-- Avocent PM MIB
|
|
-- Copyright 2010 Avocent Corporation
|
|
-- Revision: 2.0.1
|
|
-- Last Modified: Nov 24, 2010
|
|
--------------------------------------------------------------------------------
|
|
|
|
PM-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, OBJECT-TYPE, MODULE-IDENTITY, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
InterfaceIndex, InterfaceIndexOrZero
|
|
FROM IF-MIB;
|
|
|
|
--------------------------------------------------------------------------------
|
|
-- Object Groupings
|
|
--------------------------------------------------------------------------------
|
|
|
|
--@ Note: every product type should be uniquely identified underneath the
|
|
--@ Products object group. Each product should report its unique Products
|
|
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
|
|
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
|
|
--@ IDs that have been assigned.
|
|
|
|
-- enterprises .1.3.6.1.4.1
|
|
|
|
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
|
|
|
|
pm MODULE-IDENTITY
|
|
LAST-UPDATED "201011240000Z"
|
|
ORGANIZATION "Avocent Corporation"
|
|
CONTACT-INFO "postal : Avocent Corporation
|
|
47281 Bayside Parkway
|
|
Fremont, CA 94538, USA
|
|
e-mail : Technical Support
|
|
techsupport@avocent.com"
|
|
DESCRIPTION
|
|
"This module defines the Avocent MIB extensions to
|
|
PM-PDU products."
|
|
|
|
REVISION "201011240000Z"
|
|
DESCRIPTION "Adding Power Management OIDs.
|
|
Fixed SYNTAX of some OIDs.
|
|
Updating OIDs DESCRIPTION to include not applicable values."
|
|
|
|
REVISION "201009240000Z"
|
|
DESCRIPTION "Syntax fixed to pass validation level 3."
|
|
|
|
REVISION "201004140000Z"
|
|
DESCRIPTION "Obsoleting fixed index OIDs from PDU table.
|
|
Added measurent type and alarm in PDU table.
|
|
Added missing power factor reset in outlet table.
|
|
Added sensor type and digital status in sensors table."
|
|
|
|
REVISION "200905210000Z"
|
|
DESCRIPTION "New tables for power measurements"
|
|
::= { enterprises 10418 17 }
|
|
|
|
pmProducts OBJECT IDENTIFIER ::= { pm 1 }
|
|
pmManagement OBJECT IDENTIFIER ::= { pm 2 }
|
|
--
|
|
pm1024 OBJECT IDENTIFIER ::= { pmProducts 1 } -- 10418.17.1.1
|
|
pm2003 OBJECT IDENTIFIER ::= { pmProducts 2 } -- 10418.17.1.2
|
|
pm2006 OBJECT IDENTIFIER ::= { pmProducts 3 } -- 10418.17.1.3
|
|
pm2024 OBJECT IDENTIFIER ::= { pmProducts 4 }
|
|
pm3003 OBJECT IDENTIFIER ::= { pmProducts 5 }
|
|
pm3006 OBJECT IDENTIFIER ::= { pmProducts 6 }
|
|
pm3024 OBJECT IDENTIFIER ::= { pmProducts 7 }
|
|
pm1010 OBJECT IDENTIFIER ::= { pmProducts 8 }
|
|
pm2010 OBJECT IDENTIFIER ::= { pmProducts 9 }
|
|
pm3010 OBJECT IDENTIFIER ::= { pmProducts 10 }
|
|
pm1020 OBJECT IDENTIFIER ::= { pmProducts 11 }
|
|
pm2020 OBJECT IDENTIFIER ::= { pmProducts 12 }
|
|
pm3020 OBJECT IDENTIFIER ::= { pmProducts 13 }
|
|
|
|
pmAppliance OBJECT IDENTIFIER ::= { pmManagement 1 } -- 10418.17.2.1
|
|
pmSessions OBJECT IDENTIFIER ::= { pmManagement 2 } -- 10418.17.2.2
|
|
pmPowerMgmt OBJECT IDENTIFIER ::= { pmManagement 5 } -- 10418.17.2.5
|
|
|
|
--
|
|
-- Note that traps are defined in a separate trap MIB
|
|
--
|
|
pmTrapObject OBJECT IDENTIFIER ::= { pmManagement 6 } -- 10418.17.2.6
|
|
|
|
|
|
--
|
|
-- pmAppliance
|
|
-- OBJECT IDENTIFIER ::= { pmManagement 1 } 10418.17.2.1
|
|
--
|
|
pmHostName OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance name"
|
|
::= { pmAppliance 1 }
|
|
|
|
pmProductModel OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..50) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance product model"
|
|
::= { pmAppliance 2 }
|
|
|
|
pmPartNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The part number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { pmAppliance 3 }
|
|
|
|
pmSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { pmAppliance 4 }
|
|
|
|
pmEIDNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electronic ID number (EID) of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { pmAppliance 5 }
|
|
|
|
pmBootcodeVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the bootcode of this appliance."
|
|
::= { pmAppliance 6 }
|
|
|
|
pmFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the firmware of this appliance."
|
|
::= { pmAppliance 7 }
|
|
|
|
pmReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reboot(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of reboot(2) will reboot the appliance.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reboot(2) = when SET the appliance immediately reboots."
|
|
::= { pmAppliance 9 }
|
|
|
|
--
|
|
-- pmSessions
|
|
-- OBJECT IDENTIFIER ::= { pmManagement 2 } 10418.17.2.2
|
|
--
|
|
pmActiveSessionsNumberOfSession OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of active sessions."
|
|
::= { pmSessions 1 }
|
|
|
|
pmActiveSessionsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of active sessions."
|
|
::= { pmSessions 2 }
|
|
|
|
pmActiveSessionsTableEntry OBJECT-TYPE
|
|
SYNTAX PmActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the active session"
|
|
INDEX { pmActiveSessionsTableIndex }
|
|
::= { pmActiveSessionsTable 1 }
|
|
|
|
PmActiveSessionsTableEntry ::= SEQUENCE {
|
|
pmActiveSessionsTableIndex InterfaceIndexOrZero,
|
|
pmActiveSessionsTableUser DisplayString, -- user name
|
|
pmActiveSessionsTableGroup DisplayString, -- group name
|
|
pmActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
|
|
pmActiveSessionsTableConnection DisplayString, -- type + target name
|
|
pmActiveSessionsTableSessionTime DisplayString, -- time of session
|
|
pmActiveSessionsTableFrom DisplayString, -- source of the session
|
|
pmActiveSessionsTableKill INTEGER
|
|
}
|
|
|
|
pmActiveSessionsTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique index representing an entry in this table."
|
|
::= { pmActiveSessionsTableEntry 1 }
|
|
|
|
pmActiveSessionsTableUser OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the user that opens this session."
|
|
::= { pmActiveSessionsTableEntry 2 }
|
|
|
|
pmActiveSessionsTableGroup OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the group that the user belongs to."
|
|
::= { pmActiveSessionsTableEntry 3 }
|
|
|
|
pmActiveSessionsTableType OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The session type."
|
|
::= { pmActiveSessionsTableEntry 4 }
|
|
|
|
pmActiveSessionsTableConnection OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Connection type."
|
|
::= { pmActiveSessionsTableEntry 5 }
|
|
|
|
pmActiveSessionsTableSessionTime OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time of the session"
|
|
::= { pmActiveSessionsTableEntry 6 }
|
|
|
|
pmActiveSessionsTableFrom OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The source IP address of the session."
|
|
::= { pmActiveSessionsTableEntry 7 }
|
|
|
|
pmActiveSessionsTableKill OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
killSession(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of killSession(2) will kill the session.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
killSession(2)= when SET the appliance immediately kills the session."
|
|
::= { pmActiveSessionsTableEntry 8 }
|
|
|
|
|
|
--
|
|
-- pmPowerMgmt
|
|
-- OBJECT IDENTIFIER ::= { pmManagement 5 } 10418.17.2.5
|
|
--
|
|
pmPowerMgmtNumSerialPorts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Serial Ports that has PDU connected on the appliance."
|
|
::= { pmPowerMgmt 1 }
|
|
|
|
pmPowerMgmtSerialTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
::= { pmPowerMgmt 2 }
|
|
|
|
pmPowerMgmtSerialTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
INDEX { pmPowerMgmtSerialTableIndex }
|
|
::= { pmPowerMgmtSerialTable 1 }
|
|
|
|
PmPowerMgmtSerialTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtSerialTableIndex InterfaceIndex,
|
|
pmPowerMgmtSerialTablePortNumber Integer32,
|
|
pmPowerMgmtSerialTableDeviceName DisplayString,
|
|
pmPowerMgmtSerialTableNumberPDUs Integer32,
|
|
pmPowerMgmtSerialTableBuzzer Integer32,
|
|
pmPowerMgmtSerialTableSyslog Integer32,
|
|
pmPowerMgmtSerialTableOverCurrent Integer32,
|
|
pmPowerMgmtSerialTableCycleInterval Integer32,
|
|
pmPowerMgmtSerialTablePollRate Integer32,
|
|
pmPowerMgmtSerialTablePassWord DisplayString,
|
|
pmPowerMgmtSerialTableSave INTEGER,
|
|
pmPowerMgmtSerialTableRestore INTEGER
|
|
}
|
|
|
|
pmPowerMgmtSerialTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the register."
|
|
::= { pmPowerMgmtSerialTableEntry 1 }
|
|
|
|
pmPowerMgmtSerialTablePortNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the serial port when the PDU is connected."
|
|
::= { pmPowerMgmtSerialTableEntry 2 }
|
|
|
|
pmPowerMgmtSerialTableDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device name of this serial port."
|
|
::= { pmPowerMgmtSerialTableEntry 3 }
|
|
|
|
pmPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of units connected in this serial port."
|
|
::= { pmPowerMgmtSerialTableEntry 4 }
|
|
|
|
pmPowerMgmtSerialTableBuzzer OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set/get buzzer(s) on or off for the chain.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSerialTableEntry 10 }
|
|
|
|
pmPowerMgmtSerialTableSyslog OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set/get syslog on or off for the chain.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSerialTableEntry 11 }
|
|
|
|
pmPowerMgmtSerialTableOverCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set/get over current proctection on or off for the chain.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSerialTableEntry 12 }
|
|
|
|
pmPowerMgmtSerialTableCycleInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set/get cycle interval for the chain in whole seconds.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSerialTableEntry 13 }
|
|
|
|
pmPowerMgmtSerialTablePollRate OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set/get the poll rate for the chain in whole seconds.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSerialTableEntry 14 }
|
|
|
|
pmPowerMgmtSerialTablePassWord OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set the global password for admin user"
|
|
::= { pmPowerMgmtSerialTableEntry 15 }
|
|
|
|
pmPowerMgmtSerialTableSave OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
save(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
save(2) = when SET the save command is sent to PDU."
|
|
::= { pmPowerMgmtSerialTableEntry 20 }
|
|
|
|
pmPowerMgmtSerialTableRestore OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
restore(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
restore(2) = when SET the restore command is sent to PDU."
|
|
::= { pmPowerMgmtSerialTableEntry 21 }
|
|
|
|
pmPowerMgmtPDUTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of detected PDUs."
|
|
::= { pmPowerMgmt 3 }
|
|
|
|
pmPowerMgmtPDUTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the PDU."
|
|
INDEX { pmPowerMgmtPDUTablePortNumber, pmPowerMgmtPDUTablePduIndex }
|
|
::= { pmPowerMgmtPDUTable 1 }
|
|
|
|
PmPowerMgmtPDUTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
|
|
pmPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
|
|
pmPowerMgmtPDUTablePduId DisplayString, -- PDU identification
|
|
pmPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
|
|
pmPowerMgmtPDUTableModel DisplayString, -- PDU model
|
|
pmPowerMgmtPDUTableVendor DisplayString, -- Vendor
|
|
pmPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
|
|
pmPowerMgmtPDUTableNumberOfOutlets Integer32,
|
|
pmPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
|
|
pmPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
|
|
pmPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
|
|
pmPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
|
|
pmPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
|
|
pmPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
|
|
pmPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
|
|
pmPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
|
|
pmPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
|
|
pmPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
|
|
pmPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
|
|
pmPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
|
|
pmPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
|
|
pmPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
|
|
pmPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
|
|
pmPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
|
|
pmPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
|
|
pmPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
|
|
pmPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
|
|
pmPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
|
|
pmPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
|
|
pmPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
|
|
pmPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
|
|
pmPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
|
|
pmPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
|
|
pmPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
|
|
pmPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
|
|
pmPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
|
|
pmPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (0 if single phase)
|
|
pmPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
|
|
pmPowerMgmtPDUTableNumberOfSensors Integer32, -- number of sensors
|
|
pmPowerMgmtPDUTableFactoryDefault INTEGER, -- set PDU to factory default settings
|
|
pmPowerMgmtPDUTableColdStartDelay Integer32, -- get/set PDUs cold start delay
|
|
pmPowerMgmtPDUTableReboot INTEGER, -- reboot the PDU
|
|
pmPowerMgmtPDUTableMaxCurrent Integer32, -- max value allowed for current
|
|
pmPowerMgmtPDUTableAlarm INTEGER, -- PDU alarm status
|
|
pmPowerMgmtPDUTableCurrentValue Integer32, -- actual value for current of the sensor
|
|
pmPowerMgmtPDUTableCurrentMax Integer32, -- max value for current
|
|
pmPowerMgmtPDUTableCurrentMin Integer32, -- min value for current
|
|
pmPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current
|
|
pmPowerMgmtPDUTableCurrentReset INTEGER, -- reset the current stats
|
|
pmPowerMgmtPDUTablePowerValue Integer32, -- actual value for power
|
|
pmPowerMgmtPDUTablePowerMax Integer32, -- max value for power
|
|
pmPowerMgmtPDUTablePowerMin Integer32, -- min value for power
|
|
pmPowerMgmtPDUTablePowerAvg Integer32, -- average value for power
|
|
pmPowerMgmtPDUTablePowerReset INTEGER, -- reset the power stats
|
|
pmPowerMgmtPDUTablePowerType INTEGER, -- type of power measurement
|
|
pmPowerMgmtPDUTableVoltageValue Integer32, -- actual value for voltage
|
|
pmPowerMgmtPDUTableVoltageMax Integer32, -- max value for voltage
|
|
pmPowerMgmtPDUTableVoltageMin Integer32, -- min value for voltage
|
|
pmPowerMgmtPDUTableVoltageAvg Integer32, -- average value for voltage
|
|
pmPowerMgmtPDUTableVoltageReset INTEGER, -- reset the voltage stats
|
|
pmPowerMgmtPDUTableVoltageType INTEGER, -- type of voltage measurement
|
|
pmPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
pmPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
pmPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for powerfactor
|
|
pmPowerMgmtPDUTablePowerFactorAvg Integer32, -- average value for powerfactor
|
|
pmPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset the powerfactor stats
|
|
pmPowerMgmtPDUTablePowerFactorType INTEGER, -- type of power factor measurement
|
|
pmPowerMgmtPDUTablePowerControl INTEGER, -- manage the outlets in this PDU
|
|
pmPowerMgmtPDUTableResetOCP INTEGER, -- reset the ocp (pdu wide)
|
|
pmPowerMgmtPDUTableCurrentHighCritical Integer32, -- get/set current high critical threshold
|
|
pmPowerMgmtPDUTableCurrentHighWarning Integer32, -- get/set current high warning threshold
|
|
pmPowerMgmtPDUTableCurrentLowWarning Integer32, -- get/set current low warning threshold
|
|
pmPowerMgmtPDUTableCurrentLowCritical Integer32, -- get/set current low critical threshold
|
|
pmPowerMgmtPDUTableEnergyValue Integer32, -- Energy value
|
|
pmPowerMgmtPDUTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
|
|
pmPowerMgmtPDUTableEnergyReset INTEGER -- reset energy calculation and start time to now
|
|
}
|
|
|
|
pmPowerMgmtPDUTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { pmPowerMgmtPDUTableEntry 1 }
|
|
|
|
pmPowerMgmtPDUTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { pmPowerMgmtPDUTableEntry 2 }
|
|
|
|
pmPowerMgmtPDUTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { pmPowerMgmtPDUTableEntry 3 }
|
|
|
|
pmPowerMgmtPDUTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { pmPowerMgmtPDUTableEntry 4 }
|
|
|
|
pmPowerMgmtPDUTableModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model of the PDU.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtPDUTableEntry 5 }
|
|
|
|
pmPowerMgmtPDUTableVendor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Vendor of the PDU.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtPDUTableEntry 6 }
|
|
|
|
pmPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Version of the PDU firmware.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtPDUTableEntry 7 }
|
|
|
|
pmPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets of the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 8 }
|
|
|
|
pmPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of current sensors in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 9 }
|
|
|
|
pmPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 1 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.).
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentValue,
|
|
pmPowerMgmtPhasesTableCurrentValue, or
|
|
pmPowerMgmtOutletsTableCurrentValue"
|
|
::= { pmPowerMgmtPDUTableEntry 10 }
|
|
|
|
pmPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 1 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentMax,
|
|
pmPowerMgmtPhasesTableCurrentMax, or
|
|
pmPowerMgmtOutletsTableCurrentMax"
|
|
::= { pmPowerMgmtPDUTableEntry 11 }
|
|
|
|
pmPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 2 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.).
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentValue,
|
|
pmPowerMgmtPhasesTableCurrentValue, or
|
|
pmPowerMgmtOutletsTableCurrentValue"
|
|
::= { pmPowerMgmtPDUTableEntry 12 }
|
|
|
|
pmPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 2 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentMax,
|
|
pmPowerMgmtPhasesTableCurrentMax, or
|
|
pmPowerMgmtOutletsTableCurrentMax"
|
|
::= { pmPowerMgmtPDUTableEntry 13}
|
|
|
|
pmPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 3 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentValue,
|
|
pmPowerMgmtPhasesTableCurrentValue, or
|
|
pmPowerMgmtOutletsTableCurrentValue"
|
|
::= { pmPowerMgmtPDUTableEntry 14 }
|
|
|
|
pmPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 3 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableCurrentMax,
|
|
pmPowerMgmtPhasesTableCurrentMax, or
|
|
pmPowerMgmtOutletsTableCurrentMax"
|
|
::= { pmPowerMgmtPDUTableEntry 15 }
|
|
|
|
pmPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of temperature sensors in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 16 }
|
|
|
|
pmPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { pmPowerMgmtPDUTableEntry 17 }
|
|
|
|
pmPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 18 }
|
|
|
|
pmPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { pmPowerMgmtPDUTableEntry 19 }
|
|
|
|
pmPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 20 }
|
|
|
|
pmPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { pmPowerMgmtPDUTableEntry 21 }
|
|
|
|
pmPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 22 }
|
|
|
|
pmPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of humidity sensors in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 23 }
|
|
|
|
pmPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { pmPowerMgmtPDUTableEntry 24 }
|
|
|
|
pmPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 25 }
|
|
|
|
pmPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { pmPowerMgmtPDUTableEntry 26 }
|
|
|
|
pmPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 27 }
|
|
|
|
pmPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { pmPowerMgmtPDUTableEntry 28 }
|
|
|
|
pmPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { pmPowerMgmtPDUTableEntry 29 }
|
|
|
|
pmPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of voltage sensors in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 30 }
|
|
|
|
pmPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageValue,
|
|
pmPowerMgmtPhasesTableVoltageValue, or
|
|
pmPowerMgmtOutletsTableVoltageValue"
|
|
::= { pmPowerMgmtPDUTableEntry 31 }
|
|
|
|
pmPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageMax,
|
|
pmPowerMgmtPhasesTableVoltageMax, or
|
|
pmPowerMgmtOutletsTableVoltageMax"
|
|
::= { pmPowerMgmtPDUTableEntry 32 }
|
|
|
|
pmPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageValue,
|
|
pmPowerMgmtPhasesTableVoltageValue, or
|
|
pmPowerMgmtOutletsTableVoltageValue"
|
|
::= { pmPowerMgmtPDUTableEntry 33 }
|
|
|
|
pmPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageMax,
|
|
pmPowerMgmtPhasesTableVoltageMax, or
|
|
pmPowerMgmtOutletsTableVoltageMax"
|
|
::= { pmPowerMgmtPDUTableEntry 34 }
|
|
|
|
pmPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageValue,
|
|
pmPowerMgmtPhasesTableVoltageValue, or
|
|
pmPowerMgmtOutletsTableVoltageValue"
|
|
::= { pmPowerMgmtPDUTableEntry 35 }
|
|
|
|
pmPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage.
|
|
This OID is obsoleted. The value can be retrieved
|
|
from pmPowerMgmtPDUTableVoltageMax,
|
|
pmPowerMgmtPhasesTableVoltageMax, or
|
|
pmPowerMgmtOutletsTableVoltageMax"
|
|
::= { pmPowerMgmtPDUTableEntry 36 }
|
|
|
|
pmPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of phases of the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 37 }
|
|
|
|
pmPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of banks in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 38 }
|
|
|
|
pmPowerMgmtPDUTableNumberOfSensors OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of sensors in the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 40 }
|
|
|
|
pmPowerMgmtPDUTableFactoryDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of 2 will set the PDU to factory default settings.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the factory default command is sent to the PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 41 }
|
|
|
|
pmPowerMgmtPDUTableColdStartDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDUs cold start delay in whole seconds (0-60).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 42 }
|
|
|
|
pmPowerMgmtPDUTableReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reboot(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reboot(2) = when SET the reboot command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 43 }
|
|
|
|
pmPowerMgmtPDUTableMaxCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of current allowed in the PDU (A x 10)."
|
|
::= { pmPowerMgmtPDUTableEntry 44 }
|
|
|
|
pmPowerMgmtPDUTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the PDU alarm status.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 45 }
|
|
|
|
--@ Note: Intentionally left space for future expansion (thanks!)
|
|
pmPowerMgmtPDUTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current in the PDU (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 50 }
|
|
|
|
pmPowerMgmtPDUTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of current in the PDU (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 51 }
|
|
|
|
pmPowerMgmtPDUTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of current in the PDU (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 52 }
|
|
|
|
pmPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of current in the PDU (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 53 }
|
|
|
|
pmPowerMgmtPDUTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 54 }
|
|
|
|
pmPowerMgmtPDUTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power in the PDU (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 60 }
|
|
|
|
pmPowerMgmtPDUTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power in the PDU (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 61 }
|
|
|
|
pmPowerMgmtPDUTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power in the PDU (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 62 }
|
|
|
|
pmPowerMgmtPDUTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power in the PDU (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 63 }
|
|
|
|
pmPowerMgmtPDUTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 64 }
|
|
|
|
pmPowerMgmtPDUTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 65 }
|
|
|
|
pmPowerMgmtPDUTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage in the PDU (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 70 }
|
|
|
|
pmPowerMgmtPDUTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of voltage in the PDU (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 71 }
|
|
|
|
pmPowerMgmtPDUTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of voltage in the PDU (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 72 }
|
|
|
|
pmPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of voltage in the PDU (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 73 }
|
|
|
|
pmPowerMgmtPDUTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 74 }
|
|
|
|
pmPowerMgmtPDUTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 75 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in the PDU (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 80 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power factor in the PDU (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 81 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power factor in the PDU (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 82 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power factor in the PDU (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 83 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 84 }
|
|
|
|
pmPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 85 }
|
|
|
|
pmPowerMgmtPDUTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-4) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 90 }
|
|
|
|
pmPowerMgmtPDUTableResetOCP OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 91 }
|
|
|
|
pmPowerMgmtPDUTableCurrentHighCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet high critical (alarm) current threshold (A x 10).
|
|
Set fails if value is lower that CurrentHighWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 100 }
|
|
|
|
pmPowerMgmtPDUTableCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet high warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 101 }
|
|
|
|
pmPowerMgmtPDUTableCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet low warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 102 }
|
|
|
|
pmPowerMgmtPDUTableCurrentLowCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet low critical current threshold (A x 10).
|
|
Set fails if value is higher than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 103 }
|
|
|
|
pmPowerMgmtPDUTableEnergyValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"pdu energy value (Wh).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPDUTableEntry 105 }
|
|
|
|
pmPowerMgmtPDUTableEnergyStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"time at which energy calculation commenced (ISO8601 format).
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtPDUTableEntry 106 }
|
|
|
|
pmPowerMgmtPDUTableEnergyReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPDUTableEntry 107 }
|
|
|
|
pmPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets managed by the appliance."
|
|
::= { pmPowerMgmt 4 }
|
|
|
|
pmPowerMgmtOutletsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about outlets."
|
|
::= { pmPowerMgmt 5 }
|
|
|
|
pmPowerMgmtOutletsTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the outlet."
|
|
INDEX { pmPowerMgmtOutletsTablePortNumber,
|
|
pmPowerMgmtOutletsTablePduNumber,
|
|
pmPowerMgmtOutletsTableNumber }
|
|
::= { pmPowerMgmtOutletsTable 1 }
|
|
|
|
PmPowerMgmtOutletsTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
|
|
pmPowerMgmtOutletsTablePduNumber InterfaceIndex,
|
|
pmPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
|
|
pmPowerMgmtOutletsTableName DisplayString, -- outlet name
|
|
pmPowerMgmtOutletsTableStatus INTEGER, -- outlet status
|
|
pmPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
|
|
pmPowerMgmtOutletsTablePortName DisplayString, -- serial port name
|
|
pmPowerMgmtOutletsTablePduId DisplayString, -- PDU ID
|
|
pmPowerMgmtOutletsTablePostOnDelay Integer32, -- outlet post on delay delay/post power on
|
|
pmPowerMgmtOutletsTablePostOffDelay Integer32, -- outlet post off delay/post power off
|
|
pmPowerMgmtOutletsTableAlarm INTEGER, -- outlet alarm status
|
|
pmPowerMgmtOutletsTableCurrentValue Integer32, -- actual value for current of the sensor
|
|
pmPowerMgmtOutletsTableCurrentMax Integer32, -- max value for current
|
|
pmPowerMgmtOutletsTableCurrentMin Integer32, -- min value for current
|
|
pmPowerMgmtOutletsTableCurrentAvg Integer32, -- average value for current
|
|
pmPowerMgmtOutletsTableCurrentReset INTEGER, -- reset the current stats
|
|
pmPowerMgmtOutletsTablePowerValue Integer32, -- actual value for power
|
|
pmPowerMgmtOutletsTablePowerMax Integer32, -- max value for power
|
|
pmPowerMgmtOutletsTablePowerMin Integer32, -- min value for power
|
|
pmPowerMgmtOutletsTablePowerAvg Integer32, -- average value for power
|
|
pmPowerMgmtOutletsTablePowerReset INTEGER, -- reset the power stats
|
|
pmPowerMgmtOutletsTablePowerType INTEGER, -- power type
|
|
pmPowerMgmtOutletsTableVoltageValue Integer32, -- actual value for voltage
|
|
pmPowerMgmtOutletsTableVoltageMax Integer32, -- max value for voltage
|
|
pmPowerMgmtOutletsTableVoltageMin Integer32, -- min value for voltage
|
|
pmPowerMgmtOutletsTableVoltageAvg Integer32, -- average value for voltage
|
|
pmPowerMgmtOutletsTableVoltageReset INTEGER, -- reset the voltage stats
|
|
pmPowerMgmtOutletsTableVoltageType INTEGER, -- type of voltage measurement
|
|
pmPowerMgmtOutletsTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
pmPowerMgmtOutletsTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
pmPowerMgmtOutletsTablePowerFactorMin Integer32, -- min value for powerfactor
|
|
pmPowerMgmtOutletsTablePowerFactorAvg Integer32, -- average value for powerfactor
|
|
pmPowerMgmtOutletsTablePowerFactorReset INTEGER, -- reset the powerfactor stats
|
|
pmPowerMgmtOutletsTablePowerFactorType INTEGER, -- power factor type
|
|
pmPowerMgmtOutletsTableCurrentHighCritical Integer32, -- outlet current high critical threshold
|
|
pmPowerMgmtOutletsTableCurrentHighWarning Integer32, -- outlet current high warning threshold
|
|
pmPowerMgmtOutletsTableCurrentLowWarning Integer32, -- outlet current low warning threshold
|
|
pmPowerMgmtOutletsTableCurrentLowCritical Integer32, -- outlet current low critical threshold
|
|
pmPowerMgmtOutletsTableEnergyValue Integer32, -- Energy value
|
|
pmPowerMgmtOutletsTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
|
|
pmPowerMgmtOutletsTableEnergyReset INTEGER -- reset energy calculation and start time to now
|
|
}
|
|
|
|
pmPowerMgmtOutletsTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { pmPowerMgmtOutletsTableEntry 1 }
|
|
|
|
pmPowerMgmtOutletsTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { pmPowerMgmtOutletsTableEntry 2 }
|
|
|
|
pmPowerMgmtOutletsTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the outlet in the PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 3 }
|
|
|
|
pmPowerMgmtOutletsTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the outlet."
|
|
::= { pmPowerMgmtOutletsTableEntry 4 }
|
|
|
|
pmPowerMgmtOutletsTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2),
|
|
offLocked(3),
|
|
onLocked(4),
|
|
offCycle(5),
|
|
onPendingOff(6),
|
|
offPendingOn(7),
|
|
onPendingCycle(8),
|
|
notSet(9),
|
|
onFixed(10),
|
|
offShutdown(11),
|
|
tripped(12)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the outlet.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 5 }
|
|
|
|
pmPowerMgmtOutletsTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4),
|
|
powerLock(5),
|
|
powerUnlock(6)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-6) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU.
|
|
powerLock(5)= when SET the power lock command is sent to PDU.
|
|
powerUnlock(6)=when SET the power unlock command is sent to PDU.
|
|
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
|
|
::= { pmPowerMgmtOutletsTableEntry 6 }
|
|
|
|
pmPowerMgmtOutletsTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { pmPowerMgmtOutletsTableEntry 7 }
|
|
|
|
pmPowerMgmtOutletsTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { pmPowerMgmtOutletsTableEntry 8 }
|
|
|
|
pmPowerMgmtOutletsTablePostOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"post on delay for the outlet (seconds x 10)
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 9 }
|
|
|
|
pmPowerMgmtOutletsTablePostOffDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"post off delay for the outlet (seconds x 10)
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 10 }
|
|
|
|
pmPowerMgmtOutletsTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the outlet alarm status.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 45 }
|
|
|
|
--@ Note: Intentionally left space for future expansion
|
|
pmPowerMgmtOutletsTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current in the outlet (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 50 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of current in the outlet (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 51 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of current in the outlet (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 52 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of current in the outlet (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 53 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 54 }
|
|
|
|
pmPowerMgmtOutletsTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power in the outlet (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 60 }
|
|
|
|
pmPowerMgmtOutletsTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power in the outlet (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 61 }
|
|
|
|
pmPowerMgmtOutletsTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power in the outlet (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 62 }
|
|
|
|
pmPowerMgmtOutletsTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power in the outlet (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 63 }
|
|
|
|
pmPowerMgmtOutletsTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 64 }
|
|
|
|
pmPowerMgmtOutletsTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 65 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage in the outlet (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 70 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of voltage in the outlet (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 71 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of voltage in the outlet (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 72 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of voltage in the outlet (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 73 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 74 }
|
|
|
|
pmPowerMgmtOutletsTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 75 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in the outlet (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 80 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power factor in the outlet (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 81 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power factor in the outlet (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 82 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power factor in the outlet (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 83 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 84 }
|
|
|
|
pmPowerMgmtOutletsTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 85 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentHighCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet high critical (alarm) current threshold (A x 10).
|
|
Set fails if value is lower that CurrentHighWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 100 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet high warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 101 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet low warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 102 }
|
|
|
|
pmPowerMgmtOutletsTableCurrentLowCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet low critical current threshold (A x 10).
|
|
Set fails if value is higher than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 103 }
|
|
|
|
pmPowerMgmtOutletsTableEnergyValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"outlet energy value (Wh).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtOutletsTableEntry 105 }
|
|
|
|
pmPowerMgmtOutletsTableEnergyStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"time at which energy calculation commenced (ISO8601 format).
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtOutletsTableEntry 106 }
|
|
|
|
pmPowerMgmtOutletsTableEnergyReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtOutletsTableEntry 107 }
|
|
|
|
pmPowerMgmtNumberOfOutletGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of configured group of outlets."
|
|
::= { pmPowerMgmt 6 }
|
|
|
|
pmPowerMgmtGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about group of outlets."
|
|
::= { pmPowerMgmt 7 }
|
|
|
|
pmPowerMgmtGroupTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about group of outlets."
|
|
INDEX { pmPowerMgmtGroupTableIndex }
|
|
::= { pmPowerMgmtGroupTable 1 }
|
|
|
|
PmPowerMgmtGroupTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtGroupTableIndex InterfaceIndexOrZero,
|
|
pmPowerMgmtGroupTableName DisplayString, -- group name
|
|
pmPowerMgmtGroupTableStatus INTEGER, -- group status
|
|
pmPowerMgmtGroupTablePowerControl INTEGER -- manage the group
|
|
}
|
|
|
|
pmPowerMgmtGroupTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of the group."
|
|
::= { pmPowerMgmtGroupTableEntry 1 }
|
|
|
|
pmPowerMgmtGroupTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the group of outlets."
|
|
::= { pmPowerMgmtGroupTableEntry 2 }
|
|
|
|
pmPowerMgmtGroupTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the group of outlet."
|
|
::= { pmPowerMgmtGroupTableEntry 3 }
|
|
|
|
pmPowerMgmtGroupTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-4) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU."
|
|
::= { pmPowerMgmtGroupTableEntry 4 }
|
|
|
|
pmPowerMgmtTotalNumberOfPhases OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of phases managed by the appliance."
|
|
::= { pmPowerMgmt 8 }
|
|
|
|
pmPowerMgmtPhasesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about phases."
|
|
::= { pmPowerMgmt 9 }
|
|
|
|
pmPowerMgmtPhasesTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the phases."
|
|
INDEX { pmPowerMgmtPhasesTablePortNumber,
|
|
pmPowerMgmtPhasesTablePduNumber,
|
|
pmPowerMgmtPhasesTableNumber }
|
|
::= { pmPowerMgmtPhasesTable 1 }
|
|
|
|
PmPowerMgmtPhasesTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtPhasesTablePortNumber InterfaceIndex, -- serial port #
|
|
pmPowerMgmtPhasesTablePduNumber InterfaceIndex,
|
|
pmPowerMgmtPhasesTableNumber InterfaceIndex, -- phase number in PDU
|
|
pmPowerMgmtPhasesTableName DisplayString, -- phase sysname
|
|
pmPowerMgmtPhasesTablePortName DisplayString, -- serial port name
|
|
pmPowerMgmtPhasesTablePduId DisplayString, -- PDU ID
|
|
pmPowerMgmtPhasesTableAlarm INTEGER, -- phase alarm status
|
|
pmPowerMgmtPhasesTableCurrentValue Integer32, -- actual value for current of the sensor
|
|
pmPowerMgmtPhasesTableCurrentMax Integer32, -- max value for current
|
|
pmPowerMgmtPhasesTableCurrentMin Integer32, -- min value for current
|
|
pmPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current
|
|
pmPowerMgmtPhasesTableCurrentReset INTEGER, -- reset the current stats
|
|
pmPowerMgmtPhasesTablePowerValue Integer32, -- actual value for power
|
|
pmPowerMgmtPhasesTablePowerMax Integer32, -- max value for power
|
|
pmPowerMgmtPhasesTablePowerMin Integer32, -- min value for power
|
|
pmPowerMgmtPhasesTablePowerAvg Integer32, -- average value for power
|
|
pmPowerMgmtPhasesTablePowerReset INTEGER, -- reset the power stats
|
|
pmPowerMgmtPhasesTablePowerType INTEGER, -- power type
|
|
pmPowerMgmtPhasesTableVoltageValue Integer32, -- actual value for voltage
|
|
pmPowerMgmtPhasesTableVoltageMax Integer32, -- max value for voltage
|
|
pmPowerMgmtPhasesTableVoltageMin Integer32, -- min value for voltage
|
|
pmPowerMgmtPhasesTableVoltageAvg Integer32, -- average value for voltage
|
|
pmPowerMgmtPhasesTableVoltageReset INTEGER, -- reset the voltage stats
|
|
pmPowerMgmtPhasesTableVoltageType INTEGER, -- voltage type
|
|
pmPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
pmPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
pmPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for powerfactor
|
|
pmPowerMgmtPhasesTablePowerFactorAvg Integer32, -- average value for powerfactor
|
|
pmPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset the powerfactor stats
|
|
pmPowerMgmtPhasesTablePowerFactorType INTEGER, -- power factor type
|
|
pmPowerMgmtPhasesTableCurrentHighCritical Integer32, -- outlet current high critical threshold
|
|
pmPowerMgmtPhasesTableCurrentHighWarning Integer32, -- outlet current high warning threshold
|
|
pmPowerMgmtPhasesTableCurrentLowWarning Integer32, -- outlet current low warning threshold
|
|
pmPowerMgmtPhasesTableCurrentLowCritical Integer32 -- outlet current low critical threshold
|
|
}
|
|
|
|
pmPowerMgmtPhasesTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { pmPowerMgmtPhasesTableEntry 1 }
|
|
|
|
pmPowerMgmtPhasesTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { pmPowerMgmtPhasesTableEntry 2 }
|
|
|
|
pmPowerMgmtPhasesTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the phase in the PDU."
|
|
::= { pmPowerMgmtPhasesTableEntry 3 }
|
|
|
|
pmPowerMgmtPhasesTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the phase.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtPhasesTableEntry 4 }
|
|
|
|
pmPowerMgmtPhasesTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { pmPowerMgmtPhasesTableEntry 5 }
|
|
|
|
pmPowerMgmtPhasesTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { pmPowerMgmtPhasesTableEntry 6 }
|
|
|
|
pmPowerMgmtPhasesTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the phase alarm status.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 45 }
|
|
|
|
--@ Note: Intentionally left space for future expansion
|
|
pmPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current in the phase (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 50 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of current in the phase (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 51 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of current in the phase (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 52 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of current in the phase (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 53 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPhasesTableEntry 54 }
|
|
|
|
pmPowerMgmtPhasesTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power in the phase (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 60 }
|
|
|
|
pmPowerMgmtPhasesTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power in the phase (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 61 }
|
|
|
|
pmPowerMgmtPhasesTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power in the phase (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 62 }
|
|
|
|
pmPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power in the phase (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 63 }
|
|
|
|
pmPowerMgmtPhasesTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPhasesTableEntry 64 }
|
|
|
|
pmPowerMgmtPhasesTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 65 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage in the phase (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 70 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of voltage in the phase (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 71 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of voltage in the phase (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 72 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of voltage in the phase (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 73 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPhasesTableEntry 74 }
|
|
|
|
pmPowerMgmtPhasesTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 75 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in the phase (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 80 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power factor in the phase (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 81 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power factor in the phase (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 82 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power factor in the phase (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 83 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtPhasesTableEntry 84 }
|
|
|
|
pmPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 85 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentHighCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase high critical (alarm) current threshold (A x 10).
|
|
Set fails if value is lower that CurrentHighWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 100 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase high warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 101 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase low warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 102 }
|
|
|
|
pmPowerMgmtPhasesTableCurrentLowCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase low critical current threshold (A x 10).
|
|
Set fails if value is higher than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtPhasesTableEntry 103 }
|
|
|
|
--@ BANKS
|
|
|
|
pmPowerMgmtTotalNumberOfBanks OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of banks managed by the appliance."
|
|
::= { pmPowerMgmt 10 }
|
|
|
|
pmPowerMgmtBanksTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about banks."
|
|
::= { pmPowerMgmt 11 }
|
|
|
|
pmPowerMgmtBanksTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the banks."
|
|
INDEX { pmPowerMgmtBanksTablePortNumber,
|
|
pmPowerMgmtBanksTablePduNumber,
|
|
pmPowerMgmtBanksTableNumber }
|
|
::= { pmPowerMgmtBanksTable 1 }
|
|
|
|
PmPowerMgmtBanksTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtBanksTablePortNumber InterfaceIndex, -- serial port #
|
|
pmPowerMgmtBanksTablePduNumber InterfaceIndex,
|
|
pmPowerMgmtBanksTableNumber InterfaceIndex, -- bank number in PDU
|
|
pmPowerMgmtBanksTableName DisplayString, -- bank sysname
|
|
pmPowerMgmtBanksTablePortName DisplayString, -- serial port name
|
|
pmPowerMgmtBanksTablePduId DisplayString, -- PDU ID
|
|
pmPowerMgmtBanksTableAlarm INTEGER, -- bank alarm status
|
|
pmPowerMgmtBanksTableCurrentValue Integer32, -- actual value for current of the sensor
|
|
pmPowerMgmtBanksTableCurrentMax Integer32, -- max value for current
|
|
pmPowerMgmtBanksTableCurrentMin Integer32, -- min value for current
|
|
pmPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current
|
|
pmPowerMgmtBanksTableCurrentReset INTEGER, -- reset current stats
|
|
pmPowerMgmtBanksTablePowerValue Integer32, -- actual value for power
|
|
pmPowerMgmtBanksTablePowerMax Integer32, -- max value for power
|
|
pmPowerMgmtBanksTablePowerMin Integer32, -- min value for power
|
|
pmPowerMgmtBanksTablePowerAvg Integer32, -- average value for power
|
|
pmPowerMgmtBanksTablePowerReset INTEGER, -- reset power stats
|
|
pmPowerMgmtBanksTablePowerType INTEGER, -- power type
|
|
pmPowerMgmtBanksTableVoltageValue Integer32, -- actual value for voltage
|
|
pmPowerMgmtBanksTableVoltageMax Integer32, -- max value for voltage
|
|
pmPowerMgmtBanksTableVoltageMin Integer32, -- min value for voltage
|
|
pmPowerMgmtBanksTableVoltageAvg Integer32, -- average value for voltage
|
|
pmPowerMgmtBanksTableVoltageReset INTEGER, -- reset voltage stats
|
|
pmPowerMgmtBanksTableVoltageType INTEGER, -- voltage type
|
|
pmPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value for powerfactor
|
|
pmPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for powerfactor
|
|
pmPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for powerfactor
|
|
pmPowerMgmtBanksTablePowerFactorAvg Integer32, -- average value for powerfactor
|
|
pmPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset powerfactor stats
|
|
pmPowerMgmtBanksTablePowerFactorType INTEGER, -- power factor type
|
|
pmPowerMgmtBanksTableCurrentHighCritical Integer32, -- outlet current high critical threshold
|
|
pmPowerMgmtBanksTableCurrentHighWarning Integer32, -- outlet current high warning threshold
|
|
pmPowerMgmtBanksTableCurrentLowWarning Integer32, -- outlet current low warning threshold
|
|
pmPowerMgmtBanksTableCurrentLowCritical Integer32, -- outlet current low critical threshold
|
|
pmPowerMgmtBanksTableEnergyValue Integer32, -- Energy value
|
|
pmPowerMgmtBanksTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
|
|
pmPowerMgmtBanksTableEnergyReset INTEGER -- reset energy calculation and start time to now
|
|
}
|
|
|
|
pmPowerMgmtBanksTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { pmPowerMgmtBanksTableEntry 1 }
|
|
|
|
pmPowerMgmtBanksTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { pmPowerMgmtBanksTableEntry 2 }
|
|
|
|
pmPowerMgmtBanksTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the bank in the PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 3 }
|
|
|
|
pmPowerMgmtBanksTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the bank."
|
|
::= { pmPowerMgmtBanksTableEntry 4 }
|
|
|
|
pmPowerMgmtBanksTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { pmPowerMgmtBanksTableEntry 5 }
|
|
|
|
pmPowerMgmtBanksTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { pmPowerMgmtBanksTableEntry 6 }
|
|
|
|
pmPowerMgmtBanksTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the bank alarm status.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 45 }
|
|
|
|
|
|
--@ Note: Intentionally left space for future expansion
|
|
pmPowerMgmtBanksTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current in the bank (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 50 }
|
|
|
|
pmPowerMgmtBanksTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of current in the bank (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 51 }
|
|
|
|
pmPowerMgmtBanksTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of current in the bank (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 52 }
|
|
|
|
pmPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of current in the bank (A x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 53 }
|
|
|
|
pmPowerMgmtBanksTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 54 }
|
|
|
|
pmPowerMgmtBanksTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power in the bank (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 60 }
|
|
|
|
pmPowerMgmtBanksTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power in the bank (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 61 }
|
|
|
|
pmPowerMgmtBanksTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power in the bank (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 62 }
|
|
|
|
pmPowerMgmtBanksTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power in the bank (W x 10).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 63 }
|
|
|
|
pmPowerMgmtBanksTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 64 }
|
|
|
|
pmPowerMgmtBanksTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 65 }
|
|
|
|
pmPowerMgmtBanksTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage in the bank (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 70 }
|
|
|
|
pmPowerMgmtBanksTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of voltage in the bank (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 71 }
|
|
|
|
pmPowerMgmtBanksTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of voltage in the bank (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 72 }
|
|
|
|
pmPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of voltage in the bank (V).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 73 }
|
|
|
|
pmPowerMgmtBanksTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 74 }
|
|
|
|
pmPowerMgmtBanksTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 75 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in the bank (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 80 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of power factor in the bank (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 81 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of power factor in the bank (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 82 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of power factor in the bank (Pf x 100).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 83 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 84 }
|
|
|
|
pmPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
measured (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 85 }
|
|
|
|
pmPowerMgmtBanksTableCurrentHighCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"bank high critical (alarm) current threshold (A x 10).
|
|
Set fails if value is lower that CurrentHighWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 100 }
|
|
|
|
pmPowerMgmtBanksTableCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"bank high warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 101 }
|
|
|
|
pmPowerMgmtBanksTableCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"bank low warning current threshold (A x 10).
|
|
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 102 }
|
|
|
|
pmPowerMgmtBanksTableCurrentLowCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"bank low critical current threshold (A x 10).
|
|
Set fails if value is higher than CurrentLowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 103 }
|
|
|
|
pmPowerMgmtBanksTableEnergyValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"bank energy value (Wh).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtBanksTableEntry 105 }
|
|
|
|
pmPowerMgmtBanksTableEnergyStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"time at which energy calculation commenced (ISO8601 format).
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtBanksTableEntry 106 }
|
|
|
|
pmPowerMgmtBanksTableEnergyReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to PDU."
|
|
::= { pmPowerMgmtBanksTableEntry 107 }
|
|
|
|
--@ Sensors
|
|
|
|
pmPowerMgmtTotalNumberOfSensors OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Sensors managed by the appliance."
|
|
::= { pmPowerMgmt 12 }
|
|
|
|
pmPowerMgmtSensorsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PmPowerMgmtSensorsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about sensors."
|
|
::= { pmPowerMgmt 13 }
|
|
|
|
pmPowerMgmtSensorsTableEntry OBJECT-TYPE
|
|
SYNTAX PmPowerMgmtSensorsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the sensors."
|
|
INDEX { pmPowerMgmtSensorsTablePortNumber,
|
|
pmPowerMgmtSensorsTablePduNumber,
|
|
pmPowerMgmtSensorsTableNumber }
|
|
::= { pmPowerMgmtSensorsTable 1 }
|
|
|
|
PmPowerMgmtSensorsTableEntry ::= SEQUENCE {
|
|
pmPowerMgmtSensorsTablePortNumber InterfaceIndex, -- serial port #
|
|
pmPowerMgmtSensorsTablePduNumber InterfaceIndex,
|
|
pmPowerMgmtSensorsTableNumber InterfaceIndex, -- sensor number in PDU
|
|
pmPowerMgmtSensorsTableName DisplayString, -- sensor name
|
|
pmPowerMgmtSensorsTablePortName DisplayString, -- serial port name
|
|
pmPowerMgmtSensorsTablePduId DisplayString, -- PDU ID
|
|
pmPowerMgmtSensorsTableType INTEGER, -- sensor type
|
|
pmPowerMgmtSensorsTableStatus INTEGER, -- digital sensor status
|
|
pmPowerMgmtSensorsTableValue DisplayString, -- actual value for current of the sensor
|
|
pmPowerMgmtSensorsTableValueMax DisplayString, -- max value for current
|
|
pmPowerMgmtSensorsTableValueMin DisplayString, -- min value for current
|
|
pmPowerMgmtSensorsTableValueAvg DisplayString, -- average value for current
|
|
pmPowerMgmtSensorsTableValueInt Integer32, -- actual value for current of the sensor
|
|
pmPowerMgmtSensorsTableValueMaxInt Integer32, -- max value for current
|
|
pmPowerMgmtSensorsTableValueMinInt Integer32, -- min value for current
|
|
pmPowerMgmtSensorsTableValueAvgInt Integer32, -- average value for current
|
|
pmPowerMgmtSensorsTableValueReset INTEGER, -- reset current stats
|
|
pmPowerMgmtSensorsTableHighCritical Integer32, -- set/get sensor high critical threshold
|
|
pmPowerMgmtSensorsTableHighWarning Integer32, -- set/get sensor high warning threshold
|
|
pmPowerMgmtSensorsTableLowWarning Integer32, -- set/get sensor low warning threshold
|
|
pmPowerMgmtSensorsTableLowCritical Integer32, -- set/get sensor low critical threshold
|
|
pmPowerMgmtSensorsTableUnit INTEGER, -- set/get sensor unit of measurement
|
|
pmPowerMgmtSensorsTableHighCriticalC Integer32, -- get sensor high critical threshold
|
|
pmPowerMgmtSensorsTableHighWarningC Integer32, -- get sensor high warning threshold
|
|
pmPowerMgmtSensorsTableLowWarningC Integer32, -- get sensor low warning threshold
|
|
pmPowerMgmtSensorsTableLowCriticalC Integer32, -- get sensor low critical threshold
|
|
pmPowerMgmtSensorsTableHighCriticalF Integer32, -- get sensor high critical threshold
|
|
pmPowerMgmtSensorsTableHighWarningF Integer32, -- get sensor high warning threshold
|
|
pmPowerMgmtSensorsTableLowWarningF Integer32, -- get sensor low warning threshold
|
|
pmPowerMgmtSensorsTableLowCriticalF Integer32 -- get sensor low critical threshold
|
|
}
|
|
|
|
pmPowerMgmtSensorsTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { pmPowerMgmtSensorsTableEntry 1 }
|
|
|
|
pmPowerMgmtSensorsTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { pmPowerMgmtSensorsTableEntry 2 }
|
|
|
|
pmPowerMgmtSensorsTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the sensor in the PDU."
|
|
::= { pmPowerMgmtSensorsTableEntry 3 }
|
|
|
|
pmPowerMgmtSensorsTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the sensor."
|
|
::= { pmPowerMgmtSensorsTableEntry 4 }
|
|
|
|
pmPowerMgmtSensorsTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { pmPowerMgmtSensorsTableEntry 5 }
|
|
|
|
pmPowerMgmtSensorsTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { pmPowerMgmtSensorsTableEntry 6 }
|
|
|
|
pmPowerMgmtSensorsTableType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temp-internal (1),
|
|
temperature (2),
|
|
humidity (3),
|
|
air-flow (4),
|
|
smoke (5),
|
|
dry-concact (6),
|
|
water-level (7),
|
|
motion (8),
|
|
unplugged (9),
|
|
unknown (10)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of environmental monitor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 7 }
|
|
|
|
pmPowerMgmtSensorsTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
triggered(2),
|
|
not-applicable(3),
|
|
opened(4),
|
|
closed(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 8 }
|
|
|
|
|
|
--@ Note: Intentionally left space for future expansion
|
|
pmPowerMgmtSensorsTableValue OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of the sensor.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtSensorsTableEntry 20 }
|
|
|
|
pmPowerMgmtSensorsTableValueMax OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of the sensor.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtSensorsTableEntry 21 }
|
|
|
|
pmPowerMgmtSensorsTableValueMin OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of the sensor.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtSensorsTableEntry 22 }
|
|
|
|
pmPowerMgmtSensorsTableValueAvg OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of the sensor.
|
|
Returns N/A if not applicable."
|
|
::= { pmPowerMgmtSensorsTableEntry 23 }
|
|
|
|
pmPowerMgmtSensorsTableValueInt OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of the sensor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 25 }
|
|
|
|
pmPowerMgmtSensorsTableValueMaxInt OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum value of the sensor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 26 }
|
|
|
|
pmPowerMgmtSensorsTableValueMinInt OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum value of the sensor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 27 }
|
|
|
|
pmPowerMgmtSensorsTableValueAvgInt OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value of the sensor.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 28 }
|
|
|
|
pmPowerMgmtSensorsTableValueReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reset(2) = when SET the reset command is sent to sensor."
|
|
::= { pmPowerMgmtSensorsTableEntry 30 }
|
|
|
|
pmPowerMgmtSensorsTableHighCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
|
|
Set fails if value is lower that CurrentHighWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 40 }
|
|
|
|
pmPowerMgmtSensorsTableHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
|
|
Set fails if value is higher than HighCritical or lower than LowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 41 }
|
|
|
|
pmPowerMgmtSensorsTableLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
|
|
Set fails if value is higher than HighWarning or lower than LowCritical.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 42 }
|
|
|
|
pmPowerMgmtSensorsTableLowCritical OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
|
|
Set fails if value is higher than LowWarning.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 43 }
|
|
|
|
pmPowerMgmtSensorsTableUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
undefined (1),
|
|
fahrenheit (2),
|
|
celsius (3),
|
|
percent (4),
|
|
afu (5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor unit.
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 45 }
|
|
|
|
pmPowerMgmtSensorsTableHighCriticalC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high critical (alarm) threshold (Celcius x 10).
|
|
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 50 }
|
|
|
|
pmPowerMgmtSensorsTableHighWarningC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high warning threshold (Celcius x 10).
|
|
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 51 }
|
|
|
|
pmPowerMgmtSensorsTableLowWarningC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low warning threshold (Celcius x 10).
|
|
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 52 }
|
|
|
|
pmPowerMgmtSensorsTableLowCriticalC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low critical threshold (Celcius x 10).
|
|
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 53 }
|
|
|
|
pmPowerMgmtSensorsTableHighCriticalF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high critical (alarm) threshold (Fahrenheit x 10).
|
|
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 60 }
|
|
|
|
pmPowerMgmtSensorsTableHighWarningF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor high warning threshold (Fahrenheit x 10).
|
|
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 61 }
|
|
|
|
pmPowerMgmtSensorsTableLowWarningF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low warning threshold (Fahrenheit x 10).
|
|
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 62 }
|
|
|
|
pmPowerMgmtSensorsTableLowCriticalF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"sensor low critical threshold (Fahrenheit x 10).
|
|
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
|
|
Returns 0 if not supported."
|
|
::= { pmPowerMgmtSensorsTableEntry 63 }
|
|
|
|
END
|