363 lines
9.1 KiB
Plaintext
363 lines
9.1 KiB
Plaintext
--
|
|
--defines ROOMALERT7E-MIB for SNMP agent extension of Room Alert 7E
|
|
--Contents: Global Registration Module
|
|
-- Room Alert OIDs - Enterprise 20916
|
|
--Version: 2.0.3
|
|
--Date: 11 September 2007
|
|
--Developed By: AVTECH Software, Inc.
|
|
|
|
--
|
|
--Copyright (c) 2007 AVTECH Software, Inc.
|
|
--
|
|
|
|
ROOMALERT7E-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Counter, TimeTicks
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
|
products OBJECT IDENTIFIER ::= { avtech 1 }
|
|
roomalert7e OBJECT IDENTIFIER ::= { products 2 }
|
|
sensors OBJECT IDENTIFIER ::= { roomalert7e 1 }
|
|
traps OBJECT IDENTIFIER ::= { roomalert7e 2 }
|
|
thresholds OBJECT IDENTIFIER ::= { roomalert7e 3 }
|
|
temperature OBJECT IDENTIFIER ::= { sensors 1 }
|
|
switch OBJECT IDENTIFIER ::= { sensors 2 }
|
|
|
|
-- Room Alert 7E MIB
|
|
-- Parameters
|
|
|
|
tempreading1c OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 1 (Celsius)"
|
|
::= { temperature 1 }
|
|
|
|
tempreading2c OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 2 (Celsius)"
|
|
::= { temperature 2 }
|
|
|
|
tempreading3c OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 3 (Celsius)"
|
|
::= { temperature 3 }
|
|
|
|
|
|
tempreading4c OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 4 (Celsius)"
|
|
::= { temperature 4 }
|
|
|
|
tempreading1f OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 1 (Fahrenheit)"
|
|
::= { temperature 5 }
|
|
|
|
tempreading2f OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 2 (Fahrenheit)"
|
|
::= { temperature 6 }
|
|
|
|
tempreading3f OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 3 (Fahrenheit)"
|
|
::= { temperature 7 }
|
|
|
|
|
|
tempreading4f OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Temperature Sensor 4 (Fahrenheit)"
|
|
::= { temperature 8 }
|
|
|
|
switch1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Switch Sensor 1 (0 = OFF, 1 = ON)"
|
|
::= { switch 1 }
|
|
|
|
switch2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Switch Sensor 2 (0 = OFF, 1 = ON)"
|
|
::= { switch 2 }
|
|
|
|
switch3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Switch Sensor 3 (0 = OFF, 1 = ON)"
|
|
::= { switch 3 }
|
|
|
|
alarmtemp1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for temperature 1
|
|
0 = temperature OK
|
|
1 = temperature too high
|
|
2 = temperature too low"
|
|
::= { traps 1 }
|
|
|
|
alarmtemp2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for temperature 2
|
|
0 = temperature OK
|
|
1 = temperature too high
|
|
2 = temperature too low"
|
|
::= { traps 2 }
|
|
|
|
alarmtemp3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for temperature 3
|
|
0 = temperature OK
|
|
1 = temperature too high
|
|
2 = temperature too low"
|
|
::= { traps 3 }
|
|
|
|
alarmtemp4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for temperature 4
|
|
0 = temperature OK
|
|
1 = temperature too high
|
|
2 = temperature too low"
|
|
::= { traps 4 }
|
|
|
|
alarmswitch1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for switch sensor 1
|
|
0 = Switch Open
|
|
1 = Switch Closed"
|
|
::= { traps 5 }
|
|
|
|
alarmswitch2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for switch sensor 2
|
|
0 = Switch Open
|
|
1 = Switch Closed"
|
|
::= { traps 6 }
|
|
|
|
alarmswitch3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for switch sensor 3
|
|
0 = Switch Open
|
|
1 = Switch Closed"
|
|
::= { traps 7 }
|
|
|
|
alarmmessage OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Message string to send with trap messages"
|
|
::= { traps 8 }
|
|
|
|
upperlimit1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "High temperature threshold for temperature sensor 1"
|
|
::= { thresholds 1 }
|
|
|
|
lowerlimit1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Low temperature threshold for temperature sensor 1"
|
|
::= { thresholds 2 }
|
|
|
|
upperlimit2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "High temperature threshold for temperature sensor 2"
|
|
::= { thresholds 3 }
|
|
|
|
lowerlimit2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Low temperature threshold for temperature sensor 2"
|
|
::= { thresholds 4 }
|
|
|
|
upperlimit3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "High temperature threshold for temperature sensor 3"
|
|
::= { thresholds 5 }
|
|
|
|
lowerlimit3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Low temperature threshold for temperature sensor 3"
|
|
::= { thresholds 6 }
|
|
|
|
upperlimit4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "High temperature threshold for temperature sensor 4"
|
|
::= { thresholds 7 }
|
|
|
|
lowerlimit4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..15000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Low temperature threshold for temperature sensor 4"
|
|
::= { thresholds 8 }
|
|
|
|
-- ROOMALERT7E TRAPS
|
|
|
|
alarmstart1-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading1c, tempreading1f }
|
|
DESCRIPTION "A alarmstart1 trap signifies that the current
|
|
temperature on sensor 1 is outside the
|
|
defined high or low threshold."
|
|
::= 1
|
|
|
|
room-alert-7e-snmp-trap TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage }
|
|
DESCRIPTION "A room-alert-7e-snmp-trap indicates that an alarm
|
|
condition has occurred on the sensor inidcated
|
|
by the alarmmessage variable."
|
|
::= 2
|
|
|
|
alarmstart2-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading2c, tempreading2f }
|
|
DESCRIPTION "A alarmstart2 trap signifies that the current
|
|
temperature on sensor 2 is outside the
|
|
defined high or low threshold."
|
|
::= 3
|
|
|
|
alarmclear2-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading2c, tempreading2f }
|
|
DESCRIPTION "A alarmclear2 trap signifies that the current
|
|
temperature on sensor 2 has returned to a
|
|
normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 4
|
|
|
|
alarmstart3-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading3c, tempreading3f }
|
|
DESCRIPTION "A alarmstart3 trap signifies that the current
|
|
temperature on sensor 3 is outside the
|
|
defined high or low threshold."
|
|
::= 5
|
|
|
|
alarmclear3-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading3c, tempreading3f }
|
|
DESCRIPTION "A alarmclear3 trap signifies that the current
|
|
temperature on sensor 3 has returned to a
|
|
normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 6
|
|
|
|
alarmstart4-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading4c, tempreading4f }
|
|
DESCRIPTION "A alarmstart4 trap signifies that the current
|
|
temperature on sensor 4 is outside the
|
|
defined high or low threshold."
|
|
::= 7
|
|
|
|
alarmclear4-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, tempreading4c, tempreading4f }
|
|
DESCRIPTION "A alarmclear4 trap signifies that the current
|
|
temperature on sensor 4 has returned to a
|
|
normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 8
|
|
|
|
alarmstart5-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch1, switch1 }
|
|
DESCRIPTION "A alarmstart5 trap signifies that the current
|
|
status of switch sensor 1 is outside the
|
|
defined threshold."
|
|
::= 9
|
|
|
|
alarmclear5-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch1, switch1 }
|
|
DESCRIPTION "A alarmclear5 trap signifies that the current
|
|
status of switch sensor 1 is outside the
|
|
defined threshold."
|
|
::= 10
|
|
|
|
alarmstart6-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch2, switch2 }
|
|
DESCRIPTION "A alarmstart6 trap signifies that the current
|
|
status of switch sensor 2 is outside the
|
|
defined threshold."
|
|
::= 11
|
|
|
|
alarmclear6-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch2, switch2 }
|
|
DESCRIPTION "A alarmclear6 trap signifies that the current
|
|
status of switch sensor 2 is outside the
|
|
defined threshold."
|
|
::= 12
|
|
|
|
alarmstart7-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch3, switch3 }
|
|
DESCRIPTION "A alarmstart7 trap signifies that the current
|
|
status of switch sensor 3 is outside the
|
|
defined threshold."
|
|
::= 13
|
|
|
|
alarmclear7-7e TRAP-TYPE
|
|
ENTERPRISE roomalert7e
|
|
VARIABLES { alarmmessage, switch3, switch3 }
|
|
DESCRIPTION "A alarmclear7 trap signifies that the current
|
|
status of switch sensor 3 is outside the
|
|
defined threshold."
|
|
::= 14
|
|
END
|