184 lines
4.8 KiB
Plaintext
184 lines
4.8 KiB
Plaintext
--
|
|
--defines ROOMALERT3E-MIB for SNMP agent extension of Room Alert 3E
|
|
--Contents: Global Registration Module
|
|
-- Room Alert OIDs - Enterprise 20916
|
|
--Version: 1.0.1
|
|
--Date: WEB_RELEASE_DATE_PLACEHOLDER
|
|
--Developed By: AVTECH Software, Inc.
|
|
|
|
--
|
|
--Copyright (c) COPYRIGHT_YEAR_PLACEHOLDER AVTECH Software, Inc.
|
|
--
|
|
|
|
ROOMALERT3E-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Counter, TimeTicks
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
|
products OBJECT IDENTIFIER ::= { avtech 1 }
|
|
ROOMALERT3E OBJECT IDENTIFIER ::= { products 9 }
|
|
sensors OBJECT IDENTIFIER ::= { ROOMALERT3E 1 }
|
|
signaltower OBJECT IDENTIFIER ::= { ROOMALERT3E 2 }
|
|
traps OBJECT IDENTIFIER ::= { ROOMALERT3E 3 }
|
|
digital OBJECT IDENTIFIER ::= { sensors 1 }
|
|
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
|
|
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
|
|
switch OBJECT IDENTIFIER ::= { sensors 2 }
|
|
|
|
|
|
-- Room Alert 3E MIB
|
|
-- Parameters
|
|
|
|
digital-sen1-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current temperature reading in Celsius of the Internal Temperature Sensor."
|
|
::= { digital-sen1 1 }
|
|
|
|
digital-sen1-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current temperature reading in Fahrenheit of the Internal Temperature Sensor."
|
|
::= { digital-sen1 2 }
|
|
|
|
digital-sen1-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= {digital-sen1 3}
|
|
|
|
digital-sen2-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius."
|
|
::= { digital-sen2 1 }
|
|
|
|
digital-sen2-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit."
|
|
::= { digital-sen2 2 }
|
|
|
|
digital-sen2-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity."
|
|
::= { digital-sen2 3 }
|
|
|
|
digital-sen2-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit."
|
|
::= { digital-sen2 4 }
|
|
|
|
digital-sen2-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
|
::= { digital-sen2 5 }
|
|
|
|
digital-sen2-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= {digital-sen2 6}
|
|
|
|
switch-sen1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for the switch sensor (0 = OPEN, 1 = CLOSED)."
|
|
::= { switch 1 }
|
|
|
|
switch-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for the switch sensor"
|
|
::= { switch 2 }
|
|
|
|
red-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 1 }
|
|
|
|
amber-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 2 }
|
|
|
|
green-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 3 }
|
|
|
|
blue-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 4 }
|
|
|
|
white-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 5 }
|
|
|
|
alarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 6 }
|
|
|
|
alarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The status of this Signal Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 7 }
|
|
|
|
alarmmessage OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Last Alarm Message"
|
|
::= { traps 1 }
|
|
|
|
|
|
-- ROOMALERT3E TRAPS
|
|
|
|
room-alert-3e-snmp-trap TRAP-TYPE
|
|
ENTERPRISE ROOMALERT3E
|
|
VARIABLES { alarmmessage }
|
|
DESCRIPTION "A room-alert-3e-snmp-trap indicates that an alarm
|
|
condition has occurred on the sensor indicated
|
|
by the alarmmessage variable."
|
|
::= 2
|
|
END
|