mibs/MIBS/avtech/ROOMALERT24E-MIB
2023-12-05 12:25:34 +01:00

628 lines
21 KiB
Plaintext

--
--defines ROOMALERT24E-MIB for SNMP agent extension of Room Alert 24E
--Contents: Global Registration Module
-- Room Alert OIDs - Enterprise 20916
--Version: 1.0.2
--Date: 11 September 2007
--Developed By: AVTECH Software, Inc.
--
--Copyright (c) 2007 AVTECH Software, Inc.
--
ROOMALERT24E-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Counter, TimeTicks
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
products OBJECT IDENTIFIER ::= { avtech 1 }
roomalert24e OBJECT IDENTIFIER ::= { products 5 }
sensors OBJECT IDENTIFIER ::= { roomalert24e 1 }
traps OBJECT IDENTIFIER ::= { roomalert24e 2 }
internal OBJECT IDENTIFIER ::= { sensors 1 }
temperature OBJECT IDENTIFIER ::= { internal 1 }
humidity OBJECT IDENTIFIER ::= { internal 2 }
heat-index OBJECT IDENTIFIER ::= { internal 3 }
digital OBJECT IDENTIFIER ::= { sensors 2 }
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
digital-sen3 OBJECT IDENTIFIER ::= { digital 3 }
digital-sen4 OBJECT IDENTIFIER ::= { digital 4 }
digital-sen5 OBJECT IDENTIFIER ::= { digital 5 }
digital-sen6 OBJECT IDENTIFIER ::= { digital 6 }
switch OBJECT IDENTIFIER ::= { sensors 3 }
-- Room Alert 24E MIB
-- Parameters
internal-tempf OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { temperature 1 }
internal-tempc OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { temperature 2 }
internal-humidity OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { humidity 1 }
internal-heat-index OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { heat-index 1 }
internal-heat-indexc OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The internal heat index reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
::= { heat-index 2 }
digital-sen1-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen1 1 }
digital-sen1-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen1 2 }
digital-sen1-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen1 3 }
digital-sen1-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen1 4 }
digital-sen1-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen1 5 }
digital-sen2-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen2 1 }
digital-sen2-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen2 2 }
digital-sen2-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen2 3 }
digital-sen2-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen2 4 }
digital-sen2-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen2 5 }
digital-sen3-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen3 1 }
digital-sen3-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen3 2 }
digital-sen3-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen3 3 }
digital-sen3-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen3 4 }
digital-sen3-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen3 5 }
digital-sen4-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen4 1 }
digital-sen4-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen4 2 }
digital-sen4-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen4 3 }
digital-sen4-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen4 4 }
digital-sen4-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen4 5 }
digital-sen5-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen5 1 }
digital-sen5-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen5 2 }
digital-sen5-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen5 3 }
digital-sen5-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen5 4 }
digital-sen5-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen5 5 }
digital-sen6-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen6 1 }
digital-sen6-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen6 2 }
digital-sen6-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen6 3 }
digital-sen6-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen6 4 }
digital-sen6-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen6 5 }
switch-sen1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
::= { switch 1 }
switch-sen2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
::= { switch 2 }
switch-sen3 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
::= { switch 3 }
switch-sen4 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
::= { switch 4 }
switch-sen5 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 5 (0 = OPEN, 1 = CLOSED)."
::= { switch 5 }
switch-sen6 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 6 (0 = OPEN, 1 = CLOSED)."
::= { switch 6 }
switch-sen7 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 7 (0 = OPEN, 1 = CLOSED)."
::= { switch 7 }
switch-sen8 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 8 (0 = OPEN, 1 = CLOSED)."
::= { switch 8 }
switch-sen9 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 9 (0 = OPEN, 1 = CLOSED)."
::= { switch 9 }
switch-sen10 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 10 (0 = OPEN, 1 = CLOSED)."
::= { switch 10 }
switch-sen11 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 11 (0 = OPEN, 1 = CLOSED)."
::= { switch 11 }
switch-sen12 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 12 (0 = OPEN, 1 = CLOSED)."
::= { switch 12 }
switch-sen13 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 13 (0 = OPEN, 1 = CLOSED)."
::= { switch 13 }
switch-sen14 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 14 (0 = OPEN, 1 = CLOSED)."
::= { switch 14 }
switch-sen15 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 15 (0 = OPEN, 1 = CLOSED)."
::= { switch 15 }
switch-sen16 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for switch sensor 16 (0 = OPEN, 1 = CLOSED)."
::= { switch 16 }
alarmmessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Last Alarm Message"
::= { traps 1 }
-- ROOMALERT24E TRAPS
tempalarm1-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm1 trap signifies that the current
temperature on external sensor 1 is outside the
defined high or low threshold."
::= 1
room-alert-24e-snmp-trap TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A room-alert-24e-snmp-trap indicates that an alarm
condition has occurred on the sensor indicated
by the alarmmessage variable."
::= 2
tempalarm2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm2 trap signifies that the current
temperature on external sensor 2 is outside the
defined high or low threshold."
::= 3
tempclear2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A tempclear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 4
tempalarm3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A tempalarm3 trap signifies that the current
temperature on external sensor 3 is outside the
defined high or low threshold."
::= 5
tempclear3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A tempclear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 6
humidityalarm1-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm1 trap signifies that the current
humidity on external sensor 1 is outside the
defined high or low threshold."
::= 7
humidityclear1-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined
high or low threshold."
::= 8
humidityalarm2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm2 trap signifies that the current
humidity on external sensor 2 is outside the
defined high or low threshold."
::= 9
humidityclear2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 10
humidityalarm3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityalarm3 trap signifies that the current
humidity on external sensor 3 is outside the
defined high or low threshold."
::= 11
humidityclear3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A humidityclear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 12
switchalarm1-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm1 trap signifies that switch sensor 1
is in an alarm state."
::= 13
switchclear1-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear1 trap signifies that the switch sensor 1
has returned to a normal state."
::= 14
switchalarm2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm2 trap signifies that switch sensor 2
is in an alarm state."
::= 15
switchclear2-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear2 trap signifies that the switch sensor 2
has returned to a normal state."
::= 16
switchalarm3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm1 trap signifies that switch sensor 1
is in an alarm state."
::= 17
switchclear3-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear3 trap signifies that the switch sensor 3
has returned to a normal state."
::= 18
switchalarm4-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm4 trap signifies that switch sensor 4
is in an alarm state."
::= 19
switchclear4-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear4 trap signifies that the switch sensor 4
has returned to a normal state."
::= 20
switchalarm5-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm5 trap signifies that switch sensor 5
is in an alarm state."
::= 21
switchclear5-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear5 trap signifies that the switch sensor 5
has returned to a normal state."
::= 22
switchalarm6-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm6 trap signifies that switch sensor 6
is in an alarm state."
::= 23
switchclear6-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear6 trap signifies that the switch sensor 6
has returned to a normal state."
::= 24
switchalarm7-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm7 trap signifies that switch sensor 7
is in an alarm state."
::= 25
switchclear7-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear7 trap signifies that the switch sensor 7
has returned to a normal state."
::= 26
switchalarm8-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchalarm8 trap signifies that switch sensor 8
is in an alarm state."
::= 27
switchclear8-24e TRAP-TYPE
ENTERPRISE roomalert24e
VARIABLES { alarmmessage }
DESCRIPTION "A switchclear8 trap signifies that the switch sensor 8
has returned to a normal state."
::= 28
END