } --###########################################################################################-- --t3hdSensorTable-- --###########################################################################################-- t3hdSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF T3hdSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Remote Temperature x 3, Humidity and Dewpoint Sensor" ::= { imd 8 } t3hdSensorEntry OBJECT-TYPE SYNTAX T3hdSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the t3hdSensorTable table: each entry contains an index and other sensor details" INDEX { t3hdSensorIndex } ::= { t3hdSensorTable 1 } T3hdSensorEntry ::= SEQUENCE { t3hdSensorIndex Integer32, t3hdSensorSerial DisplayString, t3hdSensorLabel SnmpAdminString, t3hdSensorAvail Gauge32, t3hdSensorIntLabel SnmpAdminString, t3hdSensorIntTemp Integer32, t3hdSensorIntHumidity Integer32, t3hdSensorIntDewPoint Integer32, t3hdSensorExtAAvail Gauge32, t3hdSensorExtALabel SnmpAdminString, t3hdSensorExtATemp Integer32, t3hdSensorExtBAvail Gauge32, t3hdSensorExtBLabel SnmpAdminString, t3hdSensorExtBTemp Integer32 } t3hdSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { t3hdSensorEntry 1 } t3hdSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { t3hdSensorEntry 2 } t3hdSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { t3hdSensorEntry 3 } t3hdSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { t3hdSensorEntry 4 } t3hdSensorIntLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Internal label (user-defined)" ::= { t3hdSensorEntry 5 } t3hdSensorIntTemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { t3hdSensorEntry 6 } t3hdSensorIntHumidity OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Internal humidity" ::= { t3hdSensorEntry 7 } t3hdSensorIntDewPoint OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { t3hdSensorEntry 8 } t3hdSensorExtAAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "External A status: 0 = Unavailable 1 = Available" ::= { t3hdSensorEntry 9 } t3hdSensorExtALabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "External A label (user-defined)" ::= { t3hdSensorEntry 10 } t3hdSensorExtATemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { t3hdSensorEntry 11 } t3hdSensorExtBAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "External B status: 0 = Unavailable 1 = Available" ::= { t3hdSensorEntry 12 } t3hdSensorExtBLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "External B label (user-defined)" ::= { t3hdSensorEntry 13 } t3hdSensorExtBTemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { t3hdSensorEntry 14 } --###########################################################################################-- --thdSensorTable-- --###########################################################################################-- thdSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF ThdSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Remote Temperature, Humidity, and Dewpoint (THD) Sensor" ::= { imd 9 } thdSensorEntry OBJECT-TYPE SYNTAX ThdSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the thdSensorTable table: each entry contains an index and other sensor details" INDEX { thdSensorIndex } ::= { thdSensorTable 1 } ThdSensorEntry ::= SEQUENCE { thdSensorIndex Integer32, thdSensorSerial DisplayString, thdSensorLabel SnmpAdminString, thdSensorAvail Gauge32, thdSensorTemp Integer32, thdSensorHumidity Integer32, thdSensorDewPoint Integer32 } thdSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { thdSensorEntry 1 } thdSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { thdSensorEntry 2 } thdSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { thdSensorEntry 3 } thdSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { thdSensorEntry 4 } thdSensorTemp OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { thdSensorEntry 5 } thdSensorHumidity OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Humidity value" ::= { thdSensorEntry 6 } thdSensorDewPoint OBJECT-TYPE SYNTAX Integer32(-400..2540) UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { thdSensorEntry 7 } --###########################################################################################-- --a2dSensorTable-- --###########################################################################################-- a2dSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF A2dSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Analog measurement (A2D) sensor (voltage, current, or dry-contact)" ::= { imd 11 } a2dSensorEntry OBJECT-TYPE SYNTAX A2dSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the a2dSensorTable table: each entry contains an index and other sensor details" INDEX { a2dSensorIndex } ::= { a2dSensorTable 1 } A2dSensorEntry ::= SEQUENCE { a2dSensorIndex Integer32, a2dSensorSerial DisplayString, a2dSensorLabel SnmpAdminString, a2dSensorAvail Gauge32, a2dSensorValue Integer32, a2dSensorDisplayValue SnmpAdminString, a2dSensorMode INTEGER, a2dSensorUnits SnmpAdminString, a2dSensorMin Integer32, a2dSensorMax Integer32, a2dSensorLowLabel SnmpAdminString, a2dSensorHighLabel SnmpAdminString, a2dSensorAnalogLabel SnmpAdminString } a2dSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { a2dSensorEntry 1 } a2dSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { a2dSensorEntry 2 } a2dSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { a2dSensorEntry 3 } a2dSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { a2dSensorEntry 4 } a2dSensorValue OBJECT-TYPE SYNTAX Integer32(-1000000..1000000) MAX-ACCESS read-only STATUS current DESCRIPTION "Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode." ::= { a2dSensorEntry 5 } a2dSensorDisplayValue OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue." ::= { a2dSensorEntry 6 } a2dSensorMode OBJECT-TYPE SYNTAX INTEGER { door(1), powerFailure(2), flood(3), wscLeak(4), wscFault(5), smoke(6), ivsNegGnd(7), ivsPosGnd(8), customVoltage(9), customBinary(10), customCurrent(11) } MAX-ACCESS read-write STATUS current DESCRIPTION "Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current)" ::= { a2dSensorEntry 7 } a2dSensorUnits OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..7)) MAX-ACCESS read-write STATUS current DESCRIPTION "The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode." ::= { a2dSensorEntry 8 } a2dSensorMin OBJECT-TYPE SYNTAX Integer32(-1000000..1000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode." ::= { a2dSensorEntry 9 } a2dSensorMax OBJECT-TYPE SYNTAX Integer32(-1000000..1000000) MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode." ::= { a2dSensorEntry 10 } a2dSensorLowLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode." ::= { a2dSensorEntry 11 } a2dSensorHighLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode." ::= { a2dSensorEntry 12 } a2dSensorAnalogLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Label for the analog measurement" ::= { a2dSensorEntry 13 } --###########################################################################################-- --humiditySensorTable-- --###########################################################################################-- humiditySensorTable OBJECT-TYPE SYNTAX SEQUENCE OF HumiditySensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Remote humidity sensor" ::= { imd 12 } humiditySensorEntry OBJECT-TYPE SYNTAX HumiditySensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the humiditySensorTable table: each entry contains an index and other sensor details" INDEX { humiditySensorIndex } ::= { humiditySensorTable 1 } HumiditySensorEntry ::= SEQUENCE { humiditySensorIndex Integer32, humiditySensorSerial DisplayString, humiditySensorLabel SnmpAdminString, humiditySensorAvail Gauge32, humiditySensorValue Integer32 } humiditySensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { humiditySensorEntry 1 } humiditySensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { humiditySensorEntry 2 } humiditySensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { humiditySensorEntry 3 } humiditySensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { humiditySensorEntry 4 } humiditySensorValue OBJECT-TYPE SYNTAX Integer32(0..100) MAX-ACCESS read-only STATUS current DESCRIPTION "Humidity value" ::= { humiditySensorEntry 5 } --###########################################################################################-- --sn2dSensorTable-- --###########################################################################################-- sn2dSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF Sn2dSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "2 Door Switch Sensor (SN-2D)" ::= { imd 13 } sn2dSensorEntry OBJECT-TYPE SYNTAX Sn2dSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the sn2dSensorTable table: each entry contains an index and other sensor details" INDEX { sn2dSensorIndex } ::= { sn2dSensorTable 1 } Sn2dSensorEntry ::= SEQUENCE { sn2dSensorIndex Integer32, sn2dSensorSerial DisplayString, sn2dSensorLabel SnmpAdminString, sn2dSensorAvail Gauge32, sn2dSensorDoor1Label SnmpAdminString, sn2dSensorDoor1State INTEGER, sn2dSensorDoor1DisplayState SnmpAdminString, sn2dSensorDoor2Label SnmpAdminString, sn2dSensorDoor2State INTEGER, sn2dSensorDoor2DisplayState SnmpAdminString } sn2dSensorIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table entry index value" ::= { sn2dSensorEntry 1 } sn2dSensorSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { sn2dSensorEntry 2 } sn2dSensorLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "User-defined label" ::= { sn2dSensorEntry 3 } sn2dSensorAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { sn2dSensorEntry 4 } sn2dSensorDoor1Label OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Door switch 1 label" ::= { sn2dSensorEntry 5 } sn2dSensorDoor1State OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Door switch 1 state: 1 = open 2 = closed" ::= { sn2dSensorEntry 6 } sn2dSensorDoor1DisplayState OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Door switch 1 state given as a string" ::= { sn2dSensorEntry 7 } sn2dSensorDoor2Label OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "Door switch 2 label" ::= { sn2dSensorEntry 8 } sn2dSensorDoor2State OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Door switch 2 state: 1 = open 2 = closed" ::= { sn2dSensorEntry 9 } sn2dSensorDoor2DisplayState OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Door switch 2 state given as a string" ::= { sn2dSensorEntry 10 } --###########################################################################################-- --cooling-- --###########################################################################################-- cooling OBJECT IDENTIFIER ::= { imd 30 } --###########################################################################################-- --vrc-- --###########################################################################################-- vrc OBJECT IDENTIFIER ::= { cooling 1 } --###########################################################################################-- --vrcMainTable-- --###########################################################################################-- vrcMainTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcMainEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains general VRC information" ::= { vrc 1 } vrcMainEntry OBJECT-TYPE SYNTAX VrcMainEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcMainTable: each entry represents a VRC device" INDEX { vrcMainIndex } ::= { vrcMainTable 1 } VrcMainEntry ::= SEQUENCE { vrcMainIndex Integer32, vrcMainSerial DisplayString, vrcMainName SnmpAdminString, vrcMainLabel SnmpAdminString, vrcMainAvail Gauge32 } vrcMainIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcMainEntry 1 } vrcMainSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Serial number" ::= { vrcMainEntry 2 } vrcMainName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "VRC name (factory-assigned)" ::= { vrcMainEntry 3 } vrcMainLabel OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (0..25)) MAX-ACCESS read-write STATUS current DESCRIPTION "VRC label (user-defined)" ::= { vrcMainEntry 4 } vrcMainAvail OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS current DESCRIPTION "Device availability: 0 = Unavailable 1 = Available 2 = Partially Unavailable" ::= { vrcMainEntry 5 } --###########################################################################################-- --vrcMainPtTable-- --###########################################################################################-- vrcMainPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcMainPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains general VRC status" ::= { vrc 2 } vrcMainPtEntry OBJECT-TYPE SYNTAX VrcMainPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcMainPtTable: each entry contains status data for a VRC device" INDEX { vrcMainPtIndex } ::= { vrcMainPtTable 1 } VrcMainPtEntry ::= SEQUENCE { vrcMainPtIndex Integer32, vrcMainPtRunState INTEGER, vrcMainPtEevOpened Integer32, vrcMainPtAlarmNumbers Integer32, vrcMainPtHistoryAlarmNumbers Integer32, vrcMainPtHpAbnRecordCnt Integer32, vrcMainPtMonitorBaudrate INTEGER, vrcMainPtMonitorAddress Integer32, vrcMainPtLp TruthValue, vrcMainPtFilterMaintRemind TruthValue, vrcMainPtCoolingFlag TruthValue, vrcMainPtFirstOnFlag TruthValue, vrcMainPtNewAlarmFlag TruthValue, vrcMainPtComAlarmOutState TruthValue, vrcMainPtHighWaterInput TruthValue, vrcMainPtHighWaterAlarm TruthValue, vrcMainPtWaterUnderFloorAlarm TruthValue, vrcMainPtSwShutDownStatus TruthValue, vrcMainPtRemoteShutdown TruthValue, vrcMainPtRemoteShutDownFlag TruthValue, vrcMainPtRemoteShutDownAlarm TruthValue, vrcMainPtHmiShutDownFlag TruthValue, vrcMainPtLpAlarm TruthValue, vrcMainPtHpAlarm TruthValue, vrcMainPtLpFreqAlarm TruthValue, vrcMainPtHpFreqAlarm TruthValue, vrcMainPtLpSensorFailAlarm TruthValue, vrcMainPtHpSensorFailAlarm TruthValue, vrcMainPtEevCommFailAlarm TruthValue } vrcMainPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcMainPtEntry 1 } vrcMainPtRunState OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "VRC run state: 1 = on 2 = off" ::= { vrcMainPtEntry 2 } vrcMainPtEevOpened OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Eev opened value (percent)" ::= { vrcMainPtEntry 3 } vrcMainPtAlarmNumbers OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-only STATUS current DESCRIPTION "Alarm numbers value" ::= { vrcMainPtEntry 4 } vrcMainPtHistoryAlarmNumbers OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-only STATUS current DESCRIPTION "History alarm numbers value" ::= { vrcMainPtEntry 5 } vrcMainPtHpAbnRecordCnt OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-only STATUS current DESCRIPTION "Hp Abnormal record count" ::= { vrcMainPtEntry 6 } vrcMainPtMonitorBaudrate OBJECT-TYPE SYNTAX INTEGER { error(1), baud1200(2), baud2400(3), baud4800(4), baud9600(5), baud19200(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Monitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200" ::= { vrcMainPtEntry 7 } vrcMainPtMonitorAddress OBJECT-TYPE SYNTAX Integer32(1..247) MAX-ACCESS read-only STATUS current DESCRIPTION "Monitor address" ::= { vrcMainPtEntry 8 } vrcMainPtLp OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Lp status" ::= { vrcMainPtEntry 9 } vrcMainPtFilterMaintRemind OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Filter maintenance reminder status" ::= { vrcMainPtEntry 10 } vrcMainPtCoolingFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Cooling flag" ::= { vrcMainPtEntry 11 } vrcMainPtFirstOnFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "First on flag" ::= { vrcMainPtEntry 12 } vrcMainPtNewAlarmFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "New alarm flag" ::= { vrcMainPtEntry 13 } vrcMainPtComAlarmOutState OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Common alarm output state" ::= { vrcMainPtEntry 14 } vrcMainPtHighWaterInput OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "High water input" ::= { vrcMainPtEntry 15 } vrcMainPtHighWaterAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "High water alarm status" ::= { vrcMainPtEntry 16 } vrcMainPtWaterUnderFloorAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Water under floor alarm status" ::= { vrcMainPtEntry 17 } vrcMainPtSwShutDownStatus OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Software shutdown status" ::= { vrcMainPtEntry 18 } vrcMainPtRemoteShutdown OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Remote shutdown status" ::= { vrcMainPtEntry 19 } vrcMainPtRemoteShutDownFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Remote shutdown flag" ::= { vrcMainPtEntry 20 } vrcMainPtRemoteShutDownAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Remote shutdown alarm status" ::= { vrcMainPtEntry 21 } vrcMainPtHmiShutDownFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Hmi shutdown flag" ::= { vrcMainPtEntry 22 } vrcMainPtLpAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure alarm status" ::= { vrcMainPtEntry 23 } vrcMainPtHpAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure alarm status" ::= { vrcMainPtEntry 24 } vrcMainPtLpFreqAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure frequently alarm status" ::= { vrcMainPtEntry 25 } vrcMainPtHpFreqAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure frequently alarm status" ::= { vrcMainPtEntry 26 } vrcMainPtLpSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Low pressure sensor failure alarm status" ::= { vrcMainPtEntry 27 } vrcMainPtHpSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "High pressure sensor failure alarm status" ::= { vrcMainPtEntry 28 } vrcMainPtEevCommFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Eev communication failure alarm status" ::= { vrcMainPtEntry 29 } --###########################################################################################-- --vrcMainCfgTable-- --###########################################################################################-- vrcMainCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcMainCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains general VRC configuration" ::= { vrc 3 } vrcMainCfgEntry OBJECT-TYPE SYNTAX VrcMainCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcMainCfgTable: each entry contains general config fields for a VRC device" INDEX { vrcMainCfgIndex } ::= { vrcMainCfgTable 1 } VrcMainCfgEntry ::= SEQUENCE { vrcMainCfgIndex Integer32, vrcMainCfgModelSelect INTEGER, vrcMainCfgSystemTimeYear Integer32, vrcMainCfgSystemTimeMonth Integer32, vrcMainCfgSystemTimeDay Integer32, vrcMainCfgSystemTimeHour Integer32, vrcMainCfgSystemTimeMin Integer32, vrcMainCfgSystemTimeSec Integer32, vrcMainCfgEevShtSettingMin Integer32, vrcMainCfgEevShtSettingMax Integer32, vrcMainCfgEevValveCloseSht Integer32, vrcMainCfgEevMopPressSetting Integer32, vrcMainCfgLpdt Integer32, vrcMainCfgDeadBand Integer32, vrcMainCfgOnOffSwitch TruthValue, vrcMainCfgVacuumState TruthValue, vrcMainCfgControlMode INTEGER, vrcMainCfgManualRunEnable TruthValue, vrcMainCfgRemShutdownInput TruthValue, vrcMainCfgMonitorShutDownFlag TruthValue, vrcMainCfgFirstOnPassword Integer32, vrcMainCfgFilterMaintSetting TruthValue, vrcMainCfgFilterMaintRemindTime Integer32, vrcMainCfgFilterMaintRemindCtrl INTEGER, vrcMainCfgCommonAlarmOutputDir TruthValue, vrcMainCfgHpAbnAlarmSetting Integer32, vrcMainCfgLpAlarmCtrl INTEGER, vrcMainCfgHpAlarmCtrl INTEGER, vrcMainCfgLpFreqAlarmCtrl INTEGER, vrcMainCfgHpFreqAlarmCtrl INTEGER, vrcMainCfgLpSensorFailAlarmCtrl INTEGER, vrcMainCfgHpSensorFailAlarmCtrl INTEGER, vrcMainCfgHighWaterAlarmCtrl INTEGER, vrcMainCfgRemShutdownAlarmCtrl INTEGER, vrcMainCfgEevCommFailAlarmCtrl INTEGER } vrcMainCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcMainCfgEntry 1 } vrcMainCfgModelSelect OBJECT-TYPE SYNTAX INTEGER { tmLoc(1), r035Ap(2), r035Ak(3), scLoc(4), zeroULoc(5), r035Ep(6), r035Ek(7) } MAX-ACCESS read-write STATUS current DESCRIPTION "Model Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZ" ::= { vrcMainCfgEntry 2 } vrcMainCfgSystemTimeYear OBJECT-TYPE SYNTAX Integer32(2000..2099) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - year" ::= { vrcMainCfgEntry 3 } vrcMainCfgSystemTimeMonth OBJECT-TYPE SYNTAX Integer32(1..12) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - month" ::= { vrcMainCfgEntry 4 } vrcMainCfgSystemTimeDay OBJECT-TYPE SYNTAX Integer32(1..31) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - day" ::= { vrcMainCfgEntry 5 } vrcMainCfgSystemTimeHour OBJECT-TYPE SYNTAX Integer32(0..23) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - hour" ::= { vrcMainCfgEntry 6 } vrcMainCfgSystemTimeMin OBJECT-TYPE SYNTAX Integer32(0..59) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - minutes" ::= { vrcMainCfgEntry 7 } vrcMainCfgSystemTimeSec OBJECT-TYPE SYNTAX Integer32(0..59) MAX-ACCESS read-write STATUS current DESCRIPTION "System time - seconds" ::= { vrcMainCfgEntry 8 } vrcMainCfgEevShtSettingMin OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Min Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359" ::= { vrcMainCfgEntry 9 } vrcMainCfgEevShtSettingMax OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Max Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359" ::= { vrcMainCfgEntry 10 } vrcMainCfgEevValveCloseSht OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Eev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179" ::= { vrcMainCfgEntry 11 } vrcMainCfgEevMopPressSetting OBJECT-TYPE SYNTAX Integer32(0..200) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Eev mop pressure setting in tenths of a bar." ::= { vrcMainCfgEntry 12 } vrcMainCfgLpdt OBJECT-TYPE SYNTAX Integer32(30..600) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure dt in seconds" ::= { vrcMainCfgEntry 13 } vrcMainCfgDeadBand OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Dead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35" ::= { vrcMainCfgEntry 14 } vrcMainCfgOnOffSwitch OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "On-off switch" ::= { vrcMainCfgEntry 15 } vrcMainCfgVacuumState OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Vacuum state" ::= { vrcMainCfgEntry 16 } vrcMainCfgControlMode OBJECT-TYPE SYNTAX INTEGER { supply(1), return(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Control mode: 1 = supply 2 = return" ::= { vrcMainCfgEntry 17 } vrcMainCfgManualRunEnable OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Manual run enable" ::= { vrcMainCfgEntry 18 } vrcMainCfgRemShutdownInput OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Remote shutdown input" ::= { vrcMainCfgEntry 19 } vrcMainCfgMonitorShutDownFlag OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Monitor shutdown flag" ::= { vrcMainCfgEntry 20 } vrcMainCfgFirstOnPassword OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-write STATUS current DESCRIPTION "First on password value" ::= { vrcMainCfgEntry 21 } vrcMainCfgFilterMaintSetting OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Filter maintenance setting" ::= { vrcMainCfgEntry 22 } vrcMainCfgFilterMaintRemindTime OBJECT-TYPE SYNTAX Integer32(30..360) UNITS "days" MAX-ACCESS read-write STATUS current DESCRIPTION "Time between filter maintenance reminders in days" ::= { vrcMainCfgEntry 23 } vrcMainCfgFilterMaintRemindCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Filter maintenance reminder: 1 = close 2 = suspend 3 = open" ::= { vrcMainCfgEntry 24 } vrcMainCfgCommonAlarmOutputDir OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Common alarm output direction" ::= { vrcMainCfgEntry 25 } vrcMainCfgHpAbnAlarmSetting OBJECT-TYPE SYNTAX Integer32(300..360) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Abnormal high pressure alarm value in tenths of a bar" ::= { vrcMainCfgEntry 26 } vrcMainCfgLpAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 27 } vrcMainCfgHpAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "High pressure alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 28 } vrcMainCfgLpFreqAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure frequently alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 29 } vrcMainCfgHpFreqAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "High pressure frequently alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 30 } vrcMainCfgLpSensorFailAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Low pressure sensor failure alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 31 } vrcMainCfgHpSensorFailAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "High pressure sensor failure alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 32 } vrcMainCfgHighWaterAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "High water alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcMainCfgEntry 33 } vrcMainCfgRemShutdownAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Remote shutdown alarm control: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 34 } vrcMainCfgEevCommFailAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Eev communication failure alarm: 2 = suspend 3 = open" ::= { vrcMainCfgEntry 35 } --###########################################################################################-- --vrcOutFanPtTable-- --###########################################################################################-- vrcOutFanPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcOutFanPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC out-fan status" ::= { vrc 4 } vrcOutFanPtEntry OBJECT-TYPE SYNTAX VrcOutFanPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan" INDEX { vrcOutFanPtIndex } ::= { vrcOutFanPtTable 1 } VrcOutFanPtEntry ::= SEQUENCE { vrcOutFanPtIndex Integer32, vrcOutFanPtName SnmpAdminString, vrcOutFanPtSpeed Integer32 } vrcOutFanPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcOutFanPtEntry 1 } vrcOutFanPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Out-fan name (factory-assigned)" ::= { vrcOutFanPtEntry 2 } vrcOutFanPtSpeed OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan speed (percent)" ::= { vrcOutFanPtEntry 3 } --###########################################################################################-- --vrcOutFanCfgTable-- --###########################################################################################-- vrcOutFanCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcOutFanCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC out-fan configuration" ::= { vrc 5 } vrcOutFanCfgEntry OBJECT-TYPE SYNTAX VrcOutFanCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan" INDEX { vrcOutFanCfgIndex } ::= { vrcOutFanCfgTable 1 } VrcOutFanCfgEntry ::= SEQUENCE { vrcOutFanCfgIndex Integer32, vrcOutFanCfgStartPress Integer32, vrcOutFanCfgPressSetting Integer32, vrcOutFanCfgMinPowerVoltage Integer32, vrcOutFanCfgMaxPowerVoltage Integer32, vrcOutFanCfgSpeed Integer32 } vrcOutFanCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcOutFanCfgEntry 1 } vrcOutFanCfgStartPress OBJECT-TYPE SYNTAX Integer32(190..250) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Out-fan start pressure in tenths of a bar" ::= { vrcOutFanCfgEntry 2 } vrcOutFanCfgPressSetting OBJECT-TYPE SYNTAX Integer32(50..80) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Out-fan pressure setting in tenths of a bar" ::= { vrcOutFanCfgEntry 3 } vrcOutFanCfgMinPowerVoltage OBJECT-TYPE SYNTAX Integer32(30..50) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Min out-fan voltage (percent)" ::= { vrcOutFanCfgEntry 4 } vrcOutFanCfgMaxPowerVoltage OBJECT-TYPE SYNTAX Integer32(60..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Max out-fan voltage (percent)" ::= { vrcOutFanCfgEntry 5 } vrcOutFanCfgSpeed OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Out-fan speed (percent)" ::= { vrcOutFanCfgEntry 6 } --###########################################################################################-- --vrcInFanPtTable-- --###########################################################################################-- vrcInFanPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcInFanPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC in-fan status" ::= { vrc 6 } vrcInFanPtEntry OBJECT-TYPE SYNTAX VrcInFanPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcInFanPtTable: each entry represents data for a VRC in- fan" INDEX { vrcInFanPtIndex } ::= { vrcInFanPtTable 1 } VrcInFanPtEntry ::= SEQUENCE { vrcInFanPtIndex Integer32, vrcInFanPtName SnmpAdminString, vrcInFanPtRunTimeHours Integer32, vrcInFanPtStartStopCount Integer32 } vrcInFanPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcInFanPtEntry 1 } vrcInFanPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "In-fan name (factory-assigned)" ::= { vrcInFanPtEntry 2 } vrcInFanPtRunTimeHours OBJECT-TYPE SYNTAX Integer32(-32768..32767) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "In-fan run time in hours" ::= { vrcInFanPtEntry 3 } vrcInFanPtStartStopCount OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-only STATUS current DESCRIPTION "In-fan start/stop count" ::= { vrcInFanPtEntry 4 } --###########################################################################################-- --vrcInFanCfgTable-- --###########################################################################################-- vrcInFanCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcInFanCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC in-fan configuration" ::= { vrc 7 } vrcInFanCfgEntry OBJECT-TYPE SYNTAX VrcInFanCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan" INDEX { vrcInFanCfgIndex } ::= { vrcInFanCfgTable 1 } VrcInFanCfgEntry ::= SEQUENCE { vrcInFanCfgIndex Integer32, vrcInFanCfgOutputStatus TruthValue, vrcInFanCfgLowSpeedStep Integer32, vrcInFanCfgHighSpeedStep Integer32, vrcInFanCfgMinSpeed Integer32, vrcInFanCfgStandardSpeed Integer32, vrcInFanCfgMinCfc Integer32, vrcInFanCfgStandardCfc Integer32, vrcInFanCfgStartDelay Integer32, vrcInFanCfgStopDelay Integer32, vrcInFanCfgReduceSpeedDelay Integer32, vrcInFanCfgJumpBand1 Integer32, vrcInFanCfgJumpBand2 Integer32, vrcInFanCfgJumpBand3 Integer32, vrcInFanCfgJumpBand4 Integer32, vrcInFanCfgJumpBand5 Integer32, vrcInFanCfgJumpFreq1 Integer32, vrcInFanCfgJumpFreq2 Integer32, vrcInFanCfgJumpFreq3 Integer32, vrcInFanCfgJumpFreq4 Integer32, vrcInFanCfgJumpFreq5 Integer32, vrcInFanCfgTempP Integer32, vrcInFanCfgTempI Integer32, vrcInFanCfgTempD Integer32 } vrcInFanCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcInFanCfgEntry 1 } vrcInFanCfgOutputStatus OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan output status" ::= { vrcInFanCfgEntry 2 } vrcInFanCfgLowSpeedStep OBJECT-TYPE SYNTAX Integer32(1..20) UNITS "0.1%/s" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan low speed step in tenths of a percent per second" ::= { vrcInFanCfgEntry 3 } vrcInFanCfgHighSpeedStep OBJECT-TYPE SYNTAX Integer32(1..50) UNITS "0.1%/s" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan high speed step in tenths of a percent per second" ::= { vrcInFanCfgEntry 4 } vrcInFanCfgMinSpeed OBJECT-TYPE SYNTAX Integer32(30..80) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Min in-fan speed (percent)" ::= { vrcInFanCfgEntry 5 } vrcInFanCfgStandardSpeed OBJECT-TYPE SYNTAX Integer32(80..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Standard in-fan speed (percent)" ::= { vrcInFanCfgEntry 6 } vrcInFanCfgMinCfc OBJECT-TYPE SYNTAX Integer32(0..30) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Min in-fan cfc (percent)" ::= { vrcInFanCfgEntry 7 } vrcInFanCfgStandardCfc OBJECT-TYPE SYNTAX Integer32(85..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Standard in-fan cfc (percent)" ::= { vrcInFanCfgEntry 8 } vrcInFanCfgStartDelay OBJECT-TYPE SYNTAX Integer32(10..600) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan start delay in seconds" ::= { vrcInFanCfgEntry 9 } vrcInFanCfgStopDelay OBJECT-TYPE SYNTAX Integer32(10..300) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan stop delay in seconds" ::= { vrcInFanCfgEntry 10 } vrcInFanCfgReduceSpeedDelay OBJECT-TYPE SYNTAX Integer32(0..300) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan reduce speed delay in seconds" ::= { vrcInFanCfgEntry 11 } vrcInFanCfgJumpBand1 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump band 1 in tenths of a percent" ::= { vrcInFanCfgEntry 12 } vrcInFanCfgJumpBand2 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump band 2 in tenths of a percent" ::= { vrcInFanCfgEntry 13 } vrcInFanCfgJumpBand3 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump band 3 in tenths of a percent" ::= { vrcInFanCfgEntry 14 } vrcInFanCfgJumpBand4 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump band 4 in tenths of a percent" ::= { vrcInFanCfgEntry 15 } vrcInFanCfgJumpBand5 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump band 5 in tenths of a percent" ::= { vrcInFanCfgEntry 16 } vrcInFanCfgJumpFreq1 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump frequency 1 in tenths of a percent" ::= { vrcInFanCfgEntry 17 } vrcInFanCfgJumpFreq2 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump frequency 2 in tenths of a percent" ::= { vrcInFanCfgEntry 18 } vrcInFanCfgJumpFreq3 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump frequency 3 in tenths of a percent" ::= { vrcInFanCfgEntry 19 } vrcInFanCfgJumpFreq4 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump frequency 4 in tenths of a percent" ::= { vrcInFanCfgEntry 20 } vrcInFanCfgJumpFreq5 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan jump frequency 5 in tenths of a percent" ::= { vrcInFanCfgEntry 21 } vrcInFanCfgTempP OBJECT-TYPE SYNTAX Integer32(10..150) UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo." ::= { vrcInFanCfgEntry 22 } vrcInFanCfgTempI OBJECT-TYPE SYNTAX Integer32(0..900) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan temperature I in seconds" ::= { vrcInFanCfgEntry 23 } vrcInFanCfgTempD OBJECT-TYPE SYNTAX Integer32(0..900) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "In-fan temperature D in seconds" ::= { vrcInFanCfgEntry 24 } --###########################################################################################-- --vrcCompPtTable-- --###########################################################################################-- vrcCompPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcCompPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC compressor status" ::= { vrc 8 } vrcCompPtEntry OBJECT-TYPE SYNTAX VrcCompPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcCompPtTable: each entry represents data for a VRC compressor" INDEX { vrcCompPtIndex } ::= { vrcCompPtTable 1 } VrcCompPtEntry ::= SEQUENCE { vrcCompPtIndex Integer32, vrcCompPtName SnmpAdminString, vrcCompPtCapacity Integer32, vrcCompPtRunTimeHours Integer32, vrcCompPtStartStopCount Integer32, vrcCompPtDriverFaultU00 TruthValue, vrcCompPtDriverFaultU01 TruthValue, vrcCompPtDriverFaultU02 TruthValue, vrcCompPtDriverFaultU03 TruthValue, vrcCompPtDriverFaultU04 TruthValue, vrcCompPtDriverFaultU05 TruthValue, vrcCompPtDriverFaultU06 TruthValue, vrcCompPtDriverFaultU07 TruthValue, vrcCompPtDriverFaultU08 TruthValue, vrcCompPtDriverFaultU09 TruthValue, vrcCompPtDriverFaultU10 TruthValue, vrcCompPtDriverFaultU11 TruthValue, vrcCompPtDriverFaultU12 TruthValue, vrcCompPtDriverFaultU13 TruthValue, vrcCompPtDriverFaultU14 TruthValue, vrcCompPtDriverFaultU15 TruthValue, vrcCompPtDriverCommFailAlarm TruthValue, vrcCompPtFaultLockAlarm TruthValue } vrcCompPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcCompPtEntry 1 } vrcCompPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor name (factory-assigned)" ::= { vrcCompPtEntry 2 } vrcCompPtCapacity OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor capacity value (percent)" ::= { vrcCompPtEntry 3 } vrcCompPtRunTimeHours OBJECT-TYPE SYNTAX Integer32(-32768..32767) UNITS "hours" MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor run time in hours" ::= { vrcCompPtEntry 4 } vrcCompPtStartStopCount OBJECT-TYPE SYNTAX Integer32(-32768..32767) MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor start/stop count" ::= { vrcCompPtEntry 5 } vrcCompPtDriverFaultU00 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U00 state" ::= { vrcCompPtEntry 6 } vrcCompPtDriverFaultU01 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U01 state" ::= { vrcCompPtEntry 7 } vrcCompPtDriverFaultU02 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U02 state" ::= { vrcCompPtEntry 8 } vrcCompPtDriverFaultU03 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U03 state" ::= { vrcCompPtEntry 9 } vrcCompPtDriverFaultU04 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U04 state" ::= { vrcCompPtEntry 10 } vrcCompPtDriverFaultU05 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U05 state" ::= { vrcCompPtEntry 11 } vrcCompPtDriverFaultU06 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U06 state" ::= { vrcCompPtEntry 12 } vrcCompPtDriverFaultU07 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U07 state" ::= { vrcCompPtEntry 13 } vrcCompPtDriverFaultU08 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U08 state" ::= { vrcCompPtEntry 14 } vrcCompPtDriverFaultU09 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U09 state" ::= { vrcCompPtEntry 15 } vrcCompPtDriverFaultU10 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U10 state" ::= { vrcCompPtEntry 16 } vrcCompPtDriverFaultU11 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U11 state" ::= { vrcCompPtEntry 17 } vrcCompPtDriverFaultU12 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U12 state" ::= { vrcCompPtEntry 18 } vrcCompPtDriverFaultU13 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U13 state" ::= { vrcCompPtEntry 19 } vrcCompPtDriverFaultU14 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U14 state" ::= { vrcCompPtEntry 20 } vrcCompPtDriverFaultU15 OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver fault alarm U15 state" ::= { vrcCompPtEntry 21 } vrcCompPtDriverCommFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor driver communication failure alarm state" ::= { vrcCompPtEntry 22 } vrcCompPtFaultLockAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Compressor fault lock alarm state" ::= { vrcCompPtEntry 23 } --###########################################################################################-- --vrcCompCfgTable-- --###########################################################################################-- vrcCompCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcCompCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC compressor configuration" ::= { vrc 9 } vrcCompCfgEntry OBJECT-TYPE SYNTAX VrcCompCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor" INDEX { vrcCompCfgIndex } ::= { vrcCompCfgTable 1 } VrcCompCfgEntry ::= SEQUENCE { vrcCompCfgIndex Integer32, vrcCompCfgOutputStatus TruthValue, vrcCompCfgOutputDeadBand Integer32, vrcCompCfgCapacityOutputValue Integer32, vrcCompCfgMinCapacity Integer32, vrcCompCfgStartCapacity Integer32, vrcCompCfgStandardCapacity Integer32, vrcCompCfgStartCfc Integer32, vrcCompCfgStopCfc Integer32, vrcCompCfgMinRunTime Integer32, vrcCompCfgMinStopTime Integer32, vrcCompCfgJumpBand1 Integer32, vrcCompCfgJumpBand2 Integer32, vrcCompCfgJumpBand3 Integer32, vrcCompCfgJumpBand4 Integer32, vrcCompCfgJumpBand5 Integer32, vrcCompCfgJumpFreq1 Integer32, vrcCompCfgJumpFreq2 Integer32, vrcCompCfgJumpFreq3 Integer32, vrcCompCfgJumpFreq4 Integer32, vrcCompCfgJumpFreq5 Integer32, vrcCompCfgTempP Integer32, vrcCompCfgTempI Integer32, vrcCompCfgTempD Integer32, vrcCompCfgDriverFaultAlmCtrl INTEGER, vrcCompCfgDriverCommFailAlmCtrl INTEGER, vrcCompCfgFaultLockAlmCtrl INTEGER } vrcCompCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcCompCfgEntry 1 } vrcCompCfgOutputStatus OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor output status" ::= { vrcCompCfgEntry 2 } vrcCompCfgOutputDeadBand OBJECT-TYPE SYNTAX Integer32(0..50) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor output dead band in tenths of a percent" ::= { vrcCompCfgEntry 3 } vrcCompCfgCapacityOutputValue OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor capacity output (percent)" ::= { vrcCompCfgEntry 4 } vrcCompCfgMinCapacity OBJECT-TYPE SYNTAX Integer32(15..50) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor min capacity (percent)" ::= { vrcCompCfgEntry 5 } vrcCompCfgStartCapacity OBJECT-TYPE SYNTAX Integer32(40..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor start capacity (percent)" ::= { vrcCompCfgEntry 6 } vrcCompCfgStandardCapacity OBJECT-TYPE SYNTAX Integer32(80..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor standard capacity (percent)" ::= { vrcCompCfgEntry 7 } vrcCompCfgStartCfc OBJECT-TYPE SYNTAX Integer32(1..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor start cfc (percent)" ::= { vrcCompCfgEntry 8 } vrcCompCfgStopCfc OBJECT-TYPE SYNTAX Integer32(-200..-50) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor stop cfc (percent)" ::= { vrcCompCfgEntry 9 } vrcCompCfgMinRunTime OBJECT-TYPE SYNTAX Integer32(0..30) UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor min run time in minutes" ::= { vrcCompCfgEntry 10 } vrcCompCfgMinStopTime OBJECT-TYPE SYNTAX Integer32(0..10) UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor min stop time in minutes" ::= { vrcCompCfgEntry 11 } vrcCompCfgJumpBand1 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump band 1 in tenths of a percent" ::= { vrcCompCfgEntry 12 } vrcCompCfgJumpBand2 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump band 2 in tenths of a percent" ::= { vrcCompCfgEntry 13 } vrcCompCfgJumpBand3 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump band 3 in tenths of a percent" ::= { vrcCompCfgEntry 14 } vrcCompCfgJumpBand4 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump band 4 in tenths of a percent" ::= { vrcCompCfgEntry 15 } vrcCompCfgJumpBand5 OBJECT-TYPE SYNTAX Integer32(0..100) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump band 5 in tenths of a percent" ::= { vrcCompCfgEntry 16 } vrcCompCfgJumpFreq1 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump frequency 1 in tenths of a percent" ::= { vrcCompCfgEntry 17 } vrcCompCfgJumpFreq2 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump frequency 2 in tenths of a percent" ::= { vrcCompCfgEntry 18 } vrcCompCfgJumpFreq3 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump frequency 3 in tenths of a percent" ::= { vrcCompCfgEntry 19 } vrcCompCfgJumpFreq4 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump frequency 4 in tenths of a percent" ::= { vrcCompCfgEntry 20 } vrcCompCfgJumpFreq5 OBJECT-TYPE SYNTAX Integer32(0..1000) UNITS "0.1%" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor jump frequency 5 in tenths of a percent" ::= { vrcCompCfgEntry 21 } vrcCompCfgTempP OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269" ::= { vrcCompCfgEntry 22 } vrcCompCfgTempI OBJECT-TYPE SYNTAX Integer32(0..900) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor temperature I in seconds" ::= { vrcCompCfgEntry 23 } vrcCompCfgTempD OBJECT-TYPE SYNTAX Integer32(0..900) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor temperature D in seconds" ::= { vrcCompCfgEntry 24 } vrcCompCfgDriverFaultAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor driver fault alarm control: 2 = suspend 3 = open" ::= { vrcCompCfgEntry 25 } vrcCompCfgDriverCommFailAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor driver communication failure alarm control: 2 = suspend 3 = open" ::= { vrcCompCfgEntry 26 } vrcCompCfgFaultLockAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Compressor fault lock alarm control: 2 = suspend 3 = open" ::= { vrcCompCfgEntry 27 } --###########################################################################################-- --vrcReturnPtTable-- --###########################################################################################-- vrcReturnPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcReturnPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC return status" ::= { vrc 10 } vrcReturnPtEntry OBJECT-TYPE SYNTAX VrcReturnPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcReturnPtTable: each entry represents return data for a VRC" INDEX { vrcReturnPtIndex } ::= { vrcReturnPtTable 1 } VrcReturnPtEntry ::= SEQUENCE { vrcReturnPtIndex Integer32, vrcReturnPtName SnmpAdminString, vrcReturnPtTemp Integer32, vrcReturnPtHighTempAlarm TruthValue, vrcReturnPtTempSensorFailAlarm TruthValue } vrcReturnPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcReturnPtEntry 1 } vrcReturnPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Return name (factory-assigned)" ::= { vrcReturnPtEntry 2 } vrcReturnPtTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Return temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120" ::= { vrcReturnPtEntry 3 } vrcReturnPtHighTempAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Return high temperature alarm state" ::= { vrcReturnPtEntry 4 } vrcReturnPtTempSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Return temperature sensor failure alarm state" ::= { vrcReturnPtEntry 5 } --###########################################################################################-- --vrcReturnCfgTable-- --###########################################################################################-- vrcReturnCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcReturnCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC return configuration" ::= { vrc 11 } vrcReturnCfgEntry OBJECT-TYPE SYNTAX VrcReturnCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcReturnCfgTable: each entry contains config fields for VRC return" INDEX { vrcReturnCfgIndex } ::= { vrcReturnCfgTable 1 } VrcReturnCfgEntry ::= SEQUENCE { vrcReturnCfgIndex Integer32, vrcReturnCfgOilCycle Integer32, vrcReturnCfgOilRunCapacity Integer32, vrcReturnCfgOilRunTime Integer32, vrcReturnCfgTempCalValue Integer32, vrcReturnCfgTempSetting Integer32, vrcReturnCfgHighTempAlarmValue Integer32, vrcReturnCfgHighTempAlarmCtrl INTEGER, vrcReturnCfgTempSensFailAlmCtrl INTEGER } vrcReturnCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcReturnCfgEntry 1 } vrcReturnCfgOilCycle OBJECT-TYPE SYNTAX Integer32(5..50) UNITS "decihours" MAX-ACCESS read-write STATUS current DESCRIPTION "Return oil cycle in tenths of an hour" ::= { vrcReturnCfgEntry 2 } vrcReturnCfgOilRunCapacity OBJECT-TYPE SYNTAX Integer32(50..100) UNITS "%" MAX-ACCESS read-write STATUS current DESCRIPTION "Return Oil run capacity (percent)" ::= { vrcReturnCfgEntry 3 } vrcReturnCfgOilRunTime OBJECT-TYPE SYNTAX Integer32(0..10) UNITS "minutes" MAX-ACCESS read-write STATUS current DESCRIPTION "Return oil run time in minutes" ::= { vrcReturnCfgEntry 4 } vrcReturnCfgTempCalValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Return temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179" ::= { vrcReturnCfgEntry 5 } vrcReturnCfgTempSetting OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Return temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949" ::= { vrcReturnCfgEntry 6 } vrcReturnCfgHighTempAlarmValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Return high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129" ::= { vrcReturnCfgEntry 7 } vrcReturnCfgHighTempAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Return high temperature alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcReturnCfgEntry 8 } vrcReturnCfgTempSensFailAlmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Return temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcReturnCfgEntry 9 } --###########################################################################################-- --vrcSupplyPtTable-- --###########################################################################################-- vrcSupplyPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcSupplyPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC supply status" ::= { vrc 12 } vrcSupplyPtEntry OBJECT-TYPE SYNTAX VrcSupplyPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcSupplyPtTable: each entry represents supply data for a VRC" INDEX { vrcSupplyPtIndex } ::= { vrcSupplyPtTable 1 } VrcSupplyPtEntry ::= SEQUENCE { vrcSupplyPtIndex Integer32, vrcSupplyPtName SnmpAdminString, vrcSupplyPtTemp Integer32, vrcSupplyPtLowTempAlarm TruthValue, vrcSupplyPtHighTempAlarm TruthValue, vrcSupplyPtTempSensorFailAlarm TruthValue } vrcSupplyPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcSupplyPtEntry 1 } vrcSupplyPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Supply name (factory-assigned)" ::= { vrcSupplyPtEntry 2 } vrcSupplyPtTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Supply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120" ::= { vrcSupplyPtEntry 3 } vrcSupplyPtLowTempAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Supply low temperature alarm state" ::= { vrcSupplyPtEntry 4 } vrcSupplyPtHighTempAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Supply high temperature alarm state" ::= { vrcSupplyPtEntry 5 } vrcSupplyPtTempSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Supply temperature sensor failure alarm state" ::= { vrcSupplyPtEntry 6 } --###########################################################################################-- --vrcSupplyCfgTable-- --###########################################################################################-- vrcSupplyCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcSupplyCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC supply configuration" ::= { vrc 13 } vrcSupplyCfgEntry OBJECT-TYPE SYNTAX VrcSupplyCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply" INDEX { vrcSupplyCfgIndex } ::= { vrcSupplyCfgTable 1 } VrcSupplyCfgEntry ::= SEQUENCE { vrcSupplyCfgIndex Integer32, vrcSupplyCfgTempCalValue Integer32, vrcSupplyCfgTempSetting Integer32, vrcSupplyCfgLowTempAlarmValue Integer32, vrcSupplyCfgHighTempAlarmValue Integer32, vrcSupplyCfgLowTempAlmCtrl INTEGER, vrcSupplyCfgHighTempAlmCtrl INTEGER, vrcSupplyCfgTempSensFailAlmCtrl INTEGER } vrcSupplyCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcSupplyCfgEntry 1 } vrcSupplyCfgTempCalValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Supply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179" ::= { vrcSupplyCfgEntry 2 } vrcSupplyCfgTempSetting OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Supply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823" ::= { vrcSupplyCfgEntry 3 } vrcSupplyCfgLowTempAlarmValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Supply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679" ::= { vrcSupplyCfgEntry 4 } vrcSupplyCfgHighTempAlarmValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Supply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949" ::= { vrcSupplyCfgEntry 5 } vrcSupplyCfgLowTempAlmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Supply low temperature alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcSupplyCfgEntry 6 } vrcSupplyCfgHighTempAlmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Supply high temperature alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcSupplyCfgEntry 7 } vrcSupplyCfgTempSensFailAlmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Supply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcSupplyCfgEntry 8 } --###########################################################################################-- --vrcPowerPtTable-- --###########################################################################################-- vrcPowerPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcPowerPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC power status" ::= { vrc 14 } vrcPowerPtEntry OBJECT-TYPE SYNTAX VrcPowerPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcPowerPtTable: each entry represents power data for a VRC" INDEX { vrcPowerPtIndex } ::= { vrcPowerPtTable 1 } VrcPowerPtEntry ::= SEQUENCE { vrcPowerPtIndex Integer32, vrcPowerPtName SnmpAdminString, vrcPowerPtVoltage Integer32, vrcPowerPtFrequency Integer32, vrcPowerPtLowVoltageAlarm TruthValue, vrcPowerPtHighVoltageAlarm TruthValue, vrcPowerPtLossOfPhasePowerAlarm TruthValue, vrcPowerPtLossOfPowerAlarm TruthValue, vrcPowerPtFrequencyErrorAlarm TruthValue } vrcPowerPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcPowerPtEntry 1 } vrcPowerPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Power name (factory-assigned)" ::= { vrcPowerPtEntry 2 } vrcPowerPtVoltage OBJECT-TYPE SYNTAX Integer32(-32768..32767) UNITS "decivolts" MAX-ACCESS read-only STATUS current DESCRIPTION "Power voltage measurement in tenths of a volt" ::= { vrcPowerPtEntry 3 } vrcPowerPtFrequency OBJECT-TYPE SYNTAX Integer32(-32768..32767) UNITS "decihertz" MAX-ACCESS read-only STATUS current DESCRIPTION "Power frequency measurement in tenths of hertz" ::= { vrcPowerPtEntry 4 } vrcPowerPtLowVoltageAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Power low voltage alarm state" ::= { vrcPowerPtEntry 5 } vrcPowerPtHighVoltageAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Power high voltage alarm state" ::= { vrcPowerPtEntry 6 } vrcPowerPtLossOfPhasePowerAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Phase power loss alarm state" ::= { vrcPowerPtEntry 7 } vrcPowerPtLossOfPowerAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Power loss alarm state" ::= { vrcPowerPtEntry 8 } vrcPowerPtFrequencyErrorAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Power frequency error alarm state" ::= { vrcPowerPtEntry 9 } --###########################################################################################-- --vrcPowerCfgTable-- --###########################################################################################-- vrcPowerCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcPowerCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC power configuration" ::= { vrc 15 } vrcPowerCfgEntry OBJECT-TYPE SYNTAX VrcPowerCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcPowerCfgTable: each entry contains config fields for VRC power" INDEX { vrcPowerCfgIndex } ::= { vrcPowerCfgTable 1 } VrcPowerCfgEntry ::= SEQUENCE { vrcPowerCfgIndex Integer32, vrcPowerCfgLowVoltageSetting Integer32, vrcPowerCfgHighVoltageSetting Integer32, vrcPowerCfgLowVoltageAlarmCtrl INTEGER, vrcPowerCfgHighVoltageAlarmCtrl INTEGER, vrcPowerCfgLossOfPowerAlarmCtrl INTEGER, vrcPowerCfgFreqErrorAlarmCtrl INTEGER } vrcPowerCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcPowerCfgEntry 1 } vrcPowerCfgLowVoltageSetting OBJECT-TYPE SYNTAX Integer32(100..230) UNITS "volts" MAX-ACCESS read-write STATUS current DESCRIPTION "Power low voltage setting in volts" ::= { vrcPowerCfgEntry 2 } vrcPowerCfgHighVoltageSetting OBJECT-TYPE SYNTAX Integer32(100..300) UNITS "volts" MAX-ACCESS read-write STATUS current DESCRIPTION "Power high voltage setting in volts" ::= { vrcPowerCfgEntry 3 } vrcPowerCfgLowVoltageAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Power low voltage alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcPowerCfgEntry 4 } vrcPowerCfgHighVoltageAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Power high voltage alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcPowerCfgEntry 5 } vrcPowerCfgLossOfPowerAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Power loss alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcPowerCfgEntry 6 } vrcPowerCfgFreqErrorAlarmCtrl OBJECT-TYPE SYNTAX INTEGER { close(1), suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Power frequency error alarm control: 1 = close 2 = suspend 3 = open" ::= { vrcPowerCfgEntry 7 } --###########################################################################################-- --vrcOutdoorPtTable-- --###########################################################################################-- vrcOutdoorPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcOutdoorPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC outdoor status" ::= { vrc 16 } vrcOutdoorPtEntry OBJECT-TYPE SYNTAX VrcOutdoorPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor" INDEX { vrcOutdoorPtIndex } ::= { vrcOutdoorPtTable 1 } VrcOutdoorPtEntry ::= SEQUENCE { vrcOutdoorPtIndex Integer32, vrcOutdoorPtName SnmpAdminString, vrcOutdoorPtTemp Integer32 } vrcOutdoorPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcOutdoorPtEntry 1 } vrcOutdoorPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Outdoor name (factory-assigned)" ::= { vrcOutdoorPtEntry 2 } vrcOutdoorPtTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Outdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120" ::= { vrcOutdoorPtEntry 3 } --###########################################################################################-- --vrcDischPtTable-- --###########################################################################################-- vrcDischPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcDischPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC discharge status" ::= { vrc 18 } vrcDischPtEntry OBJECT-TYPE SYNTAX VrcDischPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcDischPtTable: each entry represents discharge data for a VRC" INDEX { vrcDischPtIndex } ::= { vrcDischPtTable 1 } VrcDischPtEntry ::= SEQUENCE { vrcDischPtIndex Integer32, vrcDischPtName SnmpAdminString, vrcDischPtTemp Integer32, vrcDischPtPressure Integer32, vrcDischPtHighTempAlarm TruthValue, vrcDischPtHighTempFreqAlarm TruthValue, vrcDischPtTempSensorFailAlarm TruthValue } vrcDischPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcDischPtEntry 1 } vrcDischPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Discharge name (factory-assigned)" ::= { vrcDischPtEntry 2 } vrcDischPtTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128" ::= { vrcDischPtEntry 3 } vrcDischPtPressure OBJECT-TYPE SYNTAX Integer32(0..460) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge air pressure value in tenths of a bar" ::= { vrcDischPtEntry 4 } vrcDischPtHighTempAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Discharge high temperature alarm state" ::= { vrcDischPtEntry 5 } vrcDischPtHighTempFreqAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Discharge high temperature frequently alarm state" ::= { vrcDischPtEntry 6 } vrcDischPtTempSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Discharge temperature sensor failure alarm state" ::= { vrcDischPtEntry 7 } --###########################################################################################-- --vrcDischCfgTable-- --###########################################################################################-- vrcDischCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcDischCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC discharge configuration" ::= { vrc 19 } vrcDischCfgEntry OBJECT-TYPE SYNTAX VrcDischCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcDischCfgTable: each entry contains config fields for VRC discharge" INDEX { vrcDischCfgIndex } ::= { vrcDischCfgTable 1 } VrcDischCfgEntry ::= SEQUENCE { vrcDischCfgIndex Integer32, vrcDischCfgTempCalValue Integer32, vrcDischCfgPressCalValue Integer32, vrcDischCfgHighTempAlmCtrl INTEGER, vrcDischCfgHighTempFreqAlmCtrl INTEGER, vrcDischCfgTempSensFailAlmCtrl INTEGER } vrcDischCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcDischCfgEntry 1 } vrcDischCfgTempCalValue OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179" ::= { vrcDischCfgEntry 2 } vrcDischCfgPressCalValue OBJECT-TYPE SYNTAX Integer32(-100..100) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge pressure calibration value in tenths of a bar" ::= { vrcDischCfgEntry 3 } vrcDischCfgHighTempAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge high temperature alarm control: 2 = suspend 3 = open" ::= { vrcDischCfgEntry 4 } vrcDischCfgHighTempFreqAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge high temperature frequenctly alarm control: 2 = suspend 3 = open" ::= { vrcDischCfgEntry 5 } vrcDischCfgTempSensFailAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Discharge temperature sensor failure alarm control: 2 = suspend 3 = open" ::= { vrcDischCfgEntry 6 } --###########################################################################################-- --vrcSuctPtTable-- --###########################################################################################-- vrcSuctPtTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcSuctPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table that contains VRC suction status" ::= { vrc 20 } vrcSuctPtEntry OBJECT-TYPE SYNTAX VrcSuctPtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcSuctPtTable: each entry represents suction data for a VRC" INDEX { vrcSuctPtIndex } ::= { vrcSuctPtTable 1 } VrcSuctPtEntry ::= SEQUENCE { vrcSuctPtIndex Integer32, vrcSuctPtName SnmpAdminString, vrcSuctPtTemp Integer32, vrcSuctPtPressure Integer32, vrcSuctPtSuperHeatTemp Integer32, vrcSuctPtTempSensorFailAlarm TruthValue } vrcSuctPtIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcSuctPtEntry 1 } vrcSuctPtName OBJECT-TYPE SYNTAX SnmpAdminString(SIZE (1..25)) MAX-ACCESS read-only STATUS current DESCRIPTION "Suction name (factory-assigned)" ::= { vrcSuctPtEntry 2 } vrcSuctPtTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Suction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120" ::= { vrcSuctPtEntry 3 } vrcSuctPtPressure OBJECT-TYPE SYNTAX Integer32(0..173) UNITS "decibars" MAX-ACCESS read-only STATUS current DESCRIPTION "Suction air pressure in tenths of a bar" ::= { vrcSuctPtEntry 4 } vrcSuctPtSuperHeatTemp OBJECT-TYPE SYNTAX Integer32 UNITS "decidegrees" MAX-ACCESS read-only STATUS current DESCRIPTION "Suction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120" ::= { vrcSuctPtEntry 5 } vrcSuctPtTempSensorFailAlarm OBJECT-TYPE SYNTAX TruthValue MAX-ACCESS read-only STATUS current DESCRIPTION "Suction temperature sensor failure alarm state" ::= { vrcSuctPtEntry 6 } --###########################################################################################-- --vrcSuctCfgTable-- --###########################################################################################-- vrcSuctCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF VrcSuctCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table used for VRC suction configuration" ::= { vrc 21 } vrcSuctCfgEntry OBJECT-TYPE SYNTAX VrcSuctCfgEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry in the vrcSuctCfgTable: each entry contains config fields for VRC suction" INDEX { vrcSuctCfgIndex } ::= { vrcSuctCfgTable 1 } VrcSuctCfgEntry ::= SEQUENCE { vrcSuctCfgIndex Integer32, vrcSuctCfgPressCalValue Integer32, vrcSuctCfgTempSensFailAlmCtrl INTEGER } vrcSuctCfgIndex OBJECT-TYPE SYNTAX Integer32(1..100) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unique id for each entry in the table" ::= { vrcSuctCfgEntry 1 } vrcSuctCfgPressCalValue OBJECT-TYPE SYNTAX Integer32(-100..100) UNITS "decibars" MAX-ACCESS read-write STATUS current DESCRIPTION "Suction pressure calibration value in tenths of a bar" ::= { vrcSuctCfgEntry 2 } vrcSuctCfgTempSensFailAlmCtrl OBJECT-TYPE SYNTAX INTEGER { suspend(2), open(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Suction temperature sensor failure alarm control: 2 = suspend 3 = open" ::= { vrcSuctCfgEntry 3 } --###########################################################################################-- --Notifications-- --###########################################################################################-- trap OBJECT IDENTIFIER ::= { imd 32767 } trapPrefix OBJECT IDENTIFIER ::= { trap 0 } trapObj OBJECT IDENTIFIER ::= { trap 1 } trapSeverity OBJECT-TYPE SYNTAX INTEGER { none(0), warning(1), alarm(2) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Indicates the severity of the trap: 0 = None 1 = Warning 2 = Alarm" ::= { trapObj 1 } trapThreshType OBJECT-TYPE SYNTAX INTEGER { low(1), high(2) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "Only sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = High" ::= { trapObj 2 } internalTestNOTIFY NOTIFICATION-TYPE STATUS current DESCRIPTION "Test SNMP Trap" ::= { trapPrefix 10101 } --#####deviceInfo#####-- --#####pdu#####-- --#####pduMainTable#####-- pduMainAvailNOTIFY NOTIFICATION-TYPE OBJECTS { pduMainAvail, trapSeverity, sysName, pduMainLabel } STATUS current DESCRIPTION "PDU availability trap" ::= { trapPrefix 10305 } pduMainAvailCLEAR NOTIFICATION-TYPE OBJECTS { pduMainAvail, trapSeverity, sysName, pduMainLabel } STATUS current DESCRIPTION "PDU availability clear trap" ::= { trapPrefix 20305 } pduTotalRealPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduTotalRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total real power trap" ::= { trapPrefix 10309 } pduTotalRealPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduTotalRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total real power clear trap" ::= { trapPrefix 20309 } pduTotalApparentPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduTotalApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total apparent power trap" ::= { trapPrefix 10310 } pduTotalApparentPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduTotalApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total apparent power clear trap" ::= { trapPrefix 20310 } pduTotalPowerFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduTotalPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total power factor trap" ::= { trapPrefix 10311 } pduTotalPowerFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduTotalPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total power factor clear trap" ::= { trapPrefix 20311 } pduTotalEnergyNOTIFY NOTIFICATION-TYPE OBJECTS { pduTotalEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total energy trap" ::= { trapPrefix 10312 } pduTotalEnergyCLEAR NOTIFICATION-TYPE OBJECTS { pduTotalEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduTotalLabel } STATUS current DESCRIPTION "PDU total energy clear trap" ::= { trapPrefix 20312 } --#####pduPhaseTable#####-- pduPhaseVoltageNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase voltage trap" ::= { trapPrefix 10324 } pduPhaseVoltageCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase voltage clear trap" ::= { trapPrefix 20324 } pduPhaseCurrentNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase current trap" ::= { trapPrefix 10328 } pduPhaseCurrentCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase current clear trap" ::= { trapPrefix 20328 } pduPhaseRealPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase real power trap" ::= { trapPrefix 10332 } pduPhaseRealPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase real power clear trap" ::= { trapPrefix 20332 } pduPhaseApparentPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase apparent power trap" ::= { trapPrefix 10333 } pduPhaseApparentPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase apparent power clear trap" ::= { trapPrefix 20333 } pduPhasePowerFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhasePowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase power factor trap" ::= { trapPrefix 10334 } pduPhasePowerFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduPhasePowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase power factor clear trap" ::= { trapPrefix 20334 } pduPhaseEnergyNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase energy trap" ::= { trapPrefix 10335 } pduPhaseEnergyCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase energy clear trap" ::= { trapPrefix 20335 } pduPhaseBalanceNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseBalance, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase balance trap" ::= { trapPrefix 10337 } pduPhaseBalanceCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseBalance, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase balance clear trap" ::= { trapPrefix 20337 } pduPhaseCurrentCrestFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduPhaseCurrentCrestFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase current crest factor trap" ::= { trapPrefix 10339 } pduPhaseCurrentCrestFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduPhaseCurrentCrestFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduPhaseLabel } STATUS current DESCRIPTION "PDU phase current crest factor clear trap" ::= { trapPrefix 20339 } --#####pduBreakerTable#####-- pduBreakerCurrentNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker current trap" ::= { trapPrefix 10354 } pduBreakerCurrentCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker current clear trap" ::= { trapPrefix 20354 } pduBreakerVoltageNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker voltage trap" ::= { trapPrefix 10358 } pduBreakerVoltageCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker voltage clear trap" ::= { trapPrefix 20358 } pduBreakerRealPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker real power trap" ::= { trapPrefix 10362 } pduBreakerRealPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker real power clear trap" ::= { trapPrefix 20362 } pduBreakerApparentPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker apparent power trap" ::= { trapPrefix 10363 } pduBreakerApparentPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker apparent power clear trap" ::= { trapPrefix 20363 } pduBreakerPowerFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker power factor trap" ::= { trapPrefix 10364 } pduBreakerPowerFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker power factor clear trap" ::= { trapPrefix 20364 } pduBreakerEnergyNOTIFY NOTIFICATION-TYPE OBJECTS { pduBreakerEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker energy trap" ::= { trapPrefix 10365 } pduBreakerEnergyCLEAR NOTIFICATION-TYPE OBJECTS { pduBreakerEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduBreakerLabel } STATUS current DESCRIPTION "PDU breaker energy clear trap" ::= { trapPrefix 20365 } --#####pduLineTable#####-- pduLineCurrentNOTIFY NOTIFICATION-TYPE OBJECTS { pduLineCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduLineLabel } STATUS current DESCRIPTION "PDU line current trap" ::= { trapPrefix 10374 } pduLineCurrentCLEAR NOTIFICATION-TYPE OBJECTS { pduLineCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduLineLabel } STATUS current DESCRIPTION "PDU line current clear trap" ::= { trapPrefix 20374 } --#####pduOutletSwitchTable#####-- --#####pduOutletMeterTable#####-- pduOutletMeterVoltageNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet voltage trap" ::= { trapPrefix 10385 } pduOutletMeterVoltageCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterVoltage, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet voltage clear trap" ::= { trapPrefix 20385 } pduOutletMeterCurrentNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet current trap" ::= { trapPrefix 10389 } pduOutletMeterCurrentCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterCurrent, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet current clear trap" ::= { trapPrefix 20389 } pduOutletMeterRealPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet real power trap" ::= { trapPrefix 10393 } pduOutletMeterRealPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterRealPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet real power clear trap" ::= { trapPrefix 20393 } pduOutletMeterApparentPowerNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet apparent power trap" ::= { trapPrefix 10394 } pduOutletMeterApparentPowerCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterApparentPower, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet apparent power clear trap" ::= { trapPrefix 20394 } pduOutletMeterPowerFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet power factor trap" ::= { trapPrefix 10395 } pduOutletMeterPowerFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterPowerFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet power factor clear trap" ::= { trapPrefix 20395 } pduOutletMeterEnergyNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletMeterEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet energy trap" ::= { trapPrefix 10396 } pduOutletMeterEnergyCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletMeterEnergy, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet energy clear trap" ::= { trapPrefix 20396 } pduOutletCurrentCrestFactorNOTIFY NOTIFICATION-TYPE OBJECTS { pduOutletCurrentCrestFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet current crest factor trap" ::= { trapPrefix 10400 } pduOutletCurrentCrestFactorCLEAR NOTIFICATION-TYPE OBJECTS { pduOutletCurrentCrestFactor, trapThreshType, trapSeverity, sysName, pduMainLabel, pduOutletMeterLabel } STATUS current DESCRIPTION "PDU outlet current crest factor clear trap" ::= { trapPrefix 20400 } --#####tempSensorTable#####-- tempSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { tempSensorAvail, trapSeverity, sysName, tempSensorLabel } STATUS current DESCRIPTION "RT availability trap" ::= { trapPrefix 10404 } tempSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { tempSensorAvail, trapSeverity, sysName, tempSensorLabel } STATUS current DESCRIPTION "RT availability clear trap" ::= { trapPrefix 20404 } tempSensorTempNOTIFY NOTIFICATION-TYPE OBJECTS { tempSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, tempSensorLabel } STATUS current DESCRIPTION "RT temperature trap" ::= { trapPrefix 10405 } tempSensorTempCLEAR NOTIFICATION-TYPE OBJECTS { tempSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, tempSensorLabel } STATUS current DESCRIPTION "RT temperature clear trap" ::= { trapPrefix 20405 } --#####airFlowSensorTable#####-- airFlowSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { airFlowSensorAvail, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 availability trap" ::= { trapPrefix 10504 } airFlowSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { airFlowSensorAvail, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 availability clear trap" ::= { trapPrefix 20504 } airFlowSensorTempNOTIFY NOTIFICATION-TYPE OBJECTS { airFlowSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 temperature trap" ::= { trapPrefix 10505 } airFlowSensorTempCLEAR NOTIFICATION-TYPE OBJECTS { airFlowSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 temperature clear trap" ::= { trapPrefix 20505 } airFlowSensorFlowNOTIFY NOTIFICATION-TYPE OBJECTS { airFlowSensorFlow, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 airflow trap" ::= { trapPrefix 10506 } airFlowSensorFlowCLEAR NOTIFICATION-TYPE OBJECTS { airFlowSensorFlow, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 airflow clear trap" ::= { trapPrefix 20506 } airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE OBJECTS { airFlowSensorHumidity, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 humidity trap" ::= { trapPrefix 10507 } airFlowSensorHumidityCLEAR NOTIFICATION-TYPE OBJECTS { airFlowSensorHumidity, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 humidity clear trap" ::= { trapPrefix 20507 } airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE OBJECTS { airFlowSensorDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 dewpoint trap" ::= { trapPrefix 10508 } airFlowSensorDewPointCLEAR NOTIFICATION-TYPE OBJECTS { airFlowSensorDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, airFlowSensorLabel } STATUS current DESCRIPTION "AFHT3 dewpoint clear trap" ::= { trapPrefix 20508 } --#####t3hdSensorTable#####-- t3hdSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorAvail, trapSeverity, sysName, t3hdSensorLabel } STATUS current DESCRIPTION "T3HD availability trap" ::= { trapPrefix 10804 } t3hdSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorAvail, trapSeverity, sysName, t3hdSensorLabel } STATUS current DESCRIPTION "T3HD availability clear trap" ::= { trapPrefix 20804 } t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorIntTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal temperature trap" ::= { trapPrefix 10806 } t3hdSensorIntTempCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorIntTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal temperature clear trap" ::= { trapPrefix 20806 } t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorIntHumidity, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal humidity trap" ::= { trapPrefix 10807 } t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorIntHumidity, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal humidity clear trap" ::= { trapPrefix 20807 } t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorIntDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal dewpoint trap" ::= { trapPrefix 10808 } t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorIntDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorIntLabel } STATUS current DESCRIPTION "T3HD Internal dewpoint clear trap" ::= { trapPrefix 20808 } t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorExtATemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorExtALabel } STATUS current DESCRIPTION "T3HD External A temperature trap" ::= { trapPrefix 10811 } t3hdSensorExtATempCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorExtATemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorExtALabel } STATUS current DESCRIPTION "T3HD External A temperature clear trap" ::= { trapPrefix 20811 } t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE OBJECTS { t3hdSensorExtBTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorExtBLabel } STATUS current DESCRIPTION "T3HD External B temperature trap" ::= { trapPrefix 10814 } t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE OBJECTS { t3hdSensorExtBTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, t3hdSensorLabel, t3hdSensorExtBLabel } STATUS current DESCRIPTION "T3HD External B temperature clear trap" ::= { trapPrefix 20814 } --#####thdSensorTable#####-- thdSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { thdSensorAvail, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD availability trap" ::= { trapPrefix 10904 } thdSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { thdSensorAvail, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD availability clear trap" ::= { trapPrefix 20904 } thdSensorTempNOTIFY NOTIFICATION-TYPE OBJECTS { thdSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD temperature trap" ::= { trapPrefix 10905 } thdSensorTempCLEAR NOTIFICATION-TYPE OBJECTS { thdSensorTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD temperature clear trap" ::= { trapPrefix 20905 } thdSensorHumidityNOTIFY NOTIFICATION-TYPE OBJECTS { thdSensorHumidity, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD humidity trap" ::= { trapPrefix 10906 } thdSensorHumidityCLEAR NOTIFICATION-TYPE OBJECTS { thdSensorHumidity, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD humidity clear trap" ::= { trapPrefix 20906 } thdSensorDewPointNOTIFY NOTIFICATION-TYPE OBJECTS { thdSensorDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD dewpoint trap" ::= { trapPrefix 10907 } thdSensorDewPointCLEAR NOTIFICATION-TYPE OBJECTS { thdSensorDewPoint, temperatureUnits, trapThreshType, trapSeverity, sysName, thdSensorLabel } STATUS current DESCRIPTION "THD dewpoint clear trap" ::= { trapPrefix 20907 } --#####a2dSensorTable#####-- a2dSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { a2dSensorAvail, trapSeverity, sysName, a2dSensorLabel } STATUS current DESCRIPTION "A2D availability trap" ::= { trapPrefix 11104 } a2dSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { a2dSensorAvail, trapSeverity, sysName, a2dSensorLabel } STATUS current DESCRIPTION "A2D availability clear trap" ::= { trapPrefix 21104 } a2dSensorValueNOTIFY NOTIFICATION-TYPE OBJECTS { a2dSensorValue, trapThreshType, trapSeverity, sysName, a2dSensorLabel, a2dSensorAnalogLabel, a2dSensorDisplayValue } STATUS current DESCRIPTION "A2D measurement trap" ::= { trapPrefix 11105 } a2dSensorValueCLEAR NOTIFICATION-TYPE OBJECTS { a2dSensorValue, trapThreshType, trapSeverity, sysName, a2dSensorLabel, a2dSensorAnalogLabel, a2dSensorDisplayValue } STATUS current DESCRIPTION "A2D measurement clear trap" ::= { trapPrefix 21105 } --#####humiditySensorTable#####-- humiditySensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { humiditySensorAvail, trapSeverity, sysName, humiditySensorLabel } STATUS current DESCRIPTION "Remote humidity availability trap" ::= { trapPrefix 11204 } humiditySensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { humiditySensorAvail, trapSeverity, sysName, humiditySensorLabel } STATUS current DESCRIPTION "Remote humidity availability clear trap" ::= { trapPrefix 21204 } humiditySensorValueNOTIFY NOTIFICATION-TYPE OBJECTS { humiditySensorValue, trapThreshType, trapSeverity, sysName, humiditySensorLabel } STATUS current DESCRIPTION "Remote humidity value trap" ::= { trapPrefix 11205 } humiditySensorValueCLEAR NOTIFICATION-TYPE OBJECTS { humiditySensorValue, trapThreshType, trapSeverity, sysName, humiditySensorLabel } STATUS current DESCRIPTION "Remote humidity value clear trap" ::= { trapPrefix 21205 } --#####sn2dSensorTable#####-- sn2dSensorAvailNOTIFY NOTIFICATION-TYPE OBJECTS { sn2dSensorAvail, trapSeverity, sysName, sn2dSensorLabel } STATUS current DESCRIPTION "SN-2D availability trap" ::= { trapPrefix 11304 } sn2dSensorAvailCLEAR NOTIFICATION-TYPE OBJECTS { sn2dSensorAvail, trapSeverity, sysName, sn2dSensorLabel } STATUS current DESCRIPTION "SN-2D availability clear trap" ::= { trapPrefix 21304 } sn2dSensorDoor1StateNOTIFY NOTIFICATION-TYPE OBJECTS { sn2dSensorDoor1State, trapThreshType, trapSeverity, sysName, sn2dSensorLabel, sn2dSensorDoor1Label, sn2dSensorDoor1DisplayState } STATUS current DESCRIPTION "SN-2D Door switch 1 state trap" ::= { trapPrefix 11306 } sn2dSensorDoor1StateCLEAR NOTIFICATION-TYPE OBJECTS { sn2dSensorDoor1State, trapThreshType, trapSeverity, sysName, sn2dSensorLabel, sn2dSensorDoor1Label, sn2dSensorDoor1DisplayState } STATUS current DESCRIPTION "SN-2D Door switch 1 state clear trap" ::= { trapPrefix 21306 } sn2dSensorDoor2StateNOTIFY NOTIFICATION-TYPE OBJECTS { sn2dSensorDoor2State, trapThreshType, trapSeverity, sysName, sn2dSensorLabel, sn2dSensorDoor2Label, sn2dSensorDoor2DisplayState } STATUS current DESCRIPTION "SN-2D Door switch 2 state trap" ::= { trapPrefix 11309 } sn2dSensorDoor2StateCLEAR NOTIFICATION-TYPE OBJECTS { sn2dSensorDoor2State, trapThreshType, trapSeverity, sysName, sn2dSensorLabel, sn2dSensorDoor2Label, sn2dSensorDoor2DisplayState } STATUS current DESCRIPTION "SN-2D Door switch 2 state clear trap" ::= { trapPrefix 21309 } --#####cooling#####-- --#####vrc#####-- --#####vrcMainTable#####-- vrcMainAvailNOTIFY NOTIFICATION-TYPE OBJECTS { vrcMainAvail, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC availability trap" ::= { trapPrefix 13001 } vrcMainAvailCLEAR NOTIFICATION-TYPE OBJECTS { vrcMainAvail, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC availability clear trap" ::= { trapPrefix 23001 } --#####vrcMainPtTable#####-- --#####vrcMainCfgTable#####-- --#####vrcOutFanPtTable#####-- vrcOutFanPtSpeedNOTIFY NOTIFICATION-TYPE OBJECTS { vrcOutFanPtSpeed, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC out-fan speed trap" ::= { trapPrefix 13002 } vrcOutFanPtSpeedCLEAR NOTIFICATION-TYPE OBJECTS { vrcOutFanPtSpeed, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC out-fan speed clear trap" ::= { trapPrefix 23002 } --#####vrcOutFanCfgTable#####-- --#####vrcInFanPtTable#####-- --#####vrcInFanCfgTable#####-- --#####vrcCompPtTable#####-- vrcCompPtCapacityNOTIFY NOTIFICATION-TYPE OBJECTS { vrcCompPtCapacity, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC compressor capacity trap" ::= { trapPrefix 13003 } vrcCompPtCapacityCLEAR NOTIFICATION-TYPE OBJECTS { vrcCompPtCapacity, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC compressor capacity clear trap" ::= { trapPrefix 23003 } --#####vrcCompCfgTable#####-- --#####vrcReturnPtTable#####-- vrcReturnPtTempNOTIFY NOTIFICATION-TYPE OBJECTS { vrcReturnPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC return temperature trap" ::= { trapPrefix 13004 } vrcReturnPtTempCLEAR NOTIFICATION-TYPE OBJECTS { vrcReturnPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC return temperature clear trap" ::= { trapPrefix 23004 } --#####vrcReturnCfgTable#####-- --#####vrcSupplyPtTable#####-- vrcSupplyPtTempNOTIFY NOTIFICATION-TYPE OBJECTS { vrcSupplyPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC supply temperature trap" ::= { trapPrefix 13005 } vrcSupplyPtTempCLEAR NOTIFICATION-TYPE OBJECTS { vrcSupplyPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC supply temperature clear trap" ::= { trapPrefix 23005 } --#####vrcSupplyCfgTable#####-- --#####vrcPowerPtTable#####-- vrcPowerPtVoltageNOTIFY NOTIFICATION-TYPE OBJECTS { vrcPowerPtVoltage, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC power voltage trap" ::= { trapPrefix 13006 } vrcPowerPtVoltageCLEAR NOTIFICATION-TYPE OBJECTS { vrcPowerPtVoltage, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC power voltage clear trap" ::= { trapPrefix 23006 } vrcPowerPtFrequencyNOTIFY NOTIFICATION-TYPE OBJECTS { vrcPowerPtFrequency, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC power frequency trap" ::= { trapPrefix 13007 } vrcPowerPtFrequencyCLEAR NOTIFICATION-TYPE OBJECTS { vrcPowerPtFrequency, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC power frequency clear trap" ::= { trapPrefix 23007 } --#####vrcPowerCfgTable#####-- --#####vrcOutdoorPtTable#####-- vrcOutdoorPtTempNOTIFY NOTIFICATION-TYPE OBJECTS { vrcOutdoorPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC outdoor temperature trap" ::= { trapPrefix 13008 } vrcOutdoorPtTempCLEAR NOTIFICATION-TYPE OBJECTS { vrcOutdoorPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC outdoor temperature clear trap" ::= { trapPrefix 23008 } --#####vrcDischPtTable#####-- vrcDischPtTempNOTIFY NOTIFICATION-TYPE OBJECTS { vrcDischPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC discharge temperature trap" ::= { trapPrefix 13009 } vrcDischPtTempCLEAR NOTIFICATION-TYPE OBJECTS { vrcDischPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC discharge temperature clear trap" ::= { trapPrefix 23009 } vrcDischPtPressureNOTIFY NOTIFICATION-TYPE OBJECTS { vrcDischPtPressure, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC discharge pressure trap" ::= { trapPrefix 13010 } vrcDischPtPressureCLEAR NOTIFICATION-TYPE OBJECTS { vrcDischPtPressure, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC discharge pressure clear trap" ::= { trapPrefix 23010 } --#####vrcDischCfgTable#####-- --#####vrcSuctPtTable#####-- vrcSuctPtTempNOTIFY NOTIFICATION-TYPE OBJECTS { vrcSuctPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC suction temperature trap" ::= { trapPrefix 13011 } vrcSuctPtTempCLEAR NOTIFICATION-TYPE OBJECTS { vrcSuctPtTemp, temperatureUnits, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC suction temperature clear trap" ::= { trapPrefix 23011 } vrcSuctPtPressureNOTIFY NOTIFICATION-TYPE OBJECTS { vrcSuctPtPressure, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC suction pressure trap" ::= { trapPrefix 13012 } vrcSuctPtPressureCLEAR NOTIFICATION-TYPE OBJECTS { vrcSuctPtPressure, trapThreshType, trapSeverity, sysName, vrcMainLabel } STATUS current DESCRIPTION "VRC suction pressure clear trap" ::= { trapPrefix 23012 } --#####vrcSuctCfgTable#####-- --###########################################################################################-- --common group-- --###########################################################################################-- common OBJECT IDENTIFIER ::= { vertiv 42 } identity OBJECT IDENTIFIER ::= { common 1 } i03 OBJECT-IDENTITY STATUS current DESCRIPTION "Value given for sysObjectID on IMD3 units" ::= { identity 53 } r05 OBJECT-IDENTITY STATUS current DESCRIPTION "Value given for sysObjectID on R-Series units" ::= { identity 15 } END