5011 lines
146 KiB
Plaintext
5011 lines
146 KiB
Plaintext
-- MIB version: 1.1.115
|
|
|
|
-- MIB release note
|
|
-- | date | MIB version | author | note
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 02/11/2015 | 1.1.116 | Zack Huang | Syntax modification of POP modes
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 12/02/2014 | 1.1.115 | Zack Huang | Wording modification
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 10/22/2014 | 1.1.114 | HC Sun | Add get/set function for new POP feature
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 07/28/2014 | 1.1.113 | Zack Huang | Modify and unify responses of empty and not-support measurement values
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 10/31/2013 | 1.1.112 | Zack Huang | updated mib to pass smilint level 3
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 10/03/2013 | 1.1.111 | Jenny Teng | updated mib to pass smilint level 3
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 08/09/2013 | 1.1.110 | Jenny Teng | Add outlet init mode
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 07/17/2013 | 1.1.109 | Zack Huang | Add CAP Priority Settings
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 07/05/2013 | 1.1.108 | Jenny Teng | Add Description and change some Syntax of oids
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 05/23/2013 | 1.1.107 | Carter Wu | Change "usrEnable" order from 40 to 47 in "UsrListEntry"
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 05/21/2013 | 1.1.106 | Carter Wu | Hide CAP function
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 05/14/2013 | 1.1.105 | Carter Wu | Modify Power Threshold Description
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 05/07/2013 | 1.1.104 | Carter Wu | Add CAP Function OID
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 04/26/2013 | 1.1.103 | Zack Huang | Add Door Sensor Type OID
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 04/24/2013 | 1.1.102 | Zack Huang | Modify Status Description of Door Sensor
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 02/20/2013 | 1.1.101 | Zack Huang |
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 02/17/2012 | | Jenny Teng |
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
-- | 03/29/2010 | | Zack Yang | Initiative Version
|
|
-- --------------------------------------------------------------------------------------------------------------------------
|
|
|
|
-- ATEN International Co., Ltd.
|
|
-- This file defines the mib struct of Management in PE series
|
|
-- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe subtree
|
|
|
|
-- RENAMED TO AVOID CONFLICTS
|
|
ATEN-PE-CFG-STR DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
|
|
enterprises FROM RFC1155-SMI
|
|
DisplayString FROM RFC1213-MIB
|
|
OBJECT-TYPE FROM RFC-1212
|
|
TRAP-TYPE FROM RFC-1215
|
|
MODULE-IDENTITY,
|
|
NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
KeyChange FROM SNMP-USER-BASED-SM-MIB
|
|
TEXTUAL-CONVENTION FROM SNMPv2-TC;
|
|
|
|
|
|
|
|
aten MODULE-IDENTITY
|
|
LAST-UPDATED "201310311110Z"
|
|
ORGANIZATION "ATEN"
|
|
CONTACT-INFO "Aten, Inc."
|
|
DESCRIPTION
|
|
"ATEN PE MIB"
|
|
REVISION "201310311110Z"
|
|
DESCRIPTION
|
|
"updated mib to pass smilint level 3"
|
|
::= { enterprises 21317 }
|
|
|
|
|
|
atenProducts OBJECT IDENTIFIER ::= { aten 1 }
|
|
overip OBJECT IDENTIFIER ::= { atenProducts 3 }
|
|
poweroverip OBJECT IDENTIFIER ::= { overip 2}
|
|
pe OBJECT IDENTIFIER ::= {poweroverip 2}
|
|
userManagement OBJECT IDENTIFIER ::= { pe 1 }
|
|
control OBJECT IDENTIFIER ::= { pe 2 }
|
|
device OBJECT IDENTIFIER ::= { control 1 }
|
|
doorSensor OBJECT IDENTIFIER ::= { device 16 }
|
|
pop OBJECT IDENTIFIER ::= { device 17 }
|
|
cap OBJECT IDENTIFIER ::= { device 18 }
|
|
outlet OBJECT IDENTIFIER ::= { control 2 }
|
|
bank OBJECT IDENTIFIER ::= { control 3 }
|
|
deviceManagement OBJECT IDENTIFIER ::= { pe 3 }
|
|
config OBJECT IDENTIFIER ::= { deviceManagement 4 }
|
|
dashBoard OBJECT IDENTIFIER ::= { config 4 }
|
|
servicePorts OBJECT IDENTIFIER ::= { config 5 }
|
|
ipv4config OBJECT IDENTIFIER ::= { config 6 }
|
|
eventNotification OBJECT IDENTIFIER ::= { config 7 }
|
|
devicesnmp OBJECT IDENTIFIER ::= { eventNotification 1 }
|
|
syslog OBJECT IDENTIFIER ::= { eventNotification 2 }
|
|
smtp OBJECT IDENTIFIER ::= { eventNotification 3 }
|
|
configurationNotification OBJECT IDENTIFIER ::= { eventNotification 9 }
|
|
|
|
|
|
dateTime OBJECT IDENTIFIER ::= { config 8 }
|
|
timeZone OBJECT IDENTIFIER ::= { dateTime 1 }
|
|
manualInput OBJECT IDENTIFIER ::= { dateTime 2 }
|
|
networkTime OBJECT IDENTIFIER ::= { dateTime 3 }
|
|
|
|
devicesecurity OBJECT IDENTIFIER ::= { deviceManagement 5 }
|
|
loginFailures OBJECT IDENTIFIER ::= { devicesecurity 1 }
|
|
workingMode OBJECT IDENTIFIER ::= { devicesecurity 2 }
|
|
accountPolicy OBJECT IDENTIFIER ::= { devicesecurity 3 }
|
|
loginRestriction OBJECT IDENTIFIER ::= { devicesecurity 4 }
|
|
ipFilter OBJECT IDENTIFIER ::= { loginRestriction 2 }
|
|
macFilter OBJECT IDENTIFIER ::= { loginRestriction 3 }
|
|
authentication OBJECT IDENTIFIER ::= { devicesecurity 5 }
|
|
radius OBJECT IDENTIFIER ::= { authentication 1 }
|
|
--CPM OBJECT IDENTIFIER ::= { pe 7 }
|
|
-- CPMDevice OBJECT IDENTIFIER ::= { CPM 9 }
|
|
-- Sensor OBJECT IDENTIFIER ::= { CPM 10 }
|
|
-- EnergySensor OBJECT IDENTIFIER ::= { CPM 11 }
|
|
|
|
|
|
--SNMPv3UsmAuthPrivProtocol ::= TEXTUAL-CONVENTION
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "This textual convention enumerates the authentication and privledge
|
|
-- protocol for USM configuration.
|
|
-- "
|
|
-- SYNTAX INTEGER
|
|
-- {
|
|
-- hmacMD5Auth(2),
|
|
-- hmacSHAAuth(3)
|
|
-- desPrivProtocol(5),
|
|
-- aesPrivProtocol(6)
|
|
-- }
|
|
|
|
-- Device Control
|
|
modelName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicate PE device model name."
|
|
::= { device 1 }
|
|
|
|
deviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of PE device.
|
|
string length: 1~39
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { device 2 }
|
|
|
|
deviceValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DeviceValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device value table. This table displays device's current, voltage, power and
|
|
power dissipation.
|
|
"
|
|
::= { device 3 }
|
|
|
|
deviceValueEntry OBJECT-TYPE
|
|
SYNTAX DeviceValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single deviceValue entry containing device info."
|
|
INDEX { deviceValueIndex }
|
|
::= { deviceValueTable 1 }
|
|
|
|
DeviceValueEntry ::=
|
|
SEQUENCE {
|
|
deviceValueIndex
|
|
INTEGER,
|
|
deviceCurrent
|
|
DisplayString,
|
|
deviceVoltage
|
|
DisplayString,
|
|
devicePower
|
|
DisplayString,
|
|
devicePowerDissipation
|
|
DisplayString,
|
|
inputMaxVoltage
|
|
INTEGER,
|
|
inputMaxCurrent
|
|
INTEGER,
|
|
powerCapacity
|
|
INTEGER,
|
|
devicePowerFactor
|
|
DisplayString
|
|
}
|
|
|
|
deviceValueIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of deviceValue."
|
|
::= { deviceValueEntry 1 }
|
|
deviceCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device electric current value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { deviceValueEntry 2 }
|
|
deviceVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device voltage value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { deviceValueEntry 3 }
|
|
devicePower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device power value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { deviceValueEntry 4 }
|
|
|
|
devicePowerDissipation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device power dissipation value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { deviceValueEntry 5 }
|
|
|
|
inputMaxVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device input Voltage value. unit:(V)
|
|
If the device does not support this OID, we show value 0.
|
|
"
|
|
::= { deviceValueEntry 6 }
|
|
|
|
inputMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device input Current value. unit:(A)
|
|
If the device does not support this OID, we show value 0."
|
|
::= { deviceValueEntry 7 }
|
|
|
|
powerCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device power Capacity value.unit:(VA)
|
|
If the device does not support this OID, we show value 0."
|
|
::= { deviceValueEntry 8 }
|
|
|
|
devicePowerFactor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device power Factor value.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { deviceValueEntry 9 }
|
|
|
|
sensorValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SensorValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device's sensor value table. This table displays sensor's temperature, humidity and
|
|
pressure.
|
|
"
|
|
::= { device 4 }
|
|
|
|
sensorValueEntry OBJECT-TYPE
|
|
SYNTAX SensorValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single device's sensor value entry containing device info."
|
|
INDEX { sensorValueIndex }
|
|
::= { sensorValueTable 1 }
|
|
|
|
SensorValueEntry ::=
|
|
SEQUENCE {
|
|
sensorValueIndex
|
|
INTEGER,
|
|
sensorTemperature
|
|
DisplayString,
|
|
sensorHumidity
|
|
DisplayString,
|
|
sensorPressure
|
|
DisplayString,
|
|
sensorProperty
|
|
INTEGER
|
|
}
|
|
|
|
sensorValueIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of sensor number."
|
|
::= { sensorValueEntry 1 }
|
|
sensorTemperature OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor's Temperature value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { sensorValueEntry 2 }
|
|
sensorHumidity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor's Humidity value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { sensorValueEntry 3 }
|
|
sensorPressure OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor's Pressure value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { sensorValueEntry 4 }
|
|
|
|
sensorProperty OBJECT-TYPE
|
|
SYNTAX INTEGER { intake(1), exhaust(2), floor(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor's Property."
|
|
::= { sensorValueEntry 5 }
|
|
|
|
deviceOutletStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DeviceOutletStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device outlet status value table."
|
|
::= { device 5 }
|
|
|
|
deviceOutletStatusEntry OBJECT-TYPE
|
|
SYNTAX DeviceOutletStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single deviceOutletStatus entry containing device info."
|
|
INDEX { deviceOutletStatusIndex }
|
|
::= { deviceOutletStatusTable 1 }
|
|
|
|
DeviceOutletStatusEntry ::=
|
|
SEQUENCE {
|
|
deviceOutletStatusIndex
|
|
INTEGER,
|
|
displayOutletStatus
|
|
INTEGER
|
|
--deviceOutletControl
|
|
--INTEGER,
|
|
--deviceOutletReboot
|
|
-- INTEGER
|
|
|
|
}
|
|
|
|
deviceOutletStatusIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of deviceOutletStatus"
|
|
::= { deviceOutletStatusEntry 1 }
|
|
displayOutletStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), fault(4), noauth(5), not-support(6), pop(7) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display outlet status."
|
|
::= { deviceOutletStatusEntry 2 }
|
|
|
|
|
|
deviceConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DeviceConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device configuration table"
|
|
::= { device 6 }
|
|
|
|
deviceConfigEntry OBJECT-TYPE
|
|
SYNTAX DeviceConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single deviceConfig entry containing device info."
|
|
INDEX { deviceConfigIndex }
|
|
::= { deviceConfigTable 1 }
|
|
|
|
DeviceConfigEntry ::=
|
|
SEQUENCE {
|
|
deviceConfigIndex
|
|
INTEGER,
|
|
deviceMinCurMT
|
|
INTEGER,
|
|
deviceMaxCurMT
|
|
INTEGER,
|
|
|
|
deviceMinVolMT
|
|
INTEGER,
|
|
deviceMaxVolMT
|
|
INTEGER,
|
|
deviceMinPMT
|
|
INTEGER,
|
|
deviceMaxPMT
|
|
INTEGER,
|
|
|
|
--deviceMinPDMT
|
|
--INTEGER,
|
|
deviceMaxPDMT
|
|
INTEGER
|
|
--deviceCurFlu
|
|
-- INTEGER,
|
|
--deviceVolFlu
|
|
-- INTEGER,
|
|
--devicePFlu
|
|
-- INTEGER
|
|
--devicePDFlu
|
|
--INTEGER
|
|
}
|
|
|
|
deviceConfigIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of deviceConfig"
|
|
::= { deviceConfigEntry 1 }
|
|
deviceMinCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device minimum electric current measurement threshold.
|
|
Example: range 0.0~32.0 represents 0~320.
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 2 }
|
|
deviceMaxCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device maximum electric current measurement threshold.
|
|
Example: range 0.0~32.0 represents 0~320
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 3 }
|
|
|
|
deviceMinVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device minimum voltage measurement threshold.
|
|
Exapmple: range 90.0~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 4 }
|
|
|
|
deviceMaxVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device maximum voltage measurement threshold.
|
|
Example: range 90.0~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 5 }
|
|
|
|
deviceMinPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device minimum power measurement threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 6 }
|
|
|
|
deviceMaxPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device maximum power measurement threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 7 }
|
|
|
|
--deviceCurFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display device electric current fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceConfigEntry 9 }
|
|
|
|
--deviceVolFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display device voltage fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceConfigEntry 10 }
|
|
|
|
--devicePFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display device power fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceConfigEntry 11 }
|
|
|
|
--deviceMinPDMT OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..2000)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set device minimum power dissipation measurement threshold."
|
|
--::= { deviceConfigEntry 8 }
|
|
deviceMaxPDMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999990 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device maximum power dissipation measurement threshold.
|
|
Example: range 0.0 ~ 99999.0 represents 0~999990
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceConfigEntry 8 }
|
|
--devicePDFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..2000)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display device power dissipation fluctuation threshold."
|
|
--::= { deviceConfigEntry 13 }
|
|
|
|
|
|
deviceSensorTresholdTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DeviceSensorTresholdEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device environment value table"
|
|
::= { device 7 }
|
|
|
|
deviceSensorTresholdEntry OBJECT-TYPE
|
|
SYNTAX DeviceSensorTresholdEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device's sensor Environment entry containing sensor info."
|
|
INDEX { deviceSensorTresholdIndex }
|
|
::= { deviceSensorTresholdTable 1 }
|
|
|
|
DeviceSensorTresholdEntry ::=
|
|
SEQUENCE {
|
|
deviceSensorTresholdIndex
|
|
INTEGER,
|
|
sensorMinTempMT
|
|
INTEGER,
|
|
sensorMaxTempMT
|
|
INTEGER,
|
|
|
|
sensorMinHumMT
|
|
INTEGER,
|
|
sensorMaxHumMT
|
|
INTEGER,
|
|
sensorMinPressMT
|
|
INTEGER,
|
|
sensorMaxPressMT
|
|
INTEGER
|
|
--sensorTempFlu
|
|
--INTEGER,
|
|
--sensorHumFlu
|
|
--INTEGER,
|
|
--sensorPressFlu
|
|
--INTEGER
|
|
}
|
|
|
|
deviceSensorTresholdIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of sensor number"
|
|
::= { deviceSensorTresholdEntry 1 }
|
|
|
|
sensorMinTempMT OBJECT-TYPE
|
|
SYNTAX INTEGER (-200..600 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor minimum temperature measurement threshold.
|
|
Example: range -20.0 ~ 60.0 represents -200~600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 2 }
|
|
sensorMaxTempMT OBJECT-TYPE
|
|
SYNTAX INTEGER (-200..600 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor maximum temperature measurement threshold.
|
|
Example: range -20.0 ~ 60.0 represents -200~600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 3 }
|
|
|
|
sensorMinHumMT OBJECT-TYPE
|
|
SYNTAX INTEGER (150..950 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor minimum humidity measurement threshold.
|
|
Example: range 15.0 ~ 95.0 represents 150~950
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 4 }
|
|
sensorMaxHumMT OBJECT-TYPE
|
|
SYNTAX INTEGER (150..950 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor maximum humidity measurement threshold.
|
|
Example: range 15.0 ~ 95.0 represents 150~950
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 5 }
|
|
|
|
sensorMinPressMT OBJECT-TYPE
|
|
SYNTAX INTEGER (-2500..2500 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor minimum pressure measurement threshold.
|
|
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 6 }
|
|
|
|
sensorMaxPressMT OBJECT-TYPE
|
|
SYNTAX INTEGER (-2500..2500 | -3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set sensor maximum pressure measurement threshold.
|
|
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { deviceSensorTresholdEntry 7 }
|
|
|
|
--sensorTempFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display sensor temperature fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceEnvironmentEntry 8 }
|
|
|
|
--sensorHumFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display sensor humidity fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceEnvironmentEntry 9 }
|
|
|
|
|
|
--sensorPressFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display sensor pressure fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { deviceEnvironmentEntry 10 }
|
|
|
|
deviceOutletControl OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), nostatus(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This function is used for all outlet ports control.
|
|
Set off(1) to turn off for all outlet ports.
|
|
Set on(2) to turn on for all outlet ports.
|
|
Get this object always return nostatus(3), because there is no device status.
|
|
|
|
"
|
|
::= { device 8 }
|
|
|
|
deviceOutletReboot OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This function is used for all outlet ports to reboot.
|
|
Only when outlet status is ON can do outlet reboot action to all ports.
|
|
Set yes(2) to reboot all outlet ports.
|
|
Get this object always return no(1).
|
|
"
|
|
::= { device 9 }
|
|
|
|
switchable OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2), mix(3)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Outlet is switchable or not."
|
|
::= { device 10 }
|
|
|
|
perportreading OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Outlet is per-port reading or not."
|
|
::= { device 11 }
|
|
|
|
sensornumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Sensor number."
|
|
::= { device 12 }
|
|
|
|
outletnumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Outlet number."
|
|
::= { device 13 }
|
|
|
|
banknumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Bank number."
|
|
::= { device 14 }
|
|
|
|
--chainnumber OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-only
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- " The slave device number."
|
|
--::= { device 15 }
|
|
|
|
doorSensorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { close(0), open(1), not-attached(2), not-support(4) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Display door sensor status.
|
|
close(0) represents door close.
|
|
open(1) represents door open.
|
|
not-attached(2) represents door sensor don't attach to device."
|
|
::= { doorSensor 1 }
|
|
|
|
doorSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER { notinstalled(0), photo(1), inductiveproximity(2), reed(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door Sensor Type Selection"
|
|
::= { doorSensor 2 }
|
|
--
|
|
-- pop
|
|
enablePOPmode OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable/Disable POP mode."
|
|
::= { pop 1 }
|
|
|
|
popThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" (-1)means default value same as Bank Max Current 16 A.
|
|
|
|
Example: range 0.0~32.0 represents 0~320
|
|
You can define the POP threshold or set as default(-1) value."
|
|
::= { pop 2 }
|
|
|
|
enableOutletPOPmode OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2), not-support(3)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable/Disable Outlet POP mode."
|
|
::= { pop 3 }
|
|
|
|
enableLIFOPOPmode OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2), not-support(3)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable/Disable LIFO POP mode."
|
|
::= { pop 4 }
|
|
|
|
enablePriorityPOPmode OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2), not-support(3)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable/Disable Priority POP mode."
|
|
::= { pop 5 }
|
|
|
|
-- CAP
|
|
enableCAPmode OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable/Disable CAP mode."
|
|
::= { cap 1 }
|
|
|
|
outletCAPTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletCAPEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet CAP table"
|
|
::= { cap 2 }
|
|
|
|
outletCAPEntry OBJECT-TYPE
|
|
SYNTAX OutletCAPEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet CAP entry containing CAP info."
|
|
INDEX { outletCAPIndex }
|
|
::= { outletCAPTable 1 }
|
|
|
|
OutletCAPEntry ::=
|
|
SEQUENCE {
|
|
outletCAPIndex
|
|
INTEGER,
|
|
outletCAPPriority
|
|
INTEGER
|
|
}
|
|
|
|
outletCAPIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..40)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of outlet's CAP configuration"
|
|
::= { outletCAPEntry 1 }
|
|
|
|
outletCAPPriority OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the CAP Priority of outlet.
|
|
Priority 0 means this outlet does not support this OID."
|
|
::= { outletCAPEntry 2 }
|
|
-- ontlet control init mode
|
|
|
|
outletInitMode OBJECT-TYPE
|
|
SYNTAX INTEGER {no-delaytime(1), delaytime(2), not-support(3)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"choose outlet init mode you want."
|
|
::= { device 19 }
|
|
|
|
|
|
|
|
-- integer value
|
|
|
|
--deviceIntegerValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF DeviceIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device value table. This table displays device's current, voltage, power and
|
|
-- power dissipation.
|
|
-- "
|
|
-- ::= { device 99 }
|
|
|
|
--deviceIntegerValueEntry OBJECT-TYPE
|
|
-- SYNTAX DeviceIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single deviceValue entry containing device info."
|
|
-- INDEX { deviceIntegerValueIndex }
|
|
-- ::= { deviceIntegerValueTable 1 }
|
|
|
|
--DeviceIntegerValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- deviceIntegerValueIndex
|
|
-- INTEGER,
|
|
-- deviceIntegerCurrent
|
|
-- INTEGER,
|
|
-- deviceIntegerVoltage
|
|
-- INTEGER,
|
|
-- deviceIntegerPower
|
|
-- INTEGER,
|
|
-- deviceIntegerPowerDissipation
|
|
-- INTEGER
|
|
--inputMaxVoltage
|
|
-- INTEGER,
|
|
--inputMaxCurrent
|
|
-- INTEGER,
|
|
--powerCapacity
|
|
-- INTEGER
|
|
--devicePowerFactor
|
|
-- INTEGER
|
|
-- }
|
|
|
|
--deviceIntegerValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1)
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of deviceValue."
|
|
-- ::= { deviceIntegerValueEntry 1 }
|
|
|
|
--deviceIntegerCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device electric current value.
|
|
-- This value indicates that 1,000 times.
|
|
-- "
|
|
-- ::= { deviceIntegerValueEntry 2 }
|
|
|
|
--deviceIntegerVoltage OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device voltage value.
|
|
-- This value indicates that 1,000 times
|
|
-- "
|
|
-- ::= { deviceIntegerValueEntry 3 }
|
|
|
|
--deviceIntegerPower OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power value.
|
|
-- This value indicates that 1,000 times.
|
|
-- "
|
|
-- ::= { deviceIntegerValueEntry 4 }
|
|
|
|
--deviceIntegerPowerDissipation OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power dissipation value.
|
|
-- This value indicates that 1,000 times
|
|
-- "
|
|
-- ::= { deviceIntegerValueEntry 5 }
|
|
|
|
--inputMaxVoltage OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device input Voltage value. unit:(V)"
|
|
-- ::= { deviceValueEntry 6 }
|
|
|
|
--inputMaxCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device input Current value. unit:(A)"
|
|
-- ::= { deviceValueEntry 7 }
|
|
|
|
--powerCapacity OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power Capacity value.unit:(VA)"
|
|
-- ::= { deviceValueEntry 8 }
|
|
|
|
--devicePowerFactor OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power Factor value."
|
|
-- ::= { deviceValueEntry 9 }
|
|
--
|
|
|
|
--sensorIntegerValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF SensorIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device's sensor value table. This table displays sensor's temperature, humidity and
|
|
-- pressure.
|
|
-- "
|
|
-- ::= { device 100 }
|
|
|
|
--sensorIntegerValueEntry OBJECT-TYPE
|
|
-- SYNTAX SensorIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single device's sensor value entry containing device info."
|
|
-- INDEX { sensorIntegerValueIndex }
|
|
-- ::= { sensorIntegerValueTable 1 }
|
|
|
|
--SensorIntegerValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- sensorIntegerValueIndex
|
|
-- INTEGER,
|
|
-- sensorIntegerTemperature
|
|
-- INTEGER,
|
|
-- sensorIntegerHumidity
|
|
-- INTEGER,
|
|
-- sensorIntegerPressure
|
|
-- INTEGER
|
|
--sensorIntegerProperty
|
|
-- INTEGER
|
|
-- }
|
|
|
|
--sensorIntegerValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..6)
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of sensor number."
|
|
-- ::= { sensorIntegerValueEntry 1 }
|
|
|
|
--sensorIntegerTemperature OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Sensor's Temperature value.
|
|
-- This value indicates that 1,000 times.
|
|
-- Value -300000 represents empty value."
|
|
-- ::= { sensorIntegerValueEntry 2 }
|
|
|
|
--sensorIntegerHumidity OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Sensor's Humidity value.
|
|
-- This value indicates that 1,000 times.
|
|
-- Value -300000 represents empty value."
|
|
-- ::= { sensorIntegerValueEntry 3 }
|
|
|
|
--sensorIntegerPressure OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Sensor's Pressure value.
|
|
-- This value indicates that 1,000 times.
|
|
-- Value -300000 represents empty value."
|
|
-- ::= { sensorIntegerValueEntry 4 }
|
|
|
|
--sensorIntegerProperty OBJECT-TYPE
|
|
-- SYNTAX INTEGER { intake(1), exhaust(2), floor(3) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Sensor's Property."
|
|
-- ::= { sensorIntegerValueEntry 5 }
|
|
|
|
-- Device Control End
|
|
|
|
-- Outlet Control
|
|
outletValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display total outlet value table"
|
|
::= { outlet 1 }
|
|
|
|
outletValueEntry OBJECT-TYPE
|
|
SYNTAX OutletValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single outletValue entry containing outlet info."
|
|
INDEX { outletValueIndex }
|
|
::= { outletValueTable 1 }
|
|
|
|
OutletValueEntry ::=
|
|
SEQUENCE {
|
|
outletValueIndex
|
|
INTEGER,
|
|
outletCurrent
|
|
DisplayString,
|
|
outletVoltage
|
|
DisplayString,
|
|
outletPower
|
|
DisplayString,
|
|
outletPowerDissipation
|
|
DisplayString,
|
|
outletMaxCurrent
|
|
INTEGER,
|
|
outletPowerFactor
|
|
DisplayString
|
|
}
|
|
|
|
outletValueIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of outlet number"
|
|
::= { outletValueEntry 1 }
|
|
outletCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet electric current value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { outletValueEntry 2 }
|
|
outletVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet voltage value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { outletValueEntry 3 }
|
|
outletPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet power value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { outletValueEntry 4 }
|
|
outletPowerDissipation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet power dissipation value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { outletValueEntry 5 }
|
|
|
|
outletMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Max Current value. unit: (A).
|
|
If the device does not support this OID, we show value 0.
|
|
"
|
|
::= { outletValueEntry 6 }
|
|
|
|
outletPowerFactor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Power Factor value.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { outletValueEntry 7 }
|
|
|
|
outlet1Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 1 status. Can't set pending status."
|
|
::= { outlet 2 }
|
|
|
|
outlet2Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 2 status. Can't set pending status."
|
|
::= { outlet 3 }
|
|
outlet3Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 3 status. Can't set pending status."
|
|
::= { outlet 4 }
|
|
outlet4Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 4 status. Can't set pending status."
|
|
::= { outlet 5 }
|
|
outlet5Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 5 status. Can't set pending status."
|
|
::= { outlet 6 }
|
|
outlet6Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 6 status. Can't set pending status."
|
|
::= { outlet 7 }
|
|
outlet7Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 7 status. Can't set pending status."
|
|
::= { outlet 8 }
|
|
outlet8Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 8 status. Can't set pending status."
|
|
::= { outlet 9 }
|
|
|
|
outlet9Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 9 status. Can't set pending status."
|
|
::= { outlet 11 }
|
|
|
|
outlet10Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 10 status. Can't set pending status."
|
|
::= { outlet 12 }
|
|
|
|
outlet11Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 11 status. Can't set pending status."
|
|
::= { outlet 13 }
|
|
|
|
outlet12Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 12 status. Can't set pending status."
|
|
::= { outlet 14 }
|
|
|
|
outlet13Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 13 status. Can't set pending status."
|
|
::= { outlet 15 }
|
|
|
|
outlet14Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 14 status. Can't set pending status."
|
|
::= { outlet 16 }
|
|
|
|
outlet15Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 15 status. Can't set pending status."
|
|
::= { outlet 17 }
|
|
|
|
outlet16Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 16 status. Can't set pending status."
|
|
::= { outlet 18 }
|
|
|
|
outlet17Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 17 status. Can't set pending status."
|
|
::= { outlet 19 }
|
|
|
|
outlet18Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 18 status. Can't set pending status."
|
|
::= { outlet 20 }
|
|
|
|
outlet19Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 19 status. Can't set pending status."
|
|
::= { outlet 21 }
|
|
|
|
outlet20Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 20 status. Can't set pending status."
|
|
::= { outlet 22 }
|
|
|
|
outlet21Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 21 status. Can't set pending status."
|
|
::= { outlet 23 }
|
|
|
|
outlet22Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 22 status. Can't set pending status."
|
|
::= { outlet 24 }
|
|
|
|
outlet23Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 23 status. Can't set pending status."
|
|
::= { outlet 25 }
|
|
|
|
outlet24Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 24 status. Can't set pending status."
|
|
::= { outlet 26 }
|
|
|
|
outlet25Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 25 status. Can't set pending status."
|
|
::= { outlet 27 }
|
|
|
|
outlet26Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 26 status. Can't set pending status."
|
|
::= { outlet 28 }
|
|
|
|
outlet27Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 27 status. Can't set pending status."
|
|
::= { outlet 29 }
|
|
|
|
outlet28Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 28 status. Can't set pending status."
|
|
::= { outlet 30 }
|
|
|
|
outlet29Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 29 status. Can't set pending status."
|
|
::= { outlet 31 }
|
|
|
|
outlet30Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 30 status. Can't set pending status."
|
|
::= { outlet 32 }
|
|
|
|
outlet31Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 31 status. Can't set pending status."
|
|
::= { outlet 33 }
|
|
|
|
outlet32Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 32 status. Can't set pending status."
|
|
::= { outlet 34 }
|
|
|
|
outlet33Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 33 status. Can't set pending status."
|
|
::= { outlet 35 }
|
|
|
|
|
|
outlet34Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 34 status. Can't set pending status."
|
|
::= { outlet 36 }
|
|
|
|
outlet35Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 35 status. Can't set pending status."
|
|
::= { outlet 37 }
|
|
|
|
outlet36Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 36 status. Can't set pending status."
|
|
::= { outlet 38 }
|
|
|
|
outlet37Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 37 status. Can't set pending status."
|
|
::= { outlet 39 }
|
|
|
|
outlet38Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 38 status. Can't set pending status."
|
|
::= { outlet 40 }
|
|
|
|
outlet39Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 39 status. Can't set pending status."
|
|
::= { outlet 41 }
|
|
|
|
outlet40Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 40 status. Can't set pending status."
|
|
::= { outlet 42 }
|
|
|
|
outlet41Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 41 status. Can't set pending status."
|
|
::= { outlet 43 }
|
|
|
|
outlet42Status OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display and control outlet 42 status. Can't set pending status."
|
|
::= { outlet 44 }
|
|
|
|
--
|
|
|
|
outletSwitchableTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletSwitchableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { outlet 70 }
|
|
|
|
outletSwitchableEntry OBJECT-TYPE
|
|
SYNTAX OutletSwitchableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
""
|
|
INDEX { outletSwitchableIndex }
|
|
::= { outletSwitchableTable 1 }
|
|
|
|
OutletSwitchableEntry ::=
|
|
SEQUENCE {
|
|
outletSwitchableIndex
|
|
INTEGER,
|
|
outletSwitchable
|
|
INTEGER
|
|
|
|
}
|
|
|
|
outletSwitchableIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of outlet number.
|
|
"
|
|
::= { outletSwitchableEntry 1 }
|
|
|
|
outletSwitchable OBJECT-TYPE
|
|
SYNTAX INTEGER {no(1), yes(2) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { outletSwitchableEntry 2 }
|
|
|
|
|
|
--outlet integer value
|
|
|
|
--outletIntegerValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF OutletIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display total outlet value table"
|
|
-- ::= { outlet 99 }
|
|
|
|
--outletIntegerValueEntry OBJECT-TYPE
|
|
-- SYNTAX OutletIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single outletValue entry containing outlet info."
|
|
-- INDEX { outletIntegerValueIndex }
|
|
-- ::= { outletIntegerValueTable 1 }
|
|
|
|
--OutletIntegerValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- outletIntegerValueIndex
|
|
-- INTEGER,
|
|
-- outletIntegerCurrent
|
|
-- INTEGER,
|
|
-- outletIntegerVoltage
|
|
-- INTEGER,
|
|
-- outletIntegerPower
|
|
-- INTEGER,
|
|
-- outletIntegerPowerDissipation
|
|
-- INTEGER
|
|
-- }
|
|
|
|
--outletIntegerValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..30)
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of outlet number.
|
|
-- "
|
|
-- ::= { outletIntegerValueEntry 1 }
|
|
|
|
--outletIntegerCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Outlet electric current value.
|
|
-- This value indicates that 1,000 times.
|
|
-- "
|
|
-- ::= { outletIntegerValueEntry 2 }
|
|
|
|
--outletIntegerVoltage OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Outlet voltage value.
|
|
-- This value indicates that 1,000 times.
|
|
-- "
|
|
-- ::= { outletIntegerValueEntry 3 }
|
|
|
|
--outletIntegerPower OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Outlet power value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { outletIntegerValueEntry 4 }
|
|
|
|
--outletIntegerPowerDissipation OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Outlet power dissipation value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { outletIntegerValueEntry 5 }
|
|
|
|
|
|
|
|
|
|
|
|
outletConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet configuration table"
|
|
::= { outlet 10 }
|
|
|
|
outletConfigEntry OBJECT-TYPE
|
|
SYNTAX OutletConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Config entry containing outlet info."
|
|
INDEX { outletConfigIndex }
|
|
::= { outletConfigTable 1 }
|
|
|
|
OutletConfigEntry ::=
|
|
SEQUENCE {
|
|
outletConfigIndex
|
|
INTEGER,
|
|
outletName
|
|
DisplayString,
|
|
outletConfirmation
|
|
INTEGER,
|
|
outletOnDelayTime
|
|
INTEGER,
|
|
outletOffDelayTime
|
|
INTEGER,
|
|
outletShutdownMethod
|
|
INTEGER,
|
|
outletMAC
|
|
DisplayString,
|
|
outletMinCurMT
|
|
INTEGER,
|
|
outletMaxCurMT
|
|
INTEGER,
|
|
|
|
outletMinVolMT
|
|
INTEGER,
|
|
outletMaxVolMT
|
|
INTEGER,
|
|
|
|
outletMinPMT
|
|
INTEGER,
|
|
outletMaxPMT
|
|
INTEGER,
|
|
--outletMinPDMT
|
|
--INTEGER,
|
|
outletMaxPDMT
|
|
INTEGER
|
|
--outletCurFlu
|
|
--INTEGER,
|
|
--outletVolFlu
|
|
--INTEGER,
|
|
--outletPFlu
|
|
--INTEGER
|
|
--outletPDFlu
|
|
--INTEGER
|
|
}
|
|
|
|
outletConfigIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of outlet number"
|
|
::= { outletConfigEntry 1 }
|
|
outletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the name of outlet.
|
|
If the device does not support this OID, we show n/a.
|
|
string length: 0~15
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { outletConfigEntry 2 }
|
|
outletConfirmation OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) , noauth(3), not-support(4)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the confirmation of outlet."
|
|
::= { outletConfigEntry 3 }
|
|
outletOnDelayTime OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999 | -1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the ON delay time of outlet.
|
|
When this model does not support the OID, we show value -1. "
|
|
::= { outletConfigEntry 4 }
|
|
outletOffDelayTime OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999 | -1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the OFF delay time of outlet.
|
|
When this model does not support the OID, we show value -1. "
|
|
::= { outletConfigEntry 5 }
|
|
outletShutdownMethod OBJECT-TYPE
|
|
SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the shutdown mehtod of outlet."
|
|
::= { outletConfigEntry 6 }
|
|
outletMAC OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the MAC address of ShutdownMethod.
|
|
If the device does not support this OID, we show n/a.
|
|
string length: 12
|
|
"
|
|
::= { outletConfigEntry 7 }
|
|
outletMinCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum electric current measurment threshold.
|
|
Example: range 0.0 ~16.0 rerpresnts 0~160
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 8 }
|
|
outletMaxCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum electric current measurment threshold.
|
|
Example: range 0.0 ~16.0 represents 0~160
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 9 }
|
|
|
|
outletMinVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum voltage measurment threshold.
|
|
Example: range 90.0 ~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 10 }
|
|
outletMaxVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum voltage measurment threshold.
|
|
Example: range 90.0 ~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 11 }
|
|
|
|
outletMinPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum power measurment threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 12 }
|
|
outletMaxPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum power measurment threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 13 }
|
|
|
|
--outletMinPDMT OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..100)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the outlet minimum power dissipation measurment threshold ."
|
|
--::= { outletConfigEntry 14 }
|
|
outletMaxPDMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999990 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum power dissipation measurment threshold.
|
|
Example: range 0.0 ~ 99999.0 represents 0~999990
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { outletConfigEntry 14 }
|
|
|
|
--outletCurFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display the outlet electric current fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { outletConfigEntry 15 }
|
|
|
|
--outletVolFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display the outlet voltage fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { outletConfigEntry 16 }
|
|
--outletPFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display the outlet power fluctuation threshold.
|
|
-- Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { outletConfigEntry 17 }
|
|
|
|
--outletPDFlu OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..100)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display the outlet power dissipation fluctuation threshold ."
|
|
--::= { outletConfigEntry 19 }
|
|
|
|
-- Outlet Control End
|
|
-- Bank control
|
|
breakerStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BreakerStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display total bank value table"
|
|
::= { bank 1 }
|
|
|
|
breakerStatusEntry OBJECT-TYPE
|
|
SYNTAX BreakerStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single bankValue entry containing bank info."
|
|
INDEX { breakerStatusIndex }
|
|
::= { breakerStatusTable 1 }
|
|
|
|
BreakerStatusEntry ::=
|
|
SEQUENCE {
|
|
breakerStatusIndex
|
|
INTEGER,
|
|
breakerStatus
|
|
INTEGER
|
|
}
|
|
|
|
breakerStatusIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of breaker number."
|
|
::= { breakerStatusEntry 1 }
|
|
|
|
breakerStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { off(1), on(2), not-support(3)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Breaker status."
|
|
::= { breakerStatusEntry 2 }
|
|
|
|
|
|
bankValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BankValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display total bank value table"
|
|
::= { bank 2 }
|
|
|
|
bankValueEntry OBJECT-TYPE
|
|
SYNTAX BankValueEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single bankValue entry containing bank info."
|
|
INDEX { bankValueIndex }
|
|
::= { bankValueTable 1 }
|
|
|
|
BankValueEntry ::=
|
|
SEQUENCE {
|
|
bankValueIndex
|
|
INTEGER,
|
|
bankCurrent
|
|
DisplayString,
|
|
bankVoltage
|
|
DisplayString,
|
|
bankPower
|
|
DisplayString,
|
|
bankPowerDissipation
|
|
DisplayString,
|
|
bankMaxCurrent
|
|
INTEGER,
|
|
bankAttachStatus
|
|
INTEGER,
|
|
bankPowerFactor
|
|
DisplayString
|
|
}
|
|
|
|
bankValueIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of bank number"
|
|
::= { bankValueEntry 1 }
|
|
bankCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank electric current value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { bankValueEntry 2 }
|
|
bankVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank voltage value.
|
|
We put this OID to write access type for user to set the reference voltage on EC1000 model.
|
|
And the setting should be the numbers. You can set 0 to clear the setting.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { bankValueEntry 3 }
|
|
|
|
bankPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank power value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { bankValueEntry 4 }
|
|
|
|
bankPowerDissipation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank power dissipation value.
|
|
If this measurement value is not available, it returns: N/A.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { bankValueEntry 5 }
|
|
|
|
|
|
bankMaxCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bank Max Current value. unit: (A)
|
|
EC1000:0A~320A
|
|
"
|
|
::= { bankValueEntry 6 }
|
|
|
|
bankAttachStatus OBJECT-TYPE
|
|
SYNTAX INTEGER { noattached(1), attached(2), error(3), noexisted(4) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of Energy sensor Bank attached status."
|
|
::= { bankValueEntry 7 }
|
|
|
|
bankPowerFactor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank Power Factor value.
|
|
If the device does not support this OID, it returns: not-support."
|
|
::= { bankValueEntry 8 }
|
|
|
|
bankConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BankConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank configuration table"
|
|
::= { bank 3 }
|
|
|
|
bankConfigEntry OBJECT-TYPE
|
|
SYNTAX BankConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank Config entry containing Bank info."
|
|
INDEX { bankConfigIndex }
|
|
::= { bankConfigTable 1 }
|
|
|
|
BankConfigEntry ::=
|
|
SEQUENCE {
|
|
bankConfigIndex
|
|
INTEGER,
|
|
bankName
|
|
DisplayString,
|
|
bankMinCurMT
|
|
INTEGER,
|
|
bankMaxCurMT
|
|
INTEGER,
|
|
|
|
bankMinVolMT
|
|
INTEGER,
|
|
bankMaxVolMT
|
|
INTEGER,
|
|
|
|
bankMinPMT
|
|
INTEGER,
|
|
bankMaxPMT
|
|
INTEGER,
|
|
--outletMinPDMT
|
|
--INTEGER,
|
|
bankMaxPDMT
|
|
INTEGER
|
|
--outletCurFlu
|
|
--INTEGER,
|
|
--outletVolFlu
|
|
--INTEGER,
|
|
--outletPFlu
|
|
--INTEGER
|
|
--outletPDFlu
|
|
--INTEGER
|
|
}
|
|
|
|
bankConfigIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..30)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of bank number"
|
|
::= { bankConfigEntry 1 }
|
|
|
|
bankName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the name of bank.
|
|
When this model does not support the OID, we show n/a.
|
|
string length: 0~15
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { bankConfigEntry 2 }
|
|
|
|
|
|
bankMinCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum electric current measurment threshold.
|
|
Example: range 0.0 ~16.0 rerpresnts 0~160
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 3 }
|
|
|
|
bankMaxCurMT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum electric current measurment threshold.
|
|
Example: range 0.0 ~16.0 represents 0~160
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 4}
|
|
|
|
bankMinVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum voltage measurment threshold.
|
|
Example: range 90.0 ~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 5 }
|
|
bankMaxVolMT OBJECT-TYPE
|
|
SYNTAX INTEGER (900..2600 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum voltage measurment threshold.
|
|
Example: range 90.0 ~260.0 represents 900~2600
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 6 }
|
|
|
|
bankMinPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999| -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet minimum power measurment threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 7 }
|
|
bankMaxPMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..99999 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum power measurment threshold.
|
|
Example: range 0.0 ~ 9999.9 represents 0~99999
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 8 }
|
|
|
|
--outletMinPDMT OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..100)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the outlet minimum power dissipation measurment threshold ."
|
|
--::= { outletConfigEntry 14 }
|
|
|
|
bankMaxPDMT OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999990 | -3000 | -2000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the outlet maximum power dissipation measurment threshold.
|
|
Example: range 0.0 ~ 99999.0 represents 0~999990
|
|
NOTICE: Minimum threshold should be smaller than maximum threshold.
|
|
Empty value: -3000.
|
|
If the device does not support this OID, it returns value -2000000."
|
|
::= { bankConfigEntry 9 }
|
|
|
|
|
|
bankControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BankControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank Control table"
|
|
::= { bank 4 }
|
|
|
|
bankControlEntry OBJECT-TYPE
|
|
SYNTAX BankControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank control entry."
|
|
INDEX { bankControlIndex }
|
|
::= { bankControlTable 1 }
|
|
|
|
BankControlEntry ::=
|
|
SEQUENCE {
|
|
bankControlIndex
|
|
INTEGER,
|
|
bankControlStatus
|
|
INTEGER
|
|
}
|
|
|
|
bankControlIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of bank number"
|
|
::= { bankControlEntry 1 }
|
|
|
|
bankControlStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {off(1), on(2), reboot(3), nostatus(4), not-support(5)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This function is used for outlet control of bank.
|
|
Set off(1) to turn off for outlet control of bank.
|
|
Set on(2) to turn on for all outlet control of bank.
|
|
Set reboot(3) to turn on for outlet control of bank.
|
|
Get this object always return nostatus(3), because there is no bank status.
|
|
"
|
|
::= { bankControlEntry 2 }
|
|
|
|
-- Bank control End
|
|
|
|
|
|
--bankIntegerValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF BankIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display total bank value table"
|
|
-- ::= { bank 99 }
|
|
|
|
--bankIntegerValueEntry OBJECT-TYPE
|
|
-- SYNTAX BankIntegerValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single bankValue entry containing bank info."
|
|
-- INDEX { bankIntegerValueIndex }
|
|
-- ::= { bankIntegerValueTable 1 }
|
|
|
|
--BankIntegerValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- bankIntegerValueIndex
|
|
-- INTEGER,
|
|
-- bankIntegerCurrent
|
|
-- INTEGER,
|
|
-- bankIntegerVoltage
|
|
-- INTEGER,
|
|
-- bankIntegerPower
|
|
-- INTEGER,
|
|
-- bankIntegerPowerDissipation
|
|
-- INTEGER
|
|
--bankIntegerMaxCurrent
|
|
-- INTEGER,
|
|
--bankIntegerAttachStatus
|
|
-- INTEGER,
|
|
--bankIntegerPowerFactor
|
|
--INTEGER
|
|
-- }
|
|
|
|
--bankIntegerValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..30)
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of bank number.
|
|
-- "
|
|
-- ::= { bankIntegerValueEntry 1 }
|
|
|
|
--bankIntegerCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Bank electric current value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { bankIntegerValueEntry 2 }
|
|
--bankIntegerVoltage OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Bank voltage value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { bankIntegerValueEntry 3 }
|
|
|
|
--bankIntegerPower OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Bank power value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { bankIntegerValueEntry 4 }
|
|
|
|
--bankIntegerPowerDissipation OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Bank power dissipation value.
|
|
-- This value indicates that 1,000 times."
|
|
-- ::= { bankIntegerValueEntry 5 }
|
|
|
|
|
|
--bankMaxCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The Bank Max Current value. unit: (A)
|
|
-- EC1000:0A~320A
|
|
-- "
|
|
-- ::= { bankValueEntry 6 }
|
|
|
|
--bankAttachStatus OBJECT-TYPE
|
|
-- SYNTAX INTEGER { noattached(1), attached(2), error(3) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The status of Energy sensor Bank attached status."
|
|
-- ::= { bankValueEntry 7 }
|
|
|
|
--bankPowerFactor OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Bank Power Factor value"
|
|
-- ::= { bankValueEntry 8 }
|
|
|
|
|
|
|
|
-- Device Management
|
|
deviceMAC OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display device MAC address."
|
|
::= { config 1 }
|
|
|
|
deviceIPv4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display device IP address."
|
|
::= { config 2 }
|
|
|
|
deviceFWversion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display device FW version."
|
|
::= { config 3 }
|
|
|
|
-- dashboard settings
|
|
dashboardRow OBJECT-TYPE
|
|
SYNTAX INTEGER (1..26)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device's dashboard row number."
|
|
::= { dashBoard 1 }
|
|
|
|
dashboardColumn OBJECT-TYPE
|
|
SYNTAX INTEGER (1..26)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device's dashboard column number."
|
|
::= { dashBoard 2 }
|
|
|
|
dashboardRackName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set device's dashboard rack name.
|
|
string length: 1~32
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { dashBoard 3 }
|
|
|
|
httpPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the HTTP port of PE device."
|
|
::= { servicePorts 1 }
|
|
|
|
httpsPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the HTTPs port of PE device."
|
|
::= { servicePorts 2 }
|
|
|
|
httpsOnlyEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {yes(1), no(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs"
|
|
::= { servicePorts 3 }
|
|
|
|
|
|
|
|
staticIPEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set IPv4 address automatically or not"
|
|
::= { ipv4config 1 }
|
|
fixedIPv4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set fixed IPv4 address"
|
|
::= { ipv4config 2 }
|
|
subnetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set subnet mask address"
|
|
::= { ipv4config 3 }
|
|
gateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set gateway address"
|
|
::= { ipv4config 4 }
|
|
staticDNSEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set DNS address automatically or not"
|
|
::= { ipv4config 5 }
|
|
dnsPreferIPv4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set prefer DNS address"
|
|
::= { ipv4config 6 }
|
|
dnsAlternateIPv4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set alternate DNS address"
|
|
::= { ipv4config 7 }
|
|
|
|
trapEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if this trap entry is enabled or not.
|
|
You should set the username/auth-password/priv-password first, when choosing snmpv3.
|
|
You should set the community string first, when choosing snmpv1/v2c."
|
|
::= { devicesnmp 1 }
|
|
|
|
trapVersion OBJECT-TYPE
|
|
SYNTAX INTEGER { v1(1), v2c(2), v3(3)}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Choose SNMP Trap version to send trap.
|
|
You should set the username/auth-password/priv-password first, when choosing snmpv3.
|
|
You should set the community string first, when choosing snmpv1/v2c."
|
|
::= { devicesnmp 2 }
|
|
|
|
snmpTrapTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SnmpTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PE SNMP agent trap setup table. If users want to use trap,
|
|
they must set enable trap, ip and community first."
|
|
::= { devicesnmp 3 }
|
|
|
|
snmpTrapEntry OBJECT-TYPE
|
|
SYNTAX SnmpTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Single trap entry containing trap receiver info."
|
|
INDEX { trapReceiverNumber }
|
|
::= { snmpTrapTable 1 }
|
|
|
|
SnmpTrapEntry ::=
|
|
SEQUENCE {
|
|
trapReceiverNumber
|
|
INTEGER,
|
|
--trapEnabled
|
|
--INTEGER,
|
|
trapReceiverIPAddress
|
|
IpAddress,
|
|
--trapCommunity
|
|
--DisplayString,
|
|
trapPort
|
|
INTEGER,
|
|
trapCommunity
|
|
DisplayString,
|
|
trapUsername
|
|
DisplayString,
|
|
trapAuthpassword
|
|
DisplayString,
|
|
trapPrivpassword
|
|
DisplayString
|
|
}
|
|
|
|
trapReceiverNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of trap receiver"
|
|
::= { snmpTrapEntry 1 }
|
|
|
|
|
|
|
|
trapReceiverIPAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap receiver IP address"
|
|
::= { snmpTrapEntry 2 }
|
|
|
|
|
|
trapPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"NMS trap port to be used by agent to send trap"
|
|
::= { snmpTrapEntry 3 }
|
|
|
|
trapCommunity OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If use SNMPv1/v2c to receive trap should set this Community string.
|
|
MAX string length: 20
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { snmpTrapEntry 4 }
|
|
trapUsername OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If use SNMPv3 to receive trap should set this string.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
MAX string length: 20
|
|
"
|
|
::= { snmpTrapEntry 5 }
|
|
trapAuthpassword OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (8..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If use SNMPv3 to receive trap should set this string.
|
|
MAX string length: 20
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { snmpTrapEntry 6 }
|
|
trapPrivpassword OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (8..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If use SNMPv3 to receive trap should set this string.
|
|
MAX string length: 20
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { snmpTrapEntry 7 }
|
|
|
|
|
|
--privacypassword OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "SNMPv3 privacy password to be used by agent to send trap
|
|
-- string length: 8~20
|
|
-- "
|
|
-- ::= { devicesnmp 4 }
|
|
|
|
--engineID OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "EngineID"
|
|
-- ::= { devicesnmp 5 }
|
|
--engineBoot OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "EngineBoot"
|
|
-- ::= { devicesnmp 6 }
|
|
--engineTime OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "EngineTime"
|
|
-- ::= { devicesnmp 7 }
|
|
--engineMaxMSG OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "EngineMaxMSG"
|
|
-- ::= { devicesnmp 8 }
|
|
sysLogServerEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set syslog server address automatically or not"
|
|
::= { syslog 1 }
|
|
sysLogServerIPv4 OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set syslog server address"
|
|
::= { syslog 2 }
|
|
sysLogServerPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set syslog server port"
|
|
::= { syslog 3 }
|
|
|
|
smtpServerEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set SMTP server enable status."
|
|
::= { smtp 1 }
|
|
smtpServerName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a SMTP server name.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { smtp 2 }
|
|
smtpAuthEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set authentication of SMTP server."
|
|
::= { smtp 3 }
|
|
smtpAccountName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a user's name of SMTP server.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { smtp 4 }
|
|
smtpAccountPwd OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a user's password of SMTP server.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { smtp 5 }
|
|
smtpMailFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a mail of SMTP server.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { smtp 6 }
|
|
smtpMailTo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a mail of SMTP server.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { smtp 7 }
|
|
--
|
|
|
|
configurationNotifyEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" "
|
|
::= { configurationNotification 1 }
|
|
|
|
configurationNotifyTrapMSG NOTIFICATION-TYPE
|
|
STATUS current
|
|
--OBJECTS { customTrapMSG }
|
|
DESCRIPTION " "
|
|
::= { configurationNotification 2 }
|
|
|
|
|
|
--
|
|
timeZoneSetting OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set the time zone of PE device.
|
|
(0) [GMT-12:00] Eniwetok Kwajalein
|
|
(1) [GMT-11:00] Midway Island Samoa
|
|
(2) [GMT-10:00] Hawaii
|
|
(3) [GMT-09:00] Alaska
|
|
(4) [GMT-08:00] Pacific Time (US & Canada); Tijuana
|
|
(5) [GMT-07:00] Mountain Time (US & Canada)
|
|
(6) [GMT-07:00] Arizona
|
|
(7) [GMT-06:00] Central Time (US & Canada)
|
|
(8) [GMT-06:00] Mexico City
|
|
(9) [GMT-06:00] Saskatchewan
|
|
(10)[GMT-06:00] Central America
|
|
(11)[GMT-05:00] Eastern Time (US & Canada)
|
|
(12)[GMT-05:00] Indiana (East)
|
|
(13)[GMT-05:00] Bogota Lima Quito
|
|
(14)[GMT-04:00] Atlantic Time (Canada)
|
|
(15)[GMT-04:00] Caracas La Paz
|
|
(16)[GMT-04:00] Santiago
|
|
(17)[GMT-03:30] Newfoundland
|
|
(18)[GMT-03:00] Buenos Aires Georgetown
|
|
(19)[GMT-03:00] Brasilia
|
|
(20)[GMT-03:00] Greenland
|
|
(21)[GMT-02:00] Mid-Atlantic
|
|
(22)[GMT-01:00] Azores
|
|
(23)[GMT-01:00] Cape Verde Is
|
|
(24)[GMT] Casablanca Monrovia
|
|
(25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London
|
|
(26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius
|
|
(27)[GMT+01:00] West Central Africa
|
|
(28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb
|
|
(29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw
|
|
(30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna
|
|
(31)[GMT+02:00] Cairo
|
|
(32)[GMT+02:00] Harare Pretoria
|
|
(33)[GMT+02:00] Jerusalem
|
|
(34)[GMT+02:00] Bucharest
|
|
(35)[GMT+02:00] Helsinki Riga Tallinn
|
|
(36)[GMT+02:00] Athens Istanbul Minsk
|
|
(37)[GMT+03:00] Kuwait Riyadh
|
|
(38)[GMT+03:00] Nairobi
|
|
(39)[GMT+03:00] Baghdad
|
|
(40)[GMT+03:00] Moscow St. Petersburg Volgograd
|
|
(41)[GMT+03:30] Tehran
|
|
(42)[GMT+04:00] Abu Dhabi Muscat
|
|
(43)[GMT+04:00] Baku Tbilisi Yerevan
|
|
(44)[GMT+04:30] Kabul
|
|
(45)[GMT+05:00] Islamabad Karachi Tashkent
|
|
(46)[GMT+05:00] Ekaterinburg
|
|
(47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi
|
|
(48)[GMT+05:45] Kathmandu
|
|
(49)[GMT+06:00] Astana Dhaka
|
|
(50)[GMT+06:00] Sri Jayawardenepura
|
|
(51)[GMT+06:00] Almaty Novosibirsk
|
|
(52)[GMT+06:30] Rangoon
|
|
(53)[GMT+07:00] Bangkok Hanoi Jakarta
|
|
(54)[GMT+07:00] Krasnoyarsk
|
|
(55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi
|
|
(56)[GMT+08:00] Perth
|
|
(57)[GMT+08:00] Kuala Lumpur Singapore
|
|
(58)[GMT+08:00] Taipei
|
|
(59)[GMT+08:00] Irkutsk Ulaan Bataar
|
|
(60)[GMT+09:00] Osaka Sapporo Tokyo
|
|
(61)[GMT+09:00] Seoul
|
|
(62)[GMT+09:00] Yakutsk
|
|
(63)[GMT+09:30] Darwin
|
|
(64)[GMT+09:30] Adelaide
|
|
(65)[GMT+10:00] Canberra Melbourne Sydney
|
|
(66)[GMT+10:00] Brisbane
|
|
(67)[GMT+10:00] Guam Port Moresby
|
|
(68)[GMT+10:00] Hobart
|
|
(69)[GMT+10:00] Vladivostok
|
|
(70)[GMT+11:00] Magadan Solomon Is New Caledonia
|
|
(71)[GMT+12:00] Fiji Kamchatka Marshall Is.
|
|
(72)[GMT+12:00] Auckland Wellington
|
|
(73)[GMT+13:00] Nuku'alofa
|
|
"
|
|
::= { timeZone 1 }
|
|
|
|
dstEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set daylight savings time ."
|
|
::= { timeZone 2 }
|
|
|
|
dateSetting OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set date in a manual way.(This is Greenwich Mean Time, GMT)
|
|
string length: 10
|
|
This value format must match the following form:
|
|
YYYY-MM-DD
|
|
ex. 2011-01-01
|
|
Note: range of year: 2000-2099
|
|
range of month: 01-12
|
|
range of day: 01-31
|
|
"
|
|
::= { manualInput 1 }
|
|
|
|
timeSetting OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set time in a manual way.(This is Greenwich Mean Time, GMT)
|
|
string length: 8
|
|
This value format must match the following form:
|
|
HH:MM:SS
|
|
ex. 02:02:02
|
|
Note: range of hour: 00-24
|
|
range of minute: 00-60
|
|
range of second: 00-60
|
|
|
|
"
|
|
::= { manualInput 2 }
|
|
|
|
--syncWithPC OBJECT-TYPE
|
|
-- SYNTAX INTEGER { no(1), yes(2) }
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set date time useing sync PC way."
|
|
-- ::= { manualInput 3 }
|
|
|
|
autoAdjustEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set date time useing auto adjustment way."
|
|
::= { networkTime 1 }
|
|
|
|
preferNTP OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set prefer NTP server.
|
|
AU | ntp1.cs.mu.OZ.AU(0),
|
|
AU | ntp0.cs.mu.OZ.AU(1),
|
|
BE | ntp2.oma.be(2),
|
|
BE | ntp1.oma.be(3),
|
|
BR | ntps1.pads.ufrj.br(4),
|
|
CH | swisstime.ethz.ch(5),
|
|
CL | ntp.shoa.cl(6),
|
|
CZ | ntp.nic.cz(7),
|
|
DE | ntp.stairweb.de(8),
|
|
DE | ntps1-0.cs.tu-berlin.de(9),
|
|
DE | ptbtime1.ptb.de(10),
|
|
DE | ntp1.fau.de(11),
|
|
DE | ptbtime2.ptb.de(12),
|
|
DE | time1.one4vision.de(13),
|
|
DE | rustime01.rus.uni-stuttgart.de(14),
|
|
DE | ntp.probe-networks.de(15),
|
|
DE | ntp2.fau.de(16),
|
|
ES | hora.roa.es(17),
|
|
HK | stdtime.gov.hk(18),
|
|
IE | ntp-galway.hea.net(19),
|
|
IT | ntp1.inrim.it(20),
|
|
IT | ntp2.inrim.it(21),
|
|
JP | clock.tl.fukuoka-u.ac.jp(22),
|
|
JP | ntp.nict.jp(23),
|
|
JP | clock.nc.fukuoka-u.ac.jp(24),
|
|
KR | ntp.xbsd.kr(25),
|
|
MX | cronos.cenam.mx(26),
|
|
NL | ntp0.nl.uu.net(27),
|
|
NL | ntp1.nl.uu.net(28),
|
|
NL | ntp.remco.org(29),
|
|
NL | ntp0.nl.net(30),
|
|
PL | vega.cbk.poznan.pl(31),
|
|
PL | ntp.ntp-servers.com(32),
|
|
RO | ntp3.usv.ro(33),
|
|
RO | ntp2.usv.ro(34),
|
|
RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35),
|
|
RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36),
|
|
SE | ntp1.mmo.netnod.se(37),
|
|
SE | ntp1.sth.netnod.se(38),
|
|
SE | ntp2.mmo.netnod.se(39),
|
|
SE | ntp2.sth.netnod.se(40),
|
|
SE | time2.stupi.se(41),
|
|
SE | ntp1.sp.se(42),
|
|
SE | timehost.lysator.liu.se(43),
|
|
SI | ntp.mostovna.com(44),
|
|
US CA | timekeeper.isi.edu(45),
|
|
US CA | clock.sjc.he.net(46),
|
|
US CA | nist1.symmetricom.com(47),
|
|
US CA | clock.via.net(48),
|
|
US CA | nist1.aol-ca.truetime.com(49),
|
|
US CA | clock.isc.org(50),
|
|
US CA | clepsydra.dec.com(51),
|
|
US CA | gps.layer42.net(52),
|
|
US CA | time.no-such-agency.net(53),
|
|
US CA | nist1-sj.WiTime.net(54),
|
|
US CA | clock.fmt.he.net(55),
|
|
US CO | time-b.timefreq.bldrdoc.gov(56),
|
|
US CO | time-a.timefreq.bldrdoc.gov(57),
|
|
US CO | utcnist.colorado.edu(58),
|
|
US CO | time-c.timefreq.bldrdoc.gov(59),
|
|
US DE | rackety.udel.edu(60),
|
|
US DE | mizbeaver.udel.edu(61),
|
|
US GA | nist1.columbiacountyga.gov(62),
|
|
US IL | ntp.your.org(63),
|
|
US MA | bonehed.lcs.mit.edu(64),
|
|
US MA | time.keneli.org(65),
|
|
US MA | ntp0.broad.mit.edu(66),
|
|
US MD | time-a.nist.gov(67),
|
|
US MD | time-b.nist.gov(68),
|
|
US MI | nist.netservicesgroup.com(69),
|
|
US NY | nist1-ny.WiTime.net(70),
|
|
US NY | clock.nyc.he.net(71),
|
|
US UT | time.xmission.com(72),
|
|
US VA | nist1-dc.WiTime.net(73),
|
|
US VA | nist1.aol-va.truetime.com(74),
|
|
US WA | time-nw.nist.gov(75),
|
|
FR | utp.univ-lyon1.fr(76),
|
|
FR | ntp-sop.inria.fr(77),
|
|
FR | ntp.tuxfamily.net(78),
|
|
UK | bear.zoo.bt.co.uk(79)
|
|
"
|
|
::= { networkTime 2 }
|
|
|
|
preferServerIPenable OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable or disable prefer custom server IP."
|
|
::= { networkTime 3 }
|
|
|
|
preferNTPIp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set prefer NTP server IP."
|
|
::= { networkTime 4 }
|
|
|
|
alternateNtpEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set date time using alternate NTP server."
|
|
::= { networkTime 5 }
|
|
|
|
alternateNtp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set alternative NTP server.
|
|
AU | ntp1.cs.mu.OZ.AU(0),
|
|
AU | ntp0.cs.mu.OZ.AU(1),
|
|
BE | ntp2.oma.be(2),
|
|
BE | ntp1.oma.be(3),
|
|
BR | ntps1.pads.ufrj.br(4),
|
|
CH | swisstime.ethz.ch(5),
|
|
CL | ntp.shoa.cl(6),
|
|
CZ | ntp.nic.cz(7),
|
|
DE | ntp.stairweb.de(8),
|
|
DE | ntps1-0.cs.tu-berlin.de(9),
|
|
DE | ptbtime1.ptb.de(10),
|
|
DE | ntp1.fau.de(11),
|
|
DE | ptbtime2.ptb.de(12),
|
|
DE | time1.one4vision.de(13),
|
|
DE | rustime01.rus.uni-stuttgart.de(14),
|
|
DE | ntp.probe-networks.de(15),
|
|
DE | ntp2.fau.de(16),
|
|
ES | hora.roa.es(17),
|
|
HK | stdtime.gov.hk(18),
|
|
IE | ntp-galway.hea.net(19),
|
|
IT | ntp1.inrim.it(20),
|
|
IT | ntp2.inrim.it(21),
|
|
JP | clock.tl.fukuoka-u.ac.jp(22),
|
|
JP | ntp.nict.jp(23),
|
|
JP | clock.nc.fukuoka-u.ac.jp(24),
|
|
KR | ntp.xbsd.kr(25),
|
|
MX | cronos.cenam.mx(26),
|
|
NL | ntp0.nl.uu.net(27),
|
|
NL | ntp1.nl.uu.net(28),
|
|
NL | ntp.remco.org(29),
|
|
NL | ntp0.nl.net(30),
|
|
PL | vega.cbk.poznan.pl(31),
|
|
PL | ntp.ntp-servers.com(32),
|
|
RO | ntp3.usv.ro(33),
|
|
RO | ntp2.usv.ro(34),
|
|
RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35),
|
|
RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36),
|
|
SE | ntp1.mmo.netnod.se(37),
|
|
SE | ntp1.sth.netnod.se(38),
|
|
SE | ntp2.mmo.netnod.se(39),
|
|
SE | ntp2.sth.netnod.se(40),
|
|
SE | time2.stupi.se(41),
|
|
SE | ntp1.sp.se(42),
|
|
SE | timehost.lysator.liu.se(43),
|
|
SI | ntp.mostovna.com(44),
|
|
US CA | timekeeper.isi.edu(45),
|
|
US CA | clock.sjc.he.net(46),
|
|
US CA | nist1.symmetricom.com(47),
|
|
US CA | clock.via.net(48),
|
|
US CA | nist1.aol-ca.truetime.com(49),
|
|
US CA | clock.isc.org(50),
|
|
US CA | clepsydra.dec.com(51),
|
|
US CA | gps.layer42.net(52),
|
|
US CA | time.no-such-agency.net(53),
|
|
US CA | nist1-sj.WiTime.net(54),
|
|
US CA | clock.fmt.he.net(55),
|
|
US CO | time-b.timefreq.bldrdoc.gov(56),
|
|
US CO | time-a.timefreq.bldrdoc.gov(57),
|
|
US CO | utcnist.colorado.edu(58),
|
|
US CO | time-c.timefreq.bldrdoc.gov(59),
|
|
US DE | rackety.udel.edu(60),
|
|
US DE | mizbeaver.udel.edu(61),
|
|
US GA | nist1.columbiacountyga.gov(62),
|
|
US IL | ntp.your.org(63),
|
|
US MA | bonehed.lcs.mit.edu(64),
|
|
US MA | time.keneli.org(65),
|
|
US MA | ntp0.broad.mit.edu(66),
|
|
US MD | time-a.nist.gov(67),
|
|
US MD | time-b.nist.gov(68),
|
|
US MI | nist.netservicesgroup.com(69),
|
|
US NY | nist1-ny.WiTime.net(70),
|
|
US NY | clock.nyc.he.net(71),
|
|
US UT | time.xmission.com(72),
|
|
US VA | nist1-dc.WiTime.net(73),
|
|
US VA | nist1.aol-va.truetime.com(74),
|
|
US WA | time-nw.nist.gov(75),
|
|
FR | utp.univ-lyon1.fr(76),
|
|
FR | ntp-sop.inria.fr(77),
|
|
FR | ntp.tuxfamily.net(78),
|
|
UK | bear.zoo.bt.co.uk(79)
|
|
"
|
|
::= { networkTime 6 }
|
|
|
|
alternateServerIPenable OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable or disable alternate custom server IP."
|
|
::= { networkTime 7 }
|
|
|
|
alternateNtpIp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set alternative NTP server IP."
|
|
::= { networkTime 8 }
|
|
|
|
adjustTimeEveryDays OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set frequency of adjustment in days."
|
|
::= { networkTime 9 }
|
|
|
|
--adjustTimeNow OBJECT-TYPE
|
|
--SYNTAX INTEGER { no(1), yes(2) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Adjust time using NTP server."
|
|
--::= { networkTime 8 }
|
|
|
|
loginAllowTimes OBJECT-TYPE
|
|
SYNTAX INTEGER (1..99)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set time of login faliure."
|
|
::= { loginFailures 1 }
|
|
|
|
loginTimeOut OBJECT-TYPE
|
|
SYNTAX INTEGER (1..240)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set login time out."
|
|
::= { loginFailures 2 }
|
|
|
|
icmpEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of ICMP."
|
|
::= { workingMode 1 }
|
|
|
|
--multiUserEnabled OBJECT-TYPE
|
|
--SYNTAX INTEGER { no(1), yes(2) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set status of multi-user operation."
|
|
--::= { workingMode 2 }
|
|
|
|
--browserEnabled OBJECT-TYPE
|
|
--SYNTAX INTEGER { no(1), yes(2) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set status of browser."
|
|
--::= { workingMode 3 }
|
|
|
|
minUserNameLen OBJECT-TYPE
|
|
SYNTAX INTEGER (1..16)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set minimum length of user name."
|
|
::= { accountPolicy 1 }
|
|
|
|
minUserPwdLen OBJECT-TYPE
|
|
SYNTAX INTEGER (1..16)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set minimum length of user password.
|
|
"
|
|
::= { accountPolicy 2 }
|
|
|
|
upperCaseEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set one upper case rule in user password."
|
|
::= { accountPolicy 3 }
|
|
|
|
lowerCaseEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set one lower case rule in user password."
|
|
::= { accountPolicy 4 }
|
|
|
|
numberEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set one number rule in user password."
|
|
::= { accountPolicy 5 }
|
|
|
|
disableDuplicateLogin OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of disabled duplicate login rule."
|
|
::= { accountPolicy 6 }
|
|
|
|
loginString OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set a login string.
|
|
string length: 0~32
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { loginRestriction 1 }
|
|
|
|
ipFilterEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of ip filter."
|
|
::= { ipFilter 1 }
|
|
|
|
ipFilterRule OBJECT-TYPE
|
|
SYNTAX INTEGER { include(1), exclude(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of ip filter rule."
|
|
::= { ipFilter 2 }
|
|
|
|
ipFilterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IpFilterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of restricted ip."
|
|
::= { ipFilter 3 }
|
|
|
|
ipFilterEntry OBJECT-TYPE
|
|
SYNTAX IpFilterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status and parameter values for a PE's restricted IP."
|
|
INDEX { ipFilterIndex }
|
|
::= { ipFilterTable 1 }
|
|
|
|
IpFilterEntry ::=
|
|
SEQUENCE {
|
|
ipFilterIndex
|
|
INTEGER,
|
|
ipFilterFrom
|
|
IpAddress,
|
|
ipFilterTo
|
|
IpAddress
|
|
}
|
|
|
|
ipFilterIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..5)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of index for the ip filter.
|
|
"
|
|
::= { ipFilterEntry 1 }
|
|
|
|
ipFilterFrom OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set of restricted ip.
|
|
ex. 192.168.0.1
|
|
|
|
Note: Users must follow in order to set the ip address.
|
|
Note: To clear the settings to set the ip 0.0.0.0
|
|
"
|
|
::= { ipFilterEntry 2 }
|
|
|
|
ipFilterTo OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set of restricted ip.
|
|
ex. 192.168.0.255
|
|
|
|
Note: Users must follow in order to set the ip address.
|
|
Note: To clear the settings to set the ip 0.0.0.0
|
|
"
|
|
::= { ipFilterEntry 3 }
|
|
|
|
macFilterEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of mac filter."
|
|
::= { macFilter 1 }
|
|
|
|
macFilterRule OBJECT-TYPE
|
|
SYNTAX INTEGER { include(1), exclude(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of mac filter rule."
|
|
::= { macFilter 2 }
|
|
|
|
macFilterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF MacFilterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of restricted mac."
|
|
::= { macFilter 3 }
|
|
|
|
macFilterEntry OBJECT-TYPE
|
|
SYNTAX MacFilterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status and parameter values for a PE's restricted MAC."
|
|
INDEX { macFilterIndex }
|
|
::= { macFilterTable 1 }
|
|
|
|
MacFilterEntry ::=
|
|
SEQUENCE {
|
|
macFilterIndex
|
|
INTEGER,
|
|
macFilterSet
|
|
DisplayString
|
|
}
|
|
|
|
macFilterIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..5)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of index for the mac filter.
|
|
"
|
|
::= { macFilterEntry 1 }
|
|
|
|
macFilterSet OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set of restricted mac.
|
|
string length: 12
|
|
ex. 004854655511
|
|
|
|
Note: Users must follow in order to set the MAC address.
|
|
Note: To clear the settings to set the MAC 000000000000
|
|
"
|
|
::= { macFilterEntry 2 }
|
|
|
|
--LocalAuth OBJECT-TYPE
|
|
--SYNTAX INTEGER { no(1), yes(2) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set status of disable local authentication."
|
|
--::= { authentication 1 }
|
|
|
|
radiusEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set status of RADIUS server."
|
|
::= { radius 1 }
|
|
|
|
preferRadiusIp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set prefer RADIUS server IP."
|
|
::= { radius 2 }
|
|
|
|
preferRadiusPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set prefer RADIUS server port."
|
|
::= { radius 3 }
|
|
|
|
alternateRadiusIp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set alternative RADIUS server IP."
|
|
::= { radius 4 }
|
|
|
|
alternateRadiusPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set alternative RADIUS server port."
|
|
::= { radius 5 }
|
|
|
|
radiusTimeOut OBJECT-TYPE
|
|
SYNTAX INTEGER (1..60)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set time out of authentication using RADIUS server.
|
|
The unit is sec.
|
|
"
|
|
::= { radius 6 }
|
|
|
|
radiusRetry OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set retry times of authentication using RADIUS server."
|
|
::= { radius 7 }
|
|
|
|
radiusSecret OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set shared secret of RADIUS server.
|
|
string length: 6~15
|
|
At least 6 characters.
|
|
NOTE: Input string as /empty to set this object to NULL.
|
|
"
|
|
::= { radius 8 }
|
|
|
|
-- Device Management End
|
|
|
|
-- User Management
|
|
usrListTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UsrListEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of user. The number of user is
|
|
given by the value of usrcfgNumber."
|
|
::= { userManagement 1 }
|
|
|
|
usrListEntry OBJECT-TYPE
|
|
SYNTAX UsrListEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status and parameter values for a pe8208 user."
|
|
INDEX { usrIndex }
|
|
::= { usrListTable 1 }
|
|
|
|
UsrListEntry ::=
|
|
SEQUENCE {
|
|
usrIndex
|
|
INTEGER,
|
|
usrType
|
|
INTEGER,
|
|
usrName
|
|
DisplayString,
|
|
usrPassword
|
|
DisplayString,
|
|
usrPort1Auth
|
|
INTEGER,
|
|
usrPort2Auth
|
|
INTEGER,
|
|
usrPort3Auth
|
|
INTEGER,
|
|
usrPort4Auth
|
|
INTEGER,
|
|
usrPort5Auth
|
|
INTEGER,
|
|
usrPort6Auth
|
|
INTEGER,
|
|
usrPort7Auth
|
|
INTEGER,
|
|
usrPort8Auth
|
|
INTEGER,
|
|
|
|
usrPort9Auth
|
|
INTEGER,
|
|
usrPort10Auth
|
|
INTEGER,
|
|
usrPort11Auth
|
|
INTEGER,
|
|
usrPort12Auth
|
|
INTEGER,
|
|
usrPort13Auth
|
|
INTEGER,
|
|
usrPort14Auth
|
|
INTEGER,
|
|
usrPort15Auth
|
|
INTEGER,
|
|
usrPort16Auth
|
|
INTEGER,
|
|
usrPort17Auth
|
|
INTEGER,
|
|
usrPort18Auth
|
|
INTEGER,
|
|
usrPort19Auth
|
|
INTEGER,
|
|
usrPort20Auth
|
|
INTEGER,
|
|
usrPort21Auth
|
|
INTEGER,
|
|
usrPort22Auth
|
|
INTEGER,
|
|
usrPort23Auth
|
|
INTEGER,
|
|
usrPort24Auth
|
|
INTEGER,
|
|
usrPort25Auth
|
|
INTEGER,
|
|
usrPort26Auth
|
|
INTEGER,
|
|
usrPort27Auth
|
|
INTEGER,
|
|
usrPort28Auth
|
|
INTEGER,
|
|
usrPort29Auth
|
|
INTEGER,
|
|
usrPort30Auth
|
|
INTEGER,
|
|
usrPort31Auth
|
|
INTEGER,
|
|
usrPort32Auth
|
|
INTEGER,
|
|
usrPort33Auth
|
|
INTEGER,
|
|
usrPort34Auth
|
|
INTEGER,
|
|
usrPort35Auth
|
|
INTEGER,
|
|
usrPort36Auth
|
|
INTEGER,
|
|
usrPort37Auth
|
|
INTEGER,
|
|
usrPort38Auth
|
|
INTEGER,
|
|
usrPort39Auth
|
|
INTEGER,
|
|
usrPort40Auth
|
|
INTEGER,
|
|
usrPort41Auth
|
|
INTEGER,
|
|
usrPort42Auth
|
|
INTEGER,
|
|
usrEnable
|
|
INTEGER
|
|
}
|
|
|
|
usrIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..9)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of usrIndex for the user. We have 1 administrator and 8 users.
|
|
The index 9 will be the administrator.
|
|
"
|
|
::= { usrListEntry 1 }
|
|
|
|
usrType OBJECT-TYPE
|
|
SYNTAX INTEGER { administrator(1), user(2)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user's type."
|
|
::= { usrListEntry 2 }
|
|
|
|
usrName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..16))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing name of the user.
|
|
string length: 1~16
|
|
"
|
|
::= { usrListEntry 3 }
|
|
|
|
usrPassword OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..16))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing password of the user.
|
|
string length: 1~16
|
|
"
|
|
::= { usrListEntry 4 }
|
|
|
|
usrPort1Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 1 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 5 }
|
|
usrPort2Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 2 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 6 }
|
|
usrPort3Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 3 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 7 }
|
|
usrPort4Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 4 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 8 }
|
|
usrPort5Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 5 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 9 }
|
|
usrPort6Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dispaly or set this user's outlet 6 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 10 }
|
|
usrPort7Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 7 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 11 }
|
|
usrPort8Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 8 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 12 }
|
|
usrEnable OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), enable(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user is enable or not"
|
|
::= { usrListEntry 47 }
|
|
|
|
usrPort9Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 9 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 13 }
|
|
|
|
usrPort10Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 10 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 14 }
|
|
|
|
usrPort11Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 11 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 15 }
|
|
|
|
usrPort12Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 12 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 16 }
|
|
|
|
usrPort13Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 13 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 17 }
|
|
|
|
|
|
usrPort14Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 14 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 18 }
|
|
|
|
usrPort15Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 15 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 19 }
|
|
|
|
usrPort16Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 16 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 20 }
|
|
|
|
usrPort17Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 17 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 21 }
|
|
|
|
usrPort18Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 18 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 22 }
|
|
|
|
usrPort19Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 19 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 23 }
|
|
|
|
usrPort20Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 20 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 24 }
|
|
|
|
usrPort21Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 21 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 25 }
|
|
|
|
usrPort22Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 22 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 26 }
|
|
|
|
usrPort23Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 23 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 27 }
|
|
|
|
usrPort24Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 24 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 28 }
|
|
|
|
usrPort25Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 25 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 29 }
|
|
|
|
usrPort26Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 26 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 30 }
|
|
|
|
usrPort27Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 27 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 31 }
|
|
usrPort28Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 28 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 32 }
|
|
|
|
usrPort29Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 29 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 33 }
|
|
|
|
usrPort30Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 30 authority.
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 34 }
|
|
|
|
usrPort31Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 31 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 35 }
|
|
|
|
usrPort32Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 32 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 36 }
|
|
|
|
usrPort33Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 33 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 37 }
|
|
|
|
usrPort34Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 34 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 38 }
|
|
|
|
usrPort35Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 35 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 39 }
|
|
|
|
usrPort36Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 36 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 40 }
|
|
|
|
usrPort37Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 37 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 41 }
|
|
|
|
usrPort38Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 38 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 42 }
|
|
|
|
usrPort39Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 39 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 43 }
|
|
|
|
usrPort40Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 40 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 44 }
|
|
|
|
usrPort41Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 41 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 45 }
|
|
|
|
usrPort42Auth OBJECT-TYPE
|
|
SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display or set this user's outlet 42 authority
|
|
Port in the pe of series represents outlet.
|
|
Port in the Energy monitor of series represents a bank or a pdu."
|
|
::= { usrListEntry 46 }
|
|
|
|
-- User Management End
|
|
|
|
-- SNMPv3 USM Settings
|
|
--snmpv3UsmUserTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF Snmpv3UsmUserEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION "This table is used to configure PE SNMPv3 USM.
|
|
-- To get the SNMPv3 access, One need to configure security
|
|
-- name,authentication,auth password,priv protocol and priv
|
|
-- password.
|
|
-- "
|
|
-- ::= { snmp 2 }
|
|
|
|
--snmpv3UsmUserEntry OBJECT-TYPE
|
|
-- SYNTAX Snmpv3UsmUserEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION "A user configured for the User-based
|
|
-- Security Model.
|
|
-- "
|
|
-- INDEX { usmIndex }
|
|
-- ::= { snmpv3UsmUserTable 1 }
|
|
|
|
--Snmpv3UsmUserEntry ::= SEQUENCE {
|
|
-- usmIndex INTEGER,
|
|
-- usmSecurityName SnmpAdminString,
|
|
-- smAuthProtocol SNMPv3UsmAuthPrivProtocol,
|
|
-- usmPrivPassword SnmpAdminString
|
|
-- }
|
|
|
|
--usmIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION "Usm configuration index. "
|
|
-- ::= { snmpv3UsmUserEntry 1 }
|
|
|
|
|
|
--usmSecurityName OBJECT-TYPE
|
|
-- SYNTAX SnmpAdminString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION "A human readable string representing the user in
|
|
-- Security Model independent format.
|
|
|
|
-- The default transformation of the User-based Security
|
|
-- Model dependent security ID to the securityName and
|
|
-- vice versa is the identity function so that the
|
|
-- securityName is the same as the userName.
|
|
-- "
|
|
-- ::= { snmpv3UsmUserEntry 2 }
|
|
|
|
|
|
--usmKeyAlgorithm OBJECT-TYPE
|
|
-- SYNTAX SNMPv3UsmAuthPrivProtocol
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION "
|
|
-- If usmAuthProtocol == HMACMD5Auth , supports MD5 AuthKey and PrivKey
|
|
-- If usmAuthProtocol == HMACSHAAuth, supports SHA AuthKey and PrivKey
|
|
-- "
|
|
-- ::= { snmpv3UsmUserEntry 3 }
|
|
|
|
--usmPrivProtocol OBJECT-TYPE
|
|
-- SYNTAX SNMPv3UsmAuthPrivProtocol
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION " A privacy protocol to provide encryption and decryption
|
|
-- SNMPv3 pdu.
|
|
-- "
|
|
-- ::= { snmpv3UsmUserEntry 4 }
|
|
|
|
--usmPrivPassword OBJECT-TYPE
|
|
-- SYNTAX SnmpAdminString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION "An user's privacy password, Associated protocol
|
|
-- and a secret key is used to establish a connection
|
|
-- for the snmp agent and manager commnucation.
|
|
-- "
|
|
-- ::= { snmpv3UsmUserEntry 4 }
|
|
|
|
|
|
-- SNMPv3 Target MIB
|
|
|
|
--snmpv3TargetTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF Snmpv3TargetEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "A table of SNMP target information to be used
|
|
-- in the generation of SNMP trap messages."
|
|
-- ::= { snmp 3 }
|
|
|
|
--snmpv3TargetEntry OBJECT-TYPE
|
|
-- SYNTAX Snmpv3TargetEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "A set of SNMP target information.
|
|
-- "
|
|
-- INDEX { snmpv3TargetIndex }
|
|
-- ::= { snmpv3TargetTable 1 }
|
|
|
|
--Snmpv3TargetEntry ::= SEQUENCE {
|
|
-- snmpv3TargetIndex INTEGER,
|
|
-- snmpv3TargetMPModel SnmpMessageProcessingModel,
|
|
-- snmpv3TargetSecurityModel SnmpSecurityModel,
|
|
-- snmpv3TargetSecurityName SnmpAdminString
|
|
--}
|
|
--snmpv3TargetIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER(1)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The locally arbitrary, but unique identifier associated
|
|
-- with this snmpv3TargetEntry."
|
|
-- ::= { snmpv3TargetEntry 1 }
|
|
|
|
--snmpv3TargetMPModel OBJECT-TYPE
|
|
-- SYNTAX SnmpMessageProcessingModel
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The Message Processing Model to be used when generating
|
|
-- SNMP messages using this entry."
|
|
-- ::= { snmpv3TargetEntry 2 }
|
|
|
|
--snmpv3TargetSecurityModel OBJECT-TYPE
|
|
-- SYNTAX SnmpSecurityModel (1..2147483647)
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The Security Model to be used when generating SNMP
|
|
-- messages using this entry. An implementation may
|
|
-- choose to return an inconsistentValue error if an
|
|
-- attempt is made to set this variable to a value
|
|
-- for a security model which the implementation does
|
|
-- not support."
|
|
-- ::= { snmpv3TargetEntry 3 }
|
|
|
|
--snmpv3TargetSecurityName OBJECT-TYPE
|
|
-- SYNTAX SnmpAdminString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The securityName which identifies the Principal on
|
|
-- whose behalf SNMP messages will be generated using
|
|
-- this entry."
|
|
-- ::= { snmpv3TargetEntry 4 }
|
|
|
|
--snmpv3TargetSecurityLevel OBJECT-TYPE
|
|
-- SYNTAX SnmpSecurityLevel
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The Level of Security to be used when generating
|
|
-- SNMP messages using this entry."
|
|
-- ::= { snmpv3TargetEntry 5 }
|
|
|
|
-- Custom Trap Message
|
|
|
|
customTrapMSG NOTIFICATION-TYPE
|
|
STATUS current
|
|
--OBJECTS { customTrapMSG }
|
|
DESCRIPTION "Display custom trap message."
|
|
::= { pe 5 }
|
|
|
|
rebootDevice OBJECT-TYPE
|
|
SYNTAX INTEGER { no(1), yes(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reboot PE Device"
|
|
::= { pe 6 }
|
|
-- CPM
|
|
--modelName OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Indicate CPM device model name."
|
|
-- ::= { CPM 1 }
|
|
|
|
--cpmName OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The name of CPM device.
|
|
-- string length: 1~39
|
|
-- NOTE: Input string as /empty to set this object to NULL.
|
|
-- "
|
|
-- ::= { CPM 2 }
|
|
|
|
--cpmswitchable OBJECT-TYPE
|
|
-- SYNTAX INTEGER { no(1), yes(2) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- " Switchable or not. "
|
|
-- ::= { CPM 3 }
|
|
|
|
--cpmPDUreading OBJECT-TYPE
|
|
-- SYNTAX INTEGER { no(1), yes(2) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- " CPM is per-PDU reading or not."
|
|
-- ::= { CPM 4 }
|
|
|
|
--cpmSensornumber OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- " CPM's Sensor number."
|
|
-- ::= { CPM 5 }
|
|
|
|
--cpmOutletnumber OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- " CPM's Outlet number."
|
|
-- ::= { CPM 6 }
|
|
|
|
--cpmbreaker OBJECT-TYPE
|
|
--SYNTAX INTEGER { off(1), on(2) }
|
|
--MAX-ACCESS read-only
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "CPM's breaker status."
|
|
--::= { CPM 7 }
|
|
|
|
-- Device
|
|
--cpmdeviceValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmDeviceValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device value table. This table displays device's current.
|
|
-- "
|
|
-- ::= { CPMDevice 1 }
|
|
|
|
--cpmdeviceValueEntry OBJECT-TYPE
|
|
-- SYNTAX cpmDeviceValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single deviceValue entry containing device info."
|
|
-- INDEX { cpmdeviceValueIndex }
|
|
-- ::= { cpmdeviceValueTable 1 }
|
|
|
|
--cpmDeviceValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmdeviceValueIndex
|
|
-- INTEGER,
|
|
-- cpmdeviceCurrent
|
|
-- DisplayString,
|
|
--cpmdeviceVoltage
|
|
-- DisplayString,
|
|
--cpmdevicePower
|
|
-- DisplayString,
|
|
--cpmdevicePowerDissipation
|
|
-- DisplayString,
|
|
--cpminputMaxVoltage
|
|
-- INTEGER,
|
|
-- cpminputMaxCurrent
|
|
-- INTEGER
|
|
--cpmpowerCapacity
|
|
-- INTEGER
|
|
|
|
-- }
|
|
|
|
--cpmdeviceValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of device Value."
|
|
-- ::= { cpmdeviceValueEntry 1 }
|
|
|
|
--cpmdeviceCurrent OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device electric current value.
|
|
-- "
|
|
-- ::= { cpmdeviceValueEntry 2 }
|
|
|
|
--cpmdeviceVoltage OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device voltage value."
|
|
-- ::= { cpmdeviceValueEntry 3 }
|
|
--cpmdevicePower OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power value."
|
|
-- ::= { cpmdeviceValueEntry 4 }
|
|
|
|
--cpmdevicePowerDissipation OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power dissipation value."
|
|
-- ::= { cpmdeviceValueEntry 5 }
|
|
|
|
--cpminputMaxVoltage OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device input Voltage value. unit:(V)"
|
|
-- ::= { cpmdeviceValueEntry 6 }
|
|
|
|
--cpminputMaxCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device input Current value. unit:(A)"
|
|
-- ::= { cpmdeviceValueEntry 7 }
|
|
|
|
--cpmpowerCapacity OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device power Capacity value.unit:(VA)"
|
|
-- ::= { cpmdeviceValueEntry 8 }
|
|
|
|
--cpmdeviceConfigTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmDeviceConfigEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Device configuration table"
|
|
-- ::= { CPMDevice 2 }
|
|
|
|
--cpmdeviceConfigEntry OBJECT-TYPE
|
|
-- SYNTAX cpmDeviceConfigEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Single deviceConfig entry containing device info."
|
|
-- INDEX { cpmdeviceConfigIndex }
|
|
-- ::= { cpmdeviceConfigTable 1 }
|
|
|
|
--cpmDeviceConfigEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmdeviceConfigIndex
|
|
-- INTEGER,
|
|
--cpmdeviceMinCurMT
|
|
-- INTEGER,
|
|
-- cpmdeviceMaxCurMT
|
|
-- INTEGER
|
|
--cpmdeviceMinVolMT
|
|
-- INTEGER,
|
|
--cpmdeviceMaxVolMT
|
|
-- INTEGER,
|
|
-- }
|
|
|
|
--cpmdeviceConfigIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of deviceConfig"
|
|
-- ::= { cpmdeviceConfigEntry 1 }
|
|
|
|
--cpmdeviceMinCurMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set device minimum electric current measurement threshold.
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- range:0.0~32.0 represents:0~320
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmdeviceConfigEntry 2 }
|
|
|
|
--cpmdeviceMaxCurMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set device maximum electric current measurement threshold.
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- Example: range 0.0~32.0 represents: 0~320
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmdeviceConfigEntry 3 }
|
|
|
|
--cpmdeviceMinVolMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (900..2600 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set device minimum voltage measurement threshold.
|
|
-- range:90.0~260.0 represents:900~2600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmdeviceConfigEntry 4 }
|
|
|
|
--cpmdeviceMaxVolMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (900..2600 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set device maximum voltage measurement threshold.
|
|
-- range:90.0~260.0 represents:900~2600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmdeviceConfigEntry 5 }
|
|
|
|
|
|
|
|
-- Sensor
|
|
--cpmSensorValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmSensorValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's sensor value table. This table displays sensor's temperature, humidity and
|
|
-- pressure.
|
|
-- "
|
|
-- ::= { Sensor 1 }
|
|
|
|
--cpmSensorValueEntry OBJECT-TYPE
|
|
-- SYNTAX cpmSensorValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's sensor value entry containing Sensor info."
|
|
-- INDEX { cpmSensorValueIndex }
|
|
-- ::= { cpmSensorValueTable 1 }
|
|
|
|
--cpmSensorValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmSensorValueIndex
|
|
-- INTEGER,
|
|
-- cpmSensorTemperature
|
|
-- DisplayString,
|
|
-- cpmSensorHumidity
|
|
-- DisplayString,
|
|
-- cpmSensorPressure
|
|
-- DisplayString,
|
|
-- cpmSensorProperty
|
|
-- INTEGER
|
|
-- }
|
|
|
|
--cpmSensorValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..4)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of CPM's Sensor number."
|
|
-- ::= { cpmSensorValueEntry 1 }
|
|
|
|
--cpmSensorTemperature OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's Sensor Temperature value."
|
|
-- ::= { cpmSensorValueEntry 2 }
|
|
|
|
--cpmSensorHumidity OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's Sensor Humidity value."
|
|
-- ::= { cpmSensorValueEntry 3 }
|
|
|
|
--cpmSensorPressure OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's Sensor Pressure value."
|
|
-- ::= { cpmSensorValueEntry 4 }
|
|
|
|
--cpmSensorProperty OBJECT-TYPE
|
|
-- SYNTAX INTEGER { intake(1), exhaust(2) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's Sensor Property."
|
|
-- ::= { cpmSensorValueEntry 5 }
|
|
|
|
--cpmSensorThresholdTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmSensorThresholdEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's Sensor value table"
|
|
-- ::= { Sensor 2 }
|
|
|
|
--cpmSensorThresholdEntry OBJECT-TYPE
|
|
-- SYNTAX cpmSensorThresholdEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's sensor threshold entry containing sensor info."
|
|
-- INDEX { cpmSensorThresholdIndex }
|
|
-- ::= { cpmSensorThresholdTable 1 }
|
|
|
|
--cpmSensorThresholdEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmSensorThresholdIndex
|
|
-- INTEGER,
|
|
-- cpmsensorMinTempMT
|
|
-- INTEGER,
|
|
-- cpmsensorMaxTempMT
|
|
-- INTEGER,
|
|
|
|
-- cpmsensorMinHumMT
|
|
-- INTEGER,
|
|
-- cpmsensorMaxHumMT
|
|
-- INTEGER,
|
|
-- cpmsensorMinPressMT
|
|
-- INTEGER,
|
|
-- cpmsensorMaxPressMT
|
|
-- INTEGER
|
|
--sensorTempFlu
|
|
--INTEGER,
|
|
--sensorHumFlu
|
|
--INTEGER,
|
|
--sensorPressFlu
|
|
--INTEGER
|
|
-- }
|
|
|
|
--cpmSensorThresholdIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..4)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of CPM's sensor number"
|
|
-- ::= { cpmSensorThresholdEntry 1 }
|
|
|
|
--cpmsensorMinTempMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (-200..600 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor minimum temperature measurement threshold.
|
|
-- Example: range 0.0 ~ 60.0 represents 0~600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold.
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 2 }
|
|
|
|
--cpmsensorMaxTempMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (-200..600 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor maximum temperature measurement threshold.
|
|
-- Example: range 0.0 ~ 60.0 represents 0~600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 3 }
|
|
|
|
--cpmsensorMinHumMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (150..950 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor minimum humidity measurement threshold.
|
|
-- Example: range 15.0 ~ 95.0 represents 150~950
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 4 }
|
|
--cpmsensorMaxHumMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (150..950 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor maximum humidity measurement threshold.
|
|
-- Example: range 15.0 ~ 95.0 represents 150~950
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 5 }
|
|
|
|
--cpmsensorMinPressMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (-2500..2500 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor minimum pressure measurement threshold.
|
|
-- Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 6 }
|
|
|
|
--cpmsensorMaxPressMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER (-2500..2500 | -3000)
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set sensor maximum pressure measurement threshold.
|
|
-- Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmSensorThresholdEntry 7 }
|
|
|
|
|
|
-- pdu
|
|
|
|
--cpmPDUValueTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmPDUValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display the PDU's current value of CPM"
|
|
-- ::= { EnergySensor 1 }
|
|
|
|
--cpmPDUValueEntry OBJECT-TYPE
|
|
-- SYNTAX cpmPDUValueEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's monitor pdu Value entry containing outlet info."
|
|
-- INDEX { cpmPDUValueIndex }
|
|
-- ::= { cpmPDUValueTable 1 }
|
|
|
|
--cpmPDUValueEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmPDUValueIndex
|
|
-- INTEGER,
|
|
-- cpmPDUCurrent
|
|
-- DisplayString,
|
|
--cpmPDUVoltage
|
|
-- DisplayString,
|
|
--cpmPDUPower
|
|
-- DisplayString,
|
|
--cpmPDUPowerDissipation
|
|
-- DisplayString,
|
|
-- cpmPDUMaxCurrent
|
|
-- INTEGER
|
|
-- }
|
|
|
|
--cpmPDUValueIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..4)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of PDU number"
|
|
-- ::= { cpmPDUValueEntry 1 }
|
|
|
|
--cpmPDUCurrent OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's monitor PDU electric current value"
|
|
-- ::= { cpmPDUValueEntry 2 }
|
|
|
|
--cpmPDUVoltage OBJECT-TYPE
|
|
--SYNTAX DisplayString
|
|
--MAX-ACCESS read-only
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "CPM's monitor PDU voltage value"
|
|
--::= { cpmPDUValueEntry 3 }
|
|
|
|
--cpmPDUPower OBJECT-TYPE
|
|
--SYNTAX DisplayString
|
|
--MAX-ACCESS read-only
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "CPM's monitor PDU power value"
|
|
--::= { cpmPDUValueEntry 4 }
|
|
|
|
--cpmPDUPowerDissipation OBJECT-TYPE
|
|
--SYNTAX DisplayString
|
|
--MAX-ACCESS read-only
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "CPM's monitor PDU power dissipation value"
|
|
--::= { cpmPDUValueEntry 5 }
|
|
|
|
--cpmPDUMaxCurrent OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's monitor PDU Max Current value. unit: (A)"
|
|
-- ::= { cpmPDUValueEntry 6 }
|
|
|
|
--cpmBankStatus OBJECT-TYPE
|
|
-- SYNTAX INTEGER { noattached(1), attached(2) }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The status CPM device Bank status."
|
|
-- ::= { cpmPDUValueEntry 7 }
|
|
|
|
|
|
--cpmPDUConfigTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF cpmPDUConfigEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's monitor PDU configuration table"
|
|
-- ::= { EnergySensor 2 }
|
|
|
|
--cpmPDUConfigEntry OBJECT-TYPE
|
|
-- SYNTAX cpmPDUConfigEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "CPM's monitor PDU config entry containing PDU info."
|
|
-- INDEX { cpmPDUConfigIndex }
|
|
-- ::= { cpmPDUConfigTable 1 }
|
|
|
|
--cpmPDUConfigEntry ::=
|
|
-- SEQUENCE {
|
|
-- cpmPDUConfigIndex
|
|
-- INTEGER,
|
|
-- cpmPDUName
|
|
-- DisplayString,
|
|
--cpmPDUConfirmation
|
|
-- INTEGER,
|
|
--cpmPDUOnDelayTime
|
|
-- INTEGER,
|
|
--cpmPDUOffDelayTime
|
|
-- INTEGER,
|
|
--cpmPDUShutdownMethod
|
|
-- INTEGER,
|
|
--cpmPDUMAC
|
|
-- DisplayString,
|
|
--cpmPDUMinCurMT
|
|
-- INTEGER,
|
|
-- cpmPDUMaxCurMT
|
|
-- INTEGER
|
|
|
|
--cpmPDUMinVolMT
|
|
-- INTEGER,
|
|
--cpmPDUMaxVolMT
|
|
-- INTEGER,
|
|
|
|
|
|
-- }
|
|
|
|
--cpmPDUConfigIndex OBJECT-TYPE
|
|
-- SYNTAX INTEGER (1..4)
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Index of PDU number"
|
|
-- ::= { cpmPDUConfigEntry 1 }
|
|
|
|
--cpmPDUName OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set the name of pdu.
|
|
-- string length: 0~15
|
|
-- NOTE: Input string as /empty to set this object to NULL.
|
|
-- "
|
|
-- ::= { cpmPDUConfigEntry 2 }
|
|
|
|
--cpmPDUConfirmation OBJECT-TYPE
|
|
--SYNTAX INTEGER { no(1), yes(2) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the confirmation of outlet."
|
|
--::= { cpmPDUConfigEntry 3 }
|
|
|
|
--cpmPDUOnDelayTime OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..999)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the ON delay time of outlet."
|
|
--::= { cpmPDUConfigEntry 4 }
|
|
|
|
--cpmPDUOffDelayTime OBJECT-TYPE
|
|
--SYNTAX INTEGER (0..999)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the OFF delay time of outlet."
|
|
--::= { cpmPDUConfigEntry 5 }
|
|
|
|
--cpmPDUShutdownMethod OBJECT-TYPE
|
|
--SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3) }
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the shutdown mehtod of outlet."
|
|
--::= { cpmPDUConfigEntry 6 }
|
|
|
|
--cpmPDUMAC OBJECT-TYPE
|
|
--SYNTAX DisplayString
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the MAC address of ShutdownMethod.
|
|
-- string length: 12
|
|
-- "
|
|
--::= { cpmPDUConfigEntry 7 }
|
|
|
|
--cpmPDUMinCurMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set the PDU minimum electric current measurment threshold.
|
|
-- Range:0.0 ~16.0 rerpresnts 0~160
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
--
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmPDUConfigEntry 3 }
|
|
|
|
--cpmPDUMaxCurMT OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Display or set the PDU maximum electric current measurment threshold.
|
|
-- Example: range 0.0 ~16.0 represents 0~160
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
-- ::= { cpmPDUConfigEntry 4 }
|
|
|
|
--cpmPDUMinVolMT OBJECT-TYPE
|
|
--SYNTAX INTEGER (900..2600)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the outlet minimum voltage measurment threshold.
|
|
-- Range:90.0 ~260.0 represents 900~2600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { cpmPDUConfigEntry 10 }
|
|
|
|
--cpmPDUMaxVolMT OBJECT-TYPE
|
|
--SYNTAX INTEGER (900..2600)
|
|
--MAX-ACCESS read-write
|
|
--STATUS current
|
|
--DESCRIPTION
|
|
-- "Display or set the outlet maximum voltage measurment threshold.
|
|
-- Range:90.0 ~260.0 represents 900~2600
|
|
-- When this value is -3000,it indicate this is NULL.
|
|
-- When set this value to -3000, indicate set this object as NULL.
|
|
-- NOTICE:Minimum threshold should be setted smaller than Maxima threshold
|
|
-- "
|
|
--::= { cpmPDUConfigEntry 11 }
|
|
|
|
|
|
END
|