258 lines
7.8 KiB
Plaintext
258 lines
7.8 KiB
Plaintext
--
|
|
--defines ROOMALERT4E-MIB for SNMP agent extension of Room Alert 4E
|
|
--Contents: Global Registration Module
|
|
-- Room Alert OIDs - Enterprise 20916
|
|
--Version: 4.2.4
|
|
--Date: 15 February 2019
|
|
--Developed By: AVTECH Software, Inc.
|
|
|
|
--
|
|
--Copyright (c) 2019 AVTECH Software, Inc.
|
|
--
|
|
|
|
ROOMALERT4E-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Counter, TimeTicks
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
|
products OBJECT IDENTIFIER ::= { avtech 1 }
|
|
roomalert4E OBJECT IDENTIFIER ::= { products 6 }
|
|
sensors OBJECT IDENTIFIER ::= { roomalert4E 1 }
|
|
signaltower OBJECT IDENTIFIER ::= { roomalert4E 2 }
|
|
traps OBJECT IDENTIFIER ::= { roomalert4E 3 }
|
|
internal OBJECT IDENTIFIER ::= { sensors 1 }
|
|
temperature OBJECT IDENTIFIER ::= { internal 1 }
|
|
label OBJECT IDENTIFIER ::= { internal 2 }
|
|
digital OBJECT IDENTIFIER ::= { sensors 2 }
|
|
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
|
|
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
|
|
switch OBJECT IDENTIFIER ::= { sensors 3 }
|
|
|
|
|
|
-- Room Alert 4E MIB
|
|
-- Parameters
|
|
|
|
|
|
internal-tempf OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The internal temperature reading in Fahrenheit."
|
|
::= { temperature 1 }
|
|
|
|
internal-tempc OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The internal temperature reading in Celsius."
|
|
::= { temperature 2 }
|
|
|
|
internal-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= { label 1 }
|
|
|
|
digital-sen1-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
|
::= { digital-sen1 1 }
|
|
|
|
digital-sen1-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
|
::= { digital-sen1 2 }
|
|
|
|
digital-sen1-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
|
::= { digital-sen1 3 }
|
|
|
|
digital-sen1-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
|
::= { digital-sen1 4 }
|
|
|
|
digital-sen1-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
|
::= { digital-sen1 5 }
|
|
|
|
digital-sen1-6 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
|
::= { digital-sen1 6 }
|
|
|
|
digital-sen1-7 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
|
::= { digital-sen1 7 }
|
|
|
|
digital-sen1-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= {digital-sen1 8}
|
|
|
|
digital-sen2-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
|
::= { digital-sen2 1 }
|
|
|
|
digital-sen2-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
|
::= { digital-sen2 2 }
|
|
|
|
digital-sen2-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
|
::= { digital-sen2 3 }
|
|
|
|
digital-sen2-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
|
::= { digital-sen2 4 }
|
|
|
|
digital-sen2-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
|
::= { digital-sen2 5 }
|
|
|
|
digital-sen2-6 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
|
::= { digital-sen2 6 }
|
|
|
|
digital-sen2-7 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
|
::= { digital-sen2 7 }
|
|
|
|
digital-sen2-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= {digital-sen2 8}
|
|
|
|
switch-sen1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for the switch sensor 1 (0 = OPEN, 1 = CLOSED)."
|
|
::= { switch 1 }
|
|
|
|
switch-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for the switch sensor"
|
|
::= { switch 2 }
|
|
|
|
red-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 1 }
|
|
|
|
amber-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 2 }
|
|
|
|
green-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 3 }
|
|
|
|
blue-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 4 }
|
|
|
|
white-led OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 5 }
|
|
|
|
alarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 6 }
|
|
|
|
alarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
|
::= { signaltower 7 }
|
|
|
|
alarmmessage OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Last Alarm Message"
|
|
::= { traps 1 }
|
|
|
|
|
|
-- roomalert4E TRAPS
|
|
|
|
room-alert-4e-snmp-trap TRAP-TYPE
|
|
ENTERPRISE roomalert4E
|
|
VARIABLES { alarmmessage }
|
|
DESCRIPTION "A room-alert-4e-snmp-trap indicates that an alarm
|
|
condition has occurred on the sensor indicated
|
|
by the alarmmessage variable."
|
|
::= 2
|
|
END
|