1807 lines
		
	
	
		
			40 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
			
		
		
	
	
			1807 lines
		
	
	
		
			40 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
NETTRACK-E3METER-CTR-SNMP-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
IMPORTS
 | 
						|
	MODULE-IDENTITY,
 | 
						|
	OBJECT-TYPE,
 | 
						|
	Integer32,
 | 
						|
	TimeTicks,
 | 
						|
	Unsigned32
 | 
						|
		FROM SNMPv2-SMI
 | 
						|
	enterprises
 | 
						|
		FROM SNMPv2-SMI
 | 
						|
	TEXTUAL-CONVENTION
 | 
						|
		FROM SNMPv2-TC
 | 
						|
	NOTIFICATION-TYPE
 | 
						|
		FROM SNMPv2-SMI
 | 
						|
	;
 | 
						|
 | 
						|
nettrack OBJECT IDENTIFIER
 | 
						|
	::= { enterprises 21695 }
 | 
						|
 | 
						|
public OBJECT IDENTIFIER
 | 
						|
	::= { nettrack 1 }
 | 
						|
 | 
						|
e3Mib MODULE-IDENTITY
 | 
						|
	LAST-UPDATED    "201903200000Z"
 | 
						|
	ORGANIZATION    "net-track GmbH"
 | 
						|
	CONTACT-INFO    "net-track GmbH
 | 
						|
			Duensstrasse 1
 | 
						|
			3186 Duedingen
 | 
						|
			Switzerland
 | 
						|
			Tel: +41 26 4240924
 | 
						|
 | 
						|
			http://www.net-track.ch
 | 
						|
			info@net-track.ch"
 | 
						|
	DESCRIPTION
 | 
						|
		"Management Information for the E3METER suite."
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201903200000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Add tables containing information about IPS and PRO meters:
 | 
						|
 | 
						|
		* e3MeterConfigTable, e3MeterDataTable, e3MeterSensorTable"
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201810230000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Add residual current monitoring data:
 | 
						|
 | 
						|
		* e3IpsRcm and e3IpsRcmTable"
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201707100000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Add traps for events:
 | 
						|
 | 
						|
		* Add objects: e3CtrEventTime, e3CtrEventSeverityLevel,
 | 
						|
		  e3CtrEventSource and e3CtrEventDescription
 | 
						|
 | 
						|
		* Add notification: e3ConcentratorEventLog"
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201506170000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Numerous changes for providing the data collected with
 | 
						|
		period oriented polling:
 | 
						|
 | 
						|
		* Changes to e3Concentrator:
 | 
						|
 | 
						|
		  - renamed e3ConcentratorVersion to
 | 
						|
		    e3ConcentratorFWVersion and changed it to string.
 | 
						|
 | 
						|
		  - added: e3ConcentratorSystemTime
 | 
						|
 | 
						|
		  - deprecated: e3ConcentratorUptime
 | 
						|
 | 
						|
		* Removed entire e3IpsLocal.
 | 
						|
 | 
						|
		* Changes to e3IpsNetwork:
 | 
						|
 | 
						|
		  - deprecated: e3IpsUnknownNodes, e3IpsActiveNodes,
 | 
						|
		    e3IpsDeadNodes
 | 
						|
 | 
						|
		  - added: e3IpsPolledPeriodStart,
 | 
						|
		    e3IpsPolledPeriodDuration, e3IpsPolledNodesSuccess
 | 
						|
 | 
						|
		* Changes to e3IpsTable:
 | 
						|
 | 
						|
		  - removed: e3IpsLastDataTime
 | 
						|
 | 
						|
		  - added: e3IpsBuild
 | 
						|
 | 
						|
		* Changes to e3IpsMeterTable:
 | 
						|
 | 
						|
		  - removed: e3IpsEnergyQ, e3IpsEnergyS
 | 
						|
 | 
						|
		  - deprecated: e3IpsEnergyP, e3IpsPowerP,
 | 
						|
		    e3IpsPowerQ, e3IpsPowerS, e3IpsUrms, e3IpsIrms,
 | 
						|
		    e3IpsFrequency
 | 
						|
 | 
						|
		  - added: e3IpsPolledPeriodStart,
 | 
						|
		    e3IpsPolledPeriodDuration,
 | 
						|
		    e3IpsPolledNodesSuccess, e3IpsPeriodType,
 | 
						|
		    e3IpsPeriodStart, e3IpsPeriodDuration,
 | 
						|
		    e3IpsDataStatus, e3IpsPMin/Max/Avg,
 | 
						|
		    e3IpsQMin/Max/Avg, e3IpsSAvg,
 | 
						|
		    e3IpsUrmsMin/Max/Avg, e3IpsIrmsMin/Max/Avg,
 | 
						|
		    e3IpsFreqMin/Max
 | 
						|
 | 
						|
		* Changes to e3IpsSensorTable:
 | 
						|
 | 
						|
		  - deprecated: e3IpsSensorTemperatureCelsius,
 | 
						|
		    e3IpsSensorHumidity
 | 
						|
 | 
						|
		  - added: e3IpsSensorPeriodType,
 | 
						|
		    e3IpsSensorPeriodStart, e3IpsSensorPeriodDuration,
 | 
						|
		    e3IpsSensorDataType, e3IpsSensorTempCMin/Max,
 | 
						|
		    e3IpsSensorRHMin/Max"
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201303270000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Added e3ConcentratorUptime and e3IpsLastDataTime."
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201301040000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Added e3IpsChannelConfig."
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201204120000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Added import of TEXTUAL-CONVENTION."
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201104060000Z"
 | 
						|
        DESCRIPTION
 | 
						|
		"Corrected some syntax errors."
 | 
						|
 | 
						|
	REVISION
 | 
						|
		"201003110000Z"
 | 
						|
	DESCRIPTION
 | 
						|
		"Initial version of this MIB module."
 | 
						|
 | 
						|
	::= { public 10 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Textual conventions
 | 
						|
--
 | 
						|
 | 
						|
Watts ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Watts"
 | 
						|
	SYNTAX		INTEGER
 | 
						|
 | 
						|
VoltAmpereReactives ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Volt-ampere reactives"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
VoltAmperes ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Volt-amperes"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
WattHours ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Watt hours"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
VoltAmpereReactiveHours ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Volt-ampere reactive hours"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
VoltAmpereHours ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Volt-ampere hours"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
MilliAmperes ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Milli-amperes"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
MilliVolts ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Milli-volts"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
DeciDegreesCelsius ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Deci-degrees celsius"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
MilliHertz ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Milli-hertz"
 | 
						|
	SYNTAX		Integer32
 | 
						|
 | 
						|
Percent ::= TEXTUAL-CONVENTION
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Percent"
 | 
						|
	SYNTAX		INTEGER
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Agent information
 | 
						|
--
 | 
						|
 | 
						|
e3Concentrator OBJECT IDENTIFIER
 | 
						|
	::= { e3Mib 1 }
 | 
						|
 | 
						|
e3ConcentratorFWVersion OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"CTR firmware version."
 | 
						|
	::= { e3Concentrator 1 }
 | 
						|
 | 
						|
e3ConcentratorUptime OBJECT-TYPE
 | 
						|
	SYNTAX		TimeTicks
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"The system uptime in hundredths of a second."
 | 
						|
	::= { e3Concentrator 2 }
 | 
						|
 | 
						|
e3ConcentratorSystemTime OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The current system time represented in seconds since 1970-01-01
 | 
						|
		00:00:00 UTC."
 | 
						|
	::= { e3Concentrator 3 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- IPS network information
 | 
						|
--
 | 
						|
 | 
						|
e3IpsNetwork OBJECT IDENTIFIER
 | 
						|
	::= { e3Mib 2 }
 | 
						|
 | 
						|
e3IpsTotalNodes OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of configured nodes in total."
 | 
						|
	::= { e3IpsNetwork 1 }
 | 
						|
 | 
						|
e3IpsUnknownNodes OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of unknown nodes.
 | 
						|
		 This object is deprecated, it will return 0."
 | 
						|
	::= { e3IpsNetwork 2 }
 | 
						|
 | 
						|
e3IpsActiveNodes OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of active nodes.
 | 
						|
		 This object is deprecated, use e3IpsPolledNodesSuccess instead."
 | 
						|
	::= { e3IpsNetwork 3 }
 | 
						|
 | 
						|
e3IpsDeadNodes OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of dead (unreachable) nodes.
 | 
						|
		 This object is deprecated, it will return 0."
 | 
						|
	::= { e3IpsNetwork 4 }
 | 
						|
 | 
						|
e3IpsPolledPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the most recent polling period in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC."
 | 
						|
	::= { e3IpsNetwork 5 }
 | 
						|
 | 
						|
e3IpsPolledPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3IpsNetwork 6 }
 | 
						|
 | 
						|
e3IpsPolledNodesSuccess OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The number of nodes for which data was available for the most
 | 
						|
		 reccently polled period."
 | 
						|
	::= { e3IpsNetwork 7 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- IPS information
 | 
						|
--
 | 
						|
 | 
						|
e3IpsTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3IpsEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The e3IpsTable holds information about all IPS nodes in the
 | 
						|
		network."
 | 
						|
	::= { e3Mib 3 }
 | 
						|
 | 
						|
e3IpsEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3IpsEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Holds information about one particular IPS."
 | 
						|
	INDEX		{ e3IpsSerial }
 | 
						|
	::=		{ e3IpsTable 1 }
 | 
						|
 | 
						|
E3IpsEntry ::= SEQUENCE {
 | 
						|
		e3IpsSerial		Integer32,
 | 
						|
		e3IpsCtrSerial		Integer32,
 | 
						|
		e3IpsModel		Integer32,
 | 
						|
		e3IpsHWVersion		INTEGER,
 | 
						|
		e3IpsFWVersion		Integer32,
 | 
						|
		e3IpsPLCVersion		Integer32,
 | 
						|
		e3IpsPLCBand		INTEGER,
 | 
						|
		e3IpsLabel		OCTET STRING,
 | 
						|
		e3IpsState		INTEGER,
 | 
						|
		e3IpsMeters		INTEGER,
 | 
						|
		e3IpsSensors		INTEGER,
 | 
						|
		e3IpsChannelConfig	INTEGER,
 | 
						|
		e3IpsBuild		OCTET STRING,
 | 
						|
		e3IpsRcm		INTEGER
 | 
						|
	}
 | 
						|
 | 
						|
e3IpsSerial OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The serial number is the primary identification for
 | 
						|
		for every IPS."
 | 
						|
	::= { e3IpsEntry 1 }
 | 
						|
 | 
						|
e3IpsCtrSerial OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The serial number of the concentrator this IPS is
 | 
						|
		connected to."
 | 
						|
	::= { e3IpsEntry 2 }
 | 
						|
 | 
						|
e3IpsModel OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Model number."
 | 
						|
	::= { e3IpsEntry 3 }
 | 
						|
 | 
						|
e3IpsHWVersion OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		rev-a (0),
 | 
						|
		rev-b (1),
 | 
						|
		rev-c (2),
 | 
						|
		rev-d (3),
 | 
						|
		rev-e (4)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Hardware revision."
 | 
						|
	::= { e3IpsEntry 4 }
 | 
						|
 | 
						|
e3IpsFWVersion OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Integer representation of the firmware revision
 | 
						|
		(major.minor) represented as a 16 bit integer."
 | 
						|
	::= { e3IpsEntry 5 }
 | 
						|
 | 
						|
e3IpsPLCVersion OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"PLC firmware revision (major.minor.build) represented
 | 
						|
		as a 24 bit integer."
 | 
						|
	::= { e3IpsEntry 6 }
 | 
						|
 | 
						|
e3IpsPLCBand OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		fcc (0),
 | 
						|
		arib (1),
 | 
						|
		cenelec-a (2),
 | 
						|
		cenelec-b (3)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Holds the PLC band used by the corresponding node."
 | 
						|
	::= { e3IpsEntry 7 }
 | 
						|
 | 
						|
e3IpsLabel OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING (SIZE (0..15))
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"IPS label shown on display."
 | 
						|
	::= { e3IpsEntry 8 }
 | 
						|
 | 
						|
e3IpsState OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		active (1),
 | 
						|
		dead (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"State of this node."
 | 
						|
	::= { e3IpsEntry 9 }
 | 
						|
 | 
						|
e3IpsMeters OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of power meters in this IPS."
 | 
						|
	::= { e3IpsEntry 10 }
 | 
						|
 | 
						|
e3IpsSensors OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of sensors connected to this IPS."
 | 
						|
	::= { e3IpsEntry 11 }
 | 
						|
 | 
						|
e3IpsChannelConfig OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		1L (1),
 | 
						|
		3L1N (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Channel configuration."
 | 
						|
	::= { e3IpsEntry 12 }
 | 
						|
 | 
						|
e3IpsBuild OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING (SIZE (0..15))
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"IPS firmware build number."
 | 
						|
	::= { e3IpsEntry 14 }
 | 
						|
 | 
						|
e3IpsRcm OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		none (0),
 | 
						|
		total-rcm (1)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Type of installed residual current monitoring: none (0)
 | 
						|
		or total (1), where the total residual current of all phases
 | 
						|
		is monitored."
 | 
						|
	::= { e3IpsEntry 15 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- IPS meters
 | 
						|
--
 | 
						|
 | 
						|
e3IpsMeterTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3IpsMeterEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The e3IpsMeterTable holds information related to the
 | 
						|
		powermeters of all IPS nodes."
 | 
						|
	::= { e3Mib 4 }
 | 
						|
 | 
						|
e3IpsMeterEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3IpsMeterEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Holds the information related to one specific powermeter."
 | 
						|
	INDEX		{ e3IpsSerial, e3IpsMeter }
 | 
						|
	::=		{ e3IpsMeterTable 1 }
 | 
						|
 | 
						|
E3IpsMeterEntry ::= SEQUENCE {
 | 
						|
		e3IpsMeter		Integer32,
 | 
						|
		e3IpsEnergyP		WattHours,
 | 
						|
		e3IpsPowerP		Watts,
 | 
						|
		e3IpsPowerQ		VoltAmpereReactives,
 | 
						|
		e3IpsPowerS		VoltAmperes,
 | 
						|
		e3IpsUrms		MilliVolts,
 | 
						|
		e3IpsIrms		MilliAmperes,
 | 
						|
		e3IpsFrequency		MilliHertz,
 | 
						|
		e3IpsPeriodType		INTEGER,
 | 
						|
		e3IpsPeriodStart	Unsigned32,
 | 
						|
		e3IpsPeriodDuration	Unsigned32,
 | 
						|
		e3IpsDataStatus		INTEGER,
 | 
						|
		e3IpsPMin		Watts,
 | 
						|
		e3IpsPMax		Watts,
 | 
						|
		e3IpsPAvg		Watts,
 | 
						|
		e3IpsQMin		VoltAmpereReactives,
 | 
						|
		e3IpsQMax		VoltAmpereReactives,
 | 
						|
		e3IpsQAvg		VoltAmpereReactives,
 | 
						|
		e3IpsSAvg		VoltAmperes,
 | 
						|
		e3IpsUrmsMin		MilliVolts,
 | 
						|
		e3IpsUrmsMax		MilliVolts,
 | 
						|
		e3IpsUrmsAvg		MilliVolts,
 | 
						|
		e3IpsIrmsMin		MilliAmperes,
 | 
						|
		e3IpsIrmsMax		MilliAmperes,
 | 
						|
		e3IpsIrmsAvg		MilliAmperes,
 | 
						|
		e3IpsFreqMin		MilliHertz,
 | 
						|
		e3IpsFreqMax		MilliHertz,
 | 
						|
		e3IpsPFAvg		INTEGER,
 | 
						|
		e3IpsActiveEnergy	WattHours,
 | 
						|
		e3IpsReactiveEnergyL	VoltAmpereReactiveHours,
 | 
						|
		e3IpsReactiveEnergyC	VoltAmpereReactiveHours
 | 
						|
	}
 | 
						|
 | 
						|
e3IpsMeter OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Index of this power meter in the current node."
 | 
						|
	::= { e3IpsMeterEntry 2 }
 | 
						|
 | 
						|
e3IpsEnergyP OBJECT-TYPE
 | 
						|
	SYNTAX		WattHours
 | 
						|
	UNITS		"Wh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Active energy in watt hours.
 | 
						|
		This object is deprecated, use the e3IpsActiveEnergy object instead."
 | 
						|
	::= { e3IpsMeterEntry 3 }
 | 
						|
 | 
						|
e3IpsPowerP OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Active power at a given instant.
 | 
						|
		This object is deprecated, use the e3IpsPAvg object instead."
 | 
						|
	::= { e3IpsMeterEntry 6 }
 | 
						|
 | 
						|
e3IpsPowerQ OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Reactive power at a given instant.
 | 
						|
		This object is deprecated, use the e3IpsQAvg object instead."
 | 
						|
	::= { e3IpsMeterEntry 7 }
 | 
						|
 | 
						|
e3IpsPowerS OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmperes
 | 
						|
	UNITS		"VA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Apparent power at a given instant.
 | 
						|
		This object is deprecated, use the e3IpsQAvg object instead."
 | 
						|
	::= { e3IpsMeterEntry 8 }
 | 
						|
 | 
						|
e3IpsUrms OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"RMS voltage at a given instant.
 | 
						|
		This object is deprecated, use the e3IpsUrmsAvg object instead."
 | 
						|
	::= { e3IpsMeterEntry 9 }
 | 
						|
 | 
						|
e3IpsIrms OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"RMS current at a given instant.
 | 
						|
		This object is deprecated, use the e3IpsIrmsAvg object instead."
 | 
						|
	::= { e3IpsMeterEntry 10 }
 | 
						|
 | 
						|
e3IpsFrequency OBJECT-TYPE
 | 
						|
	SYNTAX		MilliHertz
 | 
						|
	UNITS		"mHz"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Frequency measured a given instant.
 | 
						|
		This object is deprecated, use e3IpsFreqMin/Max instead."
 | 
						|
	::= { e3IpsMeterEntry 11 }
 | 
						|
 | 
						|
e3IpsPeriodType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		aggregated (0),
 | 
						|
		sample (1)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Specifies whether the data is truly aggregated over
 | 
						|
		the indicated period or if it represents just a sample
 | 
						|
		during the indicated period (for old firmware
 | 
						|
		versions)."
 | 
						|
	::= { e3IpsMeterEntry 12 }
 | 
						|
 | 
						|
e3IpsPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the data period which is represented by the
 | 
						|
		values in the MIB. This is given in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC. If this is 0, no data has
 | 
						|
		been received from this node yet."
 | 
						|
	::= { e3IpsMeterEntry 13 }
 | 
						|
 | 
						|
e3IpsPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3IpsMeterEntry 14 }
 | 
						|
 | 
						|
e3IpsDataStatus OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		current-data (1),
 | 
						|
		old-data (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Informs about the nature of the data in this table
 | 
						|
		entry: 0 (unknown) means no data has yet been received
 | 
						|
		from this node, 1 (current-data) means that the data
 | 
						|
		is from the most recently polled period, 2 (old-data)
 | 
						|
		means the data is from a previous period."
 | 
						|
	::= { e3IpsMeterEntry 15 }
 | 
						|
 | 
						|
e3IpsPMin OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 16 }
 | 
						|
 | 
						|
e3IpsPMax OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 17 }
 | 
						|
 | 
						|
e3IpsPAvg OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 18 }
 | 
						|
 | 
						|
e3IpsQMin OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 19 }
 | 
						|
 | 
						|
e3IpsQMax OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 20 }
 | 
						|
 | 
						|
e3IpsQAvg OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 21 }
 | 
						|
 | 
						|
e3IpsSAvg OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmperes
 | 
						|
	UNITS		"VA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg apparent power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 22 }
 | 
						|
 | 
						|
e3IpsUrmsMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 23 }
 | 
						|
 | 
						|
e3IpsUrmsMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 24 }
 | 
						|
 | 
						|
e3IpsUrmsAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 25 }
 | 
						|
 | 
						|
e3IpsIrmsMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 26 }
 | 
						|
 | 
						|
e3IpsIrmsMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 27 }
 | 
						|
 | 
						|
e3IpsIrmsAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 28 }
 | 
						|
 | 
						|
e3IpsFreqMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliHertz
 | 
						|
	UNITS		"mHz"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min frequency measured during the indicated period."
 | 
						|
	::= { e3IpsMeterEntry 29 }
 | 
						|
 | 
						|
e3IpsFreqMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliHertz
 | 
						|
	UNITS		"mHz"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max frequency measured during the indicated period."
 | 
						|
	::= { e3IpsMeterEntry 30 }
 | 
						|
 | 
						|
e3IpsPFAvg OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg power factor * 100 measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 31 }
 | 
						|
 | 
						|
e3IpsActiveEnergy OBJECT-TYPE
 | 
						|
	SYNTAX		WattHours
 | 
						|
	UNITS		"Wh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Active energy at the end of the indicated period."
 | 
						|
	::= { e3IpsMeterEntry 32 }
 | 
						|
 | 
						|
e3IpsReactiveEnergyL OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactiveHours
 | 
						|
	UNITS		"varh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Reactive inductive energy at the end of the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsMeterEntry 33 }
 | 
						|
 | 
						|
e3IpsReactiveEnergyC OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactiveHours
 | 
						|
	UNITS		"varh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Reactive capacitive energy at the end of the
 | 
						|
		indicated period."
 | 
						|
	::= { e3IpsMeterEntry 34 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- IPS sensors
 | 
						|
--
 | 
						|
 | 
						|
e3IpsSensorTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3IpsSensorEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The sensor table holds all the sensors of this E3METER
 | 
						|
		concentrator."
 | 
						|
	::= { e3Mib 5 }
 | 
						|
 | 
						|
e3IpsSensorEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3IpsSensorEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"An entry containing all data related to a sensor."
 | 
						|
	INDEX		{ e3IpsSerial, e3IpsSensorPort }
 | 
						|
	::=		{ e3IpsSensorTable 1 }
 | 
						|
 | 
						|
E3IpsSensorEntry ::= SEQUENCE {
 | 
						|
		e3IpsSensorPort			Integer32,
 | 
						|
		e3IpsSensorType			INTEGER,
 | 
						|
		e3IpsSensorTemperatureCelsius	DeciDegreesCelsius,
 | 
						|
		e3IpsSensorHumidity		Percent,
 | 
						|
		e3IpsSensorPeriodType		INTEGER,
 | 
						|
		e3IpsSensorPeriodStart		Unsigned32,
 | 
						|
		e3IpsSensorPeriodDuration	Unsigned32,
 | 
						|
		e3IpsSensorDataStatus		INTEGER,
 | 
						|
		e3IpsSensorTempCMin		DeciDegreesCelsius,
 | 
						|
		e3IpsSensorTempCMax		DeciDegreesCelsius,
 | 
						|
		e3IpsSensorRHMin		Percent,
 | 
						|
		e3IpsSensorRHMax		Percent
 | 
						|
	}
 | 
						|
 | 
						|
e3IpsSensorPort OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Sensor port number. Zero denotes the built-in sensor."
 | 
						|
	::= { e3IpsSensorEntry 2 }
 | 
						|
 | 
						|
e3IpsSensorType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		none (0),
 | 
						|
		internal-temp (1),
 | 
						|
		temp (2),
 | 
						|
		temp-rh (3)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Sensor type."
 | 
						|
	::= { e3IpsSensorEntry 3 }
 | 
						|
 | 
						|
e3IpsSensorTemperatureCelsius OBJECT-TYPE
 | 
						|
	SYNTAX		DeciDegreesCelsius
 | 
						|
	UNITS		"deg-C/10"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Temperature in tenth degrees measured at a given instant."
 | 
						|
	::= { e3IpsSensorEntry 4 }
 | 
						|
 | 
						|
e3IpsSensorHumidity OBJECT-TYPE
 | 
						|
	SYNTAX		Percent
 | 
						|
	UNITS		"%"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		deprecated
 | 
						|
	DESCRIPTION
 | 
						|
		"Humidity measured at a given instant."
 | 
						|
	::= { e3IpsSensorEntry 5 }
 | 
						|
 | 
						|
e3IpsSensorPeriodType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		aggregated (0),
 | 
						|
		sample (1)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Specifies whether the data is truly aggregated over
 | 
						|
		the indicated period or if it represents just a sample
 | 
						|
		during the indicated period (for old firmware
 | 
						|
		versions)."
 | 
						|
	::= { e3IpsSensorEntry 6 }
 | 
						|
 | 
						|
e3IpsSensorPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the data period which is represented by the
 | 
						|
		values in the MIB. This is given in seconds since the
 | 
						|
		1970-01-01 00:00:00 UTC. If this is 0, no data was
 | 
						|
		received from this node yet."
 | 
						|
	::= { e3IpsSensorEntry 7 }
 | 
						|
 | 
						|
e3IpsSensorPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3IpsSensorEntry 8 }
 | 
						|
 | 
						|
e3IpsSensorDataStatus OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		current-data (1),
 | 
						|
		old-data (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Informs about the nature of the data in this table
 | 
						|
		entry: 0 (unknown) means no data has yet been received
 | 
						|
		from this node, 1 (current-data) means that the data
 | 
						|
		is from the most recently polled period, 2 (old-data)
 | 
						|
		means the data is from a previous period."
 | 
						|
	::= { e3IpsSensorEntry 9 }
 | 
						|
 | 
						|
e3IpsSensorTempCMin OBJECT-TYPE
 | 
						|
	SYNTAX		DeciDegreesCelsius
 | 
						|
	UNITS		"deg-C/10"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min temperature in celsius measured during the
 | 
						|
		indicated period."
 | 
						|
	::= { e3IpsSensorEntry 10 }
 | 
						|
 | 
						|
e3IpsSensorTempCMax OBJECT-TYPE
 | 
						|
	SYNTAX		DeciDegreesCelsius
 | 
						|
	UNITS		"deg-C/10"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max temperature in celsius measured during the
 | 
						|
		indicated period."
 | 
						|
	::= { e3IpsSensorEntry 11 }
 | 
						|
 | 
						|
e3IpsSensorRHMin OBJECT-TYPE
 | 
						|
	SYNTAX		Percent
 | 
						|
	UNITS		"%"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min relative humidity measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsSensorEntry 12 }
 | 
						|
 | 
						|
e3IpsSensorRHMax OBJECT-TYPE
 | 
						|
	SYNTAX		Percent
 | 
						|
	UNITS		"%"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max relative humidity measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3IpsSensorEntry 13 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- RCM objects
 | 
						|
--
 | 
						|
 | 
						|
e3IpsRcmTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3IpsRcmEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The sensor table holds the residual current monitoring data
 | 
						|
		of this E3METER concentrator."
 | 
						|
	::= { e3Mib 11 }
 | 
						|
 | 
						|
e3IpsRcmEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3IpsRcmEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"An entry containing all data related to an rcm measuring point."
 | 
						|
	INDEX		{ e3IpsSerial }
 | 
						|
	::=		{ e3IpsRcmTable 1 }
 | 
						|
 | 
						|
E3IpsRcmEntry ::= SEQUENCE {
 | 
						|
		e3IpsRcmPeriodStart		Unsigned32,
 | 
						|
		e3IpsRcmPeriodDuration		Unsigned32,
 | 
						|
		e3IpsRcmDataStatus		INTEGER,
 | 
						|
		e3IpsRcmAcMin			MilliAmperes,
 | 
						|
		e3IpsRcmAcMax			MilliAmperes,
 | 
						|
		e3IpsRcmAcAvg			MilliAmperes,
 | 
						|
		e3IpsRcmDcMin			MilliAmperes,
 | 
						|
		e3IpsRcmDcMax			MilliAmperes,
 | 
						|
		e3IpsRcmDcAvg			MilliAmperes
 | 
						|
	}
 | 
						|
 | 
						|
e3IpsRcmPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the data period which is represented by the
 | 
						|
		values in the MIB. This is given in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC. If this is 0, no data has
 | 
						|
		been received from this node yet."
 | 
						|
	::= { e3IpsRcmEntry 2 }
 | 
						|
 | 
						|
e3IpsRcmPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3IpsRcmEntry 3 }
 | 
						|
 | 
						|
e3IpsRcmDataStatus OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		current-data (1),
 | 
						|
		old-data (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Informs about the nature of the data in this table
 | 
						|
		entry: 0 (unknown) means no data has yet been received
 | 
						|
		from this node, 1 (current-data) means that the data
 | 
						|
		is from the most recently polled period, 2 (old-data)
 | 
						|
		means the data is from a previous period."
 | 
						|
	::= { e3IpsRcmEntry 4 }
 | 
						|
 | 
						|
e3IpsRcmAcMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min AC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 5 }
 | 
						|
 | 
						|
e3IpsRcmAcMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max AC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 6 }
 | 
						|
 | 
						|
e3IpsRcmAcAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg AC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 7 }
 | 
						|
 | 
						|
e3IpsRcmDcMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min DC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 8 }
 | 
						|
 | 
						|
e3IpsRcmDcMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max DC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 9 }
 | 
						|
 | 
						|
e3IpsRcmDcAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg DC residual current measured during the indicated
 | 
						|
		period"
 | 
						|
	::= { e3IpsRcmEntry 10 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Static information about the available meters
 | 
						|
--
 | 
						|
 | 
						|
e3MeterConfigTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3MeterConfigEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The e3MeterConfigTable holds information about all meters."
 | 
						|
	::= { e3Mib 12 }
 | 
						|
 | 
						|
e3MeterConfigEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3MeterConfigEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Holds the information related to one specific meter."
 | 
						|
	INDEX		{ e3MeterIndex }
 | 
						|
	::=		{ e3MeterConfigTable 1 }
 | 
						|
 | 
						|
E3MeterConfigEntry ::= SEQUENCE {
 | 
						|
		e3MeterIndex		Integer32,
 | 
						|
		e3MeterUID		OCTET STRING,
 | 
						|
		e3MeterType		Integer32,
 | 
						|
		e3MeterVersion		OCTET STRING,
 | 
						|
		e3MeterLabel		OCTET STRING,
 | 
						|
		e3MeterSerial		OCTET STRING,
 | 
						|
		e3MeterModel		OCTET STRING,
 | 
						|
		e3MeterChannelConfig	Integer32,
 | 
						|
		e3MeterNumSensors	Integer32
 | 
						|
	}
 | 
						|
 | 
						|
e3MeterIndex OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32 (0..2147483647)
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Index of the meter on this CTR. The index is maintained
 | 
						|
		across CTR reboots and changes only if a meter is deleted
 | 
						|
		and added again."
 | 
						|
	::= { e3MeterConfigEntry 1 }
 | 
						|
 | 
						|
e3MeterUID OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING (SIZE (0..8))
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Unique ID of the meter on this CTR."
 | 
						|
	::= { e3MeterConfigEntry 2 }
 | 
						|
 | 
						|
e3MeterType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		ips (1),
 | 
						|
		pro (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Meter type."
 | 
						|
	::= { e3MeterConfigEntry 3 }
 | 
						|
 | 
						|
e3MeterVersion OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Hardware & software versions."
 | 
						|
	::= { e3MeterConfigEntry 4 }
 | 
						|
 | 
						|
e3MeterLabel OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Device label."
 | 
						|
	::= { e3MeterConfigEntry 5 }
 | 
						|
 | 
						|
e3MeterSerial OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Serial number of a meter."
 | 
						|
	::= { e3MeterConfigEntry 6 }
 | 
						|
 | 
						|
e3MeterModel OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Meter model."
 | 
						|
	::= { e3MeterConfigEntry 7 }
 | 
						|
 | 
						|
e3MeterChannelConfig OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		ch-unknown (0),
 | 
						|
		ch-1L (1),
 | 
						|
		ch-3L1N (2),
 | 
						|
		ch-3L (3)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Channel configuration of this meter. This defines the
 | 
						|
		number of channels of a meter and the nature of the
 | 
						|
		individual meters in e3MeterTable:
 | 
						|
		- 1L: 1 live wire channel
 | 
						|
		- 3L1N: 3 live wires, 1 neutral wire (4 channels total)
 | 
						|
		- 3L: 3 live wires"
 | 
						|
	::= { e3MeterConfigEntry 8 }
 | 
						|
 | 
						|
e3MeterNumSensors OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Number of sensors of this meter in e3MeterSensorTable"
 | 
						|
	::= { e3MeterConfigEntry 9 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Metering data of each channel of every meter
 | 
						|
--
 | 
						|
 | 
						|
e3MeterDataTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3MeterDataEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"This table holds the metering data of all meters."
 | 
						|
	::= { e3Mib 13 }
 | 
						|
 | 
						|
e3MeterDataEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3MeterDataEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"An entry containing all measurement data related a meter."
 | 
						|
	INDEX		{ e3MeterDataMeterIndex, e3MeterDataChannel }
 | 
						|
	::=		{ e3MeterDataTable 1 }
 | 
						|
 | 
						|
E3MeterDataEntry ::= SEQUENCE {
 | 
						|
		e3MeterDataMeterIndex		Integer32,
 | 
						|
		e3MeterDataChannel		Integer32,
 | 
						|
		e3MeterDataPeriodType		INTEGER,
 | 
						|
		e3MeterDataPeriodStart		Unsigned32,
 | 
						|
		e3MeterDataPeriodDuration	Unsigned32,
 | 
						|
		e3MeterDataStatus		INTEGER,
 | 
						|
		e3MeterDataPMin			Watts,
 | 
						|
		e3MeterDataPMax			Watts,
 | 
						|
		e3MeterDataPAvg			Watts,
 | 
						|
		e3MeterDataQMin			VoltAmpereReactives,
 | 
						|
		e3MeterDataQMax			VoltAmpereReactives,
 | 
						|
		e3MeterDataQAvg			VoltAmpereReactives,
 | 
						|
		e3MeterDataSAvg			VoltAmperes,
 | 
						|
		e3MeterDataUrmsMin		MilliVolts,
 | 
						|
		e3MeterDataUrmsMax		MilliVolts,
 | 
						|
		e3MeterDataUrmsAvg		MilliVolts,
 | 
						|
		e3MeterDataIrmsMin		MilliAmperes,
 | 
						|
		e3MeterDataIrmsMax		MilliAmperes,
 | 
						|
		e3MeterDataIrmsAvg		MilliAmperes,
 | 
						|
		e3MeterDataFreqMin		MilliHertz,
 | 
						|
		e3MeterDataFreqMax		MilliHertz,
 | 
						|
		e3MeterDataPFAvg		INTEGER,
 | 
						|
		e3MeterDataActiveEnergy		WattHours,
 | 
						|
		e3MeterDataReactiveEnergyL	VoltAmpereReactiveHours,
 | 
						|
		e3MeterDataReactiveEnergyC	VoltAmpereReactiveHours
 | 
						|
	}
 | 
						|
 | 
						|
e3MeterDataMeterIndex OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32 (0..2147483647)
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Corresponds to the e3MeterIndex entry in e3MeterConfig table."
 | 
						|
	::= { e3MeterDataEntry 1 }
 | 
						|
 | 
						|
e3MeterDataChannel OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32 (0..3)
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Channel number."
 | 
						|
	::= { e3MeterDataEntry 2 }
 | 
						|
 | 
						|
e3MeterDataPeriodType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		aggregated (0),
 | 
						|
		sample (1)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Specifies whether the data is truly aggregated over
 | 
						|
		the indicated period or if it represents just a sample
 | 
						|
		during the indicated period (for old firmware
 | 
						|
		versions)."
 | 
						|
	::= { e3MeterDataEntry 3 }
 | 
						|
 | 
						|
e3MeterDataPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the data period which is represented by the
 | 
						|
		values in the MIB. This is given in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC. If this is 0, no data has
 | 
						|
		been received from this meter yet."
 | 
						|
	::= { e3MeterDataEntry 4 }
 | 
						|
 | 
						|
e3MeterDataPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3MeterDataEntry 5 }
 | 
						|
 | 
						|
e3MeterDataStatus OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		current-data (1),
 | 
						|
		old-data (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Informs about the nature of the data in this table
 | 
						|
		entry: 0 (unknown) means no data has yet been received
 | 
						|
		from this meter, 1 (current-data) means that the data
 | 
						|
		is from the most recently polled period, 2 (old-data)
 | 
						|
		means the data is from a previous period."
 | 
						|
	::= { e3MeterDataEntry 6 }
 | 
						|
 | 
						|
e3MeterDataPMin OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 7 }
 | 
						|
 | 
						|
e3MeterDataPMax OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 8 }
 | 
						|
 | 
						|
e3MeterDataPAvg OBJECT-TYPE
 | 
						|
	SYNTAX		Watts
 | 
						|
	UNITS		"W"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg active power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 9 }
 | 
						|
 | 
						|
e3MeterDataQMin OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 10 }
 | 
						|
 | 
						|
e3MeterDataQMax OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 11 }
 | 
						|
 | 
						|
e3MeterDataQAvg OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactives
 | 
						|
	UNITS		"var"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg reactive power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 12 }
 | 
						|
 | 
						|
e3MeterDataSAvg OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmperes
 | 
						|
	UNITS		"VA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg apparent power measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 13 }
 | 
						|
 | 
						|
e3MeterDataUrmsMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 14 }
 | 
						|
 | 
						|
e3MeterDataUrmsMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 15 }
 | 
						|
 | 
						|
e3MeterDataUrmsAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliVolts
 | 
						|
	UNITS		"mV"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg RMS voltage measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 16 }
 | 
						|
 | 
						|
e3MeterDataIrmsMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 17 }
 | 
						|
 | 
						|
e3MeterDataIrmsMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 18 }
 | 
						|
 | 
						|
e3MeterDataIrmsAvg OBJECT-TYPE
 | 
						|
	SYNTAX		MilliAmperes
 | 
						|
	UNITS		"mA"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg RMS current measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 19 }
 | 
						|
 | 
						|
e3MeterDataFreqMin OBJECT-TYPE
 | 
						|
	SYNTAX		MilliHertz
 | 
						|
	UNITS		"mHz"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min frequency measured during the indicated period."
 | 
						|
	::= { e3MeterDataEntry 20 }
 | 
						|
 | 
						|
e3MeterDataFreqMax OBJECT-TYPE
 | 
						|
	SYNTAX		MilliHertz
 | 
						|
	UNITS		"mHz"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max frequency measured during the indicated period."
 | 
						|
	::= { e3MeterDataEntry 21 }
 | 
						|
 | 
						|
e3MeterDataPFAvg OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Avg power factor * 100 measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 22 }
 | 
						|
 | 
						|
e3MeterDataActiveEnergy OBJECT-TYPE
 | 
						|
	SYNTAX		WattHours
 | 
						|
	UNITS		"Wh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Active energy at the end of the indicated period."
 | 
						|
	::= { e3MeterDataEntry 23 }
 | 
						|
 | 
						|
e3MeterDataReactiveEnergyL OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactiveHours
 | 
						|
	UNITS		"varh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Reactive inductive energy at the end of the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterDataEntry 24 }
 | 
						|
 | 
						|
e3MeterDataReactiveEnergyC OBJECT-TYPE
 | 
						|
	SYNTAX		VoltAmpereReactiveHours
 | 
						|
	UNITS		"varh"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Reactive capacitive energy at the end of the
 | 
						|
		indicated period."
 | 
						|
	::= { e3MeterDataEntry 25 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Sensor data of each channel of every meter
 | 
						|
--
 | 
						|
 | 
						|
e3MeterSensorTable OBJECT-TYPE
 | 
						|
	SYNTAX		SEQUENCE OF E3MeterSensorEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"This table holds the sensor data of all meters."
 | 
						|
	::= { e3Mib 14 }
 | 
						|
 | 
						|
e3MeterSensorEntry OBJECT-TYPE
 | 
						|
	SYNTAX		E3MeterSensorEntry
 | 
						|
	MAX-ACCESS	not-accessible
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"An entry containing each meter's sensor data."
 | 
						|
	INDEX		{ e3MeterSensorMeterIndex, e3MeterSensorIndex }
 | 
						|
	::=		{ e3MeterSensorTable 1 }
 | 
						|
 | 
						|
E3MeterSensorEntry ::= SEQUENCE {
 | 
						|
		e3MeterSensorMeterIndex		Integer32,
 | 
						|
		e3MeterSensorIndex		Integer32,
 | 
						|
		e3MeterSensorPeriodType		INTEGER,
 | 
						|
		e3MeterSensorPeriodStart	Unsigned32,
 | 
						|
		e3MeterSensorPeriodDuration	Unsigned32,
 | 
						|
		e3MeterSensorStatus		INTEGER,
 | 
						|
		e3MeterSensorDescription	OCTET STRING,
 | 
						|
		e3MeterSensorType		INTEGER,
 | 
						|
		e3MeterSensorTempCMin		DeciDegreesCelsius,
 | 
						|
		e3MeterSensorTempCMax		DeciDegreesCelsius,
 | 
						|
		e3MeterSensorRHMin		Percent,
 | 
						|
		e3MeterSensorRHMax		Percent
 | 
						|
	}
 | 
						|
 | 
						|
e3MeterSensorMeterIndex OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32 (0..2147483647)
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Corresponds to the e3MeterIndex entry in e3MeterConfig table."
 | 
						|
	::= { e3MeterSensorEntry 1 }
 | 
						|
 | 
						|
e3MeterSensorIndex OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32 (0..3)
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Sensor index."
 | 
						|
	::= { e3MeterSensorEntry 2 }
 | 
						|
 | 
						|
e3MeterSensorPeriodType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		aggregated (0),
 | 
						|
		sample (1)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Specifies whether the data is truly aggregated over
 | 
						|
		the indicated period or if it represents just a sample
 | 
						|
		during the indicated period (for old firmware
 | 
						|
		versions)."
 | 
						|
	::= { e3MeterSensorEntry 3 }
 | 
						|
 | 
						|
e3MeterSensorPeriodStart OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Start of the data period which is represented by the
 | 
						|
		values in the MIB. This is given in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC. If this is 0, no data has
 | 
						|
		been received from this meter yet."
 | 
						|
	::= { e3MeterSensorEntry 4 }
 | 
						|
 | 
						|
e3MeterSensorPeriodDuration OBJECT-TYPE
 | 
						|
	SYNTAX		Unsigned32
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Duration of the data period in seconds."
 | 
						|
	::= { e3MeterSensorEntry 5 }
 | 
						|
 | 
						|
e3MeterSensorStatus OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		unknown (0),
 | 
						|
		current-data (1),
 | 
						|
		old-data (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Informs about the nature of the data in this table
 | 
						|
		entry: 0 (unknown) means no data has yet been received
 | 
						|
		from this meter, 1 (current-data) means that the data
 | 
						|
		is from the most recently polled period, 2 (old-data)
 | 
						|
		means the data is from a previous period."
 | 
						|
	::= { e3MeterSensorEntry 6 }
 | 
						|
 | 
						|
e3MeterSensorDescription OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Textual description of the sensor."
 | 
						|
	::= { e3MeterSensorEntry 7 }
 | 
						|
 | 
						|
e3MeterSensorType OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		none (0),
 | 
						|
		temp (1),
 | 
						|
		temprh (2)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Sensor type."
 | 
						|
	::= { e3MeterSensorEntry 8 }
 | 
						|
 | 
						|
e3MeterSensorTempCMin OBJECT-TYPE
 | 
						|
	SYNTAX		DeciDegreesCelsius
 | 
						|
	UNITS		"deg-C/10"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min temperature in celsius measured during the
 | 
						|
		indicated period."
 | 
						|
	::= { e3MeterSensorEntry 9 }
 | 
						|
 | 
						|
e3MeterSensorTempCMax OBJECT-TYPE
 | 
						|
	SYNTAX		DeciDegreesCelsius
 | 
						|
	UNITS		"deg-C/10"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max temperature in celsius measured during the
 | 
						|
		indicated period."
 | 
						|
	::= { e3MeterSensorEntry 10 }
 | 
						|
 | 
						|
e3MeterSensorRHMin OBJECT-TYPE
 | 
						|
	SYNTAX		Percent
 | 
						|
	UNITS		"%"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Min relative humidity measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterSensorEntry 11 }
 | 
						|
 | 
						|
e3MeterSensorRHMax OBJECT-TYPE
 | 
						|
	SYNTAX		Percent
 | 
						|
	UNITS		"%"
 | 
						|
	MAX-ACCESS	read-only
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Max relative humidity measured during the indicated
 | 
						|
		period."
 | 
						|
	::= { e3MeterSensorEntry 12 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- CTR Trap objects
 | 
						|
--
 | 
						|
 | 
						|
e3ConcentratorTrapObjects OBJECT IDENTIFIER
 | 
						|
 | 
						|
	::= { e3Mib 9 }
 | 
						|
 | 
						|
e3CtrEventTime OBJECT-TYPE
 | 
						|
	SYNTAX		Integer32
 | 
						|
	MAX-ACCESS	accessible-for-notify
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The time at which the event occurred represented in seconds since
 | 
						|
		1970-01-01 00:00:00 UTC."
 | 
						|
	::= { e3ConcentratorTrapObjects 1 }
 | 
						|
 | 
						|
e3CtrEventSeverityLevel OBJECT-TYPE
 | 
						|
	SYNTAX		INTEGER {
 | 
						|
		informational(10),
 | 
						|
		warning(20),
 | 
						|
		critical(30),
 | 
						|
		emergency(40)
 | 
						|
	}
 | 
						|
	MAX-ACCESS	accessible-for-notify
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"The severity level of the event."
 | 
						|
	::= { e3ConcentratorTrapObjects 2 }
 | 
						|
 | 
						|
e3CtrEventSource OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	accessible-for-notify
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Type and serial number of the device which caused the event."
 | 
						|
	::= { e3ConcentratorTrapObjects 3 }
 | 
						|
 | 
						|
e3CtrEventDescription OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	MAX-ACCESS	accessible-for-notify
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Description of the event."
 | 
						|
	::= { e3ConcentratorTrapObjects 4 }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- CTR Traps
 | 
						|
--
 | 
						|
 | 
						|
e3ConcentratorTraps OBJECT IDENTIFIER
 | 
						|
 | 
						|
	::= { e3Mib 10 }
 | 
						|
 | 
						|
e3ConcentratorEventLog NOTIFICATION-TYPE
 | 
						|
	OBJECTS		{	e3CtrEventTime,
 | 
						|
					e3CtrEventSeverityLevel,
 | 
						|
					e3CtrEventSource,
 | 
						|
					e3CtrEventDescription }
 | 
						|
	STATUS		current
 | 
						|
	DESCRIPTION
 | 
						|
		"Event detected by the Data Concentrator in a 'log' format.
 | 
						|
		Fields are delimited by the ';' character."
 | 
						|
	::= { e3ConcentratorTraps 1 }
 | 
						|
 | 
						|
END
 |