372 lines
11 KiB
Plaintext
372 lines
11 KiB
Plaintext
ALPHA-RECTIFIER-SYS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
--==========================================================================
|
|
--
|
|
-- Alpha Technologies Ltd.
|
|
-- Copyright 2014
|
|
--
|
|
--==========================================================================
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE
|
|
FROM SNMPv2-SMI
|
|
ScaledNumber, simple
|
|
FROM ALPHA-RESOURCE-MIB
|
|
MODULE-COMPLIANCE, OBJECT-GROUP
|
|
FROM SNMPv2-CONF;
|
|
|
|
rectifierSystem MODULE-IDENTITY
|
|
LAST-UPDATED "201704060000Z"
|
|
ORGANIZATION "Alpha Technologies Ltd."
|
|
CONTACT-INFO
|
|
"Alpha Technologies Ltd.
|
|
7700 Riverfront Gate
|
|
Burnaby, BC V5J 5M4
|
|
Canada
|
|
|
|
Tel: 1-604-436-5900
|
|
Fax: 1-604-436-1233"
|
|
DESCRIPTION
|
|
"This MIB defines the notification block(s) available in system controllers."
|
|
|
|
REVISION "201704060000Z" -- April 4, 2017
|
|
DESCRIPTION
|
|
"
|
|
Added fields for power save and some battery fields.
|
|
Tested with SimpleWeb: http://www.simpleweb.org
|
|
Passed highest level of compliance. (level 6)
|
|
"
|
|
|
|
REVISION "201507280000Z" -- July 28, 2015
|
|
DESCRIPTION
|
|
"
|
|
Updated to follow MIB structure conformance rules. Tested with
|
|
SimpleWeb: http://www.simpleweb.org
|
|
Passed highest level of compliance. (level 6)
|
|
"
|
|
|
|
REVISION "201507230000Z" -- July 23, 2015
|
|
DESCRIPTION
|
|
"Fixed MIB syntax warnings."
|
|
|
|
REVISION "201506230000Z" -- June 23, 2015
|
|
DESCRIPTION
|
|
"General revision."
|
|
|
|
::= { simple 1 }
|
|
|
|
|
|
-- Tectual convention
|
|
|
|
rectSysTotalOutputCurrent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
Total accumulated output current of all the rectifiers associated with the current system.
|
|
"
|
|
::= { rectifierSystem 1 }
|
|
|
|
rectSysTotalOutputPower OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total output current of all system rectifiers."
|
|
::= { rectifierSystem 2 }
|
|
|
|
rectSysTotalCapacityInstalledAmps OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A rectifier output current multiplied by the number of rectifiers installed."
|
|
::= { rectifierSystem 3 }
|
|
|
|
rectSysTotalCapacityInstalledPower OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A rectifier output power multiplied by the number of rectifiers installed."
|
|
::= { rectifierSystem 4 }
|
|
|
|
rectSysAverageRectifierOutputVoltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average rectifier output voltage."
|
|
::= { rectifierSystem 5 }
|
|
|
|
rectSysAverageRectifierACInputVoltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average rectifier input voltage."
|
|
::= { rectifierSystem 6 }
|
|
|
|
rectSysAveragePhase1Voltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average output voltage of rectifiers in Phase 1."
|
|
::= { rectifierSystem 7 }
|
|
|
|
rectSysAveragePhase2Voltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average output voltage of rectifiers in Phase 2."
|
|
::= { rectifierSystem 8 }
|
|
|
|
rectSysAveragePhase3Voltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average output voltage of rectifiers in Phase 3."
|
|
::= { rectifierSystem 9 }
|
|
|
|
rectSysSystemVoltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System voltage."
|
|
::= { rectifierSystem 10 }
|
|
|
|
rectSysTotalLoadCurrent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total load current."
|
|
::= { rectifierSystem 11 }
|
|
|
|
rectSysBatteryVoltage OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery voltage."
|
|
::= { rectifierSystem 12 }
|
|
|
|
rectSysBatteryCurrent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery current."
|
|
::= { rectifierSystem 13 }
|
|
|
|
rectSysBatteryTemperature OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery temperature."
|
|
::= { rectifierSystem 14 }
|
|
|
|
rectSysSystemNumber OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Snmp ID# assigned to the system."
|
|
::= { rectifierSystem 15 }
|
|
|
|
rectSysEstimatedRequiredCapacityInWatts OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated required capacity needed in watts."
|
|
::= { rectifierSystem 16 }
|
|
|
|
rectSysEstimatedRequiredCapacityInAmps OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated required capacity needed in amps."
|
|
::= { rectifierSystem 17 }
|
|
|
|
rectSysEstimatedAvailableCapacityInWatts OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated available capacity needed in watts."
|
|
::= { rectifierSystem 18 }
|
|
|
|
rectSysEstimatedAvailableCapacityInAmps OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated available capacity needed in amps."
|
|
::= { rectifierSystem 19 }
|
|
|
|
rectSysEstimatedRedundantCapacityInWatts OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated redundant capacity needed in watts."
|
|
::= { rectifierSystem 20 }
|
|
|
|
rectSysEstimatedRedundantCapacityInAmps OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated redundant capacity needed in amps."
|
|
::= { rectifierSystem 21 }
|
|
|
|
rectSysEstimatedStandbyCapacityInWatts OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated standby capacity needed in watts."
|
|
::= { rectifierSystem 22 }
|
|
|
|
rectSysEstimatedStandbyCapacityInAmps OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated standby capacity needed in amps."
|
|
::= { rectifierSystem 23 }
|
|
|
|
rectSysPowerAveragePower OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average power of all modules supplying power for Power Save in percentage."
|
|
::= { rectifierSystem 24 }
|
|
|
|
rectSysModulesSupplyingPower OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of modules supplying power."
|
|
::= { rectifierSystem 25 }
|
|
|
|
rectSysModulesInStandby OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of modules in standby."
|
|
::= { rectifierSystem 26 }
|
|
|
|
rectSysEstimatedCapacityRemainingCurrent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated capacity remaining in amps."
|
|
::= { rectifierSystem 28 }
|
|
|
|
rectSysEstimatedCapacityRemainingPower OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated capacity remaining in watts."
|
|
::= { rectifierSystem 29 }
|
|
|
|
rectSysEstimatedSOCPercent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated state of charge percent remaining."
|
|
::= { rectifierSystem 30 }
|
|
|
|
rectSysEstimatedBatteryRuntime OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated battery runtime remaining in hours."
|
|
::= { rectifierSystem 31 }
|
|
|
|
rectSysEstimatedBatteryHealthPercent OBJECT-TYPE
|
|
SYNTAX ScaledNumber
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Estimated battery health percentage."
|
|
::= { rectifierSystem 32 }
|
|
|
|
|
|
-- Conformance
|
|
|
|
conformance OBJECT IDENTIFIER ::= { rectifierSystem 100 }
|
|
|
|
compliances OBJECT IDENTIFIER ::= { conformance 1 }
|
|
|
|
compliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compliance statement for systems supporting
|
|
the alpha MIB."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS {
|
|
rectifierGroup
|
|
}
|
|
::= { compliances 1 }
|
|
|
|
rectifierGroups OBJECT IDENTIFIER ::= { conformance 2 }
|
|
|
|
rectifierGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
rectSysTotalOutputCurrent,
|
|
rectSysTotalOutputPower,
|
|
rectSysTotalCapacityInstalledAmps,
|
|
rectSysTotalCapacityInstalledPower,
|
|
rectSysAverageRectifierOutputVoltage,
|
|
rectSysAverageRectifierACInputVoltage,
|
|
rectSysAveragePhase1Voltage,
|
|
rectSysAveragePhase2Voltage,
|
|
rectSysAveragePhase3Voltage,
|
|
rectSysSystemVoltage,
|
|
rectSysTotalLoadCurrent,
|
|
rectSysBatteryVoltage,
|
|
rectSysBatteryCurrent,
|
|
rectSysBatteryTemperature,
|
|
rectSysSystemNumber,
|
|
rectSysEstimatedRequiredCapacityInWatts,
|
|
rectSysEstimatedRequiredCapacityInAmps,
|
|
rectSysEstimatedAvailableCapacityInWatts,
|
|
rectSysEstimatedAvailableCapacityInAmps,
|
|
rectSysEstimatedRedundantCapacityInWatts,
|
|
rectSysEstimatedRedundantCapacityInAmps,
|
|
rectSysEstimatedStandbyCapacityInWatts,
|
|
rectSysEstimatedStandbyCapacityInAmps,
|
|
rectSysPowerAveragePower,
|
|
rectSysModulesSupplyingPower,
|
|
rectSysModulesInStandby,
|
|
rectSysEstimatedCapacityRemainingCurrent,
|
|
rectSysEstimatedCapacityRemainingPower,
|
|
rectSysEstimatedSOCPercent,
|
|
rectSysEstimatedBatteryRuntime,
|
|
rectSysEstimatedBatteryHealthPercent
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alpha Rectifier System data list group."
|
|
::= { rectifierGroups 1 }
|
|
|
|
|
|
END
|